Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:43:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34973.57 | 755.04 | 755.04 |
Net Site Energy | 34973.57 | 755.04 | 755.04 |
Total Source Energy | 109301.96 | 2359.69 | 2359.69 |
Net Source Energy | 109301.96 | 2359.69 | 2359.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 64.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7124.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3926.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 695.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2831.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 971.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2030.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21069.67 |
Humidification | 81.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 636.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34272.98 | 700.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23380.20 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 64.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 7124.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3926.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 695.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2831.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 971.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2030.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21069.67 |
Humidification | General | 81.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 636.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 64.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7124.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3926.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 695.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2831.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 971.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2030.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21069.67 |
Humidification | Unassigned | 81.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 636.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 281.51 | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Other | 358.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.91 | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 281.51 | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Other | 358.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.91 | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 34272.979 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 34272.979 | 100.00 |
Total On-Site and Utility Electric Sources | 34272.979 | 100.00 |
Total Electricity End Uses | 34272.979 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 23380.20 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 23380.20 | 100.00 |
Total Water End Uses | 23380.20 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1129.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:20 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 07-JUN-15:39 |
Heating | 0.00 | 606698.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 611904.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 262940.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 60415.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 95095.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2225472.94 | 614845.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 606698.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 611904.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 262940.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 60415.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 95095.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 69.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22563.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12434.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2203.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8967.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3076.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6431.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 258.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 689.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108542.53 | 759.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 138.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2343.30 | 16.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 138.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2343.30 | 16.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.29 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.498199 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.76 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.480754 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 22.02 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.72 | 0.282865 | 0.299000 | 2.01 | 0.754307 | 0.500000 | 0.001347 | 0.000173 | 2.01 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 64.36 | 0.295540 | 0.309000 | 19.89 | 0.788108 | 0.500000 | 0.001289 | 0.003734 | 19.89 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.45 | 0.294830 | 0.318000 | 2.05 | 0.786215 | 0.500000 | 0.001292 | 0.000600 | 2.09 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.45 | 0.165223 | 0.200000 | 0.289088 | 0.440596 | 0.500000 | 0.002306 | 0.000072 | 0.289088 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.14 | 0.134490 | 0.200000 | 0.228872 | 0.358641 | 0.500000 | 0.002833 | 0.000053 | 0.228872 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.46 | 0.163695 | 0.200000 | 0.291793 | 0.436521 | 0.500000 | 0.002327 | 0.000087 | 0.302197 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.47 | 0.104435 | 0.200000 | 0.294740 | 0.300000 | 0.500000 | 0.003648 | 0.000046 | 0.294740 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 14.41 | 0.165761 | 0.200000 | 2.88 | 0.442030 | 0.500000 | 0.002298 | 0.001473 | 5.15 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.96 | 0.128632 | 0.200000 | 2.39 | 0.343018 | 0.500000 | 0.002962 | 0.000972 | 3.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.41 | 0.165682 | 0.200000 | 2.88 | 0.441819 | 0.500000 | 0.002300 | 0.001473 | 5.15 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.13 | 0.117252 | 0.200000 | 2.63 | 0.312672 | 0.500000 | 0.003249 | 0.000899 | 3.14 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.60 | 0.149162 | 0.200000 | 0.320216 | 0.397766 | 0.500000 | 0.002554 | 0.000181 | 0.631725 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.24 | 0.124080 | 0.200000 | 0.248075 | 0.330879 | 0.500000 | 0.003071 | 0.000119 | 0.414376 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.149462 | 0.200000 | 0.319581 | 0.398565 | 0.500000 | 0.002549 | 0.000181 | 0.631731 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.41 | 0.108783 | 0.200000 | 0.282957 | 0.300000 | 0.500000 | 0.003502 | 0.000113 | 0.395266 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19732.96 | 0.000173 | 397.80 |
CORE_MID VAV BOX REHEAT COIL | 426803.31 | 0.003734 | 9755.22 |
CORE_TOP VAV BOX REHEAT COIL | 68555.12 | 0.000600 | 1810.93 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8192.39 | 0.000072 | 203.79 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6106.42 | 0.000053 | 148.72 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9902.33 | 0.000087 | 261.47 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5245.73 | 0.000046 | 115.01 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 168366.22 | 0.001473 | 4441.90 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 111081.83 | 0.000972 | 2930.52 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 168367.36 | 0.001473 | 4441.93 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 102765.39 | 0.000899 | 2711.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20651.49 | 0.000181 | 544.71 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13545.70 | 0.000119 | 357.28 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20651.68 | 0.000181 | 544.72 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12922.23 | 0.000113 | 340.85 |
VAV_BOT WITH REHEAT HEATING COIL | 23267.28 | 0.000204 | 408.76 |
VAV_MID WITH REHEAT HEATING COIL | 129148.10 | 0.001130 | 2310.32 |
VAV_TOP WITH REHEAT HEATING COIL | 11108.25 | 0.000097 | 199.99 |
CAV_BAS HEATING COIL | 287976.18 | 0.002519 | 6544.31 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.12 | 3.12 | 12.25 | 3.12 | 11.24 | 11.24 | 0.300000 | 0.277202 | 11.24 |
VAV_MID WITH REHEAT | 59.14 | 30.67 | 118.27 | 30.67 | 107.16 | 107.16 | 0.300000 | 0.286194 | 107.16 |
VAV_TOP WITH REHEAT | 6.15 | 3.22 | 12.31 | 4.16 | 12.19 | 12.19 | 0.300000 | 0.341462 | 12.19 |
CAV_BAS | 6.29 | 6.29 | 6.29 | 6.29 | 6.29 | 6.29 | 1.00 | 1.00 | 6.29 |
AIRLOOP DATACENTER BASEMENT | 22.02 | 22.02 | 22.02 | 22.02 | 22.02 | 22.02 | 1.00 | 0.999992 | 22.02 |
AIRLOOP DATACENTER BOT | 0.498199 | 0.498199 | 0.498199 | 0.498199 | 0.498199 | 0.498199 | 1.00 | 1.00 | 0.498199 |
AIRLOOP DATACENTER MID | 4.76 | 4.76 | 4.76 | 4.76 | 4.76 | 4.76 | 1.00 | 1.00 | 4.76 |
AIRLOOP DATACENTER TOP | 0.480754 | 0.480754 | 0.480754 | 0.480754 | 0.480754 | 0.480754 | 1.00 | 1.00 | 0.480754 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.24 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 107.16 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 12.19 | |
CAV_BAS_OA_CONTROLLER | 6.29 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 22.02 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.498199 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.76 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.480754 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.07 | 6.67 | 11.00 | 0.007717 | 0.007000 | 253257.03 | 0.010774 | 11.24 |
VAV_MID WITH REHEAT COOLING COIL | 28.35 | 6.67 | 11.00 | 0.007771 | 0.007000 | 2468239.94 | 0.105005 | 107.16 |
VAV_TOP WITH REHEAT COOLING COIL | 27.76 | 6.67 | 11.00 | 0.007681 | 0.007000 | 268981.28 | 0.011443 | 12.19 |
CAV_BAS COOLING COIL | 26.19 | 6.67 | 11.38 | 0.007743 | 0.007000 | 125326.60 | 0.005332 | 6.29 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.24 |
VAV_MID WITH REHEAT FAN | 107.16 |
VAV_TOP WITH REHEAT FAN | 12.19 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010774 | 0.000044 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000204 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.105005 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001130 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011443 | 0.000042 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000097 | |
CAV_BAS_COOLC_CONTROLLER | 0.005332 | 0.000089 |
CAV_BAS_HEATC_CONTROLLER | 0.002519 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.29 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 22.02 | 453514.80 | 282433.88 | 0.011107 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.498199 | 10229.79 | 6367.58 | 0.000251 |
AIRLOOP DATACENTER MID COOLING COIL | 4.76 | 95275.30 | 60043.75 | 0.002333 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.480754 | 9879.01 | 6146.91 | 0.000242 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 22.02 | 22.02 | 22.02 | 22.02 | 453514.80 | 453514.80 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.498199 | 0.498199 | 0.498199 | 0.498199 | 10229.79 | 10229.79 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.76 | 4.76 | 4.76 | 4.76 | 95275.30 | 95275.30 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.480754 | 0.480754 | 0.480754 | 0.480754 | 9879.01 | 9879.01 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 22.02 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.498199 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.76 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.480754 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 22.02 | 453514.80 | 0.011107 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.498199 | 10229.79 | 0.000251 |
AIRLOOP DATACENTER MID HEATING COIL | 4.76 | 95275.30 | 0.002333 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.480754 | 9879.01 | 0.000242 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.132554 | 21641.94 | |
HEATSYS1 PUMP | 0.014123 | 4253.34 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.132554 | 15.91 |
HEATSYS1 | 0.014123 | 1.69 |
COOLSYS1_SUPPLY | 0.132554 | 15.91 |
SINGLE WATER PLANT LOOP | 0.013932 | 1.67 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.132554 | 0.132554 | 556393.72 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1614389.96 | 1614389.96 | 0.014123 |
CENTRAL BOILER | 573891.22 | 562818.57 | 0.013932 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.066277 | 7491.72 |
COOLSYS1 CHILLER2 PUMP | 0.066277 | 7491.72 |
PLANT CIRC PUMP | 0.013932 | 3553.43 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.132554 | 0.066980 | 1578300.09 | 1585776.67 | 0.078474 |
COOLSYS1 CHILLER2 | 0.132554 | 0.066980 | 1578300.09 | 1585776.67 | 0.078474 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013932 | 139666.47 | 56971.31 | 69833.23 | 7879.72 | 21178.10 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.156948 | 18.83 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.156948 | 38856.96 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 61.89 | 1881486.27 | 12.38 | 235185.78 |
TOWERWATERSYS COOLTOWER 2 | 61.89 | 1881486.27 | 12.38 | 235185.78 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.081510 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7418E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7432E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9496E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9507E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0253E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0261E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7731E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8603E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9752E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0483E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0454E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1043E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3553E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7740E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1026 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9828E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3944E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6859E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7794E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8909E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9820E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0812E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0516E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1280E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7417E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7433E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9495E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9509E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.0252E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0263E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9023E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0550E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7266E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8840E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5334E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6132E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3779E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0561E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1108E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8651E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1874E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6876E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8670E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9293E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6825E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7282E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5094E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5286E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7227E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7241E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4823E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4834E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3151E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3159E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7548E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8338E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5085E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5714E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3359E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3810E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6453E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3706E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0494E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0476E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8207E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.0939E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7526E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8310E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5057E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5658E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3310E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3663E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7226E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7240E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4822E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4832E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3150E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3156E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3447E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4098E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0504E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0974E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0205E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0377E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4766E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7216E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0304E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4651E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2982E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3530E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3729E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4929E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0860E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2038E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0428E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1131E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7829E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.5492E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.8456E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.2054E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.1061E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2203E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9849E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9230E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7530E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9796E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5235E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3299E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1989E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6516E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7551E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3939E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3262E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.1990E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5206E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6975E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1959E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9804E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0714E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7949E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.5612E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1049 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.8590E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.2204E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.1163E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2253E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9897E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9286E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7576E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9881E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5289E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3305E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2014E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6524E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7571E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3977E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3285E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2019E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5242E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7006E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1991E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9870E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0756E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 84933.66458 | 84933.66458 | 6.29286 | 6.29286 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 90756.59319 | 90756.59319 | 6.72421 | 6.72421 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 868791.54354 | 868791.54354 | 64.35815 | 64.35815 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 231620.22998 | 231620.22998 | 10.00787 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 87086.44370 | 87086.44370 | 6.45131 | 6.45131 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48039.25986 | 48039.25986 | 2.09031 | 2.09031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 19339.49135 | 19339.49135 | 1.44544 | 1.44544 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5355.55934 | 5355.55934 | 0.23282 | 0.23282 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15311.16348 | 15311.16348 | 1.14436 | 1.14436 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3860.45308 | 3860.45308 | 0.16797 | 0.16797 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19520.45561 | 19520.45561 | 1.45897 | 1.45897 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6936.71240 | 6936.71240 | 0.30220 | 0.30220 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19717.71069 | 19717.71069 | 1.47370 | 1.47370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2353.61662 | 2353.61662 | 0.10349 | 0.10349 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 192764.78103 | 192764.78103 | 14.40752 | 14.40752 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 41.41800 | 9.15693E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 117846.65983 | 117846.65983 | 5.14779 | 5.14779 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 160082.66788 | 160082.66788 | 11.96478 | 11.96478 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 77748.74523 | 77748.74523 | 3.39654 | 3.39654 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 192860.91787 | 192860.91787 | 14.41471 | 14.41471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 117847.46541 | 117847.46541 | 5.14783 | 5.14783 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 175619.57146 | 175619.57146 | 13.12601 | 13.12601 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 71934.67469 | 71934.67469 | 3.14161 | 3.14161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 21421.47658 | 21421.47658 | 1.60108 | 1.60108 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14451.71393 | 14451.71393 | 0.63172 | 0.63172 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16595.47773 | 16595.47773 | 1.24037 | 1.24037 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9478.99460 | 9478.99460 | 0.41438 | 0.41438 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21379.00880 | 21379.00880 | 1.59791 | 1.59791 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14451.85190 | 14451.85190 | 0.63173 | 0.63173 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18929.05542 | 18929.05542 | 1.41479 | 1.41479 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9043.11117 | 9043.11117 | 0.39527 | 0.39527 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8452.10124 | 8452.10124 | 0.49820 | 0.49820 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 32.33233 | 9.14187E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 80686.45648 | 80686.45648 | 4.75597 | 4.75597 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8155.21802 | 8155.21802 | 0.48075 | 0.48075 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 40.90067 | 9.15606E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373533.96828 | 373533.96828 | 22.01960 | 22.01960 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 202157.51 | 11.23738 | 11.23738 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 14428.12 | 1.88193 | 1.88193 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1926886.82 | 107.16262 | 107.16262 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 194006.09 | 27.61201 | 27.61201 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 214324.84 | 12.19287 | 12.19287 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 19453.84 | 4.16340 | 4.16340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
7 | CAV_BAS | Cooling | Sensible | 98861.54 | 6.29286 | 6.29286 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 374273.66 | 22.01977 | 22.01977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8453.11 | 0.49820 | 0.49820 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80645.55 | 4.75597 | 4.75597 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8308.39 | 0.48075 | 0.48075 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.29286 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.72421 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28287 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01054 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75431 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34693E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72633E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.01054 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19732.95624 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72633E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.80091 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 64.35815 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29554 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.88667 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78811 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28916E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.73386E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.88667 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 426803.30506 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.73386E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9755.21559 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.45131 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29483 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.05152 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78621 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29227E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.99750E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.09031 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 68555.12263 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.99750E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1810.93208 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44544 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16522 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28909 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44060 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30597E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.16706E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28909 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8192.39196 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.16706E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 203.78703 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14436 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13449 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22887 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35864 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83292E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.34216E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22887 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6106.42233 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.34216E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 148.71652 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45897 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16370 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29179 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43652 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32749E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.66299E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30220 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9902.33292 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.66299E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.47134 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47370 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10443 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29474 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64822E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.58919E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29474 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5245.72660 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.58919E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.00882 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.40752 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16576 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.88150 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44203 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29849E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47294E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.14779 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 168366.21601 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47294E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4441.89651 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.96478 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12863 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.39296 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34302 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96194E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.71792E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.39654 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 111081.83301 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.71792E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2930.51583 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.41471 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16568 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.88294 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44182 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29959E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47295E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.14783 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 168367.36386 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47295E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4441.92687 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.12601 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11725 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62520 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31267 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24941E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.99036E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.14161 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 102765.38631 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99036E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2711.36678 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60108 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14916 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32022 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39777 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55427E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80668E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63172 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20651.48546 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80668E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 544.71385 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24037 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12408 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24807 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33088 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07061E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18504E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41438 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13545.69913 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18504E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 357.28172 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59791 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14946 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31958 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39856 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54915E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80670E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63173 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20651.68238 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80670E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 544.71905 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41479 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10878 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28296 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50238E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13049E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39527 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12922.23122 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13049E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 340.85211 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49820 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.75597 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48075 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 22.01960 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.12333 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.11503 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.24667 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.11503 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.23738 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.23738 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27720 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.13558 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.66927 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 118.27116 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.66927 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 107.16262 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 107.16262 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28619 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.15273 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.22235 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.30546 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.16340 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 12.19287 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 12.19287 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34146 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.29286 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.29286 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.29286 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.29286 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.29286 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.29286 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.01960 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.01960 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.01960 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.01960 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.01977 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 22.01977 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49820 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49820 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49820 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49820 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49820 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49820 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.75597 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.75597 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.75597 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.75597 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.75597 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.75597 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48075 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48075 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48075 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48075 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48075 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48075 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.23738 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 107.16262 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 12.19287 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.29286 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 22.01977 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49820 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.75597 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48075 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.23738 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.06927 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00325 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.71661E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 253257.02670 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07741E-002 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.23738 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 23267.27638 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03552E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 408.76144 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.23738 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.07741E-002 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.41975E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.03552E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 107.16262 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.34688 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00342 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.77124E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2468239.93725 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10500 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 107.16262 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 129148.09976 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12984E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2310.31521 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 107.16262 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10500 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.53495E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12984E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 12.19287 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.76046 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00313 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.68084E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 268981.27619 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14431E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 12.19287 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 11108.25135 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.71798E-005 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 199.98618 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 12.19287 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14431E-002 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.16138E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.71798E-005 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.29286 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.19187 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38266 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.74264E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 125326.59917 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.33168E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.29286 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 287976.17668 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51934E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6544.30994 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.29286 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.33168E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.93133E-005 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.51934E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.01977 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.01977 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 453514.80215 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 282433.88240 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.11065E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 