Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:44
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:44:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32632.21 | 704.49 | 704.49 |
Net Site Energy | 32632.21 | 704.49 | 704.49 |
Total Source Energy | 101724.33 | 2196.10 | 2196.10 |
Net Source Energy | 101724.33 | 2196.10 | 2196.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 104.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4172.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3926.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 696.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2877.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 655.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1301.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14685.25 |
Humidification | 1611.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.58 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 674.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31853.58 | 778.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17565.00 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 104.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 4172.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3926.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 696.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2877.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 655.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1301.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14685.25 |
Humidification | General | 1611.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.58 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 674.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 104.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4172.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3926.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 696.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2877.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 655.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1301.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14685.25 |
Humidification | Unassigned | 1611.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.58 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 674.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.27 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 687.68 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.27 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 687.68 | 16.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31853.583 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31853.583 | 100.00 |
Total On-Site and Utility Electric Sources | 31853.583 | 100.00 |
Total Electricity End Uses | 31853.583 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 17565.00 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 17565.00 | 100.00 |
Total Water End Uses | 17565.00 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 1010.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5850.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:44 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-AUG-15:09 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 27-JUN-11:00 |
Heating | 0.00 | 498515.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 473188.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 269526.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49783.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 87736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16448.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2175351.10 | 514963.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 498515.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 473188.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 269526.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 49783.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 87736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 16448.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 113.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13215.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12434.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2204.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9114.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2077.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4122.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5104.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 730.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 100880.30 | 844.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 285.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 196.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 89.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2177.88 | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 285.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 196.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 89.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2177.88 | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.68 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.527209 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.03 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.514235 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 23.57 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.89 | 0.275903 | 0.292000 | 2.01 | 0.735741 | 0.500000 | 0.001381 | 0.000161 | 2.01 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 65.25 | 0.291509 | 0.304000 | 19.84 | 0.777358 | 0.500000 | 0.001307 | 0.003415 | 19.84 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.49 | 0.293135 | 0.315000 | 2.04 | 0.781693 | 0.500000 | 0.001300 | 0.000619 | 2.32 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.32 | 0.181058 | 0.200000 | 0.263806 | 0.482820 | 0.500000 | 0.002104 | 0.000071 | 0.263965 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.27 | 0.121379 | 0.200000 | 0.253593 | 0.323679 | 0.500000 | 0.003139 | 0.000057 | 0.253593 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162504 | 0.200000 | 0.293931 | 0.433345 | 0.500000 | 0.002345 | 0.000094 | 0.353139 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.62 | 0.095111 | 0.200000 | 0.323632 | 0.300000 | 0.500000 | 0.004006 | 0.000049 | 0.323632 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.96 | 0.184334 | 0.200000 | 2.59 | 0.491558 | 0.500000 | 0.002067 | 0.001600 | 6.01 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.27 | 0.116011 | 0.200000 | 2.65 | 0.309362 | 0.500000 | 0.003284 | 0.001074 | 4.03 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.39 | 0.165971 | 0.200000 | 2.88 | 0.442590 | 0.500000 | 0.002296 | 0.001617 | 6.07 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.48 | 0.106306 | 0.200000 | 2.90 | 0.300000 | 0.500000 | 0.003584 | 0.000994 | 3.73 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.46 | 0.163026 | 0.200000 | 0.292985 | 0.434735 | 0.500000 | 0.002337 | 0.000202 | 0.758452 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.36 | 0.113153 | 0.200000 | 0.272031 | 0.301740 | 0.500000 | 0.003367 | 0.000135 | 0.505399 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.149523 | 0.200000 | 0.319451 | 0.398727 | 0.500000 | 0.002548 | 0.000204 | 0.765651 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.56 | 0.098790 | 0.200000 | 0.311580 | 0.300000 | 0.500000 | 0.003857 | 0.000128 | 0.479542 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18400.76 | 0.000161 | 370.94 |
CORE_MID VAV BOX REHEAT COIL | 390319.78 | 0.003415 | 8887.61 |
CORE_TOP VAV BOX REHEAT COIL | 70749.76 | 0.000619 | 1868.37 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8060.14 | 0.000071 | 212.88 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6479.41 | 0.000057 | 159.31 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10768.09 | 0.000094 | 284.22 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5585.30 | 0.000049 | 123.46 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 182859.23 | 0.001600 | 4823.20 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 122783.07 | 0.001074 | 3238.46 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 184887.84 | 0.001617 | 4876.65 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 113606.41 | 0.000994 | 2996.64 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23081.33 | 0.000202 | 608.68 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15379.44 | 0.000135 | 405.56 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23300.02 | 0.000204 | 614.44 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14593.83 | 0.000128 | 384.86 |
VAV_BOT WITH REHEAT HEATING COIL | 37131.82 | 0.000325 | 634.06 |
VAV_MID WITH REHEAT HEATING COIL | 285154.89 | 0.002495 | 4929.86 |
VAV_TOP WITH REHEAT HEATING COIL | 28157.41 | 0.000246 | 490.21 |
CAV_BAS HEATING COIL | 292824.99 | 0.002562 | 6583.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.28 | 3.15 | 12.57 | 3.15 | 11.25 | 11.25 | 0.300000 | 0.279934 | 11.25 |
VAV_MID WITH REHEAT | 60.17 | 30.85 | 120.34 | 30.85 | 106.00 | 106.00 | 0.300000 | 0.291082 | 106.00 |
VAV_TOP WITH REHEAT | 6.23 | 3.24 | 12.47 | 4.83 | 11.96 | 11.96 | 0.300000 | 0.403595 | 11.96 |
CAV_BAS | 6.68 | 6.68 | 6.68 | 6.68 | 6.68 | 6.68 | 1.00 | 1.00 | 6.68 |
AIRLOOP DATACENTER BASEMENT | 23.57 | 23.57 | 23.57 | 23.57 | 23.57 | 23.57 | 1.00 | 0.999991 | 23.57 |
AIRLOOP DATACENTER BOT | 0.527209 | 0.527209 | 0.527209 | 0.527209 | 0.527209 | 0.527209 | 1.00 | 1.00 | 0.527209 |
AIRLOOP DATACENTER MID | 5.03 | 5.03 | 5.03 | 5.03 | 5.03 | 5.03 | 1.00 | 1.00 | 5.03 |
AIRLOOP DATACENTER TOP | 0.514235 | 0.514235 | 0.514235 | 0.514235 | 0.514235 | 0.514235 | 1.00 | 1.00 | 0.514235 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.25 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 106.00 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.96 | |
CAV_BAS_OA_CONTROLLER | 6.68 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 23.57 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.527209 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.03 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.514235 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.83 | 6.67 | 10.87 | 0.008066 | 0.008066 | 212623.81 | 0.009046 | 11.25 |
VAV_MID WITH REHEAT COOLING COIL | 28.15 | 6.67 | 10.87 | 0.007998 | 0.007998 | 2041715.22 | 0.086859 | 106.00 |
VAV_TOP WITH REHEAT COOLING COIL | 27.58 | 6.67 | 10.87 | 0.008066 | 0.008066 | 222807.78 | 0.009479 | 11.96 |
CAV_BAS COOLING COIL | 27.27 | 6.67 | 11.29 | 0.008283 | 0.008283 | 119071.31 | 0.005066 | 6.68 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.25 |
VAV_MID WITH REHEAT FAN | 106.00 |
VAV_TOP WITH REHEAT FAN | 11.96 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009046 | 0.000053 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000325 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.086859 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002495 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009479 | 0.000050 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000246 | |
CAV_BAS_COOLC_CONTROLLER | 0.005066 | 0.000094 |
CAV_BAS_HEATC_CONTROLLER | 0.002562 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.68 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 23.57 | 443651.01 | 290324.13 | 0.010865 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.527209 | 9698.75 | 6416.35 | 0.000238 |
AIRLOOP DATACENTER MID COOLING COIL | 5.03 | 92575.26 | 61221.65 | 0.002267 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.514235 | 9468.54 | 6261.14 | 0.000232 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 23.57 | 23.57 | 23.57 | 23.57 | 443651.01 | 443651.01 | 14683.19 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.527209 | 0.527209 | 0.527209 | 0.527209 | 9698.75 | 9698.75 | 678.30 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.03 | 5.03 | 5.03 | 5.03 | 92575.26 | 92575.26 | 6783.03 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.514235 | 0.514235 | 0.514235 | 0.514235 | 9468.54 | 9468.54 | 678.30 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 23.57 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.527209 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.03 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.514235 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 23.57 | 443651.01 | 0.010865 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.527209 | 9698.75 | 0.000238 |
AIRLOOP DATACENTER MID HEATING COIL | 5.03 | 92575.26 | 0.002267 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.514235 | 9468.54 | 0.000232 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14683.19 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 678.30 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6783.03 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 678.30 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000104 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.110449 | 18032.97 | |
HEATSYS1 PUMP | 0.016046 | 4832.26 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.110449 | 13.25 |
HEATSYS1 | 0.016046 | 1.93 |
COOLSYS1_SUPPLY | 0.110449 | 13.25 |
SINGLE WATER PLANT LOOP | 0.013602 | 1.63 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.110449 | 0.110449 | 463610.38 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1834123.53 | 1834123.53 | 0.016046 |
CENTRAL BOILER | 560267.37 | 548384.16 | 0.013602 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.055225 | 6242.42 |
COOLSYS1 CHILLER2 PUMP | 0.055225 | 6242.42 |
PLANT CIRC PUMP | 0.013602 | 3469.08 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.110449 | 0.055930 | 1317920.63 | 1324145.97 | 0.065527 |
COOLSYS1 CHILLER2 | 0.110449 | 0.055930 | 1317920.63 | 1324145.97 | 0.065527 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013602 | 139666.47 | 58102.57 | 69833.23 | 7879.72 | 21297.40 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.131054 | 15.73 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.131054 | 32446.11 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 55.79 | 1571680.44 | 11.16 | 196460.06 |
TOWERWATERSYS COOLTOWER 2 | 55.79 | 1571680.44 | 11.16 | 196460.06 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.068062 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.567_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.224 | 3.224 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60245 | 0.60245 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.42129E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1541E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1555E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4749E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4761E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1446E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1455E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1871E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2816E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5024E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5833E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1675E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2346E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1048 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6139E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1171 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0515E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7648E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9542E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1916E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3034E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5071E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6067E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1717E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2505E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1540E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1555E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4748E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4761E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1445E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1456E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9043E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0903E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7213E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9204E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5390E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6265E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3488E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0811E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0676E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8868E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2079E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7221E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8539E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9216E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6570E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7063E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5116E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5313E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7778E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7792E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5183E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5195E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3457E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3465E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8102E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8915E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5448E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6093E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3670E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4135E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7838E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4576E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1413E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1067E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9200E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4748E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8087E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8898E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5429E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6056E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3638E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4037E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7777E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7791E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5183E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5194E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3456E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3463E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5106E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5804E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2340E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2844E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2155E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2339E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7526E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8527E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3389E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6077E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6649E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5119E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5533E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7064E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2888E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4470E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2416E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3218E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1049 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5516E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1138 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1197E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5402E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4281E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1871E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0141E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8733E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7778E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9992E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5600E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4831E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3131E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7533E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8322E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5075E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3800E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5124E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6982E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0478E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3907E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3899E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2783E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1050 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5659E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1139 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1362E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5542E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4392E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1914E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0188E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8782E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7823E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0074E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5654E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4835E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3158E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7539E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8343E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5115E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3825E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5154E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7021E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0512E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3942E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3970E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2831E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 84170.01737 | 84170.01737 | 6.67917 | 6.67917 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 0.50000 | 4.31558E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 86886.93628 | 86886.93628 | 6.89389 | 6.89389 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 822518.78709 | 822518.78709 | 65.24811 | 65.24811 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 209006.20922 | 209006.20922 | 9.69432 | 10.77825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 81795.61102 | 81795.61102 | 6.48863 | 6.48863 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 49563.90188 | 49563.90188 | 2.31770 | 2.31770 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 16482.02808 | 16482.02808 | 1.31903 | 1.31903 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5649.56410 | 5649.56410 | 0.26397 | 0.26397 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15844.03118 | 15844.03118 | 1.26797 | 1.26797 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 34.99233 | 5.62211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4163.19852 | 4163.19852 | 0.19474 | 0.19474 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18364.21023 | 18364.21023 | 1.46966 | 1.46966 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 40.57833 | 5.63076E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7541.96607 | 7541.96607 | 0.35314 | 0.35314 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20219.97742 | 20219.97742 | 1.61816 | 1.61816 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2631.48432 | 2631.48432 | 0.12262 | 0.12262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 161896.00701 | 161896.00701 | 12.95584 | 12.95584 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 127984.64053 | 127984.64053 | 6.00596 | 6.00596 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 165778.35984 | 165778.35984 | 13.26645 | 13.26645 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 85933.06713 | 85933.06713 | 4.03315 | 4.03315 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 179812.34768 | 179812.34768 | 14.38960 | 14.38960 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40.68917 | 5.63093E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 129402.71834 | 129402.71834 | 6.07275 | 6.07275 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 180912.69658 | 180912.69658 | 14.47759 | 14.47759 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 79517.92865 | 79517.92865 | 3.73111 | 3.73111 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 18305.98193 | 18305.98193 | 1.46493 | 1.46493 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 16151.42333 | 16151.42333 | 0.75845 | 0.75845 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16996.82767 | 16996.82767 | 1.36016 | 1.36016 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10761.65766 | 10761.65766 | 0.50540 | 0.50540 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19959.58575 | 19959.58575 | 1.59726 | 1.59726 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16304.30932 | 16304.30932 | 0.76565 | 0.76565 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19467.88507 | 19467.88507 | 1.55790 | 1.55790 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10212.39506 | 10212.39506 | 0.47954 | 0.47954 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8352.03129 | 8352.03129 | 0.52721 | 0.52721 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79664.51005 | 79664.51005 | 5.02873 | 5.02873 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8146.47426 | 8146.47426 | 0.51424 | 0.51424 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 36.27800 | 5.62409E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373423.29196 | 373423.29196 | 23.57140 | 23.57140 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 28.69700 | 5.61258E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 0.50000 | 4.31558E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 183731.34 | 11.24542 | 11.24542 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 27189.25 | 2.01229 | 2.01229 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1731863.03 | 105.99523 | 105.99523 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 342939.44 | 30.62122 | 30.62122 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 14:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 193239.95 | 11.95939 | 11.95939 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 34258.84 | 4.82675 | 4.82675 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
7 | CAV_BAS | Cooling | Sensible | 94021.19 | 6.67917 | 6.67917 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52075.95 | 1.20016 | 1.20016 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 372293.56 | 23.57160 | 23.57160 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14683.19 | 0.33839 | 0.33839 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8379.28 | 0.52721 | 0.52721 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79977.00 | 5.02873 | 5.02873 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6783.03 | 0.15632 | 0.15632 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8180.00 | 0.51424 | 0.51424 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.67917 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.89389 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27590 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01302 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73574 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38092E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60978E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.01302 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18400.76192 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60978E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 370.94492 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 65.24811 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29151 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.83543 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77736 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30699E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41469E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.83543 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 390319.77812 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41469E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8887.61319 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.48863 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29313 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.04392 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78169 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29974E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.18950E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.31770 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70749.75978 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.18950E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1868.36864 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31903 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18106 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26381 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48282 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10430E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.05136E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26397 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8060.13997 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.05136E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.88212 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26797 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12138 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25359 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32368 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13892E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.66847E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25359 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6479.40979 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.66847E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.30596 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46966 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16250 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29393 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43335 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34455E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.42039E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35314 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10768.08794 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.42039E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.22247 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61816 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.51111E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32363 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.00584E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.88626E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32363 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5585.29548 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.88626E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 123.45830 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.95584 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18433 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59117 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49156 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06690E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59973E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.00596 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 182859.23412 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59973E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4823.19683 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.26645 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11601 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.65329 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30936 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28418E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07416E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.03315 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122783.07447 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07416E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3238.45708 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.38960 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16597 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.87792 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44259 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29558E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61748E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.07275 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 184887.84407 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61748E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4876.64846 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.47759 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10631 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89552 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58400E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.93878E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73111 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 113606.40829 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.93878E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2996.64339 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46493 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16303 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29299 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43473 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33706E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01926E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75845 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23081.33235 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01926E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 608.67702 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36016 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11315 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27203 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30174 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36714E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34546E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50540 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15379.44076 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34546E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 405.55927 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59726 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14952 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31945 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39873 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54811E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03839E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76565 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23300.02354 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03839E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 614.43924 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55790 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.87900E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31158 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.85667E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27673E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47954 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14593.82659 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27673E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 384.85730 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52721 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.02873 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51424 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 23.57140 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.28435 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.14798 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.56871 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.14798 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.24542 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.24542 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27993 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 60.16879 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.85332 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 120.33759 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.85332 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 105.99523 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 105.99523 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29108 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.23444 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.23997 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.46887 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.82675 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.95939 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.95939 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40359 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.67917 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.67917 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.67917 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.67917 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.67917 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.67917 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 23.57140 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 23.57140 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.57140 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.57140 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.57160 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 23.57160 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52721 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52721 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52721 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52721 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52721 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.52721 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.02873 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.02873 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.02873 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.02873 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.02873 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.02873 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51424 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51424 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51424 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51424 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51424 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51424 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.24542 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 105.99523 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.95939 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.67917 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 23.57160 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.52721 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.02873 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51424 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.24542 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.83138 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87202 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06567E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06567E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 212623.81071 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.04551E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.24542 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 37131.82270 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.24845E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 634.06439 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.24542 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.04551E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.26439E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.24845E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 105.99523 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.15145 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87178 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.99828E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.99828E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2041715.22215 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.68593E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 105.99523 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 285154.88855 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.49466E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4929.86356 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 105.99523 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.68593E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.48232E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.49466E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.95939 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.58271 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87202 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06606E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06606E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 222807.78483 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.47876E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.95939 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 28157.41119 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46333E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.21220 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.95939 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.47876E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.02376E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.46333E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.67917 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.27350 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.28948 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.28278E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.28278E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 119071.31303 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.06557E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.67917 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 292824.98956 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56176E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6583.49664 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.67917 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.06557E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.40053E-005 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.56176E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.57160 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.57160 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 443651.01243 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 290324.13362 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08650E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 23.57160 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 23.57160 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 23.57160 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 23.57160 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 443651.01243 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 443651.01243 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14683.19080 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 23.57160 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.57160 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 443651.01243 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.08650E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14683.19080 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.03825E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52721 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52721 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9698.75429 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6416.34669 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37522E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52721 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52721 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52721 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52721 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9698.75429 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9698.75429 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52721 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52721 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9698.75429 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37522E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.02873 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.02873 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92575.26198 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 61221.64773 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26716E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.02873 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.02873 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.02873 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.02873 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92575.26198 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92575.26198 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6783.02586 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.02873 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.02873 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92575.26198 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26716E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6783.02586 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51424 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51424 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9468.54314 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6261.13545 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31884E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51424 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51424 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51424 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51424 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9468.54314 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9468.54314 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51424 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51424 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9468.54314 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31884E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11045 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18032.96650 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11045 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.25389 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11045 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11045 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 463610.38049 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.60457E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.92549 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.60457E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4832.26403 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1834123.52920 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1834123.53000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.60457E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11045 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.25389 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.52246E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 6242.41542 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.52246E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 6242.41542 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11045 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.59300E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1317920.63146 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1324145.96500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.55271E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11045 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.59300E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1317920.63146 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1324145.96500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.55271E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.36016E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.63219 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.36016E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3469.07615 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.36016E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58102.57377 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21297.39528 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 560267.36975 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 548384.16000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.36016E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13105 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.72650 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13105 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32446.10857 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 55.78965 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1571680.44122 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.15793 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 196460.05515 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 55.78965 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1571680.44122 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.15793 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 196460.05515 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.80625E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.80625E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17448.85 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 369929.52 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 67059.95 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7639.97 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6138.44 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10205.54 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5294.07 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 173283.81 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 116352.61 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 175205.82 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 107658.07 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21871.81 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14573.44 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22079.01 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13829.10 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 30765.74 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 241932.06 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 24208.06 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 234919.60 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 285833.20 | 185915.89 | 99917.31 | 0.65 | 34330.21 | 348.20 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2728130.17 | 1767336.42 | 960793.75 | 0.65 | 330600.65 | 3353.14 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 302402.70 | 197083.05 | 105319.65 | 0.65 | 36449.08 | 369.69 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 160148.44 | 106004.13 | 54144.31 | 0.66 | 18081.34 | 183.39 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_NORTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_EAST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_SOUTH_0.25 | N/A | 3.224 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.567_SHGC_WEST_0.25 | N/A | 3.224 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2271245521 | 0.1897530647 | Pass | Pass | 1.0039163675 | 4.7320815043 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.1538561625E-002 | 0.1579763277 | Pass | Pass | 0.1186234819 | 0.3225237833 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.0306512195E-002 | 8.9323949138E-002 | Pass | Pass | 7.7093269822E-002 | 0.2658429488 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.0685910710E-002 | 5.1727059954E-002 | Pass | Pass | 0.2224980953 | 0.4105892966 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.6162939897E-002 | 0.1052222048 | Pass | Pass | 0.1184278553 | 0.3217229517 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1396152166 | 0.1930621752 | Pass | Pass | 0.1190839134 | 0.3236180205 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1931520965 | 0.2808552358 | Pass | Pass | 0.1415530012 | 0.3731814781 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1580465245 | 0.2731989773 | Pass | Pass | 0.1178148996 | 0.3175344274 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.7666381450E-002 | 4.1191151202E-002 | Pass | Pass | 7.6007030985E-002 | 0.2606162688 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.3969080435E-002 | 0.1198601090 | Pass | Pass | 7.7036675911E-002 | 0.2661345881 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1855573065 | 0.2071862907 | Pass | Pass | 8.9130413990E-002 | 0.2928947369 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1144036351 | 0.1609232177 | Pass | Pass | 7.3939463433E-002 | 0.2531791712 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1546486515 | 0.2095535019 | Pass | Pass | 8.1794319816 | 31.2351018042 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1197227434 | 0.1581265596 | Pass | Pass | 6.7640786490 | 28.0059754691 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1609160817 | 0.1234161436 | Pass | Pass | 0.7032916838 | 5.3842630482 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1356324599 | 0.1215043837 | Pass | Pass | 0.8589184030 | 4.1561329735 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6775517686E-002 | 2.5728932640E-002 | Pass | Pass | 0.3021560691 | 1.0801906289 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9462404152E-002 | 3.1871783476E-002 | Pass | Pass | 0.1848664302 | 0.7677708533 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1004915048 | 6.9049389082E-002 | Pass | Pass | 0.2332546103 | 0.4131936672 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8549928888E-006 | 5.5084419404E-006 | Pass | Pass | 7.9713999033E-003 | 8.4654802138E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.9242040513E-003 | 2.2545744454E-002 | Pass | Pass | 0.1665162589 | 0.4445604052 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.6421586812E-002 | 3.6662550039E-002 | Pass | Pass | 0.1240413261 | 0.6295988761 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4844376271E-005 | 1.5354111812E-005 | Pass | Pass | 7.2892730606E-005 | 1.0661961996E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5211.43 | 38.51 | 0.00 | 17299.49 | 26318.61 | 48868.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.567_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.567_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.567_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.224 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.224 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.567_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.567_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.567_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.567_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.224 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.224 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.224 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.89 | 0.0000 | Y | 17.46 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.25 | 0.0000 | Y | 11.00 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.05 | 0.0000 | Y | 16.96 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.61 | 0.0000 | Y | 11.14 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.76 | 0.0000 | Y | 173.85 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 109.83 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.01 | 0.0000 | Y | 169.27 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.53 | 0.0000 | Y | 111.11 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.76 | 0.0000 | Y | 17.38 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 10.98 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.01 | 0.0000 | Y | 16.93 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.53 | 0.0000 | Y | 11.11 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1234.37 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.79 | 41.79 | 104.16 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.79 | 71.19 | 591.98 | |
Exterior Lighting Total | 57580.60 | 696.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2590247.60 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1834123.53 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1324145.97 | 6.28 | 1267385.55 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1324145.97 | 6.28 | 1267385.55 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 548384.16 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1571680.44 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1571680.44 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 212623.81 | 285833.20 | 185915.89 | 99917.31 | 0.65 | - | 34330.21 | 348.20 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2041715.22 | 2728130.17 | 1767336.42 | 960793.75 | 0.65 | - | 330600.65 | 3353.14 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 222807.78 | 302402.70 | 197083.05 | 105319.65 | 0.65 | - | 36449.08 | 369.69 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 119071.31 | 160148.44 | 106004.13 | 54144.31 | 0.66 | - | 18081.34 | 183.39 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 443651.01 | 290324.13 | 153326.88 | 0.65 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9698.75 | 6416.35 | 3282.41 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92575.26 | 61221.65 | 31353.61 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9468.54 | 6261.14 | 3207.41 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18400.76 | 17448.85 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 390319.78 | 369929.52 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 70749.76 | 67059.95 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8060.14 | 7639.97 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6479.41 | 6138.44 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10768.09 | 10205.54 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5585.30 | 5294.07 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 182859.23 | 173283.81 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 122783.07 | 116352.61 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 184887.84 | 175205.82 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 113606.41 | 107658.07 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23081.33 | 21871.81 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15379.44 | 14573.44 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23300.02 | 22079.01 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14593.83 | 13829.10 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 37131.82 | 30765.74 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 285154.89 | 241932.06 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 28157.41 | 24208.06 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 292824.99 | 234919.60 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 443651.01 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9698.75 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92575.26 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9468.54 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14683.19 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6783.03 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.25 | 24171.63 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 106.00 | 227832.99 | 2149.46 | 1.00 | 1.08 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.96 | 25706.28 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.68 | 11252.49 | 1684.71 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 23.57 | 38875.40 | 1649.25 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 590.53 | 1120.11 | 1.00 | 1.58 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.03 | 5632.72 | 1120.11 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 576.00 | 1120.11 | 1.00 | 1.59 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.110449 | 18032.97 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.016046 | 4832.26 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.055225 | 6242.42 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.055225 | 6242.42 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013602 | 3469.08 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.131054 | 32446.11 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 84170.02 | 84170.02 | 30.28 | 6.679 | 6.679 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 30.96 | 0.00562 | 1.200 | 0.00 |
CORE_BOTTOM | 86886.94 | 86886.94 | 34.81 | 6.894 | 6.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 30.96 | 0.00562 | 1.078 | 0.00 |
CORE_MID | 822518.79 | 822518.79 | 329.52 | 65.248 | 65.248 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 30.96 | 0.00562 | 10.778 | 0.00 |
CORE_TOP | 81795.61 | 81795.61 | 32.77 | 6.489 | 6.489 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 30.96 | 0.00562 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16482.03 | 16482.03 | 52.59 | 1.319 | 1.319 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00867 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15844.03 | 15844.03 | 78.45 | 1.268 | 1.268 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00861 | 34.99 | 0.00562 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18364.21 | 18364.21 | 58.59 | 1.470 | 1.470 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00865 | 40.58 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20219.98 | 20219.98 | 100.11 | 1.618 | 1.618 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00859 | 39.12 | 0.00563 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 161896.01 | 161896.01 | 516.56 | 12.956 | 12.956 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00859 | 40.80 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 165778.36 | 165778.36 | 820.79 | 13.266 | 13.266 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00856 | 35.75 | 0.00562 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 179812.35 | 179812.35 | 573.71 | 14.390 | 14.390 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00858 | 40.69 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 180912.70 | 180912.70 | 895.72 | 14.478 | 14.478 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00855 | 38.94 | 0.00563 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18305.98 | 18305.98 | 58.41 | 1.465 | 1.465 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00855 | 40.53 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16996.83 | 16996.83 | 84.15 | 1.360 | 1.360 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00853 | 36.08 | 0.00562 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19959.59 | 19959.59 | 63.68 | 1.597 | 1.597 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00855 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19467.89 | 19467.89 | 96.39 | 1.558 | 1.558 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00853 | 38.94 | 0.00563 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8352.03 | 8352.03 | 230.70 | 0.527 | 0.527 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79664.51 | 79664.51 | 2200.51 | 5.029 | 5.029 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8146.47 | 8146.47 | 225.02 | 0.514 | 0.514 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 36.28 | 0.00562 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373423.29 | 373423.29 | 476.50 | 23.571 | 23.571 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 28.70 | 0.00561 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.14 | 0.00432 | 0.50 | 0.00432 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.57 | 0.00432 | 0.50 | 0.00432 | 1.078 | 0.00 | |
CORE_MID | 209006.21 | 209006.21 | 83.73 | 9.694 | 10.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 10.778 | 0.00 |
CORE_TOP | 49563.90 | 49563.90 | 19.86 | 2.318 | 2.318 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5649.56 | 5649.56 | 18.03 | 0.264 | 0.264 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4163.20 | 4163.20 | 20.61 | 0.195 | 0.195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00762 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7541.97 | 7541.97 | 24.06 | 0.353 | 0.353 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2631.48 | 2631.48 | 13.03 | 0.123 | 0.123 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00724 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 127984.64 | 127984.64 | 408.36 | 6.006 | 6.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 85933.07 | 85933.07 | 425.46 | 4.033 | 4.033 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 129402.72 | 129402.72 | 412.87 | 6.073 | 6.073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 79517.93 | 79517.93 | 393.70 | 3.731 | 3.731 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16151.42 | 16151.42 | 51.53 | 0.758 | 0.758 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10761.66 | 10761.66 | 53.28 | 0.505 | 0.505 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16304.31 | 16304.31 | 52.02 | 0.766 | 0.766 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10212.40 | 10212.40 | 50.56 | 0.480 | 0.480 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.51 | 0.00610 | 0.50 | 0.00432 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.51 | 0.00468 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.25 | 11.25 | 2.01 | 2.01 | 11.2454 | 3.1480 | 11.2454 | 0.2799 | 0.3000 |
VAV_MID WITH REHEAT | 106.00 | 106.00 | 30.62 | 30.62 | 105.9952 | 30.8533 | 105.9952 | 0.2911 | 0.3000 |
VAV_TOP WITH REHEAT | 11.96 | 11.96 | 4.83 | 4.83 | 11.9594 | 4.8267 | 11.9594 | 0.4036 | 0.3000 |