22.01977 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 22.01977 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 22.01977 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 22.01977 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 453514.80215 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 453514.80215 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 22.01977 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 22.01977 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 453514.80215 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.11065E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.80782E-005 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49820 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49820 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10229.79258 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6367.57886 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50527E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49820 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49820 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49820 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49820 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10229.79258 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10229.79258 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49820 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49820 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10229.79258 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50527E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.75597 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.75597 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 95275.30136 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 60043.75477 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33329E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.75597 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.75597 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.75597 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.75597 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 95275.30136 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 95275.30136 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.75597 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.75597 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 95275.30136 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33329E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48075 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48075 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9879.01486 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6146.90773 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41936E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48075 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48075 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48075 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48075 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9879.01486 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9879.01486 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48075 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48075 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9879.01486 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41936E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13255 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 21641.94280 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13255 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.90642 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13255 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13255 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 556393.72130 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.41234E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.69481 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.41234E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4253.34413 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1614389.95929 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1614389.96000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.41234E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13255 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.90642 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.62768E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 7491.72342 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.62768E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 7491.72342 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13255 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.69800E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1578300.08752 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1585776.66500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.84742E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13255 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.69800E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1578300.08752 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1585776.66500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.84742E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.39323E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.67188 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.39323E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3553.43264 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.39323E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 56971.30723 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21178.10000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 573891.22355 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 562818.57000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.39323E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15695 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.83381 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15695 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 38856.95626 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 61.89441 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1881486.27333 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.37888 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 235185.78417 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 61.89441 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1881486.27333 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.37888 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 235185.78417 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.15100E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 8.15100E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18711.04 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 404421.58 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 64973.94 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7759.53 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5784.64 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9384.35 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4971.83 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 159533.56 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 105253.81 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 159534.65 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 97375.38 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19567.28 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12834.50 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19567.46 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12243.87 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 20346.72 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 116753.81 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 10158.88 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 233979.97 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 322663.83 | 212983.39 | 109680.44 | 0.66 | 42940.66 | 435.53 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3097782.26 | 2040051.49 | 1057730.78 | 0.66 | 410756.43 | 4166.12 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 347828.69 | 230117.37 | 117711.31 | 0.66 | 46491.75 | 471.55 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 171387.42 | 115163.97 | 56223.45 | 0.67 | 22671.72 | 229.95 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3238387782 | 0.1512673750 | Pass | Pass | 0.2674284387 | 0.4608644864 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8182956276E-003 | 5.3421956696E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4298361518E-003 | 5.7450957741E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.1887596444E-002 | 5.1794600828E-002 | Pass | Pass | 0.1232702075 | 0.3260589190 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8787515485E-002 | 1.9799889146E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.8450394399E-002 | 4.2847261431E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.5378162305E-002 | 5.0312347329E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.5627734833E-002 | 4.0626471272E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.1860282301E-002 | 2.1166034495E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2620653228E-002 | 4.2394954137E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.4820396646E-002 | 5.4641750595E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9766960382E-002 | 4.2223708933E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.0011868257E-002 | 0.1211779710 | Pass | Pass | 0.2662966919 | 0.7983426555 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9038344507E-002 | 7.8015808126E-002 | Pass | Pass | 0.2105699860 | 0.6060715578 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.8514966965E-002 | 6.6500531903E-002 | Pass | Pass | 0.2162759130 | 0.7140396650 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.8645502431E-002 | 5.7507253620E-002 | Pass | Pass | 0.2940820656 | 1.3025062346 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4025824091E-003 | 5.1930565142E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7290752176E-003 | 5.5554108888E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.3072517260E-002 | 6.4800018449E-002 | Pass | Pass | 0.1256732966 | 0.3261567004 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.6371026267E-005 | 6.4420646645E-005 | Pass | Pass | 4.6993223269E-003 | 2.7700811345E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.1563163249E-003 | 9.4460393601E-003 | Pass | Pass | 0.1757980671 | 0.6905500506 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1634918595E-002 | 2.0812716769E-002 | Pass | Pass | 1.2249955733E-002 | 9.3501233468E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2504283486E-004 | 1.7678228625E-004 | Pass | Pass | 8.2431342513E-005 | 1.0641507291E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4343.90 | -43.2 | 0.00 | -5273.1 | 44774.27 | 43801.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.64 | 0.0000 | Y | 17.31 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 11.08 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.21 | 0.0000 | Y | 17.05 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 11.08 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.57 | 0.0000 | Y | 172.68 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.40 | 0.0000 | Y | 110.62 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 170.26 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.39 | 0.0000 | Y | 110.59 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.57 | 0.0000 | Y | 17.27 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.40 | 0.0000 | Y | 11.06 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 17.02 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.39 | 0.0000 | Y | 11.06 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1234.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.75 | 41.75 | 104.08 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.75 | 71.15 | 591.72 | |
Exterior Lighting Total | 57580.60 | 695.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3108639.41 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1614389.96 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1585776.67 | 6.28 | 1517797.67 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1585776.67 | 6.28 | 1517797.67 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 562818.57 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1881486.27 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1881486.27 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 253257.03 | 322663.83 | 212983.39 | 109680.44 | 0.66 | - | 42940.66 | 435.53 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2468239.94 | 3097782.26 | 2040051.49 | 1057730.78 | 0.66 | - | 410756.43 | 4166.12 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 268981.28 | 347828.69 | 230117.37 | 117711.31 | 0.66 | - | 46491.75 | 471.55 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 125326.60 | 171387.42 | 115163.97 | 56223.45 | 0.67 | - | 22671.72 | 229.95 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 453514.80 | 282433.88 | 171080.92 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10229.79 | 6367.58 | 3862.21 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 95275.30 | 60043.75 | 35231.55 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9879.01 | 6146.91 | 3732.11 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19732.96 | 18711.04 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 426803.31 | 404421.58 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 68555.12 | 64973.94 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8192.39 | 7759.53 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6106.42 | 5784.64 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9902.33 | 9384.35 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5245.73 | 4971.83 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 168366.22 | 159533.56 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 111081.83 | 105253.81 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 168367.36 | 159534.65 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 102765.39 | 97375.38 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20651.49 | 19567.28 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13545.70 | 12834.50 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20651.68 | 19567.46 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12922.23 | 12243.87 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 23267.28 | 20346.72 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 129148.10 | 116753.81 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 11108.25 | 10158.88 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 287976.18 | 233979.97 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 453514.80 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10229.79 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 95275.30 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9879.01 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.24 | 24154.36 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 107.16 | 230342.26 | 2149.46 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 12.19 | 26208.14 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.29 | 10670.52 | 1695.65 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 22.02 | 36316.05 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 558.04 | 1120.11 | 1.00 | 1.61 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.76 | 5327.19 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 538.50 | 1120.11 | 1.00 | 1.62 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.132554 | 21641.94 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014123 | 4253.34 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.066277 | 7491.72 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.066277 | 7491.72 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013932 | 3553.43 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.156948 | 38856.96 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 84933.66 | 84933.66 | 30.56 | 6.293 | 6.293 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 90756.59 | 90756.59 | 36.36 | 6.724 | 6.724 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00734 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 868791.54 | 868791.54 | 348.06 | 64.358 | 64.358 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 87086.44 | 87086.44 | 34.89 | 6.451 | 6.451 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 34.82 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 19339.49 | 19339.49 | 61.71 | 1.445 | 1.445 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00722 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15311.16 | 15311.16 | 75.81 | 1.144 | 1.144 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00718 | 38.80 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19520.46 | 19520.46 | 62.28 | 1.459 | 1.459 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00722 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19717.71 | 19717.71 | 97.62 | 1.474 | 1.474 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00714 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 192764.78 | 192764.78 | 615.05 | 14.408 | 14.408 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 24.00 | 24.00 | 0.00725 | 41.42 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 160082.67 | 160082.67 | 792.59 | 11.965 | 11.965 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00720 | 39.04 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 192860.92 | 192860.92 | 615.34 | 14.415 | 14.415 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 24.00 | 24.00 | 0.00725 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 175619.57 | 175619.57 | 869.51 | 13.126 | 13.126 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00718 | 41.03 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 21421.48 | 21421.48 | 68.35 | 1.601 | 1.601 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00724 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16595.48 | 16595.48 | 82.17 | 1.240 | 1.240 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00720 | 39.28 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21379.01 | 21379.01 | 68.21 | 1.598 | 1.598 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 24.00 | 24.00 | 0.00724 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18929.06 | 18929.06 | 93.72 | 1.415 | 1.415 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00718 | 41.03 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8452.10 | 8452.10 | 233.47 | 0.498 | 0.498 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 27.00 | 27.00 | 0.00700 | 32.33 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80686.46 | 80686.46 | 2228.74 | 4.756 | 4.756 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8155.22 | 8155.22 | 225.27 | 0.481 | 0.481 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 27.00 | 27.00 | 0.00709 | 40.90 | 0.00916 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373533.97 | 373533.97 | 476.64 | 22.020 | 22.020 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.75 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.13 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 231620.23 | 231620.23 | 92.79 | 10.008 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 48039.26 | 48039.26 | 19.25 | 2.090 | 2.090 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5355.56 | 5355.56 | 17.09 | 0.233 | 0.233 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3860.45 | 3860.45 | 19.11 | 0.168 | 0.168 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6936.71 | 6936.71 | 22.13 | 0.302 | 0.302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2353.62 | 2353.62 | 11.65 | 0.103 | 0.103 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00788 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 117846.66 | 117846.66 | 376.01 | 5.148 | 5.148 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 77748.75 | 77748.75 | 384.94 | 3.397 | 3.397 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 117847.47 | 117847.47 | 376.01 | 5.148 | 5.148 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 71934.67 | 71934.67 | 356.16 | 3.142 | 3.142 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14451.71 | 14451.71 | 46.11 | 0.632 | 0.632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9478.99 | 9478.99 | 46.93 | 0.414 | 0.414 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14451.85 | 14451.85 | 46.11 | 0.632 | 0.632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9043.11 | 9043.11 | 44.77 | 0.395 | 0.395 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 26.83 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.53 | 0.00655 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.70 | 0.00614 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.24 | 11.24 | 1.88 | 1.88 | 11.2374 | 3.1150 | 11.2374 | 0.2772 | 0.3000 |
VAV_MID WITH REHEAT | 107.16 | 107.16 | 27.61 | 27.61 | 107.1626 | 30.6693 | 107.1626 | 0.2862 | 0.3000 |
VAV_TOP WITH REHEAT | 12.19 | 12.19 | 4.16 | 4.16 | 12.1929 | 4.1634 | 12.1929 | 0.3415 | 0.3000 |
CAV_BAS | 6.29 | 6.29 | 1.20 | 1.20 | 6.2929 | 6.2929 | 6.2929 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.02 | 22.02 | 0.34 | 0.34 | 22.0198 | 22.0196 | 22.0198 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.4982 | 0.4982 | 0.4982 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.76 | 4.76 | 0.16 | 0.16 | 4.7560 | 4.7560 | 4.7560 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4808 | 0.4808 | 0.4808 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19732.956 | 19732.956 | 2.010538 | 0.00017263 | 397.801 | 1/21 00:10:00 | 1/21 00:10:00 | 19732.96 | 19732.96 | 2.010538 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19805.72 | 19805.72 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 426803.305 | 426803.305 | 19.886668 | 0.00373386 | 9755.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 426803.31 | 426803.31 | 19.886668 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 231620.23 | 0.00 | 428225.03 | 428225.03 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 68555.123 | 68555.123 | 2.090306 | 0.00059975 | 1810.932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 68555.12 | 68555.12 | 2.090306 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 48039.26 | 0.00 | 68801.24 | 68801.24 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8192.392 | 8192.392 | 0.289088 | 0.00007167 | 203.787 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8192.39 | 8192.39 | 0.289088 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791460 | 49.8816 | 5355.56 | 0.00 | 8218.00 | 8218.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6106.422 | 6106.422 | 0.228872 | 0.00005342 | 148.717 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6106.42 | 6106.42 | 0.228872 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792448 | 49.9431 | 3860.45 | 0.00 | 6126.11 | 6126.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9902.333 | 9902.333 | 0.302197 | 0.00008663 | 261.471 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9902.33 | 9902.33 | 0.302197 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794121 | 50.0472 | 6936.71 | 0.00 | 9937.13 | 9937.13 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5245.727 | 5245.727 | 0.294740 | 0.00004589 | 115.009 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5245.73 | 5245.73 | 0.294740 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00787844 | 49.6565 | 2353.62 | 0.00 | 5263.88 | 5263.88 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 168366.216 | 168366.216 | 5.147791 | 0.00147294 | 4441.897 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 168366.22 | 168366.22 | 5.147791 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795860 | 50.1555 | 117846.66 | 0.00 | 168930.38 | 168930.38 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 111081.833 | 111081.833 | 3.396536 | 0.00097179 | 2930.516 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 111081.83 | 111081.83 | 3.396536 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795944 | 50.1606 | 77748.75 | 0.00 | 111453.44 | 111453.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 168367.364 | 168367.364 | 5.147826 | 0.00147295 | 4441.927 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 168367.36 | 168367.36 | 5.147826 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795860 | 50.1555 | 117847.47 | 0.00 | 168931.53 | 168931.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 102765.386 | 102765.386 | 3.141607 | 0.00089904 | 2711.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 102765.39 | 102765.39 | 3.141607 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795132 | 50.1102 | 71934.67 | 0.00 | 103110.99 | 103110.99 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20651.485 | 20651.485 | 0.631725 | 0.00018067 | 544.714 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20651.49 | 20651.49 | 0.631725 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796849 | 50.2169 | 14451.71 | 0.00 | 20719.81 | 20719.81 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13545.699 | 13545.699 | 0.414376 | 0.00011850 | 357.282 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13545.70 | 13545.70 | 0.414376 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796839 | 50.2163 | 9478.99 | 0.00 | 13590.47 | 13590.47 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20651.682 | 20651.682 | 0.631731 | 0.00018067 | 544.719 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20651.68 | 20651.68 | 0.631731 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796849 | 50.2169 | 14451.85 | 0.00 | 20720.01 | 20720.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12922.231 | 12922.231 | 0.395266 | 0.00011305 | 340.852 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12922.23 | 12922.23 | 0.395266 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796470 | 50.1933 | 9043.11 | 0.00 | 12965.05 | 12965.05 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 253257.027 | -999.000 | 11.237383 | 0.01077414 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 253257.03 | 232094.85 | 11.237383 | 28.07 | 16.88 | 0.00771661 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.5870 | 24.00 | 0.00729546 | 38.3574 | 150183.30 | 0.00 | 258153.45 | 246213.59 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 23267.276 | 23267.276 | 3.371215 | 0.00020355 | 408.761 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23267.28 | 23267.28 | 3.371215 | 6.95 | 6.85 | 0.00626738 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 75.2901 | 21.46 | 0.00711320 | 43.6455 | 18488.32 | 0.00 | 24633.73 | 24633.73 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2468239.937 | -999.000 | 107.162622 | 0.10500463 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2468239.94 | 2250427.17 | 107.162622 | 28.35 | 17.02 | 0.00777124 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.6855 | 24.00 | 0.00732962 | 38.5351 | 1405916.35 | 0.00 | 2515282.43 | 2383991.03 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 129148.100 | 129148.100 | 32.148787 | 0.00112984 | 2310.315 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 129148.10 | 129148.10 | 32.148787 | 9.39 | 8.24 | 0.00647422 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 78.9515 | 21.00 | 0.00797983 | 50.2872 | 526401.90 | 0.00 | 141353.81 | 141353.81 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 268981.276 | -999.000 | 12.192868 | 0.01144309 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 268981.28 | 247228.46 | 12.192868 | 27.76 | 16.74 | 0.00768084 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.8170 | 24.00 | 0.00729063 | 38.3325 | 162507.66 | 0.00 | 274257.14 | 262621.48 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 11108.251 | 11108.251 | 3.657860 | 0.00009718 | 199.986 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11108.25 | 11108.25 | 3.657860 | 10.23 | 8.82 | 0.00664798 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 69.3900 | 19.60 | 0.00795162 | 54.6409 | 61866.11 | 0.00 | 12299.36 | 12299.36 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 125326.599 | -999.000 | 6.292861 | 0.00533168 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 125326.60 | 113490.16 | 6.292861 | 26.19 | 16.25 | 0.00774264 | 11.38 | 9.72 | 0.00700000 | 35.44 | 0.00914698 | 20.36 | 19.0717 | 24.00 | 0.00740947 | 38.9499 | 83739.71 | 0.00 | 127943.95 | 122269.21 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 287976.177 | 287976.177 | 6.292861 | 0.00251934 | 6544.310 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 287976.18 | 287976.18 | 6.292861 | 1.20 | 1.20 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 19.0717 | 24.75 | 0.00607234 | 30.5768 | 0.00 | 0.00 | 247612.36 | 247612.36 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 453514.802 | 282433.882 | 22.019774 | 0.01110655 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 407340.34 | 403623.04 | -999.0 | 28.66 | 16.54 | 0.00707451 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704196 | 30.9971 | 373048.05 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10229.793 | 6367.579 | 0.498199 | 0.00025053 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 9183.93 | 9011.31 | -999.0 | 28.42 | 16.53 | 0.00715319 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00708708 | 31.1916 | 8300.36 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95275.301 | 60043.755 | 4.755965 | 0.00233329 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 85136.52 | 84383.57 | -999.0 | 28.15 | 16.36 | 0.00707040 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 79073.93 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9879.015 | 6146.908 | 0.480754 | 0.00024194 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 8870.29 | 8700.74 | -999.0 | 28.43 | 16.53 | 0.00715589 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00708865 | 31.1984 | 8153.77 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 453514.802 | 453514.802 | 22.019774 | 0.01110655 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 453514.80 | 453514.80 | 22.019774 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5368 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10229.793 | 10229.793 | 0.498199 | 0.00025053 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10229.79 | 10229.79 | 0.498199 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.1378 | 26.83 | 0.00699999 | 31.1182 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95275.301 | 95275.301 | 4.755965 | 0.00233329 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 95275.30 | 95275.30 | 4.755965 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2869 | 24.53 | 0.00654590 | 33.3770 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9879.015 | 9879.015 | 0.480754 | 0.00024194 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9879.01 | 9879.01 | 0.480754 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2516 | 23.70 | 0.00614020 | 32.9383 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 22.019774 | 0.10 | 0.10 | 0.00698574 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5368 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.498199 | 0.20 | 0.20 | 0.00697089 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.1378 | 26.83 | 0.00699999 | 31.1182 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.755965 | 0.21 | 0.21 | 0.00653033 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2869 | 24.53 | 0.00654590 | 33.3770 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.480754 | 0.20 | 0.20 | 0.00613800 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2516 | 23.70 | 0.00614020 | 32.9383 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19732.956 | 19732.956 | 2.010538 | 0.00017263 | 397.801 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 1.1982 | 1.222317 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19732.96 | 19732.96 | 1.0000 | 2.35993989 | 2.010538 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17261490 | 60.00 | 32.22 | 27.78 | 0.000 | 19732.96 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19805.72 | 19805.72 | 2.35993989 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 426803.305 | 426803.305 | 19.886668 | 0.00373386 | 9755.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 25.9159 | 26.437436 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 426803.31 | 426803.31 | 1.0000 | 23.34268135 | 19.886668 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.73348061 | 60.00 | 32.22 | 27.78 | 0.000 | 426803.31 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 231620.23 | 0.00 | 428225.03 | 428225.03 | 23.34268135 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.79 | 18.30 | 0.00800000 | 51405.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 68555.123 | 68555.123 | 2.090306 | 0.00059975 | 1810.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 4.1627 | 4.246503 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 68555.12 | 68555.12 | 1.0000 | 2.45357068 | 2.090306 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.59968894 | 60.00 | 32.22 | 27.78 | 0.000 | 68555.12 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 48039.26 | 0.00 | 68801.24 | 68801.24 | 2.45357068 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61101.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8192.392 | 8192.392 | 0.289088 | 0.00007167 | 203.787 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.4974 | 0.507461 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8192.39 | 8192.39 | 1.0000 | 0.33932730 | 0.289088 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07166331 | 60.00 | 32.22 | 27.78 | 0.000 | 8192.39 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00791460 | 21.00 | 0.00791460 | 49.8816 | 5355.56 | 0.00 | 8218.00 | 8218.00 | 0.33932730 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.55 | 20.14 | 0.00800000 | 57278.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6106.422 | 6106.422 | 0.228872 | 0.00005342 | 148.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.3708 | 0.378250 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6106.42 | 6106.42 | 1.0000 | 0.26864638 | 0.228872 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05341620 | 60.00 | 32.22 | 27.78 | 0.000 | 6106.42 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00792448 | 21.00 | 0.00792448 | 49.9431 | 3860.45 | 0.00 | 6126.11 | 6126.11 | 0.26864638 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.16 | 19.71 | 0.00800000 | 55863.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9902.333 | 9902.333 | 0.302197 | 0.00008663 | 261.471 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.6013 | 0.613379 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9902.33 | 9902.33 | 1.0000 | 0.35471413 | 0.302197 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08662109 | 60.00 | 32.22 | 27.78 | 0.000 | 9902.33 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794121 | 21.00 | 0.00794121 | 50.0472 | 6936.71 | 0.00 | 9937.13 | 9937.13 | 0.35471413 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61074.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5245.727 | 5245.727 | 0.294740 | 0.00004589 | 115.009 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.3185 | 0.324936 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 5245.73 | 5245.73 | 1.0000 | 0.34596126 | 0.294740 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.04588722 | 60.00 | 32.22 | 27.78 | 0.000 | 5245.73 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00787844 | 21.00 | 0.00787844 | 49.6565 | 2353.62 | 0.00 | 5263.88 | 5263.88 | 0.34596126 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.72 | 17.27 | 0.00800000 | 48275.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 168366.216 | 168366.216 | 5.147791 | 0.00147294 | 4441.897 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 10.2233 | 10.429092 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 168366.22 | 168366.22 | 1.0000 | 6.04240203 | 5.147791 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.47279085 | 60.00 | 32.22 | 27.78 | 0.000 | 168366.22 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795860 | 21.00 | 0.00795860 | 50.1555 | 117846.66 | 0.00 | 168930.38 | 168930.38 | 6.04240203 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 111081.833 | 111081.833 | 3.396536 | 0.00097179 | 2930.516 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 6.7450 | 6.880731 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 111081.83 | 111081.83 | 1.0000 | 3.98680413 | 3.396536 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.97169320 | 60.00 | 32.22 | 27.78 | 0.000 | 111081.83 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795944 | 21.00 | 0.00795944 | 50.1606 | 77748.75 | 0.00 | 111453.44 | 111453.44 | 3.98680413 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 168367.364 | 168367.364 | 5.147826 | 0.00147295 | 4441.927 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 10.2234 | 10.429163 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 168367.36 | 168367.36 | 1.0000 | 6.04244297 | 5.147826 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.47280089 | 60.00 | 32.22 | 27.78 | 0.000 | 168367.36 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795860 | 21.00 | 0.00795860 | 50.1555 | 117847.47 | 0.00 | 168931.53 | 168931.53 | 6.04244297 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102765.386 | 102765.386 | 3.141607 | 0.00089904 | 2711.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 6.2400 | 6.365586 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 102765.39 | 102765.39 | 1.0000 | 3.68757221 | 3.141607 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.89894472 | 60.00 | 32.22 | 27.78 | 0.000 | 102765.39 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795132 | 21.00 | 0.00795132 | 50.1102 | 71934.67 | 0.00 | 103110.99 | 103110.99 | 3.68757221 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20651.485 | 20651.485 | 0.631725 | 0.00018067 | 544.714 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 1.2540 | 1.279213 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20651.49 | 20651.49 | 1.0000 | 0.74150915 | 0.631725 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.18064977 | 60.00 | 32.22 | 27.78 | 0.000 | 20651.49 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796849 | 21.00 | 0.00796849 | 50.2169 | 14451.71 | 0.00 | 20719.81 | 20719.81 | 0.74150915 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13545.699 | 13545.699 | 0.414376 | 0.00011850 | 357.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.8225 | 0.839060 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13545.70 | 13545.70 | 1.0000 | 0.48638882 | 0.414376 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11849160 | 60.00 | 32.22 | 27.78 | 0.000 | 13545.70 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796839 | 21.00 | 0.00796839 | 50.2163 | 9478.99 | 0.00 | 13590.47 | 13590.47 | 0.48638882 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20651.682 | 20651.682 | 0.631731 | 0.00018067 | 544.719 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 1.2540 | 1.279225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20651.68 | 20651.68 | 1.0000 | 0.74151620 | 0.631731 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.18065150 | 60.00 | 32.22 | 27.78 | 0.000 | 20651.68 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796849 | 21.00 | 0.00796849 | 50.2169 | 14451.85 | 0.00 | 20720.01 | 20720.01 | 0.74151620 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12922.231 | 12922.231 | 0.395266 | 0.00011305 | 340.852 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.7846 | 0.800441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12922.23 | 12922.23 | 1.0000 | 0.46395717 | 0.395266 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11303778 | 60.00 | 32.22 | 27.78 | 0.000 | 12922.23 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796470 | 21.00 | 0.00796470 | 50.1933 | 9043.11 | 0.00 | 12965.05 | 12965.05 | 0.46395717 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 253257.027 | -999.000 | 11.237383 | 0.01077414 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1848 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.237383 | 13.19027651 | 4197.9300 | 999.8980 | 132.54001884 | 12.27 | 6.67 | 5.60 | 3115804.84 | 8.1281 | 8.128142 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 253257.03 | 232094.85 | 1.0000 | 13.19027651 | 11.237383 | 28.07 | 16.88 | 0.00771661 | 47906.5 | 11.00 | 9.55 | 0.00700000 | 28706.3 | 10.77304030 | 6.67 | 12.27 | 5.60 | 24154.356 | 229102.67 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 22.5870 | 24.00 | 0.00729546 | 24.00 | 0.00729546 | 38.3574 | 150183.30 | 0.00 | 258153.45 | 246213.59 | 13.19027651 | 28.07 | 17.15 | 0.00771661 | 47906.5 | 9.75 | 9.59 | 0.00735727 | 28335.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23267.276 | 23267.276 | 3.371215 | 0.00020355 | 408.761 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.237383 | 13.19027651 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 1.4128 | 1.441243 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23267.28 | 23267.28 | 1.0000 | 3.95708295 | 3.371215 | 6.95 | 6.85 | 0.00626738 | 22737.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.20353152 | 60.00 | 32.22 | 27.78 | 0.000 | 23267.28 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 75.2901 | 8.92 | 0.00686165 | 21.46 | 0.00711320 | 43.6455 | 18488.32 | 0.00 | 24633.73 | 24633.73 | 3.95708295 | 2.80 | 2.80 | 0.00626738 | 18520.5 | 8.92 | 7.99 | 0.00626738 | 24745.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2468239.937 | -999.000 | 107.162622 | 0.10500463 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2863 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.162622 | 125.78592763 | 4197.9300 | 999.8980 | 132.54001884 | 12.27 | 6.67 | 5.60 | 3115804.84 | 79.2168 | 79.216769 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2468239.94 | 2250427.17 | 1.0000 | 125.78592763 | 107.162622 | 28.35 | 17.02 | 0.00777124 | 48329.0 | 11.00 | 9.55 | 0.00700000 | 28706.4 | 104.99392121 | 6.67 | 12.27 | 5.60 | 230342.259 | 2237897.68 | 42.00 | 0.00915790 | 22.26 | 25.38195000 | 23.6855 | 24.00 | 0.00732962 | 24.00 | 0.00732962 | 38.5351 | 1405916.35 | 0.00 | 2515282.43 | 2383991.03 | 125.78592763 | 28.35 | 17.29 | 0.00777124 | 48329.0 | 9.75 | 9.59 | 0.00735689 | 28332.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 129148.100 | 129148.100 | 32.148787 | 0.00112984 | 2310.315 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.162622 | 125.78592763 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 7.8420 | 7.999808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 129148.10 | 129148.10 | 1.0000 | 37.73577829 | 32.148787 | 9.39 | 8.24 | 0.00647422 | 25744.3 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.12972866 | 60.00 | 32.22 | 27.78 | 0.000 | 129148.10 | 6.30 | 0.00607234 | 6.30 | 25.38195000 | 78.9515 | 21.00 | 0.00798165 | 21.00 | 0.00797983 | 50.2872 | 526401.90 | 0.00 | 141353.81 | 141353.81 | 37.73577829 | 2.80 | 2.80 | 0.00647422 | 19038.9 | 6.48 | 6.48 | 0.00647422 | 22784.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 268981.276 | -999.000 | 12.192868 | 0.01144309 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1183 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.192868 | 14.31181094 | 4197.9300 | 999.8980 | 132.54001884 | 12.27 | 6.67 | 5.60 | 3115804.84 | 8.6328 | 8.632802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 268981.28 | 247228.46 | 1.0000 | 14.31181094 | 12.192868 | 27.76 | 16.74 | 0.00768084 | 47500.5 | 11.00 | 9.55 | 0.00700000 | 28706.1 | 11.44191798 | 6.67 | 12.27 | 5.60 | 26208.137 | 242773.14 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 20.8170 | 24.00 | 0.00729063 | 24.00 | 0.00729063 | 38.3325 | 162507.66 | 0.00 | 274257.14 | 262621.48 | 14.31181094 | 27.76 | 17.01 | 0.00768084 | 47500.5 | 9.75 | 9.60 | 0.00735809 | 28337.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 11108.251 | 11108.251 | 3.657860 | 0.00009718 | 199.986 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 12.192868 | 14.31181094 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 0.6745 | 0.688077 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11108.25 | 11108.25 | 1.0000 | 4.29354328 | 3.657860 | 10.23 | 8.82 | 0.00664798 | 27027.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.09716992 | 60.00 | 32.22 | 27.78 | 0.000 | 11108.25 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 69.3900 | 19.12 | 0.00795291 | 19.60 | 0.00795162 | 54.6409 | 61866.11 | 0.00 | 12299.36 | 12299.36 | 4.29354328 | 2.80 | 2.80 | 0.00664798 | 19474.4 | 5.62 | 5.62 | 0.00664798 | 22339.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 125326.599 | -999.000 | 6.292861 | 0.00533168 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2332 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 6.292861 | 7.38646896 | 4197.9300 | 999.8980 | 132.54001884 | 12.27 | 6.67 | 5.60 | 3115804.84 | 4.0223 | 4.022287 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 125326.60 | 113490.16 | 1.0000 | 7.38646896 | 6.292861 | 26.19 | 16.25 | 0.00774264 | 46059.5 | 11.38 | 9.72 | 0.00700000 | 29092.4 | 5.33113936 | 6.67 | 12.27 | 5.60 | 10670.517 | 114656.08 | 35.44 | 0.00914698 | 20.36 | 1.20015641 | 19.0717 | 24.00 | 0.00740947 | 24.00 | 0.00740947 | 38.9499 | 83739.71 | 0.00 | 127943.95 | 122269.21 | 7.38646896 | 26.19 | 16.51 | 0.00774264 | 46059.5 | 9.95 | 9.77 | 0.00743771 | 28738.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 287976.177 | 287976.177 | 6.292861 | 0.00251934 | 6544.310 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 6.292861 | 7.38646896 | 4197.9300 | 999.8980 | 14.12194689 | 54.44 | 82.22 | 27.78 | 1646880.20 | 17.4862 | 17.838080 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 287976.18 | 287976.18 | 1.0000 | 7.38646896 | 6.292861 | 1.20 | 1.20 | 0.00607234 | 16407.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.51908422 | 60.00 | 32.22 | 27.78 | 0.000 | 287976.18 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 19.0717 | 0.00 | 0.00607234 | 24.75 | 0.00607234 | 30.5768 | 0.00 | 0.00 | 247612.36 | 247612.36 | 7.38646896 | 12.80 | 9.56 | 0.00607234 | 28193.0 | 45.79 | 21.50 | 0.00607234 | 61715.4 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 453514.802 | 282433.882 | 22.019774 | 0.01110655 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9912 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 407340.34 | 403623.04 | 0.8982 | -999.0 | -999.0 | 28.66 | 16.54 | 0.00707451 | 46867.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407340.34 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704196 | 27.00 | 0.00704196 | 30.9971 | 373048.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10229.793 | 6367.579 | 0.498199 | 0.00025053 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1374 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | Sensible | 9183.93 | 9011.31 | 0.8978 | -999.0 | -999.0 | 28.42 | 16.53 | 0.00715319 | 46824.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9183.93 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00708708 | 27.00 | 0.00708708 | 31.1916 | 8300.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 95275.301 | 60043.755 | 4.755965 | 0.00233329 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9835 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 85136.52 | 84383.57 | 0.8936 | -999.0 | -999.0 | 28.15 | 16.36 | 0.00707040 | 46336.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85136.52 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 79073.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9879.015 | 6146.908 | 0.480754 | 0.00024194 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1425 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | Sensible | 8870.29 | 8700.74 | 0.8979 | -999.0 | -999.0 | 28.43 | 16.53 | 0.00715589 | 46839.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8870.29 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00708865 | 27.00 | 0.00708865 | 31.1984 | 8153.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 453514.802 | 453514.802 | 22.019774 | 0.01110655 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 453514.80 | 453514.80 | 1.0000 | 25.84649048 | 22.019774 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 453514.80 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5368 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10229.793 | 10229.793 | 0.498199 | 0.00025053 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10229.79 | 10229.79 | 1.0000 | 0.58477855 | 0.498199 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10229.79 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.1378 | 0.00 | 0.00699999 | 26.83 | 0.00699999 | 31.1182 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 95275.301 | 95275.301 | 4.755965 | 0.00233329 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 95275.30 | 95275.30 | 1.0000 | 5.58248271 | 4.755965 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95275.30 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.2869 | 0.00 | 0.00654590 | 24.53 | 0.00654590 | 33.3770 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9879.015 | 9879.015 | 0.480754 | 0.00024194 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9879.01 | 9879.01 | 1.0000 | 0.56430170 | 0.480754 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9879.01 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2516 | 0.00 | 0.00614020 | 23.70 | 0.00614020 | 32.9383 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 22.019774 | 25.84649048 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 25.84649048 | 22.019774 | 0.10 | 0.10 | 0.00698574 | 17569.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5368 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.498199 | 0.58477855 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.58477855 | 0.498199 | 0.20 | 0.20 | 0.00697089 | 17635.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.1378 | 0.00 | 0.00699999 | 26.83 | 0.00699999 | 31.1182 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.755965 | 5.58248271 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.58248271 | 4.755965 | 0.21 | 0.21 | 0.00653033 | 16542.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.2869 | 0.00 | 0.00654590 | 24.53 | 0.00654590 | 33.3770 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.480754 | 0.56430170 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.56430170 | 0.480754 | 0.20 | 0.20 | 0.00613800 | 15558.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2516 | 0.00 | 0.00614020 | 23.70 | 0.00614020 | 32.9383 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5444.50 | 1665.17 | 1665.17 |
CORE_BOTTOM | 5399.33 | 31.33 | 15.83 |
CORE_MID | 4649.67 | 513.67 | 22.33 |
CORE_TOP | 4295.67 | 1117.67 | 35.67 |
PERIMETER_BOT_ZN_3 | 4414.17 | 1223.67 | 237.83 |
PERIMETER_BOT_ZN_2 | 4649.33 | 1104.00 | 313.00 |
PERIMETER_BOT_ZN_1 | 5185.33 | 846.33 | 414.83 |
PERIMETER_BOT_ZN_4 | 5308.50 | 1038.83 | 685.33 |
PERIMETER_MID_ZN_3 | 3946.83 | 2015.17 | 371.00 |
PERIMETER_MID_ZN_2 | 3578.67 | 1587.50 | 428.17 |
PERIMETER_MID_ZN_1 | 4974.50 | 1112.67 | 486.50 |
PERIMETER_MID_ZN_4 | 4327.00 | 1749.00 | 466.00 |
PERIMETER_TOP_ZN_3 | 4001.67 | 2258.83 | 577.33 |
PERIMETER_TOP_ZN_2 | 4277.83 | 1952.50 | 562.83 |
PERIMETER_TOP_ZN_1 | 4822.00 | 1379.17 | 564.17 |
PERIMETER_TOP_ZN_4 | 4264.33 | 2002.33 | 611.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2080.83 | 2080.83 |
DATACENTER_MID_ZN_6 | 5937.67 | 704.83 | 704.83 |
DATACENTER_TOP_ZN_6 | 5886.33 | 1010.50 | 980.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 90.50 | 0.00 | 5.00 |
CORE_BOTTOM | 0.00 | 6.50 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.50 | 0.33 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 99.67 | 0.00 | 39.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 105.67 | 0.00 | 62.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 166.00 | 0.00 | 88.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 348.17 | 0.00 | 117.83 |
PERIMETER_MID_ZN_3 | 0.17 | 84.33 | 0.00 | 34.50 |
PERIMETER_MID_ZN_2 | 0.17 | 118.17 | 0.00 | 67.17 |
PERIMETER_MID_ZN_1 | 0.00 | 156.00 | 0.00 | 84.83 |
PERIMETER_MID_ZN_4 | 0.00 | 164.83 | 0.00 | 57.00 |
PERIMETER_TOP_ZN_3 | 2.50 | 103.17 | 0.00 | 41.33 |
PERIMETER_TOP_ZN_2 | 1.50 | 134.67 | 0.00 | 69.83 |
PERIMETER_TOP_ZN_1 | 0.67 | 159.83 | 0.00 | 81.00 |
PERIMETER_TOP_ZN_4 | 0.67 | 167.83 | 0.00 | 59.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 326.33 | 0.00 | 275.33 |
DATACENTER_MID_ZN_6 | 0.00 | 390.83 | 0.00 | 351.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 236.67 | 0.00 | 209.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1280.00 | 0.00 | 918.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.67 | 1768.33 | 0.00 | 1129.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.50 | 149.60 | 6779.02 | 0.538 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.23 | 134.35 | 6849.35 | 0.478 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.23 | 134.35 | 6849.35 | 0.453 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.23 | 134.35 | 6849.35 | 0.442 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.93 | 16.87 | 860.00 | 0.604 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.47 | 10.87 | 554.22 | 0.743 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.93 | 16.87 | 860.02 | 0.818 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.47 | 10.87 | 554.22 | 1.068 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.93 | 16.87 | 860.00 | 0.642 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.90 | 10.87 | 554.22 | 0.829 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.93 | 16.87 | 860.02 | 0.914 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.47 | 10.87 | 554.22 | 0.927 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.93 | 16.87 | 860.00 | 0.644 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.47 | 10.87 | 554.22 | 0.847 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.93 | 16.87 | 860.02 | 0.880 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.47 | 10.87 | 554.22 | 0.906 | 0.050 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.34 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.50 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.90 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.34 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.50 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.90 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.34 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1019.15 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23751772.38 | 0.00 | 23751772.38 | 0.00 | 23751772.38 | 37848132.68 | 3262.62 | 5497.38 | 0.00 | 656.87 |
CORE_BOTTOM | 23196299.48 | 0.00 | 23196299.48 | 0.00 | 23196299.48 | 33990283.35 | 7614.12 | 90.43 | 1055.45 | 1194.97 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 8035.47 | 68.74 | 655.79 | 840.25 |
CORE_TOP | 20370777.41 | 0.00 | 20370777.41 | 0.00 | 20370777.41 | 33990283.35 | 8522.61 | 51.28 | 186.12 | 826.79 |
PERIMETER_BOT_ZN_3 | 3630840.49 | 0.00 | 3630840.49 | 135485.55 | 3766326.04 | 4267819.30 | 4053.81 | 107.11 | 4599.09 | 1194.97 |
PERIMETER_BOT_ZN_2 | 2865831.43 | 0.00 | 2865831.43 | 90323.64 | 2956155.07 | 2750345.05 | 2889.81 | 92.76 | 5777.42 | 1194.97 |
PERIMETER_BOT_ZN_1 | 4708120.66 | 0.00 | 4708120.66 | 135485.55 | 4843606.21 | 4267912.63 | 2699.88 | 31.89 | 6028.22 | 1194.97 |
PERIMETER_BOT_ZN_4 | 4146128.47 | 0.00 | 4146128.47 | 90323.64 | 4236452.11 | 2750345.05 | 2286.43 | 0.35 | 6473.22 | 1194.97 |
PERIMETER_MID_ZN_3 | 36399095.95 | 0.00 | 36399095.95 | 317743.67 | 36716839.62 | 42678193.03 | 4021.57 | 93.98 | 4644.45 | 840.25 |
PERIMETER_MID_ZN_2 | 31220090.10 | 0.00 | 31220090.10 | 211828.97 | 31431919.06 | 27503450.52 | 2924.41 | 46.29 | 5789.30 | 1749.25 |
PERIMETER_MID_ZN_1 | 49995834.18 | 0.00 | 49995834.18 | 317743.67 | 50313577.85 | 42679126.28 | 2933.01 | 18.22 | 5808.77 | 840.25 |
PERIMETER_MID_ZN_4 | 34038362.01 | 0.00 | 34038362.01 | 211828.97 | 34250190.98 | 27503450.52 | 2853.50 | 29.10 | 5877.40 | 840.25 |
PERIMETER_TOP_ZN_3 | 3681260.10 | 0.00 | 3681260.10 | 394502.81 | 4075762.90 | 4267819.30 | 3578.24 | 59.50 | 5122.26 | 826.79 |
PERIMETER_TOP_ZN_2 | 3075732.23 | 0.00 | 3075732.23 | 263001.69 | 3338733.92 | 2750345.05 | 2888.18 | 20.45 | 5851.37 | 826.79 |
PERIMETER_TOP_ZN_1 | 4859689.80 | 0.00 | 4859689.80 | 394502.81 | 5254192.61 | 4267912.63 | 2850.81 | 5.07 | 5904.12 | 826.79 |
PERIMETER_TOP_ZN_4 | 3343207.03 | 0.00 | 3343207.03 | 263001.69 | 3606208.72 | 2750345.05 | 2838.77 | 16.36 | 5904.87 | 826.79 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.38E+10 | 0.00 | 0.38E+10 | 12358080.11 | 0.38E+10 | 0.50E+10 | 8760.00 | 8760.00 | 6815.88 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9775 | 0.0000 | 0.9775 | 0.0000 | 0.9775 | 1.2002 | 1102.49 | 4840.51 | 0.00 |
CORE_BOTTOM | 0.8797 | 0.0000 | 0.8797 | 0.0000 | 0.8797 | 1.0778 | 4816.44 | 89.15 | 1037.41 |
CORE_MID | 8.3400 | 0.0000 | 8.3400 | 0.0000 | 8.3400 | 10.7782 | 5224.12 | 68.65 | 650.22 |
CORE_TOP | 0.8130 | 0.0000 | 0.8130 | 0.0000 | 0.8130 | 1.0778 | 5707.83 | 51.18 | 183.99 |
PERIMETER_BOT_ZN_3 | 0.1392 | 0.0000 | 0.1392 | 0.0039 | 0.1431 | 0.1353 | 2403.23 | 99.49 | 3440.28 |
PERIMETER_BOT_ZN_2 | 0.1105 | 0.0000 | 0.1105 | 0.0026 | 0.1130 | 0.0872 | 1253.42 | 91.89 | 4597.69 |
PERIMETER_BOT_ZN_1 | 0.1888 | 0.0000 | 0.1888 | 0.0039 | 0.1927 | 0.1353 | 1057.42 | 27.30 | 4858.28 |
PERIMETER_BOT_ZN_4 | 0.1587 | 0.0000 | 0.1587 | 0.0026 | 0.1613 | 0.0872 | 661.30 | 0.05 | 5281.65 |
PERIMETER_MID_ZN_3 | 1.4811 | 0.0000 | 1.4811 | 0.0091 | 1.4902 | 1.3533 | 2035.83 | 92.82 | 3814.36 |
PERIMETER_MID_ZN_2 | 1.2324 | 0.0000 | 1.2324 | 0.0062 | 1.2387 | 0.8721 | 892.94 | 25.40 | 4115.66 |
PERIMETER_MID_ZN_1 | 2.1096 | 0.0000 | 2.1096 | 0.0091 | 2.1187 | 1.3533 | 952.33 | 18.02 | 4972.65 |
PERIMETER_MID_ZN_4 | 1.3784 | 0.0000 | 1.3784 | 0.0060 | 1.3845 | 0.8721 | 874.21 | 29.02 | 5039.77 |
PERIMETER_TOP_ZN_3 | 0.1488 | 0.0000 | 0.1488 | 0.0113 | 0.1600 | 0.1353 | 1584.26 | 59.21 | 4299.53 |
PERIMETER_TOP_ZN_2 | 0.1259 | 0.0000 | 0.1259 | 0.0075 | 0.1334 | 0.0872 | 896.44 | 20.29 | 5026.27 |
PERIMETER_TOP_ZN_1 | 0.2033 | 0.0000 | 0.2033 | 0.0113 | 0.2146 | 0.1353 | 859.45 | 5.04 | 5078.51 |
PERIMETER_TOP_ZN_4 | 0.1347 | 0.0000 | 0.1347 | 0.0075 | 0.1422 | 0.0872 | 848.16 | 16.29 | 5078.55 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 151.2295 | 0.0000 | 151.2295 | 0.3545 | 151.5840 | 158.4706 | 5943.00 | 5943.00 | 5418.95 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 53109312.43 | 0.00 | 53109312.43 | 48026705.38 | 2280.40 | 0.00 | 6479.60 | 1194.97 |
VAV_MID WITH REHEAT | 0.50E+09 | 0.00 | 0.50E+09 | 0.48E+09 | 2771.46 | 0.00 | 5988.54 | 840.25 |
VAV_TOP WITH REHEAT | 48677614.31 | 0.00 | 48677614.31 | 48026705.38 | 2809.27 | 0.00 | 5950.73 | 826.79 |
CAV_BAS | 32724534.22 | 0.00 | 32724534.22 | 37848132.68 | 3262.62 | 0.00 | 5497.38 | 656.87 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.0348 | 0.0000 | 2.0348 | 1.5229 | 658.37 | 0.00 | 5284.63 |
VAV_MID WITH REHEAT | 20.1005 | 0.0000 | 20.1005 | 15.2292 | 794.71 | 0.00 | 5148.29 |
VAV_TOP WITH REHEAT | 1.9643 | 0.0000 | 1.9643 | 1.5229 | 819.07 | 0.00 | 5123.93 |
CAV_BAS | 1.3468 | 0.0000 | 1.3468 | 1.2002 | 1102.49 | 0.00 | 4840.51 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6479.60 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5988.54 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5950.73 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5497.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2886 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 23.2046 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2787 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6537 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
Electricity:Building | 18602.60 | 225715.65 | 28-MAY-17:10 | 1157640.89 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18602.60 | 225715.65 | 28-MAY-17:10 | 1157640.89 | 29-DEC-17:00 |
InteriorLights:Electricity | 3926.20 | 18459.50 | 01-JAN-09:40 | 385834.94 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3926.20 | 18459.50 | 01-JAN-09:40 | 385834.94 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 3926.20 | 18459.50 | 01-JAN-09:40 | 385834.94 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3926.20 | 18459.50 | 01-JAN-09:40 | 385834.94 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.67 | 627.57 | 26-MAR-17:10 | 4748.47 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.31 | 68.40 | 01-JAN-09:40 | 2587.92 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.31 | 68.40 | 01-JAN-09:40 | 2587.92 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.52 | 404.43 | 28-MAY-17:10 | 3060.10 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.08 | 44.08 | 01-JAN-07:50 | 1667.75 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.08 | 44.08 | 01-JAN-07:50 | 1667.75 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.41 | 627.58 | 12-MAR-17:10 | 4748.56 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.05 | 68.40 | 01-JAN-08:00 | 2587.98 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.05 | 68.40 | 01-JAN-08:00 | 2587.98 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.52 | 404.43 | 12-MAR-17:10 | 3060.09 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.08 | 44.08 | 01-JAN-09:40 | 1667.75 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.08 | 44.08 | 01-JAN-09:40 | 1667.75 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 536.33 | 6275.73 | 26-MAR-17:10 | 47484.70 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.68 | 684.02 | 01-JAN-09:30 | 25879.19 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 172.68 | 684.02 | 01-JAN-09:30 | 25879.19 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 344.97 | 4044.32 | 21-MAY-17:10 | 30600.95 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.62 | 440.81 | 01-JAN-07:50 | 16677.53 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.62 | 440.81 | 01-JAN-07:50 | 16677.53 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 533.92 | 6275.83 | 12-MAR-17:10 | 47485.60 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.26 | 684.04 | 01-JAN-08:00 | 25879.75 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.26 | 684.04 | 01-JAN-08:00 | 25879.75 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 344.94 | 4044.30 | 12-MAR-17:10 | 30600.86 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 110.59 | 440.81 | 01-JAN-09:30 | 16677.53 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 110.59 | 440.81 | 01-JAN-09:30 | 16677.53 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.63 | 627.57 | 26-MAR-17:10 | 4748.47 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.27 | 68.40 | 01-JAN-09:30 | 2587.92 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.27 | 68.40 | 01-JAN-09:30 | 2587.92 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.50 | 404.43 | 21-MAY-17:10 | 3060.10 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.06 | 44.08 | 01-JAN-07:50 | 1667.75 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.06 | 44.08 | 01-JAN-07:50 | 1667.75 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.39 | 627.58 | 12-MAR-17:10 | 4748.56 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.02 | 68.40 | 01-JAN-08:00 | 2587.98 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.02 | 68.40 | 01-JAN-08:00 | 2587.98 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.49 | 404.43 | 12-MAR-17:10 | 3060.09 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.06 | 44.08 | 01-JAN-09:30 | 1667.75 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.06 | 44.08 | 01-JAN-09:30 | 1667.75 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6677.31 | 8164.98 | 05-JAN-05:50 | 592150.85 | 22-JUN-15:40 |
HeatRejection:Electricity | 2030.83 | 4496.01 | 05-JAN-07:00 | 95095.80 | 06-MAR-15:30 |
General:HeatRejection:Electricity | 2030.83 | 4496.01 | 05-JAN-07:00 | 95095.80 | 06-MAR-15:30 |
Electricity:HVAC | 6442.66 | 81548.48 | 16-JAN-05:00 | 480204.59 | 07-JUL-14:50 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118535.44 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 80.17 | 1421.04 | 01-JAN-00:10 | 5057.48 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
ElectricityPurchased:Plant | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
Cogeneration:ElectricityPurchased | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
ElectricityNet:Plant | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
Cogeneration:ElectricityNet | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
General:Cogeneration:ElectricityNet | 34272.98 | 373567.02 | 01-JAN-10:10 | 2225472.94 | 07-AUG-15:20 |
Fans:Electricity | 2831.42 | 42739.77 | 01-JAN-10:40 | 282346.45 | 07-JUN-14:10 |
General:Fans:Electricity | 2831.42 | 42739.77 | 01-JAN-10:40 | 282346.45 | 07-JUN-14:10 |
ExteriorLights:Electricity | 695.80 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 695.80 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 7124.55 | 31392.98 | 01-JAN-05:00 | 613938.38 | 07-AUG-15:40 |
General:Cooling:Electricity | 7124.55 | 31392.98 | 01-JAN-05:00 | 613938.38 | 07-AUG-15:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 81.62 | 0.00 | 12-JAN-13:10 | 28629.27 | 22-DEC-06:00 |
General:Humidifier:Electricity | 81.62 | 0.00 | 12-JAN-13:10 | 28629.27 | 22-DEC-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 971.38 | 3553.43 | 01-JAN-00:10 | 61369.93 | 12-JUN-16:00 |
General:Pumps:Electricity | 971.38 | 3553.43 | 01-JAN-00:10 | 61369.93 | 12-JUN-16:00 |
WIRED_LTG_ELECTRICITY | 110.33 | 0.00 | 01-JAN-00:10 | 10841.96 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 700.59 | 8146.58 | 02-APR-15:50 | 614845.52 | 02-JAN-06:10 |
NaturalGas:Plant | 700.59 | 8146.58 | 02-APR-15:50 | 614845.52 | 02-JAN-06:10 |
Heating:NaturalGas | 64.19 | 0.00 | 01-JAN-00:10 | 606698.94 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 64.19 | 0.00 | 01-JAN-00:10 | 606698.94 | 02-JAN-06:10 |
WaterSystems:NaturalGas | 636.39 | 8146.58 | 03-JAN-05:20 | 75311.95 | 19-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 636.39 | 8146.58 | 03-JAN-05:20 | 75311.95 | 19-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 38075.52 | 155340.40 | 01-JAN-05:00 | 3347856.96 | 28-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 38075.52 | 155340.40 | 01-JAN-05:00 | 3347856.96 | 28-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 38075.52 | 155340.40 | 01-JAN-05:00 | 3347856.96 | 28-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 23380.20 | 0.00 | 11-MAR-00:10 | 0.00 | 07-JUN-15:40 |
Water:HVAC | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:Water | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:Water | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
MainsWater:Facility | 23380.20 | 0.00 | 11-MAR-00:10 | 0.00 | 07-JUN-15:40 |
MainsWater:HVAC | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:MainsWater | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:MainsWater | 30.36 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Water:Plant | 23349.84 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 23349.84 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 21069.67 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
General:HeatRejection:Water | 21069.67 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
HeatRejection:MainsWater | 21069.67 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
General:HeatRejection:MainsWater | 21069.67 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUN-15:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 136688.86 | 215681.47 | 01-JAN-05:50 | 13482373.91 | 22-JUN-15:40 |
EnergyTransfer:Building | 24934.41 | 90433.59 | 03-JAN-05:50 | 1897789.06 | 28-APR-15:40 |
EnergyTransfer:Zone:BASEMENT | 826.16 | 0.00 | 01-JAN-00:10 | 80842.06 | 13-NOV-06:10 |
Heating:EnergyTransfer | 35.62 | 0.00 | 03-JAN-19:00 | 339160.54 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.64 | 0.00 | 01-JAN-00:10 | 34262.30 | 10-JUN-16:10 |
General:Heating:EnergyTransfer | 35.62 | 0.00 | 03-JAN-19:00 | 339160.54 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.64 | 0.00 | 01-JAN-00:10 | 34262.30 | 10-JUN-16:10 |
Cooling:EnergyTransfer | 24898.79 | 89794.92 | 01-JAN-08:40 | 1897789.06 | 28-APR-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 821.52 | 0.00 | 01-JAN-00:10 | 80842.06 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 24898.79 | 89794.92 | 01-JAN-08:40 | 1897789.06 | 28-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 821.52 | 0.00 | 01-JAN-00:10 | 80842.06 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 817.14 | 0.00 | 01-JAN-00:10 | 63098.80 | 07-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 817.14 | 0.00 | 01-JAN-00:10 | 63098.80 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 817.14 | 0.00 | 01-JAN-00:10 | 63098.80 | 07-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 6333.54 | 0.00 | 01-JAN-00:10 | 493007.95 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6333.54 | 0.00 | 01-JAN-00:10 | 493007.95 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6333.54 | 0.00 | 01-JAN-00:10 | 493007.95 | 12-JUN-16:00 |
EnergyTransfer:Zone:CORE_TOP | 645.32 | 0.00 | 01-JAN-00:10 | 61629.71 | 12-JUN-15:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.43 | 0.00 | 01-JAN-00:10 | 59056.46 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.43 | 0.00 | 01-JAN-00:10 | 59056.46 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 644.88 | 0.00 | 01-JAN-00:10 | 61629.71 | 12-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 644.88 | 0.00 | 01-JAN-00:10 | 61629.71 | 12-JUN-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.43 | 0.00 | 01-JAN-00:10 | 15785.94 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.43 | 0.00 | 01-JAN-00:10 | 15785.94 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.43 | 0.00 | 01-JAN-00:10 | 15785.94 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.74 | 0.00 | 01-JAN-00:10 | 15436.63 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.74 | 0.00 | 01-JAN-00:10 | 15436.63 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.74 | 0.00 | 01-JAN-00:10 | 15436.63 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 180.10 | 0.00 | 01-JAN-00:10 | 20462.90 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1144.89 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1144.89 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 180.10 | 0.00 | 01-JAN-00:10 | 20462.90 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 180.10 | 0.00 | 01-JAN-00:10 | 20462.90 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 154.66 | 0.00 | 01-JAN-00:10 | 19942.72 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 154.66 | 0.00 | 01-JAN-00:10 | 19942.72 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 154.66 | 0.00 | 01-JAN-00:10 | 19942.72 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1155.91 | 0.00 | 01-JAN-00:10 | 155027.07 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.84 | 0.00 | 01-JAN-00:10 | 79564.06 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.84 | 0.00 | 01-JAN-00:10 | 79564.06 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1152.07 | 0.00 | 01-JAN-00:10 | 155027.07 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1152.07 | 0.00 | 01-JAN-00:10 | 155027.07 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1009.23 | 0.00 | 01-JAN-00:10 | 157324.63 | 04-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.35 | 0.00 | 01-JAN-00:10 | 47374.84 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.35 | 0.00 | 01-JAN-00:10 | 47374.84 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1007.89 | 0.00 | 01-JAN-00:10 | 157324.63 | 04-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1007.89 | 0.00 | 01-JAN-00:10 | 157324.63 | 04-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1646.34 | 0.00 | 01-JAN-00:10 | 204809.15 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.51 | 0.00 | 01-JAN-00:10 | 48542.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.51 | 0.00 | 01-JAN-00:10 | 48542.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1645.83 | 0.00 | 01-JAN-00:10 | 204809.15 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1645.83 | 0.00 | 01-JAN-00:10 | 204809.15 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.89 | 0.00 | 01-JAN-00:10 | 176458.62 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.81 | 0.00 | 01-JAN-00:10 | 35231.62 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.81 | 0.00 | 01-JAN-00:10 | 35231.62 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.08 | 0.00 | 01-JAN-00:10 | 176458.62 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1084.08 | 0.00 | 01-JAN-00:10 | 176458.62 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.98 | 0.00 | 01-JAN-00:10 | 16976.69 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.05 | 0.00 | 01-JAN-00:10 | 16199.72 | 02-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.05 | 0.00 | 01-JAN-00:10 | 16199.72 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 119.93 | 0.00 | 01-JAN-00:10 | 16976.69 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 119.93 | 0.00 | 01-JAN-00:10 | 16976.69 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 104.62 | 0.00 | 01-JAN-00:10 | 16633.55 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.80 | 0.00 | 01-JAN-00:10 | 10142.22 | 02-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.80 | 0.00 | 01-JAN-00:10 | 10142.22 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 103.82 | 0.00 | 01-JAN-00:10 | 16633.55 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 103.82 | 0.00 | 01-JAN-00:10 | 16633.55 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 166.89 | 0.00 | 01-JAN-00:10 | 22160.12 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.60 | 0.00 | 01-JAN-00:10 | 13372.88 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.60 | 0.00 | 01-JAN-00:10 | 13372.88 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 166.29 | 0.00 | 01-JAN-00:10 | 22160.12 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 166.29 | 0.00 | 01-JAN-00:10 | 22160.12 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 111.42 | 0.00 | 01-JAN-00:10 | 18694.58 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.60 | 0.00 | 01-JAN-00:10 | 8852.54 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.60 | 0.00 | 01-JAN-00:10 | 8852.54 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 110.82 | 0.00 | 01-JAN-00:10 | 18694.58 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 110.82 | 0.00 | 01-JAN-00:10 | 18694.58 | 06-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 147.76 | 0.00 | 01-JAN-00:10 | 18651.49 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.70 | 0.00 | 01-JAN-00:10 | 4128.39 | 31-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.70 | 0.00 | 01-JAN-00:10 | 4128.39 | 31-DEC-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 147.06 | 0.00 | 01-JAN-00:10 | 18651.49 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 147.06 | 0.00 | 01-JAN-00:10 | 18651.49 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1191.69 | 0.00 | 01-JAN-00:10 | 155585.47 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.89 | 0.00 | 01-JAN-00:10 | 43516.46 | 02-JAN-14:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.89 | 0.00 | 01-JAN-00:10 | 43516.46 | 02-JAN-14:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1179.80 | 0.00 | 01-JAN-00:10 | 155585.47 | 12-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1179.80 | 0.00 | 01-JAN-00:10 | 155585.47 | 12-JUN-14:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 190.09 | 0.00 | 01-JAN-00:10 | 35854.95 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.11 | 0.00 | 01-JAN-00:10 | 19586.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.11 | 0.00 | 01-JAN-00:10 | 19586.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 182.98 | 0.00 | 01-JAN-00:10 | 35854.95 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 182.98 | 0.00 | 01-JAN-00:10 | 35854.95 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.91 | 981.59 | 07-JAN-08:00 | 7942.92 | 16-APR-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.91 | 981.59 | 07-JAN-08:00 | 7942.92 | 16-APR-21:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.91 | 981.59 | 07-JAN-08:00 | 7942.92 | 16-APR-21:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.62 | 14.29 | 01-JAN-20:20 | 74657.62 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.15 | 0.00 | 01-JAN-14:20 | 2541.48 | 01-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.15 | 0.00 | 01-JAN-14:20 | 2541.48 | 01-JAN-11:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.47 | 0.00 | 01-JAN-00:10 | 74657.62 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1331.47 | 0.00 | 01-JAN-00:10 | 74657.62 | 12-APR-16:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.72 | 0.30 | 08-JAN-24:00 | 7609.08 | 16-APR-20:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-11:50 | 359.24 | 01-JAN-14:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-11:50 | 359.24 | 01-JAN-14:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.59 | 0.00 | 01-JAN-00:10 | 7609.08 | 16-APR-20:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 130.59 | 0.00 | 01-JAN-00:10 | 7609.08 | 16-APR-20:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.25 | 88342.61 | 08-JAN-06:00 | 370392.29 | 15-AUG-24:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.25 | 88342.61 | 08-JAN-06:00 | 370392.29 | 15-AUG-24:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.25 | 88342.61 | 08-JAN-06:00 | 370392.29 | 15-AUG-24:00 |
PlantLoopHeatingDemand:Facility | 338.40 | 0.00 | 01-JAN-00:10 | 495610.66 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 293.17 | 0.00 | 01-JAN-00:10 | 40156.34 | 17-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40156.34 | 17-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40156.34 | 17-JAN-12:20 |
EnergyTransfer:HVAC | 34671.29 | 123996.77 | 01-JAN-05:50 | 3148351.23 | 28-AUG-14:40 |
HeatingCoils:EnergyTransfer | 45.22 | 0.00 | 01-JAN-00:10 | 490771.81 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 45.22 | 0.00 | 01-JAN-00:10 | 490771.81 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 45.22 | 0.00 | 01-JAN-00:10 | 490771.81 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 34626.07 | 123947.41 | 01-JAN-05:00 | 3148351.23 | 28-AUG-14:40 |
EnergyTransfer:Plant | 77083.16 | 0.00 | 01-JAN-00:10 | 8791799.06 | 22-JUN-15:40 |
LoopToLoop:EnergyTransfer | 24484.77 | 0.00 | 01-JAN-00:10 | 2773065.88 | 22-JUN-15:30 |
WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40156.34 | 17-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40156.34 | 17-JAN-12:20 |
Boilers:EnergyTransfer | 44.71 | 0.00 | 01-JAN-00:10 | 502234.36 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 24292.71 | 0.00 | 01-JAN-00:10 | 2781740.85 | 22-JUN-15:40 |
HeatRejection:EnergyTransfer | 27967.80 | 0.00 | 01-JAN-00:10 | 3217830.88 | 22-JUN-15:40 |
General:HeatRejection:EnergyTransfer | 27967.80 | 0.00 | 01-JAN-00:10 | 3217830.88 | 22-JUN-15:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.644 | -821.511 | 0.000 | 0.000 | 92.652 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 36.973 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -817.136 | 0.000 | 0.000 | 83.421 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 208.048 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6333.523 | 0.000 | 0.000 | 836.583 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 240.285 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_TOP | 0.000 | 0.000 | 0.434 | -644.879 | 0.000 | 0.000 | 84.393 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 34.387 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -135.433 | 0.000 | 0.000 | 10.555 | 17.307 | 36.365 | 56.729 | 0.000 | 0.622 | 44.275 | 0.000 | -30.077 | 0.000 | -0.344 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -106.744 | 0.000 | 0.000 | 6.780 | 11.081 | 23.435 | 67.048 | 0.000 | 0.420 | 16.588 | 0.000 | -18.376 | 0.000 | -0.231 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.001 | -180.095 | 0.000 | 0.000 | 10.490 | 17.049 | 36.366 | 120.332 | 0.000 | 0.610 | 25.320 | 0.000 | -29.688 | 0.000 | -0.385 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -154.664 | 0.000 | 0.000 | 6.762 | 11.080 | 23.435 | 65.319 | 0.000 | 0.392 | 71.294 | 0.000 | -23.339 | 0.000 | -0.278 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.837 | -1152.058 | 0.000 | 0.000 | 107.612 | 172.679 | 363.654 | 585.169 | 0.000 | 14.304 | 180.002 | 0.000 | -268.355 | 0.000 | -6.844 | -0.004 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.347 | -1007.878 | 0.000 | 0.000 | 50.377 | 110.620 | 234.352 | 671.331 | 0.000 | 9.350 | 109.909 | 0.000 | -174.370 | 0.000 | -5.038 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.512 | -1645.813 | 0.000 | 0.000 | 105.236 | 170.260 | 363.660 | 1204.548 | 0.000 | 13.816 | 86.944 | 0.000 | -290.322 | 0.000 | -8.841 | -0.015 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.809 | -1084.071 | 0.000 | 0.000 | 68.944 | 110.594 | 234.351 | 676.057 | 0.000 | 9.219 | 185.145 | 0.000 | -195.787 | 0.000 | -5.260 | -0.009 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.052 | -119.926 | 0.000 | 0.000 | 10.869 | 17.266 | 36.365 | 58.312 | 0.000 | 1.746 | 19.185 | 0.000 | -25.099 | 0.000 | -0.770 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.798 | -103.823 | 0.000 | 0.000 | 6.897 | 11.061 | 23.435 | 67.008 | 0.000 | 1.134 | 10.591 | 0.000 | -16.523 | 0.000 | -0.579 | -0.002 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.603 | -166.287 | 0.000 | 0.000 | 10.588 | 17.025 | 36.366 | 120.124 | 0.000 | 1.682 | 8.463 | 0.000 | -27.535 | 0.000 | -1.030 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.602 | -110.814 | 0.000 | 0.000 | 6.950 | 11.059 | 23.435 | 67.351 | 0.000 | 1.127 | 19.496 | 0.000 | -18.593 | 0.000 | -0.613 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.906 | 0.000 | 0.000 | 0.943 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.545 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.150 | -1331.469 | 0.000 | 0.000 | 9.405 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -283.172 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.132 | -130.589 | 0.000 | 0.000 | 0.945 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -30.996 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7197.263 | 0.000 | 0.000 | 19.446 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -391.151 |
GROUNDFLOOR_PLENUM | 0.698 | -147.061 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.118 | 146.042 | 0.000 | 0.000 | 0.000 | -0.797 | -0.000 |
MIDFLOOR_PLENUM | 11.895 | -1179.792 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.312 | 1160.943 | 0.000 | 0.000 | 0.000 | -13.357 | -0.007 |
TOPFLOOR_PLENUM | 7.106 | -182.978 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.137 | 175.076 | 0.000 | 0.000 | 0.000 | -1.341 | -0.000 |
Total Facility | 19.699 | -1509.831 | 15.920 | -23388.883 | 0.000 | 0.000 | 1529.850 | 3926.204 | 14676.396 | 3759.329 | 0.000 | 77.988 | 2778.967 | 0.000 | -1118.065 | 0.000 | -45.709 | -721.928 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JAN-05:11 | 0.00 | 0.00 | 0.00 | -122515.47 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 106507.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 20-NOV-05:11 | 0.00 | 0.00 | 0.00 | -108445.97 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 100218.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-OCT-04:12 | 0.00 | 0.00 | 0.00 | -959669.64 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 877391.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-MAR-04:12 | 0.00 | 0.00 | 0.00 | -95251.42 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 87023.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -25955.64 | 0.00 | 0.00 | 37.32 | 68.40 | 720.18 | 6975.02 | 0.00 | 481.98 | 17672.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 28-MAY-15:11 | 0.00 | 0.00 | 0.00 | -20952.99 | 0.00 | 0.00 | 22.55 | 44.08 | 464.11 | 4441.63 | 0.00 | 349.76 | 15630.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 12-NOV-12:51 | 0.00 | 0.00 | 0.00 | -28174.99 | 0.00 | 0.00 | 31.76 | 68.40 | 720.19 | 20590.32 | 0.00 | 0.00 | 6789.79 | 0.00 | -0.00 | 0.00 | -25.48 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-APR-16:21 | 0.00 | 0.00 | 0.00 | -31446.84 | 0.00 | 0.00 | 12.74 | 44.08 | 464.11 | 14983.48 | 0.00 | 110.50 | 15831.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 28-MAY-16:41 | 0.00 | 0.00 | 0.00 | -265037.26 | 0.00 | 0.00 | 357.74 | 684.02 | 7201.84 | 70079.57 | 0.00 | 10740.42 | 175973.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 28-MAY-10:01 | 0.00 | 0.00 | 0.00 | -236589.26 | 0.00 | 0.00 | 179.03 | 440.81 | 4641.14 | 124314.07 | 0.00 | 2802.84 | 104211.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:01 | 0.00 | 0.00 | 0.00 | -285627.07 | 0.00 | 0.00 | 300.45 | 684.04 | 7201.95 | 202376.31 | 0.00 | 1055.44 | 74008.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-16:01 | 0.00 | 0.00 | 0.00 | -279901.61 | 0.00 | 0.00 | 135.95 | 440.81 | 4641.11 | 166286.79 | 0.00 | 6348.61 | 102048.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-16:11 | 0.00 | 0.00 | 0.00 | -29081.23 | 0.00 | 0.00 | 36.09 | 68.40 | 720.18 | 6055.68 | 0.00 | 367.82 | 21833.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-09:31 | 0.00 | 0.00 | 0.00 | -22834.18 | 0.00 | 0.00 | 16.31 | 44.08 | 464.11 | 13307.30 | 0.00 | 719.92 | 8282.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-15:21 | 0.00 | 0.00 | 0.00 | -32000.95 | 0.00 | 0.00 | 28.03 | 68.40 | 720.19 | 11068.42 | 0.00 | 127.89 | 19988.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:11 | 0.00 | 0.00 | 0.00 | -27900.22 | 0.00 | 0.00 | 17.72 | 44.08 | 464.11 | 9897.43 | 0.00 | 204.83 | 17272.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-20:52 | 0.00 | 0.00 | 0.00 | -7959.75 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 133.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 12-APR-16:00 | 0.00 | 0.00 | 0.00 | -74653.35 | 0.00 | 0.00 | 999.51 | 5787.18 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10077.57 |