CAV_BAS | 6.68 | 6.68 | 1.20 | 1.20 | 6.6792 | 6.6792 | 6.6792 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.57 | 23.57 | 0.34 | 0.34 | 23.5716 | 23.5714 | 23.5716 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5272 | 0.5272 | 0.5272 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.03 | 5.03 | 0.16 | 0.16 | 5.0287 | 5.0287 | 5.0287 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.51 | 0.51 | 0.02 | 0.02 | 0.5142 | 0.5142 | 0.5142 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18400.762 | 18400.762 | 2.013016 | 0.00016098 | 370.945 | 12/21 00:10:00 | 12/21 00:10:00 | 18400.76 | 18400.76 | 2.013016 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 18468.61 | 18468.61 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 390319.778 | 390319.778 | 19.835427 | 0.00341469 | 8887.613 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 390319.78 | 390319.78 | 19.835427 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 209006.21 | 0.00 | 391647.66 | 391647.66 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 70749.760 | 70749.760 | 2.317702 | 0.00061895 | 1868.369 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70749.76 | 70749.76 | 2.317702 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 49563.90 | 0.00 | 70999.92 | 70999.92 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8060.140 | 8060.140 | 0.263965 | 0.00007051 | 212.882 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8060.14 | 8060.14 | 0.263965 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00754237 | 44.3003 | 5649.56 | 0.00 | 8088.85 | 8088.85 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6479.410 | 6479.410 | 0.253593 | 0.00005668 | 159.306 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6479.41 | 6479.41 | 0.253593 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00762209 | 44.7627 | 4163.20 | 0.00 | 6499.80 | 6499.80 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10768.088 | 10768.088 | 0.353139 | 0.00009420 | 284.222 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10768.09 | 10768.09 | 0.353139 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00772935 | 45.3844 | 7541.97 | 0.00 | 10805.14 | 10805.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5585.295 | 5585.295 | 0.323632 | 0.00004886 | 123.458 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5585.30 | 5585.30 | 0.323632 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00724398 | 42.5682 | 2631.48 | 0.00 | 5604.55 | 5604.55 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 182859.234 | 182859.234 | 6.005963 | 0.00159973 | 4823.197 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 182859.23 | 182859.23 | 6.005963 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779953 | 45.7914 | 127984.64 | 0.00 | 183464.33 | 183464.33 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 122783.074 | 122783.074 | 4.033152 | 0.00107416 | 3238.457 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 122783.07 | 122783.07 | 4.033152 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780475 | 45.8217 | 85933.07 | 0.00 | 123188.38 | 123188.38 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 184887.844 | 184887.844 | 6.072745 | 0.00161748 | 4876.648 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 184887.84 | 184887.84 | 6.072745 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780272 | 45.8099 | 129402.72 | 0.00 | 185499.25 | 185499.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 113606.408 | 113606.408 | 3.731107 | 0.00099388 | 2996.643 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 113606.41 | 113606.41 | 3.731107 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777994 | 45.6780 | 79517.93 | 0.00 | 113983.05 | 113983.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23081.332 | 23081.332 | 0.758452 | 0.00020193 | 608.677 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23081.33 | 23081.33 | 0.758452 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781650 | 45.8900 | 16151.42 | 0.00 | 23156.78 | 23156.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15379.441 | 15379.441 | 0.505399 | 0.00013455 | 405.559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15379.44 | 15379.44 | 0.505399 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781698 | 45.8928 | 10761.66 | 0.00 | 15429.63 | 15429.63 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23300.024 | 23300.024 | 0.765651 | 0.00020384 | 614.439 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23300.02 | 23300.02 | 0.765651 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781830 | 45.9004 | 16304.31 | 0.00 | 23376.15 | 23376.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14593.827 | 14593.827 | 0.479542 | 0.00012767 | 384.857 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14593.83 | 14593.83 | 0.479542 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780628 | 45.8308 | 10212.40 | 0.00 | 14641.56 | 14641.56 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 212623.811 | -999.000 | 11.245419 | 0.00904551 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 212623.81 | 212623.81 | 11.245419 | 27.83 | 16.34 | 0.00806567 | 10.87 | 10.01 | 0.00806567 | 40.80 | 0.00563111 | 18.58 | 22.5709 | 24.00 | 0.00878513 | 42.9163 | 139036.21 | 0.00 | 228775.08 | 216470.82 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 37131.823 | 37131.823 | 3.373626 | 0.00032485 | 634.064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 37131.82 | 37131.82 | 3.373626 | 2.78 | 2.26 | 0.00469219 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 75.2363 | 21.60 | 0.00627221 | 35.5713 | 19986.21 | 0.00 | 37237.83 | 37237.83 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2041715.222 | -999.000 | 105.995232 | 0.08685928 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2041715.22 | 2041715.18 | 105.995232 | 28.15 | 16.39 | 0.00799828 | 10.87 | 9.94 | 0.00799828 | 40.80 | 0.00563111 | 18.58 | 23.9463 | 24.00 | 0.00877540 | 42.8690 | 1283259.60 | 0.00 | 2195751.48 | 2088979.16 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 285154.889 | 285154.889 | 31.798570 | 0.00249466 | 4929.864 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 285154.89 | 285154.89 | 31.798570 | 4.64 | 3.67 | 0.00503072 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 79.8210 | 21.00 | 0.00782944 | 45.9641 | 442660.85 | 0.00 | 292851.34 | 292851.34 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 222807.785 | -999.000 | 11.959386 | 0.00947876 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 222807.78 | 222807.78 | 11.959386 | 27.58 | 16.26 | 0.00806606 | 10.87 | 10.01 | 0.00806606 | 40.80 | 0.00563111 | 18.58 | 21.2234 | 24.00 | 0.00872624 | 42.6320 | 148694.87 | 0.00 | 239906.30 | 226890.80 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 28157.411 | 28157.411 | 3.587816 | 0.00024633 | 490.212 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28157.41 | 28157.41 | 3.587816 | 5.66 | 4.57 | 0.00533296 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 70.7447 | 19.60 | 0.00773794 | 49.5390 | 48883.83 | 0.00 | 29304.62 | 29304.62 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 119071.313 | -999.000 | 6.679169 | 0.00506557 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 119071.31 | 119071.31 | 6.679169 | 27.27 | 16.33 | 0.00828278 | 11.29 | 10.40 | 0.00828278 | 40.13 | 0.00563007 | 18.37 | 17.9686 | 24.00 | 0.00895823 | 43.7506 | 75312.49 | 0.00 | 128197.54 | 120332.89 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 292824.990 | 292824.990 | 6.679169 | 0.00256176 | 6583.497 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 292824.99 | 292824.99 | 6.679169 | 0.09 | 0.09 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 17.9686 | 25.14 | 0.00431558 | 19.8311 | 0.00 | 0.00 | 248355.96 | 248355.96 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 443651.012 | 290324.134 | 23.571604 | 0.01086498 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403453.10 | 403439.85 | -999.0 | 28.73 | 16.99 | 0.00850024 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | -999.0000 | 27.00 | 0.00854209 | 34.9356 | 372929.45 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9698.754 | 6416.347 | 0.527209 | 0.00023752 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8786.47 | 8786.47 | -999.0 | 28.32 | 16.85 | 0.00849882 | 12.80 | 11.23 | 0.00849882 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00858669 | 35.1132 | 8349.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92575.262 | 61221.648 | 5.028733 | 0.00226716 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83877.24 | 83877.24 | -999.0 | 28.33 | 16.85 | 0.00849859 | 12.80 | 11.23 | 0.00849859 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859087 | 35.1303 | 79614.57 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9468.543 | 6261.135 | 0.514235 | 0.00023188 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8579.24 | 8579.24 | -999.0 | 28.33 | 16.86 | 0.00849871 | 12.80 | 11.23 | 0.00849871 | 36.61 | 0.00562460 | 17.26 | -999.0000 | 27.00 | 0.00858889 | 35.1222 | 8140.82 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 443651.012 | 443651.012 | 23.571604 | 0.01086498 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 443651.01 | 443651.01 | 23.571604 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4356 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9698.754 | 9698.754 | 0.527209 | 0.00023752 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9698.75 | 9698.75 | 0.527209 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 2.9651 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92575.262 | 92575.262 | 5.028733 | 0.00226716 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 92575.26 | 92575.26 | 5.028733 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1086 | 24.51 | 0.00610103 | 29.0246 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9468.543 | 9468.543 | 0.514235 | 0.00023188 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9468.54 | 9468.54 | 0.514235 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0399 | 23.51 | 0.00468101 | 23.7080 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14683.19 | 14683.19 | 23.571604 | 0.01 | 0.01 | 0.00843993 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4356 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.527209 | 0.01 | 0.01 | 0.00837593 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 2.9651 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6783.03 | 6783.03 | 5.028733 | 0.02 | 0.02 | 0.00604553 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1086 | 24.51 | 0.00610103 | 29.0246 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.514235 | 0.02 | 0.02 | 0.00466990 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0399 | 23.51 | 0.00468101 | 23.7080 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18400.762 | 18400.762 | 2.013016 | 0.00016098 | 370.945 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.9835 | 1.003246 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 18400.76 | 18400.76 | 1.0000 | 2.20061766 | 2.013016 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.16096147 | 60.00 | 32.22 | 27.78 | 0.000 | 18400.76 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 18468.61 | 18468.61 | 2.20061766 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 390319.778 | 390319.778 | 19.835427 | 0.00341469 | 8887.613 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 20.8612 | 21.280997 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 390319.78 | 390319.78 | 1.0000 | 21.68397397 | 19.835427 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 3.41433936 | 60.00 | 32.22 | 27.78 | 0.000 | 390319.78 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 209006.21 | 0.00 | 391647.66 | 391647.66 | 21.68397397 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.51 | 18.21 | 0.00800000 | 51121.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 70749.760 | 70749.760 | 2.317702 | 0.00061895 | 1868.369 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 3.7813 | 3.857415 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 70749.76 | 70749.76 | 1.0000 | 2.53369797 | 2.317702 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.61888662 | 60.00 | 32.22 | 27.78 | 0.000 | 70749.76 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 49563.90 | 0.00 | 70999.92 | 70999.92 | 2.53369797 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61082.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8060.140 | 8060.140 | 0.263965 | 0.00007051 | 212.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.4308 | 0.439455 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8060.14 | 8060.14 | 1.0000 | 0.28856525 | 0.263965 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.07050643 | 60.00 | 32.22 | 27.78 | 0.000 | 8060.14 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00754237 | 21.00 | 0.00754237 | 44.3003 | 5649.56 | 0.00 | 8088.85 | 8088.85 | 0.28856525 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61091.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6479.410 | 6479.410 | 0.253593 | 0.00005668 | 159.306 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.3463 | 0.353270 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6479.41 | 6479.41 | 1.0000 | 0.27722662 | 0.253593 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.05667892 | 60.00 | 32.22 | 27.78 | 0.000 | 6479.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00762209 | 21.00 | 0.00762209 | 44.7627 | 4163.20 | 0.00 | 6499.80 | 6499.80 | 0.27722662 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.79 | 19.90 | 0.00800000 | 56505.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10768.088 | 10768.088 | 0.353139 | 0.00009420 | 284.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.5755 | 0.587097 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10768.09 | 10768.09 | 1.0000 | 0.38604947 | 0.353139 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09419432 | 60.00 | 32.22 | 27.78 | 0.000 | 10768.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00772935 | 21.00 | 0.00772935 | 45.3844 | 7541.97 | 0.00 | 10805.14 | 10805.14 | 0.38604947 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61048.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5585.295 | 5585.295 | 0.323632 | 0.00004886 | 123.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.2985 | 0.304521 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5585.30 | 5585.30 | 1.0000 | 0.35379289 | 0.323632 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04885762 | 60.00 | 32.22 | 27.78 | 0.000 | 5585.30 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00724398 | 21.00 | 0.00724398 | 42.5682 | 2631.48 | 0.00 | 5604.55 | 5604.55 | 0.35379289 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.34 | 17.48 | 0.00800000 | 48901.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 182859.234 | 182859.234 | 6.005963 | 0.00159973 | 4823.197 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 9.7732 | 9.969843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 182859.23 | 182859.23 | 1.0000 | 6.56568443 | 6.005963 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.59956916 | 60.00 | 32.22 | 27.78 | 0.000 | 182859.23 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00779953 | 21.00 | 0.00779953 | 45.7914 | 127984.64 | 0.00 | 183464.33 | 183464.33 | 6.56568443 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122783.074 | 122783.074 | 4.033152 | 0.00107416 | 3238.457 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 6.5623 | 6.694373 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 122783.07 | 122783.07 | 1.0000 | 4.40901867 | 4.033152 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.07405032 | 60.00 | 32.22 | 27.78 | 0.000 | 122783.07 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780475 | 21.00 | 0.00780475 | 45.8217 | 85933.07 | 0.00 | 123188.38 | 123188.38 | 4.40901867 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 184887.844 | 184887.844 | 6.072745 | 0.00161748 | 4876.648 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 9.8816 | 10.080447 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 184887.84 | 184887.84 | 1.0000 | 6.63869002 | 6.072745 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.61731452 | 60.00 | 32.22 | 27.78 | 0.000 | 184887.84 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780272 | 21.00 | 0.00780272 | 45.8099 | 129402.72 | 0.00 | 185499.25 | 185499.25 | 6.63869002 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 113606.408 | 113606.408 | 3.731107 | 0.00099388 | 2996.643 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 6.0718 | 6.194043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 113606.41 | 113606.41 | 1.0000 | 4.07882453 | 3.731107 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.99377703 | 60.00 | 32.22 | 27.78 | 0.000 | 113606.41 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777994 | 21.00 | 0.00777994 | 45.6780 | 79517.93 | 0.00 | 113983.05 | 113983.05 | 4.07882453 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23081.332 | 23081.332 | 0.758452 | 0.00020193 | 608.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 1.2336 | 1.258439 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23081.33 | 23081.33 | 1.0000 | 0.82913508 | 0.758452 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.20190497 | 60.00 | 32.22 | 27.78 | 0.000 | 23081.33 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781650 | 21.00 | 0.00781650 | 45.8900 | 16151.42 | 0.00 | 23156.78 | 23156.78 | 0.82913508 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15379.441 | 15379.441 | 0.505399 | 0.00013455 | 405.559 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.8220 | 0.838517 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15379.44 | 15379.44 | 1.0000 | 0.55249931 | 0.505399 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.13453233 | 60.00 | 32.22 | 27.78 | 0.000 | 15379.44 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781698 | 21.00 | 0.00781698 | 45.8928 | 10761.66 | 0.00 | 15429.63 | 15429.63 | 0.55249931 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23300.024 | 23300.024 | 0.765651 | 0.00020384 | 614.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 1.2453 | 1.270363 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23300.02 | 23300.02 | 1.0000 | 0.83700550 | 0.765651 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.20381798 | 60.00 | 32.22 | 27.78 | 0.000 | 23300.02 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00781830 | 21.00 | 0.00781830 | 45.9004 | 16304.31 | 0.00 | 23376.15 | 23376.15 | 0.83700550 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14593.827 | 14593.827 | 0.479542 | 0.00012767 | 384.857 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 0.7800 | 0.795684 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14593.83 | 14593.83 | 1.0000 | 0.52423223 | 0.479542 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12766014 | 60.00 | 32.22 | 27.78 | 0.000 | 14593.83 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780628 | 21.00 | 0.00780628 | 45.8308 | 10212.40 | 0.00 | 14641.56 | 14641.56 | 0.52423223 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 212623.811 | -999.000 | 11.245419 | 0.00904551 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8337 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.245419 | 12.29342708 | 4197.9300 | 999.8980 | 110.43785401 | 12.27 | 6.67 | 5.60 | 2596218.13 | 8.1898 | 8.189751 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 212623.81 | 212623.81 | 1.0000 | 12.29342708 | 11.245419 | 27.83 | 16.34 | 0.00806567 | 48555.1 | 10.87 | 10.01 | 0.00806567 | 31259.4 | 9.04458569 | 6.67 | 12.27 | 5.60 | 24171.630 | 188452.18 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 22.5709 | 24.00 | 0.00878513 | 24.00 | 0.00878513 | 42.9163 | 139036.21 | 0.00 | 228775.08 | 216470.82 | 12.29342708 | 27.83 | 17.36 | 0.00806567 | 48555.1 | 10.57 | 10.29 | 0.00766859 | 29945.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 37131.823 | 37131.823 | 3.373626 | 0.00032485 | 634.064 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.245419 | 12.29342708 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 1.9846 | 2.024500 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 37131.82 | 37131.82 | 1.0000 | 3.68802813 | 3.373626 | 2.78 | 2.26 | 0.00469219 | 14553.1 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.32481225 | 60.00 | 32.22 | 27.78 | 0.000 | 37131.82 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 75.2363 | 9.71 | 0.00583638 | 21.60 | 0.00627221 | 35.5713 | 19986.21 | 0.00 | 37237.83 | 37237.83 | 3.68802813 | 2.80 | 2.80 | 0.00469219 | 14572.9 | 12.76 | 7.98 | 0.00469219 | 24669.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2041715.222 | -999.000 | 105.995232 | 0.08685928 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7084 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 105.995232 | 115.87337459 | 4197.9300 | 999.8980 | 110.43785401 | 12.27 | 6.67 | 5.60 | 2596218.13 | 78.6419 | 78.641898 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2041715.22 | 2041715.18 | 1.0000 | 115.87337459 | 105.995232 | 28.15 | 16.39 | 0.00799828 | 48709.5 | 10.87 | 9.94 | 0.00799828 | 31089.3 | 86.85042484 | 6.67 | 12.27 | 5.60 | 227832.995 | 1813882.23 | 40.80 | 0.00563111 | 18.58 | 25.38195000 | 23.9463 | 24.00 | 0.00877540 | 24.00 | 0.00877540 | 42.8690 | 1283259.60 | 0.00 | 2195751.48 | 2088979.16 | 115.87337459 | 28.15 | 17.41 | 0.00799828 | 48709.5 | 10.47 | 10.21 | 0.00763268 | 29759.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 285154.889 | 285154.889 | 31.798570 | 0.00249466 | 4929.864 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 105.995232 | 115.87337459 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 15.2405 | 15.547202 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 14:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 285154.89 | 285154.89 | 1.0000 | 34.76201238 | 31.798570 | 4.64 | 3.67 | 0.00503072 | 17283.9 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 2.49440488 | 60.00 | 32.22 | 27.78 | 0.000 | 285154.89 | 0.50 | 0.00431558 | 0.50 | 25.38195000 | 79.8210 | 21.00 | 0.00785957 | 21.00 | 0.00782944 | 45.9641 | 442660.85 | 0.00 | 292851.34 | 292851.34 | 34.76201238 | 2.80 | 2.80 | 0.00503072 | 15421.3 | 11.11 | 7.59 | 0.00503072 | 23845.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 222807.785 | -999.000 | 11.959386 | 0.00947876 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8344 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.959386 | 13.07393134 | 4197.9300 | 999.8980 | 110.43785401 | 12.27 | 6.67 | 5.60 | 2596218.13 | 8.5820 | 8.582013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 222807.78 | 222807.78 | 1.0000 | 13.07393134 | 11.959386 | 27.58 | 16.26 | 0.00806606 | 48302.5 | 10.87 | 10.01 | 0.00806606 | 31260.4 | 9.47779130 | 6.67 | 12.27 | 5.60 | 25706.276 | 197101.51 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 21.2234 | 24.00 | 0.00872624 | 24.00 | 0.00872624 | 42.6320 | 148694.87 | 0.00 | 239906.30 | 226890.80 | 13.07393134 | 27.58 | 17.27 | 0.00806606 | 48302.5 | 10.57 | 10.29 | 0.00767110 | 29952.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28157.411 | 28157.411 | 3.587816 | 0.00024633 | 490.212 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.959386 | 13.07393134 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 1.5049 | 1.535197 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 28157.41 | 28157.41 | 1.0000 | 3.92217940 | 3.587816 | 5.66 | 4.57 | 0.00533296 | 19076.5 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.24630819 | 60.00 | 32.22 | 27.78 | 0.000 | 28157.41 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 70.7447 | 18.12 | 0.00779316 | 19.60 | 0.00773794 | 49.5390 | 48883.83 | 0.00 | 29304.62 | 29304.62 | 3.92217940 | 2.80 | 2.80 | 0.00533296 | 16178.7 | 10.16 | 7.49 | 0.00533296 | 23650.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 119071.313 | -999.000 | 6.679169 | 0.00506557 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2373 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 6.679169 | 7.30162885 | 4197.9300 | 999.8980 | 110.43785401 | 12.27 | 6.67 | 5.60 | 2596218.13 | 4.5863 | 4.586337 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 119071.31 | 119071.31 | 1.0000 | 7.30162885 | 6.679169 | 27.27 | 16.33 | 0.00828278 | 48540.2 | 11.29 | 10.40 | 0.00828278 | 32232.7 | 5.06505217 | 6.67 | 12.27 | 5.60 | 11252.494 | 107818.82 | 40.13 | 0.00563007 | 18.37 | 1.20015641 | 17.9686 | 24.00 | 0.00895823 | 24.00 | 0.00895823 | 43.7506 | 75312.49 | 0.00 | 128197.54 | 120332.89 | 7.30162885 | 27.27 | 17.35 | 0.00828278 | 48540.2 | 11.12 | 10.73 | 0.00785563 | 30982.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 292824.990 | 292824.990 | 6.679169 | 0.00256176 | 6583.497 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 6.679169 | 7.30162885 | 4197.9300 | 999.8980 | 16.04407592 | 54.44 | 82.22 | 27.78 | 1871035.99 | 15.6504 | 15.965391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 292824.99 | 292824.99 | 1.0000 | 7.30162885 | 6.679169 | 0.09 | 0.09 | 0.00431558 | 10884.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 2.56149942 | 60.00 | 32.22 | 27.78 | 0.000 | 292824.99 | 0.50 | 0.00431558 | 0.50 | 1.20015641 | 17.9686 | 0.00 | 0.00431558 | 25.14 | 0.00431558 | 19.8311 | 0.00 | 0.00 | 248355.96 | 248355.96 | 7.30162885 | 12.80 | 7.56 | 0.00431558 | 23757.7 | 46.38 | 20.39 | 0.00431558 | 57771.4 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 443651.012 | 290324.134 | 23.571604 | 0.01086498 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6415 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403453.10 | 403439.85 | 0.9094 | -999.0 | -999.0 | 28.73 | 16.99 | 0.00850024 | 50582.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403453.10 | 40.80 | 0.00563111 | 18.58 | 0.33839277 | -999.0000 | 27.00 | 0.00854209 | 27.00 | 0.00854209 | 34.9356 | 372929.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9698.754 | 6416.347 | 0.527209 | 0.00023752 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6389 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8786.47 | 8786.47 | 0.9059 | -999.0 | -999.0 | 28.32 | 16.85 | 0.00849882 | 50155.9 | 12.80 | 11.23 | 0.00849882 | 34319.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8786.47 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00858669 | 27.00 | 0.00858669 | 35.1132 | 8349.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92575.262 | 61221.648 | 5.028733 | 0.00226716 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6384 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 83877.24 | 83877.24 | 0.9060 | -999.0 | -999.0 | 28.33 | 16.85 | 0.00849859 | 50169.0 | 12.80 | 11.23 | 0.00849859 | 34318.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83877.24 | 36.28 | 0.00562409 | 17.15 | 0.15632344 | -999.0000 | 27.00 | 0.00859087 | 27.00 | 0.00859087 | 35.1303 | 79614.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9468.543 | 6261.135 | 0.514235 | 0.00023188 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6387 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8579.24 | 8579.24 | 0.9061 | -999.0 | -999.0 | 28.33 | 16.86 | 0.00849871 | 50173.2 | 12.80 | 11.23 | 0.00849871 | 34318.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8579.24 | 36.61 | 0.00562460 | 17.26 | 0.01563234 | -999.0000 | 27.00 | 0.00858889 | 27.00 | 0.00858889 | 35.1222 | 8140.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 443651.012 | 443651.012 | 23.571604 | 0.01086498 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 443651.01 | 443651.01 | 1.0000 | 25.76834168 | 23.571604 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 443651.01 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4356 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9698.754 | 9698.754 | 0.527209 | 0.00023752 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9698.75 | 9698.75 | 1.0000 | 0.57634193 | 0.527209 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9698.75 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 2.9651 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92575.262 | 92575.262 | 5.028733 | 0.00226716 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 92575.26 | 92575.26 | 1.0000 | 5.49738136 | 5.028733 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92575.26 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.1086 | 0.00 | 0.00610103 | 24.51 | 0.00610103 | 29.0246 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9468.543 | 9468.543 | 0.514235 | 0.00023188 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9468.54 | 9468.54 | 1.0000 | 0.56215881 | 0.514235 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9468.54 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0399 | 0.00 | 0.00468101 | 23.51 | 0.00468101 | 23.7080 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 23.571604 | 25.76834168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14683.19 | 14683.19 | 1.0000 | 25.76834168 | 23.571604 | 0.01 | 0.01 | 0.00843993 | 21115.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14683.19 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4356 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.527209 | 0.57634193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.57634193 | 0.527209 | 0.01 | 0.01 | 0.00837593 | 20962.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 2.9651 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.028733 | 5.49738136 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6783.03 | 6783.03 | 1.0000 | 5.49738136 | 5.028733 | 0.02 | 0.02 | 0.00604553 | 15135.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6783.03 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.1086 | 0.00 | 0.00610103 | 24.51 | 0.00610103 | 29.0246 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.514235 | 0.56215881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.56215881 | 0.514235 | 0.02 | 0.02 | 0.00466990 | 11694.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0399 | 0.00 | 0.00468101 | 23.51 | 0.00468101 | 23.7080 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.25 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 106.00 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.96 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.68 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 23.57 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2626.00 | 882.50 | 420.83 |
CORE_BOTTOM | 2389.83 | 490.17 | 17.00 |
CORE_MID | 1736.00 | 1779.33 | 51.50 |
CORE_TOP | 1754.83 | 2471.50 | 158.50 |
PERIMETER_BOT_ZN_3 | 2170.33 | 2333.67 | 120.67 |
PERIMETER_BOT_ZN_2 | 2774.50 | 1938.67 | 224.67 |
PERIMETER_BOT_ZN_1 | 3182.00 | 1420.17 | 241.33 |
PERIMETER_BOT_ZN_4 | 3667.33 | 1163.50 | 372.17 |
PERIMETER_MID_ZN_3 | 2169.17 | 3044.17 | 432.17 |
PERIMETER_MID_ZN_2 | 2277.17 | 2253.50 | 409.83 |
PERIMETER_MID_ZN_1 | 2969.17 | 1803.17 | 306.83 |
PERIMETER_MID_ZN_4 | 2692.67 | 2539.50 | 355.83 |
PERIMETER_TOP_ZN_3 | 2671.50 | 3222.00 | 906.00 |
PERIMETER_TOP_ZN_2 | 2980.00 | 2714.83 | 662.83 |
PERIMETER_TOP_ZN_1 | 3099.00 | 2104.17 | 508.83 |
PERIMETER_TOP_ZN_4 | 2952.00 | 2754.33 | 662.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1477.00 | 1477.00 |
DATACENTER_MID_ZN_6 | 5934.83 | 583.67 | 583.67 |
DATACENTER_TOP_ZN_6 | 5778.17 | 735.00 | 723.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5819.00 | 5819.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5923.50 | 5850.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 71.67 | 0.00 | 6.50 |
CORE_BOTTOM | 0.00 | 4.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 40.50 | 0.00 | 21.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 65.50 | 0.00 | 59.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 91.33 | 0.00 | 71.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 207.83 | 0.00 | 79.83 |
PERIMETER_MID_ZN_3 | 0.67 | 29.67 | 0.00 | 17.33 |
PERIMETER_MID_ZN_2 | 0.50 | 74.00 | 0.00 | 65.83 |
PERIMETER_MID_ZN_1 | 0.00 | 90.00 | 0.00 | 76.17 |
PERIMETER_MID_ZN_4 | 0.17 | 74.17 | 0.00 | 34.67 |
PERIMETER_TOP_ZN_3 | 7.67 | 49.00 | 0.83 | 27.33 |
PERIMETER_TOP_ZN_2 | 5.67 | 86.17 | 0.33 | 67.33 |
PERIMETER_TOP_ZN_1 | 2.33 | 85.83 | 0.00 | 62.50 |
PERIMETER_TOP_ZN_4 | 2.17 | 84.67 | 0.00 | 38.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 595.33 | 0.00 | 495.67 |
DATACENTER_MID_ZN_6 | 0.00 | 510.67 | 0.00 | 430.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 417.50 | 0.00 | 348.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1026.33 | 0.00 | 792.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 8.17 | 1431.00 | 0.83 | 1010.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 1.423 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.984 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.761 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.684 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.877 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.366 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 1.525 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.870 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.759 | 0.081 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.249 | 0.091 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 1.415 | 0.082 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.344 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.773 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.260 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 1.368 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.335 | 0.105 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 27.180 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.19 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.25 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1014.08 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 60833003.21 | 0.00 | 60833003.21 | 0.00 | 60833003.21 | 37848132.68 | 3807.43 | 2335.53 | 2617.04 | 385.69 |
CORE_BOTTOM | 42717799.34 | 0.00 | 42717799.34 | 0.00 | 42717799.34 | 33990283.35 | 5645.11 | 5.17 | 3109.72 | 468.89 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 6153.18 | 22.07 | 2584.75 | 132.37 |
CORE_TOP | 28264773.78 | 0.00 | 28264773.78 | 0.00 | 28264773.78 | 33990283.35 | 6348.10 | 20.87 | 2391.03 | 156.11 |
PERIMETER_BOT_ZN_3 | 4817095.34 | 0.00 | 4817095.34 | 347995.63 | 5165090.96 | 4267819.30 | 3764.51 | 56.64 | 4938.84 | 468.89 |
PERIMETER_BOT_ZN_2 | 4814331.93 | 0.00 | 4814331.93 | 231996.93 | 5046328.86 | 2750345.05 | 3536.05 | 13.33 | 5210.61 | 468.89 |
PERIMETER_BOT_ZN_1 | 8116574.36 | 0.00 | 8116574.36 | 347995.63 | 8464569.98 | 4267912.63 | 3519.64 | 21.81 | 5218.55 | 468.89 |
PERIMETER_BOT_ZN_4 | 6593146.19 | 0.00 | 6593146.19 | 231996.93 | 6825143.11 | 2750345.05 | 3453.66 | 0.00 | 5306.34 | 468.89 |
PERIMETER_MID_ZN_3 | 39315800.17 | 0.00 | 39315800.17 | 816132.14 | 40131932.31 | 42678193.03 | 4258.08 | 105.62 | 4396.30 | 132.37 |
PERIMETER_MID_ZN_2 | 43936221.40 | 0.00 | 43936221.40 | 544087.72 | 44480309.12 | 27503450.52 | 3904.39 | 5.60 | 4850.01 | 1041.37 |
PERIMETER_MID_ZN_1 | 72324640.12 | 0.00 | 72324640.12 | 816132.14 | 73140772.26 | 42679126.28 | 3955.39 | 13.22 | 4791.38 | 132.37 |
PERIMETER_MID_ZN_4 | 44850367.25 | 0.00 | 44850367.25 | 544087.72 | 45394454.97 | 27503450.52 | 3919.12 | 6.67 | 4834.22 | 132.37 |
PERIMETER_TOP_ZN_3 | 4013774.12 | 0.00 | 4013774.12 | 1013296.28 | 5027070.40 | 4267819.30 | 4290.52 | 40.25 | 4429.23 | 156.11 |
PERIMETER_TOP_ZN_2 | 4196535.45 | 0.00 | 4196535.45 | 675530.39 | 4872065.85 | 2750345.05 | 3946.40 | 4.12 | 4809.48 | 156.11 |
PERIMETER_TOP_ZN_1 | 7006419.28 | 0.00 | 7006419.28 | 1013296.28 | 8019715.56 | 4267912.63 | 4042.92 | 16.11 | 4700.98 | 156.11 |
PERIMETER_TOP_ZN_4 | 4461987.71 | 0.00 | 4461987.71 | 675530.39 | 5137518.10 | 2750345.05 | 3966.81 | 9.94 | 4783.25 | 156.11 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.46E+09 | 0.00 | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 695.78 | 1551.00 | 6513.22 | 2478.79 |
Total Facility | 0.58E+10 | 0.00 | 0.58E+10 | 31742035.64 | 0.58E+10 | 0.50E+10 | 6791.75 | 4385.53 | 8064.61 | 3388.01 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.6253 | 0.0000 | 2.6253 | 0.0000 | 2.6253 | 1.2002 | 1286.02 | 2334.03 | 2322.95 |
CORE_BOTTOM | 1.8352 | 0.0000 | 1.8352 | 0.0000 | 1.8352 | 1.0778 | 3282.87 | 2.70 | 2657.43 |
CORE_MID | 14.1913 | 0.0000 | 14.1913 | 0.0000 | 14.1913 | 10.7782 | 3460.96 | 21.84 | 2460.19 |
CORE_TOP | 1.2761 | 0.0000 | 1.2761 | 0.0000 | 1.2761 | 1.0778 | 3636.96 | 20.29 | 2285.74 |
PERIMETER_BOT_ZN_3 | 0.2053 | 0.0000 | 0.2053 | 0.0081 | 0.2134 | 0.1353 | 1404.33 | 54.85 | 4483.82 |
PERIMETER_BOT_ZN_2 | 0.2062 | 0.0000 | 0.2062 | 0.0054 | 0.2116 | 0.0872 | 1187.88 | 13.33 | 4741.78 |
PERIMETER_BOT_ZN_1 | 0.3573 | 0.0000 | 0.3573 | 0.0081 | 0.3654 | 0.1353 | 1165.19 | 19.93 | 4757.88 |
PERIMETER_BOT_ZN_4 | 0.2821 | 0.0000 | 0.2821 | 0.0054 | 0.2875 | 0.0872 | 1105.55 | 0.00 | 4837.45 |
PERIMETER_MID_ZN_3 | 1.7799 | 0.0000 | 1.7799 | 0.0191 | 1.7990 | 1.3533 | 1567.32 | 105.48 | 4270.20 |
PERIMETER_MID_ZN_2 | 1.8868 | 0.0000 | 1.8868 | 0.0137 | 1.9005 | 0.8721 | 1216.19 | 3.27 | 3814.54 |
PERIMETER_MID_ZN_1 | 3.3162 | 0.0000 | 3.3162 | 0.0191 | 3.3353 | 1.3533 | 1264.41 | 13.22 | 4665.36 |
PERIMETER_MID_ZN_4 | 2.0313 | 0.0000 | 2.0313 | 0.0127 | 2.0440 | 0.8721 | 1234.48 | 6.67 | 4701.85 |
PERIMETER_TOP_ZN_3 | 0.1813 | 0.0000 | 0.1813 | 0.0237 | 0.2050 | 0.1353 | 1587.04 | 38.69 | 4317.27 |
PERIMETER_TOP_ZN_2 | 0.1904 | 0.0000 | 0.1904 | 0.0158 | 0.2062 | 0.0872 | 1267.09 | 3.31 | 4672.60 |
PERIMETER_TOP_ZN_1 | 0.3207 | 0.0000 | 0.3207 | 0.0237 | 0.3443 | 0.1353 | 1341.61 | 14.91 | 4586.48 |
PERIMETER_TOP_ZN_4 | 0.2018 | 0.0000 | 0.2018 | 0.0158 | 0.2176 | 0.0872 | 1288.61 | 9.92 | 4644.47 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.9574 | 0.0000 | 13.9574 | 0.0000 | 13.9574 | 0.3384 | 357.57 | 1551.00 | 4034.43 |
Total Facility | 254.8583 | 0.0000 | 254.8583 | 0.7512 | 255.6094 | 158.4706 | 3974.75 | 4373.65 | 5585.59 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 80140391.39 | 0.00 | 80140391.39 | 48026705.38 | 3455.83 | 0.32 | 5303.85 | 468.89 |
VAV_MID WITH REHEAT | 0.61E+09 | 0.00 | 0.61E+09 | 0.48E+09 | 3911.32 | 1.62 | 4847.07 | 132.37 |
VAV_TOP WITH REHEAT | 57295999.98 | 0.00 | 57295999.98 | 48026705.38 | 3980.31 | 5.16 | 4774.53 | 156.11 |
CAV_BAS | 72699915.87 | 0.00 | 72699915.87 | 37848132.68 | 3787.08 | 1.64 | 4971.28 | 385.65 |
AIRLOOP DATACENTER BASEMENT | 0.55E+09 | 0.00 | 0.55E+09 | 10671554.30 | 695.78 | 0.00 | 8064.22 | 2478.79 |
AIRLOOP DATACENTER BOT | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2919517.21 | 0.00 | 2919517.21 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.4490 | 0.0000 | 3.4490 | 1.5229 | 1106.04 | 0.02 | 4836.94 |
VAV_MID WITH REHEAT | 27.8627 | 0.0000 | 27.8627 | 15.2292 | 1221.21 | 1.42 | 4720.37 |
VAV_TOP WITH REHEAT | 2.5937 | 0.0000 | 2.5937 | 1.5229 | 1287.35 | 2.07 | 4653.59 |
CAV_BAS | 3.1375 | 0.0000 | 3.1375 | 1.2002 | 1283.67 | 0.28 | 4659.05 |
AIRLOOP DATACENTER BASEMENT | 16.6801 | 0.0000 | 16.6801 | 0.3384 | 357.57 | 0.00 | 5585.43 |
AIRLOOP DATACENTER BOT | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1365 | 0.0000 | 0.1365 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.37 | 3128.30 | 0.00 | 0.00 | 0.00 | 2177.67 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.72 | 2615.02 | 0.00 | 0.00 | 0.00 | 2248.64 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.05 | 2552.55 | 0.00 | 0.00 | 0.00 | 2300.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2333.58 | 2718.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1551.00 | 6513.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 6.1085 | 0.0000 | 0.0000 | 0.0000 | 1.9531 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 48.4114 | 0.0000 | 0.0000 | 0.0000 | 20.1875 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.5376 | 0.0000 | 0.0000 | 0.0000 | 1.9747 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.4346 | 6.5576 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4044 | 24.4181 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
Electricity:Building | 18602.56 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18602.56 | 225715.65 | 07-MAY-17:10 | 1164206.62 | 01-DEC-16:30 |
InteriorLights:Electricity | 3926.16 | 18459.50 | 01-JAN-10:10 | 385834.94 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3926.16 | 18459.50 | 01-JAN-10:10 | 385834.94 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity | 3926.16 | 18459.50 | 01-JAN-10:10 | 385834.94 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3926.16 | 18459.50 | 01-JAN-10:10 | 385834.94 | 20-JAN-17:00 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.82 | 627.57 | 02-APR-17:10 | 4748.47 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.46 | 68.40 | 01-JAN-10:10 | 2587.92 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.46 | 68.40 | 01-JAN-10:10 | 2587.92 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.44 | 404.43 | 16-APR-17:10 | 3060.10 | 20-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.00 | 44.08 | 01-JAN-07:50 | 1667.75 | 20-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.00 | 44.08 | 01-JAN-07:50 | 1667.75 | 20-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.32 | 627.58 | 02-APR-17:10 | 4748.56 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.96 | 68.40 | 01-JAN-08:00 | 2587.98 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 16.96 | 68.40 | 01-JAN-08:00 | 2587.98 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.58 | 404.43 | 12-MAR-17:10 | 3060.09 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.14 | 44.08 | 01-JAN-10:00 | 1667.75 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.14 | 44.08 | 01-JAN-10:00 | 1667.75 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 537.51 | 6275.73 | 02-APR-17:10 | 47484.70 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 173.85 | 684.02 | 01-JAN-10:00 | 25879.19 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 173.85 | 684.02 | 01-JAN-10:00 | 25879.19 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 344.18 | 4044.32 | 02-APR-17:10 | 30600.95 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 109.83 | 440.81 | 01-JAN-07:50 | 16677.53 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 109.83 | 440.81 | 01-JAN-07:50 | 16677.53 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 532.93 | 6275.83 | 26-MAR-17:10 | 47485.60 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.27 | 684.04 | 01-JAN-08:00 | 25879.75 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 169.27 | 684.04 | 01-JAN-08:00 | 25879.75 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 345.46 | 4044.30 | 12-MAR-17:10 | 30600.86 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.11 | 440.81 | 01-JAN-09:50 | 16677.53 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 111.11 | 440.81 | 01-JAN-09:50 | 16677.53 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.75 | 627.57 | 02-APR-17:10 | 4748.47 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.38 | 68.40 | 01-JAN-10:00 | 2587.92 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.38 | 68.40 | 01-JAN-10:00 | 2587.92 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.42 | 404.43 | 02-APR-17:10 | 3060.10 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.98 | 44.08 | 01-JAN-07:50 | 1667.75 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.98 | 44.08 | 01-JAN-07:50 | 1667.75 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.29 | 627.58 | 26-MAR-17:10 | 4748.56 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.93 | 68.40 | 01-JAN-08:00 | 2587.98 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 16.93 | 68.40 | 01-JAN-08:00 | 2587.98 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.55 | 404.43 | 12-MAR-17:10 | 3060.09 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.11 | 44.08 | 01-JAN-09:50 | 1667.75 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.11 | 44.08 | 01-JAN-09:50 | 1667.75 | 20-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3901.47 | 3752.09 | 01-JAN-06:00 | 437743.73 | 05-SEP-07:50 |
HeatRejection:Electricity | 1301.65 | 264.19 | 01-JAN-08:00 | 87736.39 | 10-APR-14:30 |
General:HeatRejection:Electricity | 1301.65 | 264.19 | 01-JAN-08:00 | 87736.39 | 10-APR-14:30 |
Electricity:HVAC | 6798.80 | 52472.42 | 21-JAN-04:00 | 590959.65 | 25-AUG-15:00 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118530.30 | 20-JAN-08:40 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
ElectricityPurchased:Plant | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
Cogeneration:ElectricityPurchased | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
ElectricityNet:Plant | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
Cogeneration:ElectricityNet | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
General:Cogeneration:ElectricityNet | 31853.58 | 343206.80 | 22-JAN-10:10 | 2175351.10 | 25-AUG-15:10 |
Fans:Electricity | 2877.99 | 45674.65 | 08-APR-17:40 | 285016.27 | 28-JUN-14:50 |
General:Fans:Electricity | 2877.99 | 45674.65 | 08-APR-17:40 | 285016.27 | 28-JUN-14:50 |
ExteriorLights:Electricity | 696.14 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 696.14 | 0.00 | 01-JAN-07:30 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 4172.81 | 2383.55 | 02-JAN-07:10 | 487904.20 | 11-AUG-15:50 |
General:Cooling:Electricity | 4172.81 | 2383.55 | 02-JAN-07:10 | 487904.20 | 11-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1611.79 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:00 |
General:Humidifier:Electricity | 1611.79 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 655.85 | 3469.08 | 01-JAN-00:40 | 56932.35 | 28-SEP-13:50 |
General:Pumps:Electricity | 655.85 | 3469.08 | 01-JAN-00:40 | 56932.35 | 28-SEP-13:50 |
WIRED_LTG_ELECTRICITY | 110.32 | 0.00 | 01-JAN-00:10 | 10841.96 | 20-JAN-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 778.62 | 8146.58 | 02-APR-16:20 | 514963.75 | 02-JAN-06:10 |
NaturalGas:Plant | 778.62 | 8146.58 | 02-APR-16:20 | 514963.75 | 02-JAN-06:10 |
Heating:NaturalGas | 104.29 | 0.00 | 01-JAN-00:40 | 498515.56 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 104.29 | 0.00 | 01-JAN-00:40 | 498515.56 | 02-JAN-06:10 |
WaterSystems:NaturalGas | 674.33 | 8146.58 | 02-JAN-05:20 | 77703.73 | 20-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 674.33 | 8146.58 | 02-JAN-05:20 | 77703.73 | 20-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 21764.24 | 6971.41 | 02-JAN-07:10 | 2657789.67 | 11-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 21764.24 | 6971.41 | 02-JAN-07:10 | 2657789.67 | 11-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 21764.24 | 6971.41 | 02-JAN-07:10 | 2657789.67 | 11-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 17565.00 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
Water:HVAC | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Humidifier:Water | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
General:Humidifier:Water | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
MainsWater:Facility | 17565.00 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
MainsWater:HVAC | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Humidifier:MainsWater | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
General:Humidifier:MainsWater | 599.58 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:10 |
Water:Plant | 16965.42 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 16965.42 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 14685.25 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
General:HeatRejection:Water | 14685.25 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
HeatRejection:MainsWater | 14685.25 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
General:HeatRejection:MainsWater | 14685.25 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 84401.84 | 99932.70 | 01-JAN-06:00 | 10387425.34 | 11-AUG-15:50 |
EnergyTransfer:Building | 22388.23 | 91026.93 | 01-JAN-23:20 | 1760213.62 | 14-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 787.58 | 0.00 | 01-JAN-00:10 | 76040.06 | 28-AUG-05:10 |
Heating:EnergyTransfer | 46.79 | 0.00 | 01-JAN-17:30 | 309554.87 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.75 | 0.00 | 01-JAN-00:10 | 29569.68 | 26-AUG-16:10 |
General:Heating:EnergyTransfer | 46.79 | 0.00 | 01-JAN-17:30 | 309554.87 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.75 | 0.00 | 01-JAN-00:10 | 29569.68 | 26-AUG-16:10 |
Cooling:EnergyTransfer | 22341.44 | 89437.94 | 01-JAN-08:40 | 1760213.62 | 14-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 782.83 | 0.00 | 01-JAN-00:10 | 76040.06 | 28-AUG-05:10 |
General:Cooling:EnergyTransfer | 22341.44 | 89437.94 | 01-JAN-08:40 | 1760213.62 | 14-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 782.83 | 0.00 | 01-JAN-00:10 | 76040.06 | 28-AUG-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 753.98 | 0.00 | 01-JAN-00:10 | 62464.31 | 28-AUG-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 753.98 | 0.00 | 01-JAN-00:10 | 62464.31 | 28-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 753.98 | 0.00 | 01-JAN-00:10 | 62464.31 | 28-AUG-09:10 |
EnergyTransfer:Zone:CORE_MID | 5623.47 | 0.00 | 01-JAN-00:10 | 466015.20 | 06-SEP-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5623.47 | 0.00 | 01-JAN-00:10 | 466015.20 | 06-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5623.47 | 0.00 | 01-JAN-00:10 | 466015.20 | 06-SEP-14:00 |
EnergyTransfer:Zone:CORE_TOP | 551.80 | 0.00 | 01-JAN-00:40 | 54741.51 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.40 | 0.00 | 01-JAN-00:10 | 41793.51 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.40 | 0.00 | 01-JAN-00:10 | 41793.51 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 551.40 | 0.00 | 01-JAN-00:40 | 54741.51 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 551.40 | 0.00 | 01-JAN-00:40 | 54741.51 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.83 | 0.00 | 01-JAN-00:10 | 12659.35 | 28-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 876.73 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 876.73 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.83 | 0.00 | 01-JAN-00:10 | 12659.35 | 28-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.83 | 0.00 | 01-JAN-00:10 | 12659.35 | 28-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 97.24 | 0.00 | 01-JAN-00:10 | 14126.23 | 19-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1579.55 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1579.55 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 97.23 | 0.00 | 01-JAN-00:10 | 14126.23 | 19-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 97.23 | 0.00 | 01-JAN-00:10 | 14126.23 | 19-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 153.86 | 0.00 | 01-JAN-00:10 | 19236.93 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1184.87 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1184.87 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 153.86 | 0.00 | 01-JAN-00:10 | 19236.93 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 153.86 | 0.00 | 01-JAN-00:10 | 19236.93 | 02-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.40 | 0.00 | 01-JAN-00:10 | 19937.02 | 25-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.40 | 0.00 | 01-JAN-00:10 | 19937.02 | 25-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.40 | 0.00 | 01-JAN-00:10 | 19937.02 | 25-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 834.98 | 0.00 | 01-JAN-00:10 | 123533.95 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.09 | 0.00 | 01-JAN-00:10 | 88687.96 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.09 | 0.00 | 01-JAN-00:10 | 88687.96 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 828.89 | 0.00 | 01-JAN-00:10 | 123533.95 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 828.89 | 0.00 | 01-JAN-00:10 | 123533.95 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 887.69 | 0.00 | 01-JAN-00:10 | 145221.42 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.73 | 0.00 | 01-JAN-00:10 | 52160.93 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.73 | 0.00 | 01-JAN-00:10 | 52160.93 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 884.96 | 0.00 | 01-JAN-00:10 | 145221.42 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 884.96 | 0.00 | 01-JAN-00:10 | 145221.42 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1357.25 | 0.00 | 01-JAN-00:10 | 191891.98 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.32 | 0.00 | 01-JAN-00:10 | 43067.58 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.32 | 0.00 | 01-JAN-00:10 | 43067.58 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1355.94 | 0.00 | 01-JAN-00:10 | 191891.98 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1355.94 | 0.00 | 01-JAN-00:10 | 191891.98 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 925.53 | 0.00 | 01-JAN-00:10 | 161889.92 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.51 | 0.00 | 01-JAN-00:10 | 34967.65 | 07-DEC-05:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.51 | 0.00 | 01-JAN-00:10 | 34967.65 | 07-DEC-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 924.03 | 0.00 | 01-JAN-00:10 | 161889.92 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 924.03 | 0.00 | 01-JAN-00:10 | 161889.92 | 29-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 89.72 | 0.00 | 01-JAN-00:40 | 15676.85 | 02-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.66 | 0.00 | 01-JAN-00:40 | 15676.85 | 02-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.66 | 0.00 | 01-JAN-00:40 | 15676.85 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.06 | 0.00 | 01-JAN-00:20 | 13763.99 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.06 | 0.00 | 01-JAN-00:20 | 13763.99 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 91.46 | 0.00 | 01-JAN-00:40 | 14713.28 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 9878.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.64 | 0.00 | 01-JAN-00:10 | 9878.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 89.82 | 0.00 | 01-JAN-00:40 | 14713.28 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 89.82 | 0.00 | 01-JAN-00:40 | 14713.28 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 136.36 | 0.00 | 01-JAN-00:40 | 20781.20 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.36 | 0.00 | 01-JAN-00:10 | 11248.98 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.36 | 0.00 | 01-JAN-00:10 | 11248.98 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 135.00 | 0.00 | 01-JAN-00:40 | 20781.20 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 135.00 | 0.00 | 01-JAN-00:40 | 20781.20 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 94.80 | 0.00 | 01-JAN-00:40 | 17097.23 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.10 | 0.00 | 01-JAN-00:10 | 7799.37 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.10 | 0.00 | 01-JAN-00:10 | 7799.37 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 93.71 | 0.00 | 01-JAN-00:40 | 17097.23 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 93.71 | 0.00 | 01-JAN-00:40 | 17097.23 | 29-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 106.51 | 0.00 | 01-JAN-00:10 | 14385.82 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.94 | 0.00 | 01-JAN-00:10 | 3147.42 | 05-FEB-15:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.94 | 0.00 | 01-JAN-00:10 | 3147.42 | 05-FEB-15:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 105.57 | 0.00 | 01-JAN-00:10 | 14385.82 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 105.57 | 0.00 | 01-JAN-00:10 | 14385.82 | 28-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 769.04 | 0.00 | 01-JAN-00:10 | 98717.93 | 19-JUN-15:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.43 | 0.00 | 01-JAN-00:10 | 53601.91 | 02-JAN-15:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.43 | 0.00 | 01-JAN-00:10 | 53601.91 | 02-JAN-15:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 757.61 | 0.00 | 01-JAN-00:10 | 98717.93 | 19-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 757.61 | 0.00 | 01-JAN-00:10 | 98717.93 | 19-JUN-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 134.15 | 0.00 | 01-JAN-00:40 | 25789.91 | 28-JUN-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.53 | 0.00 | 01-JAN-00:40 | 16804.99 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.53 | 0.00 | 01-JAN-00:40 | 16804.99 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 124.62 | 0.00 | 01-JAN-00:10 | 25789.91 | 28-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 124.62 | 0.00 | 01-JAN-00:10 | 25789.91 | 28-JUN-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.14 | 1105.91 | 02-JAN-07:00 | 8109.81 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.14 | 1105.91 | 02-JAN-07:00 | 8109.81 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.14 | 1105.91 | 02-JAN-07:00 | 8109.81 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1302.74 | 107.02 | 01-JAN-14:40 | 75889.13 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.24 | 0.00 | 01-JAN-14:40 | 5151.48 | 01-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.24 | 0.00 | 01-JAN-14:40 | 5151.48 | 01-JAN-08:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1302.50 | 0.00 | 01-JAN-00:10 | 75889.13 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1302.50 | 0.00 | 01-JAN-00:10 | 75889.13 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.72 | 6.20 | 23-JAN-02:50 | 7640.16 | 26-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.09 | 0.00 | 01-JAN-16:40 | 606.03 | 02-JAN-01:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.09 | 0.00 | 01-JAN-16:40 | 606.03 | 02-JAN-01:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.64 | 0.00 | 01-JAN-00:10 | 7640.16 | 26-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.64 | 0.00 | 01-JAN-00:10 | 7640.16 | 26-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7177.97 | 88214.40 | 22-JAN-06:00 | 383417.48 | 26-AUG-02:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7177.97 | 88214.40 | 22-JAN-06:00 | 383417.48 | 26-AUG-02:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7177.97 | 88214.40 | 22-JAN-06:00 | 383417.48 | 26-AUG-02:40 |
PlantLoopHeatingDemand:Facility | 396.28 | 0.00 | 01-JAN-00:40 | 393258.66 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 323.62 | 0.00 | 01-JAN-00:10 | 42571.79 | 24-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42571.79 | 24-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42571.79 | 24-JAN-12:20 |
EnergyTransfer:HVAC | 19608.05 | 4924.06 | 01-JAN-08:00 | 2453601.67 | 11-AUG-15:50 |
HeatingCoils:EnergyTransfer | 72.66 | 0.00 | 01-JAN-00:40 | 388186.92 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 72.66 | 0.00 | 01-JAN-00:40 | 388186.92 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 72.66 | 0.00 | 01-JAN-00:40 | 388186.92 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 19535.40 | 4587.87 | 02-JAN-07:10 | 2453601.67 | 11-AUG-15:50 |
EnergyTransfer:Plant | 42405.56 | 0.00 | 01-JAN-00:40 | 6603253.15 | 05-SEP-07:50 |
LoopToLoop:EnergyTransfer | 13469.53 | 0.00 | 01-JAN-00:10 | 2095394.87 | 19-JUN-14:20 |
WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42571.79 | 24-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42571.79 | 24-JAN-12:20 |
Boilers:EnergyTransfer | 71.98 | 0.00 | 01-JAN-00:40 | 404529.99 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 13298.23 | 0.00 | 01-JAN-00:10 | 2097616.47 | 05-SEP-07:50 |
HeatRejection:EnergyTransfer | 15242.20 | 0.00 | 01-JAN-00:10 | 2396697.60 | 05-SEP-07:50 |
General:HeatRejection:EnergyTransfer | 15242.20 | 0.00 | 01-JAN-00:10 | 2396697.60 | 05-SEP-07:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.753 | -782.824 | 0.000 | 0.000 | 92.664 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -1.834 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -753.973 | 0.000 | 0.000 | 83.408 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 144.899 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5623.443 | 0.000 | 0.000 | 836.351 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -469.563 |
CORE_TOP | 0.000 | 0.000 | 0.404 | -551.394 | 0.000 | 0.000 | 84.556 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -59.232 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -104.825 | 0.000 | 0.000 | 10.568 | 17.459 | 36.365 | 44.284 | 0.000 | 0.797 | 45.289 | 0.000 | -47.959 | 0.000 | -1.978 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.004 | -97.233 | 0.000 | 0.000 | 6.798 | 11.004 | 23.435 | 77.547 | 0.000 | 0.553 | 7.869 | 0.000 | -28.674 | 0.000 | -1.303 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.001 | -153.860 | 0.000 | 0.000 | 10.510 | 16.956 | 36.366 | 127.345 | 0.000 | 0.789 | 9.791 | 0.000 | -45.825 | 0.000 | -2.072 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -138.393 | 0.000 | 0.000 | 6.768 | 11.144 | 23.435 | 73.046 | 0.000 | 0.496 | 61.461 | 0.000 | -36.430 | 0.000 | -1.526 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 6.095 | -828.881 | 0.000 | 0.000 | 108.600 | 173.853 | 363.654 | 462.750 | 0.000 | 18.358 | 165.780 | 0.000 | -429.530 | 0.000 | -40.678 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.727 | -884.960 | 0.000 | 0.000 | 50.707 | 109.832 | 234.352 | 774.828 | 0.000 | 12.108 | 0.700 | 0.000 | -271.689 | 0.000 | -28.606 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.316 | -1355.914 | 0.000 | 0.000 | 105.668 | 169.274 | 363.660 | 1273.046 | 0.000 | 17.789 | 0.009 | 0.000 | -444.165 | 0.000 | -46.826 | -83.848 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.506 | -924.009 | 0.000 | 0.000 | 69.881 | 111.113 | 234.351 | 749.726 | 0.000 | 11.658 | 84.993 | 0.000 | -309.245 | 0.000 | -29.975 | -0.013 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.663 | -86.058 | 0.000 | 0.000 | 11.031 | 17.384 | 36.365 | 46.484 | 0.000 | 2.241 | 13.673 | 0.000 | -40.145 | 0.000 | -4.638 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.635 | -89.825 | 0.000 | 0.000 | 6.942 | 10.983 | 23.435 | 77.520 | 0.000 | 1.461 | 0.001 | 0.000 | -25.789 | 0.000 | -3.316 | -3.048 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.363 | -134.993 | 0.000 | 0.000 | 10.666 | 16.927 | 36.366 | 127.306 | 0.000 | 2.157 | 0.002 | 0.000 | -42.205 | 0.000 | -5.454 | -12.132 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.097 | -93.705 | 0.000 | 0.000 | 7.067 | 11.111 | 23.435 | 74.825 | 0.000 | 1.426 | 7.657 | 0.000 | -29.412 | 0.000 | -3.501 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.137 | 0.000 | 0.000 | 0.936 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.308 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.243 | -1302.499 | 0.000 | 0.000 | 9.382 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -312.211 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.087 | -125.636 | 0.000 | 0.000 | 0.941 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -35.900 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7177.975 | 0.000 | 0.000 | 19.187 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -410.180 |
GROUNDFLOOR_PLENUM | 0.938 | -105.573 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.491 | 107.611 | 0.000 | 0.000 | 0.000 | -4.466 | 0.000 |
MIDFLOOR_PLENUM | 11.426 | -757.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27.226 | 794.864 | 0.000 | 0.000 | 0.000 | -75.906 | -0.003 |
TOPFLOOR_PLENUM | 9.530 | -124.617 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.823 | 119.936 | 0.000 | 0.000 | 0.000 | -7.672 | -0.000 |
Total Facility | 21.894 | -987.801 | 24.894 | -21353.539 | 0.000 | 0.000 | 1532.629 | 3926.162 | 14676.396 | 3908.708 | 0.000 | 101.373 | 1564.538 | 0.000 | -1751.069 | 0.000 | -257.915 | -1406.283 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 24-APR-04:11 | 0.00 | 0.00 | 0.00 | -122402.88 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 106395.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | -102910.56 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 94682.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-JUL-04:12 | 0.00 | 0.00 | 0.00 | -896113.35 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 813835.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUL-04:13 | 0.00 | 0.00 | 0.00 | -92675.43 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 84447.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-17:41 | 0.00 | 0.00 | 0.00 | -21728.73 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 6873.47 | 0.00 | 464.48 | 13763.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:31 | 0.00 | 0.00 | 0.00 | -21965.03 | 0.00 | 0.00 | 20.82 | 44.08 | 464.11 | 12991.14 | 0.00 | 0.00 | 8468.40 | 0.00 | -0.00 | 0.00 | -23.53 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:41 | 0.00 | 0.00 | 0.00 | -26040.73 | 0.00 | 0.00 | 32.23 | 68.40 | 720.19 | 21129.87 | 0.00 | 35.09 | 4054.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-16:21 | 0.00 | 0.00 | 0.00 | -32770.42 | 0.00 | 0.00 | 10.85 | 44.08 | 464.11 | 16979.58 | 0.00 | 163.45 | 15108.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-17:31 | 0.00 | 0.00 | 0.00 | -214352.78 | 0.00 | 0.00 | 0.00 | 684.02 | 5591.71 | 67204.84 | 0.00 | 10554.90 | 130317.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 | -240745.87 | 0.00 | 0.00 | 193.42 | 440.81 | 4641.14 | 149507.08 | 0.00 | 593.91 | 85369.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-12:31 | 0.00 | 0.00 | 0.00 | -257428.21 | 0.00 | 0.00 | 317.23 | 684.04 | 7201.95 | 210200.74 | 0.00 | 695.53 | 38328.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -281579.30 | 0.00 | 0.00 | 145.00 | 440.81 | 4641.11 | 159742.01 | 0.00 | 5471.82 | 111138.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-16:11 | 0.00 | 0.00 | 0.00 | -25111.43 | 0.00 | 0.00 | 36.07 | 68.40 | 720.18 | 5093.85 | 0.00 | 1482.44 | 17710.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 | -24795.86 | 0.00 | 0.00 | 18.92 | 44.08 | 464.11 | 14876.83 | 0.00 | 68.60 | 9323.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 13-AUG-15:31 | 0.00 | 0.00 | 0.00 | -28024.38 | 0.00 | 0.00 | 33.80 | 68.40 | 720.19 | 6529.46 | 0.00 | 1256.01 | 19416.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -31023.50 | 0.00 | 0.00 | 12.84 | 44.08 | 464.11 | 15789.28 | 0.00 | 636.95 | 14076.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -8109.80 | 0.00 | 0.00 | 100.85 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -364.20 |
DATACENTER_MID_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -75888.97 | 0.00 | 0.00 | 1008.50 | 5787.18 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8850.94 |
DATACENTER_TOP_ZN_6 | 26-APR-18:20 | 0.00 | 0.00 | 0.00 | -7640.04 | 0.00 | 0.00 | 10.59 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -357.88 |
DATACENTER_BASEMENT_ZN_6 | 23-AUG-22:53 | 0.00 | 0.00 | 0.00 | -387533.29 | 0.00 | 0.00 | 106.19 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 7435.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-AUG-05:15 | 0.00 | -17814.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 17788.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-05:02 | 0.00 | -120057.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120227.77 | 0.00 | -0.00 | 0.00 | -169.96 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:50 | 0.00 | -25790.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.24 | 25128.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-05:02 | 0.00 | -87370.16 | 0.00 | -2131231.38 | 0.00 | 0.00 | 15710.41 | 42872.09 | 616289.16 | 0.00 | 0.00 | 317.88 | 1577542.54 | 0.00 | -34126.17 | 0.00 | -4.37 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-AUG-16:01 | 0.00 | 0.00 | 31370.37 | 0.00 | 0.00 | 0.00 | 520.13 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -46622.96 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:21 | 0.00 | 0.00 | 72121.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -80349.02 |
PERIMETER_BOT_ZN_3 | 07-DEC-06:01 | 0.00 | 0.00 | 6598.86 | 0.00 | 0.00 | 0.00 | 142.82 | 287.56 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6836.68 | 0.00 | -114.53 | -1038.27 |
PERIMETER_BOT_ZN_2 | 07-DEC-06:02 | 0.00 | 0.00 | 5067.60 | 0.00 | 0.00 | 0.00 | 94.15 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4560.30 | 0.00 | -76.27 | -1329.32 |
PERIMETER_BOT_ZN_1 | 07-DEC-06:01 | 0.00 | 0.00 | 9078.46 | 0.00 | 0.00 | 0.00 | 144.23 | 287.56 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6933.62 | 0.00 | -114.05 | -3422.84 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 159465.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44089.15 | 0.00 | -2645.80 | -123061.48 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 131755.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30745.11 | 0.00 | -1835.12 | -105832.86 |
PERIMETER_MID_ZN_1 | 07-DEC-05:01 | 0.00 | 0.00 | 158874.85 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.64 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -68525.54 | 0.00 | -10805.11 | -89875.56 |
PERIMETER_MID_ZN_4 | 07-DEC-05:01 | 0.00 | 0.00 | 119080.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43164.20 | 0.00 | -7044.47 | -75529.85 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:11 | 0.00 | 0.00 | 19622.59 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3883.95 | 0.00 | -509.76 | -16262.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:21 | 0.00 | 0.00 | 16938.79 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2588.99 | 0.00 | -209.18 | -14806.40 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:21 | 0.00 | 0.00 | 20134.78 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4339.77 | 0.00 | -340.52 | -16487.63 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:21 | 0.00 | 0.00 | 16673.46 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2781.50 | 0.00 | -225.17 | -14332.56 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:25 | 0.00 | 0.00 | 5151.50 | 0.00 | 0.00 | 0.00 | 53.08 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25012.16 |
DATACENTER_TOP_ZN_6 | 02-JAN-01:00 | 0.00 | 0.00 | 606.03 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2586.79 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 11605.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -600.83 | -11004.61 |
MIDFLOOR_PLENUM | 27-AUG-16:31 | 98629.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12824.32 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -111453.74 |
TOPFLOOR_PLENUM | 02-JAN-06:13 | 21904.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -166.93 | -21737.78 |
Total Facility | 02-JAN-06:01 | -414240.24 | 419425.05 | 657087.19 | -419425.05 | 0.00 | 0.00 | 20255.98 | 42872.09 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196168.71 | 0.00 | -6025.40 | -365195.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.5687 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2454 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 120.3376 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 105.9952 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.4689 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.9594 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.6792 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.6792 | 0.1797 | 1.0000 | Not calculated | 1.2002 | 0.1797 | ||
AIRLOOP DATACENTER BASEMENT | 23.5714 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.5716 | 0.0144 | 1.0000 | Not calculated | 0.3384 | 0.0144 | ||
AIRLOOP DATACENTER BOT | 0.5272 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5272 | 0.0297 | 1.0000 | Not calculated | 0.0156 | 0.0297 | ||
AIRLOOP DATACENTER MID | 5.0287 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0287 | 0.0311 | 1.0000 | Not calculated | 0.1563 | 0.0311 | ||
AIRLOOP DATACENTER TOP | 0.5142 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5142 | 0.0304 | 1.0000 | Not calculated | 0.0156 | 0.0304 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2844 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1480 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 60.1688 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.8533 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.2344 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2400 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.6792 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.6792 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1797 | ||
AIRLOOP DATACENTER BASEMENT | 23.5714 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.5714 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0144 | ||
AIRLOOP DATACENTER BOT | 0.5272 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5272 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0297 | ||
AIRLOOP DATACENTER MID | 5.0287 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0287 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0311 | ||
AIRLOOP DATACENTER TOP | 0.5142 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5142 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0304 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.6792 | 6.6792 | 6.6792 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8939 | 6.8939 | 2.0130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 65.2481 | 65.2481 | 19.8354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4886 | 6.4886 | 2.0439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3190 | 1.3190 | 0.2638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2680 | 1.2680 | 0.2536 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4697 | 1.4697 | 0.2939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6182 | 1.6182 | 0.3236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.9558 | 12.9558 | 2.5912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2664 | 13.2664 | 2.6533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.3896 | 14.3896 | 2.8779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4776 | 14.4776 | 2.8955 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4649 | 1.4649 | 0.2930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3602 | 1.3602 | 0.2720 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5973 | 1.5973 | 0.3195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5579 | 1.5579 | 0.3116 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5272 | 0.5272 | 0.5272 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0287 | 5.0287 | 5.0287 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5142 | 0.5142 | 0.5142 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.5714 | 23.5714 | 23.5714 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.5687 | 11.2454 | 12.5687 | 3.1480 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 120.3376 | 105.9952 | 120.3376 | 30.8533 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.4689 | 11.9594 | 12.4689 | 3.2400 | 0.0000 | 1.0000 |
CAV_BAS | 6.6792 | 6.6792 | 6.6792 | 6.6792 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.5714 | 23.5716 | 23.5714 | 23.5714 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5272 | 0.5272 | 0.5272 | 0.5272 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0287 | 5.0287 | 5.0287 | 5.0287 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5142 | 0.5142 | 0.5142 | 0.5142 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.6792 | 6.6792 | 6.6792 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4469 | 3.4469 | 2.0130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 32.6241 | 32.6241 | 19.8354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2443 | 3.2443 | 2.0439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6595 | 0.6595 | 0.2638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6340 | 0.6340 | 0.2536 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7348 | 0.7348 | 0.2939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8091 | 0.8091 | 0.3236 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4779 | 6.4779 | 2.5912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6332 | 6.6332 | 2.6533 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1948 | 7.1948 | 2.8779 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2388 | 7.2388 | 2.8955 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7325 | 0.7325 | 0.2930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6801 | 0.6801 | 0.2720 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7986 | 0.7986 | 0.3195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7790 | 0.7790 | 0.3116 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5272 | 0.5272 | 0.5272 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0287 | 5.0287 | 5.0287 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5142 | 0.5142 | 0.5142 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.5714 | 23.5714 | 23.5714 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2844 | 3.1480 | 3.1480 | 3.1480 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 60.1688 | 30.8533 | 30.8533 | 30.8533 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.2344 | 3.2400 | 3.2400 | 3.2400 | 0.0000 | 1.0000 |
CAV_BAS | 6.6792 | 6.6792 | 6.6792 | 6.6792 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.5714 | 23.5714 | 23.5714 | 23.5714 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5272 | 0.5272 | 0.5272 | 0.5272 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0287 | 5.0287 | 5.0287 | 5.0287 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5142 | 0.5142 | 0.5142 | 0.5142 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 1010.83 |
Number of hours not met | 1011.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 104.29 | 498515.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4172.81 | 487904.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3926.16 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 696.14 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2877.99 | 285016.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 655.85 | 56932.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1301.65 | 87736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1611.79 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 674.33 | 77703.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31853.58 |
Natural Gas | 0.00 | 778.62 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32632.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.76 |
Space Heating | 0.00 |
Space Cooling | 90.09 |
Fans (All) | 62.13 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 687.68 |
Subtotal | 687.68 |
Natural Gas [MJ/m2] | |
Space Heating | 2.25 |
Service Water Heating | 14.56 |
Miscellaneous (All) | 16.81 |
Subtotal | 16.81 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.03 |
Space Heating | 0.32 |
Space Cooling | 12.79 |
Fans (All) | 8.82 |
Service Water Heating | 2.07 |
Receptacle Equipment | 44.98 |
Miscellaneous | 19.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8341.83 | 418.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8709.33 | 50.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8703.83 | 56.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8688.50 | 71.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8648.67 | 111.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8397.50 | 362.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8693.83 | 66.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8619.00 | 141.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8596.33 | 163.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8500.17 | 259.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8674.33 | 85.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8605.33 | 154.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8589.50 | 170.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8525.00 | 235.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7607.83 | 1152.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7673.00 | 1087.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7718.83 | 1041.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6621.00 | 2055.33 | 83.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8583.50 | 176.50 | 0.00 | 0.00 | 0.00 |
Min | 6621.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2055.33 | 83.67 | 0.00 | 0.00 |
Average | 8413.36 | 343.01 | 3.64 | 0.00 | 0.00 |
Sum | 193507.17 | 7889.17 | 83.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367491.33 | 1124.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330787.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1708.33 | 559.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1713.17 | 554.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1735.17 | 532.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 74077.33 | 27873.17 | 1444.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367491.33 | 27873.17 | 1444.50 | 0.00 | 0.00 |
Average | 78934.62 | 1337.49 | 62.80 | 0.00 | 0.00 |
Sum | 1815496.33 | 30762.17 | 1444.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8015.17 | 744.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8406.33 | 353.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8439.33 | 320.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8450.33 | 309.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8327.33 | 432.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8476.00 | 284.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8327.17 | 432.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8145.00 | 615.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8277.17 | 482.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8274.17 | 485.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8245.00 | 515.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8229.00 | 531.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8288.83 | 471.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8278.33 | 481.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8255.83 | 504.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8251.00 | 509.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8246.00 | 514.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8277.33 | 482.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8307.00 | 453.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7155.33 | 1600.67 | 4.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8242.50 | 517.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8275.00 | 485.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7856.50 | 903.50 | 0.00 | 0.00 | 0.00 |
Min | 7155.33 | 284.00 | 0.00 | 0.00 | 0.00 |
Max | 8476.00 | 1600.67 | 4.00 | 0.00 | 0.00 |
Average | 8219.38 | 540.45 | 0.17 | 0.00 | 0.00 |
Sum | 189045.67 | 12430.33 | 4.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 365673.50 | 2942.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330103.00 | 710.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330297.00 | 516.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330289.00 | 524.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1938.00 | 330.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1943.00 | 325.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1963.50 | 304.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82696.67 | 20590.33 | 108.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365673.50 | 20590.33 | 108.00 | 0.00 | 0.00 |
Average | 79189.25 | 1140.97 | 4.70 | 0.00 | 0.00 |
Sum | 1821352.67 | 26242.33 | 108.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:44:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609761E+11 | 121672.61 | 23-JAN-05:11 | 6.67 | 5.22 | 0.567035E+10 | 7499.16 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.513758E+11 | 120121.03 | 13-FEB-05:11 | 8.00 | 8.00 | 0.513945E+10 | 7499.34 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.606732E+11 | 121228.48 | 20-MAR-04:12 | 11.83 | 7.65 | 0.613321E+10 | 7499.19 | 14-MAR-09:50 | 11.83 | 7.65 |
April | 0.609507E+11 | 122403.29 | 24-APR-04:11 | 16.33 | 5.24 | 0.545293E+10 | 7499.25 | 04-APR-09:09 | 16.33 | 5.24 |
May | 0.620559E+11 | 120894.17 | 22-MAY-04:12 | 15.00 | 5.49 | 0.590277E+10 | 7499.00 | 11-MAY-09:09 | 15.00 | 5.49 |
June | 0.634368E+11 | 116081.26 | 12-JUN-04:11 | 20.00 | 10.45 | 0.588376E+10 | 7499.09 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.678651E+11 | 116364.30 | 05-JUL-04:11 | 23.00 | 11.56 | 0.547680E+10 | 7499.23 | 21-JUL-09:30 | 31.50 | 21.05 |
August | 0.779795E+11 | 111941.02 | 27-AUG-18:16 | 38.33 | 18.09 | 0.614025E+10 | 7499.07 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.706581E+11 | 113440.74 | 29-SEP-04:12 | 20.53 | 11.28 | 0.545585E+10 | 7499.01 | 22-SEP-09:30 | 20.53 | 11.28 |