DATACENTER_TOP_ZN_6 | 16-APR-20:33 | 0.00 | 0.00 | 0.00 | -7618.17 | 0.00 | 0.00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -208.41 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-23:53 | 0.00 | 0.00 | 0.00 | -370570.81 | 0.00 | 0.00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9421.19 |
GROUNDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -24898.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 24846.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 30-MAY-05:03 | 0.00 | -189976.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.07 | 189652.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -35856.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.62 | 35490.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-05:02 | 0.00 | -159394.47 | 0.00 | -2271241.90 | 0.00 | 0.00 | 15342.57 | 42872.09 | 497997.76 | 9465.28 | 0.00 | 4616.01 | 1860436.44 | 0.00 | -93.76 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-JUN-16:01 | 0.00 | 0.00 | 36291.35 | 0.00 | 0.00 | 0.00 | 520.12 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -51543.95 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:21 | 0.00 | 0.00 | 75154.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -83382.33 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 02-JAN-06:01 | 0.00 | 0.00 | 7861.31 | 0.00 | 0.00 | 0.00 | 141.42 | 287.56 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4575.31 | 0.00 | 0.00 | -4675.25 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 169210.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37704.86 | 0.00 | 0.00 | -141836.51 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 118836.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25634.62 | 0.00 | 0.00 | -99859.20 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 157833.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.64 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41494.27 | 0.00 | 0.00 | -126670.43 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 108470.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27274.16 | 0.00 | 0.00 | -87854.01 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:21 | 0.00 | 0.00 | 21978.52 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2987.75 | 0.00 | 0.00 | -20023.89 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:21 | 0.00 | 0.00 | 15463.12 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2023.50 | 0.00 | 0.00 | -14105.41 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:21 | 0.00 | 0.00 | 21583.76 | 0.00 | 0.00 | 0.00 | 0.00 | 287.56 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3220.14 | 0.00 | 0.00 | -19396.75 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:21 | 0.00 | 0.00 | 15562.37 | 0.00 | 0.00 | 0.00 | 0.00 | 185.31 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2151.38 | 0.00 | 0.00 | -14076.77 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-11:40 | 0.00 | 0.00 | 2541.57 | 0.00 | 0.00 | 0.00 | 53.53 | 321.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22402.68 |
DATACENTER_TOP_ZN_6 | 01-JAN-13:50 | 0.00 | 0.00 | 365.23 | 0.00 | 0.00 | 0.00 | 6.77 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2352.75 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 22-DEC-05:12 | 13149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -560.33 | -12589.32 |
MIDFLOOR_PLENUM | 14-MAY-15:31 | 80846.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -83165.00 |
TOPFLOOR_PLENUM | 02-JAN-06:15 | 24546.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24546.37 |
Total Facility | 02-JAN-06:01 | -406521.47 | 423832.50 | 655028.19 | -423832.50 | 0.00 | 0.00 | 20233.56 | 42872.09 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -165356.27 | 0.00 | 0.00 | -407671.07 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.2467 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2374 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 118.2712 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 107.1626 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.3055 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.1929 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2929 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2929 | 0.1907 | 1.0000 | Not calculated | 1.2002 | 0.1907 | ||
AIRLOOP DATACENTER BASEMENT | 22.0196 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.0198 | 0.0154 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4982 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4982 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 | ||
AIRLOOP DATACENTER MID | 4.7560 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7560 | 0.0329 | 1.0000 | Not calculated | 0.1563 | 0.0329 | ||
AIRLOOP DATACENTER TOP | 0.4808 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4808 | 0.0325 | 1.0000 | Not calculated | 0.0156 | 0.0325 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1233 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1150 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.1356 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.6693 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1527 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2929 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2929 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1907 | ||
AIRLOOP DATACENTER BASEMENT | 22.0196 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 22.0196 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0154 | ||
AIRLOOP DATACENTER BOT | 0.4982 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4982 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 | ||
AIRLOOP DATACENTER MID | 4.7560 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7560 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0329 | ||
AIRLOOP DATACENTER TOP | 0.4808 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4808 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0325 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2929 | 6.2929 | 6.2929 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7242 | 6.7242 | 2.0105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 64.3581 | 64.3581 | 19.8867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4513 | 6.4513 | 2.0515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4454 | 1.4454 | 0.2891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1444 | 1.1444 | 0.2289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4590 | 1.4590 | 0.2918 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4737 | 1.4737 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4075 | 14.4075 | 2.8815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9648 | 11.9648 | 2.3930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4147 | 14.4147 | 2.8829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.1260 | 13.1260 | 2.6252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6011 | 1.6011 | 0.3202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2404 | 1.2404 | 0.2481 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5979 | 1.5979 | 0.3196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4148 | 1.4148 | 0.2830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4982 | 0.4982 | 0.4982 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7560 | 4.7560 | 4.7560 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4808 | 0.4808 | 0.4808 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.0196 | 22.0196 | 22.0196 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.2467 | 11.2374 | 12.2467 | 3.1150 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 118.2712 | 107.1626 | 118.2712 | 30.6693 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.3055 | 12.1929 | 12.3055 | 3.2223 | 0.0000 | 1.0000 |
CAV_BAS | 6.2929 | 6.2929 | 6.2929 | 6.2929 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.0196 | 22.0198 | 22.0196 | 22.0196 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4982 | 0.4982 | 0.4982 | 0.4982 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7560 | 4.7560 | 4.7560 | 4.7560 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4808 | 0.4808 | 0.4808 | 0.4808 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.2929 | 6.2929 | 6.2929 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3621 | 3.3621 | 2.0105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 32.1791 | 32.1791 | 19.8867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2257 | 3.2257 | 2.0515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7227 | 0.7227 | 0.2891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5722 | 0.5722 | 0.2289 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7295 | 0.7295 | 0.2918 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7368 | 0.7368 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2038 | 7.2038 | 2.8815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9824 | 5.9824 | 2.3930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2074 | 7.2074 | 2.8829 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5630 | 6.5630 | 2.6252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8005 | 0.8005 | 0.3202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6202 | 0.6202 | 0.2481 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7990 | 0.7990 | 0.3196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7074 | 0.7074 | 0.2830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4982 | 0.4982 | 0.4982 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7560 | 4.7560 | 4.7560 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4808 | 0.4808 | 0.4808 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 22.0196 | 22.0196 | 22.0196 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1233 | 3.1150 | 3.1150 | 3.1150 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.1356 | 30.6693 | 30.6693 | 30.6693 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1527 | 3.2223 | 3.2223 | 3.2223 | 0.0000 | 1.0000 |
CAV_BAS | 6.2929 | 6.2929 | 6.2929 | 6.2929 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 22.0196 | 22.0196 | 22.0196 | 22.0196 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4982 | 0.4982 | 0.4982 | 0.4982 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7560 | 4.7560 | 4.7560 | 4.7560 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4808 | 0.4808 | 0.4808 | 0.4808 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1129.67 |
Number of hours not met | 1129.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 64.19 | 606698.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7124.55 | 613938.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3926.20 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 695.80 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.17 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2831.42 | 282346.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 971.38 | 61369.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2030.83 | 95095.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 81.62 | 28629.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 636.39 | 75311.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 34272.98 |
Natural Gas | 0.00 | 700.59 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 34973.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.76 |
Space Heating | 0.00 |
Space Cooling | 153.81 |
Fans (All) | 61.13 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 739.91 |
Subtotal | 739.91 |
Natural Gas [MJ/m2] | |
Space Heating | 1.39 |
Service Water Heating | 13.74 |
Miscellaneous (All) | 15.12 |
Subtotal | 15.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.23 |
Space Heating | 0.18 |
Space Cooling | 20.37 |
Fans (All) | 8.10 |
Service Water Heating | 1.82 |
Receptacle Equipment | 41.96 |
Miscellaneous | 16.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7116.83 | 1643.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8625.83 | 134.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8546.50 | 213.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8535.33 | 224.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8380.00 | 380.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7644.17 | 1115.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8406.33 | 353.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8312.17 | 447.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8063.50 | 696.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7981.33 | 778.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8365.50 | 394.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8265.00 | 495.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8073.17 | 686.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8003.00 | 757.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6804.00 | 1956.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6300.33 | 2459.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6836.00 | 1924.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7286.83 | 1473.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8501.67 | 258.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8123.33 | 636.67 | 0.00 | 0.00 | 0.00 |
Min | 6300.33 | 2.33 | 0.00 | 0.00 | 0.00 |
Max | 8757.67 | 2459.67 | 0.00 | 0.00 | 0.00 |
Average | 8017.38 | 742.62 | 0.00 | 0.00 | 0.00 |
Sum | 184399.67 | 17080.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364806.83 | 3809.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330585.00 | 228.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330799.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330788.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1526.83 | 741.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1375.17 | 892.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1533.67 | 734.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82043.83 | 21351.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364806.83 | 21351.17 | 0.00 | 0.00 | 0.00 |
Average | 79126.41 | 1208.51 | 0.00 | 0.00 | 0.00 |
Sum | 1819907.33 | 27795.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5305.00 | 3455.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7291.83 | 1468.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7734.33 | 1025.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7598.00 | 1162.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6892.17 | 1867.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7061.33 | 1698.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6569.83 | 2190.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6312.33 | 2447.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6905.00 | 1855.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6794.67 | 1965.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6546.67 | 2213.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6666.83 | 2093.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6925.17 | 1834.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6806.67 | 1953.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6607.83 | 2152.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6715.67 | 2044.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7603.50 | 1156.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7223.00 | 1537.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7609.67 | 1150.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7550.67 | 1209.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5351.33 | 3408.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5191.67 | 3568.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4568.17 | 4191.83 | 0.00 | 0.00 | 0.00 |
Min | 4568.17 | 1025.67 | 0.00 | 0.00 | 0.00 |
Max | 7734.33 | 4191.83 | 0.00 | 0.00 | 0.00 |
Average | 6688.32 | 2071.68 | 0.00 | 0.00 | 0.00 |
Sum | 153831.33 | 47648.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 334247.83 | 34368.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328160.67 | 2652.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329002.00 | 1811.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328586.83 | 2226.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18352.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38921.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38921.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24907.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1832.50 | 435.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1673.33 | 594.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1841.00 | 427.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87419.00 | 15976.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 334247.83 | 34368.17 | 0.00 | 0.00 | 0.00 |
Average | 77791.06 | 2543.86 | 0.00 | 0.00 | 0.00 |
Sum | 1789194.33 | 58508.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:31
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607074E+11 | 122515.67 | 23-JAN-05:11 | 6.33 | 5.49 | 0.566921E+10 | 7499.24 | 04-JAN-10:00 | 6.33 | 5.49 |
February | 0.556007E+11 | 111198.99 | 27-FEB-05:12 | 11.13 | 10.43 | 0.514213E+10 | 7499.06 | 02-FEB-10:09 | 11.13 | 10.43 |
March | 0.655065E+11 | 112302.67 | 20-MAR-04:12 | 15.40 | 11.08 | 0.613636E+10 | 7499.00 | 16-MAR-09:00 | 15.40 | 11.08 |
April | 0.623680E+11 | 113256.62 | 30-APR-15:36 | 37.83 | 18.22 | 0.545368E+10 | 7499.03 | 04-APR-09:09 | 37.83 | 18.22 |
May | 0.661774E+11 | 112827.80 | 07-MAY-18:57 | 37.30 | 22.16 | 0.590519E+10 | 7499.04 | 01-MAY-09:09 | 37.30 | 22.16 |
June | 0.693301E+11 | 107365.84 | 04-JUN-16:38 | 41.97 | 22.48 | 0.588597E+10 | 7498.86 | 07-JUN-09:09 | 37.65 | 20.59 |
July | 0.730708E+11 | 98639.03 | 04-JUL-18:57 | 40.00 | 24.33 | 0.547736E+10 | 7498.77 | 28-JUL-09:20 | 28.17 | 25.73 |
August | 0.833078E+11 | 96167.59 | 29-AUG-03:02 | 27.75 | 24.39 | 0.614081E+10 | 7498.74 | 16-AUG-13:20 | 27.75 | 24.39 |
September | 0.718090E+11 | 95715.07 | 26-SEP-03:02 | 25.65 | 21.91 | 0.545639E+10 | 7498.76 | 15-SEP-13:20 | 25.65 | 21.91 |
October | 0.748963E+11 | 112491.04 | 22-OCT-15:29 | 30.70 | 17.65 | 0.567449E+10 | 7498.93 | 17-OCT-09:30 | 30.70 | 17.65 |
November | 0.715436E+11 | 117157.83 | 24-NOV-05:11 | 10.47 | 9.34 | 0.561844E+10 | 7498.95 | 16-NOV-10:09 | 10.47 | 9.34 |
December | 0.671981E+11 | 117311.45 | 20-DEC-05:12 | 5.87 | 4.21 | 0.547508E+10 | 7499.11 | 27-DEC-10:09 | 16.98 | 12.25 |
Annual Sum or Average | 0.821516E+12 | 0.680351E+11 | ||||||||
Minimum of Months | 0.556007E+11 | 95715.07 | 5.87 | 4.21 | 0.514213E+10 | 7498.74 | 6.33 | 5.49 | ||
Maximum of Months | 0.833078E+11 | 122515.67 | 41.97 | 24.39 | 0.614081E+10 | 7499.24 | 37.83 | 25.73 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455911E+11 | 100432.60 | 17-JAN-05:12 | 10.90 | 10.46 | 0.507558E+10 | 6734.82 | 04-JAN-10:00 | 10.90 | 10.46 |
February | 0.487768E+11 | 106713.74 | 21-FEB-05:12 | 11.87 | 10.80 | 0.460524E+10 | 6734.75 | 02-FEB-10:09 | 11.87 | 10.80 |
March | 0.688415E+11 | 104578.15 | 20-MAR-04:12 | 15.40 | 11.08 | 0.549850E+10 | 6734.76 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.782652E+11 | 97728.30 | 17-APR-05:05 | 24.22 | 18.83 | 0.487832E+10 | 6734.75 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.756538E+11 | 94269.64 | 01-MAY-05:02 | 32.45 | 19.07 | 0.528105E+10 | 6734.57 | 08-MAY-13:09 | 38.60 | 20.90 |
June | 0.766518E+11 | 89804.78 | 14-JUN-05:02 | 32.45 | 25.92 | 0.526649E+10 | 6734.62 | 12-JUN-13:09 | 32.45 | 25.92 |
July | 0.789453E+11 | 95992.04 | 31-JUL-05:03 | 29.03 | 26.75 | 0.489394E+10 | 6734.54 | 17-JUL-13:00 | 29.03 | 26.75 |
August | 0.884863E+11 | 97165.81 | 08-AUG-05:04 | 30.10 | 25.30 | 0.549630E+10 | 6734.55 | 10-AUG-13:00 | 27.10 | 26.16 |
September | 0.677636E+11 | 97925.39 | 13-SEP-03:02 | 25.90 | 25.36 | 0.488003E+10 | 6734.54 | 05-SEP-09:09 | 25.90 | 25.36 |
October | 0.695710E+11 | 107133.83 | 30-OCT-04:13 | 16.40 | 14.90 | 0.507803E+10 | 6734.66 | 24-OCT-09:09 | 16.40 | 14.90 |
November | 0.623350E+11 | 108449.12 | 20-NOV-05:11 | 12.73 | 11.55 | 0.503152E+10 | 6734.69 | 16-NOV-10:09 | 12.73 | 11.55 |
December | 0.562553E+11 | 107291.05 | 26-DEC-05:12 | 10.17 | 8.84 | 0.490226E+10 | 6734.76 | 27-DEC-10:09 | 16.98 | 12.25 |
Annual Sum or Average | 0.817137E+12 | 0.608873E+11 | ||||||||
Minimum of Months | 0.455911E+11 | 89804.78 | 10.17 | 8.84 | 0.460524E+10 | 6734.54 | 10.90 | 10.46 | ||
Maximum of Months | 0.884863E+11 | 108449.12 | 32.45 | 26.75 | 0.549850E+10 | 6734.82 | 38.60 | 26.75 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328527E+11 | 86570.32 | 27-JAN-06:03 | 11.07 | 9.85 | 0.497691E+10 | 6734.77 | 05-JAN-10:09 | 11.07 | 9.85 |
February | 0.365398E+11 | 92986.31 | 27-FEB-05:12 | 11.13 | 10.43 | 0.457440E+10 | 6734.73 | 02-FEB-10:09 | 11.13 | 10.43 |
March | 0.530723E+11 | 95582.66 | 10-MAR-05:12 | 17.83 | 15.81 | 0.549245E+10 | 6734.76 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.587488E+11 | 94526.79 | 11-APR-04:12 | 18.13 | 13.57 | 0.487290E+10 | 6734.75 | 04-APR-09:09 | 18.13 | 13.57 |
May | 0.663705E+11 | 90740.55 | 13-MAY-04:12 | 22.77 | 20.21 | 0.527605E+10 | 6734.59 | 08-MAY-13:09 | 22.77 | 20.21 |
June | 0.643442E+11 | 82728.76 | 21-JUN-03:02 | 28.25 | 23.92 | 0.526265E+10 | 6734.66 | 05-JUN-13:09 | 28.25 | 23.92 |
July | 0.623287E+11 | 81859.44 | 28-JUL-03:02 | 27.00 | 25.79 | 0.488770E+10 | 6734.56 | 18-JUL-13:09 | 27.00 | 25.79 |
August | 0.637795E+11 | 84811.55 | 17-AUG-03:02 | 27.35 | 25.43 | 0.549181E+10 | 6734.57 | 21-AUG-13:09 | 29.57 | 27.56 |
September | 0.564325E+11 | 90806.30 | 09-SEP-04:03 | 24.65 | 24.12 | 0.487720E+10 | 6734.57 | 08-SEP-13:30 | 24.65 | 24.12 |
October | 0.557372E+11 | 95986.43 | 12-OCT-04:12 | 21.00 | 20.42 | 0.507253E+10 | 6734.65 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.465135E+11 | 95758.51 | 01-NOV-04:12 | 15.70 | 12.48 | 0.501593E+10 | 6734.68 | 06-NOV-10:09 | 23.13 | 17.24 |
December | 0.366347E+11 | 89677.48 | 29-DEC-06:02 | 16.53 | 12.55 | 0.484960E+10 | 6734.75 | 27-DEC-10:09 | 16.53 | 12.55 |
Annual Sum or Average | 0.633354E+12 | 0.606501E+11 | ||||||||
Minimum of Months | 0.328527E+11 | 81859.44 | 11.07 | 9.85 | 0.457440E+10 | 6734.56 | 11.07 | 9.85 | ||
Maximum of Months | 0.663705E+11 | 95986.43 | 28.25 | 25.79 | 0.549245E+10 | 6734.77 | 29.57 | 27.56 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266298E+11 | 37921.51 | 26-JAN-16:40 | 19.13 | 12.86 | 0.464977E+10 | 6734.55 | 13-JAN-14:09 | 19.13 | 12.86 |
February | 0.317147E+11 | 85877.31 | 23-FEB-06:03 | 15.05 | 13.57 | 0.445794E+10 | 6734.63 | 15-FEB-10:09 | 15.05 | 13.57 |
March | 0.515475E+11 | 95266.80 | 14-MAR-04:12 | 20.77 | 16.48 | 0.547086E+10 | 6734.75 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.633009E+11 | 93194.02 | 10-APR-04:12 | 18.47 | 13.25 | 0.487398E+10 | 6734.74 | 04-APR-09:09 | 18.47 | 13.25 |
May | 0.747095E+11 | 93104.75 | 13-MAY-04:12 | 22.77 | 20.21 | 0.528150E+10 | 6734.56 | 08-MAY-13:09 | 22.77 | 20.21 |
June | 0.731657E+11 | 86197.92 | 05-JUN-04:12 | 30.23 | 20.26 | 0.526662E+10 | 6734.63 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.696095E+11 | 92655.46 | 19-JUL-04:03 | 24.72 | 24.59 | 0.489385E+10 | 6734.53 | 17-JUL-13:00 | 24.72 | 24.59 |
August | 0.696458E+11 | 91333.54 | 17-AUG-03:02 | 27.35 | 25.43 | 0.549517E+10 | 6734.54 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.596552E+11 | 93138.86 | 14-SEP-03:02 | 26.52 | 24.93 | 0.487871E+10 | 6734.54 | 08-SEP-13:00 | 26.52 | 24.93 |
October | 0.549763E+11 | 94396.63 | 11-OCT-03:02 | 24.45 | 20.86 | 0.506414E+10 | 6734.65 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.408423E+11 | 88722.50 | 09-NOV-06:03 | 17.53 | 15.94 | 0.495584E+10 | 6734.66 | 06-NOV-10:09 | 17.53 | 15.94 |
December | 0.290855E+11 | 47575.56 | 29-DEC-06:02 | 16.53 | 12.55 | 0.462712E+10 | 6734.60 | 29-DEC-14:00 | 19.50 | 14.92 |
Annual Sum or Average | 0.644883E+12 | 0.599155E+11 | ||||||||
Minimum of Months | 0.266298E+11 | 37921.51 | 15.05 | 12.55 | 0.445794E+10 | 6734.53 | 15.05 | 12.86 | ||
Maximum of Months | 0.747095E+11 | 95266.80 | 30.23 | 25.43 | 0.549517E+10 | 6734.75 | 43.40 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378490E+10 | 4915.97 | 26-JAN-14:10 | 22.35 | 13.84 | 0.592119E+09 | 845.61 | 13-JAN-14:09 | 22.35 | 13.84 |
February | 0.481963E+10 | 7200.93 | 23-FEB-14:30 | 26.10 | 14.00 | 0.561708E+09 | 845.61 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.924396E+10 | 12384.59 | 11-MAR-06:02 | 23.80 | 17.15 | 0.687871E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.143147E+11 | 25229.90 | 30-APR-15:41 | 37.82 | 18.21 | 0.613792E+09 | 845.63 | 21-APR-09:09 | 37.82 | 18.21 |
May | 0.169355E+11 | 25955.43 | 28-MAY-16:31 | 41.90 | 19.53 | 0.665540E+09 | 845.61 | 08-MAY-13:09 | 41.90 | 19.53 |
June | 0.176918E+11 | 25890.05 | 04-JUN-16:31 | 41.97 | 22.48 | 0.663248E+09 | 845.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.169621E+11 | 24511.35 | 02-JUL-17:01 | 40.18 | 26.57 | 0.617085E+09 | 845.60 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.174369E+11 | 24122.84 | 06-AUG-15:41 | 36.30 | 26.24 | 0.691720E+09 | 845.60 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.124585E+11 | 24159.23 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614006E+09 | 845.61 | 08-SEP-13:30 | 34.20 | 26.01 |
October | 0.103590E+11 | 16385.49 | 12-OCT-04:12 | 21.00 | 20.42 | 0.637259E+09 | 845.62 | 10-OCT-13:00 | 21.00 | 20.42 |
November | 0.672795E+10 | 7833.85 | 09-NOV-14:30 | 29.30 | 17.79 | 0.626081E+09 | 845.62 | 06-NOV-14:00 | 29.30 | 17.79 |
December | 0.469900E+10 | 5689.70 | 26-DEC-14:10 | 22.68 | 14.39 | 0.593875E+09 | 845.62 | 29-DEC-14:09 | 19.75 | 14.80 |
Annual Sum or Average | 0.135434E+12 | 0.756430E+10 | ||||||||
Minimum of Months | 0.378490E+10 | 4915.97 | 21.00 | 13.84 | 0.561708E+09 | 845.60 | 19.75 | 13.84 | ||
Maximum of Months | 0.176918E+11 | 25955.43 | 41.97 | 26.57 | 0.691720E+09 | 845.63 | 43.40 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330056E+10 | 4774.09 | 26-JAN-10:20 | 18.10 | 12.94 | 0.396393E+09 | 544.96 | 04-JAN-10:00 | 18.10 | 12.94 |
February | 0.437562E+10 | 8061.35 | 20-FEB-11:23 | 23.45 | 13.03 | 0.365210E+09 | 544.95 | 02-FEB-10:20 | 23.45 | 13.03 |
March | 0.811494E+10 | 18504.18 | 26-MAR-09:53 | 25.50 | 14.88 | 0.443611E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.121265E+11 | 20419.39 | 30-APR-15:01 | 37.88 | 18.24 | 0.395619E+09 | 545.42 | 28-APR-09:50 | 37.88 | 18.24 |
May | 0.143219E+11 | 20951.97 | 28-MAY-15:11 | 42.23 | 19.17 | 0.429132E+09 | 545.30 | 26-MAY-09:00 | 42.23 | 19.17 |
June | 0.133066E+11 | 20288.56 | 04-JUN-15:51 | 42.30 | 22.20 | 0.427373E+09 | 547.67 | 12-JUN-09:39 | 39.50 | 22.03 |
July | 0.118602E+11 | 19778.24 | 04-JUL-09:42 | 34.98 | 25.17 | 0.397464E+09 | 545.11 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.115133E+11 | 18918.52 | 06-AUG-15:01 | 36.30 | 26.24 | 0.445373E+09 | 545.17 | 07-AUG-09:20 | 32.40 | 25.34 |
September | 0.962353E+10 | 19443.68 | 17-SEP-10:12 | 30.97 | 25.48 | 0.395596E+09 | 544.94 | 08-SEP-13:30 | 30.97 | 25.48 |
October | 0.866891E+10 | 19612.10 | 15-OCT-10:02 | 29.07 | 17.07 | 0.410844E+09 | 544.95 | 23-OCT-09:00 | 25.70 | 17.02 |
November | 0.573509E+10 | 10987.28 | 12-NOV-10:13 | 23.23 | 16.01 | 0.404067E+09 | 544.95 | 06-NOV-14:00 | 23.23 | 16.01 |
December | 0.379797E+10 | 5399.32 | 01-DEC-10:00 | 18.30 | 11.37 | 0.385944E+09 | 544.95 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.106745E+12 | 0.489663E+10 | ||||||||
Minimum of Months | 0.330056E+10 | 4774.09 | 18.10 | 11.37 | 0.365210E+09 | 544.94 | 18.10 | 12.94 | ||
Maximum of Months | 0.143219E+11 | 20951.97 | 42.30 | 26.24 | 0.445373E+09 | 547.67 | 42.23 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.836653E+10 | 24482.35 | 08-JAN-14:02 | 22.40 | 13.22 | 0.620875E+09 | 845.91 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.959201E+10 | 27014.15 | 20-FEB-13:22 | 26.15 | 13.41 | 0.570749E+09 | 846.19 | 07-FEB-14:50 | 26.15 | 13.41 |
March | 0.148152E+11 | 26271.76 | 26-MAR-14:32 | 30.33 | 16.74 | 0.690160E+09 | 846.16 | 08-MAR-14:50 | 30.33 | 16.74 |
April | 0.177978E+11 | 27042.74 | 30-APR-14:21 | 37.65 | 18.45 | 0.614517E+09 | 846.07 | 06-APR-13:00 | 37.65 | 18.45 |
May | 0.177793E+11 | 26344.90 | 28-MAY-15:11 | 42.23 | 19.17 | 0.665677E+09 | 846.00 | 08-MAY-13:00 | 42.23 | 19.17 |
June | 0.175739E+11 | 26021.05 | 04-JUN-16:31 | 41.97 | 22.48 | 0.663234E+09 | 846.14 | 12-JUN-13:20 | 43.50 | 22.39 |
July | 0.170571E+11 | 24675.55 | 02-JUL-16:21 | 40.35 | 26.46 | 0.617087E+09 | 846.17 | 05-JUL-13:20 | 37.90 | 25.56 |
August | 0.182347E+11 | 24765.90 | 06-AUG-15:01 | 36.30 | 26.24 | 0.691852E+09 | 846.08 | 31-AUG-13:20 | 32.60 | 25.63 |
September | 0.154741E+11 | 26329.37 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614584E+09 | 846.10 | 19-SEP-13:00 | 32.90 | 24.72 |
October | 0.178163E+11 | 28161.75 | 15-OCT-13:21 | 32.80 | 18.97 | 0.640486E+09 | 885.91 | 02-OCT-13:39 | 32.80 | 18.97 |
November | 0.152886E+11 | 28171.10 | 12-NOV-12:51 | 27.70 | 16.23 | 0.631878E+09 | 855.27 | 01-NOV-13:39 | 27.70 | 16.23 |
December | 0.103004E+11 | 26108.82 | 03-DEC-13:42 | 24.42 | 14.17 | 0.608933E+09 | 846.28 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.180096E+12 | 0.763003E+10 | ||||||||
Minimum of Months | 0.836653E+10 | 24482.35 | 22.40 | 13.22 | 0.570749E+09 | 845.91 | 23.20 | 13.41 | ||
Maximum of Months | 0.182347E+11 | 28171.10 | 42.23 | 26.46 | 0.691852E+09 | 885.91 | 43.50 | 25.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479205E+10 | 7825.21 | 31-JAN-16:00 | 21.10 | 11.23 | 0.389706E+09 | 544.95 | 25-JAN-14:00 | 21.10 | 11.23 |
February | 0.630089E+10 | 25578.38 | 20-FEB-15:22 | 25.95 | 14.09 | 0.368670E+09 | 544.95 | 15-FEB-10:30 | 25.95 | 14.09 |
March | 0.122601E+11 | 26085.58 | 26-MAR-14:32 | 30.33 | 16.74 | 0.445920E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.190068E+11 | 31445.22 | 30-APR-16:21 | 37.45 | 18.00 | 0.396894E+09 | 544.96 | 21-APR-09:09 | 37.45 | 18.00 |
May | 0.169054E+11 | 30591.96 | 28-MAY-16:31 | 41.90 | 19.53 | 0.429347E+09 | 544.94 | 08-MAY-13:09 | 41.90 | 19.53 |
June | 0.178554E+11 | 30278.95 | 04-JUN-16:31 | 41.97 | 22.48 | 0.427960E+09 | 544.95 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.169691E+11 | 27255.41 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398297E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.197326E+11 | 27009.98 | 06-AUG-15:41 | 36.30 | 26.24 | 0.446702E+09 | 544.94 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.123133E+11 | 26779.13 | 17-SEP-14:51 | 34.20 | 26.01 | 0.396170E+09 | 544.94 | 08-SEP-13:30 | 34.20 | 26.01 |
October | 0.119440E+11 | 27370.24 | 22-OCT-14:51 | 31.00 | 17.63 | 0.412166E+09 | 544.95 | 10-OCT-13:00 | 31.00 | 17.63 |
November | 0.931079E+10 | 26398.10 | 12-NOV-14:51 | 28.20 | 15.74 | 0.407667E+09 | 544.97 | 06-NOV-14:00 | 28.20 | 15.74 |
December | 0.727454E+10 | 18474.16 | 24-DEC-15:13 | 23.77 | 13.93 | 0.395461E+09 | 544.95 | 18-DEC-10:00 | 23.77 | 13.93 |
Annual Sum or Average | 0.154665E+12 | 0.491496E+10 | ||||||||
Minimum of Months | 0.479205E+10 | 7825.21 | 21.10 | 11.23 | 0.368670E+09 | 544.94 | 21.10 | 11.23 | ||
Maximum of Months | 0.197326E+11 | 31445.22 | 41.97 | 26.46 | 0.446702E+09 | 544.97 | 43.40 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252794E+10 | 3028.69 | 26-JAN-15:00 | 21.60 | 13.66 | 0.523220E+09 | 845.60 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.343471E+10 | 5855.75 | 24-FEB-15:00 | 26.40 | 17.38 | 0.524779E+09 | 845.61 | 24-FEB-14:20 | 26.40 | 17.38 |
March | 0.703459E+10 | 12022.74 | 29-MAR-04:12 | 21.40 | 17.71 | 0.678599E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.118334E+11 | 24905.90 | 30-APR-16:11 | 37.57 | 18.06 | 0.613364E+09 | 845.63 | 04-APR-09:09 | 37.57 | 18.06 |
May | 0.165500E+11 | 26504.41 | 28-MAY-16:41 | 41.80 | 19.54 | 0.665677E+09 | 845.61 | 05-MAY-09:30 | 41.80 | 19.54 |
June | 0.167225E+11 | 26040.55 | 04-JUN-16:41 | 41.88 | 22.55 | 0.663332E+09 | 845.62 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.153016E+11 | 25010.58 | 16-JUL-16:51 | 34.20 | 27.01 | 0.617298E+09 | 845.60 | 10-JUL-13:09 | 34.20 | 27.01 |
August | 0.143512E+11 | 24929.39 | 06-AUG-17:31 | 35.47 | 26.59 | 0.691853E+09 | 845.60 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.111577E+11 | 24140.97 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614131E+09 | 845.60 | 08-SEP-13:30 | 34.20 | 26.01 |
October | 0.848582E+10 | 23779.25 | 01-OCT-15:21 | 35.75 | 20.04 | 0.634656E+09 | 845.61 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.487292E+10 | 6493.96 | 09-NOV-14:30 | 29.30 | 17.79 | 0.604636E+09 | 845.61 | 15-NOV-14:50 | 26.47 | 17.77 |
December | 0.293452E+10 | 3359.24 | 03-DEC-14:12 | 24.20 | 14.19 | 0.526596E+09 | 834.61 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.115207E+12 | 0.735814E+10 | ||||||||
Minimum of Months | 0.252794E+10 | 3028.69 | 21.40 | 13.66 | 0.523220E+09 | 834.61 | 21.60 | 13.66 | ||
Maximum of Months | 0.167225E+11 | 26504.41 | 41.88 | 27.01 | 0.691853E+09 | 845.63 | 42.20 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252588E+10 | 3501.31 | 26-JAN-11:10 | 19.98 | 13.28 | 0.264455E+09 | 521.20 | 12-JAN-11:20 | 19.98 | 13.28 |
February | 0.356827E+10 | 6971.67 | 22-FEB-10:00 | 20.60 | 13.92 | 0.259648E+09 | 521.21 | 15-FEB-11:20 | 20.60 | 13.92 |
March | 0.735276E+10 | 20621.37 | 12-MAR-10:02 | 26.28 | 17.32 | 0.324321E+09 | 521.22 | 16-MAR-10:20 | 20.53 | 15.55 |
April | 0.117937E+11 | 22855.67 | 30-APR-08:51 | 28.40 | 14.74 | 0.291785E+09 | 521.93 | 26-APR-10:00 | 28.40 | 14.74 |
May | 0.147899E+11 | 23656.15 | 28-MAY-10:01 | 36.92 | 19.98 | 0.316135E+09 | 521.91 | 19-MAY-10:00 | 36.92 | 19.98 |
June | 0.134074E+11 | 21611.20 | 04-JUN-16:01 | 42.22 | 22.27 | 0.314424E+09 | 522.65 | 12-JUN-12:20 | 42.70 | 22.30 |
July | 0.115922E+11 | 20915.62 | 04-JUL-10:22 | 35.80 | 25.02 | 0.293591E+09 | 521.73 | 05-JUL-10:30 | 36.60 | 25.30 |
August | 0.107478E+11 | 21351.16 | 06-AUG-10:12 | 32.70 | 25.41 | 0.327800E+09 | 521.20 | 21-AUG-12:09 | 30.20 | 27.51 |
September | 0.920339E+10 | 20524.90 | 17-SEP-10:12 | 30.97 | 25.48 | 0.291523E+09 | 521.20 | 29-SEP-14:20 | 33.83 | 22.63 |
October | 0.808024E+10 | 21458.31 | 01-OCT-10:42 | 31.62 | 19.69 | 0.302171E+09 | 521.22 | 10-OCT-14:20 | 31.63 | 20.81 |
November | 0.491510E+10 | 7210.92 | 09-NOV-10:00 | 24.50 | 17.90 | 0.293220E+09 | 521.21 | 06-NOV-15:20 | 24.50 | 17.90 |
December | 0.281201E+10 | 4264.59 | 01-DEC-10:00 | 18.30 | 11.37 | 0.264918E+09 | 521.20 | 01-DEC-15:20 | 23.03 | 13.49 |
Annual Sum or Average | 0.100789E+12 | 0.354399E+10 | ||||||||
Minimum of Months | 0.252588E+10 | 3501.31 | 18.30 | 11.37 | 0.259648E+09 | 521.20 | 19.98 | 13.28 | ||
Maximum of Months | 0.147899E+11 | 23656.15 | 42.22 | 25.48 | 0.327800E+09 | 522.65 | 42.70 | 27.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748791E+10 | 24536.90 | 08-JAN-14:13 | 22.50 | 13.35 | 0.607979E+09 | 845.83 | 12-JAN-14:50 | 23.55 | 14.16 |
February | 0.862427E+10 | 24813.89 | 20-FEB-14:22 | 26.35 | 13.75 | 0.561930E+09 | 846.02 | 07-FEB-14:50 | 26.35 | 13.75 |
March | 0.132821E+11 | 26629.19 | 12-MAR-12:42 | 30.53 | 18.94 | 0.688077E+09 | 846.04 | 08-MAR-14:00 | 30.53 | 18.94 |
April | 0.156718E+11 | 26552.51 | 30-APR-15:31 | 37.83 | 18.22 | 0.614594E+09 | 845.93 | 21-APR-13:00 | 37.83 | 18.22 |
May | 0.174171E+11 | 26633.36 | 28-MAY-16:01 | 42.20 | 19.49 | 0.665835E+09 | 845.88 | 03-MAY-13:00 | 42.20 | 19.49 |
June | 0.165704E+11 | 25856.07 | 04-JUN-16:01 | 42.22 | 22.27 | 0.663327E+09 | 845.90 | 06-JUN-13:39 | 43.43 | 22.36 |
July | 0.154376E+11 | 24909.14 | 16-JUL-16:11 | 33.47 | 26.89 | 0.617324E+09 | 845.62 | 10-JUL-13:09 | 33.47 | 26.89 |
August | 0.153495E+11 | 25265.64 | 06-AUG-17:31 | 35.47 | 26.59 | 0.692072E+09 | 845.83 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.145431E+11 | 26354.71 | 17-SEP-14:51 | 34.20 | 26.01 | 0.614956E+09 | 861.03 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.170631E+11 | 28564.15 | 01-OCT-12:01 | 34.03 | 19.84 | 0.641193E+09 | 898.09 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.144353E+11 | 28114.86 | 11-NOV-13:11 | 28.57 | 16.92 | 0.630034E+09 | 866.48 | 01-NOV-13:39 | 28.57 | 16.92 |
December | 0.870106E+10 | 26316.68 | 03-DEC-12:52 | 24.00 | 14.17 | 0.598853E+09 | 845.94 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.164583E+12 | 0.759617E+10 | ||||||||
Minimum of Months | 0.748791E+10 | 24536.90 | 22.50 | 13.35 | 0.561930E+09 | 845.62 | 23.20 | 13.75 | ||
Maximum of Months | 0.174171E+11 | 28564.15 | 42.22 | 26.89 | 0.692072E+09 | 898.09 | 43.43 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286943E+10 | 5513.03 | 31-JAN-16:10 | 20.95 | 11.21 | 0.352183E+09 | 544.94 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.384621E+10 | 9092.16 | 20-FEB-16:23 | 25.10 | 14.37 | 0.342298E+09 | 544.95 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.779444E+10 | 22700.31 | 12-MAR-16:01 | 31.18 | 19.88 | 0.439087E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.125453E+11 | 27123.54 | 30-APR-16:11 | 37.57 | 18.06 | 0.396127E+09 | 544.96 | 04-APR-09:09 | 37.57 | 18.06 |
May | 0.152107E+11 | 27991.74 | 28-MAY-16:01 | 42.20 | 19.49 | 0.429329E+09 | 544.94 | 05-MAY-09:30 | 42.20 | 19.49 |
June | 0.147603E+11 | 27137.60 | 04-JUN-16:01 | 42.22 | 22.27 | 0.427736E+09 | 544.95 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.124009E+11 | 24611.67 | 16-JUL-16:51 | 34.20 | 27.01 | 0.397952E+09 | 544.94 | 10-JUL-09:20 | 34.20 | 27.01 |
August | 0.117676E+11 | 25063.49 | 06-AUG-17:31 | 35.47 | 26.59 | 0.446078E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.984936E+10 | 23914.65 | 17-SEP-14:51 | 34.20 | 26.01 | 0.395998E+09 | 544.94 | 08-SEP-13:30 | 34.20 | 26.01 |
October | 0.849800E+10 | 25291.46 | 01-OCT-15:21 | 35.75 | 20.04 | 0.410019E+09 | 544.95 | 10-OCT-13:00 | 31.70 | 20.64 |
November | 0.553176E+10 | 21965.30 | 05-NOV-15:42 | 28.08 | 17.72 | 0.393118E+09 | 544.96 | 06-NOV-14:00 | 28.40 | 18.16 |
December | 0.333404E+10 | 6120.90 | 01-DEC-15:30 | 22.85 | 13.56 | 0.352469E+09 | 544.94 | 18-DEC-14:00 | 22.10 | 15.00 |
Annual Sum or Average | 0.108408E+12 | 0.478239E+10 | ||||||||
Minimum of Months | 0.286943E+10 | 5513.03 | 20.95 | 11.21 | 0.342298E+09 | 544.94 | 20.95 | 11.21 | ||
Maximum of Months | 0.152107E+11 | 27991.74 | 42.22 | 27.01 | 0.446078E+09 | 544.96 | 42.20 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207159E+10 | 3169.05 | 26-JAN-15:10 | 21.37 | 13.58 | 0.501957E+09 | 833.13 | 26-JAN-14:00 | 21.37 | 13.58 |
February | 0.321163E+10 | 6055.82 | 23-FEB-14:50 | 25.90 | 14.07 | 0.503994E+09 | 845.61 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.713476E+10 | 10412.49 | 29-MAR-15:30 | 33.00 | 18.86 | 0.667029E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.125848E+11 | 26923.18 | 16-APR-15:21 | 39.50 | 22.49 | 0.612484E+09 | 845.63 | 28-APR-13:20 | 37.93 | 20.83 |
May | 0.178559E+11 | 27997.15 | 28-MAY-16:11 | 42.10 | 19.51 | 0.665695E+09 | 845.61 | 08-MAY-13:09 | 42.10 | 19.51 |
June | 0.180274E+11 | 28197.86 | 11-JUN-16:21 | 43.25 | 23.12 | 0.663356E+09 | 845.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.164563E+11 | 29090.02 | 09-JUL-16:11 | 36.30 | 27.50 | 0.617361E+09 | 845.60 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.151988E+11 | 28516.92 | 06-AUG-17:31 | 35.47 | 26.59 | 0.691821E+09 | 845.60 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.116287E+11 | 20686.43 | 24-SEP-15:02 | 35.05 | 24.91 | 0.613905E+09 | 845.60 | 08-SEP-13:30 | 35.05 | 24.91 |
October | 0.862839E+10 | 27296.26 | 01-OCT-15:21 | 35.75 | 20.04 | 0.629641E+09 | 845.61 | 10-OCT-13:00 | 31.70 | 20.64 |
November | 0.463905E+10 | 6926.66 | 09-NOV-14:40 | 29.27 | 17.76 | 0.584295E+09 | 845.61 | 06-NOV-14:00 | 29.27 | 17.76 |
December | 0.248965E+10 | 3388.59 | 03-DEC-14:32 | 23.90 | 14.21 | 0.498585E+09 | 820.72 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.119927E+12 | 0.725012E+10 | ||||||||
Minimum of Months | 0.207159E+10 | 3169.05 | 21.37 | 13.58 | 0.498585E+09 | 820.72 | 21.37 | 13.58 | ||
Maximum of Months | 0.180274E+11 | 29090.02 | 43.25 | 27.50 | 0.691821E+09 | 845.63 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221004E+10 | 3190.98 | 26-JAN-14:20 | 22.20 | 13.80 | 0.347303E+09 | 544.94 | 12-JAN-14:50 | 22.20 | 13.80 |
February | 0.329967E+10 | 6610.21 | 23-FEB-10:40 | 22.80 | 14.32 | 0.347909E+09 | 544.95 | 15-FEB-10:39 | 22.80 | 14.32 |
March | 0.736079E+10 | 15525.63 | 26-MAR-10:43 | 27.33 | 15.51 | 0.440016E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.123175E+11 | 22313.20 | 16-APR-10:02 | 35.32 | 21.70 | 0.395905E+09 | 545.29 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.157024E+11 | 22838.31 | 29-MAY-09:31 | 35.10 | 21.77 | 0.429359E+09 | 545.25 | 26-MAY-09:00 | 35.10 | 21.77 |
June | 0.143362E+11 | 22042.54 | 11-JUN-10:22 | 37.75 | 25.19 | 0.427631E+09 | 545.13 | 09-JUN-09:00 | 37.75 | 25.19 |
July | 0.124113E+11 | 22321.14 | 09-JUL-16:11 | 36.30 | 27.50 | 0.397946E+09 | 545.07 | 07-JUL-09:00 | 36.30 | 27.50 |
August | 0.113956E+11 | 22367.68 | 06-AUG-10:12 | 32.70 | 25.41 | 0.445919E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.957004E+10 | 18017.18 | 24-SEP-09:02 | 29.85 | 25.28 | 0.395662E+09 | 544.94 | 08-SEP-13:30 | 29.85 | 25.28 |
October | 0.816591E+10 | 22316.09 | 01-OCT-10:42 | 31.62 | 19.69 | 0.408876E+09 | 544.95 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.461369E+10 | 6875.20 | 09-NOV-10:20 | 25.33 | 18.04 | 0.395442E+09 | 544.95 | 06-NOV-14:00 | 25.33 | 18.04 |
December | 0.244094E+10 | 3259.79 | 01-DEC-10:40 | 19.57 | 11.89 | 0.347413E+09 | 544.94 | 28-DEC-14:09 | 24.58 | 15.31 |
Annual Sum or Average | 0.103824E+12 | 0.477938E+10 | ||||||||
Minimum of Months | 0.221004E+10 | 3190.98 | 19.57 | 11.89 | 0.347303E+09 | 544.94 | 22.20 | 13.80 | ||
Maximum of Months | 0.157024E+11 | 22838.31 | 37.75 | 27.50 | 0.445919E+09 | 545.29 | 37.75 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645544E+10 | 18584.58 | 08-JAN-14:13 | 22.50 | 13.35 | 0.588458E+09 | 845.64 | 25-JAN-14:50 | 22.98 | 13.31 |
February | 0.793796E+10 | 29375.73 | 20-FEB-14:12 | 26.37 | 13.66 | 0.548628E+09 | 846.00 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.131499E+11 | 29015.93 | 26-MAR-14:02 | 30.23 | 16.67 | 0.682363E+09 | 846.12 | 08-MAR-14:50 | 30.23 | 16.67 |
April | 0.163868E+11 | 28107.08 | 16-APR-15:21 | 39.50 | 22.49 | 0.614131E+09 | 846.01 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.187149E+11 | 28386.85 | 14-MAY-14:51 | 36.10 | 21.62 | 0.665836E+09 | 845.94 | 04-MAY-13:00 | 36.10 | 21.62 |
June | 0.178695E+11 | 27999.67 | 11-JUN-16:21 | 43.25 | 23.12 | 0.663353E+09 | 845.97 | 12-JUN-13:39 | 43.70 | 22.38 |
July | 0.165892E+11 | 29071.52 | 09-JUL-16:11 | 36.30 | 27.50 | 0.617385E+09 | 845.62 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.161973E+11 | 28801.69 | 06-AUG-17:31 | 35.47 | 26.59 | 0.692027E+09 | 845.89 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.149711E+11 | 27631.87 | 24-SEP-15:02 | 35.05 | 24.91 | 0.614702E+09 | 845.86 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.170001E+11 | 32003.11 | 01-OCT-15:21 | 35.75 | 20.04 | 0.638342E+09 | 875.35 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.135920E+11 | 30884.42 | 11-NOV-13:41 | 28.67 | 16.78 | 0.623104E+09 | 846.12 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.742487E+10 | 26912.50 | 03-DEC-14:32 | 23.90 | 14.21 | 0.583019E+09 | 845.89 | 01-DEC-14:20 | 23.90 | 14.21 |
Annual Sum or Average | 0.166289E+12 | 0.753135E+10 | ||||||||
Minimum of Months | 0.645544E+10 | 18584.58 | 22.50 | 13.35 | 0.548628E+09 | 845.62 | 22.98 | 13.31 | ||
Maximum of Months | 0.187149E+11 | 32003.11 | 43.25 | 27.50 | 0.692027E+09 | 875.35 | 43.70 | 26.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254042E+10 | 5404.80 | 31-JAN-16:10 | 20.95 | 11.21 | 0.341309E+09 | 544.94 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.363085E+10 | 17742.68 | 20-FEB-16:12 | 25.27 | 14.30 | 0.331361E+09 | 544.95 | 24-FEB-14:30 | 26.15 | 17.19 |
March | 0.779642E+10 | 25240.16 | 26-MAR-16:02 | 29.87 | 16.42 | 0.432751E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.129711E+11 | 26305.41 | 30-APR-16:31 | 37.33 | 17.93 | 0.395790E+09 | 544.96 | 04-APR-09:09 | 37.33 | 17.93 |
May | 0.160149E+11 | 27418.78 | 28-MAY-16:11 | 42.10 | 19.51 | 0.429308E+09 | 544.95 | 08-MAY-13:09 | 42.10 | 19.51 |
June | 0.155832E+11 | 27211.72 | 11-JUN-16:21 | 43.25 | 23.12 | 0.427728E+09 | 544.95 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.131213E+11 | 27912.39 | 09-JUL-16:11 | 36.30 | 27.50 | 0.397952E+09 | 544.94 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.122649E+11 | 27574.18 | 06-AUG-17:31 | 35.47 | 26.59 | 0.446019E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.101338E+11 | 24642.65 | 24-SEP-15:42 | 34.85 | 25.19 | 0.395734E+09 | 544.94 | 08-SEP-13:30 | 34.85 | 25.19 |
October | 0.854417E+10 | 27731.16 | 01-OCT-15:21 | 35.75 | 20.04 | 0.407074E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.530865E+10 | 22906.58 | 05-NOV-15:42 | 28.08 | 17.72 | 0.382491E+09 | 544.96 | 06-NOV-14:00 | 28.40 | 18.16 |
December | 0.290555E+10 | 6072.35 | 28-DEC-15:40 | 24.03 | 15.27 | 0.338886E+09 | 544.94 | 04-DEC-14:00 | 24.03 | 15.27 |
Annual Sum or Average | 0.110815E+12 | 0.472640E+10 | ||||||||
Minimum of Months | 0.254042E+10 | 5404.80 | 20.95 | 11.21 | 0.331361E+09 | 544.94 | 20.95 | 11.21 | ||
Maximum of Months | 0.160149E+11 | 27912.39 | 43.25 | 27.50 | 0.446019E+09 | 544.96 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267835E+10 | 4401.50 | 21-JAN-06:10 | 5.50 | 5.15 | 0.00 | 0.00 | 01-JAN-00:10 | 5.50 | 5.15 |
February | 0.484302E+10 | 8874.77 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.105723E+11 | 12140.74 | 13-MAR-05:03 | 20.77 | 15.50 | 0.00 | 0.00 | 01-MAR-00:10 | 20.77 | 15.50 |
April | 0.162231E+11 | 21402.01 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.187863E+11 | 22066.53 | 01-MAY-05:15 | 32.50 | 19.11 | 0.00 | 0.00 | 01-MAY-00:10 | 32.50 | 19.11 |
June | 0.186145E+11 | 22904.52 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.175589E+11 | 24903.35 | 05-JUL-05:15 | 32.63 | 24.69 | 0.00 | 0.00 | 01-JUL-00:10 | 32.63 | 24.69 |
August | 0.182493E+11 | 22862.44 | 07-AUG-05:13 | 29.57 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 29.57 | 24.74 |
September | 0.133483E+11 | 19115.72 | 18-SEP-05:02 | 26.72 | 24.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.72 | 24.18 |
October | 0.126326E+11 | 13864.43 | 02-OCT-05:03 | 21.60 | 17.47 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 17.47 |
November | 0.875284E+10 | 11524.08 | 13-NOV-06:15 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.480212E+10 | 6973.32 | 26-DEC-06:08 | 10.17 | 8.52 | 0.00 | 0.00 | 01-DEC-00:10 | 10.17 | 8.52 |
Annual Sum or Average | 0.147062E+12 | 0.00 | ||||||||
Minimum of Months | 0.267835E+10 | 4401.50 | 5.50 | 5.15 | 0.00 | 0.00 | 5.50 | 5.15 | ||
Maximum of Months | 0.187863E+11 | 24903.35 | 34.23 | 24.74 | 0.00 | 0.00 | 34.23 | 24.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121032E+10 | 4010.62 | 23-JAN-06:02 | 6.48 | 5.73 | 0.00 | 0.00 | 01-JAN-00:10 | 6.48 | 5.73 |
February | 0.284239E+10 | 5482.75 | 22-FEB-16:50 | 25.83 | 15.78 | 0.00 | 0.00 | 01-FEB-00:10 | 25.83 | 15.78 |
March | 0.791677E+10 | 10701.89 | 30-MAR-05:03 | 21.37 | 16.59 | 0.00 | 0.00 | 01-MAR-00:10 | 21.37 | 16.59 |
April | 0.132138E+11 | 13770.90 | 26-APR-05:02 | 24.50 | 20.59 | 0.00 | 0.00 | 01-APR-00:10 | 24.50 | 20.59 |
May | 0.171409E+11 | 18996.95 | 30-MAY-05:03 | 30.25 | 21.57 | 0.00 | 0.00 | 01-MAY-00:10 | 30.25 | 21.57 |
June | 0.166051E+11 | 15596.30 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.148742E+11 | 15391.11 | 05-JUL-05:15 | 32.63 | 24.69 | 0.00 | 0.00 | 01-JUL-00:10 | 32.63 | 24.69 |
August | 0.141546E+11 | 16412.94 | 09-AUG-05:02 | 29.90 | 25.20 | 0.00 | 0.00 | 01-AUG-00:10 | 29.90 | 25.20 |
September | 0.116105E+11 | 15492.23 | 25-SEP-05:02 | 25.93 | 23.09 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 23.09 |
October | 0.103628E+11 | 13382.02 | 03-OCT-05:02 | 22.92 | 17.52 | 0.00 | 0.00 | 01-OCT-00:10 | 22.92 | 17.52 |
November | 0.591821E+10 | 7798.88 | 10-NOV-06:13 | 17.13 | 15.15 | 0.00 | 0.00 | 01-NOV-00:10 | 17.13 | 15.15 |
December | 0.213030E+10 | 4399.39 | 02-DEC-06:08 | 8.72 | 8.46 | 0.00 | 0.00 | 01-DEC-00:10 | 8.72 | 8.46 |
Annual Sum or Average | 0.117980E+12 | 0.00 | ||||||||
Minimum of Months | 0.121032E+10 | 4010.62 | 6.48 | 5.73 | 0.00 | 0.00 | 6.48 | 5.73 | ||
Maximum of Months | 0.171409E+11 | 18996.95 | 34.23 | 25.20 | 0.00 | 0.00 | 34.23 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178155E+10 | 7080.94 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.426591E+10 | 14635.93 | 22-FEB-15:00 | 27.10 | 16.20 | 0.00 | 0.00 | 01-FEB-00:10 | 27.10 | 16.20 |
March | 0.118721E+11 | 24111.58 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.218258E+11 | 29810.40 | 28-APR-14:50 | 39.10 | 21.04 | 0.00 | 0.00 | 01-APR-00:10 | 39.10 | 21.04 |
May | 0.288520E+11 | 34012.28 | 04-MAY-14:20 | 41.93 | 22.24 | 0.00 | 0.00 | 01-MAY-00:10 | 41.93 | 22.24 |
June | 0.286987E+11 | 35854.95 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.235605E+11 | 31865.81 | 07-JUL-14:00 | 40.30 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 40.30 | 24.54 |
August | 0.215262E+11 | 28468.61 | 07-AUG-14:20 | 37.23 | 26.37 | 0.00 | 0.00 | 01-AUG-00:10 | 37.23 | 26.37 |
September | 0.167872E+11 | 24501.86 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.141630E+11 | 23523.63 | 02-OCT-14:30 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.733723E+10 | 15992.70 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.231036E+10 | 8712.50 | 01-DEC-14:40 | 23.43 | 13.26 | 0.00 | 0.00 | 01-DEC-00:10 | 23.43 | 13.26 |
Annual Sum or Average | 0.182980E+12 | 0.00 | ||||||||
Minimum of Months | 0.178155E+10 | 7080.94 | 23.43 | 13.26 | 0.00 | 0.00 | 23.43 | 13.26 | ||
Maximum of Months | 0.288520E+11 | 35854.95 | 43.80 | 26.37 | 0.00 | 0.00 | 43.80 | 26.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383028E+10 | 1984.02 | 12-JAN-17:00 | 22.30 | 14.53 | 95237236.76 | 126.85 | 18-JAN-14:00 | 18.10 | 14.57 |
February | 0.846889E+10 | 3990.19 | 21-FEB-17:00 | 25.40 | 15.70 | 86404849.33 | 126.85 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.147984E+11 | 7241.48 | 31-MAR-23:50 | 23.63 | 16.67 | 0.103242E+09 | 126.84 | 23-MAR-09:09 | 23.63 | 16.67 |
April | 0.194841E+11 | 7959.82 | 16-APR-20:52 | 28.40 | 20.06 | 93611489.88 | 140.12 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.501490E+10 | 3527.39 | 31-MAY-23:50 | 28.10 | 22.60 | 99239974.91 | 126.85 | 09-MAY-09:20 | 28.10 | 22.60 |
June | 0.973476E+10 | 5479.60 | 30-JUN-23:55 | 33.10 | 24.67 | 98979596.67 | 126.88 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.150847E+11 | 7344.11 | 31-JUL-23:55 | 29.40 | 26.34 | 91894768.14 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.201123E+11 | 7816.88 | 10-AUG-16:00 | 26.10 | 25.05 | 0.108505E+09 | 145.97 | 07-AUG-13:00 | 26.10 | 25.05 |
September | 0.471307E+10 | 3521.02 | 30-SEP-23:57 | 26.60 | 21.92 | 91606279.93 | 126.85 | 29-SEP-13:00 | 26.60 | 21.92 |
October | 0.988859E+10 | 5415.64 | 31-OCT-24:00 | 17.80 | 15.13 | 95245340.12 | 126.87 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.142945E+11 | 5911.61 | 13-NOV-16:30 | 27.00 | 16.63 | 94305390.27 | 126.83 | 17-NOV-10:09 | 22.03 | 16.57 |
December | 0.194818E+11 | 7757.55 | 28-DEC-17:00 | 22.80 | 14.91 | 91882667.95 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.144906E+12 | 0.115016E+10 | ||||||||
Minimum of Months | 0.383028E+10 | 1984.02 | 17.80 | 14.53 | 86404849.33 | 126.83 | 17.80 | 14.57 | ||
Maximum of Months | 0.201123E+11 | 7959.82 | 33.10 | 26.34 | 0.108505E+09 | 145.97 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234728E+10 | 1808.85 | 12-JAN-17:00 | 22.30 | 14.53 | 95226617.60 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.734583E+10 | 3729.03 | 22-FEB-17:00 | 25.70 | 15.75 | 86403627.27 | 126.84 | 09-FEB-14:00 | 25.70 | 15.75 |
March | 0.139135E+11 | 7000.29 | 31-MAR-23:53 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:30 | 23.70 | 16.75 |
April | 0.183342E+11 | 7465.76 | 12-APR-16:00 | 28.10 | 17.52 | 94535155.45 | 143.22 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.469323E+10 | 3430.63 | 31-MAY-23:53 | 28.10 | 22.60 | 99239895.02 | 126.85 | 10-MAY-13:30 | 28.10 | 22.60 |
June | 0.922592E+10 | 5258.53 | 30-JUN-23:42 | 33.12 | 24.58 | 98980184.99 | 126.88 | 27-JUN-09:00 | 33.12 | 24.58 |
July | 0.142924E+11 | 7032.81 | 31-JUL-23:55 | 29.40 | 26.34 | 91895041.45 | 126.85 | 18-JUL-09:39 | 29.40 | 26.34 |
August | 0.187769E+11 | 7275.55 | 10-AUG-16:00 | 26.10 | 25.05 | 0.109930E+09 | 147.23 | 07-AUG-13:00 | 26.10 | 25.05 |
September | 0.434765E+10 | 3366.35 | 30-SEP-23:27 | 26.60 | 22.07 | 91606261.31 | 126.85 | 29-SEP-13:00 | 26.60 | 22.07 |
October | 0.925604E+10 | 5115.02 | 31-OCT-24:00 | 17.80 | 15.13 | 95244940.28 | 126.86 | 06-OCT-09:00 | 17.80 | 15.13 |
November | 0.131408E+11 | 5589.48 | 09-NOV-16:50 | 27.48 | 17.52 | 94305054.29 | 126.83 | 09-NOV-10:09 | 27.48 | 17.52 |
December | 0.174730E+11 | 7300.09 | 01-DEC-17:00 | 21.20 | 14.26 | 91882550.05 | 126.83 | 11-DEC-10:00 | 10.00 | 9.32 |
Annual Sum or Average | 0.133147E+12 | 0.115249E+10 | ||||||||
Minimum of Months | 0.234728E+10 | 1808.85 | 17.80 | 14.26 | 86403627.27 | 126.83 | 10.00 | 9.32 | ||
Maximum of Months | 0.187769E+11 | 7465.76 | 33.12 | 26.34 | 0.109930E+09 | 147.23 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139797E+10 | 1831.36 | 12-JAN-17:00 | 22.30 | 14.53 | 94858859.42 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.671279E+10 | 3780.02 | 22-FEB-17:00 | 25.70 | 15.75 | 86404351.84 | 126.84 | 09-FEB-14:00 | 25.70 | 15.75 |
March | 0.137168E+11 | 6955.30 | 31-MAR-23:53 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:00 | 23.70 | 16.75 |
April | 0.184631E+11 | 7618.32 | 16-APR-20:33 | 29.00 | 20.29 | 93380874.12 | 139.84 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.487144E+10 | 3385.34 | 31-MAY-23:53 | 28.10 | 22.60 | 99239997.12 | 126.85 | 09-MAY-09:00 | 28.10 | 22.60 |
June | 0.939655E+10 | 5315.73 | 30-JUN-23:42 | 33.12 | 24.58 | 98980510.20 | 126.88 | 28-JUN-09:00 | 33.12 | 24.58 |
July | 0.144718E+11 | 7056.67 | 31-JUL-23:55 | 29.40 | 26.34 | 91896553.30 | 126.86 | 18-JUL-09:50 | 29.40 | 26.34 |
August | 0.190147E+11 | 7409.31 | 20-AUG-15:55 | 27.80 | 26.01 | 0.106952E+09 | 143.89 | 07-AUG-13:00 | 27.80 | 26.01 |
September | 0.439850E+10 | 3377.06 | 30-SEP-23:17 | 26.60 | 22.12 | 91606245.36 | 126.85 | 27-SEP-13:09 | 26.60 | 22.12 |
October | 0.914391E+10 | 4979.08 | 31-OCT-24:00 | 17.80 | 15.13 | 95245589.10 | 126.86 | 12-OCT-13:39 | 17.80 | 15.13 |
November | 0.126205E+11 | 5647.41 | 09-NOV-16:40 | 27.67 | 17.53 | 94305689.92 | 126.83 | 09-NOV-10:09 | 27.67 | 17.53 |
December | 0.163810E+11 | 7312.06 | 28-DEC-17:00 | 22.80 | 14.91 | 91883140.26 | 126.83 | 11-DEC-10:50 | 22.80 | 14.91 |
Annual Sum or Average | 0.130589E+12 | 0.114800E+10 | ||||||||
Minimum of Months | 0.139797E+10 | 1831.36 | 17.80 | 14.53 | 86404351.84 | 126.83 | 17.80 | 14.91 | ||
Maximum of Months | 0.190147E+11 | 7618.32 | 33.12 | 26.34 | 0.106952E+09 | 143.89 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241590E+12 | 93525.92 | 26-JAN-17:00 | 18.60 | 12.70 | 0.206241E+10 | 2748.30 | 26-JAN-10:09 | 18.60 | 12.70 |
February | 0.438623E+12 | 185038.38 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187105E+10 | 2749.04 | 28-FEB-10:09 | 18.42 | 14.43 |
March | 0.731252E+12 | 359321.45 | 31-MAR-23:53 | 23.70 | 16.75 | 0.223524E+10 | 2749.80 | 21-MAR-09:09 | 23.70 | 16.75 |
April | 0.936330E+12 | 369041.38 | 30-APR-04:23 | 23.15 | 16.67 | 0.240458E+10 | 4047.59 | 28-APR-13:00 | 23.15 | 16.67 |
May | 0.244001E+12 | 176704.76 | 31-MAY-23:57 | 28.10 | 22.60 | 0.214884E+10 | 2747.22 | 24-MAY-09:00 | 28.10 | 22.60 |
June | 0.473770E+12 | 268994.67 | 30-JUN-23:53 | 33.10 | 24.67 | 0.214277E+10 | 2746.94 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.736838E+12 | 356714.78 | 31-JUL-23:23 | 29.40 | 26.34 | 0.198927E+10 | 2746.02 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.969233E+12 | 370578.88 | 15-AUG-23:53 | 23.40 | 22.91 | 0.292914E+10 | 4079.93 | 07-AUG-13:00 | 23.40 | 22.91 |
September | 0.240811E+12 | 177887.46 | 30-SEP-23:57 | 26.60 | 21.92 | 0.198369E+10 | 2747.28 | 14-SEP-13:20 | 26.60 | 21.92 |
October | 0.492163E+12 | 270022.35 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206191E+10 | 2746.42 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.712641E+12 | 278390.90 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204191E+10 | 2749.93 | 28-NOV-10:20 | 18.37 | 13.86 |
December | 0.979995E+12 | 369566.45 | 18-DEC-17:00 | 20.00 | 14.42 | 0.199047E+10 | 2813.64 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.719725E+13 | 0.258613E+11 | ||||||||
Minimum of Months | 0.240811E+12 | 93525.92 | 17.80 | 12.70 | 0.187105E+10 | 2746.02 | 17.80 | 12.70 | ||
Maximum of Months | 0.979995E+12 | 370578.88 | 33.10 | 26.34 | 0.292914E+10 | 4079.93 | 33.10 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6579413.89 | 3341.55 | 14-JAN-17:25 | 20.25 |
February | 75904434.75 | 11993.39 | 20-FEB-14:17 | 26.37 |
March | 0.159970E+09 | 16839.15 | 11-MAR-17:02 | 29.70 |
April | 0.495839E+09 | 31129.41 | 15-APR-16:01 | 39.58 |
May | 0.598755E+09 | 34468.84 | 27-MAY-16:01 | 42.00 |
June | 0.622007E+09 | 36290.89 | 10-JUN-16:01 | 43.12 |
July | 0.809608E+09 | 30863.30 | 02-JUL-16:20 | 40.37 |
August | 0.538536E+09 | 25567.27 | 05-AUG-16:01 | 35.70 |
September | 0.630033E+09 | 23696.25 | 30-SEP-16:02 | 34.78 |
October | 0.485958E+09 | 22748.38 | 01-OCT-12:53 | 35.20 |
November | 0.195031E+09 | 17813.02 | 05-NOV-14:21 | 29.20 |
December | 26074686.79 | 8352.07 | 03-DEC-12:53 | 24.00 |
Annual Sum or Average | 0.464430E+10 | |||
Minimum of Months | 6579413.89 | 3341.55 | 20.25 | |
Maximum of Months | 0.809608E+09 | 36290.89 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433547E+09 | 75154.72 | 02-JAN-05:21 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.433547E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 0.433547E+09 | 75154.72 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 973874.16 | 7862.14 | 02-JAN-06:01 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 973874.16 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 973874.16 | 7862.14 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302354E+09 | 16923.29 | 02-JAN-05:11 | 6.47 |
February | 24410035.77 | 11488.84 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 56919971.50 | 15470.71 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 0.383684E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.302354E+09 | 16923.29 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110859E+09 | 11885.72 | 02-JAN-05:11 | 6.47 |
February | 5689379.51 | 8865.99 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 18119689.08 | 10662.72 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 0.134668E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.110859E+09 | 11885.72 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44085571.90 | 15785.89 | 02-JAN-05:11 | 6.47 |
February | 6462491.14 | 11164.82 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 610196.82 | 1240.58 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 51158259.86 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 44085571.90 | 15785.89 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67366215.17 | 10849.23 | 02-JAN-05:11 | 6.47 |
February | 3864303.65 | 5930.93 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 9672557.88 | 8071.70 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 80903076.71 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 67366215.17 | 10849.23 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121697E+10 | 21978.57 | 02-JAN-05:21 | 6.45 |
February | 0.232394E+09 | 18569.25 | 11-FEB-05:12 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 22346797.53 | 12730.65 | 27-NOV-06:03 | 9.55 |
December | 0.580177E+09 | 19340.51 | 23-DEC-05:12 | 5.10 |
Annual Sum or Average | 0.205188E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 0.121697E+10 | 21978.57 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492544E+09 | 15463.13 | 02-JAN-05:21 | 6.45 |
February | 83203240.32 | 12953.14 | 11-FEB-05:12 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 3011105.71 | 2768.81 | 27-NOV-06:03 | 9.55 |
December | 0.218959E+09 | 13233.56 | 22-DEC-05:12 | 11.37 |
Annual Sum or Average | 0.797717E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 0.492544E+09 | 15463.13 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408724E+09 | 21583.82 | 02-JAN-05:21 | 6.45 |
February | 78697310.27 | 18538.16 | 11-FEB-05:12 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.115993E+09 | 17515.87 | 23-DEC-06:02 | 5.43 |
Annual Sum or Average | 0.603414E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.408724E+09 | 21583.82 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400602E+09 | 15562.35 | 02-JAN-05:21 | 6.45 |
February | 62592350.39 | 12043.90 | 02-FEB-06:02 | 6.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 25777.03 | 214.81 | 25-NOV-06:06 | 10.68 |
December | 0.139228E+09 | 12893.85 | 23-DEC-05:12 | 5.10 |
Annual Sum or Average | 0.602448E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 0.400602E+09 | 15562.35 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72675492.82 | 11865.45 | 17-JAN-05:12 | 10.90 |
February | 88345197.77 | 10216.77 | 13-FEB-05:12 | 11.03 |
March | 61953981.93 | 9247.79 | 20-MAR-04:12 | 15.40 |
April | 43656352.00 | 8493.29 | 02-APR-15:41 | 33.88 |
May | 28176802.35 | 5996.26 | 28-MAY-15:52 | 42.30 |
June | 29086673.85 | 8176.74 | 04-JUN-14:31 | 42.03 |
July | 38044756.30 | 6314.21 | 30-JUL-15:02 | 34.78 |
August | 36480811.06 | 7377.69 | 27-AUG-15:01 | 35.43 |
September | 27741513.49 | 7862.71 | 11-SEP-03:02 | 26.07 |
October | 56459776.22 | 7783.41 | 13-OCT-04:12 | 21.03 |
November | 81235424.85 | 9608.94 | 27-NOV-05:12 | 9.77 |
December | 0.134197E+09 | 13149.09 | 22-DEC-05:12 | 11.37 |
Annual Sum or Average | 0.698054E+09 | |||
Minimum of Months | 27741513.49 | 5996.26 | 9.77 | |
Maximum of Months | 0.134197E+09 | 13149.09 | 42.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.695450E+09 | 7650.38 | 18-JAN-06:03 | 13.58 |
February | 73377016.55 | 7530.34 | 10-FEB-06:03 | 12.33 |
March | 37588669.23 | 5638.01 | 26-MAR-16:12 | 29.73 |
April | 29315395.68 | 7169.25 | 30-APR-14:51 | 37.90 |
May | 34440636.84 | 8084.72 | 14-MAY-15:31 | 36.17 |
June | 26916721.24 | 8077.16 | 04-JUN-14:41 | 42.17 |
July | 37834459.96 | 6693.73 | 02-JUL-16:21 | 40.35 |
August | 26661793.52 | 6866.47 | 06-AUG-14:51 | 36.30 |
September | 25049769.57 | 7927.80 | 11-SEP-03:02 | 26.07 |
October | 44242562.07 | 6967.18 | 01-OCT-14:41 | 35.98 |
November | 50654649.39 | 6233.11 | 28-NOV-05:12 | 15.20 |
December | 0.107918E+09 | 7592.73 | 29-DEC-06:02 | 16.53 |
Annual Sum or Average | 0.118945E+10 | |||
Minimum of Months | 25049769.57 | 5638.01 | 12.33 | |
Maximum of Months | 0.695450E+09 | 8084.72 | 42.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276617E+10 | 24546.80 | 02-JAN-06:15 | 6.50 |
February | 0.116942E+10 | 15915.61 | 24-FEB-06:03 | 15.00 |
March | 0.346695E+09 | 16981.88 | 31-MAR-05:03 | 16.93 |
April | 46651581.88 | 13948.58 | 10-APR-04:12 | 18.47 |
May | 6998937.74 | 6453.38 | 25-MAY-03:02 | 26.60 |
June | 6030526.23 | 7837.54 | 28-JUN-03:02 | 26.40 |
July | 5773081.38 | 7429.70 | 19-JUL-04:03 | 24.72 |
August | 8849381.64 | 7792.77 | 21-AUG-03:02 | 25.87 |
September | 23229294.78 | 9717.32 | 11-SEP-03:02 | 26.07 |
October | 0.150734E+09 | 15299.21 | 31-OCT-05:03 | 15.53 |
November | 0.664942E+09 | 17643.63 | 14-NOV-06:03 | 14.57 |
December | 0.191033E+10 | 12110.06 | 29-DEC-06:02 | 16.53 |
Annual Sum or Average | 0.710582E+10 | |||
Minimum of Months | 5773081.38 | 6453.38 | 6.50 | |
Maximum of Months | 0.276617E+10 | 24546.80 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14967476.51 | 254.15 | 01-JAN-11:40 | 12.80 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 14967476.51 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 14967476.51 | 254.15 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131922E+09 | 365.21 | 01-JAN-13:50 | 16.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.131922E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 0.131922E+09 | 365.21 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154048E+10 | 2255.20 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135626E+10 | 2255.20 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152700E+10 | 2255.20 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133269E+10 | 1350.81 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140752E+10 | 1803.00 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.140353E+10 | 1803.00 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.135078E+10 | 2255.20 | 18-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.151446E+10 | 2255.20 | 11-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.137915E+10 | 2255.20 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147052E+10 | 2587.92 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.150837E+10 | 2255.20 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.151663E+10 | 2587.92 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173074E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.133269E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.154048E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.972960E+09 | 1453.34 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.865050E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.976673E+09 | 1161.92 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.858066E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.912262E+09 | 947.51 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.909429E+09 | 947.51 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.870984E+09 | 1453.34 | 18-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.974403E+09 | 1453.34 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.885477E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.934655E+09 | 1667.75 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.962331E+09 | 1667.75 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.958875E+09 | 1667.75 | 26-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110812E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.858066E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.976673E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146619E+10 | 2255.25 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131740E+10 | 2255.25 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151271E+10 | 2255.25 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133617E+10 | 1350.84 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142179E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.141738E+10 | 1803.04 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.136202E+10 | 2255.25 | 18-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.151926E+10 | 2255.25 | 11-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137323E+10 | 2255.25 | 05-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.144252E+10 | 2587.98 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144851E+10 | 2255.25 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.143156E+10 | 2255.25 | 26-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170487E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131740E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151926E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.965005E+09 | 1453.34 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.856971E+09 | 1453.34 | 09-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.982829E+09 | 1453.34 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.861545E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.915479E+09 | 1161.92 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.911917E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.879434E+09 | 1453.34 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.985226E+09 | 1453.34 | 11-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.891931E+09 | 1453.34 | 05-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.946056E+09 | 1667.75 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.943395E+09 | 1453.34 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.940421E+09 | 1453.34 | 26-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110802E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.856971E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.985226E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.153432E+10 | 2255.20 | 05-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135178E+10 | 2255.20 | 09-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152363E+10 | 2255.20 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133155E+10 | 1350.81 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140651E+10 | 1803.00 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.140138E+10 | 1803.00 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.134813E+10 | 2255.20 | 18-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.151184E+10 | 2255.20 | 11-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.137676E+10 | 2255.20 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.146674E+10 | 2587.92 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.150445E+10 | 2255.20 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.151077E+10 | 2587.92 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172679E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.133155E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.153432E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.971047E+09 | 1453.34 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.862722E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.975350E+09 | 1161.92 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.857217E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.911547E+09 | 947.51 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.908113E+09 | 947.51 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.869477E+09 | 1453.34 | 18-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.971769E+09 | 1453.34 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.884035E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.933109E+09 | 1667.75 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.960709E+09 | 1667.75 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.956903E+09 | 1667.75 | 26-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110620E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.857217E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.975350E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146541E+10 | 2255.25 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131569E+10 | 2255.25 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151101E+10 | 2255.25 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133465E+10 | 1350.84 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142056E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.141513E+10 | 1803.04 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.136019E+10 | 2255.25 | 18-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.151620E+10 | 2255.25 | 11-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137171E+10 | 2255.25 | 05-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.144017E+10 | 2587.98 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144480E+10 | 2135.77 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.143049E+10 | 2255.25 | 26-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170260E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131569E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151620E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.963682E+09 | 1453.34 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.855342E+09 | 1453.34 | 09-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.981362E+09 | 1453.34 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.860539E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.914151E+09 | 1161.92 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.910505E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.877191E+09 | 1453.34 | 18-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.982261E+09 | 1453.34 | 11-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.889192E+09 | 1453.34 | 05-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.944444E+09 | 1667.75 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.942190E+09 | 1453.34 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.938548E+09 | 1453.34 | 29-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110594E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.855342E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.982261E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.153402E+10 | 2255.20 | 05-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.135170E+10 | 2255.20 | 09-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.152348E+10 | 2255.20 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.133137E+10 | 1350.81 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.140651E+10 | 1803.00 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.140133E+10 | 1803.00 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.134772E+10 | 2255.20 | 18-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.151164E+10 | 2255.20 | 11-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.137675E+10 | 2255.20 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.146667E+10 | 2587.92 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.150430E+10 | 2255.20 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.151058E+10 | 2587.92 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.172661E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.133137E+10 | 1350.81 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.153402E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.970998E+09 | 1453.34 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.862546E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.975245E+09 | 1161.92 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.857141E+09 | 793.52 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.911540E+09 | 947.51 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.908091E+09 | 947.51 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.869447E+09 | 1453.34 | 18-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.971563E+09 | 1453.34 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.883982E+09 | 1453.34 | 05-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.933035E+09 | 1667.75 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.960666E+09 | 1667.75 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.956856E+09 | 1667.75 | 26-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.110611E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.857141E+09 | 793.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.975245E+09 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146540E+10 | 2255.25 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.131546E+10 | 2255.25 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151087E+10 | 2255.25 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.133465E+10 | 1350.84 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.142043E+10 | 1803.04 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.141500E+10 | 1803.04 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.136013E+10 | 2255.25 | 18-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.151606E+10 | 2255.25 | 11-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.137143E+10 | 2255.25 | 05-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.144016E+10 | 2587.98 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.144479E+10 | 2135.77 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.143049E+10 | 2255.25 | 26-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170249E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.131546E+10 | 1350.84 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151606E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.963583E+09 | 1453.34 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.855293E+09 | 1453.34 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.981362E+09 | 1453.34 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.860539E+09 | 1161.92 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.914097E+09 | 1161.92 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.910397E+09 | 1161.92 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.877028E+09 | 1453.34 | 18-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.982203E+09 | 1453.34 | 11-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.889172E+09 | 1453.34 | 05-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.944398E+09 | 1667.75 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.942093E+09 | 1453.34 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.938543E+09 | 1453.34 | 29-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110587E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.855293E+09 | 1161.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.982203E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.154048E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.97 | 85587161.05 |
February | 0.136985E+10 | 0.135626E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410388.03 | 91380077.81 |
March | 0.163685E+10 | 0.152700E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17952123.94 | 56203397.90 |
April | 0.145243E+10 | 0.133269E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69930024.46 | 3599554.78 |
May | 0.157338E+10 | 0.140752E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153102E+09 | 1214684.74 |
June | 0.156900E+10 | 0.140353E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103578E+09 | 689598.08 |
July | 0.145680E+10 | 0.135078E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130725E+09 | 283368.35 |
August | 0.163685E+10 | 0.151446E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73988187.22 | 412173.54 |
September | 0.145243E+10 | 0.137915E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43613787.12 | 1282639.39 |
October | 0.150991E+10 | 0.147052E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22736556.40 | 4827355.44 |
November | 0.149516E+10 | 0.150837E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4864296.82 | 19451707.18 |
December | 0.145680E+10 | 0.151663E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96318.98 | 79007202.61 |
Annual Sum or Average | 0.181194E+11 | 0.173074E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621997E+09 | 0.343939E+09 |
Minimum of Months | 0.136985E+10 | 0.133269E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.97 | 283368.35 |
Maximum of Months | 0.163685E+10 | 0.154048E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153102E+09 | 91380077.81 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.972960E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58369693.59 |
February | 0.882782E+09 | 0.865050E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 714575.44 | 62408093.19 |
March | 0.105485E+10 | 0.976673E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11250533.39 | 37152963.24 |
April | 0.936002E+09 | 0.858066E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46204511.85 | 2177847.03 |
May | 0.101394E+10 | 0.912262E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101682E+09 | 769976.70 |
June | 0.101113E+10 | 0.909429E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70152589.69 | 381201.40 |
July | 0.938820E+09 | 0.870984E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90189377.15 | 126614.09 |
August | 0.105485E+10 | 0.974403E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52060238.68 | 144196.61 |
September | 0.936002E+09 | 0.885477E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29647157.69 | 664161.09 |
October | 0.973041E+09 | 0.934655E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14595433.84 | 3294401.73 |
November | 0.963541E+09 | 0.962331E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3030997.74 | 13376091.55 |
December | 0.938820E+09 | 0.958875E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38784.73 | 52623445.87 |
Annual Sum or Average | 0.116768E+11 | 0.110812E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419566E+09 | 0.231489E+09 |
Minimum of Months | 0.882782E+09 | 0.858066E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126614.09 |
Maximum of Months | 0.105485E+10 | 0.976673E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101682E+09 | 62408093.19 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146619E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93314824.49 |
February | 0.136988E+10 | 0.131740E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 871586.84 | 0.102785E+09 |
March | 0.163688E+10 | 0.151271E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15273937.14 | 63256413.36 |
April | 0.145246E+10 | 0.133617E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67469224.73 | 4183347.49 |
May | 0.157341E+10 | 0.142179E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152146E+09 | 1234196.71 |
June | 0.156904E+10 | 0.141738E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103652E+09 | 684893.78 |
July | 0.145684E+10 | 0.136202E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130754E+09 | 276698.93 |
August | 0.163688E+10 | 0.151926E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73596546.95 | 434942.16 |
September | 0.145246E+10 | 0.137323E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42143895.72 | 1267136.82 |
October | 0.150994E+10 | 0.144252E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20284227.25 | 5584291.25 |
November | 0.149520E+10 | 0.144851E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3718955.32 | 22980463.80 |
December | 0.145684E+10 | 0.143156E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17124.89 | 89126883.26 |
Annual Sum or Average | 0.181198E+11 | 0.170487E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609927E+09 | 0.385129E+09 |
Minimum of Months | 0.136988E+10 | 0.131740E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276698.93 |
Maximum of Months | 0.163688E+10 | 0.151926E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152146E+09 | 0.102785E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.965005E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63416852.67 |
February | 0.882782E+09 | 0.856971E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 595167.41 | 72255869.82 |
March | 0.105485E+10 | 0.982829E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10243616.85 | 49390555.79 |
April | 0.936002E+09 | 0.861545E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43308594.04 | 4907329.51 |
May | 0.101394E+10 | 0.915479E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99075024.94 | 1213728.12 |
June | 0.101113E+10 | 0.911917E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66522407.54 | 799815.33 |
July | 0.938820E+09 | 0.879434E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82475525.15 | 349642.67 |
August | 0.105485E+10 | 0.985226E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45051673.46 | 713613.70 |
September | 0.936002E+09 | 0.891931E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27884459.00 | 1552158.30 |
October | 0.973041E+09 | 0.946056E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14071476.65 | 4127479.11 |
November | 0.963541E+09 | 0.943395E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2608086.35 | 15818443.14 |
December | 0.938820E+09 | 0.940421E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11544.89 | 63536969.12 |
Annual Sum or Average | 0.116768E+11 | 0.110802E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391848E+09 | 0.278082E+09 |
Minimum of Months | 0.882782E+09 | 0.856971E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349642.67 |
Maximum of Months | 0.105485E+10 | 0.985226E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99075024.94 | 72255869.82 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.153432E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277664.64 | 0.160946E+09 |
February | 0.136985E+10 | 0.135178E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6761271.94 | 0.179664E+09 |
March | 0.163685E+10 | 0.152363E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43909236.32 | 0.124699E+09 |
April | 0.145243E+10 | 0.133155E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164023E+09 | 11301321.78 |
May | 0.157338E+10 | 0.140651E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349806E+09 | 3172343.83 |