October | 0.721161E+11 | 120368.02 | 30-OCT-04:12 | 9.00 | 5.54 | 0.567424E+10 | 7499.14 | 11-OCT-13:20 | 9.00 | 5.54 |
November | 0.687297E+11 | 120027.57 | 06-NOV-05:12 | 7.67 | 2.51 | 0.561836E+10 | 7499.29 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.660106E+11 | 121352.30 | 18-DEC-05:11 | 4.00 | 1.01 | 0.547503E+10 | 7498.96 | 13-DEC-10:20 | 4.00 | 1.01 |
Annual Sum or Average | 0.782828E+12 | 0.680230E+11 | ||||||||
Minimum of Months | 0.513758E+11 | 111941.02 | 4.00 | 1.01 | 0.513945E+10 | 7498.96 | 4.00 | 1.01 | ||
Maximum of Months | 0.779795E+11 | 122403.29 | 38.33 | 18.09 | 0.614025E+10 | 7499.34 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503890E+11 | 96878.04 | 09-JAN-05:12 | 9.33 | 9.33 | 0.507614E+10 | 6734.83 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.449459E+11 | 96592.02 | 21-FEB-05:12 | 9.33 | 8.41 | 0.460641E+10 | 6735.13 | 15-FEB-14:00 | 9.33 | 8.41 |
March | 0.584155E+11 | 99235.40 | 20-MAR-04:12 | 11.83 | 7.65 | 0.550058E+10 | 6734.86 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.704509E+11 | 96535.19 | 27-APR-04:12 | 12.67 | 8.11 | 0.487873E+10 | 6734.83 | 10-APR-09:09 | 12.67 | 8.11 |
May | 0.631929E+11 | 100533.47 | 30-MAY-04:13 | 18.00 | 9.08 | 0.528493E+10 | 6734.74 | 12-MAY-09:09 | 18.00 | 9.08 |
June | 0.713263E+11 | 99829.03 | 12-JUN-04:13 | 20.00 | 10.45 | 0.526516E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.739575E+11 | 92738.58 | 05-JUL-05:03 | 23.00 | 11.31 | 0.489377E+10 | 6734.85 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.844357E+11 | 93995.55 | 14-AUG-05:05 | 26.00 | 16.58 | 0.549661E+10 | 6747.88 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.628168E+11 | 97141.20 | 21-SEP-04:13 | 21.07 | 16.97 | 0.488344E+10 | 6734.77 | 15-SEP-09:09 | 21.07 | 16.97 |
October | 0.613076E+11 | 102075.22 | 23-OCT-04:12 | 11.00 | 9.66 | 0.508027E+10 | 6734.81 | 03-OCT-13:30 | 11.00 | 9.66 |
November | 0.573235E+11 | 102931.32 | 13-NOV-05:11 | 17.00 | 17.00 | 0.503141E+10 | 6735.01 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.554138E+11 | 102291.63 | 04-DEC-05:11 | 3.00 | 0.78 | 0.490339E+10 | 6734.72 | 13-DEC-10:09 | 11.33 | 10.45 |
Annual Sum or Average | 0.753975E+12 | 0.609008E+11 | ||||||||
Minimum of Months | 0.449459E+11 | 92738.58 | 3.00 | 0.78 | 0.460641E+10 | 6734.72 | 9.33 | 7.65 | ||
Maximum of Months | 0.844357E+11 | 102931.32 | 26.00 | 17.00 | 0.550058E+10 | 6747.88 | 37.50 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375232E+11 | 84184.78 | 20-JAN-06:02 | 9.27 | 4.95 | 0.502341E+10 | 6734.75 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.324806E+11 | 83899.23 | 01-FEB-06:02 | 5.00 | 3.59 | 0.456958E+10 | 6735.04 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.419856E+11 | 85771.34 | 20-MAR-04:12 | 11.83 | 7.65 | 0.547907E+10 | 6734.83 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.487900E+11 | 88189.39 | 14-APR-04:12 | 17.00 | 6.15 | 0.487323E+10 | 6734.83 | 04-APR-09:09 | 17.00 | 6.15 |
May | 0.544435E+11 | 88717.11 | 19-MAY-04:12 | 17.67 | 8.89 | 0.528124E+10 | 6734.74 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.586086E+11 | 87532.78 | 21-JUN-04:12 | 18.67 | 8.59 | 0.526217E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.564052E+11 | 89629.82 | 27-JUL-04:12 | 22.00 | 18.54 | 0.489017E+10 | 6734.85 | 05-JUL-09:09 | 22.00 | 18.54 |
August | 0.589420E+11 | 87783.62 | 30-AUG-04:12 | 22.67 | 17.96 | 0.549279E+10 | 6734.84 | 28-AUG-09:20 | 22.67 | 17.96 |
September | 0.520576E+11 | 89404.86 | 26-SEP-04:12 | 20.00 | 15.92 | 0.488040E+10 | 6734.76 | 15-SEP-09:09 | 20.00 | 15.92 |
October | 0.470192E+11 | 89444.03 | 05-OCT-04:12 | 19.67 | 13.65 | 0.506769E+10 | 6734.83 | 03-OCT-13:39 | 19.67 | 13.65 |
November | 0.394205E+11 | 89242.89 | 13-NOV-05:11 | 17.00 | 17.00 | 0.500666E+10 | 6734.96 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.346709E+11 | 81695.84 | 01-DEC-06:02 | 8.83 | 4.30 | 0.484697E+10 | 6734.73 | 13-DEC-10:09 | 11.33 | 10.45 |
Annual Sum or Average | 0.562347E+12 | 0.606734E+11 | ||||||||
Minimum of Months | 0.324806E+11 | 81695.84 | 5.00 | 3.59 | 0.456958E+10 | 6734.73 | 11.33 | 6.15 | ||
Maximum of Months | 0.589420E+11 | 89629.82 | 22.67 | 18.54 | 0.549279E+10 | 6735.04 | 33.17 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309387E+11 | 40989.61 | 27-JAN-17:00 | 26.00 | 9.22 | 0.485409E+10 | 6734.68 | 20-JAN-10:39 | 26.00 | 9.22 |
February | 0.262701E+11 | 39045.11 | 22-FEB-17:00 | 20.00 | 11.26 | 0.439703E+10 | 6734.93 | 15-FEB-14:00 | 20.00 | 11.26 |
March | 0.360445E+11 | 81743.51 | 17-MAR-05:03 | 13.48 | 9.60 | 0.536764E+10 | 6734.80 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.491617E+11 | 86338.94 | 26-APR-04:12 | 20.00 | 10.45 | 0.485912E+10 | 6734.81 | 13-APR-09:09 | 20.00 | 10.45 |
May | 0.570873E+11 | 87510.71 | 25-MAY-04:12 | 20.00 | 8.60 | 0.528011E+10 | 6734.73 | 12-MAY-09:09 | 20.00 | 8.60 |
June | 0.659455E+11 | 87798.02 | 21-JUN-04:12 | 18.67 | 8.59 | 0.526541E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.634252E+11 | 92673.05 | 05-JUL-04:13 | 23.00 | 11.56 | 0.489411E+10 | 6734.85 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.646464E+11 | 88151.86 | 25-AUG-05:03 | 21.83 | 9.65 | 0.549516E+10 | 6734.84 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.553317E+11 | 89152.38 | 14-SEP-04:12 | 20.73 | 17.20 | 0.488194E+10 | 6734.74 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.433474E+11 | 88347.55 | 04-OCT-04:12 | 21.00 | 17.09 | 0.502236E+10 | 6734.78 | 03-OCT-13:30 | 21.00 | 17.09 |
November | 0.327666E+11 | 81941.23 | 03-NOV-05:03 | 16.00 | 12.46 | 0.487868E+10 | 6734.91 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.264327E+11 | 38950.36 | 22-DEC-17:00 | 24.00 | 9.52 | 0.455653E+10 | 6734.56 | 12-DEC-14:00 | 24.00 | 9.52 |
Annual Sum or Average | 0.551398E+12 | 0.597522E+11 | ||||||||
Minimum of Months | 0.262701E+11 | 38950.36 | 13.48 | 8.59 | 0.439703E+10 | 6734.56 | 18.00 | 8.60 | ||
Maximum of Months | 0.659455E+11 | 92673.05 | 26.00 | 17.20 | 0.549516E+10 | 6734.93 | 33.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421791E+10 | 5591.36 | 31-JAN-16:30 | 29.00 | 10.73 | 0.615574E+09 | 845.63 | 23-JAN-14:09 | 29.00 | 10.73 |
February | 0.355106E+10 | 5339.26 | 22-FEB-14:00 | 21.00 | 12.01 | 0.557899E+09 | 845.66 | 15-FEB-14:00 | 21.00 | 12.01 |
March | 0.555357E+10 | 7758.74 | 20-MAR-14:00 | 27.70 | 14.42 | 0.676617E+09 | 845.64 | 17-MAR-09:00 | 27.70 | 14.42 |
April | 0.975807E+10 | 14782.05 | 15-APR-05:02 | 20.83 | 11.87 | 0.611678E+09 | 845.63 | 27-APR-13:39 | 25.33 | 11.96 |
May | 0.105595E+11 | 20143.82 | 29-MAY-18:51 | 30.00 | 13.63 | 0.664245E+09 | 845.63 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.148876E+11 | 21715.70 | 25-JUN-18:01 | 37.67 | 14.86 | 0.662954E+09 | 845.64 | 19-JUN-13:09 | 37.67 | 14.86 |
July | 0.143442E+11 | 21734.31 | 16-JUL-17:41 | 36.17 | 21.47 | 0.616509E+09 | 845.64 | 05-JUL-09:09 | 36.17 | 21.47 |
August | 0.150011E+11 | 21688.09 | 27-AUG-15:41 | 40.00 | 18.27 | 0.691311E+09 | 847.76 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.106399E+11 | 20430.72 | 10-SEP-14:41 | 35.92 | 19.69 | 0.613980E+09 | 845.63 | 22-SEP-09:00 | 25.00 | 17.32 |
October | 0.721942E+10 | 15696.36 | 02-OCT-05:02 | 25.83 | 16.98 | 0.631840E+09 | 845.66 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.510278E+10 | 7458.42 | 02-NOV-13:30 | 26.50 | 15.49 | 0.620272E+09 | 845.65 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.399072E+10 | 5548.52 | 26-DEC-15:40 | 23.00 | 10.62 | 0.588796E+09 | 845.61 | 12-DEC-14:00 | 23.00 | 10.62 |
Annual Sum or Average | 0.104826E+12 | 0.755168E+10 | ||||||||
Minimum of Months | 0.355106E+10 | 5339.26 | 20.83 | 10.62 | 0.557899E+09 | 845.61 | 18.00 | 10.62 | ||
Maximum of Months | 0.150011E+11 | 21734.31 | 40.00 | 21.47 | 0.691311E+09 | 847.76 | 37.67 | 21.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449676E+10 | 7450.08 | 17-JAN-09:30 | 16.50 | 6.15 | 0.402032E+09 | 544.96 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.368042E+10 | 7564.77 | 23-FEB-09:20 | 13.33 | 10.50 | 0.361850E+09 | 544.97 | 15-FEB-14:00 | 13.33 | 10.50 |
March | 0.539695E+10 | 8944.97 | 31-MAR-09:10 | 15.37 | 6.29 | 0.437317E+09 | 544.97 | 16-MAR-09:00 | 15.37 | 6.29 |
April | 0.956096E+10 | 18950.99 | 23-APR-08:32 | 24.00 | 8.96 | 0.394258E+09 | 544.99 | 11-APR-09:09 | 24.00 | 8.96 |
May | 0.106415E+11 | 21965.00 | 29-MAY-09:31 | 27.33 | 12.10 | 0.428523E+09 | 545.63 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.133645E+11 | 21865.65 | 18-JUN-07:21 | 29.50 | 16.76 | 0.427249E+09 | 545.68 | 08-JUN-09:00 | 29.50 | 16.76 |
July | 0.123756E+11 | 21016.86 | 02-JUL-08:22 | 27.55 | 10.52 | 0.397168E+09 | 545.69 | 03-JUL-09:00 | 33.00 | 12.96 |
August | 0.125145E+11 | 21851.89 | 27-AUG-08:21 | 31.00 | 15.05 | 0.445164E+09 | 546.61 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.942664E+10 | 21382.58 | 04-SEP-09:32 | 26.07 | 22.03 | 0.395549E+09 | 546.27 | 08-SEP-09:50 | 31.83 | 20.94 |
October | 0.720287E+10 | 18051.35 | 15-OCT-10:42 | 27.67 | 11.16 | 0.407950E+09 | 544.98 | 17-OCT-09:39 | 25.33 | 10.15 |
November | 0.480993E+10 | 8314.33 | 10-NOV-09:00 | 21.00 | 9.10 | 0.400524E+09 | 544.98 | 22-NOV-10:50 | 20.00 | 11.34 |
December | 0.376254E+10 | 6496.23 | 26-DEC-09:50 | 17.17 | 7.64 | 0.381277E+09 | 544.95 | 13-DEC-10:09 | 17.17 | 7.64 |
Annual Sum or Average | 0.972331E+11 | 0.487886E+10 | ||||||||
Minimum of Months | 0.368042E+10 | 6496.23 | 13.33 | 6.15 | 0.361850E+09 | 544.95 | 13.33 | 6.29 | ||
Maximum of Months | 0.133645E+11 | 21965.00 | 31.00 | 22.03 | 0.445164E+09 | 546.61 | 33.00 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128531E+11 | 25772.82 | 29-JAN-13:11 | 24.00 | 9.48 | 0.631366E+09 | 875.49 | 17-JAN-14:20 | 24.00 | 9.48 |
February | 0.769792E+10 | 16830.85 | 28-FEB-13:40 | 17.67 | 7.95 | 0.566710E+09 | 847.26 | 23-FEB-14:50 | 17.67 | 7.95 |
March | 0.921603E+10 | 15001.95 | 23-MAR-13:40 | 25.33 | 11.79 | 0.678281E+09 | 846.17 | 22-MAR-13:09 | 25.33 | 11.79 |
April | 0.133268E+11 | 23024.16 | 02-APR-12:43 | 29.83 | 12.23 | 0.611973E+09 | 847.62 | 25-APR-13:20 | 31.00 | 14.70 |
May | 0.115200E+11 | 22262.86 | 21-MAY-14:51 | 32.00 | 13.37 | 0.663994E+09 | 845.65 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.144793E+11 | 23192.11 | 25-JUN-16:01 | 38.00 | 15.02 | 0.662600E+09 | 845.66 | 19-JUN-13:09 | 38.00 | 15.02 |
July | 0.147479E+11 | 23894.36 | 16-JUL-15:41 | 36.33 | 19.76 | 0.616338E+09 | 846.16 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.172431E+11 | 25095.12 | 27-AUG-15:01 | 40.00 | 18.27 | 0.691498E+09 | 848.50 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.147297E+11 | 24791.82 | 04-SEP-13:32 | 30.73 | 21.73 | 0.614939E+09 | 885.92 | 28-SEP-13:39 | 36.47 | 16.05 |
October | 0.143187E+11 | 26040.89 | 15-OCT-12:41 | 30.00 | 12.08 | 0.636841E+09 | 884.76 | 02-OCT-13:09 | 30.00 | 12.08 |
November | 0.123817E+11 | 25322.62 | 19-NOV-13:02 | 26.00 | 10.94 | 0.628991E+09 | 887.39 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.113475E+11 | 25006.05 | 10-DEC-13:32 | 21.00 | 8.00 | 0.606452E+09 | 866.84 | 22-DEC-14:09 | 25.17 | 10.15 |
Annual Sum or Average | 0.153862E+12 | 0.760999E+10 | ||||||||
Minimum of Months | 0.769792E+10 | 15001.95 | 17.67 | 7.95 | 0.566710E+09 | 845.65 | 17.67 | 7.95 | ||
Maximum of Months | 0.172431E+11 | 26040.89 | 40.00 | 21.73 | 0.691498E+09 | 887.39 | 38.00 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639065E+10 | 25981.75 | 29-JAN-16:32 | 24.33 | 9.38 | 0.398538E+09 | 544.97 | 30-JAN-14:50 | 24.83 | 9.61 |
February | 0.536085E+10 | 16713.71 | 20-FEB-16:32 | 17.33 | 9.62 | 0.365091E+09 | 545.00 | 15-FEB-14:00 | 17.33 | 9.62 |
March | 0.856637E+10 | 19990.10 | 26-MAR-16:02 | 18.30 | 6.21 | 0.442776E+09 | 544.97 | 09-MAR-14:00 | 18.30 | 6.21 |
April | 0.157506E+11 | 27837.06 | 02-APR-16:41 | 31.00 | 12.54 | 0.396456E+09 | 544.97 | 27-APR-13:39 | 25.33 | 11.96 |
May | 0.126387E+11 | 29420.13 | 21-MAY-16:51 | 32.00 | 13.36 | 0.428764E+09 | 544.96 | 12-MAY-09:09 | 32.00 | 13.36 |
June | 0.169160E+11 | 30966.16 | 25-JUN-17:21 | 38.00 | 15.15 | 0.427613E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.15 |
July | 0.163024E+11 | 31152.38 | 16-JUL-17:01 | 36.83 | 20.98 | 0.397978E+09 | 544.97 | 05-JUL-09:09 | 36.83 | 20.98 |
August | 0.198487E+11 | 32769.89 | 27-AUG-16:21 | 40.00 | 18.07 | 0.446617E+09 | 546.79 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.113445E+11 | 28483.98 | 04-SEP-15:31 | 31.60 | 21.45 | 0.396150E+09 | 544.96 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.973744E+10 | 27396.11 | 15-OCT-14:41 | 31.00 | 12.59 | 0.410047E+09 | 544.98 | 03-OCT-13:30 | 31.00 | 12.59 |
November | 0.823183E+10 | 26612.49 | 19-NOV-15:02 | 27.00 | 11.51 | 0.405688E+09 | 544.99 | 27-NOV-14:39 | 24.97 | 9.27 |
December | 0.730696E+10 | 25710.10 | 25-DEC-16:22 | 25.00 | 11.60 | 0.393268E+09 | 544.95 | 12-DEC-14:00 | 25.00 | 11.60 |
Annual Sum or Average | 0.138395E+12 | 0.490899E+10 | ||||||||
Minimum of Months | 0.536085E+10 | 16713.71 | 17.33 | 6.21 | 0.365091E+09 | 544.95 | 17.33 | 6.21 | ||
Maximum of Months | 0.198487E+11 | 32769.89 | 40.00 | 21.45 | 0.446617E+09 | 546.79 | 38.00 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295143E+10 | 4064.98 | 31-JAN-17:00 | 29.00 | 10.73 | 0.561092E+09 | 845.60 | 06-JAN-14:00 | 29.00 | 10.73 |
February | 0.235241E+10 | 3126.95 | 22-FEB-16:10 | 20.83 | 11.61 | 0.504960E+09 | 845.59 | 15-FEB-14:00 | 20.83 | 11.61 |
March | 0.361784E+10 | 5995.11 | 16-MAR-16:00 | 28.80 | 13.95 | 0.636943E+09 | 845.63 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.677900E+10 | 12292.63 | 25-APR-05:03 | 22.00 | 11.73 | 0.605883E+09 | 845.63 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.943162E+10 | 19675.04 | 21-MAY-18:11 | 30.33 | 12.75 | 0.663607E+09 | 845.63 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.135890E+11 | 21105.18 | 04-JUN-17:21 | 37.50 | 15.81 | 0.663104E+09 | 845.64 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.122851E+11 | 21440.16 | 16-JUL-17:31 | 36.33 | 21.35 | 0.616686E+09 | 845.64 | 05-JUL-09:09 | 36.33 | 21.35 |
August | 0.116261E+11 | 21421.16 | 13-AUG-16:11 | 38.00 | 20.37 | 0.691167E+09 | 845.64 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.927383E+10 | 18191.53 | 17-SEP-12:43 | 34.90 | 18.23 | 0.613495E+09 | 845.62 | 19-SEP-09:09 | 28.77 | 14.28 |
October | 0.545996E+10 | 14835.96 | 02-OCT-05:02 | 25.83 | 16.98 | 0.612079E+09 | 845.65 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.323210E+10 | 5904.89 | 02-NOV-14:00 | 27.00 | 15.44 | 0.579298E+09 | 845.64 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.229057E+10 | 3137.41 | 22-DEC-15:40 | 25.33 | 10.21 | 0.511046E+09 | 817.62 | 22-DEC-14:00 | 25.33 | 10.21 |
Annual Sum or Average | 0.828890E+11 | 0.725936E+10 | ||||||||
Minimum of Months | 0.229057E+10 | 3126.95 | 20.83 | 10.21 | 0.504960E+09 | 817.62 | 18.00 | 9.85 | ||
Maximum of Months | 0.135890E+11 | 21440.16 | 38.00 | 21.35 | 0.691167E+09 | 845.65 | 38.17 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352687E+10 | 5753.30 | 27-JAN-10:00 | 20.00 | 7.78 | 0.280398E+09 | 521.20 | 31-JAN-11:09 | 18.83 | 8.01 |
February | 0.278076E+10 | 6420.54 | 23-FEB-10:00 | 14.00 | 11.11 | 0.252416E+09 | 521.21 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.435211E+10 | 8033.82 | 23-MAR-10:10 | 21.97 | 10.49 | 0.309958E+09 | 521.22 | 16-MAR-10:09 | 21.97 | 10.49 |
April | 0.852936E+10 | 22046.63 | 23-APR-10:22 | 28.00 | 10.51 | 0.289913E+09 | 521.23 | 18-APR-10:50 | 28.00 | 10.51 |
May | 0.105598E+11 | 23119.09 | 21-MAY-09:31 | 28.33 | 11.86 | 0.315403E+09 | 521.30 | 10-MAY-08:50 | 28.33 | 11.86 |
June | 0.133326E+11 | 23131.14 | 04-JUN-08:61 | 29.33 | 15.80 | 0.314380E+09 | 522.56 | 08-JUN-10:30 | 35.00 | 15.24 |
July | 0.119318E+11 | 23772.19 | 04-JUL-09:31 | 31.33 | 14.72 | 0.293453E+09 | 522.20 | 10-JUL-10:30 | 35.00 | 18.96 |
August | 0.116737E+11 | 24079.45 | 13-AUG-08:51 | 32.00 | 20.88 | 0.327593E+09 | 522.23 | 18-AUG-10:30 | 35.50 | 21.64 |
September | 0.896696E+10 | 20671.81 | 10-SEP-10:12 | 32.17 | 19.22 | 0.291288E+09 | 521.23 | 22-SEP-10:09 | 25.37 | 17.42 |
October | 0.638439E+10 | 20777.96 | 15-OCT-09:12 | 24.67 | 10.00 | 0.296396E+09 | 521.22 | 02-OCT-14:30 | 24.67 | 10.00 |
November | 0.373825E+10 | 7106.57 | 10-NOV-09:30 | 22.00 | 9.55 | 0.283980E+09 | 521.23 | 10-NOV-16:00 | 22.00 | 13.28 |
December | 0.271971E+10 | 4082.99 | 27-DEC-10:00 | 14.00 | 6.80 | 0.255856E+09 | 521.20 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.884962E+11 | 0.351103E+10 | ||||||||
Minimum of Months | 0.271971E+10 | 4082.99 | 14.00 | 6.80 | 0.252416E+09 | 521.20 | 14.00 | 8.01 | ||
Maximum of Months | 0.133326E+11 | 24079.45 | 32.17 | 20.88 | 0.327593E+09 | 522.56 | 35.50 | 21.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122908E+11 | 24942.64 | 15-JAN-14:32 | 23.00 | 10.38 | 0.626104E+09 | 894.91 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.678599E+10 | 22430.40 | 26-FEB-12:02 | 16.00 | 10.32 | 0.554648E+09 | 846.91 | 23-FEB-14:00 | 16.00 | 10.32 |
March | 0.755594E+10 | 14577.20 | 23-MAR-13:50 | 25.42 | 11.73 | 0.663570E+09 | 845.94 | 16-MAR-13:00 | 25.42 | 11.73 |
April | 0.106484E+11 | 22532.32 | 23-APR-14:21 | 33.50 | 12.73 | 0.608507E+09 | 846.58 | 25-APR-13:09 | 31.00 | 14.74 |
May | 0.105575E+11 | 22000.90 | 21-MAY-16:51 | 32.00 | 13.36 | 0.663114E+09 | 845.65 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.130570E+11 | 23180.23 | 04-JUN-15:21 | 38.00 | 16.25 | 0.662719E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.126456E+11 | 23431.87 | 16-JUL-16:51 | 37.00 | 20.84 | 0.616533E+09 | 846.03 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.140537E+11 | 24403.62 | 13-AUG-15:31 | 38.00 | 20.90 | 0.691512E+09 | 846.92 | 31-AUG-13:00 | 36.00 | 18.40 |
September | 0.137582E+11 | 23726.00 | 10-SEP-13:32 | 34.80 | 19.48 | 0.615141E+09 | 909.31 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.132801E+11 | 25742.86 | 15-OCT-12:31 | 30.00 | 12.08 | 0.633568E+09 | 897.41 | 31-OCT-13:00 | 27.00 | 12.18 |
November | 0.111082E+11 | 24995.61 | 19-NOV-13:12 | 26.00 | 10.98 | 0.623057E+09 | 893.38 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.985249E+10 | 24941.88 | 03-DEC-13:52 | 21.00 | 10.84 | 0.594451E+09 | 874.68 | 22-DEC-14:09 | 25.17 | 10.15 |
Annual Sum or Average | 0.135594E+12 | 0.755292E+10 | ||||||||
Minimum of Months | 0.678599E+10 | 14577.20 | 16.00 | 10.32 | 0.554648E+09 | 845.65 | 16.00 | 9.55 | ||
Maximum of Months | 0.140537E+11 | 25742.86 | 38.00 | 20.90 | 0.691512E+09 | 909.31 | 38.17 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439986E+10 | 12586.01 | 29-JAN-16:42 | 24.17 | 9.36 | 0.364977E+09 | 544.95 | 17-JAN-14:39 | 24.17 | 9.36 |
February | 0.316443E+10 | 10630.25 | 22-FEB-16:30 | 20.50 | 11.47 | 0.325774E+09 | 544.97 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.478169E+10 | 16069.79 | 18-MAR-17:05 | 26.92 | 12.85 | 0.406806E+09 | 544.96 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.914554E+10 | 24562.53 | 23-APR-16:21 | 33.15 | 12.72 | 0.390835E+09 | 544.96 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.106826E+11 | 26664.69 | 21-MAY-16:51 | 32.00 | 13.36 | 0.427408E+09 | 544.96 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.136592E+11 | 27695.42 | 04-JUN-16:41 | 38.00 | 16.06 | 0.427414E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.114567E+11 | 27579.66 | 16-JUL-16:51 | 37.00 | 20.84 | 0.397471E+09 | 544.97 | 05-JUL-09:09 | 37.00 | 20.84 |
August | 0.116115E+11 | 28165.84 | 13-AUG-16:51 | 38.00 | 19.94 | 0.445575E+09 | 544.96 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.893882E+10 | 23352.17 | 04-SEP-15:42 | 31.60 | 21.45 | 0.395103E+09 | 544.95 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.661032E+10 | 23620.52 | 15-OCT-15:51 | 31.00 | 12.59 | 0.392561E+09 | 544.98 | 03-OCT-13:39 | 31.00 | 12.59 |
November | 0.462172E+10 | 17284.69 | 19-NOV-15:12 | 27.00 | 11.55 | 0.374627E+09 | 544.97 | 16-NOV-14:09 | 27.00 | 11.55 |
December | 0.333041E+10 | 10467.84 | 22-DEC-16:30 | 24.50 | 9.81 | 0.340159E+09 | 544.93 | 19-DEC-14:00 | 24.50 | 9.81 |
Annual Sum or Average | 0.924028E+11 | 0.468871E+10 | ||||||||
Minimum of Months | 0.316443E+10 | 10467.84 | 20.50 | 9.36 | 0.325774E+09 | 544.93 | 20.50 | 9.36 | ||
Maximum of Months | 0.136592E+11 | 28165.84 | 38.00 | 21.45 | 0.445575E+09 | 544.98 | 38.17 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263616E+10 | 3894.72 | 31-JAN-17:00 | 29.00 | 10.73 | 0.532316E+09 | 845.26 | 27-JAN-14:00 | 29.00 | 10.73 |
February | 0.199540E+10 | 2982.94 | 22-FEB-16:30 | 20.50 | 11.47 | 0.475203E+09 | 841.22 | 22-FEB-14:00 | 20.50 | 11.47 |
March | 0.340236E+10 | 6432.67 | 16-MAR-16:00 | 28.80 | 13.95 | 0.607846E+09 | 845.63 | 23-MAR-13:09 | 25.08 | 11.95 |
April | 0.706311E+10 | 14078.02 | 30-APR-16:11 | 32.67 | 11.91 | 0.598405E+09 | 845.63 | 12-APR-09:00 | 32.67 | 11.91 |
May | 0.997641E+10 | 20986.82 | 07-MAY-17:21 | 35.50 | 14.16 | 0.662216E+09 | 845.63 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.148965E+11 | 24719.03 | 04-JUN-17:21 | 37.50 | 15.81 | 0.663104E+09 | 845.64 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.135338E+11 | 23681.98 | 23-JUL-13:32 | 33.00 | 20.93 | 0.616651E+09 | 845.64 | 05-JUL-09:09 | 33.00 | 20.93 |
August | 0.126133E+11 | 25115.75 | 13-AUG-16:11 | 38.00 | 20.37 | 0.690954E+09 | 845.64 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.987931E+10 | 21233.72 | 17-SEP-12:43 | 34.90 | 18.23 | 0.612546E+09 | 845.62 | 19-SEP-13:09 | 35.50 | 16.58 |
October | 0.540328E+10 | 17525.20 | 02-OCT-05:02 | 25.83 | 16.98 | 0.594316E+09 | 845.65 | 03-OCT-13:20 | 33.00 | 20.21 |
November | 0.289051E+10 | 6149.72 | 01-NOV-15:30 | 28.50 | 15.96 | 0.551950E+09 | 845.61 | 02-NOV-13:09 | 26.17 | 15.52 |
December | 0.176913E+10 | 3228.07 | 22-DEC-13:30 | 24.50 | 10.03 | 0.483159E+09 | 802.72 | 22-DEC-16:00 | 24.00 | 9.52 |
Annual Sum or Average | 0.860593E+11 | 0.708866E+10 | ||||||||
Minimum of Months | 0.176913E+10 | 2982.94 | 20.50 | 10.03 | 0.475203E+09 | 802.72 | 20.50 | 9.52 | ||
Maximum of Months | 0.148965E+11 | 25115.75 | 38.00 | 20.93 | 0.690954E+09 | 845.65 | 38.17 | 20.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303651E+10 | 4756.29 | 27-JAN-10:30 | 21.00 | 7.83 | 0.376671E+09 | 544.94 | 27-JAN-14:09 | 27.00 | 9.95 |
February | 0.232939E+10 | 5394.57 | 23-FEB-10:20 | 14.67 | 11.08 | 0.335526E+09 | 544.95 | 23-FEB-10:09 | 14.67 | 11.08 |
March | 0.396785E+10 | 7379.38 | 23-MAR-10:20 | 22.33 | 10.61 | 0.417400E+09 | 544.96 | 23-MAR-13:09 | 25.08 | 11.95 |
April | 0.868344E+10 | 20440.19 | 30-APR-09:32 | 27.00 | 10.05 | 0.393505E+09 | 544.99 | 11-APR-09:09 | 27.00 | 10.05 |
May | 0.109788E+11 | 22546.08 | 14-MAY-09:42 | 27.72 | 10.39 | 0.428384E+09 | 545.55 | 17-MAY-09:00 | 30.00 | 11.77 |
June | 0.143355E+11 | 23777.23 | 04-JUN-08:61 | 29.33 | 15.80 | 0.427614E+09 | 545.55 | 08-JUN-09:00 | 34.00 | 15.03 |
July | 0.128763E+11 | 24557.77 | 23-JUL-09:31 | 32.67 | 22.21 | 0.397782E+09 | 545.46 | 05-JUL-09:00 | 32.67 | 22.21 |
August | 0.124785E+11 | 24801.05 | 13-AUG-08:51 | 32.00 | 20.88 | 0.445695E+09 | 545.51 | 15-AUG-09:00 | 33.00 | 19.72 |
September | 0.948542E+10 | 21325.20 | 10-SEP-10:12 | 32.17 | 19.22 | 0.395361E+09 | 545.93 | 08-SEP-09:50 | 32.17 | 19.22 |
October | 0.617817E+10 | 16746.30 | 15-OCT-09:32 | 25.33 | 10.24 | 0.401162E+09 | 544.99 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.326882E+10 | 6357.57 | 01-NOV-10:00 | 23.00 | 16.02 | 0.380789E+09 | 544.98 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.220634E+10 | 3142.54 | 22-DEC-13:30 | 24.50 | 10.03 | 0.334500E+09 | 544.93 | 01-DEC-10:00 | 24.50 | 10.03 |
Annual Sum or Average | 0.898250E+11 | 0.473439E+10 | ||||||||
Minimum of Months | 0.220634E+10 | 3142.54 | 14.67 | 7.83 | 0.334500E+09 | 544.93 | 14.67 | 9.95 | ||
Maximum of Months | 0.143355E+11 | 24801.05 | 32.67 | 22.21 | 0.445695E+09 | 545.93 | 34.00 | 22.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111029E+11 | 27850.45 | 29-JAN-14:21 | 24.00 | 9.34 | 0.611783E+09 | 849.11 | 24-JAN-14:50 | 24.00 | 9.34 |
February | 0.587431E+10 | 19289.17 | 26-FEB-14:32 | 17.00 | 9.86 | 0.537178E+09 | 846.59 | 23-FEB-14:50 | 17.00 | 9.86 |
March | 0.690688E+10 | 14696.96 | 16-MAR-13:30 | 27.45 | 13.00 | 0.644963E+09 | 845.69 | 10-MAR-14:00 | 27.45 | 13.00 |
April | 0.109139E+11 | 24971.85 | 30-APR-14:12 | 33.67 | 12.25 | 0.602624E+09 | 846.20 | 12-APR-13:00 | 33.67 | 12.25 |
May | 0.111306E+11 | 24173.81 | 14-MAY-15:41 | 34.00 | 13.09 | 0.660948E+09 | 845.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.143421E+11 | 26710.25 | 04-JUN-15:21 | 38.00 | 16.25 | 0.662571E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.138992E+11 | 26223.91 | 23-JUL-13:32 | 33.00 | 20.93 | 0.616388E+09 | 846.10 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.150954E+11 | 28029.09 | 13-AUG-15:31 | 38.00 | 20.90 | 0.691172E+09 | 846.62 | 31-AUG-13:50 | 35.83 | 18.40 |
September | 0.144429E+11 | 26425.47 | 10-SEP-13:32 | 34.80 | 19.48 | 0.614076E+09 | 885.52 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.128945E+11 | 26482.87 | 09-OCT-13:52 | 32.00 | 17.25 | 0.623676E+09 | 873.79 | 02-OCT-13:09 | 32.00 | 17.25 |
November | 0.100399E+11 | 25109.78 | 19-NOV-14:42 | 26.83 | 11.41 | 0.610624E+09 | 863.80 | 01-NOV-13:00 | 26.83 | 11.41 |
December | 0.835342E+10 | 25895.71 | 25-DEC-13:42 | 25.83 | 11.94 | 0.577609E+09 | 846.08 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.134996E+12 | 0.745361E+10 | ||||||||
Minimum of Months | 0.587431E+10 | 14696.96 | 17.00 | 9.34 | 0.537178E+09 | 845.64 | 17.00 | 9.12 | ||
Maximum of Months | 0.150954E+11 | 28029.09 | 38.00 | 20.93 | 0.691172E+09 | 885.52 | 38.17 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396885E+10 | 14289.84 | 29-JAN-16:22 | 24.50 | 9.40 | 0.353265E+09 | 544.94 | 06-JAN-14:00 | 24.50 | 9.40 |
February | 0.277090E+10 | 10583.04 | 22-FEB-16:30 | 20.50 | 11.47 | 0.313385E+09 | 544.92 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.448446E+10 | 16495.92 | 18-MAR-17:05 | 26.92 | 12.85 | 0.392370E+09 | 544.97 | 10-MAR-14:00 | 26.92 | 12.85 |
April | 0.933332E+10 | 25953.69 | 23-APR-16:31 | 33.10 | 12.69 | 0.385980E+09 | 544.96 | 27-APR-13:00 | 26.00 | 12.23 |
May | 0.110816E+11 | 27818.46 | 14-MAY-16:21 | 33.50 | 12.85 | 0.425729E+09 | 544.95 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.145665E+11 | 30513.30 | 04-JUN-16:41 | 38.00 | 16.06 | 0.427312E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.123144E+11 | 27264.81 | 30-JUL-17:31 | 38.00 | 19.05 | 0.397292E+09 | 544.97 | 05-JUL-09:09 | 38.00 | 19.05 |
August | 0.123070E+11 | 31032.00 | 13-AUG-16:51 | 38.00 | 19.94 | 0.445221E+09 | 544.96 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.940220E+10 | 25147.27 | 04-SEP-15:42 | 31.60 | 21.45 | 0.393954E+09 | 544.95 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.647082E+10 | 24579.66 | 15-OCT-16:12 | 30.67 | 12.42 | 0.383896E+09 | 544.98 | 03-OCT-13:20 | 30.67 | 12.42 |
November | 0.421433E+10 | 12717.63 | 01-NOV-16:00 | 28.00 | 15.72 | 0.363013E+09 | 544.96 | 16-NOV-14:39 | 18.00 | 12.04 |
December | 0.279275E+10 | 10417.89 | 22-DEC-16:30 | 24.50 | 9.81 | 0.328781E+09 | 544.94 | 22-DEC-14:39 | 24.50 | 9.81 |
Annual Sum or Average | 0.937071E+11 | 0.461020E+10 | ||||||||
Minimum of Months | 0.277090E+10 | 10417.89 | 20.50 | 9.40 | 0.313385E+09 | 544.92 | 18.00 | 9.40 | ||
Maximum of Months | 0.145665E+11 | 31032.00 | 38.00 | 21.45 | 0.445221E+09 | 544.98 | 38.17 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481478E+10 | 6442.00 | 17-JAN-16:50 | 24.17 | 9.15 | 0.00 | 0.00 | 01-JAN-00:10 | 24.17 | 9.15 |
February | 0.378340E+10 | 5800.73 | 22-FEB-06:15 | 9.33 | 9.13 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 9.13 |
March | 0.574636E+10 | 7793.85 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.991602E+10 | 9775.68 | 24-APR-14:50 | 33.00 | 13.29 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 13.29 |
May | 0.104770E+11 | 10242.17 | 30-MAY-05:15 | 18.00 | 8.93 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 8.93 |
June | 0.132646E+11 | 12528.47 | 19-JUN-05:03 | 22.17 | 10.17 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.17 |
July | 0.129566E+11 | 14480.85 | 24-JUL-05:15 | 24.67 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 24.67 | 18.75 |
August | 0.144362E+11 | 17814.17 | 28-AUG-05:15 | 28.67 | 19.85 | 0.00 | 0.00 | 01-AUG-00:10 | 28.67 | 19.85 |
September | 0.107450E+11 | 15330.49 | 05-SEP-05:15 | 21.63 | 18.84 | 0.00 | 0.00 | 01-SEP-00:10 | 21.63 | 18.84 |
October | 0.845729E+10 | 12083.45 | 10-OCT-05:15 | 17.33 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 11.48 |
November | 0.622466E+10 | 9406.65 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.475171E+10 | 8613.10 | 26-DEC-06:15 | 8.67 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 3.13 |
Annual Sum or Average | 0.105574E+12 | 0.00 | ||||||||
Minimum of Months | 0.378340E+10 | 5800.73 | 8.67 | 3.13 | 0.00 | 0.00 | 8.67 | 3.13 | ||
Maximum of Months | 0.144362E+11 | 17814.17 | 33.00 | 19.85 | 0.00 | 0.00 | 33.00 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247539E+10 | 4725.06 | 20-JAN-06:08 | 9.27 | 4.95 | 0.00 | 0.00 | 01-JAN-00:10 | 9.27 | 4.95 |
February | 0.187952E+10 | 4861.43 | 01-FEB-06:08 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.304024E+10 | 5142.66 | 24-MAR-05:10 | 6.70 | 4.78 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 4.78 |
April | 0.689357E+10 | 7786.65 | 14-APR-15:10 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.881796E+10 | 8822.56 | 08-MAY-05:03 | 21.67 | 9.94 | 0.00 | 0.00 | 01-MAY-00:10 | 21.67 | 9.94 |
June | 0.114577E+11 | 10479.45 | 19-JUN-05:03 | 22.17 | 10.17 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.17 |
July | 0.105682E+11 | 11816.13 | 05-JUL-05:02 | 23.00 | 11.31 | 0.00 | 0.00 | 01-JUL-00:10 | 23.00 | 11.31 |
August | 0.106936E+11 | 10574.22 | 12-AUG-05:02 | 26.00 | 19.28 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 19.28 |
September | 0.902668E+10 | 12006.00 | 05-SEP-05:02 | 21.92 | 18.79 | 0.00 | 0.00 | 01-SEP-00:10 | 21.92 | 18.79 |
October | 0.593663E+10 | 8908.88 | 02-OCT-15:40 | 34.33 | 19.15 | 0.00 | 0.00 | 01-OCT-00:10 | 34.33 | 19.15 |
November | 0.320213E+10 | 5474.17 | 04-NOV-05:08 | 6.00 | 3.72 | 0.00 | 0.00 | 01-NOV-00:10 | 6.00 | 3.72 |
December | 0.176969E+10 | 9092.36 | 07-DEC-05:01 | -1.1 | -5.5 | 0.00 | 0.00 | 01-DEC-00:10 | -1.1 | -5.5 |
Annual Sum or Average | 0.757613E+11 | 0.00 | ||||||||
Minimum of Months | 0.176969E+10 | 4725.06 | -1.1 | -5.5 | 0.00 | 0.00 | -1.1 | -5.5 | ||
Maximum of Months | 0.114577E+11 | 12006.00 | 35.00 | 19.28 | 0.00 | 0.00 | 35.00 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318448E+10 | 9635.93 | 31-JAN-16:00 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.191021E+10 | 8563.84 | 23-FEB-14:40 | 18.00 | 10.49 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.49 |
March | 0.437979E+10 | 13125.95 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.120937E+11 | 20883.90 | 14-APR-14:50 | 34.83 | 14.49 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 14.49 |
May | 0.155961E+11 | 21297.40 | 19-MAY-14:00 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.217862E+11 | 25789.91 | 28-JUN-14:50 | 41.83 | 19.32 | 0.00 | 0.00 | 01-JUN-00:10 | 41.83 | 19.32 |
July | 0.192505E+11 | 24167.69 | 20-JUL-14:00 | 39.00 | 20.25 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 20.25 |
August | 0.189013E+11 | 23823.35 | 15-AUG-14:40 | 38.67 | 19.23 | 0.00 | 0.00 | 01-AUG-00:10 | 38.67 | 19.23 |
September | 0.142809E+11 | 21461.44 | 07-SEP-15:20 | 37.37 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.37 | 19.77 |
October | 0.801836E+10 | 18872.82 | 02-OCT-14:30 | 35.00 | 19.50 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.50 |
November | 0.359106E+10 | 12317.93 | 01-NOV-15:50 | 28.17 | 15.80 | 0.00 | 0.00 | 01-NOV-00:10 | 28.17 | 15.80 |
December | 0.162660E+10 | 7498.56 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.124619E+12 | 0.00 | ||||||||
Minimum of Months | 0.162660E+10 | 7498.56 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.217862E+11 | 25789.91 | 41.83 | 20.25 | 0.00 | 0.00 | 41.83 | 20.25 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415527E+10 | 2353.98 | 24-JAN-17:00 | 24.00 | 10.79 | 95230224.23 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.825896E+10 | 4175.52 | 27-FEB-17:40 | 15.67 | 8.53 | 86398897.00 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.145011E+11 | 7162.96 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.84 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.188120E+11 | 7975.33 | 26-APR-18:40 | 19.67 | 9.73 | 98320781.09 | 158.94 | 24-APR-13:00 | 19.67 | 9.73 |
May | 0.484472E+10 | 3512.70 | 31-MAY-24:00 | 26.00 | 10.61 | 99233113.12 | 126.82 | 03-MAY-13:20 | 26.00 | 10.61 |
June | 0.966375E+10 | 5423.17 | 30-JUN-23:33 | 28.87 | 14.96 | 98957373.75 | 126.83 | 30-JUN-09:00 | 28.87 | 14.96 |
July | 0.149924E+11 | 7321.00 | 31-JUL-23:55 | 29.60 | 17.96 | 91883831.44 | 126.83 | 18-JUL-09:09 | 29.60 | 17.96 |
August | 0.198621E+11 | 7869.27 | 14-AUG-02:33 | 27.67 | 17.50 | 0.110637E+09 | 169.79 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.471375E+10 | 3522.96 | 30-SEP-23:53 | 25.20 | 15.49 | 91613567.06 | 126.86 | 05-SEP-09:20 | 25.20 | 15.49 |
October | 0.973864E+10 | 5336.65 | 31-OCT-24:00 | 17.10 | 9.96 | 95231183.88 | 126.85 | 03-OCT-09:30 | 17.10 | 9.96 |
November | 0.141585E+11 | 6352.77 | 14-NOV-17:00 | 19.00 | 14.11 | 94301957.48 | 126.84 | 13-NOV-10:09 | 19.00 | 14.11 |
December | 0.194355E+11 | 8109.81 | 28-DEC-17:00 | 18.60 | 7.88 | 92064823.03 | 134.15 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.143137E+12 | 0.115711E+10 | ||||||||
Minimum of Months | 0.415527E+10 | 2353.98 | 15.30 | 7.49 | 86398897.00 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.198621E+11 | 8109.81 | 29.60 | 17.96 | 0.110637E+09 | 169.79 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293316E+10 | 2168.36 | 24-JAN-17:00 | 24.00 | 10.79 | 95230215.86 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.687460E+10 | 3883.45 | 27-FEB-17:40 | 15.67 | 8.53 | 86398672.21 | 126.84 | 16-FEB-10:50 | 15.67 | 8.53 |
March | 0.130975E+11 | 6669.40 | 31-MAR-23:50 | 15.32 | 7.32 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.32 | 7.32 |
April | 0.177698E+11 | 7581.11 | 26-APR-18:30 | 20.00 | 9.88 | 97496240.13 | 155.74 | 24-APR-13:00 | 20.00 | 9.88 |
May | 0.445569E+10 | 3405.06 | 31-MAY-24:00 | 26.00 | 10.61 | 99233114.06 | 126.82 | 19-MAY-13:50 | 26.00 | 10.61 |
June | 0.919903E+10 | 5233.20 | 30-JUN-23:23 | 29.25 | 14.73 | 98957383.18 | 126.83 | 30-JUN-09:00 | 29.25 | 14.73 |
July | 0.142481E+11 | 7013.76 | 31-JUL-23:55 | 29.60 | 17.96 | 91884339.10 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.186740E+11 | 7393.60 | 06-AUG-18:30 | 29.50 | 19.18 | 0.109293E+09 | 165.26 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.431141E+10 | 3409.54 | 30-SEP-24:00 | 25.20 | 15.49 | 91612557.40 | 126.85 | 11-SEP-13:00 | 25.20 | 15.49 |
October | 0.879174E+10 | 4897.15 | 31-OCT-24:00 | 17.10 | 9.96 | 95231253.73 | 126.85 | 03-OCT-09:39 | 17.10 | 9.96 |
November | 0.126497E+11 | 5972.67 | 14-NOV-17:00 | 19.00 | 14.11 | 94302010.89 | 126.84 | 13-NOV-14:00 | 19.00 | 14.11 |
December | 0.172452E+11 | 7588.91 | 28-DEC-17:00 | 18.60 | 7.88 | 91963045.81 | 131.89 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.130250E+12 | 0.115484E+10 | ||||||||
Minimum of Months | 0.293316E+10 | 2168.36 | 15.32 | 7.32 | 86398672.21 | 126.82 | 15.32 | 7.32 | ||
Maximum of Months | 0.186740E+11 | 7588.91 | 29.60 | 19.18 | 0.109293E+09 | 165.26 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208302E+10 | 2192.58 | 24-JAN-17:00 | 24.00 | 10.79 | 95109275.74 | 129.63 | 02-JAN-10:50 | 24.00 | 10.79 |
February | 0.588597E+10 | 3866.62 | 22-FEB-17:00 | 20.00 | 11.26 | 86398660.74 | 126.84 | 16-FEB-10:00 | 20.00 | 11.26 |
March | 0.124175E+11 | 6481.04 | 31-MAR-23:20 | 15.37 | 6.81 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.37 | 6.81 |
April | 0.177581E+11 | 7640.16 | 26-APR-18:20 | 20.33 | 10.02 | 96469237.22 | 155.34 | 24-APR-13:00 | 20.33 | 10.02 |
May | 0.445222E+10 | 3408.01 | 31-MAY-24:00 | 26.00 | 10.61 | 99233114.81 | 126.82 | 03-MAY-13:39 | 26.00 | 10.61 |
June | 0.933682E+10 | 5261.80 | 30-JUN-23:45 | 28.48 | 15.17 | 98957381.47 | 126.83 | 30-JUN-09:00 | 28.48 | 15.17 |
July | 0.143957E+11 | 7066.14 | 31-JUL-23:45 | 29.78 | 18.02 | 91884330.02 | 126.84 | 14-JUL-09:00 | 29.78 | 18.02 |
August | 0.188175E+11 | 7558.08 | 06-AUG-18:40 | 29.33 | 19.32 | 0.108074E+09 | 165.27 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.435192E+10 | 3425.80 | 30-SEP-24:00 | 25.20 | 15.49 | 91612833.51 | 126.85 | 11-SEP-13:09 | 25.20 | 15.49 |
October | 0.840040E+10 | 4700.62 | 31-OCT-23:50 | 16.98 | 9.75 | 95231230.18 | 126.85 | 03-OCT-09:39 | 16.98 | 9.75 |
November | 0.118019E+11 | 6002.11 | 21-NOV-17:00 | 24.00 | 10.76 | 94302062.89 | 126.84 | 13-NOV-14:00 | 24.00 | 10.76 |
December | 0.159355E+11 | 7604.78 | 26-DEC-17:00 | 23.00 | 10.75 | 91903719.20 | 128.33 | 22-DEC-16:00 | 23.00 | 10.75 |
Annual Sum or Average | 0.125636E+12 | 0.115241E+10 | ||||||||
Minimum of Months | 0.208302E+10 | 2192.58 | 15.37 | 6.81 | 86398660.74 | 126.82 | 15.37 | 6.81 | ||
Maximum of Months | 0.188175E+11 | 7640.16 | 29.78 | 19.32 | 0.108074E+09 | 165.27 | 41.00 | 18.02 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241317E+12 | 93341.97 | 18-JAN-17:00 | 24.00 | 9.55 | 0.206145E+10 | 2745.44 | 23-JAN-10:09 | 19.17 | 9.85 |
February | 0.436510E+12 | 184162.73 | 22-FEB-17:00 | 20.00 | 11.26 | 0.187025E+10 | 2746.89 | 17-FEB-14:00 | 20.00 | 11.26 |
March | 0.728953E+12 | 358600.57 | 31-MAR-24:00 | 15.30 | 7.49 | 0.223502E+10 | 2748.52 | 01-MAR-14:00 | 15.30 | 7.49 |
April | 0.936278E+12 | 381320.37 | 03-APR-21:01 | 22.83 | 9.11 | 0.248231E+10 | 4982.46 | 14-APR-13:00 | 34.00 | 14.07 |
May | 0.242222E+12 | 176203.28 | 31-MAY-24:00 | 26.00 | 10.61 | 0.214824E+10 | 2747.00 | 09-MAY-13:00 | 26.00 | 10.61 |
June | 0.471117E+12 | 268106.47 | 30-JUN-23:53 | 28.10 | 15.37 | 0.214280E+10 | 2748.08 | 07-JUN-13:00 | 28.10 | 15.37 |
July | 0.734003E+12 | 355827.01 | 31-JUL-23:20 | 30.33 | 18.19 | 0.200143E+10 | 3311.15 | 14-JUL-09:00 | 30.33 | 18.19 |
August | 0.965323E+12 | 387530.08 | 23-AUG-22:53 | 24.00 | 10.56 | 0.309697E+10 | 5027.92 | 23-AUG-13:09 | 24.00 | 10.56 |
September | 0.240088E+12 | 177459.30 | 30-SEP-23:57 | 25.20 | 15.49 | 0.198323E+10 | 2746.90 | 15-SEP-09:30 | 25.20 | 15.49 |
October | 0.491052E+12 | 269589.48 | 31-OCT-24:00 | 17.10 | 9.96 | 0.206169E+10 | 2748.29 | 16-OCT-13:00 | 17.10 | 9.96 |
November | 0.711732E+12 | 278232.29 | 20-NOV-17:00 | 26.00 | 12.00 | 0.204177E+10 | 2751.04 | 13-NOV-10:09 | 26.00 | 12.00 |
December | 0.979377E+12 | 370404.25 | 25-DEC-16:32 | 24.67 | 11.46 | 0.199495E+10 | 3132.66 | 22-DEC-14:00 | 24.67 | 11.46 |
Annual Sum or Average | 0.717797E+13 | 0.261201E+11 | ||||||||
Minimum of Months | 0.240088E+12 | 93341.97 | 15.30 | 7.49 | 0.187025E+10 | 2745.44 | 15.30 | 7.49 | ||
Maximum of Months | 0.979377E+12 | 387530.08 | 30.33 | 18.19 | 0.309697E+10 | 5027.92 | 34.00 | 18.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336308E+09 | 15349.65 | 16-JAN-17:03 | 23.50 |
February | 0.125457E+09 | 15047.09 | 20-FEB-16:12 | 17.67 |
March | 0.123110E+09 | 13825.34 | 18-MAR-16:01 | 27.20 |
April | 0.412941E+09 | 20667.43 | 29-APR-16:01 | 32.67 |
May | 0.403893E+09 | 23760.79 | 20-MAY-16:01 | 34.83 |
June | 0.462139E+09 | 30179.81 | 17-JUN-16:02 | 40.50 |
July | 0.684595E+09 | 27994.68 | 22-JUL-16:01 | 38.00 |
August | 0.445503E+09 | 31370.45 | 26-AUG-16:01 | 40.83 |
September | 0.593448E+09 | 22984.08 | 23-SEP-16:01 | 34.30 |
October | 0.525378E+09 | 18426.89 | 14-OCT-16:01 | 31.00 |
November | 0.319018E+09 | 13235.15 | 06-NOV-05:15 | 7.67 |
December | 0.321147E+09 | 13802.78 | 05-DEC-05:55 | 2.00 |
Annual Sum or Average | 0.475294E+10 | |||
Minimum of Months | 0.123110E+09 | 13235.15 | 2.00 | |
Maximum of Months | 0.684595E+09 | 31370.45 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248062E+09 | 72121.35 | 02-JAN-05:21 | 4.00 |
February | 27880891.71 | 63426.59 | 13-FEB-06:02 | 8.00 |
March | 6218047.39 | 35015.76 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 9020739.66 | 42532.87 | 24-NOV-06:03 | 3.17 |
December | 0.112513E+09 | 66271.66 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.403695E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.248062E+09 | 72121.35 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 526037.02 | 6598.86 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 526037.02 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 526037.02 | 6598.86 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 3967305.54 | 5067.59 | 07-DEC-06:02 | -0.7 |
Annual Sum or Average | 3967305.54 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 3967305.54 | 5067.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 826904.94 | 9078.46 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 826904.94 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 826904.94 | 9078.46 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112631E+09 | 15946.57 | 02-JAN-05:11 | 4.00 |
February | 58710621.51 | 13915.95 | 13-FEB-06:02 | 8.00 |
March | 58373198.46 | 14772.54 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 337671.26 | 2308.91 | 26-OCT-05:02 | 7.17 |
November | 45085283.49 | 14697.68 | 24-NOV-05:11 | 3.67 |
December | 0.334328E+09 | 15162.06 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.609466E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.334328E+09 | 15946.57 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49851120.36 | 13175.59 | 02-JAN-05:11 | 4.00 |
February | 22868893.12 | 11278.89 | 13-FEB-06:02 | 8.00 |
March | 26315000.29 | 10275.17 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 17674.83 | 117.83 | 28-OCT-05:05 | 10.00 |
November | 15811850.42 | 11994.22 | 24-NOV-05:11 | 3.67 |
December | 0.157867E+09 | 12663.93 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.272732E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.157867E+09 | 13175.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21366128.33 | 15462.77 | 02-JAN-06:01 | 4.33 |
February | 7516874.94 | 15345.98 | 13-FEB-06:02 | 8.00 |
March | 15675633.01 | 12489.77 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 3549504.44 | 9809.35 | 24-NOV-06:03 | 3.17 |
December | 83513725.00 | 15887.46 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.131622E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 83513725.00 | 15887.46 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22975896.61 | 11898.62 | 02-JAN-05:11 | 4.00 |
February | 5671050.41 | 8249.65 | 13-FEB-06:02 | 8.00 |
March | 6402704.79 | 7791.35 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 5664297.52 | 8137.63 | 24-NOV-06:03 | 3.17 |
December | 0.109887E+09 | 11908.03 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.150601E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.109887E+09 | 11908.03 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.699343E+09 | 19538.34 | 02-JAN-05:21 | 4.00 |
February | 0.551860E+09 | 17834.93 | 13-FEB-05:11 | 8.00 |
March | 0.403621E+09 | 18567.07 | 27-MAR-04:11 | 2.37 |
April | 89543.03 | 596.95 | 21-APR-05:03 | 8.17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 83019453.35 | 15778.54 | 26-OCT-05:02 | 7.17 |
November | 0.429469E+09 | 18841.12 | 24-NOV-05:11 | 3.67 |
December | 0.149590E+10 | 19622.63 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.366330E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.149590E+10 | 19622.63 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306331E+09 | 16938.76 | 02-JAN-05:21 | 4.00 |
February | 0.251974E+09 | 15290.45 | 13-FEB-05:11 | 8.00 |
March | 0.184527E+09 | 15578.82 | 27-MAR-04:11 | 2.37 |
April | 6137.49 | 40.92 | 21-APR-05:05 | 8.17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 34840929.85 | 12430.28 | 26-OCT-05:02 | 7.17 |
November | 0.175389E+09 | 16067.76 | 24-NOV-05:11 | 3.67 |
December | 0.682075E+09 | 16793.18 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.163514E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.682075E+09 | 16938.76 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171438E+09 | 20134.75 | 02-JAN-05:21 | 4.00 |
February | 0.226086E+09 | 19353.85 | 13-FEB-05:11 | 8.00 |
March | 0.231346E+09 | 18957.94 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 18222958.39 | 14098.67 | 26-OCT-05:02 | 7.17 |
November | 0.118545E+09 | 18795.36 | 24-NOV-05:11 | 3.67 |
December | 0.597431E+09 | 19723.63 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.136307E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.597431E+09 | 20134.75 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170797E+09 | 16673.43 | 02-JAN-05:21 | 4.00 |
February | 0.162920E+09 | 14847.63 | 13-FEB-05:11 | 8.00 |
March | 0.113557E+09 | 14852.13 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 12876536.10 | 9684.72 | 26-OCT-05:02 | 7.17 |
November | 0.109753E+09 | 15417.05 | 24-NOV-05:11 | 3.67 |
December | 0.526985E+09 | 16344.90 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.109689E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.526985E+09 | 16673.43 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84817042.96 | 8751.35 | 29-JAN-16:32 | 24.33 |
February | 59327351.66 | 10242.13 | 13-FEB-05:11 | 8.00 |
March | 71856758.23 | 9773.75 | 27-MAR-04:11 | 2.37 |
April | 93741008.11 | 9347.82 | 23-APR-15:51 | 33.30 |
May | 61903705.09 | 7717.05 | 14-MAY-15:51 | 34.00 |
June | 52187222.28 | 9612.25 | 25-JUN-15:21 | 38.00 |
July | 78961543.59 | 9999.28 | 30-JUL-16:31 | 38.00 |
August | 82401169.84 | 10130.37 | 27-AUG-14:21 | 40.00 |
September | 60631948.57 | 8066.90 | 10-SEP-14:41 | 35.92 |
October | 78604308.55 | 9001.39 | 23-OCT-04:12 | 11.00 |
November | 97859603.18 | 9847.97 | 13-NOV-05:11 | 17.00 |
December | 0.115224E+09 | 11604.90 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.937516E+09 | |||
Minimum of Months | 52187222.28 | 7717.05 | 2.37 | |
Maximum of Months | 0.115224E+09 | 11604.90 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344424E+09 | 7991.47 | 01-JAN-15:13 | 15.03 |
February | 0.113858E+09 | 6436.11 | 07-FEB-06:02 | 9.00 |
March | 51620046.18 | 6443.40 | 08-MAR-06:02 | 10.42 |
April | 53449237.39 | 8775.62 | 23-APR-15:41 | 33.25 |
May | 48447760.13 | 8241.86 | 21-MAY-16:51 | 32.00 |
June | 49919084.93 | 9535.29 | 25-JUN-16:51 | 38.00 |
July | 65425261.41 | 9790.32 | 30-JUL-16:51 | 38.00 |
August | 53197294.68 | 9862.87 | 27-AUG-16:31 | 40.00 |
September | 43845482.68 | 6200.21 | 17-SEP-16:02 | 34.40 |
October | 52281819.29 | 8282.14 | 15-OCT-15:51 | 31.00 |
November | 52504286.76 | 7889.22 | 19-NOV-15:12 | 27.00 |
December | 0.213623E+09 | 6857.65 | 12-DEC-06:02 | 12.17 |
Annual Sum or Average | 0.114260E+10 | |||
Minimum of Months | 43845482.68 | 6200.21 | 9.00 | |
Maximum of Months | 0.344424E+09 | 9862.87 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180775E+10 | 21904.78 | 02-JAN-06:13 | 4.67 |
February | 0.138605E+10 | 9846.15 | 13-FEB-06:02 | 8.00 |
March | 0.128398E+10 | 14794.26 | 21-MAR-05:03 | 13.53 |
April | 0.305308E+09 | 15552.74 | 27-APR-05:03 | 12.00 |
May | 0.132682E+09 | 14185.66 | 01-MAY-04:12 | 12.33 |
June | 43615510.33 | 11239.18 | 12-JUN-04:11 | 20.00 |
July | 31226017.69 | 12135.69 | 03-JUL-04:12 | 20.67 |
August | 35274513.17 | 9559.06 | 25-AUG-04:12 | 22.00 |
September | 42850288.68 | 11213.93 | 22-SEP-04:12 | 17.60 |
October | 0.647603E+09 | 14571.18 | 18-OCT-05:03 | 15.83 |
November | 0.112975E+10 | 12766.93 | 02-NOV-05:03 | 16.00 |
December | 0.268396E+10 | 17171.70 | 18-DEC-06:02 | 3.83 |
Annual Sum or Average | 0.953004E+10 | |||
Minimum of Months | 31226017.69 | 9559.06 | 3.83 | |
Maximum of Months | 0.268396E+10 | 21904.78 | 22.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24281920.18 | 515.15 | 01-JAN-08:25 | 3.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 24281920.18 | |||
Minimum of Months | 0.00 | 0.00 | 3.10 | |
Maximum of Months | 24281920.18 | 515.15 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86936352.93 | 606.03 | 02-JAN-01:00 | 3.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 86936352.93 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 86936352.93 | 606.03 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160708E+10 | 2587.92 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.141101E+10 | 2255.20 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.155240E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132742E+10 | 1803.00 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.139058E+10 | 1350.81 | 25-MAY-12:20 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.135273E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129170E+10 | 1470.28 | 10-JUL-15:50 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.148626E+10 | 2255.20 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.136370E+10 | 1803.00 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.152390E+10 | 2587.92 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.155892E+10 | 2587.92 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.159286E+10 | 2587.92 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174586E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129170E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.160708E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.975702E+09 | 1667.75 | 20-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.877899E+09 | 1453.34 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.982773E+09 | 1161.92 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.846663E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.901425E+09 | 870.51 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.880263E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.841375E+09 | 947.51 | 10-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.953127E+09 | 1453.34 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.869487E+09 | 947.51 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.937306E+09 | 1161.92 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.965282E+09 | 1667.75 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.972267E+09 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110036E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.841375E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.982773E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147184E+10 | 2587.98 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133471E+10 | 2255.25 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151469E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133171E+10 | 1803.04 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141432E+10 | 1350.84 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138377E+10 | 1350.84 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132068E+10 | 1803.04 | 13-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.149618E+10 | 2255.25 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.135112E+10 | 1803.04 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142401E+10 | 2135.77 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.145692E+10 | 2587.98 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.145560E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169556E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.132068E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151469E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100236E+10 | 1667.75 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.889761E+09 | 1453.34 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.992632E+09 | 1453.34 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.859459E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.908653E+09 | 947.51 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.885692E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.847393E+09 | 1161.92 | 13-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.964375E+09 | 1453.34 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.878780E+09 | 1453.34 | 19-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.957291E+09 | 1667.75 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.972209E+09 | 1667.75 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.985002E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111436E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.847393E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.100236E+10 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159481E+10 | 2587.92 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.140187E+10 | 2255.20 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154707E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132487E+10 | 1803.00 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138944E+10 | 1350.81 | 26-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.135189E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129034E+10 | 1350.81 | 10-JUL-15:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.148311E+10 | 2255.20 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135952E+10 | 1803.00 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.151371E+10 | 2587.92 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.154969E+10 | 2587.92 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.157898E+10 | 2587.92 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173853E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129034E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.159481E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.973178E+09 | 1667.75 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.874744E+09 | 1453.34 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.981268E+09 | 1161.92 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.846315E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.900579E+09 | 870.51 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.879757E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.840102E+09 | 947.51 | 10-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.951905E+09 | 1453.34 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.868437E+09 | 947.51 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.934722E+09 | 1161.92 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.962690E+09 | 1667.75 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.969548E+09 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.109832E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.840102E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.981268E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147141E+10 | 2587.98 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133310E+10 | 2255.25 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151227E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132962E+10 | 1803.04 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141184E+10 | 1350.84 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138076E+10 | 1350.84 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.131657E+10 | 1803.04 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.149253E+10 | 2255.25 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134941E+10 | 1803.04 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142020E+10 | 2135.77 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.145479E+10 | 2587.98 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.145493E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169274E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131657E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151227E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.998416E+09 | 1667.75 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.886275E+09 | 1453.34 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.989328E+09 | 1453.34 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.857226E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.906782E+09 | 947.51 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.884430E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.844777E+09 | 1161.92 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.961940E+09 | 1453.34 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.877122E+09 | 1453.34 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953523E+09 | 1667.75 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.970171E+09 | 1667.75 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.981361E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111113E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.844777E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.998416E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159472E+10 | 2587.92 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.140150E+10 | 2255.20 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154707E+10 | 2255.20 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132487E+10 | 1803.00 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.138941E+10 | 1350.81 | 26-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.135189E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.129033E+10 | 1350.81 | 10-JUL-15:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.148310E+10 | 2255.20 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135936E+10 | 1803.00 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.151364E+10 | 2587.92 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.154949E+10 | 2587.92 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.157891E+10 | 2587.92 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173843E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.129033E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.159472E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.973172E+09 | 1667.75 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.874744E+09 | 1453.34 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.981159E+09 | 1161.92 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.846313E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.900549E+09 | 870.51 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.879732E+09 | 793.52 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.840013E+09 | 947.51 | 10-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.951800E+09 | 1453.34 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.868403E+09 | 947.51 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.934676E+09 | 1161.92 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.962592E+09 | 1667.75 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.969502E+09 | 1667.75 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.109827E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.840013E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.981159E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147141E+10 | 2587.98 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133279E+10 | 2255.25 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151224E+10 | 2255.25 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132953E+10 | 1803.04 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141183E+10 | 1350.84 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.138071E+10 | 1350.84 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.131656E+10 | 1803.04 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.149232E+10 | 2255.25 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134931E+10 | 1803.04 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.142020E+10 | 2135.77 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.145478E+10 | 2587.98 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.145492E+10 | 2587.98 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.169266E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131656E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151224E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.998370E+09 | 1667.75 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.886275E+09 | 1453.34 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.989236E+09 | 1453.34 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.857164E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.906766E+09 | 947.51 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.884450E+09 | 870.51 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.844709E+09 | 1161.92 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.961833E+09 | 1453.34 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.877073E+09 | 1453.34 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.953523E+09 | 1667.75 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.970122E+09 | 1667.75 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.981361E+09 | 1667.75 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.111109E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.844709E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.998370E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.160708E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1166074.79 | 0.326348E+09 |
February | 0.136985E+10 | 0.141101E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261844E+09 |
March | 0.163685E+10 | 0.155240E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2978603.27 | 0.335509E+09 |
April | 0.145243E+10 | 0.132742E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52881006.57 | 0.103212E+09 |
May | 0.157338E+10 | 0.139058E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101937E+09 | 67535474.67 |
June | 0.156900E+10 | 0.135273E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186533E+09 | 15871724.45 |
July | 0.145680E+10 | 0.129170E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186225E+09 | 12625071.38 |
August | 0.163685E+10 | 0.148626E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130306E+09 | 18561055.37 |
September | 0.145243E+10 | 0.136370E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96557915.34 | 44671540.41 |
October | 0.150991E+10 | 0.152390E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35062313.22 | 0.170236E+09 |
November | 0.149516E+10 | 0.155892E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3012519.39 | 0.299803E+09 |
December | 0.145680E+10 | 0.159286E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261555.98 | 0.321564E+09 |
Annual Sum or Average | 0.181194E+11 | 0.174586E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796921E+09 | 0.197778E+10 |
Minimum of Months | 0.136985E+10 | 0.129170E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12625071.38 |
Maximum of Months | 0.163685E+10 | 0.160708E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186533E+09 | 0.335509E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.975702E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 728648.74 | 0.220983E+09 |
February | 0.882782E+09 | 0.877899E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173398E+09 |
March | 0.105485E+10 | 0.982773E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2046017.45 | 0.221165E+09 |
April | 0.936002E+09 | 0.846663E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36647584.91 | 65877581.12 |
May | 0.101394E+10 | 0.901425E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67623643.01 | 45760949.62 |
June | 0.101113E+10 | 0.880263E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128533E+09 | 9342757.92 |
July | 0.938820E+09 | 0.841375E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131433E+09 | 6872730.38 |
August | 0.105485E+10 | 0.953127E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93725530.94 | 9210339.67 |
September | 0.936002E+09 | 0.869487E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66323354.47 | 28878504.36 |
October | 0.973041E+09 | 0.937306E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23561628.58 | 0.113017E+09 |
November | 0.963541E+09 | 0.965282E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1922619.98 | 0.197462E+09 |
December | 0.938820E+09 | 0.972267E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217332.22 | 0.210759E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110036E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552762E+09 | 0.130273E+10 |
Minimum of Months | 0.882782E+09 | 0.841375E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6872730.38 |
Maximum of Months | 0.105485E+10 | 0.982773E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131433E+09 | 0.221165E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.147184E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937175.67 | 0.355497E+09 |
February | 0.136988E+10 | 0.133471E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268747E+09 |
March | 0.163688E+10 | 0.151469E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2679549.24 | 0.342391E+09 |
April | 0.145246E+10 | 0.133171E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49844576.90 | 0.105686E+09 |
May | 0.157341E+10 | 0.141432E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101522E+09 | 66976448.64 |
June | 0.156904E+10 | 0.138377E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190093E+09 | 14849123.13 |
July | 0.145684E+10 | 0.132068E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188618E+09 | 11863525.86 |
August | 0.163688E+10 | 0.149618E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129837E+09 | 18193460.36 |
September | 0.145246E+10 | 0.135112E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92571484.11 | 48258613.84 |
October | 0.150994E+10 | 0.142401E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31165399.73 | 0.182817E+09 |
November | 0.149520E+10 | 0.145692E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1674632.57 | 0.318465E+09 |
December | 0.145684E+10 | 0.145560E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82534.48 | 0.338052E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169556E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789026E+09 | 0.207180E+10 |
Minimum of Months | 0.136988E+10 | 0.132068E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11863525.86 |
Maximum of Months | 0.163688E+10 | 0.151469E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190093E+09 | 0.355497E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100236E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 673096.68 | 0.239177E+09 |
February | 0.882782E+09 | 0.889761E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193161E+09 |
March | 0.105485E+10 | 0.992632E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1730448.21 | 0.256214E+09 |
April | 0.936002E+09 | 0.859459E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30135466.34 | 88689036.22 |
May | 0.101394E+10 | 0.908653E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63655306.82 | 54513355.31 |
June | 0.101113E+10 | 0.885692E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120070E+09 | 13586164.51 |
July | 0.938820E+09 | 0.847393E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117131E+09 | 12335861.93 |
August | 0.105485E+10 | 0.964375E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78312284.19 | 20661527.94 |
September | 0.936002E+09 | 0.878780E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61592780.38 | 37434806.60 |
October | 0.973041E+09 | 0.957291E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21399533.65 | 0.132553E+09 |
November | 0.963541E+09 | 0.972209E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1191941.38 | 0.231431E+09 |
December | 0.938820E+09 | 0.985002E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58663.87 | 0.246502E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111436E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495950E+09 | 0.152626E+10 |
Minimum of Months | 0.882782E+09 | 0.847393E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12335861.93 |
Maximum of Months | 0.105485E+10 | 0.100236E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120070E+09 | 0.256214E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.159481E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7160442.96 | 0.644696E+09 |
February | 0.136985E+10 | 0.140187E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526260E+09 |
March | 0.163685E+10 | 0.154707E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7037608.00 | 0.690201E+09 |
April | 0.145243E+10 | 0.132487E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129079E+09 | 0.236143E+09 |
May | 0.157338E+10 | 0.138944E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235229E+09 | 0.153920E+09 |
June | 0.156900E+10 | 0.135189E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423703E+09 | 44763305.41 |
July | 0.145680E+10 | 0.129034E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418392E+09 | 38846672.29 |
August | 0.163685E+10 | 0.148311E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296439E+09 | 53000266.81 |
September | 0.145243E+10 | 0.135952E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217669E+09 | 0.103619E+09 |
October | 0.150991E+10 | 0.151371E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85899749.97 | 0.352576E+09 |
November | 0.149516E+10 | 0.154969E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11825473.24 | 0.594229E+09 |
December | 0.145680E+10 | 0.157898E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3387638.74 | 0.629545E+09 |
Annual Sum or Average | 0.181194E+11 | 0.173853E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183582E+10 | 0.406780E+10 |
Minimum of Months | 0.136985E+10 | 0.129034E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38846672.29 |
Maximum of Months | 0.163685E+10 | 0.159481E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423703E+09 | 0.690201E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.973178E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889842.10 | 0.455662E+09 |
February | 0.649041E+09 | 0.874744E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367091E+09 |
March | 0.773965E+09 | 0.981268E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4334510.56 | 0.482833E+09 |
April | 0.688021E+09 | 0.846315E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80453091.77 | 0.171950E+09 |
May | 0.744847E+09 | 0.900579E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152488E+09 | 0.109946E+09 |
June | 0.742030E+09 | 0.879757E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286613E+09 | 30482949.79 |
July | 0.690839E+09 | 0.840102E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283007E+09 | 27383211.50 |
August | 0.773965E+09 | 0.951905E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196721E+09 | 38469249.87 |
September | 0.688021E+09 | 0.868437E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144376E+09 | 73379735.92 |
October | 0.715730E+09 | 0.934722E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53129470.09 | 0.250283E+09 |
November | 0.708685E+09 | 0.962690E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5320844.51 | 0.415911E+09 |
December | 0.690839E+09 | 0.969548E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426850.45 | 0.437185E+09 |
Annual Sum or Average | 0.858171E+10 | 0.109832E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121076E+10 | 0.286058E+10 |
Minimum of Months | 0.649041E+09 | 0.840102E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27383211.50 |
Maximum of Months | 0.773965E+09 | 0.981268E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286613E+09 | 0.482833E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.147141E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1902742.84 | 0.797241E+09 |
February | 0.136988E+10 | 0.133310E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595536E+09 |
March | 0.163688E+10 | 0.151227E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5859274.35 | 0.758358E+09 |
April | 0.145246E+10 | 0.132962E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114447E+09 | 0.254693E+09 |
May | 0.157341E+10 | 0.141184E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232666E+09 | 0.155459E+09 |
June | 0.156904E+10 | 0.138076E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431820E+09 | 42480075.75 |
July | 0.145684E+10 | 0.131657E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422196E+09 | 37754665.35 |
August | 0.163688E+10 | 0.149253E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291034E+09 | 56448967.54 |
September | 0.145246E+10 | 0.134941E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205743E+09 | 0.117877E+09 |
October | 0.150994E+10 | 0.142020E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69476865.21 | 0.415053E+09 |
November | 0.149520E+10 | 0.145479E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3556379.23 | 0.705296E+09 |
December | 0.145684E+10 | 0.145493E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166632.29 | 0.746435E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169274E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177887E+10 | 0.468263E+10 |
Minimum of Months | 0.136988E+10 | 0.131657E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37754665.35 |
Maximum of Months | 0.163688E+10 | 0.151227E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431820E+09 | 0.797241E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.998416E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2683953.86 | 0.475959E+09 |
February | 0.882782E+09 | 0.886275E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374758E+09 |
March | 0.105485E+10 | 0.989328E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4060584.49 | 0.498531E+09 |
April | 0.936002E+09 | 0.857226E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73254789.16 | 0.187147E+09 |
May | 0.101394E+10 | 0.906782E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147054E+09 | 0.119487E+09 |
June | 0.101113E+10 | 0.884430E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278311E+09 | 35429114.44 |
July | 0.938820E+09 | 0.844777E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272893E+09 | 32013979.45 |
August | 0.105485E+10 | 0.961940E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189629E+09 | 43513587.71 |
September | 0.936002E+09 | 0.877122E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140467E+09 | 79889650.24 |
October | 0.973041E+09 | 0.953523E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51591889.31 | 0.261383E+09 |
November | 0.963541E+09 | 0.970171E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5139879.66 | 0.435297E+09 |
December | 0.938820E+09 | 0.981361E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 725203.86 | 0.454075E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111113E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116581E+10 | 0.299748E+10 |
Minimum of Months | 0.882782E+09 | 0.844777E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32013979.45 |
Maximum of Months | 0.105485E+10 | 0.998416E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278311E+09 | 0.498531E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.159472E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12986696.43 | 0.716668E+09 |
February | 0.136985E+10 | 0.140150E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584708E+09 |
March | 0.163685E+10 | 0.154707E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8415135.29 | 0.790265E+09 |
April | 0.145243E+10 | 0.132487E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154381E+09 | 0.284474E+09 |
May | 0.157338E+10 | 0.138941E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283375E+09 | 0.188767E+09 |
June | 0.156900E+10 | 0.135189E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516455E+09 | 56955518.17 |
July | 0.145680E+10 | 0.129033E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508016E+09 | 49562842.46 |
August | 0.163685E+10 | 0.148310E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360194E+09 | 66748878.49 |
September | 0.145243E+10 | 0.135936E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263741E+09 | 0.130420E+09 |
October | 0.150991E+10 | 0.151364E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106951E+09 | 0.406641E+09 |
November | 0.149516E+10 | 0.154949E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18480443.60 | 0.661909E+09 |
December | 0.145680E+10 | 0.157891E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7532679.40 | 0.700972E+09 |