June | 0.156900E+10 | 0.140138E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236507E+09 | 2228280.56 |
July | 0.145680E+10 | 0.134813E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292163E+09 | 1008796.03 |
August | 0.163685E+10 | 0.151184E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167726E+09 | 1916516.26 |
September | 0.145243E+10 | 0.137676E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98269475.72 | 3365966.43 |
October | 0.150991E+10 | 0.146674E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54195551.84 | 10917238.16 |
November | 0.149516E+10 | 0.150445E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14455914.00 | 38317955.04 |
December | 0.145680E+10 | 0.151077E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2310385.31 | 0.146841E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172679E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143041E+10 | 0.684378E+09 |
Minimum of Months | 0.136985E+10 | 0.133155E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277664.64 | 1008796.03 |
Maximum of Months | 0.163685E+10 | 0.153432E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349806E+09 | 0.179664E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.971047E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22167.05 | 0.116702E+09 |
February | 0.649041E+09 | 0.862722E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1997888.54 | 0.133075E+09 |
March | 0.773965E+09 | 0.975350E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24738062.37 | 92001125.87 |
April | 0.688021E+09 | 0.857217E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104431E+09 | 9303873.73 |
May | 0.744847E+09 | 0.911547E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230905E+09 | 2244595.97 |
June | 0.742030E+09 | 0.908113E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158057E+09 | 1541443.35 |
July | 0.690839E+09 | 0.869477E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196167E+09 | 670876.10 |
August | 0.773965E+09 | 0.971769E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112106E+09 | 1305105.44 |
September | 0.688021E+09 | 0.884035E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65356622.22 | 2178302.11 |
October | 0.715730E+09 | 0.933109E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33258419.94 | 8194998.93 |
November | 0.708685E+09 | 0.960709E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7359565.36 | 28990721.69 |
December | 0.690839E+09 | 0.956903E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 615718.12 | 0.107581E+09 |
Annual Sum or Average | 0.858171E+10 | 0.110620E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935015E+09 | 0.503788E+09 |
Minimum of Months | 0.649041E+09 | 0.857217E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22167.05 | 670876.10 |
Maximum of Months | 0.773965E+09 | 0.975350E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230905E+09 | 0.133075E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146541E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208049E+09 |
February | 0.136988E+10 | 0.131569E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1854048.01 | 0.231897E+09 |
March | 0.163688E+10 | 0.151101E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34244396.46 | 0.152674E+09 |
April | 0.145246E+10 | 0.133465E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155526E+09 | 13926761.19 |
May | 0.157341E+10 | 0.142056E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347454E+09 | 3292008.44 |
June | 0.156904E+10 | 0.141513E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236633E+09 | 2179007.17 |
July | 0.145684E+10 | 0.136019E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291885E+09 | 1012765.55 |
August | 0.163688E+10 | 0.151620E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165511E+09 | 2036626.58 |
September | 0.145246E+10 | 0.137171E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94060461.93 | 3759273.09 |
October | 0.150994E+10 | 0.144017E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46135427.06 | 13688907.47 |
November | 0.149520E+10 | 0.144480E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8296314.10 | 52826330.34 |
December | 0.145684E+10 | 0.143049E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29227.29 | 0.198738E+09 |
Annual Sum or Average | 0.181198E+11 | 0.170260E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138163E+10 | 0.884079E+09 |
Minimum of Months | 0.136988E+10 | 0.131569E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012765.55 |
Maximum of Months | 0.163688E+10 | 0.151620E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347454E+09 | 0.231897E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.963682E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.19 | 0.120923E+09 |
February | 0.882782E+09 | 0.855342E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894536.37 | 0.136101E+09 |
March | 0.105485E+10 | 0.981362E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25055960.76 | 0.100833E+09 |
April | 0.936002E+09 | 0.860539E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103843E+09 | 10668548.07 |
May | 0.101394E+10 | 0.914151E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228279E+09 | 2896567.16 |
June | 0.101113E+10 | 0.910505E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155062E+09 | 1985798.22 |
July | 0.938820E+09 | 0.877191E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192640E+09 | 844779.19 |
August | 0.105485E+10 | 0.982261E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109693E+09 | 1666469.85 |
September | 0.936002E+09 | 0.889192E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63820753.44 | 2888397.08 |
October | 0.973041E+09 | 0.944444E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33674732.85 | 8202349.52 |
November | 0.963541E+09 | 0.942190E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7442184.92 | 28722065.48 |
December | 0.938820E+09 | 0.938548E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455455.17 | 0.110318E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110594E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921862E+09 | 0.526050E+09 |
Minimum of Months | 0.882782E+09 | 0.855342E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.19 | 844779.19 |
Maximum of Months | 0.105485E+10 | 0.982261E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228279E+09 | 0.136101E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.153402E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 628085.26 | 0.174396E+09 |
February | 0.136985E+10 | 0.135170E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9941615.05 | 0.202124E+09 |
March | 0.163685E+10 | 0.152348E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52495338.49 | 0.147956E+09 |
April | 0.145243E+10 | 0.133137E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198964E+09 | 13982049.22 |
May | 0.157338E+10 | 0.140651E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426887E+09 | 4229310.16 |
June | 0.156900E+10 | 0.140133E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288911E+09 | 2984082.04 |
July | 0.145680E+10 | 0.134772E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355331E+09 | 1298865.63 |
August | 0.163685E+10 | 0.151164E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203534E+09 | 2611011.00 |
September | 0.145243E+10 | 0.137675E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119408E+09 | 4378299.58 |
October | 0.150991E+10 | 0.146667E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66192691.76 | 12752411.93 |
November | 0.149516E+10 | 0.150430E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19371312.93 | 42715665.80 |
December | 0.145680E+10 | 0.151058E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4382253.95 | 0.160599E+09 |
Annual Sum or Average | 0.181194E+11 | 0.172661E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174605E+10 | 0.770027E+09 |
Minimum of Months | 0.136985E+10 | 0.133137E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 628085.26 | 1298865.63 |
Maximum of Months | 0.163685E+10 | 0.153402E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426887E+09 | 0.202124E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.970998E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135256.71 | 0.128529E+09 |
February | 0.882782E+09 | 0.862546E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2785915.33 | 0.153222E+09 |
March | 0.105485E+10 | 0.975245E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29615973.83 | 0.111289E+09 |
April | 0.936002E+09 | 0.857141E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126403E+09 | 11843230.64 |
May | 0.101394E+10 | 0.911540E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280516E+09 | 3039889.12 |
June | 0.101113E+10 | 0.908091E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192257E+09 | 2085013.59 |
July | 0.938820E+09 | 0.869447E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237457E+09 | 885277.18 |
August | 0.105485E+10 | 0.971563E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135338E+09 | 1790138.35 |
September | 0.936002E+09 | 0.883982E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78976957.29 | 2891012.28 |
October | 0.973041E+09 | 0.933035E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40235537.92 | 9793938.87 |
November | 0.963541E+09 | 0.960666E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9346640.57 | 33383066.99 |
December | 0.938820E+09 | 0.956856E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1364685.93 | 0.120210E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110611E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113443E+10 | 0.578961E+09 |
Minimum of Months | 0.882782E+09 | 0.857141E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135256.71 | 885277.18 |
Maximum of Months | 0.105485E+10 | 0.975245E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280516E+09 | 0.153222E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.146540E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235794E+09 |
February | 0.136988E+10 | 0.131546E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076372.88 | 0.270174E+09 |
March | 0.163688E+10 | 0.151087E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40965865.26 | 0.183758E+09 |
April | 0.145246E+10 | 0.133465E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189622E+09 | 17426479.25 |
May | 0.157341E+10 | 0.142043E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424151E+09 | 4381248.68 |
June | 0.156904E+10 | 0.141500E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288968E+09 | 2928790.27 |
July | 0.145684E+10 | 0.136013E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354972E+09 | 1305286.76 |
August | 0.163688E+10 | 0.151606E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200893E+09 | 2751570.29 |
September | 0.145246E+10 | 0.137143E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114452E+09 | 4939719.48 |
October | 0.150994E+10 | 0.144016E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56264387.63 | 16397145.10 |
November | 0.149520E+10 | 0.144479E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9891908.59 | 62299733.51 |
December | 0.145684E+10 | 0.143049E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24856.68 | 0.227996E+09 |
Annual Sum or Average | 0.181198E+11 | 0.170249E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168228E+10 | 0.103015E+10 |
Minimum of Months | 0.136988E+10 | 0.131546E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1305286.76 |
Maximum of Months | 0.163688E+10 | 0.151606E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424151E+09 | 0.270174E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.963583E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32086.30 | 0.137226E+09 |
February | 0.882782E+09 | 0.855293E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2640570.10 | 0.158152E+09 |
March | 0.105485E+10 | 0.981362E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30241329.47 | 0.121508E+09 |
April | 0.936002E+09 | 0.860539E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126747E+09 | 13377172.31 |
May | 0.101394E+10 | 0.914097E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279139E+09 | 3788273.54 |
June | 0.101113E+10 | 0.910397E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189852E+09 | 2536143.23 |
July | 0.938820E+09 | 0.877028E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234875E+09 | 1121241.29 |
August | 0.105485E+10 | 0.982203E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133512E+09 | 2207429.52 |
September | 0.936002E+09 | 0.889172E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77899030.14 | 3728528.19 |
October | 0.973041E+09 | 0.944398E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41316728.59 | 9733210.20 |
November | 0.963541E+09 | 0.942093E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9591957.97 | 33080934.40 |
December | 0.938820E+09 | 0.938543E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 957616.78 | 0.126123E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110587E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112680E+10 | 0.612582E+09 |
Minimum of Months | 0.882782E+09 | 0.855293E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32086.30 | 1121241.29 |
Maximum of Months | 0.105485E+10 | 0.982203E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279139E+09 | 0.158152E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193525E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021198.93 | 0.209602E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28173921.75 | 0.134329E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125600E+09 | 11302989.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281335E+09 | 3298067.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191510E+09 | 1805975.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238926E+09 | 788054.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130133E+09 | 1284920.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76353263.30 | 2379016.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38824242.47 | 11967616.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6401301.25 | 46230104.19 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.96 | 0.180825E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111828E+10 | 0.797338E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788054.02 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281335E+09 | 0.209602E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318113E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3080619.77 | 0.349997E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52765078.58 | 0.235022E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230597E+09 | 21950132.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508370E+09 | 5899822.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344962E+09 | 3477936.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431783E+09 | 1549565.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237670E+09 | 2602374.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136984E+09 | 4228430.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71027872.96 | 21300306.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13322618.55 | 77245497.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606155.41 | 0.294330E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203117E+10 | 0.133572E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549565.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508370E+09 | 0.349997E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312535E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725228.23 | 0.358032E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43461942.11 | 0.247578E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232148E+09 | 21031848.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549908E+09 | 6610425.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377105E+09 | 3514139.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459313E+09 | 1454782.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251914E+09 | 4111472.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142176E+09 | 4936854.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68468738.07 | 20524137.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10330434.05 | 75372579.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 968926.64 | 0.285279E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213652E+10 | 0.134098E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1454782.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549908E+09 | 0.358032E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 08-JAN-15:00 | 222.33 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 19-FEB-14:50 | 296.55 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 | 26-MAR-15:00 | 653.04 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1350.81 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.22 | 15-APR-17:06 | 98.48 | 22-APR-17:50 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.78 | 28-MAY-14:33 | 47.79 | 13-MAY-04:10 |
June | 2010.79 | 01-JUN-09:09 | 1803.00 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.52 | 17-JUN-20:30 | 49.88 | 18-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 2255.20 | 18-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.93 | 02-JUL-11:46 | 41.69 | 19-JUL-02:50 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 11-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.52 | 06-AUG-13:45 | 46.34 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.04 | 24-SEP-14:40 | 28.33 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.00 | 15-OCT-12:50 | 95.54 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.77 | 12-NOV-14:20 | 157.23 | 28-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 24-DEC-14:00 | 342.01 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 28.33 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 611.78 | 653.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 144.71 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 19-FEB-14:50 | 187.55 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.99 | 26-MAR-14:42 | 436.14 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.38 | 15-APR-17:06 | 63.68 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.03 | 28-MAY-14:33 | 31.00 | 13-MAY-04:10 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.56 | 17-JUN-20:50 | 29.93 | 18-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 18-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.41 | 02-JUL-11:44 | 22.90 | 19-JUL-02:50 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.95 | 06-AUG-13:45 | 25.11 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.93 | 24-SEP-14:26 | 16.70 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.63 | 15-OCT-12:10 | 59.88 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 | 12-NOV-14:20 | 102.60 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 26-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 24-DEC-14:00 | 214.51 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 409.03 | 436.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 249.03 | 22-JAN-14:30 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | 21-FEB-15:00 | 291.85 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.92 | 26-MAR-14:35 | 730.83 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1350.84 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.73 | 15-APR-17:05 | 107.64 | 22-APR-17:50 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 605.63 | 28-MAY-14:33 | 48.11 | 15-MAY-02:40 |
June | 2010.83 | 01-JUN-09:09 | 1803.04 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.26 | 17-JUN-20:30 | 49.85 | 18-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 2255.25 | 18-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.89 | 02-JUL-11:44 | 41.24 | 19-JUL-02:50 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 11-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 | 06-AUG-14:00 | 47.69 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 05-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.14 | 24-SEP-14:24 | 27.60 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.43 | 15-OCT-12:45 | 95.22 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2255.25 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 | 12-NOV-14:54 | 167.63 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2255.25 | 26-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 28-DEC-14:00 | 414.87 | 31-DEC-14:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 605.63 | 730.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 159.96 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 09-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 21-FEB-15:00 | 217.74 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.94 | 26-MAR-13:55 | 598.77 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 | 15-APR-17:10 | 114.57 | 22-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.58 | 28-MAY-14:54 | 45.93 | 15-MAY-02:40 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.03 | 17-JUN-20:27 | 47.81 | 18-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.48 | 02-JUL-11:46 | 41.98 | 19-JUL-02:50 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 11-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.80 | 06-AUG-14:00 | 51.56 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.73 | 24-SEP-14:24 | 26.97 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.39 | 15-OCT-12:10 | 78.75 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 12-NOV-13:34 | 126.30 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1453.34 | 26-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 28-DEC-14:00 | 273.92 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 399.58 | 598.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 05-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 | 08-JAN-15:00 | 429.36 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 09-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.06 | 19-FEB-14:50 | 606.33 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.12 | 26-MAR-15:00 | 1283.35 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1350.81 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.78 | 15-APR-17:01 | 203.96 | 22-APR-18:00 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1409.92 | 28-MAY-14:43 | 121.96 | 15-MAY-02:53 |
June | 2010.79 | 01-JUN-09:09 | 1803.00 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.81 | 17-JUN-20:30 | 111.90 | 18-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 2255.20 | 18-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.78 | 02-JUL-11:46 | 101.93 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 11-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.12 | 06-AUG-13:34 | 126.59 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.63 | 24-SEP-14:00 | 56.07 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.73 | 15-OCT-12:30 | 196.28 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.17 | 12-NOV-14:00 | 302.55 | 28-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 160.10 | 24-DEC-13:52 | 650.53 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 | 56.07 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1409.92 | 1283.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1453.34 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 08-JAN-15:00 | 284.64 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 | 19-FEB-14:50 | 401.88 | 18-FEB-05:55 |
March | 1239.33 | 01-MAR-08:09 | 1161.92 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.42 | 26-MAR-15:00 | 937.30 | 24-MAR-22:53 |
April | 1239.33 | 03-APR-07:10 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.09 | 15-APR-17:06 | 164.51 | 22-APR-18:00 |
May | 1239.33 | 01-MAY-07:10 | 947.51 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 944.45 | 28-MAY-14:43 | 91.15 | 15-MAY-02:53 |
June | 1239.33 | 01-JUN-07:10 | 947.51 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 440.59 | 17-JUN-20:30 | 75.16 | 18-JUN-04:00 |
July | 1239.33 | 03-JUL-07:10 | 1453.34 | 18-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.84 | 02-JUL-11:44 | 67.30 | 19-JUL-02:53 |
August | 1239.33 | 01-AUG-07:10 | 1453.34 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.31 | 06-AUG-13:34 | 87.17 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.16 | 24-SEP-14:26 | 35.62 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 1667.75 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.63 | 15-OCT-12:04 | 131.09 | 12-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 | 12-NOV-14:00 | 211.91 | 28-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 26-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 24-DEC-14:10 | 427.26 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 35.62 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 944.45 | 937.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 601.12 | 22-JAN-14:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 21-FEB-15:00 | 645.49 | 18-FEB-05:55 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.51 | 26-MAR-14:55 | 1541.62 | 24-MAR-22:53 |
April | 2010.83 | 03-APR-09:09 | 1350.84 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.62 | 15-APR-17:05 | 239.85 | 22-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.12 | 28-MAY-14:43 | 132.25 | 15-MAY-02:53 |
June | 2010.83 | 01-JUN-09:09 | 1803.04 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.74 | 03-JUN-17:10 | 110.82 | 18-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 2255.25 | 18-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.18 | 02-JUL-11:44 | 101.58 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 11-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.76 | 06-AUG-14:13 | 131.00 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 05-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.88 | 24-SEP-14:50 | 56.90 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.82 | 15-OCT-12:45 | 203.42 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2135.77 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.85 | 13-NOV-14:00 | 367.82 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2255.25 | 26-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 28-DEC-14:00 | 957.82 | 31-DEC-14:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.12 | 1541.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 08-JAN-13:53 | 301.45 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 09-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 19-FEB-13:30 | 414.44 | 18-FEB-05:55 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 292.32 | 26-MAR-13:00 | 1049.64 | 24-MAR-22:53 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.55 | 15-APR-17:05 | 163.34 | 22-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 28-MAY-14:57 | 118.27 | 15-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.13 | 17-JUN-20:27 | 92.47 | 18-JUN-02:32 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 18-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.09 | 02-JUL-11:46 | 72.66 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 11-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.81 | 06-AUG-09:40 | 94.60 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.30 | 24-SEP-14:24 | 39.62 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.71 | 15-OCT-12:10 | 137.65 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.43 | 12-NOV-12:40 | 222.90 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1453.34 | 29-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.28 | 24-DEC-13:42 | 448.20 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 39.62 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 1049.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2255.20 | 05-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.23 | 08-JAN-15:00 | 461.15 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 09-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.99 | 19-FEB-15:00 | 706.39 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 577.87 | 26-MAR-14:30 | 1506.60 | 24-MAR-22:53 |
April | 2010.79 | 03-APR-09:09 | 1350.81 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 965.28 | 15-APR-17:06 | 232.86 | 22-APR-18:03 |
May | 2010.79 | 01-MAY-09:09 | 1803.00 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.20 | 28-MAY-14:54 | 172.34 | 15-MAY-02:53 |
June | 2010.79 | 01-JUN-09:09 | 1803.00 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.57 | 17-JUN-20:30 | 147.41 | 18-JUN-02:43 |
July | 2010.79 | 03-JUL-09:09 | 2255.20 | 18-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 855.81 | 02-JUL-11:46 | 122.23 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 2255.20 | 11-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 547.82 | 06-AUG-13:34 | 167.47 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 2255.20 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.87 | 24-SEP-14:26 | 65.26 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 2587.92 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.04 | 15-OCT-11:51 | 229.04 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2255.20 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.45 | 12-NOV-13:50 | 340.89 | 29-NOV-24:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.37 | 24-DEC-13:52 | 731.60 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 73.23 | 65.26 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.20 | 1506.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 08-JAN-15:00 | 305.85 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 19-FEB-14:50 | 466.16 | 09-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1161.92 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.68 | 26-MAR-14:50 | 1109.35 | 24-MAR-22:53 |
April | 1295.83 | 03-APR-09:09 | 793.52 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.41 | 15-APR-17:06 | 197.43 | 02-APR-08:30 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.07 | 28-MAY-14:54 | 127.08 | 15-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 947.51 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 542.13 | 17-JUN-20:30 | 100.01 | 18-JUN-02:43 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 18-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.87 | 02-JUL-11:44 | 80.58 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.97 | 06-AUG-14:13 | 115.52 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.67 | 24-SEP-14:26 | 41.47 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.02 | 15-OCT-12:57 | 153.09 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.32 | 12-NOV-13:50 | 240.13 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 26-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.45 | 24-DEC-13:52 | 485.56 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 41.47 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.07 | 1109.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2255.25 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 713.62 | 22-JAN-14:27 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 21-FEB-15:00 | 729.05 | 18-FEB-05:55 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 418.28 | 26-MAR-14:45 | 1829.06 | 24-MAR-22:53 |
April | 2010.83 | 03-APR-09:09 | 1350.84 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 965.94 | 15-APR-17:05 | 277.02 | 22-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 1803.04 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1734.25 | 28-MAY-14:54 | 183.74 | 15-MAY-02:53 |
June | 2010.83 | 01-JUN-09:09 | 1803.04 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.55 | 17-JUN-20:30 | 145.86 | 18-JUN-02:43 |
July | 2010.83 | 03-JUL-09:09 | 2255.25 | 18-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 853.22 | 02-JUL-11:44 | 121.78 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 2255.25 | 11-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 546.48 | 06-AUG-14:13 | 172.64 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 2255.25 | 05-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.35 | 24-SEP-14:24 | 66.28 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 2587.98 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.40 | 15-OCT-13:00 | 238.45 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2135.77 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.33 | 13-NOV-14:00 | 433.39 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 2255.25 | 26-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 28-DEC-14:00 | 1142.08 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1350.84 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.28 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1734.25 | 1829.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1453.34 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 08-JAN-13:53 | 336.21 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 | 19-FEB-13:30 | 479.41 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.63 | 26-MAR-12:50 | 1244.73 | 24-MAR-22:53 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.14 | 15-APR-17:05 | 190.04 | 22-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1161.92 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.23 | 28-MAY-14:54 | 153.87 | 15-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 1161.92 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.65 | 17-JUN-20:27 | 120.53 | 18-JUN-02:65 |
July | 1295.83 | 03-JUL-09:09 | 1453.34 | 18-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.49 | 02-JUL-11:46 | 87.18 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 1453.34 | 11-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.63 | 06-AUG-09:40 | 123.99 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1453.34 | 05-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.79 | 24-SEP-14:24 | 45.77 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.25 | 15-OCT-11:51 | 161.68 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1453.34 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.35 | 12-NOV-13:10 | 259.34 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1453.34 | 29-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.19 | 24-DEC-13:52 | 511.20 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 1161.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 45.77 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.23 | 1244.73 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 472.10 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.45 | 19-FEB-15:00 | 681.99 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.38 | 26-MAR-15:00 | 1490.12 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.03 | 15-APR-17:01 | 218.88 | 22-APR-17:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1187.04 | 28-MAY-15:00 | 94.88 | 13-MAY-04:13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.93 | 03-JUN-17:02 | 104.87 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.47 | 02-JUL-11:30 | 86.30 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.18 | 06-AUG-14:10 | 90.45 | 15-AUG-23:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.20 | 24-SEP-14:10 | 43.57 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.62 | 15-OCT-12:30 | 191.56 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.26 | 12-NOV-14:00 | 355.41 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 28-DEC-14:00 | 748.93 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1187.04 | 1490.12 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 779.35 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.77 | 19-FEB-15:00 | 1174.19 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.91 | 26-MAR-14:42 | 2537.68 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.71 | 15-APR-17:01 | 376.44 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2147.76 | 28-MAY-15:00 | 169.19 | 13-MAY-04:12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 995.66 | 03-JUN-17:02 | 183.20 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.08 | 02-JUL-12:00 | 155.35 | 19-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.18 | 06-AUG-14:00 | 174.45 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.99 | 24-SEP-14:10 | 76.08 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.61 | 15-OCT-12:30 | 332.08 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.61 | 12-NOV-14:20 | 586.01 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.65 | 24-DEC-13:52 | 1254.36 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2147.76 | 2537.68 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 760.33 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 | 19-FEB-15:00 | 1206.48 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.62 | 26-MAR-15:10 | 2549.71 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.17 | 15-APR-17:01 | 300.79 | 22-APR-18:33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.99 | 28-MAY-14:40 | 191.80 | 15-MAY-03:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.85 | 03-JUN-17:10 | 194.83 | 18-JUN-03:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1019.49 | 02-JUL-11:30 | 157.18 | 19-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.57 | 06-AUG-09:20 | 240.18 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.03 | 24-SEP-14:10 | 66.35 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.87 | 15-OCT-11:51 | 342.05 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.59 | 12-NOV-14:10 | 548.19 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.35 | 24-DEC-13:52 | 1193.94 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.99 | 2549.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 122515.67 | 23-JAN-05:11 | 0.00 | 22951.19 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111198.99 | 27-FEB-05:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 112302.67 | 20-MAR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113256.62 | 30-APR-15:36 | 8976.13 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112827.80 | 07-MAY-18:57 | 0.00 | 8924.46 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107365.84 | 04-JUN-16:38 | 8976.13 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98639.03 | 04-JUL-18:57 | 0.00 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96167.59 | 29-AUG-03:02 | 0.00 | 7649.54 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95715.07 | 26-SEP-03:02 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112491.04 | 22-OCT-15:29 | 7180.90 | 10199.39 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 117157.83 | 24-NOV-05:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117311.45 | 20-DEC-05:12 | 0.00 | 12750.66 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95715.07 | 0.00 | 6374.62 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 122515.67 | 8976.13 | 22951.19 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 100432.60 | 17-JAN-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 106713.74 | 21-FEB-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 104578.15 | 20-MAR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97728.30 | 17-APR-05:05 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94269.64 | 01-MAY-05:02 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89804.78 | 14-JUN-05:02 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95992.04 | 31-JUL-05:03 | 9673.43 | 13741.19 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97165.81 | 08-AUG-05:04 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97925.39 | 13-SEP-03:02 | 0.00 | 5724.85 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 107133.83 | 30-OCT-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 108449.12 | 20-NOV-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107291.05 | 26-DEC-05:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89804.78 | 0.00 | 5724.85 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108449.12 | 11285.67 | 16031.39 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 86570.32 | 27-JAN-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92986.31 | 27-FEB-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95582.66 | 10-MAR-05:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94526.79 | 11-APR-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90740.55 | 13-MAY-04:12 | 0.00 | 6869.83 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82728.76 | 21-JUN-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81859.44 | 28-JUL-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84811.55 | 17-AUG-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90806.30 | 09-SEP-04:03 | 0.00 | 4579.88 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95986.43 | 12-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95758.51 | 01-NOV-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89677.48 | 29-DEC-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81859.44 | 0.00 | 4579.88 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95986.43 | 8061.19 | 13741.19 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37921.51 | 26-JAN-16:40 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85877.31 | 23-FEB-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95266.80 | 14-MAR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93194.02 | 10-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93104.75 | 13-MAY-04:12 | 0.00 | 6869.83 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86197.92 | 05-JUN-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92655.46 | 19-JUL-04:03 | 0.00 | 9160.79 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91333.54 | 17-AUG-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93138.86 | 14-SEP-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94396.63 | 11-OCT-03:02 | 0.00 | 5724.85 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88722.50 | 09-NOV-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47575.56 | 29-DEC-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 37921.51 | 0.00 | 5724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95266.80 | 15316.26 | 20611.01 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4915.97 | 26-JAN-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
February | 7200.93 | 23-FEB-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 0.00 |
March | 12384.59 | 11-MAR-06:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
April | 25229.90 | 30-APR-15:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 251.24 | 0.00 |
May | 25955.43 | 28-MAY-16:31 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 481.98 | 0.00 |
June | 25890.05 | 04-JUN-16:31 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 204.03 | 0.00 |
July | 24511.35 | 02-JUL-17:01 | 0.00 | 478.82 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 171.99 | 0.00 |
August | 24122.84 | 06-AUG-15:41 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 163.07 | 0.00 |
September | 24159.23 | 17-SEP-14:51 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 132.89 | 0.00 |
October | 16385.49 | 12-OCT-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 |
November | 7833.85 | 09-NOV-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 |
December | 5689.70 | 26-DEC-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4915.97 | 0.00 | 478.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25955.43 | 2010.79 | 1725.34 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 481.98 | 50.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4774.09 | 26-JAN-10:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
February | 8061.35 | 20-FEB-11:23 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 |
March | 18504.18 | 26-MAR-09:53 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
April | 20419.39 | 30-APR-15:01 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 160.32 | 0.00 |
May | 20951.97 | 28-MAY-15:11 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 349.76 | 0.00 |
June | 20288.56 | 04-JUN-15:51 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 148.86 | 0.00 |
July | 19778.24 | 04-JUL-09:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 64.49 | 0.00 |
August | 18918.52 | 06-AUG-15:01 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 | 0.00 |
September | 19443.68 | 17-SEP-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 0.00 |
October | 19612.10 | 15-OCT-10:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 0.00 |
November | 10987.28 | 12-NOV-10:13 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 |
December | 5399.32 | 01-DEC-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4774.09 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20951.97 | 1295.83 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 349.76 | 34.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24482.35 | 08-JAN-14:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.56 |
February | 27014.15 | 20-FEB-13:22 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
March | 26271.76 | 26-MAR-14:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 88.32 | 0.00 |
April | 27042.74 | 30-APR-14:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 213.66 | 0.00 |
May | 26344.90 | 28-MAY-15:11 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 532.71 | 0.00 |
June | 26021.05 | 04-JUN-16:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 204.96 | 0.00 |
July | 24675.55 | 02-JUL-16:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 179.09 | 0.00 |
August | 24765.90 | 06-AUG-15:01 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 171.04 | 0.00 |
September | 26329.37 | 17-SEP-14:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 112.28 | 0.00 |
October | 28161.75 | 15-OCT-13:21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 95.97 | 0.00 |
November | 28171.10 | 12-NOV-12:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 |
December | 26108.82 | 03-DEC-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24482.35 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28171.10 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 532.71 | 43.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7825.21 | 31-JAN-16:00 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
February | 25578.38 | 20-FEB-15:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
March | 26085.58 | 26-MAR-14:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 | 0.00 |
April | 31445.22 | 30-APR-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 110.50 | 0.00 |
May | 30591.96 | 28-MAY-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 266.43 | 0.00 |
June | 30278.95 | 04-JUN-16:31 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 | 0.00 |
July | 27255.41 | 02-JUL-16:21 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 | 0.00 |
August | 27009.98 | 06-AUG-15:41 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 92.83 | 0.00 |
September | 26779.13 | 17-SEP-14:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 73.56 | 0.00 |
October | 27370.24 | 22-OCT-14:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 0.00 |
November | 26398.10 | 12-NOV-14:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
December | 18474.16 | 24-DEC-15:13 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7825.21 | 260.91 | 176.32 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31445.22 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 266.43 | 36.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3028.69 | 26-JAN-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
February | 5855.75 | 24-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
March | 12022.74 | 29-MAR-04:12 | 0.00 | 1725.34 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24905.90 | 30-APR-16:11 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 587.64 | 0.00 |
May | 26504.41 | 28-MAY-16:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.04 | 0.00 |
June | 26040.55 | 04-JUN-16:41 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 460.66 | 0.00 |
July | 25010.58 | 16-JUL-16:51 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 200.99 | 0.00 |
August | 24929.39 | 06-AUG-17:31 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 237.78 | 0.00 |
September | 24140.97 | 17-SEP-14:51 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 305.54 | 0.00 |
October | 23779.25 | 01-OCT-15:21 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 156.88 | 0.00 |
November | 6493.96 | 09-NOV-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
December | 3359.24 | 03-DEC-14:12 | 506.08 | 342.01 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3028.69 | 0.00 | 342.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26504.41 | 2010.79 | 1725.34 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.04 | 28.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3501.31 | 26-JAN-11:10 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 |
February | 6971.67 | 22-FEB-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
March | 20621.37 | 12-MAR-10:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 |
April | 22855.67 | 30-APR-08:51 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
May | 23656.15 | 28-MAY-10:01 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 280.28 | 0.00 |
June | 21611.20 | 04-JUN-16:01 | 652.28 | 440.81 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 333.25 | 0.00 |
July | 20915.62 | 04-JUL-10:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 186.17 | 0.00 |
August | 21351.16 | 06-AUG-10:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 199.62 | 0.00 |
September | 20524.90 | 17-SEP-10:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.81 | 0.00 |
October | 21458.31 | 01-OCT-10:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 | 0.00 |
November | 7210.92 | 09-NOV-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
December | 4264.59 | 01-DEC-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3501.31 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23656.15 | 1239.33 | 793.52 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 333.25 | 34.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24536.90 | 08-JAN-14:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.77 |
February | 24813.89 | 20-FEB-14:22 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 |
March | 26629.19 | 12-MAR-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 0.00 |
April | 26552.51 | 30-APR-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 532.66 | 0.00 |
May | 26633.36 | 28-MAY-16:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.66 | 0.00 |
June | 25856.07 | 04-JUN-16:01 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 503.62 | 0.00 |
July | 24909.14 | 16-JUL-16:11 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 | 0.00 |
August | 25265.64 | 06-AUG-17:31 | 0.00 | 615.63 | 5032.61 | 0.00 | 0.00 | 0.00 | 0.00 | 232.03 | 0.00 |
September | 26354.71 | 17-SEP-14:51 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 249.91 | 0.00 |
October | 28564.15 | 01-OCT-12:01 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 105.54 | 0.00 |
November | 28114.86 | 11-NOV-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
December | 26316.68 | 03-DEC-12:52 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24536.90 | 0.00 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28564.15 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.66 | 105.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5513.03 | 31-JAN-16:10 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
February | 9092.16 | 20-FEB-16:23 | 260.91 | 176.32 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 |
March | 22700.31 | 12-MAR-16:01 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | 0.00 |
April | 27123.54 | 30-APR-16:11 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 279.00 | 0.00 |
May | 27991.74 | 28-MAY-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 634.86 | 0.00 |
June | 27137.60 | 04-JUN-16:01 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 281.26 | 0.00 |
July | 24611.67 | 16-JUL-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 110.02 | 0.00 |
August | 25063.49 | 06-AUG-17:31 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 128.13 | 0.00 |
September | 23914.65 | 17-SEP-14:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 168.15 | 0.00 |
October | 25291.46 | 01-OCT-15:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 | 0.00 |
November | 21965.30 | 05-NOV-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 0.00 |
December | 6120.90 | 01-DEC-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5513.03 | 0.00 | 176.32 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27991.74 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 634.86 | 22.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3169.05 | 26-JAN-15:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 |
February | 6055.82 | 23-FEB-14:50 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
March | 10412.49 | 29-MAR-15:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 182.01 | 0.00 |
April | 26923.18 | 16-APR-15:21 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 151.28 | 0.00 |
May | 27997.15 | 28-MAY-16:11 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1486.19 | 0.00 |
June | 28197.86 | 11-JUN-16:21 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 300.50 | 0.00 |
July | 29090.02 | 09-JUL-16:11 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 367.82 | 0.00 |
August | 28516.92 | 06-AUG-17:31 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 277.46 | 0.00 |
September | 20686.43 | 24-SEP-15:02 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.78 | 0.00 |
October | 27296.26 | 01-OCT-15:21 | 910.95 | 615.62 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 183.32 | 0.00 |
November | 6926.66 | 09-NOV-14:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
December | 3388.59 | 03-DEC-14:32 | 404.87 | 273.61 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3169.05 | 0.00 | 273.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29090.02 | 2010.79 | 1231.33 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1486.19 | 37.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3190.98 | 26-JAN-14:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 |
February | 6610.21 | 23-FEB-10:40 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
March | 15525.63 | 26-MAR-10:43 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 0.00 |
April | 22313.20 | 16-APR-10:02 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 | 0.00 |
May | 22838.31 | 29-MAY-09:31 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 719.92 | 0.00 |
June | 22042.54 | 11-JUN-10:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 167.90 | 0.00 |
July | 22321.14 | 09-JUL-16:11 | 587.05 | 396.73 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 249.68 | 0.00 |
August | 22367.68 | 06-AUG-10:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 235.81 | 0.00 |
September | 18017.18 | 24-SEP-09:02 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 0.00 |
October | 22316.09 | 01-OCT-10:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 58.56 | 0.00 |
November | 6875.20 | 09-NOV-10:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
December | 3259.79 | 01-DEC-10:40 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3190.98 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22838.31 | 1295.83 | 793.52 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 719.92 | 20.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18584.58 | 08-JAN-14:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 |
February | 29375.73 | 20-FEB-14:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
March | 29015.93 | 26-MAR-14:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 210.12 | 0.00 |
April | 28107.08 | 16-APR-15:21 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 143.32 | 0.00 |
May | 28386.85 | 14-MAY-14:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 153.34 | 0.00 |
June | 27999.67 | 11-JUN-16:21 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 301.95 | 0.00 |
July | 29071.52 | 09-JUL-16:11 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 366.85 | 0.00 |
August | 28801.69 | 06-AUG-17:31 | 0.00 | 615.63 | 5032.61 | 0.00 | 0.00 | 0.00 | 0.00 | 270.68 | 0.00 |
September | 27631.87 | 24-SEP-15:02 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 391.21 | 0.00 |
October | 32003.11 | 01-OCT-15:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 127.89 | 0.00 |
November | 30884.42 | 11-NOV-13:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
December | 26912.50 | 03-DEC-14:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18584.58 | 0.00 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32003.11 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 391.21 | 125.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5404.80 | 31-JAN-16:10 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
February | 17742.68 | 20-FEB-16:12 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 |
March | 25240.16 | 26-MAR-16:02 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 132.96 | 0.00 |
April | 26305.41 | 30-APR-16:31 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 424.42 | 0.00 |
May | 27418.78 | 28-MAY-16:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 880.18 | 0.00 |
June | 27211.72 | 11-JUN-16:21 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 182.73 | 0.00 |
July | 27912.39 | 09-JUL-16:11 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 | 0.00 |
August | 27574.18 | 06-AUG-17:31 | 0.00 | 396.73 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 149.64 | 0.00 |
September | 24642.65 | 24-SEP-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 219.66 | 0.00 |
October | 27731.16 | 01-OCT-15:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.56 | 0.00 |
November | 22906.58 | 05-NOV-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
December | 6072.35 | 28-DEC-15:40 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5404.80 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27912.39 | 1239.33 | 793.52 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.18 | 26.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4401.50 | 21-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8874.77 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
March | 12140.74 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 |
April | 21402.01 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
May | 22066.53 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.49 | 0.00 |
June | 22904.52 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 | 0.00 |
July | 24903.35 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | 0.00 |
August | 22862.44 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 0.00 |
September | 19115.72 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
October | 13864.43 | 02-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
November | 11524.08 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 |
December | 6973.32 | 26-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4401.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 | 60.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4010.62 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5482.75 | 22-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 0.00 |
March | 10701.89 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 |
April | 13770.90 | 26-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18996.95 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 0.00 |
June | 15596.30 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.01 | 0.00 |
July | 15391.11 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 0.00 |
August | 16412.94 | 09-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 0.00 |
September | 15492.23 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
October | 13382.02 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
November | 7798.88 | 10-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 |
December | 4399.39 | 02-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4010.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18996.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.01 | 18.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7080.94 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 |
February | 14635.93 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 |
March | 24111.58 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29810.40 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.88 | 0.00 |
May | 34012.28 | 04-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.58 | 0.00 |
June | 35854.95 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.62 | 0.00 |
July | 31865.81 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.42 | 0.00 |
August | 28468.61 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.08 | 0.00 |
September | 24501.86 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.49 | 0.00 |
October | 23523.63 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.80 | 0.00 |
November | 15992.70 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 0.00 |
December | 8712.50 | 01-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7080.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35854.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.62 | 46.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1984.02 | 12-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3990.19 | 21-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7241.48 | 31-MAR-23:50 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7959.82 | 16-APR-20:52 | 0.00 | 192.92 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3527.39 | 31-MAY-23:50 | 0.00 | 64.31 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5479.60 | 30-JUN-23:55 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7344.11 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7816.88 | 10-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3521.02 | 30-SEP-23:57 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5415.64 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5911.61 | 13-NOV-16:30 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7757.55 | 28-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1984.02 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7959.82 | 222.14 | 578.72 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1808.85 | 12-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3729.03 | 22-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7000.29 | 31-MAR-23:53 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7465.76 | 12-APR-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3430.63 | 31-MAY-23:53 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5258.53 | 30-JUN-23:42 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7032.81 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7275.55 | 10-AUG-16:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3366.35 | 30-SEP-23:27 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5115.02 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5589.48 | 09-NOV-16:50 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7300.09 | 01-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1808.85 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7465.76 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1831.36 | 12-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3780.02 | 22-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6955.30 | 31-MAR-23:53 | 0.00 | 96.46 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7618.32 | 16-APR-20:33 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3385.34 | 31-MAY-23:53 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5315.73 | 30-JUN-23:42 | 0.00 | 128.61 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7056.67 | 31-JUL-23:55 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7409.31 | 20-AUG-15:55 | 23.38 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3377.06 | 30-SEP-23:17 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4979.08 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5647.41 | 09-NOV-16:40 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7312.06 | 28-DEC-17:00 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1831.36 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7618.32 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93525.92 | 26-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 185038.38 | 21-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359321.45 | 31-MAR-23:53 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369041.38 | 30-APR-04:23 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176704.76 | 31-MAY-23:57 | 0.00 | 1078.42 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268994.67 | 30-JUN-23:53 | 0.00 | 1437.90 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356714.78 | 31-JUL-23:23 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370578.88 | 15-AUG-23:53 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177887.46 | 30-SEP-23:57 | 0.00 | 1078.42 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 270022.35 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278390.90 | 13-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369566.45 | 18-DEC-17:00 | 4808.68 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93525.92 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370578.88 | 4808.68 | 6471.01 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.181540E+13 | 1207417.09 | 12-JAN-16:40 | 0.101303E+12 | 614845.52 | 02-JAN-06:10 |
February | 0.210032E+13 | 1467671.42 | 22-FEB-16:10 | 0.617895E+11 | 373122.83 | 11-FEB-06:10 |
March | 0.295051E+13 | 1834465.31 | 28-MAR-15:00 | 0.598618E+11 | 73039.19 | 02-MAR-12:50 |
April | 0.345937E+13 | 2104683.20 | 18-APR-15:09 | 0.522508E+11 | 66670.21 | 07-APR-11:20 |
May | 0.254550E+13 | 1678408.02 | 09-MAY-15:00 | 0.512960E+11 | 62219.22 | 03-MAY-11:00 |
June | 0.302473E+13 | 1918981.12 | 22-JUN-15:09 | 0.474088E+11 | 55206.16 | 02-JUN-11:20 |
July | 0.352843E+13 | 2102920.83 | 05-JUL-15:00 | 0.457926E+11 | 49828.95 | 07-JUL-11:20 |
August | 0.397865E+13 | 2225472.94 | 07-AUG-15:20 | 0.488583E+11 | 54399.30 | 31-AUG-11:39 |
September | 0.240812E+13 | 1684270.78 | 14-SEP-15:30 | 0.482189E+11 | 60418.49 | 26-SEP-11:20 |
October | 0.261965E+13 | 1693656.59 | 03-OCT-15:09 | 0.533199E+11 | 66476.15 | 31-OCT-11:39 |
November | 0.275622E+13 | 1767278.72 | 07-NOV-16:40 | 0.559144E+11 | 72037.28 | 27-NOV-12:39 |
December | 0.308608E+13 | 1689026.59 | 28-DEC-16:30 | 0.745721E+11 | 340570.75 | 23-DEC-06:10 |
Annual Sum or Average | 0.342730E+14 | 0.700586E+12 | ||||
Minimum of Months | 0.181540E+13 | 1207417.09 | 0.457926E+11 | 49828.95 | ||
Maximum of Months | 0.397865E+13 | 2225472.94 | 0.101303E+12 | 614845.52 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.330324E+12 | 0.692018E+11 | 0.766053E+12 | 0.164269E+12 | 0.175330E+12 | 0.501084E+11 | 0.00 | 0.181833E+12 | 0.663064E+11 | 0.119707E+11 | 0.00 | 0.00 | 0.00 |
February | 0.298544E+12 | 0.592117E+11 | 0.978954E+12 | 0.148382E+12 | 0.171772E+12 | 0.480290E+11 | 0.00 | 0.280152E+12 | 0.102243E+12 | 0.130297E+11 | 0.00 | 0.00 | 0.00 |
March | 0.352112E+12 | 0.602193E+11 | 0.141687E+13 | 0.164522E+12 | 0.228198E+12 | 0.660727E+11 | 0.00 | 0.512072E+12 | 0.143811E+12 | 0.663263E+10 | 0.00 | 0.00 | 0.00 |
April | 0.313613E+12 | 0.530543E+11 | 0.165903E+13 | 0.158945E+12 | 0.261322E+12 | 0.884170E+11 | 0.00 | 0.760591E+12 | 0.163483E+12 | 0.920610E+09 | 0.00 | 0.00 | 0.00 |
May | 0.337492E+12 | 0.502348E+11 | 0.774844E+12 | 0.164394E+12 | 0.291462E+12 | 0.102594E+12 | 0.00 | 0.613080E+12 | 0.211387E+12 | 16671643.09 | 0.00 | 0.00 | 0.00 |
June | 0.335921E+12 | 0.461447E+11 | 0.106252E+13 | 0.159183E+12 | 0.288031E+12 | 0.106029E+12 | 0.00 | 0.802656E+12 | 0.224248E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.315830E+12 | 0.490256E+11 | 0.139340E+13 | 0.164156E+12 | 0.274624E+12 | 0.113301E+12 | 0.00 | 0.976558E+12 | 0.241533E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.352004E+12 | 0.527223E+11 | 0.173200E+13 | 0.164522E+12 | 0.280154E+12 | 0.115509E+12 | 0.00 | 0.104260E+13 | 0.239135E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315269E+12 | 0.560255E+11 | 0.740713E+12 | 0.158945E+12 | 0.244458E+12 | 0.950848E+11 | 0.00 | 0.579851E+12 | 0.217771E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328523E+12 | 0.633286E+11 | 0.108340E+13 | 0.164269E+12 | 0.233206E+12 | 0.763122E+11 | 0.00 | 0.501857E+12 | 0.167460E+12 | 0.129009E+10 | 0.00 | 0.00 | 0.00 |
November | 0.326159E+12 | 0.658027E+11 | 0.135889E+13 | 0.159042E+12 | 0.200033E+12 | 0.569950E+11 | 0.00 | 0.445156E+12 | 0.130639E+12 | 0.134989E+11 | 0.00 | 0.00 | 0.00 |
December | 0.320414E+12 | 0.708256E+11 | 0.170972E+13 | 0.164158E+12 | 0.182829E+12 | 0.529318E+11 | 0.00 | 0.428136E+12 | 0.122813E+12 | 0.342570E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392620E+13 | 0.695797E+12 | 0.146764E+14 | 0.193479E+13 | 0.283142E+13 | 0.971384E+12 | 0.00 | 0.712455E+13 | 0.203083E+13 | 0.816162E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.298544E+12 | 0.461447E+11 | 0.740713E+12 | 0.148382E+12 | 0.171772E+12 | 0.480290E+11 | 0.00 | 0.181833E+12 | 0.663064E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352112E+12 | 0.708256E+11 | 0.173200E+13 | 0.164522E+12 | 0.291462E+12 | 0.115509E+12 | 0.00 | 0.104260E+13 | 0.241533E+12 | 0.342570E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.405599E+11 | 0.00 | 0.607433E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.744593E+10 | 0.00 | 0.543436E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 16198330.25 | 0.00 | 0.598456E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.522508E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.512960E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.474088E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.457926E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.488583E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.482189E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.533199E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.370252E+09 | 0.00 | 0.555442E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.158017E+11 | 0.00 | 0.587705E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.641939E+11 | 0.00 | 0.636392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.457926E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.405599E+11 | 0.00 | 0.607433E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 372703.55 | 18-JAN-08:09 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118525.16 | 18-JAN-08:20 | 119264.73 | 12-JAN-15:20 | 32431.43 | 02-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 372703.55 | 10-FEB-08:09 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118525.16 | 10-FEB-08:20 | 161297.52 | 22-FEB-15:50 | 31762.63 | 23-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 369206.61 | 14-MAR-07:10 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118522.43 | 14-MAR-07:19 | 208243.22 | 13-MAR-15:00 | 59092.69 | 28-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 339583.15 | 03-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118499.31 | 03-APR-07:19 | 242193.73 | 17-APR-15:20 | 60884.82 | 10-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 352283.84 | 24-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118509.21 | 24-MAY-07:19 | 278067.41 | 30-MAY-14:09 | 61066.27 | 03-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 352283.84 | 23-JUN-07:10 | 57580.60 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 118509.21 | 23-JUN-07:19 | 282346.45 | 07-JUN-14:09 | 61369.93 | 12-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 372703.55 | 18-JUL-07:10 | 57580.60 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 118525.16 | 18-JUL-07:19 | 279978.52 | 05-JUL-15:20 | 61018.69 | 03-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 372703.55 | 16-AUG-07:10 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118525.16 | 16-AUG-07:19 | 262940.29 | 07-AUG-15:20 | 60470.29 | 07-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 372703.55 | 05-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118525.16 | 05-SEP-07:19 | 233926.13 | 26-SEP-15:00 | 60209.02 | 28-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 385834.94 | 11-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118535.44 | 11-OCT-07:19 | 208410.48 | 04-OCT-15:00 | 60333.62 | 03-OCT-14:50 | 0.00 | 01-OCT-00:10 |
November | 372823.95 | 27-NOV-16:00 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118509.47 | 02-NOV-07:19 | 174463.97 | 09-NOV-16:10 | 59726.64 | 09-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 379269.20 | 29-DEC-16:00 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118509.47 | 29-DEC-08:20 | 135585.76 | 01-DEC-15:30 | 31563.68 | 23-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 339583.15 | 57580.60 | 423497.50 | 118499.31 | 119264.73 | 31563.68 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118535.44 | 282346.45 | 61369.93 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 169012.36 | 12-JAN-15:20 | 50629.31 | 13-JAN-14:00 | 7505.96 | 21-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 271900.06 | 22-FEB-15:30 | 54145.00 | 24-FEB-15:39 | 11136.73 | 04-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 416552.26 | 29-MAR-12:20 | 95095.80 | 06-MAR-15:30 | 13986.93 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 525201.55 | 18-APR-15:39 | 95095.80 | 03-APR-09:30 | 7364.79 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 467264.96 | 17-MAY-15:30 | 95095.80 | 01-MAY-07:19 | 2128.84 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 578686.16 | 22-JUN-15:39 | 95095.80 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 593291.85 | 05-JUL-15:00 | 95095.80 | 01-JUL-00:20 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 613938.38 | 07-AUG-15:39 | 95095.80 | 01-AUG-00:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 467459.80 | 14-SEP-15:30 | 95095.80 | 01-SEP-00:00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 423056.27 | 03-OCT-14:50 | 95095.80 | 02-OCT-08:30 | 7149.74 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 399444.42 | 09-NOV-13:00 | 95095.80 | 06-NOV-11:39 | 15188.42 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 290134.09 | 28-DEC-14:00 | 51269.38 | 28-DEC-14:00 | 28629.27 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 169012.36 | 50629.31 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 613938.38 | 95095.80 | 28629.27 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1207417.09 | 12-JAN-16:40 | 343575.76 | 423497.50 | 0.00 | 84452.90 | 112915.25 | 30824.20 | 0.00 | 161694.12 | 50457.36 |
February | 1467671.42 | 22-FEB-16:10 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 158263.06 | 31367.61 | 0.00 | 266901.03 | 52605.75 |
March | 1834465.31 | 28-MAR-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 190666.20 | 59008.10 | 0.00 | 412869.83 | 95095.80 |
April | 2104683.20 | 18-APR-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 236581.12 | 59401.63 | 0.00 | 518487.89 | 95095.80 |
May | 1678408.02 | 09-MAY-15:00 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 245162.17 | 59748.73 | 0.00 | 438158.74 | 95095.80 |
June | 1918981.12 | 22-JUN-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 234710.04 | 60632.91 | 0.00 | 570008.40 | 95095.80 |
July | 2102920.83 | 05-JUL-15:00 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 277252.82 | 60454.99 | 0.00 | 593291.85 | 95095.80 |
August | 2225472.94 | 07-AUG-15:20 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 262940.29 | 60415.82 | 0.00 | 611904.27 | 95095.80 |
September | 1684270.78 | 14-SEP-15:30 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 221504.98 | 59967.63 | 0.00 | 467459.80 | 95095.80 |
October | 1693656.59 | 03-OCT-15:09 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 158058.42 | 60264.30 | 0.00 | 421704.11 | 95095.80 |
November | 1767278.72 | 07-NOV-16:40 | 343575.76 | 660080.29 | 0.00 | 84455.92 | 157012.96 | 58018.70 | 0.00 | 369039.28 | 95095.80 |
December | 1689026.59 | 28-DEC-16:30 | 343575.76 | 778371.69 | 0.00 | 84452.14 | 121509.68 | 30857.20 | 0.00 | 279334.49 | 50925.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1207417.09 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 112915.25 | 30824.20 | 0.00 | 161694.12 | 50457.36 | |
Maximum of Months | 2225472.94 | 343575.76 | 778371.69 | 0.00 | 84455.92 | 277252.82 | 60632.91 | 0.00 | 611904.27 | 95095.80 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 606698.94 | 02-JAN-06:10 | 0.00 | 75311.95 | 19-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 344136.90 | 11-FEB-06:10 | 0.00 | 75040.50 | 02-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 2897.14 | 01-MAR-06:49 | 0.00 | 73039.19 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 66670.21 | 07-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 62219.22 | 03-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 55206.16 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 49828.95 | 07-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 54399.30 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 60418.49 | 26-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 66476.15 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 24728.83 | 27-NOV-06:10 | 0.00 | 72037.28 | 27-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 332424.17 | 23-DEC-06:10 | 0.00 | 74766.09 | 27-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49828.95 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 606698.94 | 0.00 | 75311.95 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.00 | 2.00 | 27.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.95 | 0.00 | 26.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.29 | 0.00 | 26.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.97 | 0.00 | 25.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.91 | 0.00 | 25.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 25.83 | 0.00 | 25.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.09 | 0.17 | 26.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.97 | 1.17 | 26.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.19 | 1.00 | 26.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.26 | 0.00 | 26.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.76 | 0.17 | 26.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.66 | 0.50 | 26.69 |
Annual Sum or Average | 0.00 | 0.00 | 90.50 | 26.31 | 5.00 | 26.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.83 | 0.00 | 25.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.00 | 2.00 | 27.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.65 | 0.00 | 25.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.67 | 0.00 | 25.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.66 | 0.00 | 25.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.69 | 0.00 | 25.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.70 | 0.00 | 25.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.70 | 0.00 | 25.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.31 | 0.00 | 18.31 | 0.33 | 21.23 | 0.00 | 21.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.31 | 0.00 | 18.31 | 0.17 | 25.62 | 0.00 | 25.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.01 | 4.50 | 27.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.25 | 8.50 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.02 | 5.33 | 27.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.30 | 12.17 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.00 | 7.00 | 27.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.81 | 2.00 | 27.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 99.67 | 27.13 | 39.83 | 27.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.30 | 12.17 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.62 | 2.83 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.76 | 9.17 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.71 | 12.50 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.20 | 7.50 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.53 | 11.83 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.32 | 6.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.44 | 4.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.68 | 7.17 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 105.67 | 27.52 | 62.83 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.76 | 12.50 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 1.67 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.91 | 5.17 | 27.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.88 | 6.50 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.39 | 9.00 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.33 | 9.00 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.02 | 5.50 | 27.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.33 | 11.33 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.09 | 7.50 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.31 | 4.50 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 28.03 | 12.00 | 28.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.16 | 11.00 | 28.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.79 | 5.17 | 27.79 |
Annual Sum or Average | 0.00 | 0.00 | 166.00 | 27.46 | 88.33 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.02 | 1.67 | 27.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 28.16 | 12.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.87 | 2.50 | 27.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.53 | 5.00 | 27.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 27.88 | 21.00 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.62 | 13.00 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 27.63 | 14.67 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 27.77 | 20.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | 27.85 | 19.50 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.10 | 5.50 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.55 | 8.17 | 27.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.81 | 5.67 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.57 | 2.17 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 348.17 | 27.72 | 117.83 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | 27.88 | 21.00 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.44 | 2.67 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.29 | 9.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.06 | 5.00 | 27.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.21 | 10.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.84 | 5.00 | 27.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.11 | 2.00 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.23 | 0.00 | 19.23 | 84.33 | 27.14 | 34.50 | 27.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.23 | 0.00 | 19.23 | 25.67 | 27.44 | 10.83 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.65 | 3.50 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.87 | 11.00 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.74 | 12.50 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.35 | 8.33 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.53 | 12.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.39 | 6.67 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.68 | 4.50 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.74 | 8.33 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.31 | 0.00 | 19.31 | 118.17 | 27.59 | 67.17 | 27.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.31 | 0.00 | 19.31 | 27.33 | 27.87 | 12.50 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.83 | 27.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.02 | 4.50 | 28.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.93 | 5.67 | 27.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.57 | 8.00 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.32 | 9.50 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.04 | 5.00 | 27.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.23 | 10.83 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.99 | 6.33 | 27.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.27 | 4.67 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.79 | 13.17 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.20 | 11.33 | 28.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.78 | 4.00 | 27.78 |