Annual Sum or Average | 0.181194E+11 | 0.173843E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224053E+10 | 0.463809E+10 |
Minimum of Months | 0.136985E+10 | 0.129033E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49562842.46 |
Maximum of Months | 0.163685E+10 | 0.159472E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516455E+09 | 0.790265E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.973172E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4706007.98 | 0.514024E+09 |
February | 0.882782E+09 | 0.874744E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415398E+09 |
March | 0.105485E+10 | 0.981159E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5003772.18 | 0.563819E+09 |
April | 0.936002E+09 | 0.846313E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94942858.94 | 0.211354E+09 |
May | 0.101394E+10 | 0.900549E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182324E+09 | 0.136540E+09 |
June | 0.101113E+10 | 0.879732E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347049E+09 | 39290425.72 |
July | 0.938820E+09 | 0.840013E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341454E+09 | 35126901.11 |
August | 0.105485E+10 | 0.951800E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237337E+09 | 48944358.25 |
September | 0.936002E+09 | 0.868403E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174240E+09 | 92751703.01 |
October | 0.973041E+09 | 0.934676E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63954054.46 | 0.296298E+09 |
November | 0.963541E+09 | 0.962592E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7547143.29 | 0.471395E+09 |
December | 0.938820E+09 | 0.969502E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2730210.10 | 0.490795E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109827E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146129E+10 | 0.331574E+10 |
Minimum of Months | 0.882782E+09 | 0.840013E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35126901.11 |
Maximum of Months | 0.105485E+10 | 0.981159E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347049E+09 | 0.563819E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.147141E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2387712.32 | 0.913492E+09 |
February | 0.136988E+10 | 0.133279E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677104E+09 |
March | 0.163688E+10 | 0.151224E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6846268.80 | 0.884726E+09 |
April | 0.145246E+10 | 0.132953E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137456E+09 | 0.309119E+09 |
May | 0.157341E+10 | 0.141183E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280821E+09 | 0.190642E+09 |
June | 0.156904E+10 | 0.138071E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524965E+09 | 54001471.81 |
July | 0.145684E+10 | 0.131656E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512158E+09 | 48137365.27 |
August | 0.163688E+10 | 0.149232E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353752E+09 | 71179184.66 |
September | 0.145246E+10 | 0.134931E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250090E+09 | 0.148242E+09 |
October | 0.150994E+10 | 0.142020E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84373757.56 | 0.492129E+09 |
November | 0.149520E+10 | 0.145478E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4332360.43 | 0.812303E+09 |
December | 0.145684E+10 | 0.145492E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194587.98 | 0.852883E+09 |
Annual Sum or Average | 0.181198E+11 | 0.169266E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215738E+10 | 0.545396E+10 |
Minimum of Months | 0.136988E+10 | 0.131656E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48137365.27 |
Maximum of Months | 0.163688E+10 | 0.151224E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524965E+09 | 0.913492E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.998370E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961814.32 | 0.543532E+09 |
February | 0.882782E+09 | 0.886275E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429797E+09 |
March | 0.105485E+10 | 0.989236E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4959156.79 | 0.584846E+09 |
April | 0.936002E+09 | 0.857164E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88840928.10 | 0.227768E+09 |
May | 0.101394E+10 | 0.906766E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179068E+09 | 0.147180E+09 |
June | 0.101113E+10 | 0.884450E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340135E+09 | 44588815.35 |
July | 0.938820E+09 | 0.844709E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333728E+09 | 39891400.73 |
August | 0.105485E+10 | 0.961833E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231862E+09 | 54384478.94 |
September | 0.936002E+09 | 0.877073E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171680E+09 | 99301624.35 |
October | 0.973041E+09 | 0.953523E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63426215.25 | 0.309479E+09 |
November | 0.963541E+09 | 0.970122E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7088006.70 | 0.500494E+09 |
December | 0.938820E+09 | 0.981361E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1482077.30 | 0.519518E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111109E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142623E+10 | 0.350078E+10 |
Minimum of Months | 0.882782E+09 | 0.844709E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39891400.73 |
Maximum of Months | 0.105485E+10 | 0.998370E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340135E+09 | 0.584846E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216661.71 | 0.747418E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583010E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044428.71 | 0.745545E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95280097.32 | 0.240546E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190702E+09 | 0.149911E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357922E+09 | 38329700.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358261E+09 | 32027856.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240998E+09 | 50203145.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178481E+09 | 96909091.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60661735.24 | 0.384599E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3299064.16 | 0.674524E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97785.96 | 0.722713E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149096E+10 | 0.446574E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32027856.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358261E+09 | 0.747418E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2652931.08 | 0.124299E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988394E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8096039.67 | 0.127491E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181015E+09 | 0.425851E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348567E+09 | 0.264579E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643497E+09 | 71657796.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647837E+09 | 60497237.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442743E+09 | 92051678.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322891E+09 | 0.170852E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114863E+09 | 0.659162E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9308627.44 | 0.113495E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1161737.64 | 0.120468E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272263E+10 | 0.759056E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60497237.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647837E+09 | 0.127491E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2693623.22 | 0.122177E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994258E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5026450.60 | 0.132446E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165080E+09 | 0.454542E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345252E+09 | 0.271994E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695201E+09 | 75960118.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674521E+09 | 67377013.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470635E+09 | 99041577.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335969E+09 | 0.193089E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116967E+09 | 0.677754E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9772425.10 | 0.112454E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628587.83 | 0.116728E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282275E+10 | 0.767207E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67377013.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695201E+09 | 0.132446E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 | 29-JAN-16:00 | 698.79 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 748.15 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 18-MAR-17:10 | 649.43 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.47 | 30-APR-15:34 | 321.29 | 21-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 25-MAY-12:20 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.53 | 20-MAY-18:10 | 253.02 | 23-MAY-04:53 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 572.48 | 17-JUN-17:10 | 127.70 | 11-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 10-JUL-15:50 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.37 | 22-JUL-17:43 | 188.61 | 26-JUL-23:53 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.76 | 13-AUG-16:00 | 310.83 | 05-AUG-17:35 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.42 | 17-SEP-12:00 | 227.95 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.17 | 01-OCT-14:38 | 634.65 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.96 | 19-NOV-14:50 | 648.38 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 25-DEC-15:50 | 540.35 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.70 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 725.37 | 748.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 20-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 29-JAN-16:00 | 470.30 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 493.56 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.41 | 18-MAR-17:10 | 426.27 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.55 | 30-APR-15:40 | 309.24 | 16-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.35 | 20-MAY-18:30 | 164.16 | 23-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.45 | 17-JUN-17:02 | 94.02 | 11-JUN-06:10 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 10-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 501.67 | 22-JUL-18:00 | 116.27 | 27-JUL-00:27 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.11 | 13-AUG-15:55 | 196.65 | 05-AUG-17:35 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.78 | 17-SEP-12:00 | 146.63 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1161.92 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.07 | 01-OCT-14:40 | 436.32 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.08 | 19-NOV-15:10 | 421.91 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 25-DEC-15:50 | 352.63 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.02 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 501.67 | 493.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 31-JAN-14:00 | 707.77 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 793.99 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.11 | 15-MAR-13:00 | 645.93 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.47 | 30-APR-15:34 | 317.76 | 21-APR-04:53 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 | 20-MAY-18:00 | 248.63 | 23-MAY-04:53 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.67 | 17-JUN-17:02 | 117.86 | 13-JUN-04:10 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 13-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 729.23 | 22-JUL-17:44 | 186.78 | 27-JUL-00:27 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.75 | 13-AUG-16:00 | 320.11 | 05-AUG-17:35 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.23 | 17-SEP-12:27 | 233.09 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2135.77 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.05 | 01-OCT-14:35 | 708.65 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 | 01-NOV-16:00 | 665.34 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 21-DEC-15:00 | 548.06 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.86 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 729.23 | 793.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 31-JAN-14:00 | 498.39 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 564.58 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 15-MAR-13:00 | 481.31 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.70 | 30-APR-15:50 | 256.16 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.10 | 20-MAY-17:50 | 181.68 | 01-MAY-04:50 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.11 | 17-JUN-17:10 | 97.32 | 13-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 13-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.79 | 22-JUL-18:00 | 170.09 | 26-JUL-23:45 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.74 | 13-AUG-16:00 | 269.56 | 05-AUG-17:35 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 19-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.30 | 17-SEP-12:30 | 179.19 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 01-OCT-14:38 | 475.60 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 01-NOV-16:00 | 490.00 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 21-DEC-15:00 | 398.98 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.32 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 478.79 | 564.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.71 | 16-JAN-12:00 | 1167.10 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1511.16 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 18-MAR-17:02 | 1325.48 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 916.42 | 30-APR-15:00 | 696.77 | 21-APR-04:57 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 26-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 854.68 | 20-MAY-17:01 | 578.82 | 23-MAY-04:53 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1340.22 | 17-JUN-17:10 | 310.59 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 1350.81 | 10-JUL-15:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.77 | 22-JUL-17:55 | 468.73 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.13 | 13-AUG-16:00 | 681.49 | 05-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.32 | 17-SEP-12:48 | 492.31 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 682.55 | 01-OCT-14:38 | 1290.91 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.28 | 19-NOV-13:00 | 1286.03 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.30 | 25-DEC-15:52 | 1113.56 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.59 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.77 | 1511.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.09 | 29-JAN-16:10 | 818.51 | 01-JAN-00:55 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1033.55 | 02-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 1161.92 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 18-MAR-17:02 | 898.71 | 28-MAR-04:00 |
April | 1239.33 | 03-APR-07:10 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.45 | 30-APR-15:57 | 729.50 | 16-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.65 | 20-MAY-18:00 | 386.96 | 23-MAY-04:53 |
June | 1239.33 | 01-JUN-07:10 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 900.32 | 17-JUN-17:10 | 219.30 | 11-JUN-06:10 |
July | 1239.33 | 03-JUL-07:10 | 947.51 | 10-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.87 | 22-JUL-17:44 | 319.73 | 26-JUL-24:00 |
August | 1239.33 | 01-AUG-07:10 | 1453.34 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.08 | 13-AUG-16:00 | 465.40 | 05-AUG-18:00 |
September | 1239.33 | 01-SEP-07:10 | 947.51 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.23 | 17-SEP-12:48 | 332.53 | 03-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 1161.92 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 470.85 | 01-OCT-14:40 | 980.23 | 22-OCT-13:55 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.30 | 19-NOV-14:40 | 870.22 | 29-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.08 | 25-DEC-16:10 | 748.71 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.30 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.87 | 1033.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.39 | 31-JAN-14:00 | 1470.63 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1728.69 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 | 15-MAR-13:00 | 1396.14 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 900.45 | 30-APR-15:55 | 710.76 | 21-APR-04:57 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.55 | 20-MAY-17:01 | 578.57 | 23-MAY-04:53 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.41 | 17-JUN-17:10 | 305.41 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.67 | 22-JUL-17:44 | 466.12 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.13 | 13-AUG-16:00 | 710.91 | 05-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.32 | 17-SEP-12:48 | 512.63 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2135.77 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 673.23 | 01-OCT-14:35 | 1620.82 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.66 | 01-NOV-16:00 | 1414.61 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 21-DEC-15:00 | 1199.30 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.41 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.67 | 1728.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 | 16-JAN-12:00 | 907.45 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1096.96 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 15-MAR-13:00 | 942.32 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.80 | 30-APR-15:14 | 508.63 | 26-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.86 | 20-MAY-17:47 | 409.70 | 23-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 904.99 | 17-JUN-17:02 | 236.16 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.05 | 22-JUL-18:00 | 367.96 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.05 | 13-AUG-16:00 | 487.12 | 05-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 742.78 | 17-SEP-12:48 | 343.43 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.69 | 01-OCT-14:38 | 906.48 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.01 | 19-NOV-12:40 | 892.03 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.65 | 25-DEC-13:51 | 768.78 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.16 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.05 | 1096.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.66 | 16-JAN-11:53 | 1283.46 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1729.44 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.53 | 18-MAR-17:02 | 1524.66 | 28-MAR-04:15 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.67 | 30-APR-15:34 | 817.56 | 26-APR-21:10 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 26-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.79 | 20-MAY-17:01 | 686.03 | 23-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.12 | 17-JUN-17:08 | 380.66 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 1350.81 | 10-JUL-15:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.57 | 22-JUL-18:00 | 599.54 | 26-JUL-23:53 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.42 | 13-AUG-16:00 | 859.35 | 05-AUG-17:42 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.84 | 17-SEP-12:48 | 620.05 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 846.53 | 01-OCT-14:38 | 1550.63 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.83 | 19-NOV-12:22 | 1454.92 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.96 | 25-DEC-16:00 | 1350.95 | 07-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.66 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.57 | 1729.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.06 | 16-JAN-13:40 | 848.85 | 01-JAN-01:30 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1193.83 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.25 | 18-MAR-17:02 | 1022.73 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 772.89 | 30-APR-14:55 | 850.37 | 16-APR-08:40 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 681.50 | 20-MAY-17:01 | 461.44 | 23-MAY-04:57 |
June | 1295.83 | 01-JUN-09:09 | 793.52 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.99 | 17-JUN-17:10 | 271.43 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 10-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.18 | 22-JUL-17:44 | 409.68 | 26-JUL-23:53 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.94 | 13-AUG-16:00 | 588.96 | 05-AUG-17:42 |
September | 1295.83 | 01-SEP-09:09 | 947.51 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 909.48 | 17-SEP-12:48 | 418.30 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1161.92 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.96 | 01-OCT-14:38 | 1198.90 | 22-OCT-13:55 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 | 19-NOV-14:50 | 995.85 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.87 | 25-DEC-16:00 | 903.55 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.43 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.18 | 1198.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 | 31-JAN-14:00 | 1525.42 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1997.15 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 | 15-MAR-13:00 | 1595.63 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.04 | 30-APR-15:34 | 853.96 | 26-APR-21:10 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.29 | 20-MAY-17:01 | 686.08 | 23-MAY-04:57 |
June | 2010.83 | 01-JUN-09:09 | 1350.84 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1640.27 | 17-JUN-17:10 | 373.95 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.17 | 22-JUL-17:43 | 596.66 | 26-JUL-23:53 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.41 | 13-AUG-16:00 | 898.48 | 05-AUG-17:42 |
September | 2010.83 | 01-SEP-09:09 | 1803.04 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.42 | 17-SEP-12:48 | 645.02 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2135.77 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 827.16 | 01-OCT-14:35 | 1966.85 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.39 | 01-NOV-16:00 | 1631.21 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 21-DEC-15:00 | 1368.23 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.95 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.17 | 1997.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.45 | 16-JAN-11:58 | 953.91 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1269.07 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 15-MAR-13:00 | 1088.92 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.60 | 30-APR-14:53 | 625.94 | 26-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.83 | 20-MAY-17:47 | 490.93 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.97 | 17-JUN-17:10 | 288.45 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.08 | 22-JUL-18:00 | 468.51 | 26-JUL-23:53 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.89 | 13-AUG-16:00 | 613.64 | 05-AUG-17:42 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 917.87 | 17-SEP-12:48 | 429.06 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.86 | 01-OCT-14:38 | 1109.53 | 22-OCT-13:55 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.28 | 19-NOV-12:22 | 1027.24 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.02 | 25-DEC-13:51 | 904.48 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.45 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.08 | 1269.07 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.65 | 31-JAN-14:00 | 1606.71 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1701.33 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | 18-MAR-17:02 | 1450.38 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.95 | 30-APR-15:20 | 723.77 | 21-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.23 | 20-MAY-17:01 | 572.75 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.67 | 17-JUN-17:02 | 272.75 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1500.32 | 22-JUL-18:00 | 424.14 | 26-JUL-23:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.19 | 13-AUG-16:00 | 644.56 | 05-AUG-17:45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965.31 | 17-SEP-12:00 | 476.61 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.32 | 01-OCT-14:50 | 1282.14 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.59 | 19-NOV-14:53 | 1450.35 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 21-DEC-15:00 | 1216.97 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1500.32 | 1701.33 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 | 31-JAN-14:00 | 2340.90 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2949.51 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.23 | 18-MAR-17:02 | 2477.24 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1499.02 | 30-APR-15:00 | 1279.06 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.10 | 20-MAY-17:01 | 1024.27 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2213.65 | 17-JUN-17:02 | 501.01 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2707.62 | 22-JUL-18:00 | 769.11 | 26-JUL-23:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.90 | 13-AUG-16:00 | 1125.56 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1757.50 | 17-SEP-11:53 | 835.45 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.65 | 01-OCT-14:50 | 2171.75 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.15 | 19-NOV-15:00 | 2441.78 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.36 | 25-DEC-15:52 | 2099.31 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2707.62 | 2949.51 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.21 | 16-JAN-11:53 | 2104.79 | 01-JAN-01:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2928.87 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 | 18-MAR-17:02 | 2458.69 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.03 | 30-APR-16:00 | 1284.43 | 26-APR-21:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.88 | 20-MAY-17:01 | 1054.44 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2405.35 | 17-JUN-17:02 | 534.35 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2823.52 | 22-JUL-18:00 | 944.41 | 26-JUL-23:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2313.35 | 13-AUG-16:00 | 1389.30 | 05-AUG-17:42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.77 | 17-SEP-11:53 | 997.31 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.91 | 01-OCT-14:20 | 2816.92 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.55 | 19-NOV-15:00 | 2439.39 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.82 | 25-DEC-16:00 | 2048.48 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2823.52 | 2928.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 121672.61 | 23-JAN-05:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 120121.03 | 13-FEB-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 121228.48 | 20-MAR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 122403.29 | 24-APR-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120894.17 | 22-MAY-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116081.26 | 12-JUN-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116364.30 | 05-JUL-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111941.02 | 27-AUG-18:16 | 0.00 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113440.74 | 29-SEP-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120368.02 | 30-OCT-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120027.57 | 06-NOV-05:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 121352.30 | 18-DEC-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 111941.02 | 0.00 | 12749.23 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122403.29 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96878.04 | 09-JAN-05:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96592.02 | 21-FEB-05:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99235.40 | 20-MAR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96535.19 | 27-APR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 100533.47 | 30-MAY-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99829.03 | 12-JUN-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92738.58 | 05-JUL-05:03 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93995.55 | 14-AUG-05:05 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97141.20 | 21-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 102075.22 | 23-OCT-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102931.32 | 13-NOV-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102291.63 | 04-DEC-05:11 | 0.00 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92738.58 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102931.32 | 9673.43 | 18321.59 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84184.78 | 20-JAN-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83899.23 | 01-FEB-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85771.34 | 20-MAR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88189.39 | 14-APR-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88717.11 | 19-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87532.78 | 21-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89629.82 | 27-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87783.62 | 30-AUG-04:12 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89404.86 | 26-SEP-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89444.03 | 05-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89242.89 | 13-NOV-05:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81695.84 | 01-DEC-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81695.84 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89629.82 | 8061.19 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 40989.61 | 27-JAN-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39045.11 | 22-FEB-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81743.51 | 17-MAR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86338.94 | 26-APR-04:12 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87510.71 | 25-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87798.02 | 21-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92673.05 | 05-JUL-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88151.86 | 25-AUG-05:03 | 9673.43 | 13741.19 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89152.38 | 14-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88347.55 | 04-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81941.23 | 03-NOV-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38950.36 | 22-DEC-17:00 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 38950.36 | 0.00 | 9160.79 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92673.05 | 15316.26 | 20611.01 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5591.36 | 31-JAN-16:30 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 |
February | 5339.26 | 22-FEB-14:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
March | 7758.74 | 20-MAR-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
April | 14782.05 | 15-APR-05:02 | 1214.60 | 1725.34 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
May | 20143.82 | 29-MAY-18:51 | 0.00 | 525.27 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 154.06 | 0.00 |
June | 21715.70 | 25-JUN-18:01 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 423.62 | 0.00 |
July | 21734.31 | 16-JUL-17:41 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 464.48 | 0.00 |
August | 21688.09 | 27-AUG-15:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 407.69 | 0.00 |
September | 20430.72 | 10-SEP-14:41 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 125.26 | 0.00 |
October | 15696.36 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 0.00 |
November | 7458.42 | 02-NOV-13:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
December | 5548.52 | 26-DEC-15:40 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5339.26 | 0.00 | 478.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21734.31 | 2010.79 | 1725.34 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 464.48 | 35.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7450.08 | 17-JAN-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.09 |
February | 7564.77 | 23-FEB-09:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
March | 8944.97 | 31-MAR-09:10 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
April | 18950.99 | 23-APR-08:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 |
May | 21965.00 | 29-MAY-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 |
June | 21865.65 | 18-JUN-07:21 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 35.42 | 0.00 |
July | 21016.86 | 02-JUL-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
August | 21851.89 | 27-AUG-08:21 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 | 0.00 |
September | 21382.58 | 04-SEP-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
October | 18051.35 | 15-OCT-10:42 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 | 0.00 |
November | 8314.33 | 10-NOV-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
December | 6496.23 | 26-DEC-09:50 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6496.23 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21965.00 | 1295.83 | 793.52 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 | 47.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25772.82 | 29-JAN-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.66 |
February | 16830.85 | 28-FEB-13:40 | 1923.15 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 |
March | 15001.95 | 23-MAR-13:40 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 0.00 |
April | 23024.16 | 02-APR-12:43 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 64.63 | 0.00 |
May | 22262.86 | 21-MAY-14:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 132.81 | 0.00 |
June | 23192.11 | 25-JUN-16:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 186.16 | 0.00 |
July | 23894.36 | 16-JUL-15:41 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 166.33 | 0.00 |
August | 25095.12 | 27-AUG-15:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 336.53 | 0.00 |
September | 24791.82 | 04-SEP-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 50.08 | 0.00 |
October | 26040.89 | 15-OCT-12:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 0.00 |
November | 25322.62 | 19-NOV-13:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 |
December | 25006.05 | 10-DEC-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15001.95 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26040.89 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 336.53 | 126.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25981.75 | 29-JAN-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 |
February | 16713.71 | 20-FEB-16:32 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 |
March | 19990.10 | 26-MAR-16:02 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 |
April | 27837.06 | 02-APR-16:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 0.00 |
May | 29420.13 | 21-MAY-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 | 0.00 |
June | 30966.16 | 25-JUN-17:21 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 175.82 | 0.00 |
July | 31152.38 | 16-JUL-17:01 | 0.00 | 440.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 213.21 | 0.00 |
August | 32769.89 | 27-AUG-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 163.45 | 0.00 |
September | 28483.98 | 04-SEP-15:31 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 | 0.00 |
October | 27396.11 | 15-OCT-14:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
November | 26612.49 | 19-NOV-15:02 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 |
December | 25710.10 | 25-DEC-16:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16713.71 | 0.00 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32769.89 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 213.21 | 102.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4064.98 | 31-JAN-17:00 | 1923.11 | 1803.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 | 0.00 |
February | 3126.95 | 22-FEB-16:10 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.87 |
March | 5995.11 | 16-MAR-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 0.00 |
April | 12292.63 | 25-APR-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 |
May | 19675.04 | 21-MAY-18:11 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 321.60 | 0.00 |
June | 21105.18 | 04-JUN-17:21 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 595.55 | 0.00 |
July | 21440.16 | 16-JUL-17:31 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.49 | 0.00 |
August | 21421.16 | 13-AUG-16:11 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.87 | 0.00 |
September | 18191.53 | 17-SEP-12:43 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 987.81 | 0.00 |
October | 14835.96 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 0.00 |
November | 5904.89 | 02-NOV-14:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 0.00 |
December | 3137.41 | 22-DEC-15:40 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3126.95 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21440.16 | 2010.79 | 1803.00 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.87 | 63.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5753.30 | 27-JAN-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
February | 6420.54 | 23-FEB-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 |
March | 8033.82 | 23-MAR-10:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 |
April | 22046.63 | 23-APR-10:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 23119.09 | 21-MAY-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
June | 23131.14 | 04-JUN-08:61 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 0.00 |
July | 23772.19 | 04-JUL-09:31 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 0.00 |
August | 24079.45 | 13-AUG-08:51 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 0.00 |
September | 20671.81 | 10-SEP-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.01 | 0.00 |
October | 20777.96 | 15-OCT-09:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.54 |
November | 7106.57 | 10-NOV-09:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
December | 4082.99 | 27-DEC-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4082.99 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24079.45 | 1239.33 | 793.52 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 161.01 | 103.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24942.64 | 15-JAN-14:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.17 |
February | 22430.40 | 26-FEB-12:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.49 |
March | 14577.20 | 23-MAR-13:50 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 0.00 |
April | 22532.32 | 23-APR-14:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 304.89 | 0.00 |
May | 22000.90 | 21-MAY-16:51 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 654.83 | 0.00 |
June | 23180.23 | 04-JUN-15:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 901.99 | 0.00 |
July | 23431.87 | 16-JUL-16:51 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.19 | 0.00 |
August | 24403.62 | 13-AUG-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.76 | 0.00 |
September | 23726.00 | 10-SEP-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 595.90 | 0.00 |
October | 25742.86 | 15-OCT-12:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 69.55 | 0.00 |
November | 24995.61 | 19-NOV-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.47 |
December | 24941.88 | 03-DEC-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14577.20 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25742.86 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.76 | 474.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12586.01 | 29-JAN-16:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.87 |
February | 10630.25 | 22-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 |
March | 16069.79 | 18-MAR-17:05 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.00 |
April | 24562.53 | 23-APR-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 277.57 | 0.00 |
May | 26664.69 | 21-MAY-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 177.61 | 0.00 |
June | 27695.42 | 04-JUN-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 335.21 | 0.00 |
July | 27579.66 | 16-JUL-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 500.11 | 0.00 |
August | 28165.84 | 13-AUG-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 547.18 | 0.00 |
September | 23352.17 | 04-SEP-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 128.19 | 0.00 |
October | 23620.52 | 15-OCT-15:51 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 | 0.00 |
November | 17284.69 | 19-NOV-15:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 0.00 |
December | 10467.84 | 22-DEC-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10467.84 | 326.14 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28165.84 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 547.18 | 111.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3894.72 | 31-JAN-17:00 | 1923.11 | 1803.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 0.00 |
February | 2982.94 | 22-FEB-16:30 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 |
March | 6432.67 | 16-MAR-16:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 0.00 |
April | 14078.02 | 30-APR-16:11 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 932.85 | 0.00 |
May | 20986.82 | 07-MAY-17:21 | 0.00 | 478.82 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 757.83 | 0.00 |
June | 24719.03 | 04-JUN-17:21 | 0.00 | 684.02 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 695.00 | 0.00 |
July | 23681.98 | 23-JUL-13:32 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 715.59 | 0.00 |
August | 25115.75 | 13-AUG-16:11 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1482.44 | 0.00 |
September | 21233.72 | 17-SEP-12:43 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.54 | 0.00 |
October | 17525.20 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 | 0.00 |
November | 6149.72 | 01-NOV-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 76.48 | 0.00 |
December | 3228.07 | 22-DEC-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2982.94 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25115.75 | 1923.11 | 1803.00 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1482.44 | 90.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4756.29 | 27-JAN-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 |
February | 5394.57 | 23-FEB-10:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.58 |
March | 7379.38 | 23-MAR-10:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 |
April | 20440.19 | 30-APR-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
May | 22546.08 | 14-MAY-09:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 |
June | 23777.23 | 04-JUN-08:61 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
July | 24557.77 | 23-JUL-09:31 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 88.21 | 0.00 |
August | 24801.05 | 13-AUG-08:51 | 521.82 | 352.65 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 | 0.00 |
September | 21325.20 | 10-SEP-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 195.10 | 0.00 |
October | 16746.30 | 15-OCT-09:32 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 |
November | 6357.57 | 01-NOV-10:00 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
December | 3142.54 | 22-DEC-13:30 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3142.54 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24801.05 | 1295.83 | 793.52 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 195.10 | 79.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27850.45 | 29-JAN-14:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.74 |
February | 19289.17 | 26-FEB-14:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.44 |
March | 14696.96 | 16-MAR-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 0.00 |
April | 24971.85 | 30-APR-14:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 792.82 | 0.00 |
May | 24173.81 | 14-MAY-15:41 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 316.17 | 0.00 |
June | 26710.25 | 04-JUN-15:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1054.65 | 0.00 |
July | 26223.91 | 23-JUL-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 684.34 | 0.00 |
August | 28029.09 | 13-AUG-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.01 | 0.00 |
September | 26425.47 | 10-SEP-13:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 717.25 | 0.00 |
October | 26482.87 | 09-OCT-13:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 74.48 | 0.00 |
November | 25109.78 | 19-NOV-14:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 |
December | 25895.71 | 25-DEC-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14696.96 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28029.09 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.01 | 757.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14289.84 | 29-JAN-16:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
February | 10583.04 | 22-FEB-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 |
March | 16495.92 | 18-MAR-17:05 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 |
April | 25953.69 | 23-APR-16:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 0.00 |
May | 27818.46 | 14-MAY-16:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.98 | 0.00 |
June | 30513.30 | 04-JUN-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 0.00 |
July | 27264.81 | 30-JUL-17:31 | 0.00 | 352.65 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 811.56 | 0.00 |
August | 31032.00 | 13-AUG-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 636.95 | 0.00 |
September | 25147.27 | 04-SEP-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 152.08 | 0.00 |
October | 24579.66 | 15-OCT-16:12 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 0.00 |
November | 12717.63 | 01-NOV-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
December | 10417.89 | 22-DEC-16:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10417.89 | 0.00 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31032.00 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 811.56 | 118.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6442.00 | 17-JAN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 |
February | 5800.73 | 22-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 |
March | 7793.85 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.38 |
April | 9775.68 | 24-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 0.00 |
May | 10242.17 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.70 |
June | 12528.47 | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.16 |
July | 14480.85 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
August | 17814.17 | 28-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 0.00 |
September | 15330.49 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
October | 12083.45 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 |
November | 9406.65 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 |
December | 8613.10 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5800.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17814.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 181.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4725.06 | 20-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.47 |
February | 4861.43 | 01-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.06 |
March | 5142.66 | 24-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.59 |
April | 7786.65 | 14-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.70 | 0.00 |
May | 8822.56 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.96 |
June | 10479.45 | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 |
July | 11816.13 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.71 |
August | 10574.22 | 12-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 0.00 |
September | 12006.00 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 |
October | 8908.88 | 02-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.16 | 0.00 |
November | 5474.17 | 04-NOV-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 |
December | 9092.36 | 07-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1878.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4725.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12006.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.16 | 1878.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9635.93 | 31-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 | 0.00 |
February | 8563.84 | 23-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.96 |
March | 13125.95 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.47 | 0.00 |
April | 20883.90 | 14-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 0.00 |
May | 21297.40 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.02 | 0.00 |
June | 25789.91 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.24 | 0.00 |
July | 24167.69 | 20-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.83 | 0.00 |
August | 23823.35 | 15-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.00 | 0.00 |
September | 21461.44 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.42 | 0.00 |
October | 18872.82 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.97 | 0.00 |
November | 12317.93 | 01-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 0.00 |
December | 7498.56 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7498.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25789.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.24 | 188.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2353.98 | 24-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4175.52 | 27-FEB-17:40 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7162.96 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7975.33 | 26-APR-18:40 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3512.70 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5423.17 | 30-JUN-23:33 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7321.00 | 31-JUL-23:55 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7869.27 | 14-AUG-02:33 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3522.96 | 30-SEP-23:53 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5336.65 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6352.77 | 14-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8109.81 | 28-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2353.98 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8109.81 | 222.14 | 578.72 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2168.36 | 24-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3883.45 | 27-FEB-17:40 | 70.15 | 321.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6669.40 | 31-MAR-23:50 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7581.11 | 26-APR-18:30 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3405.06 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5233.20 | 30-JUN-23:23 | 0.00 | 96.46 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7013.76 | 31-JUL-23:55 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7393.60 | 06-AUG-18:30 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3409.54 | 30-SEP-24:00 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4897.15 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5972.67 | 14-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7588.91 | 28-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2168.36 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7588.91 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2192.58 | 24-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3866.62 | 22-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6481.04 | 31-MAR-23:20 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7640.16 | 26-APR-18:20 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3408.01 | 31-MAY-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5261.80 | 30-JUN-23:45 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7066.14 | 31-JUL-23:45 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7558.08 | 06-AUG-18:40 | 0.00 | 160.76 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3425.80 | 30-SEP-24:00 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4700.62 | 31-OCT-23:50 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6002.11 | 21-NOV-17:00 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7604.78 | 26-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2192.58 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7640.16 | 222.14 | 578.72 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93341.97 | 18-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184162.73 | 22-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358600.57 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381320.37 | 03-APR-21:01 | 1771.62 | 5033.20 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176203.28 | 31-MAY-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268106.47 | 30-JUN-23:53 | 0.00 | 1437.90 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 355827.01 | 31-JUL-23:20 | 0.00 | 718.95 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 387530.08 | 23-AUG-22:53 | 1012.35 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177459.30 | 30-SEP-23:57 | 0.00 | 1078.42 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269589.48 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278232.29 | 20-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 370404.25 | 25-DEC-16:32 | 1265.44 | 1797.37 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93341.97 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 387530.08 | 4808.68 | 6471.01 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.190368E+13 | 1380227.80 | 27-JAN-16:00 | 0.793080E+11 | 514963.75 | 02-JAN-06:10 |
February | 0.185097E+13 | 1423906.49 | 22-FEB-16:10 | 0.726456E+11 | 412300.11 | 13-FEB-06:10 |
March | 0.268370E+13 | 1780316.70 | 17-MAR-15:50 | 0.768544E+11 | 408578.76 | 27-MAR-05:10 |
April | 0.337270E+13 | 2077285.80 | 12-APR-15:20 | 0.559104E+11 | 73023.54 | 04-APR-11:30 |
May | 0.226494E+13 | 1525540.93 | 17-MAY-15:20 | 0.555624E+11 | 69156.17 | 01-MAY-11:20 |
June | 0.276370E+13 | 1772247.05 | 28-JUN-15:09 | 0.517643E+11 | 64142.25 | 01-JUN-11:39 |
July | 0.317885E+13 | 1932737.63 | 20-JUL-15:09 | 0.497899E+11 | 59959.03 | 06-JUL-11:50 |
August | 0.367525E+13 | 2175351.10 | 25-AUG-15:09 | 0.527757E+11 | 61855.57 | 31-AUG-11:00 |
September | 0.214924E+13 | 1565029.33 | 06-SEP-15:00 | 0.512145E+11 | 66076.30 | 28-SEP-11:00 |
October | 0.245887E+13 | 1678843.77 | 03-OCT-15:00 | 0.580838E+11 | 145497.02 | 25-OCT-06:10 |
November | 0.257795E+13 | 1772301.75 | 20-NOV-16:19 | 0.668748E+11 | 377894.66 | 24-NOV-06:10 |
December | 0.297374E+13 | 1840953.01 | 22-DEC-16:49 | 0.107839E+12 | 501833.87 | 06-DEC-07:10 |
Annual Sum or Average | 0.318536E+14 | 0.778623E+12 | ||||
Minimum of Months | 0.185097E+13 | 1380227.80 | 0.497899E+11 | 59959.03 | ||
Maximum of Months | 0.367525E+13 | 2175351.10 | 0.107839E+12 | 514963.75 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.331573E+12 | 0.708947E+11 | 0.766053E+12 | 0.164270E+12 | 0.198195E+12 | 0.342408E+11 | 0.00 | 0.998234E+11 | 0.502019E+11 | 0.188432E+12 | 0.00 | 0.00 | 0.00 |
February | 0.299877E+12 | 0.600063E+11 | 0.978954E+12 | 0.148382E+12 | 0.174429E+12 | 0.235373E+11 | 0.00 | 0.504362E+11 | 0.225609E+11 | 0.927877E+11 | 0.00 | 0.00 | 0.00 |
March | 0.352580E+12 | 0.604266E+11 | 0.141687E+13 | 0.164522E+12 | 0.207902E+12 | 0.374609E+11 | 0.00 | 0.183815E+12 | 0.685735E+11 | 0.191547E+12 | 0.00 | 0.00 | 0.00 |
April | 0.313305E+12 | 0.523288E+11 | 0.165903E+13 | 0.158945E+12 | 0.248720E+12 | 0.626479E+11 | 0.00 | 0.499597E+12 | 0.123380E+12 | 0.254752E+12 | 0.00 | 0.00 | 0.00 |
May | 0.336964E+12 | 0.487838E+11 | 0.774844E+12 | 0.164394E+12 | 0.273148E+12 | 0.645850E+11 | 0.00 | 0.332574E+12 | 0.129238E+12 | 0.140407E+12 | 0.00 | 0.00 | 0.00 |
June | 0.334260E+12 | 0.450046E+11 | 0.106252E+13 | 0.159182E+12 | 0.301074E+12 | 0.822911E+11 | 0.00 | 0.557786E+12 | 0.154253E+12 | 0.673272E+11 | 0.00 | 0.00 | 0.00 |
July | 0.313873E+12 | 0.473327E+11 | 0.139340E+13 | 0.164156E+12 | 0.289485E+12 | 0.829438E+11 | 0.00 | 0.689005E+12 | 0.178611E+12 | 0.200360E+11 | 0.00 | 0.00 | 0.00 |
August | 0.350892E+12 | 0.516858E+11 | 0.173200E+13 | 0.164522E+12 | 0.300963E+12 | 0.852467E+11 | 0.00 | 0.767057E+12 | 0.180191E+12 | 0.426925E+11 | 0.00 | 0.00 | 0.00 |
September | 0.314463E+12 | 0.557491E+11 | 0.740713E+12 | 0.158944E+12 | 0.259775E+12 | 0.674847E+11 | 0.00 | 0.367780E+12 | 0.164834E+12 | 0.194929E+11 | 0.00 | 0.00 | 0.00 |
October | 0.328987E+12 | 0.640196E+11 | 0.108340E+13 | 0.164269E+12 | 0.229317E+12 | 0.513044E+11 | 0.00 | 0.274825E+12 | 0.105596E+12 | 0.157154E+12 | 0.00 | 0.00 | 0.00 |
November | 0.327187E+12 | 0.673228E+11 | 0.135889E+13 | 0.159043E+12 | 0.200500E+12 | 0.359356E+11 | 0.00 | 0.184856E+12 | 0.696485E+11 | 0.174560E+12 | 0.00 | 0.00 | 0.00 |
December | 0.322201E+12 | 0.725876E+11 | 0.170972E+13 | 0.164159E+12 | 0.194479E+12 | 0.281752E+11 | 0.00 | 0.165258E+12 | 0.545652E+11 | 0.262597E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392616E+13 | 0.696142E+12 | 0.146764E+14 | 0.193479E+13 | 0.287799E+13 | 0.655854E+12 | 0.00 | 0.417281E+13 | 0.130165E+13 | 0.161179E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299877E+12 | 0.450046E+11 | 0.740713E+12 | 0.148382E+12 | 0.174429E+12 | 0.235373E+11 | 0.00 | 0.504362E+11 | 0.225609E+11 | 0.194929E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352580E+12 | 0.725876E+11 | 0.173200E+13 | 0.164522E+12 | 0.301074E+12 | 0.852467E+11 | 0.00 | 0.767057E+12 | 0.180191E+12 | 0.262597E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.163143E+11 | 0.00 | 0.629937E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.158934E+11 | 0.00 | 0.567522E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.135943E+11 | 0.00 | 0.632601E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 46915271.83 | 0.00 | 0.558635E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.555624E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.517643E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.497899E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.527757E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.512145E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.220954E+10 | 0.00 | 0.558743E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.918385E+10 | 0.00 | 0.576910E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.470498E+11 | 0.00 | 0.607891E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104292E+12 | 0.00 | 0.674331E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.497899E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.470498E+11 | 0.00 | 0.632601E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 20-JAN-16:00 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118530.30 | 20-JAN-08:39 | 172154.83 | 31-JAN-16:49 | 49208.72 | 31-JAN-15:20 | 0.00 | 01-JAN-00:10 |
February | 372703.55 | 10-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118525.16 | 10-FEB-08:20 | 159154.46 | 22-FEB-16:30 | 26969.70 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 368068.25 | 21-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118521.54 | 21-MAR-07:19 | 193551.30 | 16-MAR-15:30 | 51337.99 | 20-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 350435.97 | 04-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118507.77 | 04-APR-07:19 | 251408.62 | 14-APR-15:09 | 49405.48 | 14-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 337010.14 | 26-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118497.31 | 26-MAY-07:19 | 252821.32 | 18-MAY-15:20 | 49339.69 | 18-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 334652.50 | 01-JUN-07:10 | 57580.60 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 118495.47 | 01-JUN-07:19 | 285016.27 | 28-JUN-14:50 | 55970.70 | 19-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 343695.39 | 27-JUL-07:10 | 57580.60 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 118502.52 | 27-JUL-07:19 | 272738.44 | 21-JUL-15:20 | 51751.86 | 06-JUL-09:09 | 0.00 | 01-JUL-00:10 |
August | 372703.55 | 04-AUG-07:10 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118525.16 | 04-AUG-07:19 | 273790.28 | 25-AUG-14:00 | 54323.90 | 23-AUG-15:09 | 0.00 | 01-AUG-00:10 |
September | 354009.91 | 29-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118510.56 | 29-SEP-07:19 | 260360.23 | 05-SEP-15:00 | 56932.35 | 28-SEP-13:50 | 0.00 | 01-SEP-00:10 |
October | 366848.93 | 27-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118520.58 | 27-OCT-07:19 | 233611.31 | 02-OCT-15:39 | 54968.25 | 05-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 28-NOV-16:30 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118521.40 | 01-NOV-07:19 | 187336.80 | 02-NOV-15:50 | 51625.65 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:30 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118525.16 | 12-DEC-08:20 | 158534.67 | 22-DEC-16:49 | 27000.15 | 05-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 334652.50 | 57580.60 | 423497.50 | 118495.47 | 158534.67 | 26969.70 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118530.30 | 285016.27 | 56932.35 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 262342.62 | 31-JAN-15:30 | 52928.19 | 31-JAN-16:30 | 100000.00 | 01-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 129992.27 | 22-FEB-15:00 | 50509.16 | 22-FEB-15:00 | 100000.00 | 01-FEB-22:10 | 0.00 | 0.00 | 0.00 |
March | 372437.85 | 20-MAR-14:20 | 68492.33 | 10-MAR-15:09 | 100000.00 | 08-MAR-05:30 | 0.00 | 0.00 | 0.00 |
April | 421316.20 | 14-APR-15:09 | 87736.39 | 10-APR-14:30 | 100000.00 | 01-APR-04:30 | 0.00 | 0.00 | 0.00 |
May | 308226.45 | 18-MAY-15:30 | 87736.39 | 09-MAY-12:00 | 100000.00 | 01-MAY-02:20 | 0.00 | 0.00 | 0.00 |
June | 420134.35 | 19-JUN-14:20 | 87736.39 | 01-JUN-08:39 | 100000.00 | 01-JUN-00:30 | 0.00 | 0.00 | 0.00 |
July | 473667.20 | 19-JUL-13:39 | 87736.39 | 01-JUL-15:09 | 100000.00 | 01-JUL-00:40 | 0.00 | 0.00 | 0.00 |
August | 487904.20 | 11-AUG-15:50 | 87736.39 | 01-AUG-06:49 | 100000.00 | 10-AUG-21:49 | 0.00 | 0.00 | 0.00 |
September | 360232.77 | 01-SEP-12:20 | 87736.39 | 01-SEP-06:49 | 100000.00 | 15-SEP-21:10 | 0.00 | 0.00 | 0.00 |
October | 365106.79 | 02-OCT-13:00 | 87736.39 | 02-OCT-08:09 | 100000.00 | 05-OCT-21:19 | 0.00 | 0.00 | 0.00 |
November | 354150.41 | 01-NOV-15:20 | 87736.39 | 01-NOV-12:30 | 100000.00 | 03-NOV-21:10 | 0.00 | 0.00 | 0.00 |
December | 310846.28 | 22-DEC-15:30 | 51553.32 | 22-DEC-15:09 | 100000.00 | 01-DEC-05:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 129992.27 | 50509.16 | 100000.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 487904.20 | 87736.39 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1380227.80 | 27-JAN-16:00 | 343575.76 | 423497.50 | 0.00 | 84452.08 | 170405.11 | 32639.31 | 0.00 | 175319.29 | 50338.74 |
February | 1423906.49 | 22-FEB-16:10 | 334652.47 | 541788.89 | 0.00 | 84451.42 | 158989.99 | 26073.33 | 0.00 | 127483.42 | 50466.96 |
March | 1780316.70 | 17-MAR-15:50 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 177415.96 | 50278.49 | 0.00 | 330392.16 | 55054.50 |
April | 2077285.80 | 12-APR-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 243679.44 | 49244.75 | 0.00 | 401508.46 | 87736.39 |
May | 1525540.93 | 17-MAY-15:20 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 249098.58 | 49295.25 | 0.00 | 297387.99 | 87736.39 |
June | 1772247.05 | 28-JUN-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 255435.99 | 53888.78 | 0.00 | 416651.92 | 87736.39 |
July | 1932737.63 | 20-JUL-15:09 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 269536.12 | 50556.94 | 0.00 | 448082.82 | 87736.39 |
August | 2175351.10 | 25-AUG-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 269526.22 | 49783.30 | 0.00 | 473188.42 | 87736.39 |
September | 1565029.33 | 06-SEP-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 256648.49 | 50520.78 | 0.00 | 329881.10 | 87736.39 |
October | 1678843.77 | 03-OCT-15:00 | 333218.76 | 541788.89 | 0.00 | 84451.06 | 233006.29 | 49835.24 | 0.00 | 348807.14 | 87736.39 |
November | 1772301.75 | 20-NOV-16:19 | 334771.95 | 660080.29 | 0.00 | 84452.08 | 142438.60 | 49057.30 | 0.00 | 348121.16 | 53380.36 |
December | 1840953.01 | 22-DEC-16:49 | 350141.41 | 778371.69 | 0.00 | 84459.03 | 158534.67 | 26326.91 | 0.00 | 292086.67 | 51032.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1380227.80 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 142438.60 | 26073.33 | 0.00 | 127483.42 | 50338.74 | |
Maximum of Months | 2175351.10 | 350141.41 | 778371.69 | 0.00 | 84459.03 | 269536.12 | 53888.78 | 0.00 | 473188.42 | 87736.39 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 498515.56 | 02-JAN-06:10 | 0.00 | 77703.73 | 20-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 404153.53 | 13-FEB-06:10 | 0.00 | 77605.17 | 02-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 379628.67 | 27-MAR-05:10 | 0.00 | 76367.61 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 6820.19 | 21-APR-05:49 | 0.00 | 73023.54 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 69156.17 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 64142.25 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 59959.03 | 06-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 61855.57 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 66076.30 | 28-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 119875.66 | 25-OCT-06:30 | 0.00 | 69473.59 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 369748.08 | 24-NOV-06:10 | 0.00 | 73781.64 | 20-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 470914.74 | 06-DEC-07:10 | 0.00 | 76568.38 | 19-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59959.03 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 498515.56 | 0.00 | 77703.73 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.92 | 1.33 | 27.02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.70 | 0.00 | 26.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.73 | 0.00 | 25.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.38 | 0.00 | 26.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.34 | 0.00 | 26.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.26 | 0.00 | 26.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 25.97 | 0.00 | 25.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.08 | 0.50 | 26.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.34 | 0.67 | 26.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.78 | 1.67 | 26.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.68 | 1.00 | 26.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.63 | 1.33 | 26.73 |
Annual Sum or Average | 0.00 | 0.00 | 71.67 | 26.45 | 6.50 | 26.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.92 | 1.67 | 27.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.75 | 0.00 | 25.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.81 | 0.00 | 25.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.64 | 0.00 | 25.64 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 25.68 | 0.00 | 25.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.81 | 0.00 | 25.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.35 | 5.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.23 | 8.00 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.08 | 5.17 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.16 | 2.33 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.17 | 1.00 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.50 | 27.21 | 21.67 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.35 | 8.00 | 27.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.96 | 6.50 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.97 | 10.33 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.07 | 10.50 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.91 | 12.17 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.87 | 7.83 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.68 | 6.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 3.50 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.50 | 27.91 | 59.17 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.07 | 12.17 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.09 | 8.00 | 28.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.64 | 1.67 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 7.00 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.43 | 3.50 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.41 | 4.50 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.33 | 9.50 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.31 | 6.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.65 | 7.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.01 | 9.00 | 28.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.01 | 6.83 | 28.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.24 | 7.67 | 28.24 |
Annual Sum or Average | 0.00 | 0.00 | 91.33 | 27.68 | 71.83 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.24 | 9.50 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.92 | 2.17 | 27.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.88 | 0.67 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.70 | 2.33 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 27.87 | 10.50 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.33 | 6.67 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.67 | 7.17 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 27.73 | 13.17 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 27.90 | 17.67 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.34 | 5.83 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.71 | 6.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.94 | 4.00 | 27.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.12 | 3.67 | 28.12 |
Annual Sum or Average | 0.00 | 0.00 | 207.83 | 27.82 | 79.83 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 28.33 | 17.67 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.33 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.48 | 4.67 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.37 | 6.00 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.45 | 3.50 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.47 | 2.17 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.45 | 0.67 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 0.67 | 19.21 | 0.00 | 19.21 | 29.67 | 27.25 | 17.33 | 27.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.30 | 0.00 | 19.30 | 10.67 | 27.48 | 6.00 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.94 | 8.17 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.97 | 13.00 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.17 | 11.17 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.08 | 13.67 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.17 | 8.17 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.79 | 8.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.72 | 3.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 0.50 | 19.21 | 0.00 | 19.21 | 74.00 | 27.97 | 65.83 | 28.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.26 | 0.00 | 19.26 | 16.33 | 28.17 | 13.67 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.81 | 8.33 | 27.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.71 | 6.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.43 | 3.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.55 | 4.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.50 | 8.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.59 | 5.50 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.26 | 9.00 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.08 | 12.17 | 27.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.80 | 10.33 | 26.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.20 | 7.17 | 28.20 |
Annual Sum or Average | 0.00 | 0.00 | 90.00 | 27.44 | 76.17 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.80 | 0.33 | 26.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.20 | 12.17 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.72 | 0.33 | 27.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.65 | 0.17 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.44 | 4.17 | 28.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.56 | 5.00 | 28.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.20 | 4.83 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.09 | 6.67 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.05 | 5.00 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.14 | 4.50 | 28.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.10 | 3.00 | 28.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.64 | 0.50 | 27.64 |
December | 0.17 | 19.37 | 0.00 | 19.37 | 0.50 | 25.55 | 0.50 | 26.43 |
Annual Sum or Average | 0.17 | 19.37 | 0.00 | 19.37 | 74.17 | 28.18 | 34.67 | 28.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.37 | 0.00 | 19.37 | 17.00 | 28.56 | 6.67 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 16.72 | 0.67 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
February | 0.83 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.67 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.46 | 1.67 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.64 | 6.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.51 | 9.00 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.58 | 4.67 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.58 | 4.00 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.53 | 1.17 | 27.54 |
November | 0.67 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
December | 3.50 | 18.50 | 0.17 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
Annual Sum or Average | 7.67 | 18.22 | 0.83 | 18.00 | 49.00 | 26.15 | 27.33 | 26.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 | 16.61 |
Maximum of Months | 3.50 | 19.25 | 0.67 | 19.25 | 16.83 | 27.64 | 9.00 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 16.97 | 0.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
February | 0.67 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.92 | 8.67 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 28.03 | 12.67 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.26 | 11.50 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 28.12 | 14.33 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.17 | 8.50 | 28.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.96 | 8.67 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.72 | 3.00 | 27.73 |
November | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
December | 3.17 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Annual Sum or Average | 5.67 | 18.53 | 0.33 | 18.33 | 86.17 | 27.45 | 67.33 | 27.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 0.00 | 16.48 |
Maximum of Months | 3.17 | 19.31 | 0.33 | 19.31 | 20.00 | 28.26 | 14.33 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.21 | 0.00 | 18.21 | 5.67 | 27.29 | 5.67 | 27.67 |
February | 0.17 | 19.03 | 0.00 | 19.03 | 0.17 | 23.31 | 0.17 | 24.74 |
March | 0.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.83 | 6.00 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.55 | 5.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.69 | 6.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.58 | 9.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.85 | 5.50 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.03 | 7.17 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.06 | 7.67 | 28.15 |
November | 0.17 | 19.16 | 0.00 | 19.16 | 4.33 | 27.56 | 4.33 | 27.72 |
December | 1.33 | 18.91 | 0.00 | 18.91 | 4.83 | 26.06 | 4.83 | 26.93 |
Annual Sum or Average | 2.33 | 18.80 | 0.00 | 18.80 | 85.83 | 27.58 | 62.50 | 27.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | 0.00 | 19.04 |
Maximum of Months | 1.33 | 19.16 | 0.00 | 19.16 | 16.17 | 28.06 | 9.50 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
February | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
March | 0.17 | 19.21 | 0.00 | 19.21 | 0.33 | 24.84 | 0.17 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.46 | 4.67 | 28.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.65 | 5.33 | 28.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.26 | 6.17 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 28.20 | 8.33 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.18 | 5.67 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.26 | 4.83 | 28.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.15 | 3.17 | 28.19 |
November | 0.17 | 19.04 | 0.00 | 19.04 | 0.17 | 23.25 | 0.17 | 24.65 |
December | 1.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 2.17 | 18.68 | 0.00 | 18.68 | 84.67 | 28.06 | 38.50 | 28.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 | 0.00 | 17.39 |
Maximum of Months | 1.33 | 19.29 | 0.00 | 19.29 | 20.83 | 28.65 | 8.33 | 28.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 307.50 | 28.81 | 250.17 | 28.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 275.83 | 28.73 | 233.50 | 28.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.03 | 12.00 | 28.03 |
Annual Sum or Average | 0.00 | 0.00 | 595.33 | 28.76 | 495.67 | 28.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 307.50 | 28.81 | 250.17 | 28.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 277.33 | 28.64 | 226.17 | 28.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 231.00 | 28.57 | 201.67 | 28.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.80 | 2.33 | 27.80 |
Annual Sum or Average | 0.00 | 0.00 | 510.67 | 28.60 | 430.17 | 28.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 277.33 | 28.64 | 226.17 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 227.00 | 28.69 | 185.33 | 28.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 189.83 | 28.67 | 162.50 | 28.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.67 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 417.50 | 28.68 | 348.50 | 28.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 227.00 | 28.69 | 185.33 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 310.50 | 31.45 | 277.67 | 31.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 28.30 | 20.67 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 663.17 | 31.04 | 484.83 | 31.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.11 | 9.17 | 28.11 |
Annual Sum or Average | 0.00 | 0.00 | 1026.33 | 31.03 | 792.33 | 31.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 663.17 | 31.45 | 484.83 | 31.53 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.83 | 24.00 | 120.00 | 25.64 | 0.00 | 25.64 |
February | 14.33 | 24.00 | 220.17 | 24.96 | 0.00 | 24.96 |
March | 70.50 | 24.00 | 120.50 | 24.99 | 0.00 | 24.99 |
April | 74.17 | 24.00 | 96.00 | 25.42 | 0.00 | 25.42 |
May | 79.33 | 24.00 | 91.83 | 25.32 | 0.00 | 25.32 |
June | 14.83 | 24.00 | 130.17 | 25.58 | 0.00 | 25.58 |
July | 157.17 | 24.40 | 419.33 | 24.66 | 146.67 | 24.61 |
August | 137.50 | 24.60 | 457.83 | 24.57 | 137.50 | 24.58 |
September | 105.00 | 24.93 | 409.67 | 24.74 | 105.00 | 24.77 |
October | 37.33 | 24.12 | 232.00 | 25.18 | 8.83 | 25.15 |
November | 34.67 | 25.12 | 219.33 | 25.36 | 22.83 | 25.39 |
December | 107.83 | 24.00 | 109.17 | 25.29 | 0.00 | 25.29 |
Annual Sum or Average | 882.50 | 24.32 | 2626.00 | 24.98 | 420.83 | 24.95 |
Minimum of Months | 14.33 | 24.00 | 91.83 | 24.57 | 0.00 | 24.58 |
Maximum of Months | 157.17 | 25.12 | 457.83 | 25.64 | 146.67 | 25.64 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.17 | 23.99 | 74.00 | 24.77 | 0.00 | 24.77 |
February | 18.33 | 23.94 | 209.00 | 24.65 | 0.00 | 24.65 |
March | 49.50 | 24.01 | 132.17 | 24.72 | 0.00 | 24.72 |
April | 44.83 | 24.01 | 48.67 | 24.52 | 0.00 | 24.52 |
May | 51.33 | 24.01 | 38.00 | 24.81 | 0.00 | 24.81 |
June | 2.83 | 24.00 | 126.17 | 24.44 | 0.00 | 24.44 |
July | 11.50 | 24.02 | 403.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 459.83 | 24.24 | 0.00 | 24.24 |
September | 10.83 | 26.30 | 409.33 | 24.43 | 10.83 | 24.48 |
October | 39.00 | 24.01 | 222.83 | 24.67 | 0.00 | 24.67 |
November | 37.17 | 24.41 | 188.17 | 24.81 | 6.17 | 24.85 |
December | 141.67 | 24.00 | 78.67 | 24.70 | 0.00 | 24.70 |
Annual Sum or Average | 490.17 | 24.08 | 2389.83 | 24.51 | 17.00 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 38.00 | 24.24 | 0.00 | 24.24 |
Maximum of Months | 141.67 | 26.30 | 459.83 | 24.81 | 10.83 | 24.85 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.67 | 23.61 | 18.00 | 23.69 | 0.00 | 23.69 |
February | 143.50 | 23.59 | 81.17 | 23.88 | 0.00 | 23.88 |
March | 176.50 | 23.82 | 59.17 | 24.08 | 0.00 | 24.08 |
April | 161.50 | 23.95 | 19.67 | 24.16 | 0.00 | 24.16 |
May | 135.67 | 24.00 | 24.67 | 24.30 | 0.00 | 24.30 |
June | 33.67 | 23.97 | 67.50 | 24.23 | 0.00 | 24.23 |
July | 24.33 | 24.05 | 377.17 | 24.19 | 1.50 | 24.19 |
August | 19.33 | 24.33 | 435.33 | 24.19 | 9.33 | 24.20 |
September | 20.50 | 25.73 | 390.00 | 24.40 | 19.50 | 24.47 |
October | 139.67 | 23.90 | 142.33 | 24.23 | 0.50 | 24.23 |
November | 239.17 | 23.86 | 120.50 | 24.10 | 20.67 | 24.12 |
December | 406.83 | 23.76 | 0.50 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 1779.33 | 23.83 | 1736.00 | 24.09 | 51.50 | 24.11 |
Minimum of Months | 19.33 | 23.59 | 0.50 | 23.69 | 0.00 | 23.69 |
Maximum of Months | 406.83 | 25.73 | 435.33 | 24.40 | 20.67 | 24.47 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.00 | 23.02 | 19.17 | 22.87 | 18.17 | 22.72 |
February | 328.67 | 22.84 | 22.50 | 22.88 | 3.67 | 22.86 |
March | 304.00 | 23.33 | 29.33 | 23.35 | 6.83 | 23.30 |
April | 172.17 | 23.84 | 25.33 | 23.98 | 0.00 | 23.98 |
May | 132.00 | 23.98 | 29.50 | 24.25 | 0.00 | 24.25 |
June | 20.50 | 23.97 | 130.33 | 24.35 | 0.00 | 24.35 |
July | 24.67 | 24.03 | 399.33 | 24.26 | 7.17 | 24.26 |
August | 31.67 | 24.21 | 445.83 | 24.22 | 24.50 | 24.22 |
September | 37.00 | 25.00 | 401.83 | 24.42 | 36.33 | 24.47 |
October | 215.50 | 23.61 | 122.67 | 23.89 | 3.83 | 23.89 |
November | 320.67 | 23.14 | 94.67 | 23.39 | 23.67 | 23.40 |
December | 468.67 | 22.72 | 34.33 | 22.59 | 34.33 | 22.47 |
Annual Sum or Average | 2471.50 | 23.21 | 1754.83 | 23.62 | 158.50 | 23.59 |
Minimum of Months | 20.50 | 22.72 | 19.17 | 22.59 | 0.00 | 22.47 |
Maximum of Months | 468.67 | 25.00 | 445.83 | 24.42 | 36.33 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.33 | 23.31 | 7.83 | 23.33 | 0.00 | 23.33 |
February | 337.00 | 23.12 | 11.50 | 23.15 | 0.00 | 23.15 |
March | 289.67 | 23.36 | 38.50 | 23.50 | 0.00 | 23.50 |
April | 116.00 | 23.88 | 79.33 | 24.32 | 0.00 | 24.32 |
May | 53.50 | 23.98 | 100.50 | 24.85 | 0.00 | 24.85 |
June | 14.17 | 26.47 | 320.00 | 24.71 | 11.67 | 24.79 |
July | 33.83 | 26.53 | 459.17 | 24.68 | 32.33 | 24.80 |
August | 22.83 | 26.62 | 480.83 | 24.49 | 21.17 | 24.58 |
September | 33.50 | 26.37 | 434.17 | 24.63 | 33.50 | 24.74 |
October | 195.83 | 23.70 | 148.17 | 24.07 | 2.33 | 24.09 |
November | 320.33 | 23.49 | 84.33 | 23.67 | 13.67 | 23.71 |
December | 462.67 | 23.23 | 6.00 | 23.20 | 6.00 | 23.17 |
Annual Sum or Average | 2333.67 | 23.52 | 2170.33 | 24.01 | 120.67 | 24.07 |
Minimum of Months | 14.17 | 23.12 | 6.00 | 23.15 | 0.00 | 23.15 |
Maximum of Months | 462.67 | 26.62 | 480.83 | 24.85 | 33.50 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 306.67 | 23.05 | 35.67 | 23.27 | 0.00 | 23.27 |
February | 275.67 | 22.80 | 63.67 | 23.11 | 1.83 | 23.13 |
March | 239.83 | 23.08 | 99.17 | 23.50 | 2.50 | 23.50 |
April | 92.67 | 24.03 | 192.00 | 24.49 | 13.17 | 24.61 |
May | 44.33 | 25.20 | 253.33 | 24.85 | 18.67 | 24.99 |
June | 37.33 | 26.70 | 387.83 | 24.69 | 32.67 | 24.86 |
July | 47.67 | 26.74 | 466.17 | 24.71 | 46.00 | 24.88 |
August | 36.83 | 26.58 | 483.83 | 24.48 | 32.83 | 24.63 |
September | 47.00 | 26.23 | 446.17 | 24.65 | 42.83 | 24.79 |
October | 152.33 | 23.58 | 216.33 | 24.20 | 9.83 | 24.28 |
November | 262.83 | 23.18 | 108.00 | 23.53 | 15.33 | 23.56 |
December | 395.50 | 22.92 | 22.33 | 22.97 | 9.00 | 22.92 |
Annual Sum or Average | 1938.67 | 23.45 | 2774.50 | 24.08 | 224.67 | 24.19 |
Minimum of Months | 36.83 | 22.80 | 22.33 | 22.97 | 0.00 | 22.92 |
Maximum of Months | 395.50 | 26.74 | 483.83 | 24.85 | 46.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.67 | 23.72 | 202.83 | 24.22 | 22.83 | 24.35 |
February | 209.17 | 23.03 | 146.33 | 23.59 | 4.00 | 23.63 |
March | 185.00 | 23.17 | 145.17 | 23.72 | 3.00 | 23.70 |
April | 95.83 | 24.04 | 181.33 | 24.48 | 6.50 | 24.56 |
May | 71.17 | 23.90 | 139.83 | 24.63 | 0.17 | 24.63 |
June | 21.33 | 25.60 | 294.67 | 24.66 | 11.33 | 24.74 |
July | 38.00 | 26.35 | 449.83 | 24.65 | 32.83 | 24.78 |
August | 29.67 | 26.73 | 487.50 | 24.52 | 27.33 | 24.65 |
September | 45.83 | 26.70 | 449.00 | 24.75 | 45.83 | 24.92 |
October | 119.17 | 24.45 | 285.33 | 24.64 | 31.67 | 24.82 |
November | 156.83 | 23.88 | 259.33 | 24.30 | 29.33 | 24.40 |
December | 247.50 | 23.50 | 140.83 | 23.99 | 26.50 | 24.09 |
Annual Sum or Average | 1420.17 | 23.87 | 3182.00 | 24.36 | 241.33 | 24.47 |
Minimum of Months | 21.33 | 23.03 | 139.83 | 23.59 | 0.17 | 23.63 |
Maximum of Months | 247.50 | 26.73 | 487.50 | 24.75 | 45.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 262.50 | 23.29 | 95.00 | 23.68 | 3.50 | 23.71 |
February | 145.67 | 23.19 | 162.67 | 23.87 | 2.17 | 23.89 |
March | 80.50 | 23.62 | 247.33 | 24.40 | 5.50 | 24.44 |
April | 37.50 | 26.71 | 348.83 | 24.99 | 31.50 | 25.16 |
May | 35.33 | 26.02 | 278.67 | 24.99 | 22.50 | 25.14 |
June | 30.00 | 27.09 | 426.83 | 24.73 | 30.00 | 24.87 |
July | 71.83 | 26.80 | 481.67 | 24.93 | 71.83 | 25.14 |
August | 107.17 | 26.23 | 509.00 | 24.85 | 107.17 | 25.05 |
September | 46.67 | 26.80 | 467.00 | 24.76 | 46.67 | 24.93 |
October | 81.00 | 24.48 | 297.33 | 24.72 | 22.00 | 24.85 |
November | 94.67 | 24.27 | 233.33 | 24.61 | 21.17 | 24.74 |
December | 170.67 | 23.76 | 119.67 | 24.35 | 8.17 | 24.43 |
Annual Sum or Average | 1163.50 | 24.45 | 3667.33 | 24.62 | 372.17 | 24.77 |
Minimum of Months | 30.00 | 23.19 | 95.00 | 23.68 | 2.17 | 23.71 |
Maximum of Months | 262.50 | 27.09 | 509.00 | 24.99 | 107.17 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.22 | 49.83 | 22.02 | 49.83 | 21.86 |
February | 440.33 | 22.05 | 13.00 | 22.01 | 13.00 | 21.96 |
March | 431.50 | 22.62 | 30.17 | 22.53 | 24.67 | 22.44 |
April | 214.00 | 23.60 | 32.83 | 23.80 | 0.00 | 23.80 |
May | 101.17 | 23.90 | 70.17 | 24.58 | 0.00 | 24.58 |
June | 15.00 | 26.12 | 285.00 | 24.81 | 10.50 | 24.89 |
July | 42.33 | 26.04 | 450.83 | 24.70 | 39.67 | 24.81 |
August | 35.50 | 25.50 | 466.67 | 24.46 | 29.50 | 24.54 |
September | 46.83 | 25.52 | 412.00 | 24.60 | 38.83 | 24.70 |
October | 287.50 | 23.06 | 110.83 | 23.42 | 4.33 | 23.41 |
November | 431.00 | 22.46 | 90.67 | 22.49 | 64.67 | 22.43 |
December | 497.00 | 21.67 | 157.17 | 21.44 | 157.17 | 21.30 |
Annual Sum or Average | 3044.17 | 22.59 | 2169.17 | 23.19 | 432.17 | 23.12 |
Minimum of Months | 15.00 | 21.67 | 13.00 | 21.44 | 0.00 | 21.30 |
Maximum of Months | 502.00 | 26.12 | 466.67 | 24.81 | 157.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 367.33 | 22.40 | 35.00 | 22.31 | 27.33 | 22.18 |
February | 317.17 | 22.13 | 29.17 | 22.29 | 5.00 | 22.26 |
March | 288.17 | 22.58 | 62.33 | 22.87 | 11.33 | 22.80 |
April | 98.67 | 23.93 | 151.17 | 24.64 | 14.83 | 24.78 |
May | 56.83 | 25.07 | 204.00 | 25.09 | 22.33 | 25.26 |
June | 40.67 | 26.85 | 317.83 | 24.95 | 36.83 | 25.16 |
July | 63.67 | 26.66 | 394.17 | 25.00 | 62.17 | 25.21 |
August | 52.17 | 26.48 | 408.00 | 24.75 | 49.33 | 24.93 |
September | 60.17 | 25.93 | 366.50 | 24.82 | 50.17 | 24.99 |
October | 185.50 | 23.15 | 154.17 | 23.90 | 10.50 | 23.96 |
November | 312.50 | 22.55 | 68.50 | 22.71 | 33.67 | 22.67 |
December | 410.67 | 22.03 | 86.33 | 21.81 | 86.33 | 21.66 |
Annual Sum or Average | 2253.50 | 22.93 | 2277.17 | 23.70 | 409.83 | 23.77 |
Minimum of Months | 40.67 | 22.03 | 29.17 | 21.81 | 5.00 | 21.66 |
Maximum of Months | 410.67 | 26.85 | 408.00 | 25.09 | 86.33 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.17 | 23.29 | 196.83 | 23.89 | 27.83 | 23.99 |
February | 261.50 | 22.49 | 126.83 | 23.11 | 5.50 | 23.13 |
March | 253.67 | 22.76 | 119.17 | 23.20 | 13.17 | 23.12 |
April | 131.17 | 23.63 | 156.00 | 24.27 | 3.67 | 24.32 |
May | 102.17 | 23.77 | 114.00 | 24.53 | 0.00 | 24.53 |
June | 26.50 | 25.09 | 265.33 | 24.73 | 9.67 | 24.80 |
July | 50.50 | 25.89 | 442.17 | 24.69 | 43.83 | 24.81 |
August | 45.00 | 25.89 | 479.67 | 24.54 | 38.83 | 24.66 |
September | 54.00 | 26.37 | 438.50 | 24.78 | 50.67 | 24.94 |
October | 152.33 | 23.98 | 263.50 | 24.45 | 29.33 | 24.63 |
November | 209.17 | 23.32 | 225.00 | 23.93 | 39.83 | 24.00 |
December | 285.00 | 22.90 | 142.17 | 23.35 | 44.50 | 23.34 |
Annual Sum or Average | 1803.17 | 23.41 | 2969.17 | 24.13 | 306.83 | 24.21 |
Minimum of Months | 26.50 | 22.49 | 114.00 | 23.11 | 0.00 | 23.12 |
Maximum of Months | 285.00 | 26.37 | 479.67 | 24.78 | 50.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 394.33 | 22.22 | 53.33 | 22.33 | 16.67 | 22.25 |
February | 384.67 | 22.04 | 28.50 | 22.16 | 4.17 | 22.14 |
March | 350.67 | 22.53 | 83.17 | 22.78 | 15.67 | 22.72 |
April | 133.83 | 23.82 | 185.00 | 24.39 | 16.50 | 24.53 |
May | 94.67 | 24.39 | 211.33 | 24.77 | 20.00 | 24.92 |
June | 26.33 | 26.57 | 352.83 | 24.77 | 21.83 | 24.90 |
July | 53.00 | 26.61 | 460.67 | 24.80 | 50.17 | 24.97 |
August | 39.83 | 26.48 | 488.83 | 24.59 | 38.33 | 24.72 |
September | 53.00 | 25.80 | 432.33 | 24.67 | 44.00 | 24.80 |
October | 229.50 | 23.11 | 185.00 | 23.76 | 10.83 | 23.84 |
November | 338.00 | 22.51 | 116.50 | 22.87 | 35.33 | 22.87 |
December | 441.67 | 21.93 | 95.17 | 21.83 | 82.33 | 21.69 |
Annual Sum or Average | 2539.50 | 22.75 | 2692.67 | 23.60 | 355.83 | 23.64 |
Minimum of Months | 26.33 | 21.93 | 28.50 | 21.83 | 4.17 | 21.69 |
Maximum of Months | 441.67 | 26.61 | 488.83 | 24.80 | 82.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.62 | 125.17 | 21.32 | 125.17 | 21.12 |
February | 451.00 | 21.42 | 90.50 | 21.20 | 90.50 | 21.05 |
March | 453.83 | 22.13 | 68.83 | 21.93 | 63.33 | 21.76 |
April | 225.50 | 23.28 | 56.67 | 23.53 | 4.83 | 23.49 |
May | 112.67 | 23.70 | 99.83 | 24.40 | 0.33 | 24.40 |
June | 26.00 | 26.09 | 326.00 | 24.76 | 18.00 | 24.87 |
July | 57.50 | 25.98 | 452.83 | 24.72 | 52.17 | 24.86 |
August | 53.00 | 25.32 | 471.33 | 24.47 | 45.33 | 24.56 |
September | 77.83 | 25.05 | 416.83 | 24.57 | 56.00 | 24.69 |
October | 317.67 | 22.65 | 134.67 | 22.94 | 38.17 | 22.85 |
November | 448.00 | 21.88 | 152.83 | 21.71 | 136.17 | 21.56 |
December | 497.00 | 21.02 | 276.00 | 20.80 | 276.00 | 20.69 |
Annual Sum or Average | 3222.00 | 22.16 | 2671.50 | 22.73 | 906.00 | 22.57 |
Minimum of Months | 26.00 | 21.02 | 56.67 | 20.80 | 0.33 | 20.69 |
Maximum of Months | 502.00 | 26.09 | 471.33 | 24.76 | 276.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.83 | 22.26 | 67.83 | 22.00 | 65.67 | 21.79 |
February | 396.00 | 21.87 | 56.33 | 21.75 | 46.67 | 21.60 |
March | 346.17 | 22.41 | 68.67 | 22.51 | 25.00 | 22.39 |
April | 104.83 | 23.73 | 214.17 | 24.43 | 16.50 | 24.54 |
May | 64.50 | 24.98 | 290.67 | 24.81 | 25.33 | 24.98 |
June | 47.50 | 26.72 | 414.33 | 24.78 | 41.50 | 24.98 |
July | 70.83 | 26.61 | 470.50 | 24.88 | 68.50 | 25.09 |
August | 59.00 | 26.33 | 492.67 | 24.65 | 55.17 | 24.82 |
September | 71.33 | 25.76 | 442.67 | 24.70 | 56.17 | 24.88 |
October | 211.50 | 22.92 | 198.83 | 23.60 | 25.33 | 23.55 |
November | 382.33 | 22.27 | 100.33 | 22.23 | 74.00 | 22.11 |
December | 497.00 | 21.61 | 163.00 | 21.33 | 163.00 | 21.16 |
Annual Sum or Average | 2714.83 | 22.65 | 2980.00 | 23.38 | 662.83 | 23.35 |
Minimum of Months | 47.50 | 21.61 | 56.33 | 21.33 | 16.50 | 21.16 |
Maximum of Months | 497.00 | 26.72 | 492.67 | 24.88 | 163.00 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 257.17 | 22.68 | 199.00 | 23.19 | 50.67 | 23.10 |
February | 294.00 | 21.91 | 133.50 | 22.29 | 37.50 | 22.12 |
March | 297.67 | 22.39 | 114.00 | 22.66 | 31.83 | 22.50 |
April | 154.33 | 23.36 | 168.00 | 24.07 | 8.17 | 24.12 |
May | 120.33 | 23.62 | 150.67 | 24.34 | 2.17 | 24.37 |
June | 42.17 | 25.12 | 302.67 | 24.68 | 17.00 | 24.79 |
July | 62.67 | 25.77 | 443.67 | 24.70 | 52.00 | 24.84 |
August | 57.83 | 25.62 | 481.83 | 24.53 | 50.33 | 24.65 |
September | 72.17 | 25.72 | 438.17 | 24.74 | 57.33 | 24.90 |
October | 179.50 | 23.50 | 261.00 | 24.11 | 38.00 | 24.22 |
November | 247.50 | 22.71 | 224.17 | 23.25 | 62.83 | 23.15 |
December | 318.83 | 22.32 | 182.33 | 22.49 | 101.00 | 22.29 |
Annual Sum or Average | 2104.17 | 22.98 | 3099.00 | 23.74 | 508.83 | 23.72 |
Minimum of Months | 42.17 | 21.91 | 114.00 | 22.29 | 2.17 | 22.12 |
Maximum of Months | 318.83 | 25.77 | 481.83 | 24.74 | 101.00 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.67 | 21.78 | 98.50 | 21.70 | 71.33 | 21.51 |
February | 396.83 | 21.56 | 68.17 | 21.55 | 47.50 | 21.43 |
March | 377.33 | 22.15 | 99.83 | 22.33 | 36.67 | 22.21 |
April | 161.00 | 23.48 | 189.33 | 24.15 | 19.00 | 24.29 |
May | 117.17 | 24.09 | 226.33 | 24.61 | 21.50 | 24.76 |
June | 35.17 | 26.19 | 372.50 | 24.73 | 25.50 | 24.87 |
July | 66.17 | 26.35 | 458.00 | 24.80 | 59.67 | 24.99 |
August | 51.50 | 26.07 | 486.67 | 24.58 | 46.50 | 24.72 |
September | 74.67 | 25.18 | 429.50 | 24.62 | 52.00 | 24.76 |
October | 251.67 | 22.74 | 191.50 | 23.42 | 25.67 | 23.45 |
November | 363.17 | 22.06 | 144.00 | 22.24 | 78.17 | 22.12 |
December | 454.00 | 21.47 | 187.67 | 21.27 | 178.50 | 21.12 |
Annual Sum or Average | 2754.33 | 22.41 | 2952.00 | 23.23 | 662.00 | 23.18 |
Minimum of Months | 35.17 | 21.47 | 68.17 | 21.27 | 19.00 | 21.12 |
Maximum of Months | 454.00 | 26.35 | 486.67 | 24.80 | 178.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
February | 12.67 | 27.00 | 454.00 | 27.00 | 12.67 | 27.00 |
March | 44.67 | 27.00 | 514.00 | 27.00 | 44.67 | 27.00 |
April | 277.50 | 28.59 | 485.00 | 28.18 | 277.50 | 28.29 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 52.00 | 27.00 | 496.00 | 27.00 | 52.00 | 27.00 |
July | 302.50 | 27.00 | 497.00 | 27.00 | 302.50 | 27.00 |
August | 505.33 | 27.80 | 514.00 | 27.79 | 505.33 | 27.80 |
September | 96.83 | 27.00 | 485.00 | 27.00 | 96.83 | 27.00 |
October | 64.17 | 27.00 | 502.00 | 27.00 | 64.17 | 27.00 |
November | 81.83 | 27.00 | 489.00 | 27.00 | 81.83 | 27.00 |
December | 36.00 | 27.39 | 497.00 | 27.06 | 36.00 | 27.08 |
Annual Sum or Average | 1477.00 | 27.58 | 5943.00 | 27.23 | 1477.00 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 505.33 | 28.59 | 514.00 | 28.18 | 505.33 | 28.29 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.00 | 27.00 | 454.00 | 27.00 | 1.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 171.00 | 28.81 | 485.00 | 28.06 | 171.00 | 28.21 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 11.33 | 27.00 | 496.00 | 27.00 | 11.33 | 27.00 |
July | 88.17 | 27.00 | 497.00 | 27.00 | 88.17 | 27.00 |
August | 258.50 | 28.22 | 514.00 | 27.82 | 258.50 | 27.92 |
September | 25.17 | 27.00 | 485.00 | 27.00 | 25.17 | 27.00 |
October | 14.00 | 27.00 | 502.00 | 27.00 | 14.00 | 27.00 |
November | 11.17 | 27.00 | 489.00 | 27.00 | 11.17 | 27.00 |
December | 3.33 | 27.50 | 488.83 | 27.01 | 3.33 | 27.02 |
Annual Sum or Average | 583.67 | 28.07 | 5934.83 | 27.20 | 583.67 | 27.28 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 258.50 | 28.81 | 514.00 | 28.06 | 258.50 | 28.21 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 24.42 | 462.67 | 26.94 | 0.00 | 26.94 |
February | 0.50 | 27.00 | 447.00 | 27.00 | 0.50 | 27.00 |
March | 2.17 | 27.00 | 500.83 | 27.00 | 2.17 | 27.00 |
April | 157.33 | 28.74 | 485.00 | 27.93 | 157.33 | 28.09 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 41.00 | 27.00 | 496.00 | 27.00 | 41.00 | 27.00 |
July | 160.33 | 27.00 | 497.00 | 27.00 | 160.33 | 27.00 |
August | 260.67 | 28.03 | 514.00 | 27.70 | 260.67 | 27.79 |
September | 61.33 | 27.00 | 485.00 | 27.00 | 61.33 | 27.00 |
October | 25.00 | 27.00 | 502.00 | 27.00 | 25.00 | 27.00 |
November | 13.33 | 27.00 | 472.83 | 27.00 | 13.33 | 27.00 |
December | 1.67 | 27.37 | 407.83 | 27.00 | 1.67 | 27.01 |
Annual Sum or Average | 735.00 | 27.70 | 5778.17 | 27.17 | 723.33 | 27.23 |
Minimum of Months | 0.00 | 0.00 | 407.83 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 260.67 | 28.74 | 514.00 | 27.93 | 260.67 | 28.09 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.83 | 27.00 | 502.00 | 27.00 | 446.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.65 | 485.00 | 29.65 | 485.00 | 29.65 |
May | 439.17 | 27.00 | 508.00 | 27.00 | 439.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.07 | 497.00 | 27.07 | 497.00 | 27.07 |
August | 514.00 | 31.27 | 514.00 | 31.27 | 514.00 | 31.27 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
Annual Sum or Average | 5819.00 | 27.61 | 5943.00 | 27.60 | 5819.00 | 27.60 |
Minimum of Months | 439.17 | 27.00 | 454.00 | 27.00 | 439.17 | 27.00 |
Maximum of Months | 514.00 | 31.27 | 514.00 | 31.27 | 514.00 | 31.27 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.84573 | 0.82265 | 19.38258 |
February | 454.00000 | 27.00023 | 29.34157 | 0.89641 | 22.04987 |
March | 514.00000 | 27.00003 | 26.53538 | 0.92520 | 23.17983 |
April | 485.00000 | 27.94236 | 18.21853 | 1.09192 | 30.74402 |
May | 508.00000 | 27.00000 | 17.54165 | 0.17417 | 5.72688 |
June | 496.00000 | 27.00000 | 23.65393 | 0.29003 | 6.86777 |
July | 497.00000 | 27.00027 | 33.29370 | 0.40406 | 8.52225 |
August | 514.00000 | 27.78786 | 34.00422 | 0.67588 | 15.98608 |
September | 485.00000 | 27.00074 | 34.56883 | 0.32091 | 7.24064 |
October | 502.00000 | 27.00010 | 25.25241 | 0.91091 | 22.67619 |
November | 489.00000 | 27.00014 | 24.69001 | 0.92268 | 23.12166 |
December | 497.00000 | 27.03205 | 17.37160 | 0.87630 | 21.36038 |
Annual Sum or Average | 5943.00000 | 27.14785 | 25.59030 | 0.69077 | 17.18859 |
Minimum of Months | 454.00000 | 27.00000 | 17.37160 | 0.17417 | 5.72688 |
Maximum of Months | 514.00000 | 27.94236 | 34.56883 | 1.09192 | 30.74402 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.83057 | 0.74215 | 16.75397 |
February | 454.00000 | 27.00022 | 29.36365 | 0.79477 | 18.43619 |
March | 514.00000 | 27.00003 | 26.50653 | 0.81954 | 19.32089 |
April | 485.00000 | 27.78924 | 18.27106 | 0.96803 | 25.46600 |
May | 508.00000 | 27.00000 | 17.51591 | 0.12114 | 5.43040 |
June | 496.00000 | 27.00000 | 23.64228 | 0.22495 | 6.18400 |
July | 497.00000 | 27.00030 | 33.30148 | 0.30990 | 7.13063 |
August | 514.00000 | 27.62787 | 34.15221 | 0.48937 | 11.16421 |
September | 485.00000 | 27.00066 | 34.62909 | 0.26293 | 6.54726 |
October | 502.00000 | 27.00010 | 25.23109 | 0.83362 | 19.86922 |
November | 489.00000 | 27.00014 | 24.67580 | 0.80732 | 18.96370 |
December | 497.00000 | 27.00834 | 17.36572 | 0.71621 | 15.99710 |
Annual Sum or Average | 5943.00000 | 27.11953 | 25.60423 | 0.58885 | 14.22586 |
Minimum of Months | 454.00000 | 27.00000 | 17.36572 | 0.12114 | 5.43040 |
Maximum of Months | 514.00000 | 27.78924 | 34.62909 | 0.96803 | 25.46600 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.93811 | 23.04380 | 0.68707 | 15.42161 |
February | 454.00000 | 27.00022 | 29.39542 | 0.74522 | 16.92789 |
March | 514.00000 | 27.00003 | 26.52402 | 0.78727 | 18.33450 |
April | 485.00000 | 27.66464 | 18.35043 | 0.94417 | 24.63739 |
May | 508.00000 | 27.00000 | 17.52670 | 0.13039 | 5.57030 |
June | 496.00000 | 27.00000 | 23.64748 | 0.25050 | 6.50517 |
July | 497.00000 | 27.00030 | 33.29724 | 0.33352 | 7.50568 |
August | 514.00000 | 27.53631 | 34.21685 | 0.48571 | 11.23027 |
September | 485.00000 | 27.00069 | 34.61929 | 0.27427 | 6.73478 |
October | 502.00000 | 27.00010 | 25.24234 | 0.81562 | 19.34357 |
November | 489.00000 | 27.00014 | 24.69130 | 0.76533 | 17.70136 |
December | 497.00000 | 27.00187 | 17.37839 | 0.65221 | 14.27754 |
Annual Sum or Average | 5943.00000 | 27.09567 | 25.64174 | 0.57085 | 13.64423 |
Minimum of Months | 454.00000 | 26.93811 | 17.37839 | 0.13039 | 5.57030 |
Maximum of Months | 514.00000 | 27.66464 | 34.61929 | 0.94417 | 24.63739 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99996 | 25.58141 | 1.05115 | 28.36731 |
February | 454.00000 | 27.00019 | 31.01123 | 1.22630 | 36.56370 |
March | 514.00000 | 27.00151 | 25.74001 | 1.32469 | 41.57568 |
April | 485.00000 | 29.65270 | 16.69982 | 1.89295 | 68.29778 |
May | 508.00000 | 27.00045 | 26.35669 | 0.47647 | 9.85367 |
June | 496.00000 | 27.00325 | 29.52702 | 0.72403 | 16.07294 |
July | 497.00000 | 27.07268 | 36.08847 | 1.02342 | 27.33047 |
August | 514.00000 | 31.27479 | 32.16941 | 2.38770 | 84.61817 |
September | 485.00000 | 27.00134 | 38.35629 | 0.66182 | 14.34273 |
October | 502.00000 | 27.00117 | 27.37213 | 1.26107 | 38.33943 |
November | 489.00000 | 27.00253 | 25.48764 | 1.37620 | 44.29802 |
December | 497.00000 | 27.02399 | 17.84714 | 1.43187 | 47.22982 |
Annual Sum or Average | 5943.00000 | 27.59515 | 27.66843 | 1.23828 | 38.15027 |
Minimum of Months | 454.00000 | 26.99996 | 16.69982 | 0.47647 | 9.85367 |
Maximum of Months | 514.00000 | 31.27479 | 38.35629 | 2.38770 | 84.61817 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58161 | 20.34802 | 0.38261 | 8.68918 |
February | 454.00000 | 24.50618 | 32.44386 | 0.44373 | 9.74305 |
March | 514.00000 | 24.41749 | 25.87659 | 0.38117 | 8.48957 |
April | 485.00000 | 24.55165 | 18.61197 | 0.36639 | 8.28576 |
May | 508.00000 | 24.51073 | 18.09518 | -0.4962 | 11.01007 |
June | 496.00000 | 24.47892 | 25.53394 | -0.4440 | 10.10449 |
July | 497.00000 | 24.64317 | 45.31323 | -0.2426 | 7.54352 |
August | 514.00000 | 24.50380 | 47.96598 | -0.2442 | 7.39737 |
September | 485.00000 | 24.58776 | 47.04130 | -0.2295 | 7.68858 |
October | 502.00000 | 24.63573 | 26.49743 | 0.46059 | 10.33361 |
November | 489.00000 | 24.63874 | 26.23170 | 0.45685 | 10.36236 |
December | 497.00000 | 24.62567 | 14.44967 | 0.36090 | 8.42356 |
Annual Sum or Average | 5943.00000 | 24.55646 | 29.01388 | 0.09616 | 9.00118 |
Minimum of Months | 454.00000 | 24.41749 | 14.44967 | -0.4962 | 7.39737 |
Maximum of Months | 514.00000 | 24.64317 | 47.96598 | 0.46059 | 11.01007 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32005 | 21.63295 | 0.33665 | 7.65037 |
February | 454.00000 | 24.34158 | 33.83492 | 0.42408 | 9.14774 |
March | 514.00000 | 24.29921 | 26.67166 | 0.38070 | 8.34922 |
April | 485.00000 | 24.24121 | 19.80296 | 0.34452 | 7.62931 |
May | 508.00000 | 24.25861 | 19.35569 | -0.5254 | 11.06401 |
June | 496.00000 | 24.16997 | 27.36357 | -0.4800 | 10.02615 |
July | 497.00000 | 24.24121 | 45.40189 | -0.3273 | 7.57461 |
August | 514.00000 | 24.22077 | 47.49965 | -0.2954 | 7.13863 |
September | 485.00000 | 24.32766 | 46.84498 | -0.3029 | 7.55655 |
October | 502.00000 | 24.38975 | 27.54723 | 0.41888 | 9.16529 |
November | 489.00000 | 24.41365 | 26.78702 | 0.41458 | 9.21956 |
December | 497.00000 | 24.41196 | 15.57109 | 0.32625 | 7.58577 |
Annual Sum or Average | 5943.00000 | 24.30240 | 29.83430 | 0.05605 | 8.50698 |
Minimum of Months | 454.00000 | 24.16997 | 15.57109 | -0.5254 | 7.13863 |
Maximum of Months | 514.00000 | 24.41365 | 47.49965 | 0.42408 | 11.06401 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90922 | 22.79870 | 0.21240 | 6.47440 |
February | 454.00000 | 23.96555 | 35.35525 | 0.30622 | 7.18889 |
March | 514.00000 | 24.09364 | 27.74018 | 0.29855 | 7.12684 |
April | 485.00000 | 24.15769 | 20.01327 | 0.28705 | 6.91165 |
May | 508.00000 | 24.19272 | 19.37806 | -0.5746 | 12.18491 |
June | 496.00000 | 24.11874 | 27.09666 | -0.5301 | 11.03414 |
July | 497.00000 | 24.18294 | 45.81199 | -0.3884 | 8.54253 |
August | 514.00000 | 24.16996 | 48.49958 | -0.3699 | 8.17412 |
September | 485.00000 | 24.27026 | 47.10781 | -0.3523 | 8.13660 |
October | 502.00000 | 24.21749 | 28.06715 | 0.34847 | 7.95001 |
November | 489.00000 | 24.12336 | 28.09915 | 0.30863 | 7.64989 |
December | 497.00000 | 23.85709 | 17.03170 | 0.15293 | 5.77889 |
Annual Sum or Average | 5943.00000 | 24.10568 | 30.55438 | -0.0284 | 8.10858 |
Minimum of Months | 454.00000 | 23.85709 | 17.03170 | -0.5746 | 5.77889 |
Maximum of Months | 514.00000 | 24.27026 | 48.49958 | 0.34847 | 12.18491 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19639 | 24.09450 | 0.02760 | 6.75879 |
February | 454.00000 | 23.15808 | 37.84058 | 0.10060 | 6.28485 |
March | 514.00000 | 23.65329 | 28.78259 | 0.18144 | 6.53650 |
April | 485.00000 | 24.09347 | 20.14110 | 0.27588 | 6.86564 |
May | 508.00000 | 24.19485 | 19.50803 | -0.5596 | 11.86652 |
June | 496.00000 | 24.17356 | 27.05613 | -0.4821 | 10.13996 |
July | 497.00000 | 24.25075 | 45.73183 | -0.3385 | 7.86812 |
August | 514.00000 | 24.20861 | 48.57422 | -0.3338 | 7.69381 |
September | 485.00000 | 24.30566 | 47.32521 | -0.3257 | 7.83932 |
October | 502.00000 | 23.97742 | 28.66628 | 0.28531 | 7.45358 |
November | 489.00000 | 23.49581 | 29.37885 | 0.14559 | 7.03248 |
December | 497.00000 | 22.79418 | 18.52482 | -0.1185 | 6.79787 |
Annual Sum or Average | 5943.00000 | 23.79631 | 31.26028 | -0.0974 | 7.77717 |
Minimum of Months | 454.00000 | 22.79418 | 18.52482 | -0.5596 | 6.28485 |
Maximum of Months | 514.00000 | 24.30566 | 48.57422 | 0.28531 | 11.86652 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.38667 | 22.79791 | 0.07208 | 5.72437 |
February | 454.00000 | 23.34360 | 35.63122 | 0.14045 | 6.07360 |
March | 514.00000 | 23.70142 | 27.23937 | 0.19632 | 6.57711 |
April | 485.00000 | 24.21758 | 19.23003 | 0.32755 | 7.65257 |
May | 508.00000 | 24.35354 | 18.36999 | -0.4693 | 10.25125 |
June | 496.00000 | 24.41175 | 25.94300 | -0.3134 | 8.13147 |
July | 497.00000 | 24.50319 | 44.05663 | -0.1730 | 6.76624 |
August | 514.00000 | 24.36234 | 46.42448 | -0.2009 | 6.75572 |
September | 485.00000 | 24.43941 | 46.01325 | -0.2358 | 7.27377 |
October | 502.00000 | 24.09134 | 27.46131 | 0.32024 | 8.14423 |
November | 489.00000 | 23.70477 | 27.56460 | 0.19740 | 6.81246 |
December | 497.00000 | 23.29200 | 16.45115 | 0.00229 | 5.92854 |
Annual Sum or Average | 5943.00000 | 23.98806 | 29.72641 | -0.0133 | 7.18379 |
Minimum of Months | 454.00000 | 23.29200 | 16.45115 | -0.4693 | 5.72437 |
Maximum of Months | 514.00000 | 24.50319 | 46.42448 | 0.32755 | 10.25125 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.51714 | 21.93502 | 0.14642 | 6.55808 |
February | 454.00000 | 23.32382 | 35.13478 | 0.17565 | 6.97767 |
March | 514.00000 | 23.67882 | 26.80828 | 0.23536 | 7.38689 |
April | 485.00000 | 24.23998 | 18.91361 | 0.40419 | 9.46131 |
May | 508.00000 | 24.44523 | 18.06703 | -0.3271 | 8.91551 |
June | 496.00000 | 24.39970 | 25.82403 | -0.2144 | 7.71164 |
July | 497.00000 | 24.47081 | 44.01716 | -0.0995 | 6.81061 |
August | 514.00000 | 24.30457 | 46.42741 | -0.1448 | 6.93225 |
September | 485.00000 | 24.43120 | 45.75548 | -0.1632 | 7.07293 |
October | 502.00000 | 24.11780 | 26.95393 | 0.38395 | 9.65159 |
November | 489.00000 | 23.63885 | 27.33167 | 0.22198 | 7.26589 |
December | 497.00000 | 23.21303 | 15.97393 | 0.01669 | 6.51959 |
Annual Sum or Average | 5943.00000 | 23.98611 | 29.39065 | 0.05119 | 7.60835 |
Minimum of Months | 454.00000 | 23.21303 | 15.97393 | -0.3271 | 6.51959 |
Maximum of Months | 514.00000 | 24.47081 | 46.42741 | 0.40419 | 9.65159 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07374 | 20.70651 | 0.35309 | 9.58371 |
February | 454.00000 | 23.65614 | 34.17685 | 0.27904 | 8.10171 |
March | 514.00000 | 23.85884 | 26.49405 | 0.28545 | 7.94389 |
April | 485.00000 | 24.29402 | 18.94693 | 0.39615 | 9.13804 |
May | 508.00000 | 24.34365 | 18.33570 | -0.4553 | 10.31533 |
June | 496.00000 | 24.36519 | 26.03548 | -0.3396 | 8.47889 |
July | 497.00000 | 24.47734 | 44.08907 | -0.1761 | 6.95361 |
August | 514.00000 | 24.37057 | 46.31358 | -0.1596 | 6.69250 |
September | 485.00000 | 24.51148 | 45.59303 | -0.1308 | 7.03281 |
October | 502.00000 | 24.36529 | 26.44400 | 0.48317 | 11.61441 |
November | 489.00000 | 24.15849 | 26.17558 | 0.40783 | 10.05342 |
December | 497.00000 | 23.93496 | 14.83118 | 0.25780 | 8.91860 |
Annual Sum or Average | 5943.00000 | 24.20377 | 28.97900 | 0.09763 | 8.73901 |
Minimum of Months | 454.00000 | 23.65614 | 14.83118 | -0.4553 | 6.69250 |
Maximum of Months | 514.00000 | 24.51148 | 46.31358 | 0.48317 | 11.61441 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78920 | 21.35758 | 0.24676 | 7.40918 |
February | 454.00000 | 23.88928 | 33.66680 | 0.34034 | 8.18972 |
March | 514.00000 | 24.24310 | 25.63845 | 0.42363 | 9.61971 |
April | 485.00000 | 24.57909 | 18.42420 | 0.58538 | 13.35053 |
May | 508.00000 | 24.48705 | 17.99007 | -0.2703 | 8.41570 |
June | 496.00000 | 24.48382 | 25.68305 | -0.1127 | 7.21151 |
July | 497.00000 | 24.62535 | 43.56821 | 0.03076 | 7.07070 |
August | 514.00000 | 24.55068 | 45.66967 | 0.08981 | 7.25325 |
September | 485.00000 | 24.53713 | 45.47726 | -0.0793 | 6.83851 |
October | 502.00000 | 24.43850 | 26.37595 | 0.50342 | 11.62258 |
November | 489.00000 | 24.34920 | 25.79920 | 0.45253 | 10.50141 |
December | 497.00000 | 24.23808 | 14.56150 | 0.31977 | 8.20537 |
Annual Sum or Average | 5943.00000 | 24.35347 | 28.65145 | 0.20910 | 8.80295 |
Minimum of Months | 454.00000 | 23.78920 | 14.56150 | -0.2703 | 6.83851 |
Maximum of Months | 514.00000 | 24.62535 | 45.66967 | 0.58538 | 13.35053 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.21831 | 24.67711 | -0.2161 | 7.65463 |
February | 454.00000 | 22.10977 | 38.65960 | -0.1622 | 6.63990 |
March | 514.00000 | 22.85412 | 29.14067 | -0.0246 | 6.69233 |
April | 485.00000 | 23.98615 | 19.43182 | 0.23843 | 6.83335 |
May | 508.00000 | 24.30170 | 18.18163 | -0.5131 | 11.21309 |
June | 496.00000 | 24.43158 | 25.32881 | -0.3327 | 8.39731 |
July | 497.00000 | 24.52855 | 44.24080 | -0.1974 | 7.04997 |
August | 514.00000 | 24.35794 | 47.20961 | -0.2520 | 7.18897 |
September | 485.00000 | 24.40809 | 46.33580 | -0.2720 | 7.66652 |
October | 502.00000 | 23.56891 | 28.34772 | 0.17582 | 7.51089 |
November | 489.00000 | 22.65036 | 29.80635 | -0.0702 | 7.29432 |
December | 497.00000 | 21.67093 | 18.15722 | -0.4010 | 9.67398 |
Annual Sum or Average | 5943.00000 | 23.43290 | 30.74167 | -0.1699 | 7.83023 |
Minimum of Months | 454.00000 | 21.67093 | 18.15722 | -0.5131 | 6.63990 |
Maximum of Months | 514.00000 | 24.52855 | 47.20961 | 0.23843 | 11.21309 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.65831 | 23.09461 | -0.0780 | 7.06191 |
February | 385.00000 | 22.50955 | 37.03876 | -0.0370 | 6.86911 |
March | 433.00000 | 23.17757 | 27.57437 | 0.08978 | 7.17740 |
April | 410.00000 | 24.33512 | 18.21197 | 0.39354 | 9.68186 |
May | 430.00000 | 24.55114 | 17.26698 | -0.3259 | 9.44825 |
June | 418.00000 | 24.54720 | 24.62245 | -0.1924 | 7.99118 |
July | 422.00000 | 24.68764 | 43.41005 | -0.0595 | 7.25982 |
August | 433.00000 | 24.50074 | 46.13675 | -0.1190 | 7.22913 |
September | 410.00000 | 24.54111 | 45.54765 | -0.1627 | 7.56924 |
October | 427.00000 | 23.88119 | 26.81857 | 0.29821 | 9.30300 |
November | 417.00000 | 22.95552 | 28.63953 | 0.03737 | 7.00029 |
December | 422.00000 | 22.09526 | 16.59809 | -0.2743 | 8.35153 |
Annual Sum or Average | 5034.00000 | 23.70979 | 29.52211 | -0.0366 | 7.91688 |
Minimum of Months | 385.00000 | 22.09526 | 16.59809 | -0.3259 | 6.86911 |
Maximum of Months | 433.00000 | 24.68764 | 46.13675 | 0.39354 | 9.68186 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.83776 | 21.15468 | 0.29358 | 9.73105 |
February | 454.00000 | 23.23715 | 35.28903 | 0.17255 | 8.02715 |
March | 514.00000 | 23.51575 | 27.32558 | 0.18771 | 7.69938 |
April | 485.00000 | 24.19879 | 18.88199 | 0.34584 | 8.60060 |
May | 508.00000 | 24.30471 | 18.12272 | -0.4903 | 11.16707 |
June | 496.00000 | 24.38275 | 25.42301 | -0.3613 | 8.78729 |
July | 497.00000 | 24.50979 | 44.26040 | -0.1976 | 7.23530 |
August | 514.00000 | 24.39232 | 46.98580 | -0.1955 | 7.00367 |
September | 485.00000 | 24.51612 | 45.75382 | -0.1450 | 7.26212 |
October | 502.00000 | 24.23045 | 26.55912 | 0.43994 | 11.35579 |
November | 489.00000 | 23.87061 | 26.93996 | 0.32850 | 9.65910 |
December | 497.00000 | 23.53639 | 15.33114 | 0.14785 | 9.20346 |
Annual Sum or Average | 5943.00000 | 24.04908 | 29.29913 | 0.04166 | 8.81801 |
Minimum of Months | 454.00000 | 23.23715 | 15.33114 | -0.4903 | 7.00367 |
Maximum of Months | 514.00000 | 24.51612 | 46.98580 | 0.43994 | 11.35579 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65887 | 23.08785 | -0.0526 | 7.39314 |
February | 454.00000 | 22.35663 | 37.32729 | -0.0589 | 6.59002 |
March | 514.00000 | 23.06278 | 27.99719 | 0.08133 | 7.19450 |
April | 485.00000 | 24.19883 | 18.80811 | 0.38938 | 9.65862 |
May | 508.00000 | 24.37520 | 17.91860 | -0.3637 | 10.01086 |
June | 496.00000 | 24.44960 | 25.20549 | -0.2028 | 7.75565 |
July | 497.00000 | 24.55183 | 44.05949 | -0.1025 | 7.19293 |
August | 514.00000 | 24.41070 | 46.88621 | -0.1291 | 7.06161 |
September | 485.00000 | 24.44289 | 46.02415 | -0.1730 | 7.37410 |
October | 502.00000 | 23.75442 | 27.42532 | 0.28699 | 9.12387 |
November | 489.00000 | 23.02703 | 28.32815 | 0.07874 | 7.70552 |
December | 497.00000 | 22.19000 | 16.74290 | -0.2311 | 8.41820 |
Annual Sum or Average | 5943.00000 | 23.63158 | 29.93669 | -0.0406 | 7.96415 |
Minimum of Months | 454.00000 | 22.19000 | 16.74290 | -0.3637 | 6.59002 |
Maximum of Months | 514.00000 | 24.55183 | 46.88621 | 0.38938 | 10.01086 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62173 | 25.30126 | -0.3738 | 10.28807 |
February | 454.00000 | 21.43296 | 40.13602 | -0.3389 | 9.04904 |
March | 514.00000 | 22.35462 | 29.76444 | -0.1517 | 8.01097 |
April | 485.00000 | 23.82551 | 19.67145 | 0.20783 | 7.08852 |
May | 508.00000 | 24.24617 | 18.43323 | -0.5164 | 11.72337 |
June | 496.00000 | 24.43000 | 25.57172 | -0.3045 | 8.21581 |
July | 497.00000 | 24.52534 | 44.43704 | -0.1720 | 7.09039 |
August | 514.00000 | 24.34802 | 47.48137 | -0.2334 | 7.20928 |
September | 485.00000 | 24.38318 | 46.78664 | -0.2643 | 7.86634 |
October | 502.00000 | 23.22627 | 28.82669 | 0.09361 | 8.04581 |
November | 489.00000 | 22.05842 | 30.58472 | -0.2233 | 9.21393 |
December | 497.00000 | 21.01801 | 18.58415 | -0.5858 | 14.13248 |
Annual Sum or Average | 5943.00000 | 23.13421 | 31.23938 | -0.2388 | 8.99749 |
Minimum of Months | 454.00000 | 21.01801 | 18.43323 | -0.5858 | 7.08852 |
Maximum of Months | 514.00000 | 24.52534 | 47.48137 | 0.20783 | 14.13248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.39160 | 23.68018 | -0.1551 | 8.05633 |
February | 454.00000 | 22.14028 | 38.12202 | -0.1404 | 7.68343 |
March | 514.00000 | 22.98065 | 28.14965 | 0.03924 | 7.43424 |
April | 485.00000 | 24.23418 | 18.74335 | 0.39654 | 9.82552 |
May | 508.00000 | 24.44941 | 17.94604 | -0.3145 | 9.19317 |
June | 496.00000 | 24.46621 | 25.34623 | -0.1600 | 7.59472 |
July | 497.00000 | 24.59015 | 44.10395 | -0.0349 | 7.14763 |
August | 514.00000 | 24.42410 | 46.99610 | -0.0891 | 7.02805 |
September | 485.00000 | 24.44767 | 46.26261 | -0.1482 | 7.45734 |
October | 502.00000 | 23.73410 | 27.52137 | 0.27397 | 9.39459 |
November | 489.00000 | 22.64509 | 29.27983 | -0.0462 | 7.64084 |
December | 497.00000 | 21.61463 | 17.49498 | -0.4080 | 10.69211 |
Annual Sum or Average | 5943.00000 | 23.51948 | 30.25142 | -0.0658 | 8.26254 |
Minimum of Months | 454.00000 | 21.61463 | 17.49498 | -0.4080 | 7.02805 |
Maximum of Months | 514.00000 | 24.59015 | 46.99610 | 0.39654 | 10.69211 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45635 | 21.70778 | 0.18134 | 9.80594 |
February | 454.00000 | 22.71789 | 36.66931 | 0.02991 | 8.46056 |
March | 514.00000 | 23.15774 | 27.92711 | 0.08959 | 8.08334 |
April | 485.00000 | 24.06289 | 19.13568 | 0.32053 | 8.81985 |
May | 508.00000 | 24.23398 | 18.39516 | -0.4976 | 11.87745 |
June | 496.00000 | 24.37806 | 25.66662 | -0.3344 | 8.66845 |
July | 497.00000 | 24.50372 | 44.47248 | -0.1731 | 7.34101 |
August | 514.00000 | 24.37972 | 47.28700 | -0.1776 | 7.12134 |
September | 485.00000 | 24.49015 | 46.23852 | -0.1372 | 7.52018 |
October | 502.00000 | 24.01938 | 27.00257 | 0.38508 | 11.22865 |
November | 489.00000 | 23.49392 | 27.62753 | 0.22047 | 9.39982 |
December | 497.00000 | 23.04759 | 15.83134 | -0.0010 | 10.00317 |
Annual Sum or Average | 5943.00000 | 23.83529 | 29.78685 | -0.0094 | 9.03423 |
Minimum of Months | 454.00000 | 22.71789 | 15.83134 | -0.4976 | 7.12134 |
Maximum of Months | 514.00000 | 24.50372 | 47.28700 | 0.38508 | 11.87745 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24271 | 23.64136 | -0.1677 | 8.89555 |
February | 454.00000 | 21.87727 | 38.50708 | -0.1889 | 7.89514 |
March | 514.00000 | 22.69326 | 28.53178 | -0.0157 | 7.91895 |
April | 485.00000 | 24.05082 | 19.05492 | 0.36144 | 9.82636 |
May | 508.00000 | 24.30205 | 18.19946 | -0.3722 | 10.80195 |
June | 496.00000 | 24.44107 | 25.47577 | -0.1786 | 7.86326 |
July | 497.00000 | 24.53698 | 44.30573 | -0.0823 | 7.40840 |
August | 514.00000 | 24.39002 | 47.22024 | -0.1150 | 7.29910 |
September | 485.00000 | 24.40240 | 46.54457 | -0.1701 | 7.72501 |
October | 502.00000 | 23.50671 | 27.86810 | 0.22654 | 9.37398 |
November | 489.00000 | 22.60449 | 28.99311 | -0.0344 | 8.48318 |
December | 497.00000 | 21.70671 | 17.18461 | -0.3725 | 10.95870 |
Annual Sum or Average | 5943.00000 | 23.40637 | 30.40752 | -0.0927 | 8.70848 |
Minimum of Months | 454.00000 | 21.70671 | 17.18461 | -0.3725 | 7.29910 |
Maximum of Months | 514.00000 | 24.53698 | 47.22024 | 0.36144 | 10.95870 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.723738E+11 | 160729.30 | 27-JAN-15:10 | 304.53 | 0.470480E+12 | 0.00 | 0.542854E+12 | 2.36 | 7.57 | 24-JAN-16:00 | 0.00 | 0.00 |
February | 0.211125E+11 | 93279.31 | 22-FEB-16:00 | 186.08 | 0.107805E+12 | 0.00 | 0.128917E+12 | 1.29 | 7.11 | 22-FEB-16:00 | 0.00 | 0.00 |
March | 0.718943E+11 | 174506.91 | 20-MAR-13:20 | 341.26 | 0.456516E+12 | 0.00 | 0.528410E+12 | 2.54 | 7.57 | 15-MAR-16:00 | 0.00 | 0.00 |
April | 0.144501E+12 | 167520.38 | 19-APR-13:40 | 568.13 | 0.988780E+12 | 0.00 | 0.113328E+13 | 4.76 | 7.57 | 21-APR-12:40 | 0.00 | 0.00 |
May | 0.170850E+12 | 167387.43 | 12-MAY-13:00 | 530.64 | 0.118633E+13 | 0.00 | 0.135718E+13 | 4.66 | 7.57 | 08-MAY-04:13 | 0.00 | 0.00 |
June | 0.201007E+12 | 182579.07 | 30-JUN-07:50 | 644.16 | 0.139783E+13 | 0.00 | 0.159884E+13 | 5.81 | 7.58 | 20-JUN-04:13 | 0.00 | 0.00 |
July | 0.211749E+12 | 187801.15 | 18-JUL-05:05 | 679.98 | 0.144441E+13 | 0.00 | 0.165616E+13 | 5.77 | 7.61 | 18-JUL-05:03 | 0.00 | 0.00 |
August | 0.211756E+12 | 179960.55 | 29-AUG-17:34 | 689.41 | 0.145370E+13 | 0.00 | 0.166546E+13 | 5.85 | 7.57 | 24-AUG-05:03 | 0.00 | 0.00 |
September | 0.180475E+12 | 180613.51 | 08-SEP-17:10 | 536.82 | 0.124964E+13 | 0.00 | 0.143011E+13 | 4.87 | 7.57 | 19-SEP-03:04 | 0.00 | 0.00 |
October | 0.120251E+12 | 178013.01 | 05-OCT-09:30 | 436.94 | 0.808147E+12 | 0.00 | 0.928397E+12 | 3.59 | 7.57 | 13-OCT-14:20 | 0.00 | 0.00 |
November | 0.724540E+11 | 173277.82 | 01-NOV-14:40 | 321.89 | 0.468843E+12 | 0.00 | 0.541297E+12 | 2.51 | 7.57 | 21-NOV-14:00 | 0.00 | 0.00 |
December | 0.399704E+11 | 153553.89 | 22-DEC-15:40 | 230.66 | 0.235909E+12 | 0.00 | 0.275879E+12 | 1.60 | 7.57 | 22-DEC-15:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.151840E+13 | 5470.49 | 0.102684E+14 | 0.00 | 0.117868E+14 | 3.81 | 0.00 | 0.00 | ||||
Minimum of Months | 0.211125E+11 | 93279.31 | 186.08 | 0.107805E+12 | 0.00 | 0.128917E+12 | 1.29 | 7.11 | 0.00 | 0.00 | ||
Maximum of Months | 0.211756E+12 | 187801.15 | 689.41 | 0.145370E+13 | 0.00 | 0.166546E+13 | 5.85 | 7.61 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.195223E+09 | 100954.12 | 31-JAN-15:30 | 0.67 | 0.135379E+10 | 0.00 | 0.154901E+10 | 0.01 | 7.23 | 31-JAN-15:30 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.108671E+10 | 118063.08 | 20-MAR-14:20 | 3.33 | 0.774740E+10 | 0.00 | 0.883411E+10 | 0.03 | 7.42 | 20-MAR-14:20 | 0.00 | 0.00 |
April | 0.287707E+11 | 117263.49 | 10-APR-10:35 | 79.67 | 0.207114E+12 | 0.00 | 0.235884E+12 | 0.80 | 7.44 | 10-APR-10:35 | 0.00 | 0.00 |
May | 0.470145E+11 | 115746.25 | 18-MAY-15:20 | 130.50 | 0.338506E+12 | 0.00 | 0.385520E+12 | 1.26 | 7.39 | 18-MAY-14:50 | 0.00 | 0.00 |
June | 0.895448E+11 | 142989.00 | 19-JUN-14:20 | 236.00 | 0.646128E+12 | 0.00 | 0.735673E+12 | 2.35 | 7.47 | 08-JUN-14:40 | 0.00 | 0.00 |
July | 0.803756E+11 | 187801.15 | 18-JUL-05:05 | 204.28 | 0.566123E+12 | 0.00 | 0.646499E+12 | 1.92 | 7.61 | 18-JUL-05:03 | 0.00 | 0.00 |
August | 0.887820E+11 | 150556.45 | 01-AUG-05:05 | 222.76 | 0.625958E+12 | 0.00 | 0.714740E+12 | 2.11 | 7.49 | 23-AUG-08:45 | 0.00 | 0.00 |
September | 0.623576E+11 | 149540.56 | 05-SEP-07:50 | 159.14 | 0.441432E+12 | 0.00 | 0.503790E+12 | 1.56 | 7.45 | 29-SEP-13:20 | 0.00 | 0.00 |
October | 0.255383E+11 | 125958.81 | 03-OCT-11:00 | 69.07 | 0.182187E+12 | 0.00 | 0.207726E+12 | 0.66 | 7.43 | 06-OCT-12:20 | 0.00 | 0.00 |
November | 0.190347E+10 | 109379.77 | 01-NOV-13:50 | 6.00 | 0.132903E+11 | 0.00 | 0.151938E+11 | 0.06 | 7.33 | 01-NOV-13:50 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.425569E+12 | 1111.41 | 0.302984E+13 | 0.00 | 0.345541E+13 | 0.90 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.895448E+11 | 187801.15 | 236.00 | 0.646128E+12 | 0.00 | 0.735673E+12 | 2.35 | 7.61 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.496102E+11 | 744.00 | 49248.27 | 02-JAN-12:10 | 237919.32 | 27-JAN-16:00 | 20.50 | 19.64 | 14.49 |
February | 0.224337E+11 | 672.00 | 49248.27 | 06-FEB-14:00 | 186075.52 | 18-FEB-14:10 | 19.66 | 18.49 | 14.49 |
March | 0.673739E+11 | 744.00 | 49248.27 | 01-MAR-10:00 | 540502.01 | 16-MAR-16:00 | 24.29 | 20.68 | 14.49 |
April | 0.119479E+12 | 720.00 | 49248.27 | 01-APR-06:55 | 650116.60 | 25-APR-18:15 | 37.57 | 28.15 | 14.49 |
May | 0.124534E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 367241.16 | 31-MAY-23:15 | 30.95 | 27.89 | 14.49 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 532009.18 | 30-JUN-23:23 | 41.57 | 34.54 | 14.49 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 730242.97 | 13-JUL-17:53 | 46.37 | 35.59 | 14.49 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 759734.29 | 05-AUG-16:12 | 49.20 | 36.11 | 14.49 |
September | 0.127139E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 345036.84 | 04-SEP-10:20 | 33.07 | 29.46 | 14.49 |
October | 0.955554E+11 | 744.00 | 49248.27 | 01-OCT-00:05 | 515864.02 | 03-OCT-08:30 | 27.88 | 24.09 | 14.49 |
November | 0.675658E+11 | 720.00 | 49248.27 | 01-NOV-00:10 | 559700.04 | 09-NOV-17:00 | 24.29 | 20.54 | 14.49 |
December | 0.543429E+11 | 744.00 | 49248.27 | 01-DEC-09:50 | 615498.24 | 25-DEC-16:11 | 23.85 | 19.70 | 14.49 |
Annual Sum or Average | 0.111950E+13 | 8760.00 | 31.67 | 26.28 | 14.49 | ||||
Minimum of Months | 0.224337E+11 | 672.00 | 49248.27 | 186075.52 | 19.66 | 18.49 | 14.49 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 759734.29 | 49.20 | 36.11 | 14.49 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.588614E+09 | 239.27 | 2753.58 | 31-JAN-14:50 | 1389518.93 | 27-JAN-15:10 | 21.93 | 21.17 | 24.51 |
February | 0.127126E+09 | 93.42 | 1260.89 | 22-FEB-16:00 | 769876.67 | 22-FEB-16:00 | 21.28 | 21.07 | 14.13 |
March | 0.118442E+10 | 249.26 | 19244.06 | 10-MAR-15:10 | 1475833.17 | 17-MAR-14:10 | 21.86 | 21.11 | 25.98 |
April | 0.285713E+10 | 415.64 | 19244.06 | 10-APR-14:30 | 1410383.20 | 05-APR-12:30 | 22.85 | 21.07 | 44.43 |
May | 0.354212E+10 | 491.17 | 19244.06 | 04-MAY-16:10 | 1407489.30 | 12-MAY-13:00 | 23.42 | 21.30 | 45.69 |
June | 0.164199E+11 | 584.01 | 19244.06 | 01-JUN-07:50 | 1406712.26 | 15-JUN-08:20 | 23.90 | 21.40 | 57.14 |
July | 0.321336E+11 | 654.79 | 19244.06 | 01-JUL-13:10 | 1358793.69 | 03-JUL-08:20 | 24.82 | 22.49 | 57.83 |
August | 0.323002E+11 | 655.90 | 19244.06 | 01-AUG-00:20 | 1364289.78 | 17-AUG-07:30 | 24.77 | 22.44 | 58.82 |
September | 0.264444E+11 | 525.31 | 19244.06 | 01-SEP-03:02 | 1409167.13 | 20-SEP-08:40 | 24.43 | 22.35 | 47.93 |
October | 0.699377E+10 | 379.50 | 19244.06 | 01-OCT-09:55 | 1427917.26 | 17-OCT-13:20 | 22.73 | 21.38 | 36.22 |
November | 0.190981E+10 | 240.13 | 19244.06 | 01-NOV-10:10 | 1424688.98 | 02-NOV-12:50 | 21.90 | 21.11 | 26.10 |
December | 0.222303E+09 | 147.20 | 2305.05 | 22-DEC-15:10 | 1329229.38 | 22-DEC-15:50 | 21.45 | 21.06 | 16.74 |
Annual Sum or Average | 0.124723E+12 | 4675.60 | 22.95 | 21.50 | 38.09 | ||||
Minimum of Months | 0.127126E+09 | 93.42 | 1260.89 | 769876.67 | 21.28 | 21.06 | 14.13 | ||
Maximum of Months | 0.323002E+11 | 655.90 | 19244.06 | 1475833.17 | 24.82 | 22.49 | 58.82 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 3167458.80 | 0.50 | 1839.96 | 31-JAN-16:30 | 1244517.25 | 31-JAN-15:30 | 21.93 | 21.93 | 0.04 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.28 | 21.28 | 0.00 |
March | 15169555.62 | 1.67 | 3201.21 | 16-MAR-15:30 | 1242526.26 | 20-MAR-15:10 | 21.86 | 21.85 | 0.15 |
April | 0.104428E+10 | 63.00 | 19244.06 | 10-APR-14:30 | 1339751.03 | 24-APR-15:30 | 22.85 | 22.47 | 5.71 |
May | 0.116243E+10 | 113.00 | 19244.06 | 09-MAY-13:00 | 1359670.54 | 18-MAY-14:20 | 23.42 | 22.75 | 9.91 |
June | 0.101816E+11 | 213.42 | 19244.06 | 01-JUN-08:40 | 1303131.48 | 05-JUN-12:40 | 23.90 | 22.74 | 19.24 |
July | 0.145709E+11 | 224.96 | 19244.06 | 01-JUL-15:10 | 1307084.98 | 18-JUL-05:05 | 24.82 | 23.72 | 18.64 |
August | 0.159847E+11 | 236.82 | 19244.06 | 01-AUG-05:03 | 1283178.18 | 24-AUG-19:05 | 24.77 | 23.64 | 19.95 |
September | 0.112501E+11 | 167.99 | 19244.06 | 01-SEP-05:03 | 1247132.79 | 18-SEP-10:00 | 24.43 | 23.59 | 14.58 |
October | 0.304663E+10 | 61.23 | 19244.06 | 02-OCT-08:70 | 1310303.26 | 19-OCT-12:10 | 22.73 | 22.42 | 5.35 |
November | 0.172870E+09 | 4.00 | 19244.06 | 01-NOV-12:30 | 1248773.84 | 09-NOV-14:20 | 21.90 | 21.88 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.45 | 21.45 | 0.00 |
Annual Sum or Average | 0.574319E+11 | 1086.58 | 22.95 | 22.48 | 7.87 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 21.28 | 0.00 | ||
Maximum of Months | 0.159847E+11 | 236.82 | 19244.06 | 1359670.54 | 24.82 | 23.72 | 19.95 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.111911E+11 | 0.00 | 123.16 | 1018175.55 | 02-JAN-06:01 | 0.00 | 23.28 | 32.76 | 0.02 | 0.00 | 0.00 | 0.56 | 02-JAN-06:01 |
February | 0.104413E+11 | 0.00 | 136.64 | 1196696.75 | 13-FEB-06:02 | 0.00 | 22.55 | 34.41 | 0.02 | 0.00 | 0.00 | 0.65 | 13-FEB-06:02 |
March | 0.932050E+10 | 0.00 | 82.54 | 894550.39 | 27-MAR-05:03 | 0.00 | 22.89 | 29.30 | 0.02 | 0.00 | 0.00 | 0.49 | 27-MAR-05:03 |
April | 30058723.31 | 0.00 | 4.62 | 4369.71 | 21-APR-05:50 | 0.00 | 23.73 | 24.10 | 0.00 | 0.00 | 0.00 | 0.00 | 21-APR-05:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 23.45 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.45 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 23.45 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 23.45 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 23.45 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.141890E+10 | 0.00 | 32.83 | 186349.45 | 26-OCT-05:02 | 0.00 | 22.75 | 25.37 | 0.00 | 0.00 | 0.00 | 0.10 | 26-OCT-05:02 |
November | 0.611854E+10 | 0.00 | 92.36 | 862733.26 | 24-NOV-06:03 | 0.00 | 23.07 | 30.48 | 0.01 | 0.00 | 0.00 | 0.47 | 24-NOV-06:03 |
December | 0.334627E+11 | 0.00 | 217.03 | 1136676.73 | 07-DEC-05:01 | 0.00 | 24.16 | 40.42 | 0.06 | 0.00 | 0.01 | 0.62 | 07-DEC-05:01 |
Annual Sum or Average | 0.719832E+11 | 0.00 | 689.20 | 0.00 | 23.31 | 27.81 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.334627E+11 | 0.00 | 217.03 | 1196696.75 | 0.00 | 24.16 | 40.42 | 0.06 | 0.00 | 0.01 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.66 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24.29 | 24.29 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 37.57 | 37.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 30.95 | 30.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 41.57 | 41.57 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 46.37 | 46.37 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 49.20 | 49.20 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 33.07 | 33.07 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 27.88 | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 24.29 | 24.29 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 23.85 | 23.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 31.67 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 | 49.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.427190E+11 | 0.00 | 286.27 | 0.427046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106453.83 | 31-JAN-16:30 | 106453.83 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.108491E+11 | 0.00 | 170.97 | 0.108491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66906.62 | 21-FEB-15:00 | 66906.62 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.465948E+11 | 0.00 | 326.54 | 0.465948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117047.96 | 20-MAR-14:40 | 117047.96 | 20-MAR-14:40 | 0.00 | 0.00 | 0.00 |
April | 0.121909E+12 | 0.00 | 545.17 | 0.121909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 146437.53 | 24-APR-14:50 | 146437.53 | 24-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.133808E+12 | 0.00 | 505.76 | 0.133808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 137432.81 | 31-MAY-16:00 | 137432.81 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.180225E+12 | 0.00 | 604.21 | 0.180224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 166009.42 | 09-JUN-05:02 | 166009.42 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.188071E+12 | 0.00 | 629.81 | 0.177003E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322699.68 | 14-JUL-05:02 | 183525.93 | 17-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.208819E+12 | 0.00 | 653.93 | 0.197092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 293096.38 | 01-AUG-05:03 | 195360.99 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.149349E+12 | 0.00 | 503.60 | 0.139911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 238030.72 | 01-SEP-05:03 | 176727.25 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.917162E+11 | 0.00 | 415.63 | 0.902003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 257116.87 | 03-OCT-05:03 | 174580.71 | 02-OCT-04:03 | 0.00 | 0.00 | 0.00 |
November | 0.491170E+11 | 0.00 | 304.51 | 0.464224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157083.84 | 13-NOV-05:11 | 117699.77 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.245573E+11 | 0.00 | 213.79 | 0.245573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104925.92 | 22-DEC-16:20 | 104925.92 | 22-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124773E+13 | 0.00 | 5160.19 | 0.121128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.108491E+11 | 0.00 | 170.97 | 0.108491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66906.62 | 66906.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.208819E+12 | 0.00 | 653.93 | 0.197092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322699.68 | 195360.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.355006E+12 | 0.00 | 291.23 | 0.354929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 922142.72 | 31-JAN-16:30 | 922142.72 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.820809E+11 | 0.00 | 175.50 | 0.820809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 511948.09 | 22-FEB-16:00 | 511948.09 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.346369E+12 | 0.00 | 318.32 | 0.346369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 984503.14 | 16-MAR-15:30 | 984503.14 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.920911E+12 | 0.00 | 430.96 | 0.920911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1298853.71 | 14-APR-15:20 | 1298853.71 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.120231E+13 | 0.00 | 483.64 | 0.120231E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1311535.54 | 18-MAY-15:20 | 1311535.54 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.159150E+13 | 0.00 | 540.06 | 0.159150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1559011.22 | 09-JUN-05:02 | 1559011.22 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.153652E+13 | 0.00 | 536.70 | 0.145558E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3081448.06 | 14-JUL-05:02 | 1638394.36 | 07-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.156597E+13 | 0.00 | 534.78 | 0.148992E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2026416.59 | 04-AUG-05:03 | 1626839.42 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.129702E+13 | 0.00 | 462.39 | 0.121816E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2421175.53 | 05-SEP-03:02 | 1636554.47 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.750196E+12 | 0.00 | 391.61 | 0.737618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2157434.68 | 03-OCT-04:12 | 1633036.45 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.356260E+12 | 0.00 | 297.14 | 0.341553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1165899.36 | 13-NOV-05:11 | 1009941.73 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.174965E+12 | 0.00 | 209.41 | 0.174965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 804374.80 | 22-DEC-15:50 | 804374.80 | 22-DEC-15:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101791E+14 | 0.00 | 4671.72 | 0.991590E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.820809E+11 | 0.00 | 175.50 | 0.820809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 511948.09 | 511948.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159150E+13 | 0.00 | 540.06 | 0.159150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3081448.06 | 1638394.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.322360E+11 | 0.00 | 278.14 | 0.322258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97649.88 | 31-JAN-16:30 | 97649.88 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.687685E+10 | 0.00 | 155.43 | 0.687685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50205.69 | 22-FEB-16:00 | 50205.69 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.336355E+11 | 0.00 | 301.08 | 0.336355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111654.34 | 16-MAR-15:30 | 111654.34 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.100270E+12 | 0.00 | 427.35 | 0.100270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 153163.90 | 14-APR-15:20 | 153163.90 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.132199E+12 | 0.00 | 480.80 | 0.132199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 154895.11 | 18-MAY-15:30 | 154895.11 | 18-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.180600E+12 | 0.00 | 547.25 | 0.180600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 182291.74 | 28-JUN-14:50 | 182291.74 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.173225E+12 | 0.00 | 548.26 | 0.164936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314258.98 | 14-JUL-05:02 | 183284.88 | 12-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.173708E+12 | 0.00 | 539.02 | 0.165818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 216457.58 | 04-AUG-05:03 | 183575.74 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.140307E+12 | 0.00 | 468.85 | 0.132435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260663.39 | 02-SEP-03:02 | 165700.65 | 08-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.765938E+11 | 0.00 | 379.75 | 0.754236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240547.66 | 03-OCT-05:03 | 174302.21 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.322363E+11 | 0.00 | 279.79 | 0.312020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114395.72 | 01-NOV-15:30 | 114395.72 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.146221E+11 | 0.00 | 188.93 | 0.146221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83664.95 | 22-DEC-15:50 | 83664.95 | 22-DEC-15:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109651E+13 | 0.00 | 4594.65 | 0.107024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.687685E+10 | 0.00 | 155.43 | 0.687685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50205.69 | 50205.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.180600E+12 | 0.00 | 548.26 | 0.180600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314258.98 | 183575.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.271330E+11 | 0.00 | 217.89 | 0.271300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86528.80 | 16-JAN-15:37 | 86528.80 | 16-JAN-15:37 | 0.00 | 0.00 | 0.00 |
February | 0.451509E+10 | 0.00 | 89.15 | 0.448189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57815.26 | 17-FEB-06:03 | 55642.21 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.268149E+11 | 0.00 | 238.16 | 0.268085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70007.21 | 20-MAR-14:00 | 70007.21 | 20-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.643365E+11 | 0.00 | 342.10 | 0.643365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123908.11 | 30-APR-18:09 | 123908.11 | 30-APR-18:09 | 0.00 | 0.00 | 0.00 |
May | 0.795072E+11 | 0.00 | 398.57 | 0.795072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125936.97 | 29-MAY-17:37 | 125936.97 | 29-MAY-17:37 | 0.00 | 0.00 | 0.00 |
June | 0.962831E+11 | 0.00 | 424.44 | 0.962831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116804.64 | 27-JUN-03:02 | 116804.64 | 27-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.102876E+12 | 0.00 | 448.55 | 0.995042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187388.15 | 14-JUL-04:23 | 126380.06 | 04-JUL-18:50 | 0.00 | 0.00 | 0.00 |
August | 0.114697E+12 | 0.00 | 486.72 | 0.110793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 180256.89 | 01-AUG-03:02 | 126304.53 | 27-AUG-12:59 | 0.00 | 0.00 | 0.00 |
September | 0.979540E+11 | 0.00 | 441.63 | 0.937055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170933.96 | 05-SEP-07:10 | 118525.40 | 24-SEP-16:10 | 0.00 | 0.00 | 0.00 |
October | 0.615179E+11 | 0.00 | 351.23 | 0.609810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144015.71 | 03-OCT-05:03 | 125642.05 | 15-OCT-13:29 | 0.00 | 0.00 | 0.00 |
November | 0.318298E+11 | 0.00 | 228.65 | 0.298766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121027.04 | 13-NOV-05:23 | 77426.10 | 20-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.139275E+11 | 0.00 | 152.70 | 0.139253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67972.05 | 26-DEC-13:10 | 67972.05 | 26-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721392E+12 | 0.00 | 3819.80 | 0.707333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.451509E+10 | 0.00 | 89.15 | 0.448189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57815.26 | 55642.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114697E+12 | 0.00 | 486.72 | 0.110793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 187388.15 | 126380.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.292249E+11 | 0.129088E+11 | 715.75 | 0.291962E+11 | 28674621.79 | 0.00 | 0.46 | 27-JAN-16:00 | 0.00 | 20-JAN-21:20 | 136654.30 | 27-JAN-16:00 | 136654.30 | 27-JAN-16:00 | 135.89 | 09-JAN-12:00 | 56132.16 | 27-JAN-16:00 | 0.00 |
February | 0.101732E+11 | 0.585889E+10 | 474.32 | 0.959072E+10 | 0.582525E+09 | 0.00 | 0.29 | 18-FEB-14:00 | 0.00 | 12-FEB-14:20 | 100530.00 | 18-FEB-14:00 | 87487.55 | 18-FEB-15:00 | 13907.05 | 18-FEB-14:00 | 31597.14 | 18-FEB-14:00 | 0.00 |
March | 0.193312E+12 | 0.667992E+11 | 722.24 | 0.189486E+12 | 0.382637E+10 | 0.00 | 0.91 | 15-MAR-12:40 | 0.00 | 04-MAR-22:50 | 318625.98 | 17-MAR-15:20 | 318625.98 | 17-MAR-15:20 | 25863.19 | 17-MAR-10:00 | 118080.12 | 16-MAR-12:40 | 0.00 |
April | 0.672061E+12 | 0.253066E+12 | 720.00 | 0.670348E+12 | 0.171298E+10 | 0.00 | 1.00 | 01-APR-09:15 | 0.03 | 30-APR-24:00 | 377716.63 | 15-APR-09:00 | 377716.63 | 15-APR-09:00 | 33749.37 | 16-APR-06:33 | 153740.95 | 14-APR-16:10 | 0.00 |
May | 0.218752E+12 | 0.878753E+11 | 743.50 | 0.218751E+12 | 463106.27 | 0.00 | 0.67 | 31-MAY-23:10 | 0.01 | 26-MAY-03:10 | 214808.75 | 31-MAY-23:10 | 214808.75 | 31-MAY-23:10 | 97.77 | 11-MAY-02:30 | 83718.49 | 31-MAY-23:10 | 0.00 |
June | 0.520529E+12 | 0.214665E+12 | 720.00 | 0.520521E+12 | 8719942.51 | 0.00 | 0.83 | 30-JUN-23:10 | 0.03 | 21-JUN-06:00 | 306981.86 | 30-JUN-23:57 | 306981.86 | 30-JUN-23:57 | 2730.02 | 04-JUN-05:00 | 119866.62 | 16-JUN-16:00 | 0.00 |
July | 0.872548E+12 | 0.324447E+12 | 744.00 | 0.789294E+12 | 0.832534E+11 | 0.00 | 1.00 | 08-JUL-20:33 | 0.28 | 01-JUL-06:00 | 469714.03 | 14-JUL-01:00 | 392736.87 | 31-JUL-24:00 | 314514.67 | 14-JUL-01:00 | 154452.97 | 05-JUL-16:00 | 0.00 |
August | 0.106710E+13 | 0.377549E+12 | 744.00 | 0.936290E+12 | 0.130806E+12 | 0.00 | 1.00 | 01-AUG-00:03 | 0.37 | 31-AUG-24:00 | 453465.98 | 09-AUG-18:20 | 411086.66 | 27-AUG-13:17 | 262087.93 | 28-AUG-17:00 | 170970.78 | 25-AUG-16:10 | 0.00 |
September | 0.267762E+12 | 0.996889E+11 | 678.92 | 0.241186E+12 | 0.265761E+11 | 0.00 | 0.55 | 04-SEP-10:20 | 0.01 | 27-SEP-03:40 | 234364.81 | 04-SEP-10:13 | 174986.88 | 30-SEP-23:10 | 111872.41 | 04-SEP-10:00 | 70132.32 | 04-SEP-10:20 | 0.00 |
October | 0.251729E+12 | 0.920881E+11 | 716.86 | 0.240731E+12 | 0.109975E+11 | 0.00 | 0.79 | 03-OCT-08:30 | 0.00 | 10-OCT-02:50 | 338365.06 | 03-OCT-08:30 | 229944.05 | 20-OCT-16:00 | 128248.53 | 03-OCT-02:53 | 104221.37 | 03-OCT-08:30 | 0.00 |
November | 0.202148E+12 | 0.677124E+11 | 685.39 | 0.175251E+12 | 0.268972E+11 | 0.00 | 0.97 | 09-NOV-17:00 | 0.00 | 17-NOV-05:12 | 321492.27 | 09-NOV-13:05 | 321492.27 | 09-NOV-13:05 | 170871.62 | 12-NOV-14:53 | 125766.09 | 09-NOV-17:00 | 0.00 |
December | 0.201565E+12 | 0.701058E+11 | 737.69 | 0.201201E+12 | 0.363324E+09 | 0.00 | 1.00 | 02-DEC-13:30 | 0.01 | 13-DEC-05:10 | 348750.92 | 25-DEC-13:51 | 348750.92 | 25-DEC-13:51 | 18149.38 | 13-DEC-11:20 | 128821.50 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.450690E+13 | 0.167276E+13 | 8402.66 | 0.422185E+13 | 0.285053E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101732E+11 | 0.585889E+10 | 474.32 | 0.959072E+10 | 463106.27 | 0.00 | 0.29 | 0.00 | 100530.00 | 87487.55 | 97.77 | 31597.14 | 0.00 | ||||||
Maximum of Months | 0.106710E+13 | 0.377549E+12 | 744.00 | 0.936290E+12 | 0.130806E+12 | 0.00 | 1.00 | 0.37 | 469714.03 | 411086.66 | 314514.67 | 170970.78 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.554230E+10 | 0.151987E+10 | 744.00 | 0.553895E+10 | 3354113.25 | 0.00 | 0.40 | 31-JAN-17:00 | 0.17 | 02-JAN-07:30 | 2892.34 | 24-JAN-17:00 | 2892.34 | 24-JAN-17:00 | 99.86 | 09-JAN-11:30 | 1081.37 | 31-JAN-17:00 | 0.00 |
February | 0.947613E+10 | 0.227161E+10 | 672.00 | 0.943224E+10 | 43883797.21 | 0.00 | 0.54 | 28-FEB-17:00 | 0.40 | 08-FEB-07:10 | 4645.32 | 22-FEB-17:00 | 4587.45 | 22-FEB-17:00 | 171.94 | 16-FEB-10:30 | 1177.37 | 22-FEB-17:00 | 0.00 |
March | 0.158852E+11 | 0.399268E+10 | 744.00 | 0.158736E+11 | 11548300.39 | 0.00 | 0.92 | 31-MAR-24:00 | 0.61 | 07-MAR-08:00 | 7753.49 | 31-MAR-24:00 | 7753.49 | 31-MAR-24:00 | 212.03 | 06-MAR-11:10 | 2327.61 | 16-MAR-16:00 | 0.00 |
April | 0.203002E+11 | 0.639672E+10 | 720.00 | 0.203002E+11 | -0.0 | 0.00 | 1.00 | 01-APR-09:25 | 0.38 | 30-APR-24:00 | 8493.45 | 26-APR-18:40 | 8493.45 | 26-APR-18:40 | 0.00 | 02-APR-18:44 | 3231.41 | 14-APR-16:10 | 0.00 |
May | 0.648312E+10 | 0.237890E+10 | 744.00 | 0.648312E+10 | -0.0 | 0.00 | 0.58 | 31-MAY-23:15 | 0.25 | 13-MAY-06:30 | 4103.23 | 31-MAY-24:00 | 4103.23 | 31-MAY-24:00 | 0.00 | 04-MAY-12:50 | 1516.61 | 31-MAY-23:10 | 0.00 |
June | 0.113662E+11 | 0.457048E+10 | 720.00 | 0.113650E+11 | 1206043.86 | 0.00 | 0.77 | 30-JUN-23:10 | 0.48 | 21-JUN-06:10 | 6013.71 | 30-JUN-23:40 | 6013.71 | 30-JUN-23:40 | 96.10 | 30-JUN-10:00 | 2622.85 | 16-JUN-16:00 | 0.00 |
July | 0.168535E+11 | 0.630850E+10 | 744.00 | 0.167037E+11 | 0.149760E+09 | 0.00 | 1.00 | 02-JUL-17:41 | 0.67 | 01-JUL-06:10 | 7923.48 | 31-JUL-23:55 | 7911.55 | 31-JUL-23:55 | 411.75 | 13-JUL-18:00 | 3349.36 | 02-JUL-18:00 | 0.00 |
August | 0.216996E+11 | 0.778901E+10 | 744.00 | 0.215488E+11 | 0.150790E+09 | 0.00 | 1.00 | 01-AUG-09:00 | 0.35 | 31-AUG-24:00 | 8967.94 | 28-AUG-16:35 | 8466.78 | 14-AUG-02:25 | 597.45 | 28-AUG-16:15 | 3579.62 | 25-AUG-16:10 | 0.00 |
September | 0.645751E+10 | 0.224593E+10 | 720.00 | 0.631915E+10 | 0.138356E+09 | 0.00 | 0.53 | 30-SEP-23:53 | 0.25 | 22-SEP-06:10 | 4113.49 | 30-SEP-23:53 | 4113.49 | 30-SEP-23:53 | 301.89 | 11-SEP-15:10 | 1350.67 | 30-SEP-23:40 | 0.00 |
October | 0.112696E+11 | 0.333633E+10 | 744.00 | 0.112392E+11 | 30367246.16 | 0.00 | 0.72 | 15-OCT-17:02 | 0.42 | 25-OCT-06:45 | 5927.18 | 31-OCT-24:00 | 5927.18 | 31-OCT-24:00 | 307.94 | 03-OCT-09:30 | 2037.10 | 06-OCT-16:00 | 0.00 |
November | 0.155456E+11 | 0.391533E+10 | 720.00 | 0.154963E+11 | 49299254.39 | 0.00 | 0.90 | 09-NOV-17:00 | 0.61 | 18-NOV-07:45 | 7036.05 | 14-NOV-17:00 | 6904.42 | 09-NOV-17:00 | 408.84 | 13-NOV-16:10 | 2470.28 | 09-NOV-16:50 | 0.00 |
December | 0.207424E+11 | 0.508293E+10 | 744.00 | 0.207420E+11 | 414419.38 | 0.00 | 1.00 | 02-DEC-14:30 | 0.82 | 14-DEC-07:10 | 8554.07 | 28-DEC-17:00 | 8554.07 | 28-DEC-17:00 | 65.19 | 13-DEC-11:30 | 2716.49 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.161621E+12 | 0.498083E+11 | 8760.00 | 0.161042E+12 | 0.578980E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.554230E+10 | 0.151987E+10 | 672.00 | 0.553895E+10 | -0.0 | 0.00 | 0.40 | 0.17 | 2892.34 | 2892.34 | 0.00 | 1081.37 | 0.00 | ||||||
Maximum of Months | 0.216996E+11 | 0.778901E+10 | 744.00 | 0.215488E+11 | 0.150790E+09 | 0.00 | 1.00 | 0.82 | 8967.94 | 8554.07 | 597.45 | 3579.62 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.422278E+11 | 0.118613E+11 | 743.92 | 0.421960E+11 | 31842696.71 | 0.00 | 0.39 | 31-JAN-17:00 | 0.00 | 01-JAN-22:25 | 26794.72 | 24-JAN-17:00 | 26794.72 | 24-JAN-17:00 | 928.60 | 09-JAN-11:30 | 10093.31 | 31-JAN-17:00 | 0.00 |
February | 0.802507E+11 | 0.194586E+11 | 672.00 | 0.798197E+11 | 0.431049E+09 | 0.00 | 0.53 | 22-FEB-17:00 | 0.32 | 13-FEB-07:10 | 43370.34 | 22-FEB-17:00 | 42819.06 | 22-FEB-17:00 | 1697.27 | 16-FEB-10:30 | 11019.58 | 22-FEB-17:00 | 0.00 |
March | 0.144086E+12 | 0.365181E+11 | 744.00 | 0.143970E+12 | 0.115338E+09 | 0.00 | 0.90 | 31-MAR-23:50 | 0.56 | 07-MAR-08:00 | 72326.70 | 31-MAR-23:50 | 72326.70 | 31-MAR-23:50 | 2105.05 | 06-MAR-11:20 | 22042.00 | 16-MAR-16:00 | 0.00 |
April | 0.191901E+12 | 0.607385E+11 | 720.00 | 0.191901E+12 | 0.00 | 0.00 | 1.00 | 01-APR-10:20 | 0.33 | 30-APR-24:00 | 80660.64 | 26-APR-18:30 | 80660.64 | 26-APR-18:30 | 0.00 | 17-APR-21:03 | 30838.99 | 14-APR-16:10 | 0.00 |
May | 0.602109E+11 | 0.222078E+11 | 744.00 | 0.602109E+11 | -0.0 | 0.00 | 0.58 | 31-MAY-23:15 | 0.23 | 13-MAY-06:30 | 39683.34 | 31-MAY-24:00 | 39683.34 | 31-MAY-24:00 | 0.00 | 25-MAY-16:30 | 14586.40 | 31-MAY-23:10 | 0.00 |
June | 0.108310E+12 | 0.435631E+11 | 720.00 | 0.108297E+12 | 13226431.78 | 0.00 | 0.78 | 30-JUN-23:13 | 0.48 | 21-JUN-06:10 | 57964.72 | 30-JUN-23:30 | 57964.72 | 30-JUN-23:30 | 987.34 | 30-JUN-10:00 | 25025.01 | 16-JUN-16:00 | 0.00 |
July | 0.160355E+12 | 0.600389E+11 | 744.00 | 0.158864E+12 | 0.149122E+10 | 0.00 | 1.00 | 02-JUL-18:10 | 0.67 | 01-JUL-06:10 | 75887.33 | 31-JUL-23:55 | 75770.40 | 31-JUL-23:55 | 4097.88 | 13-JUL-18:00 | 31846.92 | 02-JUL-18:00 | 0.00 |
August | 0.204438E+12 | 0.737141E+11 | 744.00 | 0.202918E+12 | 0.152044E+10 | 0.00 | 1.00 | 01-AUG-09:20 | 0.31 | 31-AUG-24:00 | 84609.74 | 28-AUG-16:15 | 79785.63 | 06-AUG-18:45 | 6010.95 | 28-AUG-16:15 | 34156.06 | 25-AUG-16:10 | 0.00 |
September | 0.598211E+11 | 0.208897E+11 | 720.00 | 0.584614E+11 | 0.135972E+10 | 0.00 | 0.54 | 30-SEP-23:53 | 0.22 | 22-SEP-06:10 | 39728.10 | 30-SEP-24:00 | 39728.10 | 30-SEP-24:00 | 2981.27 | 11-SEP-15:10 | 13053.66 | 30-SEP-23:30 | 0.00 |
October | 0.102494E+12 | 0.306220E+11 | 744.00 | 0.102193E+12 | 0.301400E+09 | 0.00 | 0.70 | 15-OCT-17:22 | 0.37 | 25-OCT-06:10 | 54604.23 | 31-OCT-24:00 | 54604.23 | 31-OCT-24:00 | 3070.22 | 03-OCT-09:30 | 19331.02 | 06-OCT-16:00 | 0.00 |
November | 0.139658E+12 | 0.354906E+11 | 720.00 | 0.139169E+12 | 0.488750E+09 | 0.00 | 0.89 | 09-NOV-17:00 | 0.56 | 18-NOV-07:35 | 66259.13 | 14-NOV-17:00 | 65063.07 | 09-NOV-17:00 | 4033.21 | 13-NOV-16:10 | 23304.14 | 09-NOV-16:50 | 0.00 |
December | 0.184790E+12 | 0.457796E+11 | 744.00 | 0.184785E+12 | 4994158.48 | 0.00 | 1.00 | 21-DEC-14:40 | 0.75 | 14-DEC-07:10 | 80279.76 | 26-DEC-17:20 | 80279.76 | 26-DEC-17:20 | 720.33 | 13-DEC-11:20 | 25891.69 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.147854E+13 | 0.460882E+12 | 8759.92 | 0.147278E+13 | 0.575798E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.422278E+11 | 0.118613E+11 | 672.00 | 0.421960E+11 | -0.0 | 0.00 | 0.39 | 0.00 | 26794.72 | 26794.72 | 0.00 | 10093.31 | 0.00 | ||||||
Maximum of Months | 0.204438E+12 | 0.737141E+11 | 744.00 | 0.202918E+12 | 0.152044E+10 | 0.00 | 1.00 | 0.75 | 84609.74 | 80660.64 | 6010.95 | 34156.06 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.334418E+10 | 0.964411E+09 | 712.94 | 0.334124E+10 | 2944842.93 | 0.00 | 0.39 | 31-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2716.42 | 24-JAN-17:00 | 2716.42 | 24-JAN-17:00 | 86.16 | 09-JAN-11:50 | 1024.70 | 31-JAN-17:00 | 0.00 |
February | 0.706680E+10 | 0.173461E+10 | 672.00 | 0.702415E+10 | 42643292.91 | 0.00 | 0.53 | 22-FEB-17:00 | 0.20 | 13-FEB-07:10 | 4376.43 | 22-FEB-17:00 | 4320.71 | 22-FEB-17:00 | 170.29 | 16-FEB-10:40 | 1113.48 | 22-FEB-17:00 | 0.00 |
March | 0.137626E+11 | 0.352378E+10 | 744.00 | 0.137512E+11 | 11418938.03 | 0.00 | 0.86 | 31-MAR-23:20 | 0.45 | 27-MAR-06:10 | 7057.04 | 31-MAR-23:20 | 7057.04 | 31-MAR-23:20 | 209.44 | 06-MAR-11:20 | 2236.40 | 16-MAR-16:00 | 0.00 |
April | 0.192145E+11 | 0.612451E+10 | 720.00 | 0.192145E+11 | -0.0 | 0.00 | 1.00 | 01-APR-11:40 | 0.32 | 30-APR-24:00 | 8138.87 | 26-APR-18:00 | 8138.87 | 26-APR-18:00 | 0.00 | 02-APR-17:02 | 3153.93 | 14-APR-16:10 | 0.00 |
May | 0.605170E+10 | 0.224672E+10 | 744.00 | 0.605170E+10 | -0.0 | 0.00 | 0.57 | 31-MAY-23:33 | 0.20 | 13-MAY-06:50 | 3984.01 | 31-MAY-24:00 | 3984.01 | 31-MAY-24:00 | 0.00 | 03-MAY-04:12 | 1464.53 | 31-MAY-23:15 | 0.00 |
June | 0.110017E+11 | 0.443544E+10 | 720.00 | 0.110004E+11 | 1266570.49 | 0.00 | 0.76 | 30-JUN-23:10 | 0.46 | 21-JUN-06:10 | 5837.80 | 30-JUN-23:45 | 5837.80 | 30-JUN-23:45 | 97.44 | 30-JUN-10:00 | 2579.09 | 16-JUN-16:00 | 0.00 |
July | 0.162173E+11 | 0.608604E+10 | 744.00 | 0.160681E+11 | 0.149237E+09 | 0.00 | 1.00 | 02-JUL-17:30 | 0.65 | 29-JUL-06:05 | 7652.98 | 31-JUL-23:55 | 7642.16 | 31-JUL-23:45 | 409.81 | 13-JUL-18:00 | 3269.93 | 02-JUL-18:00 | 0.00 |
August | 0.206260E+11 | 0.746657E+10 | 744.00 | 0.204726E+11 | 0.153369E+09 | 0.00 | 1.00 | 01-AUG-10:20 | 0.30 | 31-AUG-24:00 | 8581.45 | 28-AUG-16:05 | 8154.97 | 06-AUG-18:45 | 590.60 | 28-AUG-16:05 | 3493.38 | 25-AUG-16:10 | 0.00 |
September | 0.605604E+10 | 0.212232E+10 | 720.00 | 0.591965E+10 | 0.136385E+09 | 0.00 | 0.53 | 30-SEP-23:53 | 0.19 | 22-SEP-06:40 | 4001.80 | 30-SEP-24:00 | 4001.80 | 30-SEP-24:00 | 300.00 | 11-SEP-15:10 | 1321.85 | 08-SEP-16:00 | 0.00 |
October | 0.989213E+10 | 0.298908E+10 | 744.00 | 0.986206E+10 | 30064040.29 | 0.00 | 0.70 | 15-OCT-17:11 | 0.31 | 26-OCT-06:10 | 5276.62 | 31-OCT-23:50 | 5276.62 | 31-OCT-23:50 | 307.56 | 03-OCT-09:30 | 1975.36 | 06-OCT-16:00 | 0.00 |
November | 0.131507E+11 | 0.338070E+10 | 720.00 | 0.131021E+11 | 48557075.14 | 0.00 | 0.88 | 09-NOV-17:00 | 0.43 | 24-NOV-07:05 | 6652.92 | 14-NOV-17:00 | 6566.63 | 09-NOV-17:00 | 403.84 | 13-NOV-16:10 | 2357.07 | 09-NOV-16:50 | 0.00 |
December | 0.172034E+11 | 0.431953E+10 | 744.00 | 0.172030E+11 | 471487.34 | 0.00 | 1.00 | 21-DEC-16:30 | 0.62 | 18-DEC-05:11 | 8089.80 | 26-DEC-17:00 | 8089.80 | 26-DEC-17:00 | 67.71 | 13-DEC-11:30 | 2640.76 | 22-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.143587E+12 | 0.453937E+11 | 8728.94 | 0.143011E+12 | 0.576357E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.334418E+10 | 0.964411E+09 | 672.00 | 0.334124E+10 | -0.0 | 0.00 | 0.39 | 0.00 | 2716.42 | 2716.42 | 0.00 | 1024.70 | 0.00 | ||||||
Maximum of Months | 0.206260E+11 | 0.746657E+10 | 744.00 | 0.204726E+11 | 0.153369E+09 | 0.00 | 1.00 | 0.65 | 8581.45 | 8154.97 | 590.60 | 3493.38 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 60.30 | 522.04 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 36.03 | 534.19 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 120.70 | 457.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 301.01 | 239.35 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 425.61 | 157.78 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 684.69 | 62.65 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 583.51 | 48.89 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 478.74 | 65.86 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 399.42 | 99.19 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 177.76 | 325.08 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 61.81 | 491.57 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 27.38 | 657.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 280.85 | 304.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 27.38 | 48.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 684.69 | 657.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 60.30 | 522.04 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 36.03 | 534.19 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 120.70 | 457.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 301.01 | 239.35 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 425.61 | 157.78 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 684.69 | 62.65 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 583.51 | 48.89 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 478.74 | 65.86 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 399.41 | 99.19 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 177.76 | 325.08 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 61.81 | 491.57 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 27.38 | 657.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 280.85 | 304.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 27.38 | 48.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 684.69 | 657.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 60.30 | 522.04 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 36.03 | 534.19 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 120.70 | 457.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 301.01 | 239.35 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 425.61 | 157.78 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 684.69 | 62.65 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 583.51 | 48.89 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 478.74 | 65.86 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 399.42 | 99.19 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 177.76 | 325.08 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 61.81 | 491.57 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 27.38 | 657.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 280.85 | 304.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 27.38 | 48.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 684.69 | 657.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 60.30 | 522.04 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 36.03 | 534.19 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 120.70 | 457.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 301.01 | 239.35 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 425.61 | 157.78 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 684.69 | 62.65 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 583.51 | 48.89 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 478.74 | 65.86 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 399.41 | 99.19 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 177.76 | 325.08 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 61.81 | 491.57 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 27.38 | 657.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 280.85 | 304.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 27.38 | 48.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 684.69 | 657.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 60.30 | 522.02 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 36.03 | 534.17 | 0.00 | 0.00 | 0.00 |
March | 152.95 | 0.00 | 152.95 | 120.69 | 457.92 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.41 | 301.00 | 239.34 | 0.00 | 0.00 | 0.00 |
May | 218.14 | 17.47 | 200.67 | 425.59 | 157.77 | 0.00 | 0.00 | 0.00 |
June | 253.49 | 46.06 | 207.43 | 684.66 | 62.64 | 0.00 | 0.00 | 0.00 |
July | 216.18 | 22.52 | 193.66 | 583.48 | 48.89 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.33 | 170.16 | 478.72 | 65.86 | 0.00 | 0.00 | 0.00 |
September | 164.63 | 0.04 | 164.59 | 399.40 | 99.19 | 0.00 | 0.00 | 0.00 |
October | 127.37 | 0.00 | 127.37 | 177.75 | 325.06 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 61.81 | 491.55 | 0.00 | 0.00 | 0.00 |
December | 94.34 | 0.00 | 94.34 | 27.38 | 657.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.34 | 7.71 | 151.63 | 280.84 | 304.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.34 | 0.00 | 94.34 | 27.38 | 48.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.49 | 46.06 | 207.43 | 684.66 | 657.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 435.28 | 524.35 | 0.00 | 0.00 | 0.00 |
February | 357.36 | 204.42 | 152.93 | 376.25 | 536.24 | 0.00 | 0.00 | 0.00 |
March | 447.22 | 230.05 | 217.16 | 556.36 | 455.99 | 0.00 | 0.00 | 0.00 |
April | 638.38 | 380.48 | 257.90 | 1056.02 | 235.43 | 0.00 | 0.00 | 0.00 |
May | 661.59 | 392.18 | 269.40 | 1179.71 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 689.59 | 428.50 | 261.09 | 1444.57 | 62.59 | 0.00 | 0.00 | 0.00 |
July | 582.40 | 328.39 | 254.01 | 1237.57 | 46.04 | 0.00 | 0.00 | 0.00 |
August | 552.75 | 315.45 | 237.30 | 1162.62 | 58.99 | 0.00 | 0.00 | 0.00 |
September | 453.57 | 218.63 | 234.94 | 910.57 | 100.28 | 0.00 | 0.00 | 0.00 |
October | 455.58 | 277.26 | 178.32 | 706.69 | 324.97 | 0.00 | 0.00 | 0.00 |
November | 350.32 | 210.30 | 140.02 | 420.11 | 489.22 | 0.00 | 0.00 | 0.00 |
December | 319.40 | 192.86 | 126.54 | 325.24 | 641.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.83 | 284.20 | 205.63 | 819.67 | 303.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.40 | 192.86 | 126.54 | 325.24 | 46.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.59 | 428.50 | 269.40 | 1444.57 | 641.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 435.28 | 524.35 | 0.00 | 0.00 | 0.00 |
February | 357.36 | 204.42 | 152.93 | 376.25 | 536.24 | 0.00 | 0.00 | 0.00 |
March | 447.22 | 230.05 | 217.16 | 556.36 | 455.99 | 0.00 | 0.00 | 0.00 |
April | 638.38 | 380.48 | 257.90 | 1056.02 | 235.43 | 0.00 | 0.00 | 0.00 |
May | 661.59 | 392.18 | 269.40 | 1179.71 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 689.59 | 428.50 | 261.09 | 1444.57 | 62.59 | 0.00 | 0.00 | 0.00 |
July | 582.40 | 328.39 | 254.01 | 1237.57 | 46.04 | 0.00 | 0.00 | 0.00 |
August | 552.75 | 315.45 | 237.30 | 1162.62 | 58.99 | 0.00 | 0.00 | 0.00 |
September | 453.57 | 218.63 | 234.94 | 910.57 | 100.28 | 0.00 | 0.00 | 0.00 |
October | 455.58 | 277.26 | 178.32 | 706.69 | 324.97 | 0.00 | 0.00 | 0.00 |
November | 350.32 | 210.30 | 140.02 | 420.11 | 489.22 | 0.00 | 0.00 | 0.00 |
December | 319.40 | 192.86 | 126.54 | 325.24 | 641.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.83 | 284.20 | 205.63 | 819.67 | 303.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.40 | 192.86 | 126.54 | 325.24 | 46.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.59 | 428.50 | 269.40 | 1444.57 | 641.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 435.28 | 524.34 | 0.00 | 0.00 | 0.00 |
February | 357.35 | 204.42 | 152.93 | 376.25 | 536.23 | 0.00 | 0.00 | 0.00 |
March | 447.21 | 230.05 | 217.16 | 556.35 | 455.99 | 0.00 | 0.00 | 0.00 |
April | 638.36 | 380.47 | 257.89 | 1056.00 | 235.42 | 0.00 | 0.00 | 0.00 |
May | 661.57 | 392.18 | 269.40 | 1179.69 | 173.17 | 0.00 | 0.00 | 0.00 |
June | 689.58 | 428.49 | 261.08 | 1444.55 | 62.59 | 0.00 | 0.00 | 0.00 |
July | 582.39 | 328.39 | 254.00 | 1237.55 | 46.04 | 0.00 | 0.00 | 0.00 |
August | 552.74 | 315.45 | 237.29 | 1162.60 | 58.99 | 0.00 | 0.00 | 0.00 |
September | 453.56 | 218.62 | 234.94 | 910.55 | 100.28 | 0.00 | 0.00 | 0.00 |
October | 455.57 | 277.26 | 178.31 | 706.68 | 324.96 | 0.00 | 0.00 | 0.00 |
November | 350.31 | 210.30 | 140.01 | 420.10 | 489.21 | 0.00 | 0.00 | 0.00 |
December | 319.39 | 192.86 | 126.53 | 325.23 | 641.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.82 | 284.20 | 205.62 | 819.66 | 303.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.39 | 192.86 | 126.53 | 325.23 | 46.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 428.49 | 269.40 | 1444.55 | 641.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.54 | 493.46 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 691.44 | 487.12 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 622.05 | 442.19 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.96 | 702.06 | 249.69 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 527.38 | 173.82 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 620.23 | 65.84 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 602.30 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 687.66 | 66.90 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 825.31 | 102.34 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1016.54 | 313.19 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1045.62 | 458.14 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1091.89 | 594.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 807.62 | 290.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 527.38 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.96 | 1246.54 | 594.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.54 | 493.46 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 691.44 | 487.12 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 622.05 | 442.19 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.95 | 702.06 | 249.69 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 527.38 | 173.82 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 620.23 | 65.84 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 602.30 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 687.66 | 66.90 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 825.31 | 102.34 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1016.54 | 313.19 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1045.62 | 458.14 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1091.89 | 594.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 807.62 | 290.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 527.38 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.95 | 1246.54 | 594.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.54 | 493.46 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 691.44 | 487.12 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 622.05 | 442.19 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.96 | 702.06 | 249.69 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 527.38 | 173.82 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 620.23 | 65.84 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 602.30 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 687.66 | 66.90 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 825.31 | 102.34 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1016.54 | 313.19 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1045.62 | 458.14 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1091.89 | 594.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 807.62 | 290.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 527.38 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.96 | 1246.54 | 594.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.54 | 493.46 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 691.44 | 487.12 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 622.05 | 442.19 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.95 | 702.06 | 249.69 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 527.38 | 173.82 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 620.23 | 65.84 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 602.30 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 687.66 | 66.90 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 825.31 | 102.34 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1016.54 | 313.19 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1045.62 | 458.14 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1091.89 | 594.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 807.62 | 290.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 527.38 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.95 | 1246.54 | 594.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.64 | 664.21 | 167.43 | 1246.49 | 493.44 | 0.00 | 0.00 | 0.00 |
February | 525.83 | 354.64 | 171.19 | 691.41 | 487.10 | 0.00 | 0.00 | 0.00 |
March | 437.53 | 225.35 | 212.18 | 622.03 | 442.17 | 0.00 | 0.00 | 0.00 |
April | 372.45 | 150.51 | 221.95 | 702.03 | 249.68 | 0.00 | 0.00 | 0.00 |
May | 249.58 | 41.23 | 208.35 | 527.36 | 173.81 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.47 | 197.24 | 620.21 | 65.83 | 0.00 | 0.00 | 0.00 |
July | 218.38 | 22.59 | 195.79 | 602.27 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 265.54 | 73.38 | 192.16 | 687.63 | 66.89 | 0.00 | 0.00 | 0.00 |
September | 382.62 | 163.23 | 219.38 | 825.28 | 102.33 | 0.00 | 0.00 | 0.00 |
October | 609.66 | 421.98 | 187.68 | 1016.50 | 313.18 | 0.00 | 0.00 | 0.00 |
November | 710.48 | 544.19 | 166.29 | 1045.58 | 458.12 | 0.00 | 0.00 | 0.00 |
December | 773.18 | 612.07 | 161.10 | 1091.85 | 594.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.90 | 274.10 | 191.79 | 807.59 | 290.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.47 | 161.10 | 527.36 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.64 | 664.21 | 221.95 | 1246.49 | 594.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.62 | 143.48 | 523.13 | 618.71 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 323.29 | 638.43 | 0.00 | 0.00 | 0.00 |
March | 406.78 | 193.92 | 212.86 | 504.23 | 561.36 | 0.00 | 0.00 | 0.00 |
April | 624.62 | 356.30 | 268.32 | 1035.56 | 336.92 | 0.00 | 0.00 | 0.00 |
May | 626.22 | 351.12 | 275.10 | 1138.07 | 224.46 | 0.00 | 0.00 | 0.00 |
June | 665.74 | 391.56 | 274.18 | 1391.32 | 98.57 | 0.00 | 0.00 | 0.00 |
July | 484.54 | 226.18 | 258.36 | 1035.07 | 80.14 | 0.00 | 0.00 | 0.00 |
August | 462.05 | 232.05 | 230.00 | 967.16 | 118.40 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 818.82 | 132.64 | 0.00 | 0.00 | 0.00 |
October | 412.10 | 235.64 | 176.46 | 652.43 | 404.33 | 0.00 | 0.00 | 0.00 |
November | 379.56 | 229.17 | 150.39 | 500.03 | 611.43 | 0.00 | 0.00 | 0.00 |
December | 305.91 | 174.17 | 131.73 | 353.78 | 808.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.23 | 245.63 | 209.60 | 772.09 | 385.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.91 | 148.47 | 131.73 | 323.29 | 80.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.74 | 391.56 | 275.10 | 1391.32 | 808.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.62 | 143.48 | 523.13 | 618.71 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 323.29 | 638.43 | 0.00 | 0.00 | 0.00 |
March | 406.78 | 193.92 | 212.86 | 504.23 | 561.36 | 0.00 | 0.00 | 0.00 |
April | 624.62 | 356.30 | 268.32 | 1035.56 | 336.92 | 0.00 | 0.00 | 0.00 |
May | 626.22 | 351.12 | 275.10 | 1138.07 | 224.46 | 0.00 | 0.00 | 0.00 |
June | 665.74 | 391.56 | 274.18 | 1391.32 | 98.57 | 0.00 | 0.00 | 0.00 |
July | 484.54 | 226.18 | 258.36 | 1035.07 | 80.14 | 0.00 | 0.00 | 0.00 |
August | 462.05 | 232.05 | 230.00 | 967.16 | 118.40 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 818.82 | 132.64 | 0.00 | 0.00 | 0.00 |
October | 412.10 | 235.64 | 176.46 | 652.43 | 404.33 | 0.00 | 0.00 | 0.00 |
November | 379.56 | 229.17 | 150.39 | 500.03 | 611.43 | 0.00 | 0.00 | 0.00 |
December | 305.91 | 174.17 | 131.73 | 353.78 | 808.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.23 | 245.63 | 209.60 | 772.09 | 385.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.91 | 148.47 | 131.73 | 323.29 | 80.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.74 | 391.56 | 275.10 | 1391.32 | 808.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.61 | 143.48 | 523.12 | 618.70 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 323.28 | 638.42 | 0.00 | 0.00 | 0.00 |
March | 406.77 | 193.91 | 212.86 | 504.22 | 561.35 | 0.00 | 0.00 | 0.00 |
April | 624.61 | 356.30 | 268.31 | 1035.54 | 336.91 | 0.00 | 0.00 | 0.00 |
May | 626.21 | 351.12 | 275.09 | 1138.05 | 224.46 | 0.00 | 0.00 | 0.00 |
June | 665.73 | 391.55 | 274.17 | 1391.30 | 98.57 | 0.00 | 0.00 | 0.00 |
July | 484.53 | 226.18 | 258.35 | 1035.05 | 80.14 | 0.00 | 0.00 | 0.00 |
August | 462.04 | 232.05 | 230.00 | 967.15 | 118.40 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 818.81 | 132.64 | 0.00 | 0.00 | 0.00 |
October | 412.09 | 235.63 | 176.46 | 652.41 | 404.33 | 0.00 | 0.00 | 0.00 |
November | 379.55 | 229.16 | 150.39 | 500.02 | 611.42 | 0.00 | 0.00 | 0.00 |
December | 305.90 | 174.17 | 131.73 | 353.77 | 808.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.22 | 245.62 | 209.59 | 772.08 | 385.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.90 | 148.47 | 131.73 | 323.28 | 80.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.73 | 391.55 | 275.09 | 1391.30 | 808.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.01 | 0.00 | 505.01 | 391.89 | 2304.16 | 0.00 | 0.00 | 0.00 |
February | 575.45 | 0.00 | 575.45 | 239.07 | 2336.06 | 0.00 | 0.00 | 0.00 |
March | 764.77 | 0.00 | 764.77 | 675.03 | 2057.78 | 0.00 | 0.00 | 0.00 |
April | 931.76 | 9.67 | 922.09 | 1573.00 | 1127.14 | 0.00 | 0.00 | 0.00 |
May | 1090.72 | 87.33 | 1003.39 | 2168.64 | 762.99 | 0.00 | 0.00 | 0.00 |
June | 1267.49 | 230.29 | 1037.20 | 3467.07 | 320.48 | 0.00 | 0.00 | 0.00 |
July | 1080.93 | 112.61 | 968.32 | 2964.24 | 247.02 | 0.00 | 0.00 | 0.00 |
August | 872.50 | 21.68 | 850.83 | 2469.01 | 309.46 | 0.00 | 0.00 | 0.00 |
September | 823.19 | 0.22 | 822.97 | 2032.43 | 477.29 | 0.00 | 0.00 | 0.00 |
October | 636.89 | 0.00 | 636.89 | 950.49 | 1474.05 | 0.00 | 0.00 | 0.00 |
November | 530.64 | 0.00 | 530.64 | 383.33 | 2148.78 | 0.00 | 0.00 | 0.00 |
December | 471.73 | 0.00 | 471.73 | 226.56 | 2829.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.72 | 38.56 | 758.16 | 1467.37 | 1362.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.73 | 0.00 | 471.73 | 226.56 | 247.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1267.49 | 230.29 | 1037.20 | 3467.07 | 2829.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1087.62 | 682.29 | 405.32 | 1338.64 | 1443.71 | 0.00 | 0.00 | 0.00 |
February | 1072.06 | 613.27 | 458.79 | 1142.47 | 1477.00 | 0.00 | 0.00 | 0.00 |
March | 1341.63 | 690.15 | 651.49 | 1672.77 | 1294.89 | 0.00 | 0.00 | 0.00 |
April | 1915.11 | 1141.43 | 773.68 | 3142.31 | 726.14 | 0.00 | 0.00 | 0.00 |
May | 1984.74 | 1176.54 | 808.20 | 3515.72 | 518.54 | 0.00 | 0.00 | 0.00 |
June | 2068.74 | 1285.49 | 783.26 | 4307.30 | 205.58 | 0.00 | 0.00 | 0.00 |
July | 1747.18 | 985.17 | 762.02 | 3683.82 | 158.86 | 0.00 | 0.00 | 0.00 |
August | 1658.23 | 946.35 | 711.88 | 3467.32 | 201.96 | 0.00 | 0.00 | 0.00 |
September | 1360.69 | 655.88 | 704.81 | 2716.47 | 305.11 | 0.00 | 0.00 | 0.00 |
October | 1366.73 | 831.78 | 534.95 | 2117.02 | 928.78 | 0.00 | 0.00 | 0.00 |
November | 1050.94 | 630.89 | 420.05 | 1281.17 | 1353.48 | 0.00 | 0.00 | 0.00 |
December | 958.18 | 578.58 | 379.60 | 1023.58 | 1756.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1469.47 | 852.60 | 616.87 | 2456.96 | 861.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 958.18 | 578.58 | 379.60 | 1023.58 | 158.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.74 | 1285.49 | 808.20 | 4307.30 | 1756.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4158.30 | 3321.12 | 837.18 | 6180.71 | 2417.90 | 0.00 | 0.00 | 0.00 |
February | 2629.24 | 1773.25 | 855.99 | 3430.68 | 2334.25 | 0.00 | 0.00 | 0.00 |
March | 2187.72 | 1126.79 | 1060.93 | 3099.30 | 2124.38 | 0.00 | 0.00 | 0.00 |
April | 1862.32 | 752.56 | 1109.76 | 3517.14 | 1219.32 | 0.00 | 0.00 | 0.00 |
May | 1247.95 | 206.18 | 1041.77 | 2662.63 | 846.59 | 0.00 | 0.00 | 0.00 |
June | 1068.61 | 82.38 | 986.23 | 3153.78 | 330.68 | 0.00 | 0.00 | 0.00 |
July | 1091.93 | 112.97 | 978.96 | 3055.00 | 249.29 | 0.00 | 0.00 | 0.00 |
August | 1327.73 | 366.92 | 960.81 | 3486.58 | 321.14 | 0.00 | 0.00 | 0.00 |
September | 1913.14 | 816.19 | 1096.95 | 4116.81 | 505.28 | 0.00 | 0.00 | 0.00 |
October | 3048.38 | 2109.94 | 938.45 | 5042.82 | 1524.46 | 0.00 | 0.00 | 0.00 |
November | 3552.52 | 2721.05 | 831.47 | 5190.77 | 2208.99 | 0.00 | 0.00 | 0.00 |
December | 3865.99 | 3060.45 | 805.54 | 5441.30 | 2864.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2329.55 | 1370.55 | 958.99 | 4036.80 | 1408.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1068.61 | 82.38 | 805.54 | 2662.63 | 249.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4158.30 | 3321.12 | 1109.76 | 6180.71 | 2864.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1137.30 | 706.85 | 430.45 | 1623.81 | 1642.93 | 0.00 | 0.00 | 0.00 |
February | 921.32 | 445.40 | 475.92 | 1022.41 | 1601.45 | 0.00 | 0.00 | 0.00 |
March | 1220.32 | 581.75 | 638.58 | 1589.76 | 1425.25 | 0.00 | 0.00 | 0.00 |
April | 1873.84 | 1068.90 | 804.95 | 3171.68 | 873.69 | 0.00 | 0.00 | 0.00 |
May | 1878.65 | 1053.36 | 825.29 | 3429.72 | 628.58 | 0.00 | 0.00 | 0.00 |
June | 1997.20 | 1174.67 | 822.52 | 4217.04 | 271.60 | 0.00 | 0.00 | 0.00 |
July | 1453.61 | 678.54 | 775.07 | 3182.33 | 201.94 | 0.00 | 0.00 | 0.00 |
August | 1386.14 | 696.15 | 689.99 | 3013.44 | 251.85 | 0.00 | 0.00 | 0.00 |
September | 1208.25 | 507.66 | 700.59 | 2485.65 | 354.64 | 0.00 | 0.00 | 0.00 |
October | 1236.29 | 706.91 | 529.38 | 2007.19 | 1051.66 | 0.00 | 0.00 | 0.00 |
November | 1138.66 | 687.49 | 451.17 | 1565.51 | 1524.52 | 0.00 | 0.00 | 0.00 |
December | 917.71 | 522.52 | 395.19 | 1151.00 | 1970.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1365.66 | 736.88 | 628.78 | 2377.37 | 980.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 917.71 | 445.40 | 395.19 | 1022.41 | 201.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1997.20 | 1174.67 | 825.29 | 4217.04 | 1970.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.01 | 0.00 | 505.01 | 443.98 | 2117.27 | 0.00 | 0.00 | 0.00 |
February | 575.45 | 0.00 | 575.45 | 279.25 | 2110.20 | 0.00 | 0.00 | 0.00 |
March | 764.77 | 0.00 | 764.77 | 714.81 | 1922.91 | 0.00 | 0.00 | 0.00 |
April | 931.76 | 9.67 | 922.09 | 1566.00 | 1097.08 | 0.00 | 0.00 | 0.00 |
May | 1090.72 | 87.33 | 1003.39 | 2151.91 | 758.82 | 0.00 | 0.00 | 0.00 |
June | 1267.49 | 230.29 | 1037.20 | 3427.57 | 326.85 | 0.00 | 0.00 | 0.00 |
July | 1080.93 | 112.61 | 968.32 | 2920.65 | 253.92 | 0.00 | 0.00 | 0.00 |
August | 872.50 | 21.68 | 850.83 | 2435.77 | 314.12 | 0.00 | 0.00 | 0.00 |
September | 823.19 | 0.22 | 822.97 | 2007.30 | 478.50 | 0.00 | 0.00 | 0.00 |
October | 636.89 | 0.00 | 636.89 | 968.63 | 1386.85 | 0.00 | 0.00 | 0.00 |
November | 530.64 | 0.00 | 530.64 | 426.62 | 1965.29 | 0.00 | 0.00 | 0.00 |
December | 471.73 | 0.00 | 471.73 | 279.40 | 2585.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.72 | 38.56 | 758.16 | 1474.01 | 1272.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.73 | 0.00 | 471.73 | 279.25 | 253.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1267.49 | 230.29 | 1037.20 | 3427.57 | 2585.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1087.62 | 682.29 | 405.32 | 1376.84 | 1349.23 | 0.00 | 0.00 | 0.00 |
February | 1072.06 | 613.27 | 458.79 | 1174.96 | 1358.14 | 0.00 | 0.00 | 0.00 |
March | 1341.63 | 690.15 | 651.49 | 1694.71 | 1231.10 | 0.00 | 0.00 | 0.00 |
April | 1915.11 | 1141.43 | 773.68 | 3126.54 | 718.34 | 0.00 | 0.00 | 0.00 |
May | 1984.74 | 1176.54 | 808.20 | 3493.31 | 518.75 | 0.00 | 0.00 | 0.00 |
June | 2068.74 | 1285.49 | 783.26 | 4271.09 | 211.08 | 0.00 | 0.00 | 0.00 |
July | 1747.18 | 985.17 | 762.02 | 3646.39 | 164.08 | 0.00 | 0.00 | 0.00 |
August | 1658.23 | 946.35 | 711.88 | 3436.34 | 206.20 | 0.00 | 0.00 | 0.00 |
September | 1360.69 | 655.88 | 704.81 | 2692.92 | 307.56 | 0.00 | 0.00 | 0.00 |
October | 1366.73 | 831.78 | 534.95 | 2120.25 | 890.99 | 0.00 | 0.00 | 0.00 |
November | 1050.94 | 630.89 | 420.05 | 1312.92 | 1261.29 | 0.00 | 0.00 | 0.00 |
December | 958.18 | 578.58 | 379.60 | 1077.97 | 1623.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1469.47 | 852.60 | 616.87 | 2458.15 | 817.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 958.18 | 578.58 | 379.60 | 1077.97 | 164.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.74 | 1285.49 | 808.20 | 4271.09 | 1623.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4158.30 | 3321.12 | 837.18 | 6217.76 | 2275.65 | 0.00 | 0.00 | 0.00 |
February | 2629.24 | 1773.25 | 855.99 | 3471.51 | 2149.20 | 0.00 | 0.00 | 0.00 |
March | 2187.72 | 1126.79 | 1060.93 | 3125.55 | 2012.83 | 0.00 | 0.00 | 0.00 |
April | 1862.32 | 752.56 | 1109.76 | 3499.14 | 1192.46 | 0.00 | 0.00 | 0.00 |
May | 1247.95 | 206.18 | 1041.77 | 2641.79 | 837.13 | 0.00 | 0.00 | 0.00 |
June | 1068.61 | 82.38 | 986.23 | 3114.31 | 334.89 | 0.00 | 0.00 | 0.00 |
July | 1091.93 | 112.97 | 978.96 | 3010.83 | 254.87 | 0.00 | 0.00 | 0.00 |
August | 1327.73 | 366.92 | 960.81 | 3449.64 | 324.79 | 0.00 | 0.00 | 0.00 |
September | 1913.14 | 816.19 | 1096.95 | 4085.13 | 507.77 | 0.00 | 0.00 | 0.00 |
October | 3048.38 | 2109.94 | 938.45 | 5042.36 | 1462.14 | 0.00 | 0.00 | 0.00 |
November | 3552.52 | 2721.05 | 831.47 | 5223.75 | 2074.57 | 0.00 | 0.00 | 0.00 |
December | 3865.99 | 3060.45 | 805.54 | 5498.28 | 2671.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2329.55 | 1370.55 | 958.99 | 4036.83 | 1338.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1068.61 | 82.38 | 805.54 | 2641.79 | 254.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4158.30 | 3321.12 | 1109.76 | 6217.76 | 2671.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1137.30 | 706.85 | 430.45 | 1641.05 | 1541.59 | 0.00 | 0.00 | 0.00 |
February | 921.32 | 445.40 | 475.92 | 1037.36 | 1484.33 | 0.00 | 0.00 | 0.00 |
March | 1220.32 | 581.75 | 638.58 | 1602.72 | 1353.99 | 0.00 | 0.00 | 0.00 |
April | 1873.84 | 1068.90 | 804.95 | 3157.46 | 855.64 | 0.00 | 0.00 | 0.00 |
May | 1878.65 | 1053.36 | 825.29 | 3410.14 | 622.55 | 0.00 | 0.00 | 0.00 |
June | 1997.20 | 1174.67 | 822.52 | 4185.47 | 273.72 | 0.00 | 0.00 | 0.00 |
July | 1453.61 | 678.54 | 775.07 | 3152.97 | 204.65 | 0.00 | 0.00 | 0.00 |
August | 1386.14 | 696.15 | 689.99 | 2989.33 | 253.21 | 0.00 | 0.00 | 0.00 |
September | 1208.25 | 507.66 | 700.59 | 2466.84 | 353.97 | 0.00 | 0.00 | 0.00 |
October | 1236.29 | 706.91 | 529.38 | 2007.52 | 1006.24 | 0.00 | 0.00 | 0.00 |
November | 1138.66 | 687.49 | 451.17 | 1579.77 | 1428.69 | 0.00 | 0.00 | 0.00 |
December | 917.71 | 522.52 | 395.19 | 1173.74 | 1840.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1365.66 | 736.88 | 628.78 | 2372.70 | 932.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 917.71 | 445.40 | 395.19 | 1037.36 | 204.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1997.20 | 1174.67 | 825.29 | 4185.47 | 1840.08 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270528E+09 | 0.00 | 0.270528E+09 | 0.161518E+09 | 0.139822E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 87175283.48 | 0.129232E+10 |
March | 0.409677E+09 | 0.00 | 0.409677E+09 | 0.323279E+09 | 0.122655E+10 |
April | 0.483030E+09 | 5012605.91 | 0.478017E+09 | 0.780224E+09 | 0.620391E+09 |
May | 0.584285E+09 | 46784161.73 | 0.537501E+09 | 0.113996E+10 | 0.422601E+09 |
June | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.177471E+10 | 0.162378E+09 |
July | 0.579038E+09 | 60324299.85 | 0.518714E+09 | 0.156287E+10 | 0.130943E+09 |
August | 0.467388E+09 | 11611013.59 | 0.455777E+09 | 0.128225E+10 | 0.176398E+09 |
September | 0.426749E+09 | 113921.23 | 0.426635E+09 | 0.103528E+10 | 0.257103E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.476113E+09 | 0.870681E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.160206E+09 | 0.127416E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332741.68 | 0.176023E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243230E+09 | 0.478192E+10 | 0.885691E+10 | 0.959198E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332741.68 | 0.130943E+09 |
Maximum of Months | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.177471E+10 | 0.176023E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270527E+09 | 0.00 | 0.270527E+09 | 0.161518E+09 | 0.139822E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 87175134.41 | 0.129232E+10 |
March | 0.409676E+09 | 0.00 | 0.409676E+09 | 0.323278E+09 | 0.122654E+10 |
April | 0.483029E+09 | 5012599.89 | 0.478017E+09 | 0.780224E+09 | 0.620391E+09 |
May | 0.584285E+09 | 46784105.59 | 0.537501E+09 | 0.113996E+10 | 0.422601E+09 |
June | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.177471E+10 | 0.162378E+09 |
July | 0.579038E+09 | 60324227.47 | 0.518713E+09 | 0.156286E+10 | 0.130942E+09 |
August | 0.467388E+09 | 11610999.65 | 0.455777E+09 | 0.128225E+10 | 0.176398E+09 |
September | 0.426748E+09 | 113921.09 | 0.426635E+09 | 0.103528E+10 | 0.257103E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.476113E+09 | 0.870681E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.160206E+09 | 0.127416E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332675.32 | 0.176023E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243229E+09 | 0.478192E+10 | 0.885691E+10 | 0.959197E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332675.32 | 0.130942E+09 |
Maximum of Months | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.177471E+10 | 0.176023E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270528E+09 | 0.00 | 0.270528E+09 | 0.161518E+09 | 0.139822E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 87175283.48 | 0.129232E+10 |
March | 0.409677E+09 | 0.00 | 0.409677E+09 | 0.323279E+09 | 0.122655E+10 |
April | 0.483030E+09 | 5012605.91 | 0.478017E+09 | 0.780224E+09 | 0.620391E+09 |
May | 0.584285E+09 | 46784161.73 | 0.537501E+09 | 0.113996E+10 | 0.422601E+09 |
June | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.177471E+10 | 0.162378E+09 |
July | 0.579038E+09 | 60324299.85 | 0.518714E+09 | 0.156287E+10 | 0.130943E+09 |
August | 0.467388E+09 | 11611013.59 | 0.455777E+09 | 0.128225E+10 | 0.176398E+09 |
September | 0.426749E+09 | 113921.23 | 0.426635E+09 | 0.103528E+10 | 0.257103E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.476113E+09 | 0.870681E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.160206E+09 | 0.127416E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332741.68 | 0.176023E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243230E+09 | 0.478192E+10 | 0.885691E+10 | 0.959198E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332741.68 | 0.130943E+09 |
Maximum of Months | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.177471E+10 | 0.176023E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270527E+09 | 0.00 | 0.270527E+09 | 0.161518E+09 | 0.139822E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 87175134.41 | 0.129232E+10 |
March | 0.409676E+09 | 0.00 | 0.409676E+09 | 0.323278E+09 | 0.122654E+10 |
April | 0.483029E+09 | 5012599.89 | 0.478017E+09 | 0.780224E+09 | 0.620391E+09 |
May | 0.584285E+09 | 46784105.59 | 0.537501E+09 | 0.113996E+10 | 0.422601E+09 |
June | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.177471E+10 | 0.162378E+09 |
July | 0.579038E+09 | 60324227.47 | 0.518713E+09 | 0.156286E+10 | 0.130942E+09 |
August | 0.467388E+09 | 11610999.65 | 0.455777E+09 | 0.128225E+10 | 0.176398E+09 |
September | 0.426748E+09 | 113921.09 | 0.426635E+09 | 0.103528E+10 | 0.257103E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.476113E+09 | 0.870681E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.160206E+09 | 0.127416E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332675.32 | 0.176023E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243229E+09 | 0.478192E+10 | 0.885691E+10 | 0.959197E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 73332675.32 | 0.130942E+09 |
Maximum of Months | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.177471E+10 | 0.176023E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270517E+09 | 0.00 | 0.270517E+09 | 0.161511E+09 | 0.139817E+10 |
February | 0.278417E+09 | 0.00 | 0.278417E+09 | 87171769.93 | 0.129227E+10 |
March | 0.409660E+09 | 0.00 | 0.409660E+09 | 0.323266E+09 | 0.122650E+10 |
April | 0.483010E+09 | 5012403.88 | 0.477998E+09 | 0.780193E+09 | 0.620366E+09 |
May | 0.584262E+09 | 46782276.12 | 0.537479E+09 | 0.113991E+10 | 0.422584E+09 |
June | 0.657047E+09 | 0.119379E+09 | 0.537668E+09 | 0.177464E+10 | 0.162371E+09 |
July | 0.579015E+09 | 60321868.52 | 0.518693E+09 | 0.156280E+10 | 0.130937E+09 |
August | 0.467369E+09 | 11610545.61 | 0.455759E+09 | 0.128220E+10 | 0.176391E+09 |
September | 0.426732E+09 | 113916.64 | 0.426618E+09 | 0.103524E+10 | 0.257092E+09 |
October | 0.341158E+09 | 0.00 | 0.341158E+09 | 0.476094E+09 | 0.870646E+09 |
November | 0.275078E+09 | 0.00 | 0.275078E+09 | 0.160200E+09 | 0.127411E+10 |
December | 0.252688E+09 | 0.00 | 0.252688E+09 | 73329786.05 | 0.176016E+10 |
Annual Sum or Average | 0.502495E+10 | 0.243220E+09 | 0.478173E+10 | 0.885656E+10 | 0.959159E+10 |
Minimum of Months | 0.252688E+09 | 0.00 | 0.252688E+09 | 73329786.05 | 0.130937E+09 |
Maximum of Months | 0.657047E+09 | 0.119379E+09 | 0.537668E+09 | 0.177464E+10 | 0.176016E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971035E+09 | 0.609157E+09 | 0.361878E+09 | 0.116586E+10 | 0.140442E+10 |
February | 0.864517E+09 | 0.494543E+09 | 0.369974E+09 | 0.910229E+09 | 0.129726E+10 |
March | 0.119782E+10 | 0.616168E+09 | 0.581653E+09 | 0.149017E+10 | 0.122134E+10 |
April | 0.165467E+10 | 0.986204E+09 | 0.668465E+09 | 0.273720E+10 | 0.610225E+09 |
May | 0.177199E+10 | 0.105042E+10 | 0.721572E+09 | 0.315975E+10 | 0.463832E+09 |
June | 0.178741E+10 | 0.111067E+10 | 0.676739E+09 | 0.374433E+10 | 0.162240E+09 |
July | 0.155990E+10 | 0.879565E+09 | 0.680337E+09 | 0.331471E+10 | 0.123313E+09 |
August | 0.148048E+10 | 0.844910E+09 | 0.635572E+09 | 0.311396E+10 | 0.158012E+09 |
September | 0.117565E+10 | 0.566684E+09 | 0.608965E+09 | 0.236019E+10 | 0.259921E+09 |
October | 0.122023E+10 | 0.742625E+09 | 0.477607E+09 | 0.189281E+10 | 0.870386E+09 |
November | 0.908023E+09 | 0.545098E+09 | 0.362925E+09 | 0.108891E+10 | 0.126806E+10 |
December | 0.855475E+09 | 0.516561E+09 | 0.338914E+09 | 0.871110E+09 | 0.171911E+10 |
Annual Sum or Average | 0.154472E+11 | 0.896261E+10 | 0.648460E+10 | 0.258492E+11 | 0.955811E+10 |
Minimum of Months | 0.855475E+09 | 0.494543E+09 | 0.338914E+09 | 0.871110E+09 | 0.123313E+09 |
Maximum of Months | 0.178741E+10 | 0.111067E+10 | 0.721572E+09 | 0.374433E+10 | 0.171911E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971035E+09 | 0.609157E+09 | 0.361878E+09 | 0.116586E+10 | 0.140442E+10 |
February | 0.864517E+09 | 0.494543E+09 | 0.369974E+09 | 0.910229E+09 | 0.129726E+10 |
March | 0.119782E+10 | 0.616168E+09 | 0.581653E+09 | 0.149017E+10 | 0.122134E+10 |
April | 0.165467E+10 | 0.986204E+09 | 0.668465E+09 | 0.273720E+10 | 0.610225E+09 |
May | 0.177199E+10 | 0.105042E+10 | 0.721572E+09 | 0.315975E+10 | 0.463832E+09 |
June | 0.178741E+10 | 0.111067E+10 | 0.676739E+09 | 0.374433E+10 | 0.162240E+09 |
July | 0.155990E+10 | 0.879565E+09 | 0.680337E+09 | 0.331471E+10 | 0.123313E+09 |
August | 0.148048E+10 | 0.844910E+09 | 0.635572E+09 | 0.311396E+10 | 0.158012E+09 |
September | 0.117565E+10 | 0.566684E+09 | 0.608965E+09 | 0.236019E+10 | 0.259921E+09 |
October | 0.122023E+10 | 0.742625E+09 | 0.477607E+09 | 0.189281E+10 | 0.870386E+09 |
November | 0.908023E+09 | 0.545098E+09 | 0.362925E+09 | 0.108891E+10 | 0.126806E+10 |
December | 0.855475E+09 | 0.516561E+09 | 0.338914E+09 | 0.871110E+09 | 0.171911E+10 |
Annual Sum or Average | 0.154472E+11 | 0.896261E+10 | 0.648460E+10 | 0.258492E+11 | 0.955811E+10 |
Minimum of Months | 0.855475E+09 | 0.494543E+09 | 0.338914E+09 | 0.871110E+09 | 0.123313E+09 |
Maximum of Months | 0.178741E+10 | 0.111067E+10 | 0.721572E+09 | 0.374433E+10 | 0.171911E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971017E+09 | 0.609146E+09 | 0.361871E+09 | 0.116584E+10 | 0.140440E+10 |
February | 0.864501E+09 | 0.494534E+09 | 0.369967E+09 | 0.910213E+09 | 0.129724E+10 |
March | 0.119780E+10 | 0.616157E+09 | 0.581642E+09 | 0.149014E+10 | 0.122131E+10 |
April | 0.165464E+10 | 0.986186E+09 | 0.668453E+09 | 0.273715E+10 | 0.610214E+09 |
May | 0.177196E+10 | 0.105040E+10 | 0.721558E+09 | 0.315969E+10 | 0.463823E+09 |
June | 0.178738E+10 | 0.111065E+10 | 0.676727E+09 | 0.374426E+10 | 0.162237E+09 |
July | 0.155987E+10 | 0.879549E+09 | 0.680324E+09 | 0.331465E+10 | 0.123311E+09 |
August | 0.148046E+10 | 0.844895E+09 | 0.635561E+09 | 0.311390E+10 | 0.158009E+09 |
September | 0.117563E+10 | 0.566673E+09 | 0.608954E+09 | 0.236014E+10 | 0.259916E+09 |
October | 0.122021E+10 | 0.742611E+09 | 0.477599E+09 | 0.189278E+10 | 0.870370E+09 |
November | 0.908006E+09 | 0.545088E+09 | 0.362918E+09 | 0.108889E+10 | 0.126803E+10 |
December | 0.855460E+09 | 0.516552E+09 | 0.338908E+09 | 0.871094E+09 | 0.171908E+10 |
Annual Sum or Average | 0.154469E+11 | 0.896245E+10 | 0.648448E+10 | 0.258488E+11 | 0.955794E+10 |
Minimum of Months | 0.855460E+09 | 0.494534E+09 | 0.338908E+09 | 0.871094E+09 | 0.123311E+09 |
Maximum of Months | 0.178738E+10 | 0.111065E+10 | 0.721558E+09 | 0.374426E+10 | 0.171908E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222755E+10 | 0.177908E+10 | 0.448468E+09 | 0.333874E+10 | 0.132168E+10 |
February | 0.127215E+10 | 0.857979E+09 | 0.414166E+09 | 0.167274E+10 | 0.117845E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568326E+09 | 0.166610E+10 | 0.118436E+10 |
April | 0.965439E+09 | 0.390132E+09 | 0.575308E+09 | 0.181973E+10 | 0.647198E+09 |
May | 0.668510E+09 | 0.110446E+09 | 0.558064E+09 | 0.141254E+10 | 0.465555E+09 |
June | 0.553972E+09 | 42704110.21 | 0.511268E+09 | 0.160765E+10 | 0.170646E+09 |
July | 0.584932E+09 | 60516029.40 | 0.524416E+09 | 0.161319E+10 | 0.132936E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.184183E+10 | 0.179177E+09 |
September | 0.991782E+09 | 0.423119E+09 | 0.568663E+09 | 0.213921E+10 | 0.265259E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.272271E+10 | 0.838851E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271026E+10 | 0.118750E+10 |
December | 0.207096E+10 | 0.163944E+10 | 0.431516E+09 | 0.292452E+10 | 0.159351E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864445E+10 | 0.604864E+10 | 0.254692E+11 | 0.916512E+10 |
Minimum of Months | 0.553972E+09 | 42704110.21 | 0.414166E+09 | 0.141254E+10 | 0.132936E+09 |
Maximum of Months | 0.222755E+10 | 0.177908E+10 | 0.575308E+09 | 0.333874E+10 | 0.159351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222754E+10 | 0.177908E+10 | 0.448467E+09 | 0.333874E+10 | 0.132168E+10 |
February | 0.127214E+10 | 0.857978E+09 | 0.414166E+09 | 0.167273E+10 | 0.117845E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568325E+09 | 0.166610E+10 | 0.118436E+10 |
April | 0.965438E+09 | 0.390131E+09 | 0.575307E+09 | 0.181973E+10 | 0.647197E+09 |
May | 0.668509E+09 | 0.110445E+09 | 0.558064E+09 | 0.141254E+10 | 0.465555E+09 |
June | 0.553972E+09 | 42704058.97 | 0.511268E+09 | 0.160765E+10 | 0.170645E+09 |
July | 0.584931E+09 | 60515956.79 | 0.524415E+09 | 0.161319E+10 | 0.132936E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.184183E+10 | 0.179176E+09 |
September | 0.991781E+09 | 0.423119E+09 | 0.568663E+09 | 0.213921E+10 | 0.265259E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.272270E+10 | 0.838850E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271026E+10 | 0.118750E+10 |
December | 0.207095E+10 | 0.163944E+10 | 0.431515E+09 | 0.292452E+10 | 0.159351E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864444E+10 | 0.604864E+10 | 0.254692E+11 | 0.916512E+10 |
Minimum of Months | 0.553972E+09 | 42704058.97 | 0.414166E+09 | 0.141254E+10 | 0.132936E+09 |
Maximum of Months | 0.222754E+10 | 0.177908E+10 | 0.575307E+09 | 0.333874E+10 | 0.159351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222755E+10 | 0.177908E+10 | 0.448468E+09 | 0.333874E+10 | 0.132168E+10 |
February | 0.127215E+10 | 0.857979E+09 | 0.414166E+09 | 0.167274E+10 | 0.117845E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568326E+09 | 0.166610E+10 | 0.118436E+10 |
April | 0.965439E+09 | 0.390132E+09 | 0.575308E+09 | 0.181973E+10 | 0.647198E+09 |
May | 0.668510E+09 | 0.110446E+09 | 0.558064E+09 | 0.141254E+10 | 0.465555E+09 |
June | 0.553972E+09 | 42704110.21 | 0.511268E+09 | 0.160765E+10 | 0.170646E+09 |
July | 0.584932E+09 | 60516029.40 | 0.524416E+09 | 0.161319E+10 | 0.132936E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.184183E+10 | 0.179177E+09 |
September | 0.991782E+09 | 0.423119E+09 | 0.568663E+09 | 0.213921E+10 | 0.265259E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.272271E+10 | 0.838851E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271026E+10 | 0.118750E+10 |
December | 0.207096E+10 | 0.163944E+10 | 0.431516E+09 | 0.292452E+10 | 0.159351E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864445E+10 | 0.604864E+10 | 0.254692E+11 | 0.916512E+10 |
Minimum of Months | 0.553972E+09 | 42704110.21 | 0.414166E+09 | 0.141254E+10 | 0.132936E+09 |
Maximum of Months | 0.222755E+10 | 0.177908E+10 | 0.575308E+09 | 0.333874E+10 | 0.159351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222754E+10 | 0.177908E+10 | 0.448467E+09 | 0.333874E+10 | 0.132168E+10 |
February | 0.127214E+10 | 0.857978E+09 | 0.414166E+09 | 0.167273E+10 | 0.117845E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568325E+09 | 0.166610E+10 | 0.118436E+10 |
April | 0.965438E+09 | 0.390131E+09 | 0.575307E+09 | 0.181973E+10 | 0.647197E+09 |
May | 0.668509E+09 | 0.110445E+09 | 0.558064E+09 | 0.141254E+10 | 0.465555E+09 |
June | 0.553972E+09 | 42704058.97 | 0.511268E+09 | 0.160765E+10 | 0.170645E+09 |
July | 0.584931E+09 | 60515956.79 | 0.524415E+09 | 0.161319E+10 | 0.132936E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.184183E+10 | 0.179176E+09 |
September | 0.991781E+09 | 0.423119E+09 | 0.568663E+09 | 0.213921E+10 | 0.265259E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.272270E+10 | 0.838850E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271026E+10 | 0.118750E+10 |
December | 0.207095E+10 | 0.163944E+10 | 0.431515E+09 | 0.292452E+10 | 0.159351E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864444E+10 | 0.604864E+10 | 0.254692E+11 | 0.916512E+10 |
Minimum of Months | 0.553972E+09 | 42704058.97 | 0.414166E+09 | 0.141254E+10 | 0.132936E+09 |
Maximum of Months | 0.222754E+10 | 0.177908E+10 | 0.575307E+09 | 0.333874E+10 | 0.159351E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222746E+10 | 0.177901E+10 | 0.448450E+09 | 0.333861E+10 | 0.132163E+10 |
February | 0.127209E+10 | 0.857945E+09 | 0.414150E+09 | 0.167267E+10 | 0.117840E+10 |
March | 0.117188E+10 | 0.603582E+09 | 0.568303E+09 | 0.166603E+10 | 0.118431E+10 |
April | 0.965400E+09 | 0.390116E+09 | 0.575284E+09 | 0.181966E+10 | 0.647172E+09 |
May | 0.668483E+09 | 0.110441E+09 | 0.558042E+09 | 0.141248E+10 | 0.465537E+09 |
June | 0.553950E+09 | 42702389.04 | 0.511247E+09 | 0.160758E+10 | 0.170639E+09 |
July | 0.584908E+09 | 60513590.34 | 0.524394E+09 | 0.161313E+10 | 0.132930E+09 |
August | 0.711220E+09 | 0.196546E+09 | 0.514673E+09 | 0.184176E+10 | 0.179169E+09 |
September | 0.991742E+09 | 0.423102E+09 | 0.568640E+09 | 0.213912E+10 | 0.265248E+09 |
October | 0.163291E+10 | 0.113022E+10 | 0.502693E+09 | 0.272260E+10 | 0.838817E+09 |
November | 0.184157E+10 | 0.141055E+10 | 0.431023E+09 | 0.271015E+10 | 0.118746E+10 |
December | 0.207087E+10 | 0.163937E+10 | 0.431498E+09 | 0.292440E+10 | 0.159345E+10 |
Annual Sum or Average | 0.146925E+11 | 0.864410E+10 | 0.604840E+10 | 0.254682E+11 | 0.916475E+10 |
Minimum of Months | 0.553950E+09 | 42702389.04 | 0.414150E+09 | 0.141248E+10 | 0.132930E+09 |
Maximum of Months | 0.222746E+10 | 0.177901E+10 | 0.575284E+09 | 0.333861E+10 | 0.159345E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101539E+10 | 0.631082E+09 | 0.384310E+09 | 0.140115E+10 | 0.165716E+10 |
February | 0.742963E+09 | 0.359177E+09 | 0.383786E+09 | 0.782099E+09 | 0.154449E+10 |
March | 0.108952E+10 | 0.519389E+09 | 0.570126E+09 | 0.135053E+10 | 0.150355E+10 |
April | 0.161902E+10 | 0.923537E+09 | 0.695481E+09 | 0.268417E+10 | 0.873299E+09 |
May | 0.167728E+10 | 0.940453E+09 | 0.736827E+09 | 0.304822E+10 | 0.601206E+09 |
June | 0.172559E+10 | 0.101493E+10 | 0.710667E+09 | 0.360630E+10 | 0.255506E+09 |
July | 0.129779E+10 | 0.605805E+09 | 0.691988E+09 | 0.277233E+10 | 0.214643E+09 |
August | 0.123756E+10 | 0.621529E+09 | 0.616033E+09 | 0.259045E+10 | 0.317119E+09 |
September | 0.104394E+10 | 0.438621E+09 | 0.605319E+09 | 0.212239E+10 | 0.343806E+09 |
October | 0.110377E+10 | 0.631136E+09 | 0.472638E+09 | 0.174746E+10 | 0.108296E+10 |
November | 0.983810E+09 | 0.593996E+09 | 0.389814E+09 | 0.129607E+10 | 0.158482E+10 |
December | 0.819340E+09 | 0.466507E+09 | 0.352833E+09 | 0.947567E+09 | 0.216473E+10 |
Annual Sum or Average | 0.143560E+11 | 0.774616E+10 | 0.660982E+10 | 0.243487E+11 | 0.121433E+11 |
Minimum of Months | 0.742963E+09 | 0.359177E+09 | 0.352833E+09 | 0.782099E+09 | 0.214643E+09 |
Maximum of Months | 0.172559E+10 | 0.101493E+10 | 0.736827E+09 | 0.360630E+10 | 0.216473E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101539E+10 | 0.631082E+09 | 0.384310E+09 | 0.140115E+10 | 0.165716E+10 |
February | 0.742963E+09 | 0.359177E+09 | 0.383786E+09 | 0.782099E+09 | 0.154449E+10 |
March | 0.108952E+10 | 0.519389E+09 | 0.570126E+09 | 0.135053E+10 | 0.150355E+10 |
April | 0.161902E+10 | 0.923537E+09 | 0.695481E+09 | 0.268417E+10 | 0.873299E+09 |
May | 0.167728E+10 | 0.940453E+09 | 0.736827E+09 | 0.304822E+10 | 0.601206E+09 |
June | 0.172559E+10 | 0.101493E+10 | 0.710667E+09 | 0.360630E+10 | 0.255506E+09 |
July | 0.129779E+10 | 0.605805E+09 | 0.691988E+09 | 0.277233E+10 | 0.214643E+09 |
August | 0.123756E+10 | 0.621529E+09 | 0.616033E+09 | 0.259045E+10 | 0.317119E+09 |
September | 0.104394E+10 | 0.438621E+09 | 0.605319E+09 | 0.212239E+10 | 0.343806E+09 |
October | 0.110377E+10 | 0.631136E+09 | 0.472638E+09 | 0.174746E+10 | 0.108296E+10 |
November | 0.983810E+09 | 0.593996E+09 | 0.389814E+09 | 0.129607E+10 | 0.158482E+10 |
December | 0.819340E+09 | 0.466507E+09 | 0.352833E+09 | 0.947567E+09 | 0.216473E+10 |
Annual Sum or Average | 0.143560E+11 | 0.774616E+10 | 0.660982E+10 | 0.243487E+11 | 0.121433E+11 |
Minimum of Months | 0.742963E+09 | 0.359177E+09 | 0.352833E+09 | 0.782099E+09 | 0.214643E+09 |
Maximum of Months | 0.172559E+10 | 0.101493E+10 | 0.736827E+09 | 0.360630E+10 | 0.216473E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101537E+10 | 0.631071E+09 | 0.384303E+09 | 0.140113E+10 | 0.165713E+10 |
February | 0.742950E+09 | 0.359171E+09 | 0.383779E+09 | 0.782085E+09 | 0.154447E+10 |
March | 0.108950E+10 | 0.519380E+09 | 0.570116E+09 | 0.135050E+10 | 0.150352E+10 |
April | 0.161899E+10 | 0.923520E+09 | 0.695468E+09 | 0.268412E+10 | 0.873283E+09 |
May | 0.167725E+10 | 0.940435E+09 | 0.736813E+09 | 0.304816E+10 | 0.601195E+09 |
June | 0.172556E+10 | 0.101491E+10 | 0.710654E+09 | 0.360624E+10 | 0.255501E+09 |
July | 0.129777E+10 | 0.605794E+09 | 0.691975E+09 | 0.277228E+10 | 0.214639E+09 |
August | 0.123754E+10 | 0.621517E+09 | 0.616021E+09 | 0.259040E+10 | 0.317113E+09 |
September | 0.104392E+10 | 0.438613E+09 | 0.605308E+09 | 0.212235E+10 | 0.343799E+09 |
October | 0.110375E+10 | 0.631124E+09 | 0.472630E+09 | 0.174742E+10 | 0.108294E+10 |
November | 0.983792E+09 | 0.593985E+09 | 0.389807E+09 | 0.129605E+10 | 0.158479E+10 |
December | 0.819325E+09 | 0.466499E+09 | 0.352827E+09 | 0.947550E+09 | 0.216469E+10 |
Annual Sum or Average | 0.143557E+11 | 0.774602E+10 | 0.660970E+10 | 0.243483E+11 | 0.121431E+11 |
Minimum of Months | 0.742950E+09 | 0.359171E+09 | 0.352827E+09 | 0.782085E+09 | 0.214639E+09 |
Maximum of Months | 0.172556E+10 | 0.101491E+10 | 0.736813E+09 | 0.360624E+10 | 0.216469E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.104963E+10 | 0.617145E+10 |
February | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.578363E+09 | 0.565140E+10 |
March | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.180800E+10 | 0.551156E+10 |
April | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.407721E+10 | 0.292155E+10 |
May | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.580848E+10 | 0.204360E+10 |
June | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.898665E+10 | 0.830683E+09 |
July | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.793941E+10 | 0.661611E+09 |
August | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.661301E+10 | 0.828847E+09 |
September | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.526805E+10 | 0.123714E+10 |
October | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.254578E+10 | 0.394810E+10 |
November | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.993599E+09 | 0.556963E+10 |
December | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.606830E+09 | 0.757745E+10 |
Annual Sum or Average | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.462750E+11 | 0.429530E+11 |
Minimum of Months | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.578363E+09 | 0.661611E+09 |
Maximum of Months | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.898665E+10 | 0.757745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.358541E+10 | 0.386684E+10 |
February | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.276386E+10 | 0.357317E+10 |
March | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.448035E+10 | 0.346822E+10 |
April | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.814487E+10 | 0.188214E+10 |
May | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.941651E+10 | 0.138886E+10 |
June | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.111645E+11 | 0.532861E+09 |
July | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.986675E+10 | 0.425495E+09 |
August | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.928688E+10 | 0.540929E+09 |
September | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.704108E+10 | 0.790835E+09 |
October | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.567023E+10 | 0.248764E+10 |
November | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.332080E+10 | 0.350823E+10 |
December | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.274156E+10 | 0.470367E+10 |
Annual Sum or Average | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.774828E+11 | 0.271689E+11 |
Minimum of Months | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.274156E+10 | 0.425495E+09 |
Maximum of Months | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.111645E+11 | 0.470367E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.165544E+11 | 0.647611E+10 |
February | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.829949E+10 | 0.564702E+10 |
March | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.830116E+10 | 0.568993E+10 |
April | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.911643E+10 | 0.316049E+10 |
May | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.713159E+10 | 0.226752E+10 |
June | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.817461E+10 | 0.857123E+09 |
July | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.818252E+10 | 0.667701E+09 |
August | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.933846E+10 | 0.860148E+09 |
September | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.106708E+11 | 0.130968E+10 |
October | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.135067E+11 | 0.408311E+10 |
November | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.134545E+11 | 0.572570E+10 |
December | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.145740E+11 | 0.767198E+10 |
Annual Sum or Average | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.127305E+12 | 0.444165E+11 |
Minimum of Months | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.713159E+10 | 0.667701E+09 |
Maximum of Months | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.165544E+11 | 0.767198E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.434922E+10 | 0.440041E+10 |
February | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.247341E+10 | 0.387422E+10 |
March | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.425801E+10 | 0.381738E+10 |
April | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.822100E+10 | 0.226460E+10 |
May | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.918617E+10 | 0.168358E+10 |
June | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.109306E+11 | 0.703999E+09 |
July | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.852355E+10 | 0.540889E+09 |
August | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.807120E+10 | 0.674547E+09 |
September | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.644280E+10 | 0.919231E+09 |
October | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.537605E+10 | 0.281677E+10 |
November | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.405781E+10 | 0.395156E+10 |
December | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.308283E+10 | 0.527737E+10 |
Annual Sum or Average | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.749726E+11 | 0.309245E+11 |
Minimum of Months | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.247341E+10 | 0.540889E+09 |
Maximum of Months | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.109306E+11 | 0.527737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.118915E+10 | 0.567089E+10 |
February | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.675573E+09 | 0.510500E+10 |
March | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.191454E+10 | 0.515033E+10 |
April | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.405907E+10 | 0.284362E+10 |
May | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.576367E+10 | 0.203241E+10 |
June | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.888427E+10 | 0.847194E+09 |
July | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.782268E+10 | 0.680103E+09 |
August | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.652397E+10 | 0.841327E+09 |
September | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.520291E+10 | 0.124027E+10 |
October | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.259438E+10 | 0.371454E+10 |
November | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.110581E+10 | 0.509402E+10 |
December | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.748332E+09 | 0.692518E+10 |
Annual Sum or Average | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.464844E+11 | 0.401449E+11 |
Minimum of Months | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.675573E+09 | 0.680103E+09 |
Maximum of Months | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.888427E+10 | 0.692518E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.368772E+10 | 0.361379E+10 |
February | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.284247E+10 | 0.328562E+10 |
March | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.453912E+10 | 0.329738E+10 |
April | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.810400E+10 | 0.186194E+10 |
May | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.935648E+10 | 0.138942E+10 |
June | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.110707E+11 | 0.547108E+09 |
July | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.976649E+10 | 0.439479E+09 |
August | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.920388E+10 | 0.552283E+09 |
September | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.698005E+10 | 0.797207E+09 |
October | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.567888E+10 | 0.238642E+10 |
November | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.340310E+10 | 0.326926E+10 |
December | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.288724E+10 | 0.434884E+10 |
Annual Sum or Average | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.775201E+11 | 0.257887E+11 |
Minimum of Months | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.284247E+10 | 0.439479E+09 |
Maximum of Months | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.110707E+11 | 0.434884E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.166536E+11 | 0.609510E+10 |
February | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.839828E+10 | 0.519934E+10 |
March | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.837147E+10 | 0.539117E+10 |
April | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.906976E+10 | 0.309085E+10 |
May | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.707577E+10 | 0.224217E+10 |
June | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.807229E+10 | 0.868026E+09 |
July | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.806420E+10 | 0.682636E+09 |
August | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.923952E+10 | 0.869916E+09 |
September | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.105887E+11 | 0.131613E+10 |
October | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.135055E+11 | 0.391619E+10 |
November | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.135400E+11 | 0.537728E+10 |
December | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.147266E+11 | 0.715667E+10 |
Annual Sum or Average | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.127306E+12 | 0.422055E+11 |
Minimum of Months | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.707577E+10 | 0.682636E+09 |
Maximum of Months | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.166536E+11 | 0.715667E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.439539E+10 | 0.412900E+10 |
February | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.250958E+10 | 0.359089E+10 |
March | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.429272E+10 | 0.362652E+10 |
April | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.818414E+10 | 0.221782E+10 |
May | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.913373E+10 | 0.166743E+10 |
June | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.108487E+11 | 0.709492E+09 |
July | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.844492E+10 | 0.548146E+09 |
August | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.800662E+10 | 0.678193E+09 |
September | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.639406E+10 | 0.917493E+09 |
October | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.537693E+10 | 0.269512E+10 |
November | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.409477E+10 | 0.370317E+10 |
December | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.314375E+10 | 0.492848E+10 |
Annual Sum or Average | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.748253E+11 | 0.294117E+11 |
Minimum of Months | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.250958E+10 | 0.548146E+09 |
Maximum of Months | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.108487E+11 | 0.492848E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.52 | 2610.16 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 180.17 | 2670.95 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 603.49 | 2289.68 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1505.05 | 1196.73 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2128.04 | 788.90 | 1090.73 | 87.34 | 1003.39 | 0.00 | 0.00 |
June | 3423.41 | 313.23 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2917.51 | 244.44 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2393.67 | 329.29 | 872.51 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 1997.06 | 495.95 | 823.20 | 0.22 | 822.98 | 0.00 | 0.00 |
October | 888.79 | 1625.36 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 309.04 | 2457.85 | 530.65 | 0.00 | 530.65 | 0.00 | 0.00 |
December | 136.90 | 3285.95 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1404.24 | 1520.79 | 796.73 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 136.90 | 244.44 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3423.41 | 3285.95 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1305.84 | 1573.05 | 1087.62 | 682.30 | 405.33 | 0.00 | 0.00 |
February | 1128.75 | 1608.70 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1669.08 | 1367.98 | 1341.64 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3168.03 | 706.27 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3539.12 | 519.52 | 1984.75 | 1176.54 | 808.21 | 0.00 | 0.00 |
June | 4333.69 | 187.78 | 2068.75 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3712.69 | 138.12 | 1747.19 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3487.84 | 176.98 | 1658.24 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2731.68 | 300.83 | 1360.70 | 655.88 | 704.82 | 0.00 | 0.00 |
October | 2120.07 | 974.89 | 1366.74 | 831.79 | 534.95 | 0.00 | 0.00 |
November | 1260.31 | 1467.65 | 1050.95 | 630.90 | 420.05 | 0.00 | 0.00 |
December | 975.70 | 1925.51 | 958.19 | 578.58 | 379.61 | 0.00 | 0.00 |
Annual Sum or Average | 2459.01 | 909.25 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 975.70 | 138.12 | 958.19 | 578.58 | 379.61 | 0.00 | 0.00 |
Maximum of Months | 4333.69 | 1925.51 | 2068.75 | 1285.49 | 808.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6232.66 | 2467.27 | 4158.32 | 3321.13 | 837.19 | 0.00 | 0.00 |
February | 3457.18 | 2435.60 | 2629.25 | 1773.26 | 855.99 | 0.00 | 0.00 |
March | 3110.23 | 2210.92 | 2187.73 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3510.26 | 1248.44 | 1862.33 | 752.56 | 1109.77 | 0.00 | 0.00 |
May | 2636.89 | 869.09 | 1247.95 | 206.18 | 1041.78 | 0.00 | 0.00 |
June | 3101.14 | 329.17 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 3011.47 | 248.16 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3438.28 | 334.48 | 1327.74 | 366.92 | 960.82 | 0.00 | 0.00 |
September | 4126.52 | 511.68 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5082.67 | 1565.94 | 3048.39 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5228.08 | 2290.69 | 3552.53 | 2721.06 | 831.47 | 0.00 | 0.00 |
December | 5459.41 | 2974.72 | 3866.00 | 3060.46 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 4038.08 | 1453.11 | 2329.55 | 1370.56 | 959.00 | 0.00 | 0.00 |
Minimum of Months | 2636.89 | 248.16 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6232.66 | 2974.72 | 4158.32 | 3321.13 | 1109.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1569.38 | 1856.13 | 1137.31 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 969.86 | 1915.28 | 921.33 | 445.41 | 475.92 | 0.00 | 0.00 |
March | 1512.68 | 1684.07 | 1220.33 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3106.66 | 1010.76 | 1873.85 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3414.20 | 673.39 | 1878.66 | 1053.37 | 825.29 | 0.00 | 0.00 |
June | 4173.94 | 295.72 | 1997.20 | 1174.68 | 822.53 | 0.00 | 0.00 |
July | 3105.19 | 240.41 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 2901.47 | 355.19 | 1386.15 | 696.15 | 690.00 | 0.00 | 0.00 |
September | 2456.46 | 397.92 | 1208.26 | 507.66 | 700.60 | 0.00 | 0.00 |
October | 1957.26 | 1212.99 | 1236.30 | 706.91 | 529.39 | 0.00 | 0.00 |
November | 1500.07 | 1834.27 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1061.34 | 2424.64 | 917.71 | 522.52 | 395.20 | 0.00 | 0.00 |
Annual Sum or Average | 2316.27 | 1155.18 | 1365.67 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 969.86 | 240.41 | 917.71 | 445.41 | 395.20 | 0.00 | 0.00 |
Maximum of Months | 4173.94 | 2424.64 | 1997.20 | 1174.68 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 391.89 | 2304.16 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 239.07 | 2336.06 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 675.03 | 2057.78 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1573.00 | 1127.14 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2168.64 | 762.99 | 1090.72 | 87.33 | 1003.39 | 0.00 | 0.00 |
June | 3467.07 | 320.48 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2964.24 | 247.02 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2469.01 | 309.46 | 872.50 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 2032.43 | 477.29 | 823.19 | 0.22 | 822.97 | 0.00 | 0.00 |
October | 950.49 | 1474.05 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 383.33 | 2148.78 | 530.64 | 0.00 | 530.64 | 0.00 | 0.00 |
December | 226.56 | 2829.09 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1467.37 | 1362.03 | 796.72 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 226.56 | 247.02 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3467.07 | 2829.09 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1338.64 | 1443.71 | 1087.62 | 682.29 | 405.32 | 0.00 | 0.00 |
February | 1142.47 | 1477.00 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1672.77 | 1294.89 | 1341.63 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3142.31 | 726.14 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3515.72 | 518.54 | 1984.74 | 1176.54 | 808.20 | 0.00 | 0.00 |
June | 4307.30 | 205.58 | 2068.74 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3683.82 | 158.86 | 1747.18 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3467.32 | 201.96 | 1658.23 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2716.47 | 305.11 | 1360.69 | 655.88 | 704.81 | 0.00 | 0.00 |
October | 2117.02 | 928.78 | 1366.73 | 831.78 | 534.95 | 0.00 | 0.00 |
November | 1281.17 | 1353.48 | 1050.94 | 630.89 | 420.05 | 0.00 | 0.00 |
December | 1023.58 | 1756.15 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Annual Sum or Average | 2456.96 | 861.52 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 1023.58 | 158.86 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Maximum of Months | 4307.30 | 1756.15 | 2068.74 | 1285.49 | 808.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6180.71 | 2417.90 | 4158.30 | 3321.12 | 837.18 | 0.00 | 0.00 |
February | 3430.68 | 2334.25 | 2629.24 | 1773.25 | 855.99 | 0.00 | 0.00 |
March | 3099.30 | 2124.38 | 2187.72 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3517.14 | 1219.32 | 1862.32 | 752.56 | 1109.76 | 0.00 | 0.00 |
May | 2662.63 | 846.59 | 1247.95 | 206.18 | 1041.77 | 0.00 | 0.00 |
June | 3153.78 | 330.68 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 3055.00 | 249.29 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3486.58 | 321.14 | 1327.73 | 366.92 | 960.81 | 0.00 | 0.00 |
September | 4116.81 | 505.28 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5042.82 | 1524.46 | 3048.38 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5190.77 | 2208.99 | 3552.52 | 2721.05 | 831.47 | 0.00 | 0.00 |
December | 5441.30 | 2864.39 | 3865.99 | 3060.45 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 4036.80 | 1408.44 | 2329.55 | 1370.55 | 958.99 | 0.00 | 0.00 |
Minimum of Months | 2662.63 | 249.29 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6180.71 | 2864.39 | 4158.30 | 3321.12 | 1109.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1623.81 | 1642.93 | 1137.30 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 1022.41 | 1601.45 | 921.32 | 445.40 | 475.92 | 0.00 | 0.00 |
March | 1589.76 | 1425.25 | 1220.32 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3171.68 | 873.69 | 1873.84 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3429.72 | 628.58 | 1878.65 | 1053.36 | 825.29 | 0.00 | 0.00 |
June | 4217.04 | 271.60 | 1997.20 | 1174.67 | 822.52 | 0.00 | 0.00 |
July | 3182.33 | 201.94 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 3013.44 | 251.85 | 1386.14 | 696.15 | 689.99 | 0.00 | 0.00 |
September | 2485.65 | 354.64 | 1208.25 | 507.66 | 700.59 | 0.00 | 0.00 |
October | 2007.19 | 1051.66 | 1236.29 | 706.91 | 529.38 | 0.00 | 0.00 |
November | 1565.51 | 1524.52 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1151.00 | 1970.35 | 917.71 | 522.52 | 395.19 | 0.00 | 0.00 |
Annual Sum or Average | 2377.37 | 980.61 | 1365.66 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 1022.41 | 201.94 | 917.71 | 445.40 | 395.19 | 0.00 | 0.00 |
Maximum of Months | 4217.04 | 1970.35 | 1997.20 | 1174.67 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 443.98 | 2117.27 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 279.25 | 2110.20 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 714.81 | 1922.91 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1566.00 | 1097.08 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2151.91 | 758.82 | 1090.72 | 87.33 | 1003.39 | 0.00 | 0.00 |
June | 3427.57 | 326.85 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2920.65 | 253.92 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2435.77 | 314.12 | 872.50 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 2007.30 | 478.50 | 823.19 | 0.22 | 822.97 | 0.00 | 0.00 |
October | 968.63 | 1386.85 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 426.62 | 1965.29 | 530.64 | 0.00 | 530.64 | 0.00 | 0.00 |
December | 279.40 | 2585.57 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1474.01 | 1272.99 | 796.72 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 279.25 | 253.92 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3427.57 | 2585.57 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1376.84 | 1349.23 | 1087.62 | 682.29 | 405.32 | 0.00 | 0.00 |
February | 1174.96 | 1358.14 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1694.71 | 1231.10 | 1341.63 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3126.54 | 718.34 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3493.31 | 518.75 | 1984.74 | 1176.54 | 808.20 | 0.00 | 0.00 |
June | 4271.09 | 211.08 | 2068.74 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3646.39 | 164.08 | 1747.18 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3436.34 | 206.20 | 1658.23 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2692.92 | 307.56 | 1360.69 | 655.88 | 704.81 | 0.00 | 0.00 |
October | 2120.25 | 890.99 | 1366.73 | 831.78 | 534.95 | 0.00 | 0.00 |
November | 1312.92 | 1261.29 | 1050.94 | 630.89 | 420.05 | 0.00 | 0.00 |
December | 1077.97 | 1623.67 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Annual Sum or Average | 2458.15 | 817.76 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 1077.97 | 164.08 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Maximum of Months | 4271.09 | 1623.67 | 2068.74 | 1285.49 | 808.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6217.76 | 2275.65 | 4158.30 | 3321.12 | 837.18 | 0.00 | 0.00 |
February | 3471.51 | 2149.20 | 2629.24 | 1773.25 | 855.99 | 0.00 | 0.00 |
March | 3125.55 | 2012.83 | 2187.72 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3499.14 | 1192.46 | 1862.32 | 752.56 | 1109.76 | 0.00 | 0.00 |
May | 2641.79 | 837.13 | 1247.95 | 206.18 | 1041.77 | 0.00 | 0.00 |
June | 3114.31 | 334.89 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 3010.83 | 254.87 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3449.64 | 324.79 | 1327.73 | 366.92 | 960.81 | 0.00 | 0.00 |
September | 4085.13 | 507.77 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5042.36 | 1462.14 | 3048.38 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5223.75 | 2074.57 | 3552.52 | 2721.05 | 831.47 | 0.00 | 0.00 |
December | 5498.28 | 2671.99 | 3865.99 | 3060.45 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 4036.83 | 1338.33 | 2329.55 | 1370.55 | 958.99 | 0.00 | 0.00 |
Minimum of Months | 2641.79 | 254.87 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6217.76 | 2671.99 | 4158.30 | 3321.12 | 1109.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1641.05 | 1541.59 | 1137.30 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 1037.36 | 1484.33 | 921.32 | 445.40 | 475.92 | 0.00 | 0.00 |
March | 1602.72 | 1353.99 | 1220.32 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3157.46 | 855.64 | 1873.84 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3410.14 | 622.55 | 1878.65 | 1053.36 | 825.29 | 0.00 | 0.00 |
June | 4185.47 | 273.72 | 1997.20 | 1174.67 | 822.52 | 0.00 | 0.00 |
July | 3152.97 | 204.65 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 2989.33 | 253.21 | 1386.14 | 696.15 | 689.99 | 0.00 | 0.00 |
September | 2466.84 | 353.97 | 1208.25 | 507.66 | 700.59 | 0.00 | 0.00 |
October | 2007.52 | 1006.24 | 1236.29 | 706.91 | 529.38 | 0.00 | 0.00 |
November | 1579.77 | 1428.69 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1173.74 | 1840.08 | 917.71 | 522.52 | 395.19 | 0.00 | 0.00 |
Annual Sum or Average | 2372.70 | 932.64 | 1365.66 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 1037.36 | 204.65 | 917.71 | 445.40 | 395.19 | 0.00 | 0.00 |
Maximum of Months | 4185.47 | 1840.08 | 1997.20 | 1174.67 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.807583E+09 | 0.699105E+10 | 0.135263E+10 | 0.00 | 0.135263E+10 | 0.00 | 0.00 |
February | 0.435873E+09 | 0.646156E+10 | 0.139213E+10 | 0.00 | 0.139213E+10 | 0.00 | 0.00 |
March | 0.161638E+10 | 0.613268E+10 | 0.204837E+10 | 0.00 | 0.204837E+10 | 0.00 | 0.00 |
April | 0.390109E+10 | 0.310193E+10 | 0.241513E+10 | 25062815.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.569974E+10 | 0.211299E+10 | 0.292140E+10 | 0.233919E+09 | 0.268748E+10 | 0.00 | 0.00 |
June | 0.887347E+10 | 0.811882E+09 | 0.328534E+10 | 0.596913E+09 | 0.268843E+10 | 0.00 | 0.00 |
July | 0.781426E+10 | 0.654707E+09 | 0.289517E+10 | 0.301619E+09 | 0.259355E+10 | 0.00 | 0.00 |
August | 0.641121E+10 | 0.881983E+09 | 0.233692E+10 | 58054572.09 | 0.227887E+10 | 0.00 | 0.00 |
September | 0.517638E+10 | 0.128550E+10 | 0.213373E+10 | 569601.27 | 0.213316E+10 | 0.00 | 0.00 |
October | 0.238055E+10 | 0.435337E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.801026E+09 | 0.637074E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.366661E+09 | 0.880110E+10 | 0.126348E+10 | 0.00 | 0.126348E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.442842E+11 | 0.479595E+11 | 0.251256E+11 | 0.121614E+10 | 0.239094E+11 | 0.00 | 0.00 |
Minimum of Months | 0.366661E+09 | 0.654707E+09 | 0.126348E+10 | 0.00 | 0.126348E+10 | 0.00 | 0.00 |
Maximum of Months | 0.887347E+10 | 0.880110E+10 | 0.328534E+10 | 0.596913E+09 | 0.268843E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.349757E+10 | 0.421325E+10 | 0.291309E+10 | 0.182746E+10 | 0.108563E+10 | 0.00 | 0.00 |
February | 0.273067E+10 | 0.389176E+10 | 0.259353E+10 | 0.148362E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.447048E+10 | 0.366399E+10 | 0.359344E+10 | 0.184849E+10 | 0.174495E+10 | 0.00 | 0.00 |
April | 0.821154E+10 | 0.183066E+10 | 0.496398E+10 | 0.295859E+10 | 0.200538E+10 | 0.00 | 0.00 |
May | 0.947918E+10 | 0.139149E+10 | 0.531595E+10 | 0.315125E+10 | 0.216470E+10 | 0.00 | 0.00 |
June | 0.112329E+11 | 0.486718E+09 | 0.536220E+10 | 0.333200E+10 | 0.203021E+10 | 0.00 | 0.00 |
July | 0.994407E+10 | 0.369938E+09 | 0.467968E+10 | 0.263868E+10 | 0.204100E+10 | 0.00 | 0.00 |
August | 0.934183E+10 | 0.474033E+09 | 0.444142E+10 | 0.253472E+10 | 0.190671E+10 | 0.00 | 0.00 |
September | 0.708052E+10 | 0.779758E+09 | 0.352693E+10 | 0.170004E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.567840E+10 | 0.261114E+10 | 0.366067E+10 | 0.222786E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.326672E+10 | 0.380414E+10 | 0.272405E+10 | 0.163528E+10 | 0.108877E+10 | 0.00 | 0.00 |
December | 0.261332E+10 | 0.515729E+10 | 0.256641E+10 | 0.154967E+10 | 0.101674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.775472E+11 | 0.286742E+11 | 0.463414E+11 | 0.268877E+11 | 0.194537E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261332E+10 | 0.369938E+09 | 0.256641E+10 | 0.148362E+10 | 0.101674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112329E+11 | 0.515729E+10 | 0.536220E+10 | 0.333200E+10 | 0.216470E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166936E+11 | 0.660835E+10 | 0.111376E+11 | 0.889532E+10 | 0.224232E+10 | 0.00 | 0.00 |
February | 0.836361E+10 | 0.589220E+10 | 0.636067E+10 | 0.428986E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.833043E+10 | 0.592173E+10 | 0.585961E+10 | 0.301801E+10 | 0.284160E+10 | 0.00 | 0.00 |
April | 0.909858E+10 | 0.323596E+10 | 0.482716E+10 | 0.195064E+10 | 0.287651E+10 | 0.00 | 0.00 |
May | 0.706264E+10 | 0.232776E+10 | 0.334252E+10 | 0.552223E+09 | 0.279030E+10 | 0.00 | 0.00 |
June | 0.803816E+10 | 0.853221E+09 | 0.276984E+10 | 0.213519E+09 | 0.255632E+10 | 0.00 | 0.00 |
July | 0.806591E+10 | 0.664673E+09 | 0.292463E+10 | 0.302578E+09 | 0.262206E+10 | 0.00 | 0.00 |
August | 0.920908E+10 | 0.895875E+09 | 0.355621E+10 | 0.982762E+09 | 0.257345E+10 | 0.00 | 0.00 |
September | 0.106959E+11 | 0.132628E+10 | 0.495887E+10 | 0.211558E+10 | 0.284329E+10 | 0.00 | 0.00 |
October | 0.136134E+11 | 0.419422E+10 | 0.816482E+10 | 0.565127E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.135512E+11 | 0.593747E+10 | 0.920816E+10 | 0.705297E+10 | 0.215518E+10 | 0.00 | 0.00 |
December | 0.146225E+11 | 0.796749E+10 | 0.103547E+11 | 0.819713E+10 | 0.215756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127345E+12 | 0.458252E+11 | 0.734648E+11 | 0.432219E+11 | 0.302430E+11 | 0.00 | 0.00 |
Minimum of Months | 0.706264E+10 | 0.664673E+09 | 0.276984E+10 | 0.213519E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166936E+11 | 0.796749E+10 | 0.111376E+11 | 0.889532E+10 | 0.287651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420344E+10 | 0.497145E+10 | 0.304616E+10 | 0.189324E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.234628E+10 | 0.463346E+10 | 0.222888E+10 | 0.107753E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.405156E+10 | 0.451061E+10 | 0.326853E+10 | 0.155816E+10 | 0.171037E+10 | 0.00 | 0.00 |
April | 0.805246E+10 | 0.261988E+10 | 0.485702E+10 | 0.277059E+10 | 0.208643E+10 | 0.00 | 0.00 |
May | 0.914460E+10 | 0.180361E+10 | 0.503181E+10 | 0.282134E+10 | 0.221047E+10 | 0.00 | 0.00 |
June | 0.108188E+11 | 0.766513E+09 | 0.517675E+10 | 0.304477E+10 | 0.213199E+10 | 0.00 | 0.00 |
July | 0.831694E+10 | 0.643924E+09 | 0.389335E+10 | 0.181740E+10 | 0.207595E+10 | 0.00 | 0.00 |
August | 0.777130E+10 | 0.951350E+09 | 0.371266E+10 | 0.186457E+10 | 0.184809E+10 | 0.00 | 0.00 |
September | 0.636713E+10 | 0.103141E+10 | 0.313180E+10 | 0.131586E+10 | 0.181595E+10 | 0.00 | 0.00 |
October | 0.524233E+10 | 0.324887E+10 | 0.331130E+10 | 0.189340E+10 | 0.141791E+10 | 0.00 | 0.00 |
November | 0.388819E+10 | 0.475443E+10 | 0.295141E+10 | 0.178198E+10 | 0.116944E+10 | 0.00 | 0.00 |
December | 0.284268E+10 | 0.649416E+10 | 0.245801E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.730458E+11 | 0.364297E+11 | 0.430677E+11 | 0.232383E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.234628E+10 | 0.643924E+09 | 0.222888E+10 | 0.107753E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108188E+11 | 0.649416E+10 | 0.517675E+10 | 0.304477E+10 | 0.221047E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104963E+10 | 0.617145E+10 | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.00 | 0.00 |
February | 0.578363E+09 | 0.565140E+10 | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.00 | 0.00 |
March | 0.180800E+10 | 0.551156E+10 | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.00 | 0.00 |
April | 0.407721E+10 | 0.292155E+10 | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.580848E+10 | 0.204360E+10 | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.00 | 0.00 |
June | 0.898665E+10 | 0.830683E+09 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
July | 0.793941E+10 | 0.661611E+09 | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.00 | 0.00 |
August | 0.661301E+10 | 0.828847E+09 | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.00 | 0.00 |
September | 0.526805E+10 | 0.123714E+10 | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.00 | 0.00 |
October | 0.254578E+10 | 0.394810E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.993599E+09 | 0.556963E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.606830E+09 | 0.757745E+10 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.462750E+11 | 0.429530E+11 | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.578363E+09 | 0.661611E+09 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898665E+10 | 0.757745E+10 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.358541E+10 | 0.386684E+10 | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.00 | 0.00 |
February | 0.276386E+10 | 0.357317E+10 | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.448035E+10 | 0.346822E+10 | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.00 | 0.00 |
April | 0.814487E+10 | 0.188214E+10 | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.00 | 0.00 |
May | 0.941651E+10 | 0.138886E+10 | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.00 | 0.00 |
June | 0.111645E+11 | 0.532861E+09 | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.00 | 0.00 |
July | 0.986675E+10 | 0.425495E+09 | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.00 | 0.00 |
August | 0.928688E+10 | 0.540929E+09 | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.00 | 0.00 |
September | 0.704108E+10 | 0.790835E+09 | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.567023E+10 | 0.248764E+10 | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.332080E+10 | 0.350823E+10 | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.00 | 0.00 |
December | 0.274156E+10 | 0.470367E+10 | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.774828E+11 | 0.271689E+11 | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.274156E+10 | 0.425495E+09 | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111645E+11 | 0.470367E+10 | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165544E+11 | 0.647611E+10 | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.00 | 0.00 |
February | 0.829949E+10 | 0.564702E+10 | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.830116E+10 | 0.568993E+10 | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.00 | 0.00 |
April | 0.911643E+10 | 0.316049E+10 | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.00 | 0.00 |
May | 0.713159E+10 | 0.226752E+10 | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.00 | 0.00 |
June | 0.817461E+10 | 0.857123E+09 | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.00 | 0.00 |
July | 0.818252E+10 | 0.667701E+09 | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.00 | 0.00 |
August | 0.933846E+10 | 0.860148E+09 | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.00 | 0.00 |
September | 0.106708E+11 | 0.130968E+10 | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.00 | 0.00 |
October | 0.135067E+11 | 0.408311E+10 | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.134545E+11 | 0.572570E+10 | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.00 | 0.00 |
December | 0.145740E+11 | 0.767198E+10 | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127305E+12 | 0.444165E+11 | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.713159E+10 | 0.667701E+09 | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165544E+11 | 0.767198E+10 | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434922E+10 | 0.440041E+10 | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.247341E+10 | 0.387422E+10 | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.425801E+10 | 0.381738E+10 | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.00 | 0.00 |
April | 0.822100E+10 | 0.226460E+10 | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.00 | 0.00 |
May | 0.918617E+10 | 0.168358E+10 | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.00 | 0.00 |
June | 0.109306E+11 | 0.703999E+09 | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.00 | 0.00 |
July | 0.852355E+10 | 0.540889E+09 | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.00 | 0.00 |
August | 0.807120E+10 | 0.674547E+09 | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.00 | 0.00 |
September | 0.644280E+10 | 0.919231E+09 | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.00 | 0.00 |
October | 0.537605E+10 | 0.281677E+10 | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.00 | 0.00 |
November | 0.405781E+10 | 0.395156E+10 | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.00 | 0.00 |
December | 0.308283E+10 | 0.527737E+10 | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.749726E+11 | 0.309245E+11 | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247341E+10 | 0.540889E+09 | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109306E+11 | 0.527737E+10 | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118915E+10 | 0.567089E+10 | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.00 | 0.00 |
February | 0.675573E+09 | 0.510500E+10 | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.00 | 0.00 |
March | 0.191454E+10 | 0.515033E+10 | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.00 | 0.00 |
April | 0.405907E+10 | 0.284362E+10 | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.576367E+10 | 0.203241E+10 | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.00 | 0.00 |
June | 0.888427E+10 | 0.847194E+09 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
July | 0.782268E+10 | 0.680103E+09 | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.00 | 0.00 |
August | 0.652397E+10 | 0.841327E+09 | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.00 | 0.00 |
September | 0.520291E+10 | 0.124027E+10 | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.00 | 0.00 |
October | 0.259438E+10 | 0.371454E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.110581E+10 | 0.509402E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.748332E+09 | 0.692518E+10 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.464844E+11 | 0.401449E+11 | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.675573E+09 | 0.680103E+09 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.888427E+10 | 0.692518E+10 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368772E+10 | 0.361379E+10 | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.00 | 0.00 |
February | 0.284247E+10 | 0.328562E+10 | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.453912E+10 | 0.329738E+10 | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.00 | 0.00 |
April | 0.810400E+10 | 0.186194E+10 | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.00 | 0.00 |
May | 0.935648E+10 | 0.138942E+10 | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.00 | 0.00 |
June | 0.110707E+11 | 0.547108E+09 | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.00 | 0.00 |
July | 0.976649E+10 | 0.439479E+09 | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.00 | 0.00 |
August | 0.920388E+10 | 0.552283E+09 | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.00 | 0.00 |
September | 0.698005E+10 | 0.797207E+09 | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.567888E+10 | 0.238642E+10 | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.340310E+10 | 0.326926E+10 | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.00 | 0.00 |
December | 0.288724E+10 | 0.434884E+10 | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.775201E+11 | 0.257887E+11 | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.284247E+10 | 0.439479E+09 | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110707E+11 | 0.434884E+10 | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166536E+11 | 0.609510E+10 | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.00 | 0.00 |
February | 0.839828E+10 | 0.519934E+10 | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.837147E+10 | 0.539117E+10 | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.00 | 0.00 |
April | 0.906976E+10 | 0.309085E+10 | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.00 | 0.00 |
May | 0.707577E+10 | 0.224217E+10 | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.00 | 0.00 |
June | 0.807229E+10 | 0.868026E+09 | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.00 | 0.00 |
July | 0.806420E+10 | 0.682636E+09 | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.00 | 0.00 |
August | 0.923952E+10 | 0.869916E+09 | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.00 | 0.00 |
September | 0.105887E+11 | 0.131613E+10 | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.00 | 0.00 |
October | 0.135055E+11 | 0.391619E+10 | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.135400E+11 | 0.537728E+10 | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.00 | 0.00 |
December | 0.147266E+11 | 0.715667E+10 | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127306E+12 | 0.422055E+11 | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.707577E+10 | 0.682636E+09 | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166536E+11 | 0.715667E+10 | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439539E+10 | 0.412900E+10 | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.250958E+10 | 0.359089E+10 | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.429272E+10 | 0.362652E+10 | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.00 | 0.00 |
April | 0.818414E+10 | 0.221782E+10 | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.00 | 0.00 |
May | 0.913373E+10 | 0.166743E+10 | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.00 | 0.00 |
June | 0.108487E+11 | 0.709492E+09 | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.00 | 0.00 |
July | 0.844492E+10 | 0.548146E+09 | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.00 | 0.00 |
August | 0.800662E+10 | 0.678193E+09 | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.00 | 0.00 |
September | 0.639406E+10 | 0.917493E+09 | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.00 | 0.00 |
October | 0.537693E+10 | 0.269512E+10 | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.00 | 0.00 |
November | 0.409477E+10 | 0.370317E+10 | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.00 | 0.00 |
December | 0.314375E+10 | 0.492848E+10 | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.748253E+11 | 0.294117E+11 | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250958E+10 | 0.548146E+09 | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108487E+11 | 0.492848E+10 | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331017E+11 | -0.320827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101904E+10 | 58.97 | 0.00 | 0.00 |
February | 0.297878E+11 | -0.288643E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -923510921.1 | 58.96 | 0.00 | 0.00 |
March | 0.333151E+11 | -0.322895E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102557E+10 | 58.98 | 0.00 | 0.00 |
April | 0.279343E+11 | -0.269473E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986979351.6 | 58.98 | 0.00 | 0.00 |
May | 0.271227E+11 | -0.261010E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102167E+10 | 58.98 | 0.00 | 0.00 |
June | 0.246427E+11 | -0.236532E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989459570.5 | 58.97 | 0.00 | 0.00 |
July | 0.224848E+11 | -0.214678E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101698E+10 | 58.97 | 0.00 | 0.00 |
August | 0.248785E+11 | -0.238579E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102060E+10 | 58.96 | 0.00 | 0.00 |
September | 0.241963E+11 | -0.232118E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984562091.6 | 58.97 | 0.00 | 0.00 |
October | 0.273841E+11 | -0.263680E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101610E+10 | 58.97 | 0.00 | 0.00 |
November | 0.293991E+11 | -0.284152E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983897365.6 | 58.97 | 0.00 | 0.00 |
December | 0.313326E+11 | -0.303151E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101746E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.335580E+12 | -0.323574E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120058E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.224848E+11 | -0.322895E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102557E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.333151E+11 | -0.214678E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -923510921.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9203.49 | 39.09 | 306.50 | 291.50 | 2392.35 | 29.17 | 193.17 | 287.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8290.48 | 36.52 | 234.33 | 265.00 | 1315.61 | 23.40 | 146.17 | 223.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1597.31 | 19.59 | 47.83 | 328.83 | 930.87 | 20.92 | 181.00 | 287.00 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:09 | 1243.82 | 19.20 | 19.67 | 333.50 | 780.88 | 20.52 | 131.33 | 303.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 993.15 | 18.93 | 0.17 | 359.50 | 625.61 | 20.33 | 71.00 | 318.50 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:30 | 828.08 | 18.19 | 0.00 | 363.17 | 537.08 | 19.64 | 19.00 | 313.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:49 | 954.43 | 18.63 | 0.00 | 363.83 | 577.14 | 20.03 | 80.00 | 297.33 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:49 | 1091.69 | 18.98 | 3.50 | 337.83 | 665.38 | 20.34 | 91.50 | 289.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1549.51 | 19.95 | 59.00 | 319.17 | 868.07 | 20.89 | 178.33 | 286.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3162.87 | 25.24 | 154.83 | 314.67 | 1128.80 | 20.59 | 126.00 | 298.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8715.81 | 37.79 | 282.50 | 285.33 | 1595.42 | 24.33 | 150.33 | 263.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8526.15 | 39.08 | 289.33 | 280.00 | 2228.03 | 28.90 | 188.17 | 274.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3392.98 | 24.80 | 1397.67 | 3842.33 | 1070.89 | 22.09 | 1556.00 | 3442.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 828.08 | 18.19 | 0.00 | 265.00 | 537.08 | 19.64 | 19.00 | 223.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9203.49 | 39.09 | 306.50 | 363.83 | 2392.35 | 29.17 | 193.17 | 318.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2192.14 | 24.59 | 107.83 | 274.67 | 1199.55 | 24.29 | 103.50 | 232.17 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2641.19 | 25.06 | 87.83 | 254.33 | 1465.09 | 24.83 | 101.67 | 190.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2214.91 | 23.48 | 100.17 | 316.17 | 1163.30 | 23.57 | 131.33 | 282.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3095.57 | 23.61 | 112.33 | 348.17 | 1732.56 | 23.90 | 101.17 | 327.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3515.24 | 24.69 | 134.17 | 380.83 | 1401.62 | 23.56 | 85.00 | 357.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3528.35 | 24.15 | 134.83 | 386.67 | 1384.66 | 23.04 | 78.00 | 353.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3077.60 | 24.13 | 128.17 | 381.33 | 1248.91 | 23.03 | 90.00 | 325.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3009.08 | 23.93 | 114.50 | 353.33 | 1662.54 | 24.11 | 109.83 | 310.33 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:30 | 2383.91 | 23.57 | 105.00 | 319.00 | 1272.19 | 23.77 | 127.67 | 279.33 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-06:00 | 2309.82 | 23.24 | 103.33 | 295.33 | 1237.75 | 23.17 | 114.67 | 257.67 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1868.70 | 23.17 | 80.33 | 273.67 | 982.81 | 23.04 | 86.33 | 210.50 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2181.70 | 25.15 | 106.33 | 260.83 | 1199.01 | 24.74 | 103.50 | 209.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2727.25 | 24.04 | 1314.83 | 3844.33 | 1338.93 | 23.70 | 1232.67 | 3336.83 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1868.70 | 23.17 | 80.33 | 254.33 | 982.81 | 23.03 | 78.00 | 190.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 3528.35 | 25.15 | 134.83 | 386.67 | 1732.56 | 24.83 | 131.33 | 357.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-10:09 | 480.90 | 15.63 | 0.00 | 229.83 | 330.41 | 17.51 | 0.00 | 147.17 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:30 | 588.06 | 16.56 | 0.00 | 228.17 | 377.87 | 18.15 | 0.00 | 136.00 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:20 | 672.01 | 17.78 | 0.00 | 304.17 | 419.26 | 19.16 | 3.50 | 233.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 796.33 | 18.90 | 0.00 | 336.33 | 522.06 | 20.24 | 48.17 | 305.00 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 935.27 | 19.67 | 26.67 | 388.67 | 612.15 | 20.96 | 96.00 | 373.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1079.26 | 22.45 | 108.00 | 400.00 | 636.23 | 22.54 | 140.33 | 391.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 958.26 | 21.82 | 83.50 | 394.17 | 606.45 | 23.02 | 152.17 | 360.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 803.87 | 18.99 | 0.50 | 348.83 | 509.65 | 20.32 | 49.50 | 295.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:19 | 762.32 | 18.32 | 0.00 | 315.50 | 465.96 | 19.65 | 13.00 | 257.67 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:00 | 553.73 | 16.49 | 0.00 | 264.33 | 368.99 | 18.08 | 1.00 | 191.17 |
November | 288.50 | 0.57 | 0.48 | 01-NOV-08:39 | 520.41 | 16.34 | 0.00 | 239.17 | 345.02 | 18.11 | 0.00 | 140.00 |
December | 290.67 | 0.58 | 0.48 | 01-DEC-09:20 | 483.34 | 15.81 | 0.00 | 217.17 | 324.11 | 17.70 | 0.00 | 118.50 |
Annual Sum or Average | 4135.50 | 0.54 | 744.12 | 18.50 | 218.67 | 3666.33 | 474.24 | 19.84 | 503.67 | 2949.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 480.90 | 15.63 | 0.00 | 217.17 | 324.11 | 17.51 | 0.00 | 118.50 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1079.26 | 22.45 | 108.00 | 400.00 | 636.23 | 23.02 | 152.17 | 391.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:00 | 2356.63 | 24.00 | 107.83 | 248.83 | 1310.66 | 23.76 | 109.00 | 216.17 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:30 | 2388.33 | 23.29 | 83.00 | 239.67 | 931.02 | 21.83 | 93.33 | 179.67 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:09 | 2025.85 | 22.99 | 95.33 | 315.50 | 1094.74 | 23.27 | 142.67 | 278.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:39 | 2892.48 | 21.67 | 85.00 | 335.17 | 1601.69 | 22.28 | 85.50 | 309.67 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:49 | 3100.44 | 19.74 | 54.50 | 365.83 | 1706.16 | 19.65 | 56.67 | 335.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:40 | 3155.22 | 16.68 | 0.00 | 373.00 | 1269.99 | 19.27 | 56.83 | 345.17 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:00 | 2363.26 | 17.40 | 3.67 | 372.33 | 1059.18 | 19.61 | 70.33 | 326.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-08:09 | 2421.46 | 19.55 | 49.17 | 343.33 | 1322.45 | 19.70 | 51.33 | 298.67 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:49 | 1935.35 | 21.73 | 82.83 | 318.33 | 1038.31 | 22.23 | 116.83 | 282.83 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2344.56 | 23.55 | 112.00 | 289.00 | 1274.73 | 23.59 | 122.67 | 257.67 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:50 | 2189.26 | 23.75 | 93.00 | 254.67 | 1180.36 | 23.58 | 96.67 | 211.33 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:20 | 1840.94 | 23.25 | 92.00 | 241.50 | 977.80 | 22.94 | 102.33 | 202.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2455.18 | 21.18 | 858.33 | 3697.17 | 1249.94 | 21.65 | 1104.17 | 3243.67 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1840.94 | 16.68 | 0.00 | 239.67 | 931.02 | 19.27 | 51.33 | 179.67 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3155.22 | 24.00 | 112.00 | 373.00 | 1706.16 | 23.76 | 142.67 | 345.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9294.01 | 38.70 | 306.33 | 291.67 | 2515.89 | 25.51 | 145.33 | 288.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8352.26 | 36.08 | 234.00 | 265.33 | 1412.70 | 19.02 | 38.33 | 227.00 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1636.67 | 13.18 | 2.33 | 329.33 | 1000.32 | 16.75 | 1.83 | 292.17 |
April | 380.33 | 0.53 | 0.48 | 01-APR-07:00 | 1280.31 | 13.43 | 0.00 | 334.00 | 839.61 | 16.98 | 0.00 | 308.83 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 1018.29 | 13.32 | 0.00 | 360.83 | 669.95 | 16.88 | 0.00 | 325.83 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:19 | 849.68 | 12.63 | 0.00 | 363.83 | 574.95 | 16.23 | 0.00 | 323.00 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:30 | 974.41 | 12.89 | 0.00 | 365.00 | 616.58 | 16.42 | 0.00 | 306.67 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1118.30 | 13.12 | 0.00 | 338.83 | 713.11 | 16.68 | 0.00 | 296.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1583.85 | 13.88 | 10.83 | 320.00 | 930.10 | 16.83 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3245.05 | 20.64 | 139.83 | 318.17 | 1225.75 | 16.34 | 13.17 | 301.00 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8791.35 | 37.29 | 282.17 | 285.33 | 1746.00 | 21.56 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8608.03 | 38.68 | 289.33 | 280.17 | 2350.45 | 25.03 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3439.73 | 20.54 | 1264.83 | 3852.50 | 1145.64 | 18.37 | 418.33 | 3504.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 849.68 | 12.63 | 0.00 | 265.33 | 574.95 | 16.23 | 0.00 | 227.00 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9294.01 | 38.70 | 306.33 | 365.00 | 2515.89 | 25.51 | 145.33 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2232.69 | 22.20 | 105.17 | 275.33 | 1249.11 | 22.48 | 74.67 | 240.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2689.33 | 22.51 | 85.83 | 256.00 | 1520.09 | 22.85 | 62.83 | 197.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2223.72 | 19.04 | 86.17 | 316.67 | 1220.65 | 21.18 | 69.67 | 286.67 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3141.34 | 20.63 | 112.33 | 348.50 | 1801.64 | 21.47 | 82.33 | 330.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3561.42 | 21.76 | 134.17 | 381.67 | 1475.36 | 20.86 | 72.33 | 361.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3583.74 | 21.14 | 134.83 | 387.17 | 1455.15 | 20.31 | 74.83 | 358.17 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3121.75 | 21.14 | 128.17 | 382.50 | 1314.44 | 20.32 | 68.33 | 331.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3047.39 | 20.88 | 114.50 | 353.83 | 1728.26 | 21.62 | 83.50 | 315.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2429.96 | 20.64 | 104.00 | 319.67 | 1328.63 | 21.46 | 75.17 | 284.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2360.98 | 20.39 | 102.83 | 297.00 | 1293.74 | 20.90 | 72.17 | 263.83 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1906.80 | 20.34 | 80.17 | 274.17 | 1030.19 | 20.87 | 52.83 | 217.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2217.85 | 22.79 | 105.00 | 261.67 | 1245.34 | 22.99 | 74.00 | 215.83 |
Annual Sum or Average | 4135.50 | 0.52 | 2769.16 | 21.07 | 1293.17 | 3854.17 | 1399.42 | 21.34 | 862.67 | 3403.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1906.80 | 19.04 | 80.17 | 256.00 | 1030.19 | 20.31 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3583.74 | 22.79 | 134.83 | 387.17 | 1801.64 | 22.99 | 83.50 | 361.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-09:00 | 490.54 | 10.05 | 0.00 | 231.67 | 352.63 | 13.86 | 0.00 | 167.33 |
February | 241.00 | 0.56 | 0.48 | 01-FEB-10:20 | 600.01 | 11.05 | 0.00 | 229.17 | 403.11 | 14.66 | 0.00 | 151.00 |
March | 344.33 | 0.54 | 0.48 | 01-MAR-08:20 | 686.18 | 12.36 | 0.00 | 305.17 | 447.30 | 15.88 | 0.00 | 244.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:20 | 816.50 | 13.75 | 0.00 | 337.67 | 558.34 | 17.34 | 0.00 | 310.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 959.60 | 14.16 | 2.67 | 389.67 | 653.97 | 17.81 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1106.11 | 17.71 | 81.33 | 401.00 | 703.09 | 20.93 | 81.50 | 395.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 980.33 | 16.93 | 62.50 | 394.50 | 646.11 | 20.15 | 62.83 | 366.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 823.30 | 13.50 | 0.00 | 349.17 | 544.79 | 17.13 | 0.00 | 302.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 777.49 | 12.94 | 0.00 | 316.17 | 496.84 | 16.38 | 0.00 | 269.50 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:49 | 566.55 | 11.05 | 0.00 | 266.50 | 394.17 | 14.72 | 0.00 | 207.00 |
November | 288.50 | 0.56 | 0.48 | 01-NOV-08:39 | 530.79 | 10.62 | 0.00 | 240.67 | 368.12 | 14.44 | 0.00 | 159.17 |
December | 290.67 | 0.57 | 0.48 | 01-DEC-09:20 | 492.19 | 10.04 | 0.00 | 221.00 | 345.62 | 13.90 | 0.00 | 140.83 |
Annual Sum or Average | 4135.50 | 0.53 | 761.21 | 13.15 | 146.50 | 3682.33 | 508.65 | 16.72 | 147.00 | 3089.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 490.54 | 10.04 | 0.00 | 221.00 | 345.62 | 13.86 | 0.00 | 140.83 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1106.11 | 17.71 | 81.33 | 401.00 | 703.09 | 20.93 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:50 | 2396.16 | 21.58 | 105.67 | 250.83 | 1362.09 | 21.92 | 74.67 | 221.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:20 | 2429.74 | 20.75 | 81.17 | 241.83 | 979.24 | 19.50 | 36.50 | 185.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:39 | 2072.73 | 19.93 | 93.67 | 317.67 | 1147.42 | 20.87 | 65.33 | 284.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 2932.31 | 18.20 | 85.00 | 336.83 | 1670.32 | 19.44 | 55.00 | 314.50 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:40 | 3139.47 | 15.78 | 54.50 | 366.33 | 1776.96 | 16.19 | 0.00 | 342.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:30 | 3173.97 | 11.90 | 0.00 | 373.50 | 1339.13 | 15.74 | 0.00 | 350.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:49 | 2399.58 | 12.85 | 3.67 | 374.00 | 1115.06 | 16.26 | 0.00 | 333.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2453.19 | 15.65 | 49.17 | 344.33 | 1380.01 | 16.40 | 5.00 | 304.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1976.05 | 18.51 | 81.83 | 319.17 | 1089.49 | 19.68 | 53.83 | 287.00 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2378.88 | 20.53 | 109.33 | 290.67 | 1326.34 | 21.43 | 81.17 | 263.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:39 | 2170.61 | 19.73 | 80.83 | 255.67 | 1233.27 | 21.49 | 62.50 | 217.67 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:09 | 1838.67 | 19.72 | 80.67 | 243.83 | 1024.38 | 21.02 | 57.50 | 209.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2484.98 | 17.57 | 825.50 | 3714.67 | 1307.26 | 18.93 | 491.50 | 3313.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1838.67 | 11.90 | 0.00 | 241.83 | 979.24 | 15.74 | 0.00 | 185.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3173.97 | 21.58 | 109.33 | 374.00 | 1776.96 | 21.92 | 81.17 | 350.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9295.03 | 38.69 | 306.33 | 291.67 | 2517.32 | 25.50 | 145.33 | 288.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8354.27 | 36.07 | 234.00 | 265.33 | 1414.27 | 19.01 | 38.33 | 227.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1638.79 | 13.15 | 2.33 | 329.33 | 1001.67 | 16.74 | 1.83 | 292.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-07:00 | 1281.62 | 13.40 | 0.00 | 334.17 | 840.55 | 16.97 | 0.00 | 309.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 1019.25 | 13.29 | 0.00 | 360.83 | 670.70 | 16.87 | 0.00 | 325.83 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:19 | 850.37 | 12.60 | 0.00 | 363.83 | 575.54 | 16.21 | 0.00 | 323.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:30 | 975.48 | 12.86 | 0.00 | 365.00 | 617.34 | 16.41 | 0.00 | 306.83 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1119.56 | 13.09 | 0.00 | 339.00 | 713.97 | 16.67 | 0.00 | 296.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1585.93 | 13.86 | 10.83 | 320.00 | 931.42 | 16.82 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3246.74 | 20.62 | 139.83 | 318.17 | 1226.99 | 16.33 | 13.17 | 301.17 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8792.63 | 37.29 | 282.17 | 285.33 | 1747.44 | 21.55 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8608.92 | 38.68 | 289.33 | 280.17 | 2352.00 | 25.02 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3441.07 | 20.51 | 1264.83 | 3852.83 | 1146.74 | 18.36 | 418.33 | 3505.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 850.37 | 12.60 | 0.00 | 265.33 | 575.54 | 16.21 | 0.00 | 227.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9295.03 | 38.69 | 306.33 | 365.00 | 2517.32 | 25.50 | 145.33 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2233.10 | 22.18 | 105.17 | 275.33 | 1249.71 | 22.47 | 74.67 | 240.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2690.10 | 22.48 | 85.83 | 256.00 | 1520.96 | 22.84 | 62.83 | 197.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2224.79 | 19.01 | 86.17 | 316.67 | 1221.69 | 21.17 | 69.67 | 286.67 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3142.20 | 20.60 | 112.33 | 348.50 | 1802.63 | 21.46 | 82.33 | 330.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3562.25 | 21.73 | 134.17 | 381.67 | 1476.34 | 20.84 | 72.33 | 361.50 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3584.37 | 21.11 | 134.83 | 387.17 | 1455.99 | 20.29 | 74.83 | 358.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3122.78 | 21.12 | 128.17 | 382.67 | 1315.45 | 20.31 | 68.33 | 331.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3048.44 | 20.85 | 114.50 | 354.00 | 1729.31 | 21.61 | 83.50 | 315.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2431.29 | 20.62 | 104.00 | 319.67 | 1329.82 | 21.45 | 75.17 | 284.17 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2361.62 | 20.36 | 102.83 | 297.00 | 1294.54 | 20.89 | 72.17 | 264.00 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1907.37 | 20.31 | 80.17 | 274.17 | 1030.89 | 20.86 | 52.83 | 218.00 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2218.32 | 22.77 | 105.00 | 261.67 | 1246.00 | 22.98 | 74.00 | 216.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2769.98 | 21.04 | 1293.17 | 3854.50 | 1400.33 | 21.33 | 862.67 | 3404.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1907.37 | 19.01 | 80.17 | 256.00 | 1030.89 | 20.29 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3584.37 | 22.77 | 134.83 | 387.17 | 1802.63 | 22.98 | 83.50 | 361.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-09:00 | 490.69 | 10.02 | 0.00 | 231.67 | 352.94 | 13.84 | 0.00 | 167.67 |
February | 241.00 | 0.56 | 0.48 | 01-FEB-10:20 | 600.43 | 11.02 | 0.00 | 229.33 | 403.54 | 14.64 | 0.00 | 151.17 |
March | 344.33 | 0.54 | 0.48 | 01-MAR-08:20 | 686.76 | 12.33 | 0.00 | 305.17 | 447.83 | 15.87 | 0.00 | 244.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:20 | 817.00 | 13.72 | 0.00 | 337.67 | 558.91 | 17.32 | 0.00 | 310.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 960.27 | 14.13 | 2.67 | 389.67 | 654.62 | 17.79 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1106.75 | 17.68 | 81.33 | 401.00 | 703.74 | 20.91 | 81.50 | 395.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 981.18 | 16.90 | 62.50 | 394.67 | 646.84 | 20.14 | 62.83 | 366.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 823.96 | 13.47 | 0.00 | 349.17 | 545.40 | 17.11 | 0.00 | 303.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 778.21 | 12.91 | 0.00 | 316.33 | 497.45 | 16.37 | 0.00 | 270.00 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:49 | 566.86 | 11.01 | 0.00 | 266.50 | 394.55 | 14.71 | 0.00 | 207.17 |
November | 288.50 | 0.56 | 0.48 | 01-NOV-08:39 | 531.07 | 10.58 | 0.00 | 240.83 | 368.48 | 14.43 | 0.00 | 159.83 |
December | 290.67 | 0.57 | 0.48 | 01-DEC-09:20 | 492.40 | 10.01 | 0.00 | 221.00 | 345.95 | 13.88 | 0.00 | 140.83 |
Annual Sum or Average | 4135.50 | 0.53 | 761.73 | 13.12 | 146.50 | 3683.00 | 509.18 | 16.70 | 147.00 | 3091.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 490.69 | 10.01 | 0.00 | 221.00 | 345.95 | 13.84 | 0.00 | 140.83 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1106.75 | 17.68 | 81.33 | 401.00 | 703.74 | 20.91 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:50 | 2396.56 | 21.55 | 105.67 | 250.83 | 1362.80 | 21.90 | 74.67 | 221.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:20 | 2430.65 | 20.73 | 81.17 | 241.83 | 980.19 | 19.48 | 36.50 | 185.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:39 | 2073.84 | 19.90 | 93.67 | 317.67 | 1148.44 | 20.86 | 65.33 | 284.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 2933.28 | 18.17 | 85.00 | 336.83 | 1671.43 | 19.43 | 55.00 | 314.67 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:40 | 3140.38 | 15.75 | 54.50 | 366.33 | 1778.05 | 16.17 | 0.00 | 342.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:30 | 3173.14 | 11.86 | 0.00 | 373.33 | 1340.08 | 15.73 | 0.00 | 350.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:49 | 2378.56 | 12.81 | 3.67 | 373.83 | 1116.10 | 16.24 | 0.00 | 333.67 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2454.16 | 15.61 | 49.17 | 344.33 | 1380.99 | 16.38 | 5.00 | 304.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1977.36 | 18.48 | 81.83 | 319.17 | 1090.62 | 19.66 | 53.83 | 287.33 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2379.56 | 20.50 | 109.33 | 290.67 | 1327.14 | 21.41 | 81.17 | 263.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:39 | 2171.13 | 19.71 | 80.83 | 255.67 | 1234.05 | 21.48 | 62.50 | 218.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:09 | 1839.13 | 19.70 | 80.67 | 243.83 | 1025.09 | 21.01 | 57.50 | 209.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2483.55 | 17.54 | 825.50 | 3714.33 | 1308.22 | 18.91 | 491.50 | 3314.67 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1839.13 | 11.86 | 0.00 | 241.83 | 980.19 | 15.73 | 0.00 | 185.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3173.14 | 21.55 | 109.33 | 373.83 | 1778.05 | 21.90 | 81.17 | 350.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39813.83 | 66.36 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15824657.83 | 4411.00 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120318E+09 | 9203.73 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120318E+09 | 9203.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8499885.45 | 11941.33 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8499885.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8499885.45 | 11941.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 350635.63 | 246.70 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 164051.76 | 136.14 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3289742.47 | 716.85 | 27-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 652170.47 | 358.07 | 24-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39187868.82 | 9481.40 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43644469.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39187868.82 | 9481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2373225.41 | 1537.93 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1300327.04 | 957.89 | 13-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2369754.57 | 689.11 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17128717.55 | 14957.29 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23172024.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17128717.55 | 14957.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.508011E+09 | 67054.57 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489194E+09 | 36814.41 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152716E+10 | 107616.91 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127228E+09 | 34945.17 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266095E+09 | 57249.84 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.594135E+10 | 149630.17 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594135E+10 | 149630.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7673750.53 | 5467.10 | 02-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7673750.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7673750.53 | 5467.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305655E+10 | 175271.17 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231268E+10 | 188939.88 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185119E+10 | 188325.92 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187924E+09 | 45446.45 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160641E+10 | 174266.27 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786746E+10 | 188641.28 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.786746E+10 | 188939.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204825E+10 | 151321.32 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195592E+10 | 151278.39 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132410E+10 | 152774.88 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267701E+09 | 18728.43 | 28-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104033E+10 | 151044.61 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.486333E+10 | 155346.72 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486333E+10 | 155346.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549209E+09 | 193477.90 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570963E+09 | 195097.83 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.960888E+09 | 159781.44 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5284518.97 | 1800.76 | 26-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132144E+09 | 125683.17 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234791E+10 | 193467.71 | 18-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234791E+10 | 195097.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158797E+10 | 149499.36 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159894E+10 | 105465.57 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110549E+10 | 99657.76 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176022E+09 | 16401.83 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897610E+09 | 104156.23 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453857E+10 | 149544.91 | 18-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.990460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453857E+10 | 149544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191651E+09 | 9893.60 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287668E+09 | 8332.93 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385505E+09 | 16374.43 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 59838847.05 | 7314.98 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126163E+09 | 11920.50 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129719E+10 | 21230.01 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129719E+10 | 21230.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414943E+09 | 81143.10 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160516E+09 | 81000.75 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66094627.96 | 47062.17 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94853403.20 | 54540.85 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457241E+09 | 80794.10 | 18-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457241E+09 | 81143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124561E+10 | 19883.51 | 02-JAN-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118304E+10 | 19960.82 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776247E+09 | 19851.43 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16349306.81 | 2301.06 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226632E+09 | 19739.30 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.852468E+09 | 19904.84 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258728E+10 | 19877.50 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.688763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258728E+10 | 19960.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633914E+09 | 17292.11 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.652701E+09 | 17316.17 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413849E+09 | 17291.29 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6808790.73 | 1693.12 | 21-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133675E+09 | 15879.74 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409479E+09 | 17278.69 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130961E+10 | 17300.37 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130961E+10 | 17316.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452455E+09 | 21602.39 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629599E+09 | 21752.75 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.528166E+09 | 21542.57 | 27-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6769446.38 | 1589.19 | 21-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114297E+09 | 18045.08 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312589E+09 | 21449.34 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103778E+10 | 21650.95 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103778E+10 | 21752.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.625631E+09 | 17874.68 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.682300E+09 | 17884.34 | 13-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446041E+09 | 17851.30 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3008523.31 | 590.40 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140091E+09 | 12391.02 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429159E+09 | 17862.23 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132874E+10 | 17897.55 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132874E+10 | 17897.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.427190E+11 | 0.427046E+11 | 106453.83 | 31-JAN-16:30 | 106453.83 | 0.01 |
February | 0.00 | 0.00 | 0.108491E+11 | 0.108491E+11 | 66906.62 | 21-FEB-15:00 | 66906.62 | 0.10 |
March | 0.00 | 0.00 | 0.465948E+11 | 0.465948E+11 | 117047.96 | 20-MAR-14:40 | 117047.96 | 0.09 |
April | 0.00 | 0.00 | 0.121909E+12 | 0.121909E+12 | 146437.53 | 24-APR-14:50 | 146437.53 | 0.01 |
May | 0.00 | 0.00 | 0.133808E+12 | 0.133808E+12 | 137432.81 | 31-MAY-16:00 | 137432.81 | 0.00 |
June | 0.00 | 0.00 | 0.180225E+12 | 0.180224E+12 | 166009.42 | 09-JUN-05:02 | 166009.42 | 0.10 |
July | 0.00 | 0.00 | 0.188071E+12 | 0.177003E+12 | 322699.68 | 14-JUL-05:02 | 130186.64 | 0.65 |
August | 0.00 | 0.00 | 0.208819E+12 | 0.197092E+12 | 293096.38 | 01-AUG-05:03 | 139733.10 | 0.74 |
September | 0.00 | 0.00 | 0.149349E+12 | 0.139911E+12 | 238030.72 | 01-SEP-05:03 | 122201.79 | 0.56 |
October | 0.00 | 0.00 | 0.917162E+11 | 0.902003E+11 | 257116.87 | 03-OCT-05:03 | 131577.06 | 0.19 |
November | 0.00 | 0.00 | 0.491170E+11 | 0.464224E+11 | 157083.84 | 13-NOV-05:11 | 55777.69 | 0.14 |
December | 0.00 | 0.00 | 0.245573E+11 | 0.245573E+11 | 104925.92 | 22-DEC-16:20 | 104925.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124773E+13 | 0.121128E+13 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.108491E+11 | 0.108491E+11 | 66906.62 | 55777.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208819E+12 | 0.197092E+12 | 322699.68 | 166009.42 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.355006E+12 | 0.354929E+12 | 922142.72 | 31-JAN-16:30 | 922142.72 | 0.01 |
February | 0.00 | 0.00 | 0.820809E+11 | 0.820809E+11 | 511948.09 | 22-FEB-16:00 | 511948.09 | 0.10 |
March | 0.00 | 0.00 | 0.346369E+12 | 0.346369E+12 | 984503.14 | 16-MAR-15:30 | 984503.14 | 0.08 |
April | 0.00 | 0.00 | 0.920911E+12 | 0.920911E+12 | 1298853.71 | 14-APR-15:20 | 1298853.71 | 0.00 |
May | 0.00 | 0.00 | 0.120231E+13 | 0.120231E+13 | 1311535.54 | 18-MAY-15:20 | 1311535.54 | 0.00 |
June | 0.00 | 0.00 | 0.159150E+13 | 0.159150E+13 | 1559011.22 | 09-JUN-05:02 | 1559011.22 | 0.09 |
July | 0.00 | 0.00 | 0.153652E+13 | 0.145558E+13 | 3081448.06 | 14-JUL-05:02 | 1242105.96 | 0.55 |
August | 0.00 | 0.00 | 0.156597E+13 | 0.148992E+13 | 2026416.59 | 04-AUG-05:03 | 978381.80 | 0.61 |
September | 0.00 | 0.00 | 0.129702E+13 | 0.121816E+13 | 2421175.53 | 05-SEP-03:02 | 1251048.82 | 0.51 |
October | 0.00 | 0.00 | 0.750196E+12 | 0.737618E+12 | 2157434.68 | 03-OCT-04:12 | 1125112.04 | 0.16 |
November | 0.00 | 0.00 | 0.356260E+12 | 0.341553E+12 | 1165899.36 | 13-NOV-05:11 | 410719.01 | 0.13 |
December | 0.00 | 0.00 | 0.174965E+12 | 0.174965E+12 | 804374.80 | 22-DEC-15:50 | 804374.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101791E+14 | 0.991590E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.820809E+11 | 0.820809E+11 | 511948.09 | 410719.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159150E+13 | 0.159150E+13 | 3081448.06 | 1559011.22 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322360E+11 | 0.322258E+11 | 97649.88 | 31-JAN-16:30 | 97649.88 | 0.01 |
February | 0.00 | 0.00 | 0.687685E+10 | 0.687685E+10 | 50205.69 | 22-FEB-16:00 | 50205.69 | 0.09 |
March | 0.00 | 0.00 | 0.336355E+11 | 0.336355E+11 | 111654.34 | 16-MAR-15:30 | 111654.34 | 0.08 |
April | 0.00 | 0.00 | 0.100270E+12 | 0.100270E+12 | 153163.90 | 14-APR-15:20 | 153163.90 | 0.00 |
May | 0.00 | 0.00 | 0.132199E+12 | 0.132199E+12 | 154895.11 | 18-MAY-15:30 | 154895.11 | 0.00 |
June | 0.00 | 0.00 | 0.180600E+12 | 0.180600E+12 | 182291.74 | 28-JUN-14:50 | 182291.74 | 0.09 |
July | 0.00 | 0.00 | 0.173225E+12 | 0.164936E+12 | 314258.98 | 14-JUL-05:02 | 126179.15 | 0.57 |
August | 0.00 | 0.00 | 0.173708E+12 | 0.165818E+12 | 216457.58 | 04-AUG-05:03 | 104021.06 | 0.62 |
September | 0.00 | 0.00 | 0.140307E+12 | 0.132435E+12 | 260663.39 | 02-SEP-03:02 | 140911.46 | 0.52 |
October | 0.00 | 0.00 | 0.765938E+11 | 0.754236E+11 | 240547.66 | 03-OCT-05:03 | 124432.02 | 0.16 |
November | 0.00 | 0.00 | 0.322363E+11 | 0.312020E+11 | 114395.72 | 01-NOV-15:30 | 114395.72 | 0.12 |
December | 0.00 | 0.00 | 0.146221E+11 | 0.146221E+11 | 83664.95 | 22-DEC-15:50 | 83664.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109651E+13 | 0.107024E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.687685E+10 | 0.687685E+10 | 50205.69 | 50205.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180600E+12 | 0.180600E+12 | 314258.98 | 182291.74 | 0.62 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.271330E+11 | 0.271300E+11 | 86528.80 | 16-JAN-15:37 | 86528.80 | 0.00 |
February | 0.00 | 0.00 | 0.451509E+10 | 0.448189E+10 | 57815.26 | 17-FEB-06:03 | 24409.56 | 0.06 |
March | 0.00 | 0.00 | 0.268149E+11 | 0.268085E+11 | 70007.21 | 20-MAR-14:00 | 70007.21 | 0.06 |
April | 0.00 | 0.00 | 0.643365E+11 | 0.643365E+11 | 123908.11 | 30-APR-18:09 | 123908.11 | 0.00 |
May | 0.00 | 0.00 | 0.795072E+11 | 0.795072E+11 | 125936.97 | 29-MAY-17:37 | 125936.97 | 0.00 |
June | 0.00 | 0.00 | 0.962831E+11 | 0.962831E+11 | 116804.64 | 27-JUN-03:02 | 116804.64 | 0.07 |
July | 0.00 | 0.00 | 0.102876E+12 | 0.995042E+11 | 187388.15 | 14-JUL-04:23 | 74502.03 | 0.47 |
August | 0.00 | 0.00 | 0.114697E+12 | 0.110793E+12 | 180256.89 | 01-AUG-03:02 | 93259.62 | 0.56 |
September | 0.00 | 0.00 | 0.979540E+11 | 0.937055E+11 | 170933.96 | 05-SEP-07:10 | 70122.56 | 0.49 |
October | 0.00 | 0.00 | 0.615179E+11 | 0.609810E+11 | 144015.71 | 03-OCT-05:03 | 74431.96 | 0.15 |
November | 0.00 | 0.00 | 0.318298E+11 | 0.298766E+11 | 121027.04 | 13-NOV-05:23 | 43595.10 | 0.10 |
December | 0.00 | 0.00 | 0.139275E+11 | 0.139253E+11 | 67972.05 | 26-DEC-13:10 | 67972.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.721392E+12 | 0.707333E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.451509E+10 | 0.448189E+10 | 57815.26 | 24409.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114697E+12 | 0.110793E+12 | 187388.15 | 125936.97 | 0.56 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.292249E+11 | 0.291962E+11 | 136654.30 | 27-JAN-16:00 | 136654.30 | 0.00 |
February | 0.00 | 0.00 | 0.101732E+11 | 0.959072E+10 | 100530.00 | 18-FEB-14:00 | 86622.95 | 0.00 |
March | 0.00 | 0.00 | 0.193312E+12 | 0.189486E+12 | 318625.98 | 17-MAR-15:20 | 318625.98 | 0.00 |
April | 0.00 | 0.00 | 0.672061E+12 | 0.670348E+12 | 377716.63 | 15-APR-09:00 | 377716.63 | 0.00 |
May | 0.00 | 0.00 | 0.218752E+12 | 0.218751E+12 | 214808.75 | 31-MAY-23:10 | 214808.75 | 0.00 |
June | 0.00 | 0.00 | 0.520529E+12 | 0.520521E+12 | 306981.86 | 30-JUN-23:57 | 306981.86 | 0.00 |
July | 0.00 | 0.00 | 0.872548E+12 | 0.789294E+12 | 469714.03 | 14-JUL-01:00 | 155199.36 | 0.00 |
August | 0.00 | 0.00 | 0.106710E+13 | 0.936290E+12 | 453465.98 | 09-AUG-18:20 | 229164.59 | 0.00 |
September | 0.00 | 0.00 | 0.267762E+12 | 0.241186E+12 | 234364.81 | 04-SEP-10:13 | 129910.37 | 0.00 |
October | 0.00 | 0.00 | 0.251729E+12 | 0.240731E+12 | 338365.06 | 03-OCT-08:30 | 225089.06 | 0.00 |
November | 0.00 | 0.00 | 0.202148E+12 | 0.175251E+12 | 321492.27 | 09-NOV-13:05 | 321492.27 | 0.00 |
December | 0.00 | 0.00 | 0.201565E+12 | 0.201201E+12 | 348750.92 | 25-DEC-13:51 | 348750.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.450690E+13 | 0.422185E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101732E+11 | 0.959072E+10 | 100530.00 | 86622.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106710E+13 | 0.936290E+12 | 469714.03 | 377716.63 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.554230E+10 | 0.553895E+10 | 2892.34 | 24-JAN-17:00 | 2892.34 | 0.00 |
February | 0.00 | 0.00 | 0.947613E+10 | 0.943224E+10 | 4645.32 | 22-FEB-17:00 | 4587.45 | 0.00 |
March | 0.00 | 0.00 | 0.158852E+11 | 0.158736E+11 | 7753.49 | 31-MAR-24:00 | 7753.49 | 0.00 |
April | 0.00 | 0.00 | 0.203002E+11 | 0.203002E+11 | 8493.45 | 26-APR-18:40 | 8493.45 | 0.00 |
May | 0.00 | 0.00 | 0.648312E+10 | 0.648312E+10 | 4103.23 | 31-MAY-24:00 | 4103.23 | 0.00 |
June | 0.00 | 0.00 | 0.113662E+11 | 0.113650E+11 | 6013.71 | 30-JUN-23:40 | 6013.71 | 0.00 |
July | 0.00 | 0.00 | 0.168535E+11 | 0.167037E+11 | 7923.48 | 31-JUL-23:55 | 7911.55 | 0.00 |
August | 0.00 | 0.00 | 0.216996E+11 | 0.215488E+11 | 8967.94 | 28-AUG-16:35 | 8405.43 | 0.00 |
September | 0.00 | 0.00 | 0.645751E+10 | 0.631915E+10 | 4113.49 | 30-SEP-23:53 | 4113.49 | 0.00 |
October | 0.00 | 0.00 | 0.112696E+11 | 0.112392E+11 | 5927.18 | 31-OCT-24:00 | 5927.18 | 0.00 |
November | 0.00 | 0.00 | 0.155456E+11 | 0.154963E+11 | 7036.05 | 14-NOV-17:00 | 6804.38 | 0.00 |
December | 0.00 | 0.00 | 0.207424E+11 | 0.207420E+11 | 8554.07 | 28-DEC-17:00 | 8554.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161621E+12 | 0.161042E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.554230E+10 | 0.553895E+10 | 2892.34 | 2892.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216996E+11 | 0.215488E+11 | 8967.94 | 8554.07 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.422278E+11 | 0.421960E+11 | 26794.72 | 24-JAN-17:00 | 26794.72 | 0.00 |
February | 0.00 | 0.00 | 0.802507E+11 | 0.798197E+11 | 43370.34 | 22-FEB-17:00 | 42819.06 | 0.00 |
March | 0.00 | 0.00 | 0.144086E+12 | 0.143970E+12 | 72326.70 | 31-MAR-23:50 | 72326.70 | 0.00 |
April | 0.00 | 0.00 | 0.191901E+12 | 0.191901E+12 | 80660.64 | 26-APR-18:30 | 80660.64 | 0.00 |
May | 0.00 | 0.00 | 0.602109E+11 | 0.602109E+11 | 39683.34 | 31-MAY-24:00 | 39683.34 | 0.00 |
June | 0.00 | 0.00 | 0.108310E+12 | 0.108297E+12 | 57964.72 | 30-JUN-23:30 | 57964.72 | 0.00 |
July | 0.00 | 0.00 | 0.160355E+12 | 0.158864E+12 | 75887.33 | 31-JUL-23:55 | 75770.40 | 0.00 |
August | 0.00 | 0.00 | 0.204438E+12 | 0.202918E+12 | 84609.74 | 28-AUG-16:15 | 78598.78 | 0.00 |
September | 0.00 | 0.00 | 0.598211E+11 | 0.584614E+11 | 39728.10 | 30-SEP-24:00 | 39728.10 | 0.00 |
October | 0.00 | 0.00 | 0.102494E+12 | 0.102193E+12 | 54604.23 | 31-OCT-24:00 | 54604.23 | 0.00 |
November | 0.00 | 0.00 | 0.139658E+12 | 0.139169E+12 | 66259.13 | 14-NOV-17:00 | 63970.49 | 0.00 |
December | 0.00 | 0.00 | 0.184790E+12 | 0.184785E+12 | 80279.76 | 26-DEC-17:20 | 80279.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147854E+13 | 0.147278E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.422278E+11 | 0.421960E+11 | 26794.72 | 26794.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204438E+12 | 0.202918E+12 | 84609.74 | 80660.64 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.334418E+10 | 0.334124E+10 | 2716.42 | 24-JAN-17:00 | 2716.42 | 0.00 |
February | 0.00 | 0.00 | 0.706680E+10 | 0.702415E+10 | 4376.43 | 22-FEB-17:00 | 4320.71 | 0.00 |
March | 0.00 | 0.00 | 0.137626E+11 | 0.137512E+11 | 7057.04 | 31-MAR-23:20 | 7057.04 | 0.00 |
April | 0.00 | 0.00 | 0.192145E+11 | 0.192145E+11 | 8138.87 | 26-APR-18:00 | 8138.87 | 0.00 |
May | 0.00 | 0.00 | 0.605170E+10 | 0.605170E+10 | 3984.01 | 31-MAY-24:00 | 3984.01 | 0.00 |
June | 0.00 | 0.00 | 0.110017E+11 | 0.110004E+11 | 5837.80 | 30-JUN-23:45 | 5837.80 | 0.00 |
July | 0.00 | 0.00 | 0.162173E+11 | 0.160681E+11 | 7652.98 | 31-JUL-23:55 | 7641.19 | 0.00 |
August | 0.00 | 0.00 | 0.206260E+11 | 0.204726E+11 | 8581.45 | 28-AUG-16:05 | 7990.85 | 0.00 |
September | 0.00 | 0.00 | 0.605604E+10 | 0.591965E+10 | 4001.80 | 30-SEP-24:00 | 4001.80 | 0.00 |
October | 0.00 | 0.00 | 0.989213E+10 | 0.986206E+10 | 5276.62 | 31-OCT-23:50 | 5276.62 | 0.00 |
November | 0.00 | 0.00 | 0.131507E+11 | 0.131021E+11 | 6652.92 | 14-NOV-17:00 | 6423.37 | 0.00 |
December | 0.00 | 0.00 | 0.172034E+11 | 0.172030E+11 | 8089.80 | 26-DEC-17:00 | 8089.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143587E+12 | 0.143011E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.334418E+10 | 0.334124E+10 | 2716.42 | 2716.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206260E+11 | 0.204726E+11 | 8581.45 | 8138.87 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4178.27 | 1018175.55 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4316.03 | 1196696.75 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3479.88 | 894550.39 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.60 | 4369.71 | 21-APR-05:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 529.76 | 186349.45 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2360.55 | 862733.26 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12493.56 | 1136676.73 | 07-DEC-05:01 |
Annual Sum or Average | 0.00 | 2282.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 12493.56 | 1196696.75 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 177786.93 | 1490453.52 | 31-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44562.10 | 662861.36 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 175994.12 | 1752272.75 | 20-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 484997.79 | 1763269.26 | 10-APR-17:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 601876.94 | 1758727.02 | 23-MAY-18:10 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 813148.02 | 2076000.69 | 19-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 773782.69 | 3669164.62 | 18-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 794563.64 | 2145912.68 | 01-AUG-05:05 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 674980.80 | 2097616.47 | 05-SEP-07:50 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 380164.14 | 1781559.97 | 03-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 190845.88 | 1603501.00 | 01-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88078.23 | 1162221.86 | 22-DEC-15:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 435415.24 | 0.00 | ||||
Minimum of Months | 44562.10 | 662861.36 | 0.00 | 0.00 | ||
Maximum of Months | 813148.02 | 3669164.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 175422.71 | 1374440.50 | 31-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 43026.14 | 658364.82 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 173173.87 | 1572852.76 | 20-MAR-14:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 476321.40 | 2137853.43 | 25-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 592094.84 | 2257912.60 | 08-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 801379.74 | 2844818.99 | 09-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 764525.05 | 4902676.58 | 15-JUL-04:12 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 786301.51 | 4373387.07 | 04-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 667749.33 | 4591065.31 | 08-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 374856.05 | 4127232.06 | 03-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 187857.50 | 1775206.69 | 13-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 86400.29 | 1158959.76 | 22-DEC-15:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 429424.59 | 0.00 | ||||
Minimum of Months | 43026.14 | 658364.82 | 0.00 | 0.00 | ||
Maximum of Months | 801379.74 | 4902676.58 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 109519.72 | 885663.71 | 31-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 66942.23 | 458300.92 | 18-FEB-14:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 302808.74 | 1337055.86 | 16-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 987411.68 | 1807304.04 | 14-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 644026.76 | 1332160.83 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1195070.64 | 1882736.91 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1446271.57 | 2022110.13 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1596472.10 | 2176545.60 | 25-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 751989.77 | 1413741.92 | 08-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 487573.39 | 1552162.31 | 01-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 302669.55 | 1344592.78 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 279710.49 | 1290070.26 | 25-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 684510.95 | 0.00 | ||||
Minimum of Months | 66942.23 | 458300.92 | 0.00 | 0.00 | ||
Maximum of Months | 1596472.10 | 2176545.60 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13396.44 | 44338.07 | 23-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13349.27 | 44243.62 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13472.36 | 43016.00 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11814.22 | 39994.31 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 11166.06 | 36789.58 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10551.51 | 33470.67 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 9445.25 | 31256.18 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10332.97 | 32153.25 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 10382.96 | 34738.23 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 11268.45 | 38400.46 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12383.74 | 41598.72 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12738.11 | 43715.67 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11682.63 | ||||
Minimum of Months | 0.00 | 0.00 | 9445.25 | 31256.18 | ||
Maximum of Months | 0.00 | 0.00 | 13472.36 | 44338.07 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 205382.36 | 2489034.50 | 31-JAN-15:30 | 835.99 | 109073.22 | 13-JAN-06:50 |
February | 50034.52 | 769876.67 | 22-FEB-16:00 | 1506.66 | 112105.45 | 09-FEB-07:00 |
March | 203789.14 | 2485052.52 | 20-MAR-15:10 | 1460.66 | 128028.46 | 25-MAR-06:00 |
April | 599219.25 | 2679502.06 | 24-APR-15:30 | 2288.67 | 107889.60 | 04-APR-05:50 |
May | 776916.80 | 2719341.08 | 18-MAY-14:20 | 260.94 | 73045.35 | 01-MAY-06:50 |
June | 1132993.73 | 4352791.22 | 17-JUN-15:50 | 236.28 | 62042.18 | 21-JUN-01:40 |
July | 1426102.40 | 5511110.22 | 18-JUL-05:05 | 185.87 | 62378.55 | 02-JUL-01:00 |
August | 1460531.10 | 5036426.09 | 16-AUG-11:00 | 262.65 | 61065.58 | 24-AUG-04:10 |
September | 1151345.87 | 5163556.75 | 01-SEP-12:20 | 6.37 | 9510.42 | 16-SEP-23:10 |
October | 525401.09 | 4056311.25 | 03-OCT-09:10 | 872.39 | 123856.53 | 25-OCT-08:20 |
November | 225266.34 | 2601646.33 | 01-NOV-14:50 | 1082.03 | 107884.57 | 28-NOV-20:00 |
December | 100911.08 | 1329229.38 | 22-DEC-15:50 | 1651.97 | 133075.02 | 14-DEC-06:40 |
Annual Sum or Average | 658454.18 | 882.28 | ||||
Minimum of Months | 50034.52 | 769876.67 | 6.37 | 9510.42 | ||
Maximum of Months | 1460531.10 | 5511110.22 | 2288.67 | 133075.02 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175953E+11 | 0.89 | 11252.49 | 01-JAN-00:25 | 1.52 |
February | 0.152158E+11 | 0.85 | 11252.49 | 01-FEB-05:12 | 1.52 |
March | 0.175809E+11 | 0.89 | 11252.49 | 01-MAR-05:12 | 1.51 |
April | 0.168098E+11 | 0.88 | 11252.49 | 01-APR-04:12 | 1.52 |
May | 0.174876E+11 | 0.88 | 11252.49 | 01-MAY-00:30 | 1.53 |
June | 0.177007E+11 | 0.92 | 11252.49 | 01-JUN-04:12 | 1.52 |
July | 0.187220E+11 | 0.94 | 11252.49 | 01-JUL-04:12 | 1.53 |
August | 0.201400E+11 | 1.01 | 11252.49 | 01-AUG-03:02 | 1.50 |
September | 0.188906E+11 | 0.98 | 11252.49 | 01-SEP-03:02 | 1.51 |
October | 0.191934E+11 | 0.97 | 11252.49 | 01-OCT-09:00 | 1.52 |
November | 0.182213E+11 | 0.95 | 11252.49 | 01-NOV-04:12 | 1.51 |
December | 0.183544E+11 | 0.93 | 11252.49 | 01-DEC-05:12 | 1.52 |
Annual Sum or Average | 0.215912E+12 | 0.92 | |||
Minimum of Months | 0.152158E+11 | 0.85 | 11252.49 | 1.50 | |
Maximum of Months | 0.201400E+11 | 1.01 | 11252.49 | 1.53 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.676978E+10 | 0.41 | 12930.95 | 17-JAN-16:50 | 1.32 |
February | 0.598829E+10 | 0.40 | 12385.61 | 21-FEB-15:40 | 1.27 |
March | 0.883136E+10 | 0.48 | 15499.29 | 20-MAR-14:40 | 1.46 |
April | 0.138838E+11 | 0.70 | 24161.96 | 15-APR-05:02 | 1.93 |
May | 0.127930E+11 | 0.61 | 24161.96 | 08-MAY-04:12 | 1.94 |
June | 0.159959E+11 | 0.77 | 24161.96 | 01-JUN-04:12 | 1.93 |
July | 0.158921E+11 | 0.75 | 24161.96 | 05-JUL-05:02 | 1.94 |
August | 0.190813E+11 | 0.84 | 24161.96 | 09-AUG-05:03 | 1.92 |
September | 0.121913E+11 | 0.61 | 24161.96 | 05-SEP-05:02 | 1.92 |
October | 0.101172E+11 | 0.52 | 24161.96 | 04-OCT-04:12 | 1.92 |
November | 0.853098E+10 | 0.47 | 16495.36 | 20-NOV-16:50 | 1.52 |
December | 0.764489E+10 | 0.44 | 16324.94 | 26-DEC-16:50 | 1.52 |
Annual Sum or Average | 0.137720E+12 | 0.59 | |||
Minimum of Months | 0.598829E+10 | 0.40 | 12385.61 | 1.27 | |
Maximum of Months | 0.190813E+11 | 0.84 | 24161.96 | 1.94 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.473107E+11 | 0.36 | 99199.87 | 23-JAN-06:03 | 1.15 |
February | 0.394339E+11 | 0.34 | 110470.45 | 28-FEB-06:02 | 1.23 |
March | 0.545730E+11 | 0.39 | 123682.02 | 28-MAR-05:02 | 1.33 |
April | 0.908478E+11 | 0.52 | 227741.86 | 15-APR-05:02 | 1.93 |
May | 0.109559E+12 | 0.57 | 227741.86 | 08-MAY-04:12 | 1.94 |
June | 0.134380E+12 | 0.69 | 227741.86 | 02-JUN-04:11 | 1.94 |
July | 0.119717E+12 | 0.62 | 227741.86 | 05-JUL-04:11 | 1.94 |
August | 0.126117E+12 | 0.63 | 227741.86 | 04-AUG-05:03 | 1.92 |
September | 0.100180E+12 | 0.54 | 227741.86 | 02-SEP-03:02 | 1.91 |
October | 0.712120E+11 | 0.44 | 227741.86 | 02-OCT-05:02 | 1.92 |
November | 0.510516E+11 | 0.37 | 106578.90 | 02-NOV-15:50 | 1.20 |
December | 0.425268E+11 | 0.34 | 129425.22 | 14-DEC-06:02 | 1.36 |
Annual Sum or Average | 0.986909E+12 | 0.49 | |||
Minimum of Months | 0.394339E+11 | 0.34 | 99199.87 | 1.15 | |
Maximum of Months | 0.134380E+12 | 0.69 | 227741.86 | 1.94 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.418429E+10 | 0.34 | 8334.89 | 31-JAN-16:30 | 0.97 |
February | 0.329455E+10 | 0.31 | 7189.94 | 22-FEB-16:30 | 0.89 |
March | 0.458192E+10 | 0.35 | 11105.85 | 16-MAR-15:30 | 1.15 |
April | 0.878987E+10 | 0.48 | 18370.88 | 15-APR-05:02 | 1.56 |
May | 0.109728E+11 | 0.54 | 24833.93 | 08-MAY-04:12 | 1.90 |
June | 0.146088E+11 | 0.68 | 25695.99 | 02-JUN-04:11 | 1.94 |
July | 0.128192E+11 | 0.61 | 25695.99 | 15-JUL-04:12 | 1.92 |
August | 0.132899E+11 | 0.62 | 25695.99 | 11-AUG-03:02 | 1.92 |
September | 0.101245E+11 | 0.52 | 24281.86 | 13-SEP-04:11 | 1.85 |
October | 0.645975E+10 | 0.40 | 23131.87 | 02-OCT-05:02 | 1.80 |
November | 0.430758E+10 | 0.34 | 10427.87 | 02-NOV-15:40 | 1.10 |
December | 0.361837E+10 | 0.32 | 7414.68 | 22-DEC-16:40 | 0.91 |
Annual Sum or Average | 0.970515E+11 | 0.46 | |||
Minimum of Months | 0.329455E+10 | 0.31 | 7189.94 | 0.89 | |
Maximum of Months | 0.146088E+11 | 0.68 | 25695.99 | 1.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104124E+12 | 1.49 | 38875.40 | 01-JAN-00:05 | 1.48 |
February | 0.940474E+11 | 1.48 | 38875.40 | 01-FEB-00:10 | 1.49 |
March | 0.104124E+12 | 1.49 | 38875.40 | 01-MAR-00:10 | 1.48 |
April | 0.100765E+12 | 1.49 | 38875.40 | 01-APR-00:10 | 1.49 |
May | 0.104124E+12 | 1.49 | 38875.40 | 01-MAY-00:03 | 1.49 |
June | 0.100765E+12 | 1.48 | 38875.40 | 01-JUN-00:10 | 1.49 |
July | 0.104124E+12 | 1.48 | 38875.40 | 01-JUL-00:03 | 1.48 |
August | 0.104124E+12 | 1.47 | 38875.40 | 01-AUG-00:03 | 1.48 |
September | 0.100765E+12 | 1.47 | 38875.40 | 01-SEP-00:03 | 1.48 |
October | 0.104124E+12 | 1.49 | 38875.40 | 01-OCT-00:05 | 1.48 |
November | 0.100765E+12 | 1.49 | 38875.40 | 01-NOV-00:10 | 1.49 |
December | 0.104124E+12 | 1.49 | 38875.40 | 01-DEC-00:10 | 1.49 |
Annual Sum or Average | 0.122597E+13 | 1.48 | |||
Minimum of Months | 0.940474E+11 | 1.47 | 38875.40 | 1.48 | |
Maximum of Months | 0.104124E+12 | 1.49 | 38875.40 | 1.49 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158168E+10 | 1.01 | 590.53 | 01-JAN-00:05 | 1.01 |
February | 0.142861E+10 | 1.01 | 590.53 | 01-FEB-00:20 | 1.01 |
March | 0.158168E+10 | 1.01 | 590.53 | 01-MAR-00:10 | 1.01 |
April | 0.153066E+10 | 1.01 | 590.53 | 01-APR-00:10 | 1.01 |
May | 0.158168E+10 | 1.01 | 590.53 | 01-MAY-00:03 | 1.01 |
June | 0.153066E+10 | 1.01 | 590.53 | 01-JUN-00:10 | 1.01 |
July | 0.158168E+10 | 1.00 | 590.53 | 01-JUL-00:03 | 1.01 |
August | 0.158168E+10 | 1.00 | 590.53 | 01-AUG-00:03 | 1.00 |
September | 0.153066E+10 | 1.00 | 590.53 | 01-SEP-00:03 | 1.00 |
October | 0.158168E+10 | 1.01 | 590.53 | 01-OCT-00:05 | 1.01 |
November | 0.153066E+10 | 1.01 | 590.53 | 01-NOV-00:10 | 1.01 |
December | 0.158168E+10 | 1.01 | 590.53 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.186230E+11 | 1.01 | |||
Minimum of Months | 0.142861E+10 | 1.00 | 590.53 | 1.00 | |
Maximum of Months | 0.158168E+10 | 1.01 | 590.53 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150867E+11 | 1.01 | 5632.72 | 01-JAN-00:05 | 1.01 |
February | 0.136267E+11 | 1.01 | 5632.72 | 01-FEB-00:10 | 1.01 |
March | 0.150867E+11 | 1.01 | 5632.72 | 01-MAR-00:10 | 1.01 |
April | 0.146000E+11 | 1.01 | 5632.72 | 01-APR-00:10 | 1.01 |
May | 0.150867E+11 | 1.01 | 5632.72 | 01-MAY-00:03 | 1.01 |
June | 0.146000E+11 | 1.01 | 5632.72 | 01-JUN-00:10 | 1.01 |
July | 0.150867E+11 | 1.00 | 5632.72 | 01-JUL-00:03 | 1.01 |
August | 0.150867E+11 | 1.00 | 5632.72 | 01-AUG-00:03 | 1.00 |
September | 0.146000E+11 | 1.00 | 5632.72 | 01-SEP-00:03 | 1.00 |
October | 0.150867E+11 | 1.01 | 5632.72 | 01-OCT-00:05 | 1.01 |
November | 0.146000E+11 | 1.01 | 5632.72 | 01-NOV-00:10 | 1.01 |
December | 0.150867E+11 | 1.01 | 5632.72 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.177634E+12 | 1.01 | |||
Minimum of Months | 0.136267E+11 | 1.00 | 5632.72 | 1.00 | |
Maximum of Months | 0.150867E+11 | 1.01 | 5632.72 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154276E+10 | 1.01 | 576.00 | 01-JAN-00:05 | 1.00 |
February | 0.139346E+10 | 1.01 | 576.00 | 01-FEB-00:10 | 1.01 |
March | 0.154276E+10 | 1.01 | 576.00 | 01-MAR-00:10 | 1.01 |
April | 0.149299E+10 | 1.01 | 576.00 | 01-APR-00:10 | 1.01 |
May | 0.154276E+10 | 1.01 | 576.00 | 01-MAY-00:03 | 1.01 |
June | 0.149299E+10 | 1.01 | 576.00 | 01-JUN-00:10 | 1.01 |
July | 0.154276E+10 | 1.00 | 576.00 | 01-JUL-00:03 | 1.01 |
August | 0.154276E+10 | 1.00 | 576.00 | 01-AUG-00:03 | 1.00 |
September | 0.149299E+10 | 1.00 | 576.00 | 01-SEP-00:03 | 1.00 |
October | 0.154276E+10 | 1.01 | 576.00 | 01-OCT-00:05 | 1.01 |
November | 0.149299E+10 | 1.01 | 576.00 | 01-NOV-00:10 | 1.01 |
December | 0.154276E+10 | 1.01 | 576.00 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.181647E+11 | 1.01 | |||
Minimum of Months | 0.139346E+10 | 1.00 | 576.00 | 1.00 | |
Maximum of Months | 0.154276E+10 | 1.01 | 576.00 | 1.01 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 47363719.29 | 42627347.36 | 3373.89 | 02-JAN-06:01 | 3036.50 | 3036.50 | 43.13 | 6.27 |
February | 42031245.23 | 37828120.70 | 3349.96 | 13-FEB-06:02 | 3014.97 | 3014.97 | 35.61 | 6.17 |
March | 38080518.52 | 34272466.67 | 3107.47 | 27-MAR-05:03 | 2796.72 | 2796.72 | 40.83 | 5.20 |
April | 121050.26 | 108945.23 | 17.56 | 21-APR-05:50 | 15.80 | 15.80 | 23.69 | 0.02 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 23.45 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 23.45 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 23.45 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 23.45 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 23.45 | 0.00 |
October | 5572816.52 | 5015534.87 | 711.89 | 26-OCT-05:02 | 640.70 | 640.70 | 24.80 | 0.78 |
November | 25246099.10 | 22721489.19 | 3063.27 | 24-NOV-06:03 | 2756.94 | 2756.94 | 41.13 | 5.05 |
December | 0.141867E+09 | 0.127680E+09 | 3372.36 | 18-DEC-06:02 | 3035.12 | 3035.12 | 42.11 | 6.26 |
Annual Sum or Average | 0.300282E+09 | 0.270254E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 | 0.00 | |
Maximum of Months | 0.141867E+09 | 0.127680E+09 | 3373.89 | 3036.50 | 3036.50 | 43.13 | 6.27 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.153812E+09 | 0.138431E+09 | 910.90 | 31-JAN-15:20 | 819.81 | 819.81 | 7.52 | 30.92 |
February | 26906416.40 | 24215774.76 | 376.41 | 16-FEB-13:30 | 338.77 | 338.77 | 6.70 | 20.14 |
March | 0.171486E+09 | 0.154337E+09 | 3044.62 | 20-MAR-14:40 | 2740.15 | 2740.15 | 8.14 | 53.12 |
April | 0.433288E+09 | 0.389959E+09 | 2027.43 | 25-APR-05:03 | 1824.69 | 1824.69 | 6.70 | 44.49 |
May | 0.585769E+09 | 0.527192E+09 | 2003.41 | 11-MAY-05:02 | 1803.07 | 1803.07 | 6.70 | 44.25 |
June | 0.129066E+10 | 0.116159E+10 | 7599.25 | 19-JUN-14:30 | 6839.32 | 6839.32 | 6.72 | 77.97 |
July | 0.134582E+10 | 0.121124E+10 | 18139.36 | 10-JUL-05:02 | 16325.42 | 16325.42 | 9.20 | 110.44 |
August | 0.158090E+10 | 0.142281E+10 | 18139.36 | 02-AUG-05:03 | 16325.42 | 16325.42 | 9.46 | 110.44 |
September | 0.137775E+10 | 0.123997E+10 | 18139.36 | 05-SEP-05:02 | 16325.42 | 16325.42 | 9.37 | 110.44 |
October | 0.700587E+09 | 0.630529E+09 | 14655.64 | 02-OCT-05:02 | 13190.08 | 13190.08 | 8.54 | 101.53 |
November | 0.230254E+09 | 0.207229E+09 | 3311.53 | 02-NOV-13:30 | 2980.38 | 2980.38 | 7.34 | 55.08 |
December | 62018700.27 | 55816830.25 | 727.84 | 22-DEC-15:40 | 655.06 | 655.06 | 6.71 | 27.81 |
Annual Sum or Average | 0.795924E+10 | 0.716332E+10 | ||||||
Minimum of Months | 26906416.40 | 24215774.76 | 376.41 | 338.77 | 338.77 | 6.70 | 20.14 | |
Maximum of Months | 0.158090E+10 | 0.142281E+10 | 18139.36 | 16325.42 | 16325.42 | 9.46 | 110.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.684368E+10 | 0.615932E+10 | 6242.42 | 01-JAN-14:52 | 5618.17 | 5618.17 | 6.72 | 55.22 |
February | 0.418168E+10 | 0.376351E+10 | 6242.42 | 01-FEB-12:30 | 5618.17 | 5618.17 | 6.72 | 55.22 |
March | 0.766893E+10 | 0.690204E+10 | 6242.42 | 01-MAR-05:12 | 5618.17 | 5618.17 | 6.92 | 55.22 |
April | 0.127675E+11 | 0.114907E+11 | 6242.42 | 01-APR-04:12 | 5618.17 | 5618.17 | 7.12 | 55.22 |
May | 0.119249E+11 | 0.107324E+11 | 6242.42 | 01-MAY-00:15 | 5618.17 | 5618.17 | 6.79 | 55.22 |
June | 0.144759E+11 | 0.130283E+11 | 6242.42 | 01-JUN-00:12 | 5618.17 | 5618.17 | 6.89 | 55.22 |
July | 0.152809E+11 | 0.137528E+11 | 6242.42 | 01-JUL-00:03 | 5618.17 | 5618.17 | 8.25 | 55.22 |
August | 0.154928E+11 | 0.139435E+11 | 6242.42 | 01-AUG-00:03 | 5618.17 | 5618.17 | 6.98 | 55.22 |
September | 0.120639E+11 | 0.108575E+11 | 6242.42 | 01-SEP-00:03 | 5618.17 | 5618.17 | 6.88 | 55.22 |
October | 0.981912E+10 | 0.883721E+10 | 6242.42 | 01-OCT-00:05 | 5618.17 | 5618.17 | 6.95 | 55.22 |
November | 0.723384E+10 | 0.651045E+10 | 6242.42 | 01-NOV-04:12 | 5618.17 | 5618.17 | 8.71 | 55.22 |
December | 0.518358E+10 | 0.466522E+10 | 6242.42 | 01-DEC-06:02 | 5618.17 | 5618.17 | 6.82 | 55.22 |
Annual Sum or Average | 0.122937E+12 | 0.110643E+12 | ||||||
Minimum of Months | 0.418168E+10 | 0.376351E+10 | 6242.42 | 5618.17 | 5618.17 | 6.72 | 55.22 | |
Maximum of Months | 0.154928E+11 | 0.139435E+11 | 6242.42 | 5618.17 | 5618.17 | 8.71 | 55.22 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 74908985.08 | 67418086.57 | 6242.42 | 27-JAN-15:40 | 5618.17 | 5618.17 | 11.99 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.168545E+09 | 0.151691E+09 | 6242.42 | 10-MAR-16:10 | 5618.17 | 5618.17 | 12.28 | 27.61 |
April | 0.265740E+10 | 0.239166E+10 | 6242.42 | 03-APR-10:10 | 5618.17 | 5618.17 | 11.87 | 27.61 |
May | 0.414621E+10 | 0.373159E+10 | 6242.42 | 01-MAY-11:00 | 5618.17 | 5618.17 | 11.86 | 27.61 |
June | 0.611707E+10 | 0.550536E+10 | 6242.42 | 01-JUN-07:30 | 5618.17 | 5618.17 | 11.92 | 27.61 |
July | 0.535566E+10 | 0.482009E+10 | 6242.42 | 01-JUL-13:50 | 5618.17 | 5618.17 | 11.70 | 27.61 |
August | 0.563715E+10 | 0.507344E+10 | 6242.42 | 01-AUG-05:03 | 5618.17 | 5618.17 | 13.30 | 27.61 |
September | 0.434797E+10 | 0.391317E+10 | 6242.42 | 01-SEP-05:03 | 5618.17 | 5618.17 | 12.58 | 27.61 |
October | 0.190231E+10 | 0.171208E+10 | 6242.42 | 02-OCT-07:50 | 5618.17 | 5618.17 | 12.18 | 27.61 |
November | 0.292145E+09 | 0.262931E+09 | 6242.42 | 01-NOV-12:20 | 5618.17 | 5618.17 | 12.32 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.83 | 0.00 |
Annual Sum or Average | 0.306994E+11 | 0.276294E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.611707E+10 | 0.550536E+10 | 6242.42 | 5618.17 | 5618.17 | 13.30 | 27.61 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-JAN-00:05 | 3122.17 | 3122.17 | 18.64 | 14.49 |
February | 0.839239E+10 | 0.755315E+10 | 3469.08 | 01-FEB-00:10 | 3122.17 | 3122.17 | 19.55 | 14.49 |
March | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-MAR-00:10 | 3122.17 | 3122.17 | 19.97 | 14.49 |
April | 0.899185E+10 | 0.809266E+10 | 3469.08 | 01-APR-00:10 | 3122.17 | 3122.17 | 23.07 | 14.49 |
May | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-MAY-00:03 | 3122.17 | 3122.17 | 20.69 | 14.49 |
June | 0.899185E+10 | 0.809266E+10 | 3469.08 | 01-JUN-00:10 | 3122.17 | 3122.17 | 35.54 | 14.49 |
July | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-JUL-00:03 | 3122.17 | 3122.17 | 42.85 | 14.49 |
August | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-AUG-00:03 | 3122.17 | 3122.17 | 48.73 | 14.49 |
September | 0.899185E+10 | 0.809266E+10 | 3469.08 | 01-SEP-00:03 | 3122.17 | 3122.17 | 32.70 | 14.49 |
October | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-OCT-00:05 | 3122.17 | 3122.17 | 33.80 | 14.49 |
November | 0.899185E+10 | 0.809266E+10 | 3469.08 | 01-NOV-00:10 | 3122.17 | 3122.17 | 21.92 | 14.49 |
December | 0.929157E+10 | 0.836242E+10 | 3469.08 | 01-DEC-00:10 | 3122.17 | 3122.17 | 20.57 | 14.49 |
Annual Sum or Average | 0.109401E+12 | 0.984607E+11 | ||||||
Minimum of Months | 0.839239E+10 | 0.755315E+10 | 3469.08 | 3122.17 | 3122.17 | 18.64 | 14.49 | |
Maximum of Months | 0.929157E+10 | 0.836242E+10 | 3469.08 | 3122.17 | 3122.17 | 48.73 | 14.49 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.84 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.37 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.96 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.33 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.51 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.33 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.76 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.96 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.56 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.21 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.70 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.20 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.84 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.33 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.177165E+11 | 0.159449E+11 | 32315.29 | 31-JAN-15:30 | 29083.76 | 29083.76 | 25.66 | 130.52 |
February | 0.107923E+11 | 0.971311E+10 | 16136.10 | 22-FEB-16:00 | 14522.49 | 14522.49 | 23.92 | 65.26 |
March | 0.200094E+11 | 0.180085E+11 | 32315.09 | 20-MAR-15:10 | 29083.58 | 29083.58 | 25.66 | 130.52 |
April | 0.376885E+11 | 0.339197E+11 | 32324.75 | 24-APR-15:30 | 29092.28 | 29092.28 | 26.01 | 130.52 |
May | 0.385237E+11 | 0.346713E+11 | 32326.73 | 18-MAY-14:20 | 29094.06 | 29094.06 | 26.09 | 130.52 |
June | 0.513064E+11 | 0.461758E+11 | 32400.68 | 17-JUN-15:50 | 29160.62 | 29160.62 | 29.08 | 130.52 |
July | 0.515569E+11 | 0.464012E+11 | 32400.68 | 13-JUL-12:30 | 29160.62 | 29160.62 | 28.90 | 130.52 |
August | 0.531314E+11 | 0.478183E+11 | 32400.68 | 01-AUG-13:00 | 29160.62 | 29160.62 | 28.83 | 130.52 |
September | 0.405939E+11 | 0.365345E+11 | 32400.68 | 01-SEP-09:30 | 29160.62 | 29160.62 | 28.92 | 130.52 |
October | 0.294723E+11 | 0.265251E+11 | 32393.28 | 03-OCT-09:10 | 29153.95 | 29153.95 | 28.54 | 130.52 |
November | 0.190530E+11 | 0.171477E+11 | 32320.88 | 01-NOV-14:50 | 29088.80 | 29088.80 | 25.87 | 130.52 |
December | 0.133833E+11 | 0.120449E+11 | 16161.82 | 22-DEC-15:50 | 14545.64 | 14545.64 | 25.97 | 65.26 |
Annual Sum or Average | 0.383228E+12 | 0.344905E+12 | ||||||
Minimum of Months | 0.107923E+11 | 0.971311E+10 | 16136.10 | 14522.49 | 14522.49 | 23.92 | 65.26 | |
Maximum of Months | 0.531314E+11 | 0.478183E+11 | 32400.68 | 29160.62 | 29160.62 | 29.08 | 130.52 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31.01 | 82.00 | 4178.27 | 1018175.55 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 22.85 | 22.85 | 4316.03 | 1196696.75 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.87 | 24.87 | 3479.88 | 894550.39 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24.09 | 24.09 | 11.60 | 4369.71 | 21-APR-05:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 23.45 | 23.45 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.45 | 23.45 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 23.45 | 23.45 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.45 | 23.45 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.45 | 23.45 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 23.45 | 23.45 | 529.76 | 186349.45 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.60 | 21.60 | 2360.55 | 862733.26 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22.84 | 22.84 | 12493.56 | 1136676.73 | 07-DEC-05:01 |
Annual Sum or Average | 0.00 | 2282.57 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.60 | 21.60 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 31.01 | 82.00 | 12493.56 | 1196696.75 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 177786.93 | 1490453.52 | 31-JAN-15:20 | 13.15 | 8.35 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44562.10 | 662861.36 | 22-FEB-16:00 | 9.56 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 175994.12 | 1752272.75 | 20-MAR-14:20 | 10.49 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 484997.79 | 1763269.26 | 10-APR-17:50 | 10.51 | 8.12 | 0.00 | 0.00 | 01-APR-00:10 |
May | 601876.94 | 1758727.02 | 23-MAY-18:10 | 10.50 | 8.12 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 813148.02 | 2076000.69 | 19-JUN-14:20 | 11.19 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 773782.69 | 3669164.62 | 18-JUL-05:03 | 14.64 | 8.91 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 794563.64 | 2145912.68 | 01-AUG-05:05 | 11.34 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 674980.80 | 2097616.47 | 05-SEP-07:50 | 11.23 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 380164.14 | 1781559.97 | 03-OCT-11:00 | 10.55 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 190845.88 | 1603501.00 | 01-NOV-13:50 | 13.64 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88078.23 | 1162221.86 | 22-DEC-15:40 | 11.72 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 435415.24 | 0.00 | ||||||
Minimum of Months | 44562.10 | 662861.36 | 9.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 813148.02 | 3669164.62 | 14.64 | 8.91 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 175422.71 | 1374440.50 | 31-JAN-15:20 | 17.33 | 8.58 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 43026.14 | 658364.82 | 22-FEB-16:00 | 18.28 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 173173.87 | 1572852.76 | 20-MAR-14:40 | 13.77 | 8.88 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 476321.40 | 2137853.43 | 25-APR-05:03 | 18.19 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 592094.84 | 2257912.60 | 08-MAY-04:12 | 19.51 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 801379.74 | 2844818.99 | 09-JUN-05:02 | 19.02 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 764525.05 | 4902676.58 | 15-JUL-04:12 | 17.31 | 11.99 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 786301.51 | 4373387.07 | 04-AUG-05:03 | 16.16 | 11.42 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 667749.33 | 4591065.31 | 08-SEP-05:02 | 16.64 | 11.65 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 374856.05 | 4127232.06 | 03-OCT-04:12 | 16.43 | 11.12 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 187857.50 | 1775206.69 | 13-NOV-06:02 | 15.35 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 86400.29 | 1158959.76 | 22-DEC-15:40 | 16.66 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 429424.59 | 0.00 | ||||||
Minimum of Months | 43026.14 | 658364.82 | 13.77 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 801379.74 | 4902676.58 | 19.51 | 11.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 109519.72 | 885663.71 | 31-JAN-17:00 | 35.69 | 31.14 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 66942.23 | 458300.92 | 18-FEB-14:10 | 27.39 | 23.71 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 302808.74 | 1337055.86 | 16-MAR-16:00 | 44.33 | 33.82 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 987411.68 | 1807304.04 | 14-APR-16:10 | 53.18 | 40.93 | 0.00 | 0.00 | 01-APR-00:10 |
May | 644026.76 | 1332160.83 | 31-MAY-16:00 | 44.24 | 39.34 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1195070.64 | 1882736.91 | 28-JUN-16:00 | 54.59 | 46.11 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1446271.57 | 2022110.13 | 19-JUL-14:00 | 57.18 | 45.63 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1596472.10 | 2176545.60 | 25-AUG-16:10 | 60.04 | 47.25 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 751989.77 | 1413741.92 | 08-SEP-16:00 | 45.78 | 40.72 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 487573.39 | 1552162.31 | 01-OCT-13:40 | 48.39 | 40.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 302669.55 | 1344592.78 | 01-NOV-15:00 | 44.47 | 34.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 279710.49 | 1290070.26 | 25-DEC-16:00 | 43.44 | 31.63 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 684510.95 | 0.00 | ||||||
Minimum of Months | 66942.23 | 458300.92 | 27.39 | 23.71 | 0.00 | 0.00 | ||
Maximum of Months | 1596472.10 | 2176545.60 | 60.04 | 47.25 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.08 | 57.08 | 13396.44 | 44338.07 | 23-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.85 | 56.85 | 13349.27 | 44243.62 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.49 | 56.49 | 13472.36 | 43016.00 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.82 | 56.82 | 11814.22 | 39994.31 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.07 | 57.07 | 11166.06 | 36789.58 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.71 | 57.71 | 10551.51 | 33470.67 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.06 | 57.06 | 9445.25 | 31256.18 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.26 | 57.26 | 10332.97 | 32153.25 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.91 | 56.91 | 10382.96 | 34738.23 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 56.90 | 56.90 | 11268.45 | 38400.46 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.23 | 57.23 | 12383.74 | 41598.72 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.59 | 57.59 | 12738.11 | 43715.67 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11682.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.49 | 56.49 | 9445.25 | 31256.18 | ||
Maximum of Months | 0.00 | 0.00 | 57.71 | 57.71 | 13472.36 | 44338.07 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 205382.36 | 2489034.50 | 31-JAN-15:30 | 25.66 | 21.10 | 835.99 | 109073.22 | 13-JAN-06:50 |
February | 50034.52 | 769876.67 | 22-FEB-16:00 | 23.92 | 21.10 | 1506.66 | 112105.45 | 09-FEB-07:00 |
March | 203789.14 | 2485052.52 | 20-MAR-15:10 | 25.66 | 21.10 | 1460.66 | 128028.46 | 25-MAR-06:00 |
April | 599219.25 | 2679502.06 | 24-APR-15:30 | 26.01 | 21.10 | 2288.67 | 107889.60 | 04-APR-05:50 |
May | 776916.80 | 2719341.08 | 18-MAY-14:20 | 26.09 | 21.10 | 260.94 | 73045.35 | 01-MAY-06:50 |
June | 1132993.73 | 4352791.22 | 17-JUN-15:50 | 29.08 | 26.08 | 236.28 | 62042.18 | 21-JUN-01:40 |
July | 1426102.40 | 5511110.22 | 18-JUL-05:05 | 31.20 | 26.41 | 185.87 | 62378.55 | 02-JUL-01:00 |
August | 1460531.10 | 5036426.09 | 16-AUG-11:00 | 30.33 | 26.34 | 262.65 | 61065.58 | 24-AUG-04:10 |
September | 1151345.87 | 5163556.75 | 01-SEP-12:20 | 30.56 | 26.42 | 6.37 | 9510.42 | 16-SEP-23:10 |
October | 525401.09 | 4056311.25 | 03-OCT-09:10 | 28.54 | 24.97 | 872.39 | 123856.53 | 25-OCT-08:20 |
November | 225266.34 | 2601646.33 | 01-NOV-14:50 | 25.87 | 21.84 | 1082.03 | 107884.57 | 28-NOV-20:00 |
December | 100911.08 | 1329229.38 | 22-DEC-15:50 | 25.97 | 21.10 | 1651.97 | 133075.02 | 14-DEC-06:40 |
Annual Sum or Average | 658454.18 | 882.28 | ||||||
Minimum of Months | 50034.52 | 769876.67 | 23.92 | 21.10 | 6.37 | 9510.42 | ||
Maximum of Months | 1460531.10 | 5511110.22 | 31.20 | 26.42 | 2288.67 | 133075.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 2763674.86 | 0.00 | 0.427190E+11 | 0.676978E+10 | 0.00 | 0.00 |
February | 1464378.79 | 0.00 | 0.108491E+11 | 0.598829E+10 | 0.00 | 0.00 |
March | 21484154.87 | 0.00 | 0.465948E+11 | 0.883136E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.121909E+12 | 0.138838E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.133808E+12 | 0.127930E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.180225E+12 | 0.159959E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.188071E+12 | 0.158921E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.208819E+12 | 0.190813E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.149349E+12 | 0.121913E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.917162E+11 | 0.101172E+11 | 0.00 | 0.00 |
November | 652170.47 | 0.00 | 0.491170E+11 | 0.853098E+10 | 0.00 | 0.00 |
December | 0.185134E+09 | 0.00 | 0.245573E+11 | 0.764489E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.211499E+09 | 0.00 | 0.124773E+13 | 0.137720E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.108491E+11 | 0.598829E+10 | 0.00 | 0.00 |
Maximum of Months | 0.185134E+09 | 0.00 | 0.208819E+12 | 0.190813E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.775767E+10 | 0.00 | 0.355006E+12 | 0.473107E+11 | 0.00 | 0.00 |
February | 0.692770E+10 | 0.00 | 0.820809E+11 | 0.394339E+11 | 0.00 | 0.00 |
March | 0.676883E+10 | 0.00 | 0.346369E+12 | 0.545730E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.920911E+12 | 0.908478E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.120231E+13 | 0.109559E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159150E+13 | 0.134380E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.153652E+13 | 0.119717E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.156597E+13 | 0.126117E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.129702E+13 | 0.100180E+12 | 0.00 | 0.00 |
October | 0.764160E+09 | 0.00 | 0.750196E+12 | 0.712120E+11 | 0.00 | 0.00 |
November | 0.394258E+10 | 0.00 | 0.356260E+12 | 0.510516E+11 | 0.00 | 0.00 |
December | 0.255586E+11 | 0.00 | 0.174965E+12 | 0.425268E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.517196E+11 | 0.00 | 0.101791E+14 | 0.986909E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.820809E+11 | 0.394339E+11 | 0.00 | 0.00 |
Maximum of Months | 0.255586E+11 | 0.00 | 0.159150E+13 | 0.134380E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.356421E+10 | 0.00 | 0.322360E+11 | 0.418429E+10 | 0.00 | 0.00 |
February | 0.359582E+10 | 0.00 | 0.687685E+10 | 0.329455E+10 | 0.00 | 0.00 |
March | 0.261590E+10 | 0.00 | 0.336355E+11 | 0.458192E+10 | 0.00 | 0.00 |
April | 32936067.23 | 0.00 | 0.100270E+12 | 0.878987E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.132199E+12 | 0.109728E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.180600E+12 | 0.146088E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.173225E+12 | 0.128192E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.173708E+12 | 0.132899E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.140307E+12 | 0.101245E+11 | 0.00 | 0.00 |
October | 0.674534E+09 | 0.00 | 0.765938E+11 | 0.645975E+10 | 0.00 | 0.00 |
November | 0.222471E+10 | 0.00 | 0.322363E+11 | 0.430758E+10 | 0.00 | 0.00 |
December | 0.801784E+10 | 0.00 | 0.146221E+11 | 0.361837E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.207260E+11 | 0.00 | 0.109651E+13 | 0.970515E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.687685E+10 | 0.329455E+10 | 0.00 | 0.00 |
Maximum of Months | 0.801784E+10 | 0.00 | 0.180600E+12 | 0.146088E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.271330E+11 | 0.175953E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.451509E+10 | 0.152158E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.268149E+11 | 0.175809E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.643365E+11 | 0.168098E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.795072E+11 | 0.174876E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.962831E+11 | 0.177007E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102876E+12 | 0.187220E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.114697E+12 | 0.201400E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.979540E+11 | 0.188906E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.615179E+11 | 0.191934E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.318298E+11 | 0.182213E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.139275E+11 | 0.183544E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.721392E+12 | 0.215912E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.451509E+10 | 0.152158E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.114697E+12 | 0.201400E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.421337E+11 | 0.305465E+12 | 0.00 | 70.10 |
February | 0.00 | 0.00 | 0.160321E+11 | 0.192694E+12 | 0.00 | 34.52 |
March | 0.00 | 0.00 | 0.260112E+12 | 0.362470E+12 | 0.00 | 71.26 |
April | 0.00 | 0.00 | 0.925127E+12 | 0.608583E+12 | 0.00 | 94.77 |
May | 0.00 | 0.00 | 0.306627E+12 | 0.332406E+12 | 0.00 | 52.23 |
June | 0.00 | 0.00 | 0.735194E+12 | 0.382757E+12 | 0.00 | 25.05 |
July | 0.00 | 0.00 | 0.119699E+13 | 0.448606E+12 | 0.00 | 7.45 |
August | 0.00 | 0.00 | 0.144465E+13 | 0.524366E+12 | 0.00 | 15.88 |
September | 0.00 | 0.00 | 0.367451E+12 | 0.219947E+12 | 0.00 | 7.25 |
October | 0.00 | 0.00 | 0.343817E+12 | 0.353366E+12 | 0.00 | 58.46 |
November | 0.00 | 0.00 | 0.269860E+12 | 0.343038E+12 | 0.00 | 64.94 |
December | 0.00 | 0.00 | 0.271670E+12 | 0.436827E+12 | 0.00 | 97.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.617966E+13 | 0.451053E+13 | 0.00 | 599.58 |
Minimum of Months | 0.00 | 0.00 | 0.160321E+11 | 0.192694E+12 | 0.00 | 7.25 |
Maximum of Months | 0.00 | 0.00 | 0.144465E+13 | 0.608583E+12 | 0.00 | 97.69 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.706217E+10 | 0.310155E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.117477E+11 | 0.370022E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198778E+11 | 0.557436E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.266969E+11 | 0.792738E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.886203E+10 | 0.396058E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159367E+11 | 0.610114E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.231620E+11 | 0.789018E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.294886E+11 | 0.937069E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.870344E+10 | 0.377659E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.146059E+11 | 0.491801E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194610E+11 | 0.544599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.258253E+11 | 0.666461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211430E+12 | 0.684313E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.706217E+10 | 0.310155E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.294886E+11 | 0.937069E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.540892E+11 | 0.269480E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.997094E+11 | 0.330853E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180604E+12 | 0.516048E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.252639E+12 | 0.753385E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.824187E+11 | 0.372945E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151873E+12 | 0.581631E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220394E+12 | 0.751256E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278152E+12 | 0.888008E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.807108E+11 | 0.354897E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133116E+12 | 0.457087E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.175148E+12 | 0.500906E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.230570E+12 | 0.608663E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193943E+13 | 0.638516E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.540892E+11 | 0.269480E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278152E+12 | 0.888008E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.430859E+10 | 0.250717E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.880141E+10 | 0.312807E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172864E+11 | 0.506653E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.253390E+11 | 0.761750E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.829842E+10 | 0.378947E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154371E+11 | 0.592843E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223033E+11 | 0.762880E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280926E+11 | 0.900933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.817836E+10 | 0.361531E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128812E+11 | 0.453183E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165314E+11 | 0.487369E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.215230E+11 | 0.586229E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188981E+12 | 0.635584E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.430859E+10 | 0.250717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.280926E+11 | 0.900933E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.676978E+10 | 0.427190E+11 | 2763674.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598829E+10 | 0.108491E+11 | 1464378.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.883136E+10 | 0.465948E+11 | 21484154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138838E+11 | 0.121909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127930E+11 | 0.133808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159959E+11 | 0.180225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158921E+11 | 0.188071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190813E+11 | 0.208819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121913E+11 | 0.149349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101172E+11 | 0.917162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.853098E+10 | 0.491170E+11 | 652170.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.764489E+10 | 0.245573E+11 | 0.185134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137720E+12 | 0.124773E+13 | 0.211499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.598829E+10 | 0.108491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190813E+11 | 0.208819E+12 | 0.185134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.473107E+11 | 0.355006E+12 | 0.775767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394339E+11 | 0.820809E+11 | 0.692770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.545730E+11 | 0.346369E+12 | 0.676883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.908478E+11 | 0.920911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109559E+12 | 0.120231E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134380E+12 | 0.159150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119717E+12 | 0.153652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126117E+12 | 0.156597E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100180E+12 | 0.129702E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712120E+11 | 0.750196E+12 | 0.764160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510516E+11 | 0.356260E+12 | 0.394258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425268E+11 | 0.174965E+12 | 0.255586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986909E+12 | 0.101791E+14 | 0.517196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.394339E+11 | 0.820809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134380E+12 | 0.159150E+13 | 0.255586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.418429E+10 | 0.322360E+11 | 0.356421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329455E+10 | 0.687685E+10 | 0.359582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458192E+10 | 0.336355E+11 | 0.261590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878987E+10 | 0.100270E+12 | 32936067.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109728E+11 | 0.132199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146088E+11 | 0.180600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128192E+11 | 0.173225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132899E+11 | 0.173708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101245E+11 | 0.140307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645975E+10 | 0.765938E+11 | 0.674534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430758E+10 | 0.322363E+11 | 0.222471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361837E+10 | 0.146221E+11 | 0.801784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970515E+11 | 0.109651E+13 | 0.207260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329455E+10 | 0.687685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146088E+11 | 0.180600E+12 | 0.801784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175953E+11 | 0.271330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152158E+11 | 0.451509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175809E+11 | 0.268149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168098E+11 | 0.643365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174876E+11 | 0.795072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177007E+11 | 0.962831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187220E+11 | 0.102876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201400E+11 | 0.114697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188906E+11 | 0.979540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191934E+11 | 0.615179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182213E+11 | 0.318298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183544E+11 | 0.139275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215912E+12 | 0.721392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152158E+11 | 0.451509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201400E+11 | 0.114697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104124E+12 | 0.292249E+11 | 0.00 | 0.00 | 0.00 | 0.187588E+12 | 0.00 | 0.00 |
February | 0.940474E+11 | 0.101732E+11 | 0.00 | 0.00 | 0.00 | 0.923719E+11 | 0.00 | 0.00 |
March | 0.104124E+12 | 0.193312E+12 | 0.00 | 0.00 | 0.00 | 0.190689E+12 | 0.00 | 0.00 |
April | 0.100765E+12 | 0.672061E+12 | 0.00 | 0.00 | 0.00 | 0.253610E+12 | 0.00 | 0.00 |
May | 0.104124E+12 | 0.218752E+12 | 0.00 | 0.00 | 0.00 | 0.139778E+12 | 0.00 | 0.00 |
June | 0.100765E+12 | 0.520529E+12 | 0.00 | 0.00 | 0.00 | 0.670255E+11 | 0.00 | 0.00 |
July | 0.104124E+12 | 0.872548E+12 | 0.00 | 0.00 | 0.00 | 0.199462E+11 | 0.00 | 0.00 |
August | 0.104124E+12 | 0.106710E+13 | 0.00 | 0.00 | 0.00 | 0.425012E+11 | 0.00 | 0.00 |
September | 0.100765E+12 | 0.267762E+12 | 0.00 | 0.00 | 0.00 | 0.194056E+11 | 0.00 | 0.00 |
October | 0.104124E+12 | 0.251729E+12 | 0.00 | 0.00 | 0.00 | 0.156450E+12 | 0.00 | 0.00 |
November | 0.100765E+12 | 0.202148E+12 | 0.00 | 0.00 | 0.00 | 0.173778E+12 | 0.00 | 0.00 |
December | 0.104124E+12 | 0.201565E+12 | 0.00 | 0.00 | 0.00 | 0.261421E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.122597E+13 | 0.450690E+13 | 0.00 | 0.00 | 0.00 | 0.160456E+13 | 0.00 | 0.00 |
Minimum of Months | 0.940474E+11 | 0.101732E+11 | 0.00 | 0.00 | 0.00 | 0.194056E+11 | 0.00 | 0.00 |
Maximum of Months | 0.104124E+12 | 0.106710E+13 | 0.00 | 0.00 | 0.00 | 0.261421E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158168E+10 | 0.554230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142861E+10 | 0.947613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158168E+10 | 0.158852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153066E+10 | 0.203002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158168E+10 | 0.648312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153066E+10 | 0.113662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158168E+10 | 0.168535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158168E+10 | 0.216996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153066E+10 | 0.645751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158168E+10 | 0.112696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153066E+10 | 0.155456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158168E+10 | 0.207424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186230E+11 | 0.161621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142861E+10 | 0.554230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158168E+10 | 0.216996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150867E+11 | 0.422278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136267E+11 | 0.802507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150867E+11 | 0.144086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146000E+11 | 0.191901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150867E+11 | 0.602109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146000E+11 | 0.108310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150867E+11 | 0.160355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150867E+11 | 0.204438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146000E+11 | 0.598211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150867E+11 | 0.102494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146000E+11 | 0.139658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150867E+11 | 0.184790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177634E+12 | 0.147854E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136267E+11 | 0.422278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150867E+11 | 0.204438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154276E+10 | 0.334418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139346E+10 | 0.706680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154276E+10 | 0.137626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149299E+10 | 0.192145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154276E+10 | 0.605170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149299E+10 | 0.110017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154276E+10 | 0.162173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154276E+10 | 0.206260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149299E+10 | 0.605604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154276E+10 | 0.989213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149299E+10 | 0.131507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154276E+10 | 0.172034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181647E+11 | 0.143587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139346E+10 | 0.334418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154276E+10 | 0.206260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.676978E+10 | 2763674.86 | 0.427190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598829E+10 | 1464378.79 | 0.108491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.883136E+10 | 21484154.87 | 0.465948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138838E+11 | 0.00 | 0.121909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127930E+11 | 0.00 | 0.133808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159959E+11 | 0.00 | 0.180225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158921E+11 | 0.00 | 0.188071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190813E+11 | 0.00 | 0.208819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121913E+11 | 0.00 | 0.149349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101172E+11 | 0.00 | 0.917162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.853098E+10 | 652170.47 | 0.491170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.764489E+10 | 0.185134E+09 | 0.245573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137720E+12 | 0.211499E+09 | 0.124773E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.598829E+10 | 0.00 | 0.108491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190813E+11 | 0.185134E+09 | 0.208819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.473107E+11 | 0.775767E+10 | 0.355006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394339E+11 | 0.692770E+10 | 0.820809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.545730E+11 | 0.676883E+10 | 0.346369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.908478E+11 | 0.00 | 0.920911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109559E+12 | 0.00 | 0.120231E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134380E+12 | 0.00 | 0.159150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119717E+12 | 0.00 | 0.153652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126117E+12 | 0.00 | 0.156597E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100180E+12 | 0.00 | 0.129702E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712120E+11 | 0.764160E+09 | 0.750196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510516E+11 | 0.394258E+10 | 0.356260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425268E+11 | 0.255586E+11 | 0.174965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986909E+12 | 0.517196E+11 | 0.101791E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.394339E+11 | 0.00 | 0.820809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134380E+12 | 0.255586E+11 | 0.159150E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.418429E+10 | 0.356421E+10 | 0.322360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329455E+10 | 0.359582E+10 | 0.687685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458192E+10 | 0.261590E+10 | 0.336355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878987E+10 | 32936067.23 | 0.100270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109728E+11 | 0.00 | 0.132199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146088E+11 | 0.00 | 0.180600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128192E+11 | 0.00 | 0.173225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132899E+11 | 0.00 | 0.173708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101245E+11 | 0.00 | 0.140307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645975E+10 | 0.674534E+09 | 0.765938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.430758E+10 | 0.222471E+10 | 0.322363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.361837E+10 | 0.801784E+10 | 0.146221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.970515E+11 | 0.207260E+11 | 0.109651E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329455E+10 | 0.00 | 0.687685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146088E+11 | 0.801784E+10 | 0.180600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175953E+11 | 0.00 | 0.271330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152158E+11 | 0.00 | 0.451509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175809E+11 | 0.00 | 0.268149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168098E+11 | 0.00 | 0.643365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174876E+11 | 0.00 | 0.795072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177007E+11 | 0.00 | 0.962831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187220E+11 | 0.00 | 0.102876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201400E+11 | 0.00 | 0.114697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188906E+11 | 0.00 | 0.979540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191934E+11 | 0.00 | 0.615179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182213E+11 | 0.00 | 0.318298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183544E+11 | 0.00 | 0.139275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215912E+12 | 0.00 | 0.721392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152158E+11 | 0.00 | 0.451509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201400E+11 | 0.00 | 0.114697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104124E+12 | 0.00 | 0.421337E+11 | 0.00 | 0.129088E+11 | 0.00 | 0.00 | 0.00 | 0.188432E+12 | 0.00 | 0.00 | 0.00 |
February | 0.940474E+11 | 0.00 | 0.160321E+11 | 0.00 | 0.585889E+10 | 0.00 | 0.00 | 0.00 | 0.927877E+11 | 0.00 | 0.00 | 0.00 |
March | 0.104124E+12 | 0.00 | 0.260112E+12 | 0.00 | 0.667992E+11 | 0.00 | 0.00 | 0.00 | 0.191547E+12 | 0.00 | 0.00 | 0.00 |
April | 0.100765E+12 | 0.00 | 0.925127E+12 | 0.00 | 0.253066E+12 | 0.00 | 0.00 | 0.00 | 0.254752E+12 | 0.00 | 0.00 | 0.00 |
May | 0.104124E+12 | 0.00 | 0.306627E+12 | 0.00 | 0.878753E+11 | 0.00 | 0.00 | 0.00 | 0.140407E+12 | 0.00 | 0.00 | 0.00 |
June | 0.100765E+12 | 0.00 | 0.735194E+12 | 0.00 | 0.214665E+12 | 0.00 | 0.00 | 0.00 | 0.673272E+11 | 0.00 | 0.00 | 0.00 |
July | 0.104124E+12 | 0.00 | 0.119699E+13 | 0.00 | 0.324447E+12 | 0.00 | 0.00 | 0.00 | 0.200360E+11 | 0.00 | 0.00 | 0.00 |
August | 0.104124E+12 | 0.00 | 0.144465E+13 | 0.00 | 0.377549E+12 | 0.00 | 0.00 | 0.00 | 0.426925E+11 | 0.00 | 0.00 | 0.00 |
September | 0.100765E+12 | 0.00 | 0.367451E+12 | 0.00 | 0.996889E+11 | 0.00 | 0.00 | 0.00 | 0.194929E+11 | 0.00 | 0.00 | 0.00 |
October | 0.104124E+12 | 0.00 | 0.343817E+12 | 0.00 | 0.920881E+11 | 0.00 | 0.00 | 0.00 | 0.157154E+12 | 0.00 | 0.00 | 0.00 |
November | 0.100765E+12 | 0.00 | 0.269860E+12 | 0.00 | 0.677124E+11 | 0.00 | 0.00 | 0.00 | 0.174560E+12 | 0.00 | 0.00 | 0.00 |
December | 0.104124E+12 | 0.00 | 0.271670E+12 | 0.00 | 0.701058E+11 | 0.00 | 0.00 | 0.00 | 0.262597E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122597E+13 | 0.00 | 0.617966E+13 | 0.00 | 0.167276E+13 | 0.00 | 0.00 | 0.00 | 0.161179E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.940474E+11 | 0.00 | 0.160321E+11 | 0.00 | 0.585889E+10 | 0.00 | 0.00 | 0.00 | 0.194929E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104124E+12 | 0.00 | 0.144465E+13 | 0.00 | 0.377549E+12 | 0.00 | 0.00 | 0.00 | 0.262597E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158168E+10 | 0.00 | 0.706217E+10 | 0.00 | 0.151987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142861E+10 | 0.00 | 0.117477E+11 | 0.00 | 0.227161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158168E+10 | 0.00 | 0.198778E+11 | 0.00 | 0.399268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153066E+10 | 0.00 | 0.266969E+11 | 0.00 | 0.639672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158168E+10 | 0.00 | 0.886203E+10 | 0.00 | 0.237890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153066E+10 | 0.00 | 0.159367E+11 | 0.00 | 0.457048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158168E+10 | 0.00 | 0.231620E+11 | 0.00 | 0.630850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158168E+10 | 0.00 | 0.294886E+11 | 0.00 | 0.778901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153066E+10 | 0.00 | 0.870344E+10 | 0.00 | 0.224593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158168E+10 | 0.00 | 0.146059E+11 | 0.00 | 0.333633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153066E+10 | 0.00 | 0.194610E+11 | 0.00 | 0.391533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158168E+10 | 0.00 | 0.258253E+11 | 0.00 | 0.508293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186230E+11 | 0.00 | 0.211430E+12 | 0.00 | 0.498083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142861E+10 | 0.00 | 0.706217E+10 | 0.00 | 0.151987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158168E+10 | 0.00 | 0.294886E+11 | 0.00 | 0.778901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150867E+11 | 0.00 | 0.540892E+11 | 0.00 | 0.118613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136267E+11 | 0.00 | 0.997094E+11 | 0.00 | 0.194586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150867E+11 | 0.00 | 0.180604E+12 | 0.00 | 0.365181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146000E+11 | 0.00 | 0.252639E+12 | 0.00 | 0.607385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150867E+11 | 0.00 | 0.824187E+11 | 0.00 | 0.222078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146000E+11 | 0.00 | 0.151873E+12 | 0.00 | 0.435631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150867E+11 | 0.00 | 0.220394E+12 | 0.00 | 0.600389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150867E+11 | 0.00 | 0.278152E+12 | 0.00 | 0.737141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146000E+11 | 0.00 | 0.807108E+11 | 0.00 | 0.208897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150867E+11 | 0.00 | 0.133116E+12 | 0.00 | 0.306220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146000E+11 | 0.00 | 0.175148E+12 | 0.00 | 0.354906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150867E+11 | 0.00 | 0.230570E+12 | 0.00 | 0.457796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177634E+12 | 0.00 | 0.193943E+13 | 0.00 | 0.460882E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136267E+11 | 0.00 | 0.540892E+11 | 0.00 | 0.118613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150867E+11 | 0.00 | 0.278152E+12 | 0.00 | 0.737141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154276E+10 | 0.00 | 0.430859E+10 | 0.00 | 0.964411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139346E+10 | 0.00 | 0.880141E+10 | 0.00 | 0.173461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154276E+10 | 0.00 | 0.172864E+11 | 0.00 | 0.352378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149299E+10 | 0.00 | 0.253390E+11 | 0.00 | 0.612451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154276E+10 | 0.00 | 0.829842E+10 | 0.00 | 0.224672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149299E+10 | 0.00 | 0.154371E+11 | 0.00 | 0.443544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154276E+10 | 0.00 | 0.223033E+11 | 0.00 | 0.608604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154276E+10 | 0.00 | 0.280926E+11 | 0.00 | 0.746657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149299E+10 | 0.00 | 0.817836E+10 | 0.00 | 0.212232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154276E+10 | 0.00 | 0.128812E+11 | 0.00 | 0.298908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149299E+10 | 0.00 | 0.165314E+11 | 0.00 | 0.338070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154276E+10 | 0.00 | 0.215230E+11 | 0.00 | 0.431953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181647E+11 | 0.00 | 0.188981E+12 | 0.00 | 0.453937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139346E+10 | 0.00 | 0.430859E+10 | 0.00 | 0.964411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154276E+10 | 0.00 | 0.280926E+11 | 0.00 | 0.746657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222967E+09 | 24355333.30 | 0.00 | 0.131826E+09 | 210216.13 | 0.00 | 0.567006E+11 | 0.00 | 1.42 |
February | 0.206984E+09 | 0.00 | 0.00 | 0.107541E+09 | 0.00 | 0.00 | 0.668271E+11 | 0.00 | 1.39 |
March | 0.156547E+09 | 34899885.75 | 0.00 | 0.120437E+09 | 577742.92 | 0.00 | 0.574797E+11 | 0.00 | 1.50 |
April | 60869940.62 | 0.240867E+10 | 0.00 | 83442510.54 | 0.118004E+09 | 0.00 | 0.208986E+11 | 0.00 | 0.92 |
May | 27994318.95 | 0.506534E+10 | 0.00 | 54108019.25 | 0.108470E+09 | 0.00 | 0.106644E+11 | 0.00 | 0.71 |
June | 26203652.71 | 0.129464E+11 | 0.00 | 23594123.98 | 0.191555E+09 | 0.00 | 0.334410E+10 | 0.00 | 0.56 |
July | 8916463.20 | 0.130046E+11 | 0.00 | 14514608.70 | 0.242008E+09 | 0.00 | 0.158740E+10 | 0.00 | 0.47 |
August | 28172175.11 | 0.129085E+11 | 0.00 | 25100527.06 | 0.167471E+09 | 0.00 | 0.213504E+10 | 0.00 | 0.61 |
September | 56507031.65 | 0.930974E+10 | 0.00 | 43309307.14 | 0.179116E+09 | 0.00 | 0.584875E+10 | 0.00 | 0.76 |
October | 0.244428E+09 | 0.206362E+10 | 0.00 | 0.112302E+09 | 24228568.65 | 0.00 | 0.368332E+11 | 0.00 | 1.25 |
November | 0.348661E+09 | 76557073.25 | 0.00 | 0.147573E+09 | 0.00 | 0.00 | 0.603457E+11 | 0.00 | 1.55 |
December | 0.395043E+09 | 1358015.06 | 0.00 | 0.153238E+09 | 0.00 | 0.00 | 0.752333E+11 | 0.00 | 1.44 |
Annual Sum or Average | 0.178329E+10 | 0.578441E+11 | 0.00 | 0.101699E+10 | 0.103164E+10 | 0.00 | 0.397898E+12 | 0.00 | 1.05 |
Minimum of Months | 8916463.20 | 0.00 | 0.00 | 14514608.70 | 0.00 | 0.00 | 0.158740E+10 | 0.00 | 0.47 |
Maximum of Months | 0.395043E+09 | 0.130046E+11 | 0.00 | 0.153238E+09 | 0.242008E+09 | 0.00 | 0.752333E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.226658E+10 | 3246992.03 | 0.00 | 95189519.13 | 20498371.61 | 0.00 | 0.352216E+11 | 0.00 | 0.88 |
February | 0.211064E+10 | 0.00 | 0.00 | 85166788.39 | 0.00 | 0.00 | 0.471156E+11 | 0.00 | 0.94 |
March | 0.234098E+10 | 13326730.47 | 0.00 | 0.107392E+09 | 898390.22 | 0.00 | 0.427293E+11 | 0.00 | 1.03 |
April | 0.562921E+10 | 0.115033E+10 | 0.00 | 75186566.74 | 0.232016E+09 | 0.00 | 0.155752E+11 | 0.00 | 0.83 |
May | 0.104405E+10 | 0.251044E+10 | 0.00 | 48372792.94 | 0.178375E+09 | 0.00 | 0.712635E+10 | 0.00 | 0.51 |
June | 0.139605E+10 | 0.772890E+10 | 0.00 | 13393623.91 | 0.351473E+09 | 0.00 | 0.164395E+10 | 0.00 | 0.40 |
July | 0.813961E+09 | 0.985249E+10 | 0.00 | 5609575.40 | 0.153071E+10 | 0.00 | 0.570905E+09 | 0.00 | 0.37 |
August | 0.123284E+10 | 0.100212E+11 | 0.00 | 13499830.91 | 0.799496E+09 | 0.00 | 0.925483E+09 | 0.00 | 0.50 |
September | 0.317920E+09 | 0.624231E+10 | 0.00 | 29608575.84 | 0.987714E+09 | 0.00 | 0.303587E+10 | 0.00 | 0.49 |
October | 0.151791E+10 | 0.133303E+10 | 0.00 | 81743555.70 | 0.170774E+09 | 0.00 | 0.246456E+11 | 0.00 | 0.82 |
November | 0.242996E+10 | 64581614.86 | 0.00 | 0.109122E+09 | 25875685.85 | 0.00 | 0.397673E+11 | 0.00 | 1.02 |
December | 0.232343E+10 | 169363.83 | 0.00 | 0.112207E+09 | 1234647.11 | 0.00 | 0.515694E+11 | 0.00 | 0.95 |
Annual Sum or Average | 0.234235E+11 | 0.389201E+11 | 0.00 | 0.776492E+09 | 0.429906E+10 | 0.00 | 0.269927E+12 | 0.00 | 0.73 |
Minimum of Months | 0.317920E+09 | 0.00 | 0.00 | 5609575.40 | 0.00 | 0.00 | 0.570905E+09 | 0.00 | 0.37 |
Maximum of Months | 0.562921E+10 | 0.100212E+11 | 0.00 | 0.112207E+09 | 0.153071E+10 | 0.00 | 0.515694E+11 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367851E+11 | 5676324.34 | 0.00 | 0.568704E+09 | 0.272168E+09 | 0.00 | 0.223031E+12 | 0.00 | 0.66 |
February | 0.455851E+11 | 0.00 | 0.00 | 0.475720E+09 | 0.00 | 0.00 | 0.302691E+12 | 0.00 | 0.69 |
March | 0.256211E+11 | 0.125635E+09 | 0.00 | 0.666552E+09 | 21064042.42 | 0.00 | 0.286119E+12 | 0.00 | 0.75 |
April | 0.114513E+11 | 0.119040E+11 | 0.00 | 0.565705E+09 | 0.216376E+10 | 0.00 | 0.113291E+12 | 0.00 | 0.55 |
May | 0.547020E+10 | 0.263949E+11 | 0.00 | 0.403101E+09 | 0.143330E+10 | 0.00 | 0.570843E+11 | 0.00 | 0.44 |
June | 0.384485E+10 | 0.778348E+11 | 0.00 | 0.123306E+09 | 0.224975E+10 | 0.00 | 0.158395E+11 | 0.00 | 0.34 |
July | 0.222150E+10 | 0.939290E+11 | 0.00 | 46563657.14 | 0.435519E+10 | 0.00 | 0.488905E+10 | 0.00 | 0.30 |
August | 0.287952E+10 | 0.884199E+11 | 0.00 | 0.101396E+09 | 0.317611E+10 | 0.00 | 0.829847E+10 | 0.00 | 0.36 |
September | 0.188201E+10 | 0.599797E+11 | 0.00 | 0.239133E+09 | 0.589042E+10 | 0.00 | 0.245233E+11 | 0.00 | 0.41 |
October | 0.109917E+11 | 0.134246E+11 | 0.00 | 0.559854E+09 | 0.774243E+09 | 0.00 | 0.175303E+12 | 0.00 | 0.62 |
November | 0.321152E+11 | 0.333871E+09 | 0.00 | 0.631188E+09 | 0.358023E+09 | 0.00 | 0.247609E+12 | 0.00 | 0.70 |
December | 0.632017E+11 | 8762122.96 | 0.00 | 0.475206E+09 | 9456621.80 | 0.00 | 0.260213E+12 | 0.00 | 0.61 |
Annual Sum or Average | 0.242049E+12 | 0.372361E+12 | 0.00 | 0.485643E+10 | 0.207035E+11 | 0.00 | 0.171889E+13 | 0.00 | 0.53 |
Minimum of Months | 0.188201E+10 | 0.00 | 0.00 | 46563657.14 | 0.00 | 0.00 | 0.488905E+10 | 0.00 | 0.30 |
Maximum of Months | 0.632017E+11 | 0.939290E+11 | 0.00 | 0.666552E+09 | 0.589042E+10 | 0.00 | 0.302691E+12 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.909009E+10 | 0.00 | 0.00 | 29292307.19 | 29718926.72 | 86640067.39 | 0.115812E+11 | 0.00 | 0.59 |
February | 0.103636E+11 | 0.00 | 0.00 | 23930142.05 | 157144.90 | 48112797.29 | 0.177232E+11 | 0.00 | 0.58 |
March | 0.758900E+10 | 4489584.81 | 0.00 | 43433074.52 | 793435.88 | 9118061.72 | 0.177291E+11 | 0.00 | 0.66 |
April | 0.187845E+10 | 0.799497E+09 | 0.00 | 53666596.96 | 0.192903E+09 | 0.00 | 0.801707E+10 | 0.00 | 0.52 |
May | 0.636102E+09 | 0.196850E+10 | 0.00 | 41410419.43 | 0.131147E+09 | 0.00 | 0.393696E+10 | 0.00 | 0.40 |
June | 0.415209E+09 | 0.691613E+10 | 0.00 | 11057211.26 | 0.210233E+09 | 0.00 | 0.118241E+10 | 0.00 | 0.32 |
July | 0.181465E+09 | 0.863848E+10 | 0.00 | 4103849.81 | 0.444841E+09 | 0.00 | 0.381361E+09 | 0.00 | 0.29 |
August | 0.235089E+09 | 0.809765E+10 | 0.00 | 8839147.93 | 0.331322E+09 | 0.00 | 0.597291E+09 | 0.00 | 0.35 |
September | 0.215969E+09 | 0.533916E+10 | 0.00 | 23692878.39 | 0.662995E+09 | 0.00 | 0.185047E+10 | 0.00 | 0.39 |
October | 0.303098E+10 | 0.106317E+10 | 0.00 | 40600253.31 | 0.124486E+09 | 0.00 | 0.112169E+11 | 0.00 | 0.54 |
November | 0.788112E+10 | 18416309.18 | 0.00 | 37628534.64 | 35920103.14 | 8566029.27 | 0.149072E+11 | 0.00 | 0.63 |
December | 0.137885E+11 | 1952546.39 | 0.00 | 17260588.12 | 8546426.26 | 0.103443E+09 | 0.107075E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.553055E+11 | 0.328475E+11 | 0.00 | 0.334915E+09 | 0.217306E+10 | 0.255880E+09 | 0.998307E+11 | 0.00 | 0.48 |
Minimum of Months | 0.181465E+09 | 0.00 | 0.00 | 4103849.81 | 157144.90 | 0.00 | 0.381361E+09 | 0.00 | 0.29 |
Maximum of Months | 0.137885E+11 | 0.863848E+10 | 0.00 | 53666596.96 | 0.662995E+09 | 0.103443E+09 | 0.177291E+11 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199340E+10 | 367000.32 | 0.00 | 3672341.22 | 2740286.22 | 0.00 | 0.121634E+10 | 0.00 | 0.62 |
February | 0.208315E+10 | 0.00 | 0.00 | 2971333.53 | 0.00 | 0.00 | 0.205406E+10 | 0.00 | 0.64 |
March | 0.160733E+10 | 1906060.11 | 0.00 | 6409377.44 | 117734.19 | 0.00 | 0.237372E+10 | 0.00 | 0.78 |
April | 0.103384E+10 | 0.211776E+09 | 0.00 | 7269078.91 | 30405684.64 | 0.00 | 0.117710E+10 | 0.00 | 0.80 |
May | 0.227831E+09 | 0.527963E+09 | 0.00 | 5150600.73 | 23654932.97 | 0.00 | 0.700204E+09 | 0.00 | 0.60 |
June | 0.192842E+09 | 0.193382E+10 | 0.00 | 1909285.44 | 40684553.10 | 0.00 | 0.237216E+09 | 0.00 | 0.64 |
July | 0.107975E+09 | 0.210638E+10 | 0.00 | 789555.09 | 0.192623E+09 | 0.00 | 80089025.88 | 0.00 | 0.55 |
August | 0.164590E+09 | 0.193439E+10 | 0.00 | 1683682.82 | 98976807.03 | 0.00 | 0.114218E+09 | 0.00 | 0.64 |
September | 59566688.11 | 0.119582E+10 | 0.00 | 3365601.19 | 0.128377E+09 | 0.00 | 0.312593E+09 | 0.00 | 0.58 |
October | 0.840733E+09 | 0.223558E+09 | 0.00 | 5514080.13 | 22392264.33 | 0.00 | 0.143267E+10 | 0.00 | 0.67 |
November | 0.165413E+10 | 3032530.99 | 0.00 | 5903982.41 | 6020144.27 | 0.00 | 0.194800E+10 | 0.00 | 0.73 |
December | 0.239338E+10 | 18012.10 | 0.00 | 3126736.05 | 161800.71 | 860447.26 | 0.166883E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.123588E+11 | 0.813903E+10 | 0.00 | 47765654.95 | 0.546154E+09 | 860447.26 | 0.133150E+11 | 0.00 | 0.65 |
Minimum of Months | 59566688.11 | 0.00 | 0.00 | 789555.09 | 0.00 | 0.00 | 80089025.88 | 0.00 | 0.55 |
Maximum of Months | 0.239338E+10 | 0.210638E+10 | 0.00 | 7269078.91 | 0.192623E+09 | 860447.26 | 0.237372E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153681E+10 | 399028.63 | 0.00 | 5642385.84 | 2582317.86 | 0.00 | 0.219955E+10 | 0.00 | 1.04 |
February | 0.171237E+10 | 0.00 | 0.00 | 4241775.70 | 0.00 | 0.00 | 0.273403E+10 | 0.00 | 1.01 |
March | 0.142138E+10 | 1325779.07 | 0.00 | 6960534.02 | 113176.26 | 0.00 | 0.292343E+10 | 0.00 | 1.23 |
April | 0.101740E+10 | 0.162579E+09 | 0.00 | 9357847.20 | 29209072.53 | 0.00 | 0.171463E+10 | 0.00 | 1.41 |
May | 0.242933E+09 | 0.417406E+09 | 0.00 | 7076975.31 | 22610950.71 | 0.00 | 0.943815E+09 | 0.00 | 1.05 |
June | 0.196018E+09 | 0.153355E+10 | 0.00 | 1596982.16 | 42004529.30 | 0.00 | 0.190618E+09 | 0.00 | 0.88 |
July | 0.111337E+09 | 0.168962E+10 | 0.00 | 766129.72 | 0.200445E+09 | 0.00 | 62795648.99 | 0.00 | 0.73 |
August | 0.171730E+09 | 0.152755E+10 | 0.00 | 1090846.25 | 0.110386E+09 | 0.00 | 81863884.09 | 0.00 | 0.83 |
September | 85000348.50 | 0.104713E+10 | 0.00 | 2754173.32 | 0.114664E+09 | 0.00 | 0.288538E+09 | 0.00 | 0.83 |
October | 0.763024E+09 | 0.185476E+09 | 0.00 | 6591123.59 | 22162256.37 | 0.00 | 0.197045E+10 | 0.00 | 1.13 |
November | 0.153170E+10 | 906314.53 | 0.00 | 6093329.97 | 7417569.27 | 0.00 | 0.226675E+10 | 0.00 | 1.11 |
December | 0.203150E+10 | 17314.78 | 0.00 | 3693302.15 | 155536.81 | 22562736.30 | 0.203832E+10 | 0.00 | 0.88 |
Annual Sum or Average | 0.108212E+11 | 0.656597E+10 | 0.00 | 55865405.20 | 0.551750E+09 | 22562736.30 | 0.174148E+11 | 0.00 | 1.01 |
Minimum of Months | 85000348.50 | 0.00 | 0.00 | 766129.72 | 0.00 | 0.00 | 62795648.99 | 0.00 | 0.73 |
Maximum of Months | 0.203150E+10 | 0.168962E+10 | 0.00 | 9357847.20 | 0.200445E+09 | 22562736.30 | 0.292343E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101037E+10 | 4226653.19 | 0.00 | 25338948.66 | 1191663.62 | 0.00 | 0.675377E+10 | 0.00 | 1.76 |
February | 0.148418E+10 | 0.00 | 0.00 | 11467313.84 | 0.00 | 0.00 | 0.716081E+10 | 0.00 | 1.35 |
March | 0.142889E+10 | 2896383.87 | 0.00 | 12814221.27 | 131178.86 | 0.00 | 0.470055E+10 | 0.00 | 1.28 |
April | 0.118723E+10 | 0.319499E+09 | 0.00 | 9742625.36 | 33877864.42 | 0.00 | 0.141440E+10 | 0.00 | 1.01 |
May | 0.311200E+09 | 0.589536E+09 | 0.00 | 4760064.65 | 26356210.08 | 0.00 | 0.576168E+09 | 0.00 | 0.62 |
June | 0.222718E+09 | 0.187726E+10 | 0.00 | 1502296.09 | 48354930.84 | 0.00 | 0.181495E+09 | 0.00 | 0.60 |
July | 0.126336E+09 | 0.212484E+10 | 0.00 | 628587.07 | 0.220037E+09 | 0.00 | 62088740.37 | 0.00 | 0.55 |
August | 0.184725E+09 | 0.223025E+10 | 0.00 | 1644257.42 | 0.108960E+09 | 0.00 | 0.110047E+09 | 0.00 | 0.71 |
September | 67793062.47 | 0.168574E+10 | 0.00 | 4309039.48 | 0.137685E+09 | 0.00 | 0.355541E+09 | 0.00 | 0.74 |
October | 0.685948E+09 | 0.396428E+09 | 0.00 | 14226334.17 | 21001830.36 | 0.00 | 0.354781E+10 | 0.00 | 1.30 |
November | 0.934609E+09 | 4902508.51 | 0.00 | 22145382.65 | 6704165.30 | 0.00 | 0.686081E+10 | 0.00 | 1.66 |
December | 0.140683E+10 | 667968.99 | 0.00 | 21527599.67 | 0.00 | 3834003.94 | 0.848292E+10 | 0.00 | 1.62 |
Annual Sum or Average | 0.905083E+10 | 0.923624E+10 | 0.00 | 0.130107E+09 | 0.604300E+09 | 3834003.94 | 0.402064E+11 | 0.00 | 1.10 |
Minimum of Months | 67793062.47 | 0.00 | 0.00 | 628587.07 | 0.00 | 0.00 | 62088740.37 | 0.00 | 0.55 |
Maximum of Months | 0.148418E+10 | 0.223025E+10 | 0.00 | 25338948.66 | 0.220037E+09 | 3834003.94 | 0.848292E+10 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168960E+10 | 2477538.89 | 0.00 | 7851469.60 | 2093536.64 | 0.00 | 0.260507E+10 | 0.00 | 1.39 |
February | 0.138983E+10 | 0.00 | 0.00 | 6679890.89 | 0.00 | 0.00 | 0.452195E+10 | 0.00 | 1.45 |
March | 0.774152E+09 | 2497648.77 | 0.00 | 13109544.96 | 0.00 | 0.00 | 0.495938E+10 | 0.00 | 1.84 |
April | 0.648980E+09 | 0.405989E+09 | 0.00 | 15479318.07 | 3819485.85 | 0.00 | 0.267585E+10 | 0.00 | 1.90 |
May | 0.195739E+09 | 0.719246E+09 | 0.00 | 5871123.64 | 13446993.80 | 0.00 | 0.805884E+09 | 0.00 | 1.04 |
June | 0.184965E+09 | 0.224705E+10 | 0.00 | 2684451.00 | 32030590.36 | 0.00 | 0.305798E+09 | 0.00 | 1.09 |
July | 0.104151E+09 | 0.240548E+10 | 0.00 | 1265129.65 | 0.152142E+09 | 0.00 | 0.124226E+09 | 0.00 | 0.94 |
August | 74331827.16 | 0.251196E+10 | 0.00 | 4214598.47 | 46447855.90 | 0.00 | 0.316959E+09 | 0.00 | 1.30 |
September | 57754920.23 | 0.128068E+10 | 0.00 | 3642322.97 | 0.126745E+09 | 0.00 | 0.347981E+09 | 0.00 | 0.95 |
October | 0.577965E+09 | 0.262879E+09 | 0.00 | 9791437.43 | 21164050.66 | 0.00 | 0.251706E+10 | 0.00 | 1.41 |
November | 0.735303E+09 | 11418398.43 | 0.00 | 13444001.20 | 2559797.54 | 0.00 | 0.465432E+10 | 0.00 | 1.74 |
December | 0.971969E+09 | 109417.12 | 0.00 | 11610226.78 | 144871.52 | 0.00 | 0.561603E+10 | 0.00 | 1.60 |
Annual Sum or Average | 0.740474E+10 | 0.984979E+10 | 0.00 | 95643514.65 | 0.400595E+09 | 0.00 | 0.294505E+11 | 0.00 | 1.39 |
Minimum of Months | 57754920.23 | 0.00 | 0.00 | 1265129.65 | 0.00 | 0.00 | 0.124226E+09 | 0.00 | 0.94 |
Maximum of Months | 0.168960E+10 | 0.251196E+10 | 0.00 | 15479318.07 | 0.152142E+09 | 0.00 | 0.561603E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230753E+11 | 476735.79 | 0.00 | 6984050.64 | 35554161.39 | 0.171788E+10 | 0.171640E+10 | 0.00 | 0.52 |
February | 0.284440E+11 | 0.00 | 0.00 | 3366163.31 | 0.00 | 0.188882E+10 | 0.286883E+10 | 0.00 | 0.52 |
March | 0.218904E+11 | 15638581.05 | 0.00 | 23895016.16 | 2751665.34 | 0.109603E+10 | 0.677869E+10 | 0.00 | 0.57 |
April | 0.684006E+10 | 0.228012E+10 | 0.00 | 45857038.15 | 0.256404E+09 | 0.00 | 0.560045E+10 | 0.00 | 0.53 |
May | 0.234482E+10 | 0.594862E+10 | 0.00 | 38371502.80 | 0.193304E+09 | 0.00 | 0.456493E+10 | 0.00 | 0.54 |
June | 0.666024E+09 | 0.218934E+11 | 0.00 | 17925722.76 | 0.238851E+09 | 0.00 | 0.232914E+10 | 0.00 | 0.61 |
July | 0.329877E+09 | 0.226233E+11 | 0.00 | 6156289.13 | 0.519265E+09 | 0.00 | 0.705505E+09 | 0.00 | 0.51 |
August | 0.424385E+09 | 0.194179E+11 | 0.00 | 11218923.40 | 0.338560E+09 | 0.00 | 0.946076E+09 | 0.00 | 0.53 |
September | 0.822232E+09 | 0.124854E+11 | 0.00 | 24367615.74 | 0.739468E+09 | 0.00 | 0.208776E+10 | 0.00 | 0.52 |
October | 0.123924E+11 | 0.228052E+10 | 0.00 | 25399715.92 | 0.116188E+09 | 14262313.39 | 0.495797E+10 | 0.00 | 0.52 |
November | 0.211595E+11 | 12966470.87 | 0.00 | 17829150.77 | 61635510.98 | 0.985544E+09 | 0.541596E+10 | 0.00 | 0.54 |
December | 0.277548E+11 | 0.00 | 0.00 | 856679.55 | 2051048.58 | 0.511572E+10 | 0.454055E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.146144E+12 | 0.869584E+11 | 0.00 | 0.222228E+09 | 0.250403E+10 | 0.108183E+11 | 0.384258E+11 | 0.00 | 0.53 |
Minimum of Months | 0.329877E+09 | 0.00 | 0.00 | 856679.55 | 0.00 | 0.00 | 0.454055E+09 | 0.00 | 0.49 |
Maximum of Months | 0.284440E+11 | 0.226233E+11 | 0.00 | 45857038.15 | 0.739468E+09 | 0.511572E+10 | 0.677869E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161783E+11 | 527965.50 | 0.00 | 27041486.57 | 36406560.17 | 0.112085E+10 | 0.124255E+11 | 0.00 | 0.90 |
February | 0.196470E+11 | 0.00 | 0.00 | 19936133.42 | 0.00 | 0.123514E+10 | 0.158592E+11 | 0.00 | 0.87 |
March | 0.162333E+11 | 13543506.96 | 0.00 | 46347762.69 | 2817635.57 | 0.790713E+09 | 0.189921E+11 | 0.00 | 1.05 |
April | 0.472800E+10 | 0.226511E+10 | 0.00 | 88379407.74 | 0.242514E+09 | 0.00 | 0.153486E+11 | 0.00 | 1.18 |
May | 0.206996E+10 | 0.509625E+10 | 0.00 | 65149668.29 | 0.190142E+09 | 0.00 | 0.839100E+10 | 0.00 | 1.05 |
June | 0.713125E+09 | 0.188060E+11 | 0.00 | 16930439.42 | 0.212066E+09 | 0.00 | 0.218055E+10 | 0.00 | 0.91 |
July | 0.327560E+09 | 0.204947E+11 | 0.00 | 7336959.60 | 0.571950E+09 | 0.00 | 0.738744E+09 | 0.00 | 0.76 |
August | 0.437097E+09 | 0.185169E+11 | 0.00 | 11998582.43 | 0.382644E+09 | 0.00 | 0.105966E+10 | 0.00 | 0.82 |
September | 0.902297E+09 | 0.117798E+11 | 0.00 | 25123405.84 | 0.630814E+09 | 0.00 | 0.240467E+10 | 0.00 | 0.81 |
October | 0.855925E+10 | 0.217265E+10 | 0.00 | 49007153.41 | 99122504.94 | 4452930.24 | 0.142335E+11 | 0.00 | 1.00 |
November | 0.164469E+11 | 10884066.23 | 0.00 | 34470056.40 | 63113201.15 | 0.453148E+09 | 0.140588E+11 | 0.00 | 0.93 |
December | 0.258637E+11 | 0.00 | 0.00 | 8353103.65 | 2100221.77 | 0.312950E+10 | 0.562855E+10 | 0.00 | 0.79 |
Annual Sum or Average | 0.112106E+12 | 0.791564E+11 | 0.00 | 0.400074E+09 | 0.243369E+10 | 0.673381E+10 | 0.111321E+12 | 0.00 | 0.92 |
Minimum of Months | 0.327560E+09 | 0.00 | 0.00 | 7336959.60 | 0.00 | 0.00 | 0.738744E+09 | 0.00 | 0.76 |
Maximum of Months | 0.258637E+11 | 0.204947E+11 | 0.00 | 88379407.74 | 0.630814E+09 | 0.312950E+10 | 0.189921E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.976040E+10 | 74469352.83 | 0.00 | 0.234430E+09 | 21231439.01 | 0.297777E+09 | 0.568184E+11 | 0.00 | 1.63 |
February | 0.155431E+11 | 0.00 | 0.00 | 96852345.41 | 0.00 | 0.187671E+09 | 0.599432E+11 | 0.00 | 1.22 |
March | 0.151443E+11 | 29779841.78 | 0.00 | 0.100052E+09 | 3056178.80 | 0.537082E+09 | 0.336172E+11 | 0.00 | 1.07 |
April | 0.675200E+10 | 0.401875E+10 | 0.00 | 76460608.35 | 0.262017E+09 | 0.00 | 0.943378E+10 | 0.00 | 0.77 |
May | 0.317678E+10 | 0.673791E+10 | 0.00 | 37248975.73 | 0.214696E+09 | 0.00 | 0.397859E+10 | 0.00 | 0.58 |
June | 0.779907E+09 | 0.210787E+11 | 0.00 | 13792309.44 | 0.295845E+09 | 0.00 | 0.182707E+10 | 0.00 | 0.56 |
July | 0.440461E+09 | 0.229936E+11 | 0.00 | 4878872.66 | 0.603545E+09 | 0.00 | 0.521178E+09 | 0.00 | 0.51 |
August | 0.456909E+09 | 0.235594E+11 | 0.00 | 12094573.52 | 0.350366E+09 | 0.00 | 0.101284E+10 | 0.00 | 0.62 |
September | 0.675456E+09 | 0.188291E+11 | 0.00 | 35441362.71 | 0.721218E+09 | 0.00 | 0.281761E+10 | 0.00 | 0.72 |
October | 0.718707E+10 | 0.466107E+10 | 0.00 | 0.119388E+09 | 58072933.17 | 0.00 | 0.287373E+11 | 0.00 | 1.18 |
November | 0.102961E+11 | 33709183.92 | 0.00 | 0.193733E+09 | 64540680.38 | 71598287.47 | 0.563094E+11 | 0.00 | 1.47 |
December | 0.135303E+11 | 2276922.06 | 0.00 | 0.180509E+09 | 1098025.55 | 0.171614E+10 | 0.670603E+11 | 0.00 | 1.43 |
Annual Sum or Average | 0.837429E+11 | 0.102019E+12 | 0.00 | 0.110488E+10 | 0.259569E+10 | 0.281026E+10 | 0.322077E+12 | 0.00 | 0.98 |
Minimum of Months | 0.440461E+09 | 0.00 | 0.00 | 4878872.66 | 0.00 | 0.00 | 0.521178E+09 | 0.00 | 0.51 |
Maximum of Months | 0.155431E+11 | 0.235594E+11 | 0.00 | 0.234430E+09 | 0.721218E+09 | 0.171614E+10 | 0.670603E+11 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239569E+11 | 24191774.08 | 0.00 | 33712627.12 | 27431886.56 | 0.401179E+09 | 0.790234E+10 | 0.00 | 1.07 |
February | 0.289479E+11 | 0.00 | 0.00 | 18901083.97 | 0.00 | 0.426139E+09 | 0.120272E+11 | 0.00 | 1.02 |
March | 0.229970E+11 | 20246841.03 | 0.00 | 43067709.66 | 0.00 | 0.261282E+09 | 0.126453E+11 | 0.00 | 1.14 |
April | 0.650626E+10 | 0.369806E+10 | 0.00 | 60439629.16 | 0.101484E+09 | 0.00 | 0.807551E+10 | 0.00 | 1.04 |
May | 0.260196E+10 | 0.778974E+10 | 0.00 | 33012881.03 | 73933361.00 | 0.00 | 0.423266E+10 | 0.00 | 0.88 |
June | 0.593620E+09 | 0.230175E+11 | 0.00 | 15145239.09 | 0.170218E+09 | 0.00 | 0.198450E+10 | 0.00 | 0.91 |
July | 0.362807E+09 | 0.207182E+11 | 0.00 | 5262095.17 | 0.406634E+09 | 0.00 | 0.607900E+09 | 0.00 | 0.70 |
August | 0.422504E+09 | 0.190285E+11 | 0.00 | 10492676.44 | 0.251914E+09 | 0.00 | 0.970807E+09 | 0.00 | 0.80 |
September | 0.947533E+09 | 0.119578E+11 | 0.00 | 20540098.86 | 0.729664E+09 | 0.00 | 0.189272E+10 | 0.00 | 0.76 |
October | 0.124716E+11 | 0.237046E+10 | 0.00 | 41237348.80 | 89922008.95 | 0.00 | 0.864184E+10 | 0.00 | 0.97 |
November | 0.214142E+11 | 23532852.67 | 0.00 | 42150406.02 | 67463194.94 | 0.224565E+09 | 0.126916E+11 | 0.00 | 1.08 |
December | 0.275087E+11 | 0.00 | 0.00 | 19460534.93 | 2291959.18 | 0.342410E+10 | 0.891339E+10 | 0.00 | 0.94 |
Annual Sum or Average | 0.148731E+12 | 0.886483E+11 | 0.00 | 0.343422E+09 | 0.192096E+10 | 0.473726E+10 | 0.805857E+11 | 0.00 | 0.94 |
Minimum of Months | 0.362807E+09 | 0.00 | 0.00 | 5262095.17 | 0.00 | 0.00 | 0.607900E+09 | 0.00 | 0.70 |
Maximum of Months | 0.289479E+11 | 0.230175E+11 | 0.00 | 60439629.16 | 0.729664E+09 | 0.342410E+10 | 0.126916E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209405E+10 | 0.00 | 0.00 | 361286.04 | 4260057.81 | 0.515605E+09 | 95656242.92 | 0.00 | 0.58 |
February | 0.282707E+10 | 0.00 | 0.00 | 116264.87 | 22525.93 | 0.512461E+09 | 0.124990E+09 | 0.00 | 0.56 |
March | 0.226740E+10 | 481009.43 | 0.00 | 1936891.31 | 113735.02 | 0.358077E+09 | 0.446030E+09 | 0.00 | 0.61 |
April | 0.684105E+09 | 0.147414E+09 | 0.00 | 5508141.93 | 27399938.74 | 322601.80 | 0.481653E+09 | 0.00 | 0.54 |
May | 0.297537E+09 | 0.423849E+09 | 0.00 | 4708397.99 | 19337607.81 | 0.00 | 0.293627E+09 | 0.00 | 0.51 |
June | 75332974.03 | 0.179851E+10 | 0.00 | 1507714.71 | 23136155.93 | 0.00 | 0.166314E+09 | 0.00 | 0.57 |
July | 35230635.16 | 0.195346E+10 | 0.00 | 524205.22 | 55979849.80 | 0.00 | 48853345.70 | 0.00 | 0.48 |
August | 45331983.29 | 0.167597E+10 | 0.00 | 931334.48 | 38929169.41 | 0.00 | 66206965.74 | 0.00 | 0.51 |
September | 0.122463E+09 | 0.105836E+10 | 0.00 | 2588223.46 | 93500777.32 | 0.00 | 0.147376E+09 | 0.00 | 0.51 |
October | 0.116709E+10 | 0.179090E+09 | 0.00 | 2442466.23 | 20607283.07 | 0.147265E+09 | 0.360201E+09 | 0.00 | 0.53 |
November | 0.205125E+10 | 695839.49 | 0.00 | 1164579.10 | 5666287.84 | 0.362241E+09 | 0.336050E+09 | 0.00 | 0.58 |
December | 0.225698E+10 | 0.00 | 0.00 | 29320.62 | 1504974.62 | 0.106491E+10 | 18978377.55 | 0.00 | 0.53 |
Annual Sum or Average | 0.139238E+11 | 0.723783E+10 | 0.00 | 21818825.95 | 0.290458E+09 | 0.296088E+10 | 0.258594E+10 | 0.00 | 0.54 |
Minimum of Months | 35230635.16 | 0.00 | 0.00 | 29320.62 | 22525.93 | 0.00 | 18978377.55 | 0.00 | 0.48 |
Maximum of Months | 0.282707E+10 | 0.195346E+10 | 0.00 | 5508141.93 | 93500777.32 | 0.106491E+10 | 0.481653E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137461E+10 | 0.00 | 0.00 | 1842040.74 | 3955378.73 | 0.306388E+09 | 0.901525E+09 | 0.00 | 0.86 |
February | 0.181609E+10 | 0.00 | 0.00 | 1182868.65 | 20914.87 | 0.331665E+09 | 0.113772E+10 | 0.00 | 0.83 |
March | 0.145599E+10 | 515350.32 | 0.00 | 4047666.35 | 105600.70 | 0.206350E+09 | 0.156761E+10 | 0.00 | 1.01 |
April | 0.396279E+09 | 0.153565E+09 | 0.00 | 9599090.65 | 21781174.43 | 315770.64 | 0.132448E+10 | 0.00 | 1.14 |
May | 0.200970E+09 | 0.361951E+09 | 0.00 | 7569532.86 | 16833149.18 | 0.00 | 0.647549E+09 | 0.00 | 0.99 |
June | 75094335.99 | 0.156957E+10 | 0.00 | 1514787.66 | 20542050.22 | 0.00 | 0.156006E+09 | 0.00 | 0.86 |
July | 30457945.00 | 0.178611E+10 | 0.00 | 607569.95 | 55243751.28 | 0.00 | 53044437.29 | 0.00 | 0.72 |
August | 40176889.30 | 0.162433E+10 | 0.00 | 1091186.67 | 39911499.81 | 0.00 | 76446181.28 | 0.00 | 0.78 |
September | 0.104523E+09 | 0.102764E+10 | 0.00 | 2782531.44 | 71223439.29 | 0.00 | 0.180387E+09 | 0.00 | 0.79 |
October | 0.634175E+09 | 0.181328E+09 | 0.00 | 4692753.27 | 10527810.56 | 97950663.59 | 0.117345E+10 | 0.00 | 0.93 |
November | 0.138738E+10 | 609320.64 | 0.00 | 2736578.75 | 5261035.28 | 0.176050E+09 | 0.110942E+10 | 0.00 | 0.90 |
December | 0.226175E+10 | 0.00 | 0.00 | 337905.61 | 1397338.93 | 0.554728E+09 | 0.258177E+09 | 0.00 | 0.76 |
Annual Sum or Average | 0.977749E+10 | 0.670563E+10 | 0.00 | 38004512.59 | 0.246803E+09 | 0.167345E+10 | 0.858582E+10 | 0.00 | 0.88 |
Minimum of Months | 30457945.00 | 0.00 | 0.00 | 337905.61 | 20914.87 | 0.00 | 53044437.29 | 0.00 | 0.72 |
Maximum of Months | 0.226175E+10 | 0.178611E+10 | 0.00 | 9599090.65 | 71223439.29 | 0.554728E+09 | 0.156761E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.939720E+09 | 5061598.18 | 0.00 | 18955315.00 | 3246715.01 | 0.213701E+09 | 0.525603E+10 | 0.00 | 1.65 |
February | 0.152993E+10 | 0.00 | 0.00 | 7665805.99 | 24560.72 | 0.299305E+09 | 0.533582E+10 | 0.00 | 1.15 |
March | 0.145563E+10 | 1062466.68 | 0.00 | 9013383.26 | 124008.82 | 0.265850E+09 | 0.304729E+10 | 0.00 | 1.05 |
April | 0.658418E+09 | 0.255614E+09 | 0.00 | 9442089.02 | 25845473.90 | 0.00 | 0.883658E+09 | 0.00 | 0.77 |
May | 0.404524E+09 | 0.468967E+09 | 0.00 | 4937852.66 | 21084393.31 | 0.00 | 0.231576E+09 | 0.00 | 0.56 |
June | 90967548.34 | 0.172379E+10 | 0.00 | 1118054.96 | 26484500.67 | 0.00 | 0.137663E+09 | 0.00 | 0.53 |
July | 40676667.60 | 0.196458E+10 | 0.00 | 438917.57 | 67283169.02 | 0.00 | 41705502.04 | 0.00 | 0.49 |
August | 45366307.22 | 0.198944E+10 | 0.00 | 1025192.45 | 41186174.44 | 0.00 | 75079460.95 | 0.00 | 0.59 |
September | 0.109219E+09 | 0.155371E+10 | 0.00 | 3918964.31 | 89099037.79 | 0.00 | 0.217143E+09 | 0.00 | 0.69 |
October | 0.646191E+09 | 0.362104E+09 | 0.00 | 12023144.76 | 9102594.35 | 58530286.78 | 0.266715E+10 | 0.00 | 1.14 |
November | 0.100649E+10 | 2134792.22 | 0.00 | 16061066.30 | 5614076.25 | 0.139701E+09 | 0.513086E+10 | 0.00 | 1.47 |
December | 0.126975E+10 | 1547239.66 | 0.00 | 12765573.47 | 370046.88 | 0.402884E+09 | 0.558459E+10 | 0.00 | 1.31 |
Annual Sum or Average | 0.819688E+10 | 0.832801E+10 | 0.00 | 97365359.76 | 0.289465E+09 | 0.137997E+10 | 0.286086E+11 | 0.00 | 0.95 |
Minimum of Months | 40676667.60 | 0.00 | 0.00 | 438917.57 | 24560.72 | 0.00 | 41705502.04 | 0.00 | 0.49 |
Maximum of Months | 0.152993E+10 | 0.198944E+10 | 0.00 | 18955315.00 | 89099037.79 | 0.402884E+09 | 0.558459E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199511E+10 | 1854129.74 | 0.00 | 3059758.26 | 3510141.76 | 0.330496E+09 | 0.821751E+09 | 0.00 | 1.13 |
February | 0.263423E+10 | 0.00 | 0.00 | 1622901.84 | 23955.58 | 0.289774E+09 | 0.114885E+10 | 0.00 | 1.04 |
March | 0.216068E+10 | 664960.12 | 0.00 | 4062417.06 | 0.00 | 0.250674E+09 | 0.116197E+10 | 0.00 | 1.18 |
April | 0.645676E+09 | 0.238720E+09 | 0.00 | 7824794.54 | 11136351.17 | 0.00 | 0.716540E+09 | 0.00 | 1.05 |
May | 0.333183E+09 | 0.536398E+09 | 0.00 | 4178522.15 | 8608380.06 | 0.00 | 0.262434E+09 | 0.00 | 0.83 |
June | 69242742.74 | 0.180153E+10 | 0.00 | 1262255.90 | 16063615.87 | 0.00 | 0.153707E+09 | 0.00 | 0.82 |
July | 33743765.05 | 0.173061E+10 | 0.00 | 454422.01 | 49049132.71 | 0.00 | 47766428.90 | 0.00 | 0.66 |
August | 40084367.25 | 0.157198E+10 | 0.00 | 901359.18 | 33643884.74 | 0.00 | 74158341.45 | 0.00 | 0.75 |
September | 0.134565E+09 | 0.987257E+09 | 0.00 | 2289870.75 | 90415554.34 | 0.00 | 0.129247E+09 | 0.00 | 0.74 |
October | 0.112254E+10 | 0.181755E+09 | 0.00 | 4369358.75 | 17477671.73 | 59338884.54 | 0.792792E+09 | 0.00 | 0.96 |
November | 0.189951E+10 | 1917944.70 | 0.00 | 3739870.67 | 5341899.06 | 0.231772E+09 | 0.115841E+10 | 0.00 | 1.13 |
December | 0.232684E+10 | 0.00 | 0.00 | 1570767.31 | 1600490.85 | 0.617192E+09 | 0.791561E+09 | 0.00 | 0.95 |
Annual Sum or Average | 0.133954E+11 | 0.705268E+10 | 0.00 | 35336298.41 | 0.236871E+09 | 0.177925E+10 | 0.725920E+10 | 0.00 | 0.94 |
Minimum of Months | 33743765.05 | 0.00 | 0.00 | 454422.01 | 0.00 | 0.00 | 47766428.90 | 0.00 | 0.66 |
Maximum of Months | 0.263423E+10 | 0.180153E+10 | 0.00 | 7824794.54 | 90415554.34 | 0.617192E+09 | 0.116197E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4080966.81 | 0.00 | 0.00 | 0.294574E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7818456.39 | 0.00 | 0.00 | 0.293236E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14025196.91 | 0.00 | 0.00 | 0.293028E+09 | 0.00 | 0.31 |
April | 0.00 | 353301.21 | 0.00 | 18631123.36 | 0.00 | 0.00 | 0.121040E+09 | 0.00 | 0.29 |
May | 0.00 | 13945416.23 | 0.00 | 3025084.23 | 0.00 | 0.00 | 54765344.89 | 0.00 | 0.29 |
June | 0.00 | 92458285.39 | 0.00 | 1577032.36 | 0.00 | 0.00 | 14702240.35 | 0.00 | 0.30 |
July | 0.00 | 0.185770E+09 | 0.00 | 496675.83 | 0.00 | 0.00 | 4215004.73 | 0.00 | 0.28 |
August | 0.00 | 0.158761E+09 | 0.00 | 2820972.16 | 0.00 | 0.00 | 5518031.81 | 0.00 | 0.31 |
September | 0.00 | 0.113200E+09 | 0.00 | 745585.28 | 0.00 | 0.00 | 10937209.05 | 0.00 | 0.29 |
October | 0.00 | 22312501.56 | 0.00 | 7087853.28 | 0.00 | 0.00 | 0.169652E+09 | 0.00 | 0.28 |
November | 0.00 | 1921465.06 | 0.00 | 12239577.72 | 0.00 | 0.00 | 0.237337E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18175859.13 | 0.00 | 0.00 | 0.350250E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.588722E+09 | 0.00 | 90724383.47 | 0.00 | 0.00 | 0.184926E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 496675.83 | 0.00 | 0.00 | 4215004.73 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.185770E+09 | 0.00 | 18631123.36 | 0.00 | 0.00 | 0.350250E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19986279.09 | 0.00 | 0.00 | 31660360.92 | 0.00 | 0.00 | 0.293345E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 67689509.68 | 0.00 | 0.00 | 0.294764E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.128476E+09 | 0.00 | 0.00 | 0.294020E+10 | 0.00 | 0.31 |
April | 0.00 | 6554009.53 | 0.00 | 0.172934E+09 | 0.00 | 0.00 | 0.119359E+10 | 0.00 | 0.29 |
May | 0.00 | 0.138912E+09 | 0.00 | 27969644.57 | 0.00 | 0.00 | 0.548898E+09 | 0.00 | 0.29 |
June | 0.00 | 0.923187E+09 | 0.00 | 14928027.25 | 0.00 | 0.00 | 0.146288E+09 | 0.00 | 0.30 |
July | 0.00 | 0.185413E+10 | 0.00 | 4725664.41 | 0.00 | 0.00 | 41500954.50 | 0.00 | 0.28 |
August | 0.00 | 0.163727E+10 | 0.00 | 24707490.69 | 0.00 | 0.00 | 49781429.79 | 0.00 | 0.31 |
September | 0.00 | 0.112022E+10 | 0.00 | 6800118.01 | 0.00 | 0.00 | 0.109312E+09 | 0.00 | 0.29 |
October | 0.00 | 0.221950E+09 | 0.00 | 64274242.93 | 0.00 | 0.00 | 0.170041E+10 | 0.00 | 0.28 |
November | 0.00 | 18518996.71 | 0.00 | 0.111568E+09 | 0.00 | 0.00 | 0.238269E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.164478E+09 | 0.00 | 0.00 | 0.351608E+10 | 0.00 | 0.28 |
Annual Sum or Average | 19986279.09 | 0.592074E+10 | 0.00 | 0.820211E+09 | 0.00 | 0.00 | 0.185098E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4725664.41 | 0.00 | 0.00 | 41500954.50 | 0.00 | 0.28 |
Maximum of Months | 19986279.09 | 0.185413E+10 | 0.00 | 0.172934E+09 | 0.00 | 0.00 | 0.351608E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9711811.23 | 0.00 | 0.00 | 2568288.58 | 0.00 | 0.00 | 0.286566E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6161802.85 | 0.00 | 0.00 | 0.295794E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12389940.70 | 0.00 | 0.00 | 0.294645E+09 | 0.00 | 0.31 |
April | 0.00 | 918340.68 | 0.00 | 16721471.03 | 0.00 | 0.00 | 0.116089E+09 | 0.00 | 0.29 |
May | 0.00 | 13916056.98 | 0.00 | 2775199.37 | 0.00 | 0.00 | 54937553.46 | 0.00 | 0.29 |
June | 0.00 | 92388339.60 | 0.00 | 1488823.88 | 0.00 | 0.00 | 14705415.73 | 0.00 | 0.30 |
July | 0.00 | 0.185559E+09 | 0.00 | 472252.63 | 0.00 | 0.00 | 4191129.31 | 0.00 | 0.28 |
August | 0.00 | 0.168751E+09 | 0.00 | 2307831.29 | 0.00 | 0.00 | 4656572.51 | 0.00 | 0.31 |
September | 0.00 | 0.112291E+09 | 0.00 | 667603.74 | 0.00 | 0.00 | 11009556.50 | 0.00 | 0.29 |
October | 0.00 | 22232925.58 | 0.00 | 6158533.98 | 0.00 | 0.00 | 0.170446E+09 | 0.00 | 0.28 |
November | 0.00 | 1810950.25 | 0.00 | 10665144.02 | 0.00 | 0.00 | 0.238925E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15586429.62 | 0.00 | 0.00 | 0.352331E+09 | 0.00 | 0.28 |
Annual Sum or Average | 9711811.23 | 0.597868E+09 | 0.00 | 77963321.67 | 0.00 | 0.00 | 0.184430E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 472252.63 | 0.00 | 0.00 | 4191129.31 | 0.00 | 0.28 |
Maximum of Months | 9711811.23 | 0.185559E+09 | 0.00 | 16721471.03 | 0.00 | 0.00 | 0.352331E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.564474E+09 | 0.00 | 0.00 | 0.505293E+12 | 0.00 | 22.42 |
February | 0.00 | 0.00 | 0.00 | 0.908168E+09 | 0.00 | 0.00 | 0.613755E+12 | 0.00 | 28.54 |
March | 0.00 | 0.00 | 0.00 | 0.157414E+10 | 0.00 | 0.00 | 0.831143E+12 | 0.00 | 39.02 |
April | 0.00 | 0.00 | 0.00 | 0.370440E+10 | 0.00 | 0.00 | 0.617382E+12 | 0.00 | 45.94 |
May | 0.00 | 27922.52 | 0.00 | 0.493831E+09 | 0.00 | 0.00 | 0.268262E+12 | 0.00 | 19.24 |
June | 0.00 | 0.918146E+09 | 0.00 | 0.683931E+09 | 0.00 | 0.00 | 0.119707E+12 | 0.00 | 12.30 |
July | 0.00 | 0.521487E+11 | 0.00 | 0.376743E+09 | 0.00 | 0.00 | 0.400522E+11 | 0.00 | 13.88 |
August | 0.00 | 0.258619E+11 | 0.00 | 0.147050E+10 | 0.00 | 0.00 | 0.719746E+11 | 0.00 | 29.56 |
September | 0.00 | 0.986958E+10 | 0.00 | 0.294359E+09 | 0.00 | 0.00 | 0.105501E+12 | 0.00 | 21.22 |
October | 0.00 | 0.296879E+10 | 0.00 | 0.103202E+10 | 0.00 | 0.00 | 0.504189E+12 | 0.00 | 31.40 |
November | 0.00 | 13462267.86 | 0.00 | 0.170045E+10 | 0.00 | 0.00 | 0.784622E+12 | 0.00 | 39.97 |
December | 0.00 | 0.00 | 0.00 | 0.238201E+10 | 0.00 | 0.00 | 0.114289E+13 | 0.00 | 40.83 |
Annual Sum or Average | 0.00 | 0.917806E+11 | 0.00 | 0.151850E+11 | 0.00 | 0.00 | 0.560477E+13 | 0.00 | 28.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.294359E+09 | 0.00 | 0.00 | 0.400522E+11 | 0.00 | 12.30 |
Maximum of Months | 0.00 | 0.521487E+11 | 0.00 | 0.370440E+10 | 0.00 | 0.00 | 0.114289E+13 | 0.00 | 45.94 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:44:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.323095E+12 | 0.971882E+10 | 0.00 | 0.231914E+13 | 0.734710E+12 |
February | 0.363727E+12 | 0.767382E+10 | 0.00 | 0.258240E+13 | 0.310116E+12 |
March | 0.470552E+12 | 0.100987E+11 | 0.00 | 0.270811E+13 | 0.111867E+13 |
April | 0.556063E+12 | 0.256879E+10 | 0.00 | 0.153722E+13 | 0.290124E+13 |
May | 0.549559E+12 | 0.307888E+09 | 0.00 | 0.838659E+12 | 0.257905E+13 |
June | 0.560189E+12 | -0.306126E+10 | 0.00 | 0.693885E+11 | 0.366400E+13 |
July | 0.530955E+12 | -0.556862E+10 | 0.00 | -0.265712E+12 | 0.404872E+13 |
August | 0.475446E+12 | -0.355111E+10 | 0.00 | -0.880390E+11 | 0.442749E+13 |
September | 0.397656E+12 | -0.221057E+10 | 0.00 | 0.202672E+11 | 0.264213E+13 |
October | 0.375287E+12 | 0.424772E+10 | 0.00 | 0.181074E+13 | 0.182950E+13 |
November | 0.338646E+12 | 0.886284E+10 | 0.00 | 0.258475E+13 | 0.114461E+13 |
December | 0.270251E+12 | 0.942644E+10 | 0.00 | 0.318229E+13 | 0.918372E+12 |
Annual Sum or Average | 0.521143E+13 | 0.385134E+11 | 0.00 | 0.172992E+14 | 0.263186E+14 |
Minimum of Months | 0.270251E+12 | -0.556862E+10 | 0.00 | -0.265712E+12 | 0.310116E+12 |
Maximum of Months | 0.560189E+12 | 0.100987E+11 | 0.00 | 0.318229E+13 | 0.442749E+13 |