Annual Sum or Average | 0.00 | 0.00 | 156.00 | 27.44 | 84.83 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.99 | 1.83 | 27.20 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 28.20 | 13.17 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.53 | 0.50 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 2.67 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.66 | 7.33 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 27.67 | 10.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 27.51 | 8.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.58 | 11.50 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.26 | 6.17 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.57 | 3.00 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.05 | 5.00 | 28.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.60 | 1.17 | 27.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 164.83 | 27.59 | 57.00 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 28.05 | 11.50 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.69 | 3.83 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.55 | 9.67 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.23 | 6.33 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.45 | 11.67 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.14 | 6.17 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.45 | 2.67 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.00 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 2.50 | 18.88 | 0.00 | 18.88 | 103.17 | 27.20 | 41.33 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.36 | 0.00 | 19.36 | 29.00 | 27.69 | 11.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.72 | 2.67 | 27.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.00 | 11.50 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.92 | 12.83 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.50 | 9.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.71 | 13.17 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.47 | 8.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.86 | 4.50 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.84 | 8.17 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 1.50 | 18.67 | 0.00 | 18.67 | 134.67 | 27.64 | 69.83 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.37 | 0.00 | 19.37 | 30.00 | 28.00 | 13.17 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.14 | 0.00 | 18.14 | 0.33 | 21.20 | 0.33 | 22.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.94 | 3.83 | 27.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.00 | 5.50 | 28.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.77 | 8.17 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.56 | 9.83 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.24 | 6.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.46 | 11.50 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.25 | 6.83 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.71 | 5.50 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 28.36 | 11.17 | 28.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.16 | 10.00 | 28.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.69 | 1.83 | 27.69 |
Annual Sum or Average | 0.67 | 18.14 | 0.00 | 18.14 | 159.83 | 27.60 | 81.00 | 27.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.20 | 0.33 | 22.73 |
Maximum of Months | 0.67 | 18.14 | 0.00 | 18.14 | 29.17 | 28.36 | 11.50 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.06 | 2.83 | 28.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.97 | 6.50 | 28.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 27.87 | 11.00 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 27.62 | 9.17 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.77 | 12.50 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.48 | 7.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.80 | 3.50 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.19 | 5.83 | 28.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.15 | 0.00 | 18.15 | 167.83 | 27.74 | 59.83 | 27.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.15 | 0.00 | 18.15 | 36.83 | 28.19 | 12.50 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 96.50 | 28.11 | 86.67 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 229.83 | 28.06 | 188.67 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 326.33 | 28.08 | 275.33 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 229.83 | 28.11 | 188.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 127.33 | 28.19 | 115.67 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 28.14 | 235.33 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 390.83 | 28.15 | 351.00 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 28.19 | 235.33 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 87.50 | 28.14 | 77.67 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 149.17 | 28.08 | 131.33 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 236.67 | 28.10 | 209.00 | 28.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 149.17 | 28.14 | 131.33 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 535.83 | 29.50 | 404.33 | 29.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.29 | 0.00 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.20 | 514.00 | 30.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1280.00 | 29.91 | 918.33 | 29.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.20 | 514.00 | 30.29 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 27.25 | 327.17 | 24.88 | 1.17 | 24.89 |
February | 12.00 | 26.82 | 368.83 | 24.74 | 12.00 | 24.81 |
March | 34.67 | 25.14 | 454.67 | 24.56 | 34.67 | 24.60 |
April | 30.83 | 24.24 | 428.50 | 24.60 | 30.83 | 24.58 |
May | 285.83 | 24.49 | 497.17 | 24.53 | 285.83 | 24.52 |
June | 333.17 | 24.59 | 496.00 | 24.54 | 333.17 | 24.55 |
July | 305.17 | 25.06 | 497.00 | 24.80 | 305.17 | 24.87 |
August | 271.00 | 24.97 | 514.00 | 24.67 | 271.00 | 24.74 |
September | 288.00 | 25.00 | 485.00 | 24.74 | 288.00 | 24.81 |
October | 103.17 | 25.17 | 502.00 | 24.73 | 103.17 | 24.79 |
November | 0.17 | 27.48 | 473.33 | 24.66 | 0.17 | 24.67 |
December | 0.00 | 0.00 | 400.83 | 24.78 | 0.00 | 24.78 |
Annual Sum or Average | 1665.17 | 24.85 | 5444.50 | 24.67 | 1665.17 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 327.17 | 24.53 | 0.00 | 24.52 |
Maximum of Months | 333.17 | 27.48 | 514.00 | 24.88 | 333.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 24.75 | 261.50 | 24.66 | 13.17 | 24.71 |
February | 3.50 | 25.55 | 364.50 | 24.41 | 2.33 | 24.43 |
March | 0.00 | 0.00 | 471.00 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 459.17 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 499.67 | 24.19 | 0.00 | 24.19 |
June | 0.00 | 0.00 | 496.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 485.00 | 24.26 | 0.00 | 24.26 |
October | 0.33 | 27.11 | 502.00 | 24.36 | 0.33 | 24.36 |
November | 0.00 | 0.00 | 470.33 | 24.43 | 0.00 | 24.43 |
December | 1.00 | 23.91 | 379.17 | 24.49 | 0.00 | 24.49 |
Annual Sum or Average | 31.33 | 24.84 | 5399.33 | 24.31 | 15.83 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 261.50 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 26.50 | 27.11 | 514.00 | 24.66 | 13.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 227.17 | 23.20 | 103.67 | 23.45 | 12.67 | 23.40 |
February | 97.33 | 23.55 | 233.83 | 24.06 | 8.00 | 24.10 |
March | 7.67 | 23.80 | 410.00 | 24.23 | 0.67 | 24.24 |
April | 1.67 | 23.84 | 413.00 | 24.16 | 0.00 | 24.16 |
May | 0.00 | 0.00 | 489.50 | 24.11 | 0.00 | 24.11 |
June | 0.00 | 0.00 | 496.00 | 24.13 | 0.00 | 24.13 |
July | 0.00 | 0.00 | 497.00 | 24.14 | 0.00 | 24.14 |
August | 0.00 | 0.00 | 514.00 | 24.16 | 0.00 | 24.16 |
September | 1.00 | 26.12 | 484.67 | 24.22 | 1.00 | 24.23 |
October | 0.00 | 0.00 | 493.83 | 24.27 | 0.00 | 24.27 |
November | 18.50 | 23.49 | 387.33 | 24.24 | 0.00 | 24.24 |
December | 160.33 | 23.37 | 126.83 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 513.67 | 23.34 | 4649.67 | 24.11 | 22.33 | 24.10 |
Minimum of Months | 0.00 | 0.00 | 103.67 | 23.45 | 0.00 | 23.40 |
Maximum of Months | 227.17 | 26.12 | 514.00 | 24.27 | 12.67 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 401.33 | 22.32 | 50.00 | 22.29 | 20.67 | 22.16 |
February | 207.50 | 22.87 | 152.50 | 23.40 | 7.83 | 23.43 |
March | 46.33 | 23.45 | 370.67 | 24.11 | 1.83 | 24.11 |
April | 0.17 | 23.49 | 428.50 | 24.21 | 0.00 | 24.21 |
May | 0.00 | 0.00 | 504.33 | 24.20 | 0.00 | 24.20 |
June | 0.00 | 0.00 | 496.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.83 | 26.30 | 482.00 | 24.26 | 0.83 | 24.27 |
October | 0.33 | 23.33 | 477.33 | 24.25 | 0.00 | 24.25 |
November | 117.17 | 23.08 | 266.67 | 23.81 | 0.00 | 23.81 |
December | 344.00 | 22.55 | 56.67 | 22.72 | 4.50 | 22.70 |
Annual Sum or Average | 1117.67 | 22.62 | 4295.67 | 23.86 | 35.67 | 23.84 |
Minimum of Months | 0.00 | 0.00 | 50.00 | 22.29 | 0.00 | 22.16 |
Maximum of Months | 401.33 | 26.30 | 514.00 | 24.26 | 20.67 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 392.50 | 22.65 | 24.33 | 22.73 | 0.00 | 22.73 |
February | 191.67 | 22.99 | 155.33 | 23.51 | 0.00 | 23.51 |
March | 27.83 | 23.28 | 393.50 | 24.17 | 0.00 | 24.17 |
April | 17.83 | 26.89 | 464.83 | 24.51 | 17.83 | 24.59 |
May | 39.33 | 26.82 | 508.00 | 24.65 | 39.33 | 24.80 |
June | 41.17 | 26.65 | 496.00 | 24.61 | 41.17 | 24.75 |
July | 63.50 | 26.79 | 497.00 | 24.82 | 63.50 | 25.02 |
August | 36.33 | 26.80 | 514.00 | 24.57 | 36.33 | 24.70 |
September | 34.33 | 26.45 | 485.00 | 24.57 | 34.33 | 24.68 |
October | 5.33 | 26.68 | 490.67 | 24.39 | 5.33 | 24.41 |
November | 75.33 | 23.29 | 325.50 | 24.04 | 0.00 | 24.04 |
December | 298.50 | 23.01 | 60.00 | 23.18 | 0.00 | 23.18 |
Annual Sum or Average | 1223.67 | 23.64 | 4414.17 | 24.23 | 237.83 | 24.33 |
Minimum of Months | 5.33 | 22.65 | 24.33 | 22.73 | 0.00 | 22.73 |
Maximum of Months | 392.50 | 26.89 | 514.00 | 24.82 | 63.50 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.00 | 22.68 | 58.67 | 22.93 | 0.00 | 22.93 |
February | 138.17 | 22.81 | 225.17 | 23.72 | 0.33 | 23.72 |
March | 45.33 | 24.11 | 428.83 | 24.29 | 12.67 | 24.36 |
April | 43.00 | 26.84 | 467.17 | 24.64 | 41.83 | 24.82 |
May | 54.67 | 26.98 | 508.00 | 24.76 | 54.67 | 24.95 |
June | 45.17 | 26.70 | 496.00 | 24.61 | 45.17 | 24.77 |
July | 57.33 | 26.87 | 497.00 | 24.76 | 57.33 | 24.96 |
August | 31.00 | 26.82 | 514.00 | 24.48 | 31.00 | 24.60 |
September | 31.83 | 26.54 | 485.00 | 24.55 | 31.83 | 24.67 |
October | 39.17 | 26.37 | 487.00 | 24.59 | 34.83 | 24.72 |
November | 72.50 | 23.23 | 356.50 | 24.14 | 3.33 | 24.16 |
December | 253.83 | 22.77 | 126.00 | 23.26 | 0.00 | 23.26 |
Annual Sum or Average | 1104.00 | 23.93 | 4649.33 | 24.31 | 313.00 | 24.44 |
Minimum of Months | 31.00 | 22.68 | 58.67 | 22.93 | 0.00 | 22.93 |
Maximum of Months | 292.00 | 26.98 | 514.00 | 24.76 | 57.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.33 | 22.85 | 215.33 | 23.61 | 2.00 | 23.63 |
February | 103.33 | 23.45 | 313.83 | 24.22 | 16.00 | 24.33 |
March | 45.67 | 25.38 | 451.33 | 24.50 | 25.33 | 24.62 |
April | 37.50 | 26.98 | 473.00 | 24.67 | 37.50 | 24.83 |
May | 40.83 | 26.90 | 508.00 | 24.68 | 40.83 | 24.83 |
June | 40.33 | 26.66 | 496.00 | 24.60 | 40.33 | 24.74 |
July | 60.83 | 26.81 | 497.00 | 24.81 | 60.83 | 25.00 |
August | 38.00 | 26.87 | 514.00 | 24.59 | 38.00 | 24.74 |
September | 43.50 | 26.64 | 485.00 | 24.68 | 43.50 | 24.83 |
October | 51.00 | 27.12 | 502.00 | 24.84 | 51.00 | 25.03 |
November | 62.83 | 25.90 | 433.17 | 24.76 | 43.50 | 24.95 |
December | 124.17 | 23.47 | 296.67 | 24.21 | 16.00 | 24.31 |
Annual Sum or Average | 846.33 | 24.85 | 5185.33 | 24.54 | 414.83 | 24.70 |
Minimum of Months | 37.50 | 22.85 | 215.33 | 23.61 | 2.00 | 23.63 |
Maximum of Months | 198.33 | 27.12 | 514.00 | 24.84 | 60.83 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.00 | 22.86 | 157.17 | 23.41 | 0.00 | 23.41 |
February | 73.67 | 23.56 | 329.00 | 24.30 | 10.33 | 24.37 |
March | 27.33 | 26.99 | 499.17 | 24.62 | 27.33 | 24.73 |
April | 108.83 | 26.41 | 485.00 | 24.96 | 108.83 | 25.19 |
May | 85.67 | 26.63 | 508.00 | 24.86 | 85.67 | 25.08 |
June | 99.00 | 26.37 | 496.00 | 24.84 | 99.00 | 25.05 |
July | 110.17 | 26.79 | 497.00 | 25.06 | 110.17 | 25.32 |
August | 98.33 | 26.84 | 514.00 | 24.93 | 98.33 | 25.19 |
September | 61.00 | 26.71 | 485.00 | 24.77 | 61.00 | 24.97 |
October | 54.17 | 26.96 | 502.00 | 24.83 | 54.17 | 25.02 |
November | 25.67 | 26.71 | 469.67 | 24.68 | 23.83 | 24.79 |
December | 39.00 | 23.98 | 366.50 | 24.50 | 6.67 | 24.53 |
Annual Sum or Average | 1038.83 | 25.40 | 5308.50 | 24.70 | 685.33 | 24.89 |
Minimum of Months | 25.67 | 22.86 | 157.17 | 23.41 | 0.00 | 23.41 |
Maximum of Months | 256.00 | 26.99 | 514.00 | 25.06 | 110.17 | 25.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 21.57 | 41.83 | 21.44 | 41.83 | 21.33 |
February | 347.83 | 22.32 | 50.67 | 22.53 | 2.17 | 22.52 |
March | 118.50 | 23.07 | 296.50 | 23.86 | 0.00 | 23.86 |
April | 14.00 | 26.09 | 441.83 | 24.47 | 10.67 | 24.52 |
May | 42.17 | 26.85 | 508.00 | 24.68 | 42.17 | 24.84 |
June | 52.33 | 26.53 | 496.00 | 24.65 | 52.33 | 24.81 |
July | 88.17 | 26.55 | 497.00 | 24.89 | 88.17 | 25.11 |
August | 52.83 | 26.44 | 514.00 | 24.62 | 52.83 | 24.78 |
September | 52.33 | 26.28 | 485.00 | 24.63 | 52.33 | 24.77 |
October | 23.50 | 23.29 | 457.00 | 24.25 | 1.67 | 24.26 |
November | 236.33 | 22.74 | 132.17 | 23.21 | 0.00 | 23.21 |
December | 490.50 | 21.92 | 26.83 | 21.83 | 26.83 | 21.75 |
Annual Sum or Average | 2015.17 | 22.77 | 3946.83 | 23.81 | 371.00 | 23.89 |
Minimum of Months | 14.00 | 21.57 | 26.83 | 21.44 | 0.00 | 21.33 |
Maximum of Months | 496.67 | 26.85 | 514.00 | 24.89 | 88.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.33 | 21.98 | 18.33 | 21.93 | 14.67 | 21.87 |
February | 210.50 | 22.45 | 108.17 | 23.08 | 0.00 | 23.08 |
March | 71.83 | 23.70 | 318.33 | 24.30 | 14.67 | 24.40 |
April | 45.67 | 26.87 | 392.67 | 24.87 | 44.17 | 25.06 |
May | 58.33 | 27.04 | 430.00 | 24.93 | 58.33 | 25.16 |
June | 56.83 | 26.70 | 418.00 | 24.81 | 56.83 | 25.01 |
July | 87.67 | 26.65 | 422.00 | 25.05 | 87.67 | 25.28 |
August | 50.83 | 26.59 | 433.00 | 24.75 | 50.83 | 24.92 |
September | 58.33 | 26.35 | 410.00 | 24.78 | 58.33 | 24.95 |
October | 52.00 | 25.77 | 398.33 | 24.71 | 38.50 | 24.88 |
November | 127.50 | 22.77 | 223.00 | 23.77 | 0.67 | 23.78 |
December | 360.67 | 22.22 | 6.83 | 22.22 | 3.50 | 22.20 |
Annual Sum or Average | 1587.50 | 23.43 | 3578.67 | 24.20 | 428.17 | 24.37 |
Minimum of Months | 45.67 | 21.98 | 6.83 | 21.93 | 0.00 | 21.87 |
Maximum of Months | 407.33 | 27.04 | 433.00 | 25.05 | 87.67 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 246.67 | 22.43 | 186.67 | 23.21 | 6.50 | 23.21 |
February | 139.83 | 22.96 | 263.83 | 23.96 | 15.17 | 24.07 |
March | 64.50 | 24.54 | 420.33 | 24.44 | 23.50 | 24.56 |
April | 32.33 | 26.99 | 464.33 | 24.68 | 32.33 | 24.82 |
May | 43.33 | 26.91 | 508.00 | 24.70 | 43.33 | 24.87 |
June | 51.00 | 26.53 | 496.00 | 24.64 | 51.00 | 24.80 |
July | 86.50 | 26.56 | 497.00 | 24.89 | 86.50 | 25.10 |
August | 54.83 | 26.55 | 514.00 | 24.66 | 54.83 | 24.83 |
September | 63.50 | 26.52 | 485.00 | 24.76 | 63.50 | 24.95 |
October | 54.17 | 27.09 | 492.83 | 24.89 | 54.17 | 25.09 |
November | 87.83 | 25.02 | 408.17 | 24.66 | 43.67 | 24.86 |
December | 188.17 | 22.84 | 238.33 | 23.79 | 12.00 | 23.86 |
Annual Sum or Average | 1112.67 | 24.37 | 4974.50 | 24.49 | 486.50 | 24.65 |
Minimum of Months | 32.33 | 22.43 | 186.67 | 23.21 | 6.50 | 23.21 |
Maximum of Months | 246.67 | 27.09 | 514.00 | 24.89 | 86.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.33 | 21.89 | 36.50 | 21.94 | 13.17 | 21.89 |
February | 261.00 | 22.39 | 128.50 | 23.03 | 1.67 | 23.05 |
March | 79.00 | 23.53 | 381.33 | 24.21 | 11.67 | 24.28 |
April | 39.83 | 27.01 | 476.83 | 24.72 | 39.83 | 24.89 |
May | 69.00 | 26.91 | 508.00 | 24.84 | 69.00 | 25.06 |
June | 73.17 | 26.63 | 496.00 | 24.77 | 73.17 | 24.99 |
July | 95.67 | 26.69 | 497.00 | 24.96 | 95.67 | 25.20 |
August | 58.50 | 26.69 | 514.00 | 24.70 | 58.50 | 24.89 |
September | 66.50 | 26.49 | 485.00 | 24.75 | 66.50 | 24.93 |
October | 37.83 | 25.61 | 475.33 | 24.55 | 25.33 | 24.67 |
November | 145.50 | 22.87 | 266.00 | 23.78 | 5.17 | 23.82 |
December | 391.67 | 22.17 | 62.50 | 22.38 | 6.33 | 22.35 |
Annual Sum or Average | 1749.00 | 23.38 | 4327.00 | 24.15 | 466.00 | 24.31 |
Minimum of Months | 37.83 | 21.89 | 36.50 | 21.94 | 1.67 | 21.89 |
Maximum of Months | 431.33 | 27.01 | 514.00 | 24.96 | 95.67 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 21.05 | 126.17 | 20.79 | 126.17 | 20.63 |
February | 380.67 | 21.93 | 64.50 | 22.02 | 25.00 | 21.93 |
March | 158.67 | 22.71 | 273.50 | 23.64 | 0.33 | 23.64 |
April | 36.33 | 25.04 | 433.33 | 24.47 | 17.67 | 24.56 |
May | 48.50 | 26.87 | 508.00 | 24.71 | 48.50 | 24.88 |
June | 57.00 | 26.54 | 496.00 | 24.67 | 57.00 | 24.84 |
July | 98.00 | 26.51 | 497.00 | 24.92 | 98.00 | 25.14 |
August | 59.67 | 26.40 | 514.00 | 24.64 | 59.67 | 24.81 |
September | 56.33 | 26.21 | 485.00 | 24.62 | 56.33 | 24.77 |
October | 56.50 | 23.17 | 417.00 | 24.16 | 6.17 | 24.18 |
November | 313.67 | 22.37 | 108.17 | 22.75 | 3.50 | 22.73 |
December | 494.50 | 21.34 | 79.00 | 21.12 | 79.00 | 20.96 |
Annual Sum or Average | 2258.83 | 22.45 | 4001.67 | 23.54 | 577.33 | 23.56 |
Minimum of Months | 36.33 | 21.05 | 64.50 | 20.79 | 0.33 | 20.63 |
Maximum of Months | 499.00 | 26.87 | 514.00 | 24.92 | 126.17 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.83 | 21.54 | 72.33 | 21.34 | 66.83 | 21.16 |
February | 268.17 | 22.21 | 128.50 | 22.73 | 10.67 | 22.67 |
March | 91.33 | 23.19 | 379.50 | 24.11 | 11.00 | 24.17 |
April | 56.50 | 26.46 | 461.67 | 24.75 | 48.83 | 24.94 |
May | 62.33 | 27.07 | 508.00 | 24.83 | 62.33 | 25.05 |
June | 62.17 | 26.72 | 496.00 | 24.72 | 62.17 | 24.92 |
July | 99.83 | 26.61 | 497.00 | 24.95 | 99.83 | 25.19 |
August | 59.67 | 26.55 | 514.00 | 24.67 | 59.67 | 24.85 |
September | 62.17 | 26.34 | 482.67 | 24.68 | 62.17 | 24.85 |
October | 68.50 | 24.93 | 452.17 | 24.53 | 37.50 | 24.68 |
November | 174.50 | 22.48 | 241.00 | 23.45 | 1.50 | 23.44 |
December | 463.50 | 21.90 | 45.00 | 21.78 | 40.33 | 21.66 |
Annual Sum or Average | 1952.50 | 23.05 | 4277.83 | 23.93 | 562.83 | 24.04 |
Minimum of Months | 56.50 | 21.54 | 45.00 | 21.34 | 1.50 | 21.16 |
Maximum of Months | 483.83 | 27.07 | 514.00 | 24.95 | 99.83 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 297.83 | 21.83 | 189.67 | 22.39 | 44.33 | 22.18 |
February | 182.67 | 22.46 | 236.17 | 23.52 | 17.67 | 23.57 |
March | 93.50 | 23.79 | 391.00 | 24.29 | 22.67 | 24.41 |
April | 42.67 | 26.43 | 455.50 | 24.69 | 36.17 | 24.84 |
May | 49.67 | 26.92 | 508.00 | 24.73 | 49.67 | 24.91 |
June | 56.00 | 26.55 | 496.00 | 24.66 | 56.00 | 24.84 |
July | 97.00 | 26.52 | 497.00 | 24.92 | 97.00 | 25.14 |
August | 62.17 | 26.51 | 514.00 | 24.68 | 62.17 | 24.86 |
September | 67.00 | 26.45 | 485.00 | 24.76 | 67.00 | 24.94 |
October | 65.83 | 26.23 | 473.33 | 24.81 | 51.67 | 25.01 |
November | 121.83 | 23.99 | 367.33 | 24.40 | 38.17 | 24.60 |
December | 243.00 | 22.23 | 209.00 | 23.11 | 21.67 | 23.04 |
Annual Sum or Average | 1379.17 | 23.80 | 4822.00 | 24.30 | 564.17 | 24.43 |
Minimum of Months | 42.67 | 21.83 | 189.67 | 22.39 | 17.67 | 22.18 |
Maximum of Months | 297.83 | 26.92 | 514.00 | 24.92 | 97.00 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 443.00 | 21.43 | 93.50 | 21.31 | 74.67 | 21.14 |
February | 293.00 | 22.03 | 121.33 | 22.60 | 9.33 | 22.56 |
March | 121.33 | 23.12 | 347.33 | 24.03 | 12.83 | 24.10 |
April | 48.17 | 26.41 | 460.00 | 24.72 | 43.17 | 24.88 |
May | 80.67 | 26.56 | 508.00 | 24.83 | 80.67 | 25.04 |
June | 88.17 | 26.28 | 496.00 | 24.76 | 88.17 | 24.96 |
July | 103.17 | 26.64 | 497.00 | 24.97 | 103.17 | 25.21 |
August | 65.67 | 26.62 | 514.00 | 24.72 | 65.67 | 24.91 |
September | 69.17 | 26.45 | 483.17 | 24.74 | 69.17 | 24.93 |
October | 59.83 | 24.59 | 445.17 | 24.46 | 26.17 | 24.58 |
November | 212.17 | 22.51 | 221.50 | 23.39 | 3.50 | 23.42 |
December | 418.00 | 21.74 | 77.33 | 21.82 | 34.67 | 21.70 |
Annual Sum or Average | 2002.33 | 23.05 | 4264.33 | 23.93 | 611.17 | 24.06 |
Minimum of Months | 48.17 | 21.43 | 77.33 | 21.31 | 3.50 | 21.14 |
Maximum of Months | 443.00 | 26.64 | 514.00 | 24.97 | 103.17 | 25.21 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.33 | 27.00 | 454.00 | 27.00 | 1.33 | 27.00 |
March | 115.83 | 27.00 | 514.00 | 27.00 | 115.83 | 27.00 |
April | 393.50 | 27.29 | 485.00 | 27.26 | 393.50 | 27.27 |
May | 127.50 | 27.00 | 508.00 | 27.00 | 127.50 | 27.00 |
June | 255.00 | 27.00 | 496.00 | 27.00 | 255.00 | 27.00 |
July | 344.67 | 27.00 | 497.00 | 27.00 | 344.67 | 27.00 |
August | 507.33 | 27.48 | 514.00 | 27.48 | 507.33 | 27.48 |
September | 101.83 | 27.00 | 485.00 | 27.00 | 101.83 | 27.00 |
October | 87.00 | 27.00 | 502.00 | 27.00 | 87.00 | 27.00 |
November | 90.67 | 27.00 | 489.00 | 27.00 | 90.67 | 27.00 |
December | 56.17 | 27.00 | 497.00 | 27.00 | 56.17 | 27.00 |
Annual Sum or Average | 2080.83 | 27.17 | 5943.00 | 27.09 | 2080.83 | 27.11 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 507.33 | 27.48 | 514.00 | 27.48 | 507.33 | 27.48 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 496.67 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 4.50 | 27.00 | 514.00 | 27.00 | 4.50 | 27.00 |
April | 169.50 | 27.90 | 485.00 | 27.48 | 169.50 | 27.56 |
May | 50.83 | 27.00 | 508.00 | 27.00 | 50.83 | 27.00 |
June | 86.50 | 27.00 | 496.00 | 27.00 | 86.50 | 27.00 |
July | 82.50 | 27.00 | 497.00 | 27.00 | 82.50 | 27.00 |
August | 284.17 | 28.02 | 514.00 | 27.74 | 284.17 | 27.82 |
September | 20.50 | 27.00 | 485.00 | 27.00 | 20.50 | 27.00 |
October | 6.33 | 27.00 | 502.00 | 27.00 | 6.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 704.83 | 27.63 | 5937.67 | 27.14 | 704.83 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 284.17 | 28.02 | 514.00 | 27.74 | 284.17 | 27.82 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.33 | 24.80 | 454.00 | 26.86 | 0.00 | 26.86 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 26.33 | 27.00 | 514.00 | 27.00 | 26.33 | 27.00 |
April | 171.67 | 27.59 | 485.00 | 27.31 | 171.67 | 27.37 |
May | 137.33 | 27.00 | 508.00 | 27.00 | 137.33 | 27.00 |
June | 173.33 | 27.00 | 496.00 | 27.00 | 173.33 | 27.00 |
July | 148.33 | 27.00 | 497.00 | 27.00 | 148.33 | 27.00 |
August | 223.50 | 27.75 | 514.00 | 27.46 | 223.50 | 27.53 |
September | 67.17 | 27.00 | 485.00 | 27.00 | 67.17 | 27.00 |
October | 32.00 | 27.00 | 502.00 | 27.00 | 32.00 | 27.00 |
November | 0.50 | 27.00 | 489.00 | 27.00 | 0.50 | 27.00 |
December | 0.00 | 0.00 | 488.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1010.50 | 27.20 | 5886.33 | 27.07 | 980.17 | 27.10 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 26.86 | 0.00 | 26.86 |
Maximum of Months | 223.50 | 27.75 | 514.00 | 27.46 | 223.50 | 27.53 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.30 | 485.00 | 29.30 | 485.00 | 29.30 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 30.41 | 514.00 | 30.41 | 514.00 | 30.41 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.49 | 5943.00 | 27.49 | 5943.00 | 27.49 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.41 | 514.00 | 30.41 | 514.00 | 30.41 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00077 | 28.69003 | 0.84537 | 20.13729 |
February | 454.00000 | 27.00100 | 29.04745 | 0.91056 | 22.56268 |
March | 514.00000 | 27.00062 | 30.63507 | 0.98829 | 25.66759 |
April | 485.00000 | 27.23527 | 32.17138 | 1.10741 | 31.04435 |
May | 508.00000 | 27.00067 | 36.74562 | 0.36164 | 7.78945 |
June | 496.00000 | 27.00246 | 36.53926 | 0.40664 | 8.50482 |
July | 497.00000 | 27.00172 | 35.75682 | 0.43548 | 9.01002 |
August | 514.00000 | 27.47434 | 34.33653 | 0.60728 | 13.36881 |
September | 485.00000 | 27.00010 | 39.44916 | 0.36246 | 7.78518 |
October | 502.00000 | 27.00171 | 32.61245 | 0.98747 | 25.62942 |
November | 489.00000 | 27.00068 | 29.87801 | 0.97822 | 25.25349 |
December | 497.00000 | 27.00023 | 27.73625 | 0.95854 | 24.45557 |
Annual Sum or Average | 5943.00000 | 27.06105 | 32.82002 | 0.74425 | 18.38670 |
Minimum of Months | 454.00000 | 27.00010 | 27.73625 | 0.36164 | 7.78518 |
Maximum of Months | 514.00000 | 27.47434 | 39.44916 | 1.10741 | 31.04435 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99490 | 29.67254 | 0.75978 | 17.27941 |
February | 454.00000 | 27.00086 | 29.75416 | 0.82611 | 19.48940 |
March | 514.00000 | 27.00056 | 31.27925 | 0.91667 | 22.81133 |
April | 485.00000 | 27.32809 | 32.65706 | 1.04014 | 28.12383 |
May | 508.00000 | 27.00063 | 37.48895 | 0.32220 | 7.23298 |
June | 496.00000 | 27.00243 | 37.29066 | 0.34491 | 7.54500 |
July | 497.00000 | 27.00166 | 36.51741 | 0.34666 | 7.55843 |
August | 514.00000 | 27.59032 | 35.04320 | 0.49432 | 10.86394 |
September | 485.00000 | 27.00010 | 40.49948 | 0.31736 | 7.14757 |
October | 502.00000 | 27.00161 | 33.33698 | 0.93407 | 23.47355 |
November | 489.00000 | 27.00060 | 30.54110 | 0.88573 | 21.63814 |
December | 497.00000 | 27.00020 | 28.29230 | 0.81542 | 19.12812 |
Annual Sum or Average | 5943.00000 | 27.07812 | 33.55131 | 0.66539 | 15.98230 |
Minimum of Months | 454.00000 | 26.99490 | 28.29230 | 0.31736 | 7.14757 |
Maximum of Months | 514.00000 | 27.59032 | 40.49948 | 1.04014 | 28.12383 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.84378 | 30.25410 | 0.67936 | 15.49831 |
February | 454.00000 | 27.00094 | 29.27215 | 0.78918 | 18.31703 |
March | 514.00000 | 27.00063 | 30.67522 | 0.90433 | 22.39768 |
April | 485.00000 | 27.21147 | 32.20507 | 1.02742 | 27.57032 |
May | 508.00000 | 27.00067 | 36.87577 | 0.34607 | 7.63290 |
June | 496.00000 | 27.00251 | 36.65077 | 0.36806 | 7.95326 |
July | 497.00000 | 27.00185 | 35.86993 | 0.36639 | 7.90305 |
August | 514.00000 | 27.33230 | 34.54430 | 0.44710 | 9.82517 |
September | 485.00000 | 27.00009 | 39.88302 | 0.32461 | 7.28896 |
October | 502.00000 | 27.00169 | 32.75424 | 0.92647 | 23.22245 |
November | 489.00000 | 27.00067 | 29.95084 | 0.85400 | 20.55155 |
December | 497.00000 | 27.00026 | 27.76892 | 0.75752 | 17.30444 |
Annual Sum or Average | 5943.00000 | 27.03358 | 33.07950 | 0.64771 | 15.41700 |
Minimum of Months | 454.00000 | 26.84378 | 27.76892 | 0.32461 | 7.28896 |
Maximum of Months | 514.00000 | 27.33230 | 39.88302 | 1.02742 | 27.57032 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00512 | 30.03622 | 1.09032 | 30.08273 |
February | 454.00000 | 27.00593 | 30.20326 | 1.24172 | 37.31911 |
March | 514.00000 | 27.00300 | 31.04791 | 1.38889 | 44.92521 |
April | 485.00000 | 29.30334 | 31.15865 | 1.99152 | 74.61872 |
May | 508.00000 | 27.00344 | 34.96180 | 0.57813 | 12.08049 |
June | 496.00000 | 27.00318 | 35.10692 | 0.80441 | 18.67144 |
July | 497.00000 | 27.00171 | 34.52632 | 1.01474 | 26.76403 |
August | 514.00000 | 30.41338 | 31.96667 | 2.20682 | 83.48322 |
September | 485.00000 | 27.00424 | 35.50618 | 0.64804 | 13.88903 |
October | 502.00000 | 27.00275 | 32.02708 | 1.30987 | 40.78445 |
November | 489.00000 | 27.00425 | 30.65885 | 1.42735 | 46.97734 |
December | 497.00000 | 27.00647 | 30.05708 | 1.53418 | 52.76007 |
Annual Sum or Average | 5943.00000 | 27.48651 | 32.28231 | 1.27115 | 40.27254 |
Minimum of Months | 454.00000 | 27.00171 | 30.03622 | 0.57813 | 12.08049 |
Maximum of Months | 514.00000 | 30.41338 | 35.50618 | 2.20682 | 83.48322 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56985 | 39.83306 | 0.51805 | 11.22152 |
February | 454.00000 | 24.54924 | 44.34038 | 0.54742 | 11.82235 |
March | 514.00000 | 24.46036 | 48.09006 | 0.55913 | 12.05082 |
April | 485.00000 | 24.55803 | 47.39629 | 0.57621 | 12.54822 |
May | 508.00000 | 24.53939 | 58.39408 | -0.1893 | 6.82101 |
June | 496.00000 | 24.50194 | 61.98419 | -0.1610 | 6.78065 |
July | 497.00000 | 24.64755 | 63.25734 | -0.0933 | 7.11558 |
August | 514.00000 | 24.50943 | 62.01578 | -0.1260 | 6.93093 |
September | 485.00000 | 24.59194 | 63.35296 | -0.1083 | 7.07142 |
October | 502.00000 | 24.63847 | 55.60229 | 0.67559 | 15.29838 |
November | 489.00000 | 24.64196 | 46.87933 | 0.61051 | 13.48978 |
December | 497.00000 | 24.62665 | 39.94784 | 0.54593 | 11.88177 |
Annual Sum or Average | 5943.00000 | 24.56912 | 52.66232 | 0.27675 | 10.23371 |
Minimum of Months | 454.00000 | 24.46036 | 39.83306 | -0.1893 | 6.78065 |
Maximum of Months | 514.00000 | 24.64755 | 63.35296 | 0.67559 | 15.29838 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32934 | 42.84676 | 0.47374 | 10.30078 |
February | 454.00000 | 24.32446 | 45.37934 | 0.51271 | 10.80689 |
March | 514.00000 | 24.26793 | 48.81827 | 0.54895 | 11.53093 |
April | 485.00000 | 24.22919 | 48.52922 | 0.55723 | 11.66844 |
May | 508.00000 | 24.18412 | 54.17108 | -0.2824 | 6.81956 |
June | 496.00000 | 24.18738 | 55.84108 | -0.2608 | 6.58341 |
July | 497.00000 | 24.23859 | 56.25549 | -0.2371 | 6.37975 |
August | 514.00000 | 24.21644 | 56.06681 | -0.2259 | 6.27938 |
September | 485.00000 | 24.26413 | 56.66886 | -0.2487 | 6.62061 |
October | 502.00000 | 24.35523 | 53.82184 | 0.60969 | 13.06469 |
November | 489.00000 | 24.41188 | 47.84094 | 0.57487 | 12.27766 |
December | 497.00000 | 24.38825 | 40.99183 | 0.50354 | 10.63114 |
Annual Sum or Average | 5943.00000 | 24.28245 | 50.64851 | 0.20748 | 9.39734 |
Minimum of Months | 454.00000 | 24.18412 | 40.99183 | -0.2824 | 6.27938 |
Maximum of Months | 514.00000 | 24.41188 | 56.66886 | 0.60969 | 13.06469 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69540 | 44.43615 | 0.29091 | 7.22281 |
February | 454.00000 | 24.00496 | 46.10011 | 0.40466 | 8.83501 |
March | 514.00000 | 24.18238 | 48.93911 | 0.49815 | 10.40713 |
April | 485.00000 | 24.14315 | 48.95482 | 0.50321 | 10.42183 |
May | 508.00000 | 24.10608 | 54.51219 | -0.3352 | 7.45789 |
June | 496.00000 | 24.12970 | 56.43304 | -0.3129 | 7.18797 |
July | 497.00000 | 24.14275 | 57.27867 | -0.3105 | 7.14804 |
August | 514.00000 | 24.15623 | 57.43819 | -0.3027 | 7.08668 |
September | 485.00000 | 24.21855 | 57.10790 | -0.2931 | 7.09321 |
October | 502.00000 | 24.26453 | 54.28457 | 0.56359 | 11.85297 |
November | 489.00000 | 24.18563 | 48.34829 | 0.48523 | 10.17889 |
December | 497.00000 | 23.86140 | 42.44459 | 0.33549 | 7.71987 |
Annual Sum or Average | 5943.00000 | 24.09131 | 51.40390 | 0.12440 | 8.54693 |
Minimum of Months | 454.00000 | 23.69540 | 42.44459 | -0.3352 | 7.08668 |
Maximum of Months | 514.00000 | 24.26453 | 57.43819 | 0.56359 | 11.85297 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64794 | 45.88430 | 0.01879 | 7.29644 |
February | 454.00000 | 23.48130 | 47.96250 | 0.27194 | 7.65882 |
March | 514.00000 | 24.07023 | 49.68096 | 0.47347 | 9.99330 |
April | 485.00000 | 24.18463 | 49.10587 | 0.52887 | 11.02874 |
May | 508.00000 | 24.19829 | 54.28989 | -0.2724 | 6.80123 |
June | 496.00000 | 24.19778 | 56.16234 | -0.2566 | 6.64782 |
July | 497.00000 | 24.24775 | 56.93660 | -0.2494 | 6.58348 |
August | 514.00000 | 24.21393 | 57.34667 | -0.2612 | 6.67433 |
September | 485.00000 | 24.25335 | 57.26129 | -0.2658 | 6.85188 |
October | 502.00000 | 24.21435 | 55.07293 | 0.55648 | 11.66997 |
November | 489.00000 | 23.82723 | 50.06073 | 0.39372 | 8.77050 |
December | 497.00000 | 22.98655 | 45.11642 | 0.11220 | 6.75507 |
Annual Sum or Average | 5943.00000 | 23.87980 | 52.11032 | 0.08543 | 8.06123 |
Minimum of Months | 454.00000 | 22.64794 | 45.11642 | -0.2724 | 6.58348 |
Maximum of Months | 514.00000 | 24.25335 | 57.34667 | 0.55648 | 11.66997 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93418 | 44.61074 | 0.09725 | 6.19411 |
February | 454.00000 | 23.60704 | 46.65730 | 0.30434 | 7.75210 |
March | 514.00000 | 24.13814 | 48.46592 | 0.50177 | 10.60225 |
April | 485.00000 | 24.39762 | 47.22464 | 0.63115 | 13.90082 |
May | 508.00000 | 24.48644 | 52.39775 | -0.0777 | 6.24802 |
June | 496.00000 | 24.43731 | 54.31140 | -0.0594 | 6.08900 |
July | 497.00000 | 24.56293 | 54.85957 | -0.0299 | 6.56970 |
August | 514.00000 | 24.40833 | 55.01338 | -0.0817 | 6.19735 |
September | 485.00000 | 24.43397 | 55.81243 | -0.1402 | 6.36088 |
October | 502.00000 | 24.34762 | 53.15551 | 0.60580 | 13.04844 |
November | 489.00000 | 24.02150 | 48.41927 | 0.44276 | 9.45435 |
December | 497.00000 | 23.40349 | 43.01417 | 0.21808 | 6.71929 |
Annual Sum or Average | 5943.00000 | 24.10148 | 50.36163 | 0.19960 | 8.25561 |
Minimum of Months | 454.00000 | 22.93418 | 43.01417 | -0.1402 | 6.08900 |
Maximum of Months | 514.00000 | 24.56293 | 55.81243 | 0.63115 | 13.90082 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23424 | 43.49722 | 0.18786 | 6.75923 |
February | 454.00000 | 23.75551 | 45.97531 | 0.37311 | 8.93430 |
March | 514.00000 | 24.18780 | 48.07097 | 0.55948 | 12.25378 |
April | 485.00000 | 24.41646 | 46.96302 | 0.69291 | 15.93934 |
May | 508.00000 | 24.51815 | 52.13493 | 0.01948 | 6.65773 |
June | 496.00000 | 24.42190 | 54.23601 | -0.0179 | 6.20516 |
July | 497.00000 | 24.51869 | 54.94661 | -0.0235 | 6.74822 |
August | 514.00000 | 24.33502 | 55.23957 | -0.1017 | 6.26123 |
September | 485.00000 | 24.41887 | 55.68109 | -0.1032 | 6.25644 |
October | 502.00000 | 24.41273 | 52.69889 | 0.66161 | 14.89948 |
November | 489.00000 | 24.07892 | 47.94923 | 0.49043 | 10.73833 |
December | 497.00000 | 23.42267 | 42.70384 | 0.24440 | 7.25539 |
Annual Sum or Average | 5943.00000 | 24.14598 | 50.04414 | 0.24697 | 9.06634 |
Minimum of Months | 454.00000 | 23.23424 | 42.70384 | -0.1032 | 6.20516 |
Maximum of Months | 514.00000 | 24.51869 | 55.68109 | 0.69291 | 15.93934 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67373 | 42.12490 | 0.33310 | 8.93278 |
February | 454.00000 | 24.09365 | 44.95068 | 0.49173 | 11.54297 |
March | 514.00000 | 24.32884 | 47.58046 | 0.62070 | 13.88989 |
April | 485.00000 | 24.47676 | 46.86727 | 0.69489 | 15.91499 |
May | 508.00000 | 24.49916 | 52.32974 | -0.0594 | 6.31643 |
June | 496.00000 | 24.43298 | 54.32847 | -0.0632 | 6.11477 |
July | 497.00000 | 24.56028 | 54.86348 | -0.0294 | 6.59065 |
August | 514.00000 | 24.42027 | 54.94052 | -0.0644 | 6.27109 |
September | 485.00000 | 24.49923 | 55.45057 | -0.0621 | 6.41985 |
October | 502.00000 | 24.60482 | 51.97060 | 0.76333 | 18.30801 |
November | 489.00000 | 24.48542 | 46.49288 | 0.67009 | 15.65190 |
December | 497.00000 | 24.08935 | 40.76981 | 0.45741 | 10.87548 |
Annual Sum or Average | 5943.00000 | 24.34819 | 49.42936 | 0.31052 | 10.54798 |
Minimum of Months | 454.00000 | 23.67373 | 40.76981 | -0.0644 | 6.11477 |
Maximum of Months | 514.00000 | 24.60482 | 55.45057 | 0.76333 | 18.30801 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48986 | 42.38736 | 0.27613 | 7.69362 |
February | 454.00000 | 24.18311 | 44.54458 | 0.51209 | 11.46799 |
March | 514.00000 | 24.47084 | 47.11263 | 0.69819 | 15.99480 |
April | 485.00000 | 24.63671 | 46.29469 | 0.85194 | 21.32443 |
May | 508.00000 | 24.56448 | 51.98111 | 0.08593 | 7.05427 |
June | 496.00000 | 24.53046 | 53.79463 | 0.12127 | 7.07477 |
July | 497.00000 | 24.67067 | 54.22699 | 0.14130 | 7.71654 |
August | 514.00000 | 24.56339 | 54.20207 | 0.15386 | 7.41060 |
September | 485.00000 | 24.52856 | 55.17568 | -0.0002 | 6.43769 |
October | 502.00000 | 24.60072 | 52.02239 | 0.76331 | 18.10789 |
November | 489.00000 | 24.54189 | 46.37554 | 0.66665 | 15.10336 |
December | 497.00000 | 24.35724 | 39.93034 | 0.52596 | 11.49027 |
Annual Sum or Average | 5943.00000 | 24.42926 | 49.04395 | 0.39824 | 11.38782 |
Minimum of Months | 454.00000 | 23.48986 | 39.93034 | -0.0002 | 6.43769 |
Maximum of Months | 514.00000 | 24.67067 | 55.17568 | 0.85194 | 21.32443 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.59079 | 47.52810 | -0.2432 | 7.54620 |
February | 454.00000 | 22.70052 | 48.74410 | 0.06903 | 6.64389 |
March | 514.00000 | 23.87895 | 48.95671 | 0.41328 | 9.24018 |
April | 485.00000 | 24.37091 | 47.29194 | 0.59625 | 12.95825 |
May | 508.00000 | 24.50203 | 52.48277 | -0.0828 | 6.35988 |
June | 496.00000 | 24.45102 | 54.96083 | -0.0670 | 6.18146 |
July | 497.00000 | 24.59668 | 56.13976 | -0.0391 | 6.71789 |
August | 514.00000 | 24.43657 | 56.52234 | -0.1106 | 6.35630 |
September | 485.00000 | 24.44999 | 56.85085 | -0.1497 | 6.58762 |
October | 502.00000 | 24.21939 | 53.71103 | 0.55366 | 11.79973 |
November | 489.00000 | 23.35761 | 50.14186 | 0.26132 | 7.31821 |
December | 497.00000 | 21.94204 | 46.29753 | -0.1483 | 6.75838 |
Annual Sum or Average | 5943.00000 | 23.71553 | 51.66244 | 0.08728 | 7.87438 |
Minimum of Months | 454.00000 | 21.59079 | 46.29753 | -0.2432 | 6.18146 |
Maximum of Months | 514.00000 | 24.59668 | 56.85085 | 0.59625 | 12.95825 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.07249 | 45.50905 | -0.1113 | 6.61967 |
February | 385.00000 | 23.22254 | 46.47203 | 0.21752 | 7.65522 |
March | 433.00000 | 24.16901 | 47.25474 | 0.52393 | 11.83831 |
April | 410.00000 | 24.60100 | 45.93155 | 0.71097 | 16.70428 |
May | 430.00000 | 24.64889 | 51.82612 | 0.04495 | 7.20388 |
June | 418.00000 | 24.55309 | 54.53872 | 0.01037 | 6.59257 |
July | 422.00000 | 24.71122 | 55.73198 | 0.02291 | 7.32110 |
August | 433.00000 | 24.53087 | 56.14028 | -0.0613 | 6.60390 |
September | 410.00000 | 24.55333 | 56.47724 | -0.0797 | 6.67500 |
October | 427.00000 | 24.48570 | 52.58138 | 0.65410 | 14.97496 |
November | 417.00000 | 23.76773 | 48.24121 | 0.38854 | 9.30452 |
December | 422.00000 | 22.47187 | 44.28754 | -0.0060 | 6.44714 |
Annual Sum or Average | 5034.00000 | 23.98609 | 50.44522 | 0.19219 | 8.99537 |
Minimum of Months | 385.00000 | 22.07249 | 44.28754 | -0.1113 | 6.44714 |
Maximum of Months | 433.00000 | 24.71122 | 56.47724 | 0.71097 | 16.70428 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32619 | 42.56938 | 0.23746 | 8.62757 |
February | 454.00000 | 23.86116 | 45.07888 | 0.42051 | 10.83846 |
March | 514.00000 | 24.27261 | 47.36681 | 0.58957 | 13.32461 |
April | 485.00000 | 24.49927 | 46.76580 | 0.67804 | 15.45568 |
May | 508.00000 | 24.51694 | 52.40447 | -0.0630 | 6.40991 |
June | 496.00000 | 24.44792 | 54.97410 | -0.0708 | 6.19658 |
July | 497.00000 | 24.59753 | 56.12334 | -0.0362 | 6.74429 |
August | 514.00000 | 24.45891 | 56.36211 | -0.0857 | 6.42569 |
September | 485.00000 | 24.53376 | 56.34001 | -0.0583 | 6.67511 |
October | 502.00000 | 24.62631 | 51.93948 | 0.76060 | 18.34862 |
November | 489.00000 | 24.38837 | 46.28212 | 0.63359 | 14.97196 |
December | 497.00000 | 23.76056 | 41.15922 | 0.35824 | 10.00327 |
Annual Sum or Average | 5943.00000 | 24.27643 | 49.82370 | 0.27836 | 10.31842 |
Minimum of Months | 454.00000 | 23.32619 | 41.15922 | -0.0857 | 6.19658 |
Maximum of Months | 514.00000 | 24.62631 | 56.36211 | 0.76060 | 18.34862 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18642 | 45.41381 | -0.0707 | 6.86755 |
February | 454.00000 | 23.12836 | 47.07749 | 0.21031 | 7.88348 |
March | 514.00000 | 24.10366 | 47.94573 | 0.53301 | 11.99847 |
April | 485.00000 | 24.51940 | 46.71550 | 0.72353 | 16.95976 |
May | 508.00000 | 24.56234 | 52.15069 | 0.04114 | 7.06540 |
June | 496.00000 | 24.49897 | 54.61238 | 0.04323 | 6.76571 |
July | 497.00000 | 24.62156 | 55.77140 | 0.02609 | 7.15350 |
August | 514.00000 | 24.47682 | 56.11112 | -0.0382 | 6.51159 |
September | 485.00000 | 24.50795 | 56.31411 | -0.0608 | 6.65321 |
October | 502.00000 | 24.40599 | 52.86063 | 0.65775 | 14.91226 |
November | 489.00000 | 23.74641 | 48.43175 | 0.40530 | 9.61508 |
December | 497.00000 | 22.55500 | 44.12957 | 0.02945 | 6.72525 |
Annual Sum or Average | 5943.00000 | 23.94854 | 50.66056 | 0.20765 | 9.09028 |
Minimum of Months | 454.00000 | 22.18642 | 44.12957 | -0.0707 | 6.51159 |
Maximum of Months | 514.00000 | 24.62156 | 56.31411 | 0.72353 | 16.95976 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.06230 | 48.29367 | -0.3962 | 10.48895 |
February | 454.00000 | 22.25655 | 49.99382 | -0.0437 | 7.21527 |
March | 514.00000 | 23.66840 | 49.81613 | 0.36952 | 9.04338 |
April | 485.00000 | 24.34438 | 47.73733 | 0.60522 | 13.36335 |
May | 508.00000 | 24.50480 | 52.66265 | -0.0547 | 6.52075 |
June | 496.00000 | 24.45164 | 55.10027 | -0.0397 | 6.29702 |
July | 497.00000 | 24.60323 | 56.35684 | -0.0136 | 6.93471 |
August | 514.00000 | 24.43807 | 56.78715 | -0.0915 | 6.42851 |
September | 485.00000 | 24.43968 | 57.26870 | -0.1393 | 6.65514 |
October | 502.00000 | 24.09044 | 54.69751 | 0.53106 | 11.57324 |
November | 489.00000 | 22.92053 | 51.78446 | 0.15873 | 7.10935 |
December | 497.00000 | 21.35073 | 47.64215 | -0.3092 | 8.92908 |
Annual Sum or Average | 5943.00000 | 23.52042 | 52.36635 | 0.04821 | 8.38114 |
Minimum of Months | 454.00000 | 21.06230 | 47.64215 | -0.3962 | 6.29702 |
Maximum of Months | 514.00000 | 24.60323 | 57.26870 | 0.60522 | 13.36335 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62676 | 46.59276 | -0.2325 | 8.46450 |
February | 454.00000 | 22.95407 | 47.77756 | 0.15395 | 7.65513 |
March | 514.00000 | 24.02648 | 48.41838 | 0.51233 | 11.80148 |
April | 485.00000 | 24.49840 | 47.05171 | 0.72568 | 17.12837 |
May | 508.00000 | 24.55919 | 52.28752 | 0.06955 | 7.22049 |
June | 496.00000 | 24.47217 | 54.83273 | 0.03482 | 6.62098 |
July | 497.00000 | 24.61696 | 56.09663 | 0.03457 | 7.33566 |
August | 514.00000 | 24.45338 | 56.51789 | -0.0484 | 6.53414 |
September | 485.00000 | 24.46326 | 56.87626 | -0.0737 | 6.64048 |
October | 502.00000 | 24.33076 | 53.55539 | 0.64155 | 14.69687 |
November | 489.00000 | 23.52045 | 49.55758 | 0.33685 | 8.90068 |
December | 497.00000 | 22.03071 | 45.63629 | -0.1239 | 7.30722 |
Annual Sum or Average | 5943.00000 | 23.80221 | 51.29761 | 0.16874 | 9.19347 |
Minimum of Months | 454.00000 | 21.62676 | 45.63629 | -0.2325 | 6.53414 |
Maximum of Months | 514.00000 | 24.61696 | 56.87626 | 0.72568 | 17.12837 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.79159 | 43.48175 | 0.08389 | 9.22629 |
February | 454.00000 | 23.52180 | 46.15337 | 0.32851 | 10.37484 |
March | 514.00000 | 24.13568 | 48.08240 | 0.55955 | 13.06215 |
April | 485.00000 | 24.47656 | 47.22187 | 0.68694 | 15.86513 |
May | 508.00000 | 24.51801 | 52.59508 | -0.0358 | 6.60596 |
June | 496.00000 | 24.44902 | 55.11309 | -0.0433 | 6.31405 |
July | 497.00000 | 24.60385 | 56.34438 | -0.0109 | 6.96950 |
August | 514.00000 | 24.45915 | 56.63750 | -0.0671 | 6.52956 |
September | 485.00000 | 24.52337 | 56.77014 | -0.0485 | 6.81969 |
October | 502.00000 | 24.54410 | 52.80754 | 0.74634 | 18.09079 |
November | 489.00000 | 24.15696 | 47.43867 | 0.57122 | 14.09689 |
December | 497.00000 | 23.29822 | 42.29931 | 0.22473 | 9.50877 |
Annual Sum or Average | 5943.00000 | 24.12688 | 50.45109 | 0.24812 | 10.27533 |
Minimum of Months | 454.00000 | 22.79159 | 42.29931 | -0.0671 | 6.31405 |
Maximum of Months | 514.00000 | 24.60385 | 56.77014 | 0.74634 | 18.09079 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.72608 | 46.08785 | -0.2026 | 8.70084 |
February | 454.00000 | 22.77139 | 48.15103 | 0.11952 | 7.95674 |
March | 514.00000 | 23.93087 | 48.72432 | 0.49715 | 11.73961 |
April | 485.00000 | 24.49554 | 47.17162 | 0.73109 | 17.34849 |
May | 508.00000 | 24.55944 | 52.35899 | 0.06474 | 7.39225 |
June | 496.00000 | 24.49451 | 54.78254 | 0.06670 | 7.02416 |
July | 497.00000 | 24.62357 | 56.01404 | 0.04802 | 7.43665 |
August | 514.00000 | 24.47370 | 56.39887 | -0.0230 | 6.63461 |
September | 485.00000 | 24.48733 | 56.77056 | -0.0543 | 6.82452 |
October | 502.00000 | 24.28901 | 53.80602 | 0.63755 | 14.64044 |
November | 489.00000 | 23.39993 | 49.84400 | 0.32387 | 9.08330 |
December | 497.00000 | 22.09080 | 45.22643 | -0.0980 | 7.64123 |
Annual Sum or Average | 5943.00000 | 23.78588 | 51.30629 | 0.17568 | 9.36776 |
Minimum of Months | 454.00000 | 21.72608 | 45.22643 | -0.2026 | 6.63461 |
Maximum of Months | 514.00000 | 24.62357 | 56.77056 | 0.73109 | 17.34849 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.835654E+11 | 119100.72 | 12-JAN-15:20 | 416.87 | 0.457808E+12 | 0.00 | 0.541373E+12 | 2.83 | 7.22 | 12-JAN-15:20 | 0.00 | 0.00 |
February | 0.110609E+12 | 176709.60 | 22-FEB-15:30 | 404.58 | 0.685855E+12 | 0.00 | 0.796464E+12 | 3.43 | 7.57 | 22-FEB-15:30 | 0.00 | 0.00 |
March | 0.189014E+12 | 207259.27 | 13-MAR-14:30 | 543.08 | 0.128417E+13 | 0.00 | 0.147319E+13 | 4.59 | 7.58 | 13-MAR-04:13 | 0.00 | 0.00 |
April | 0.244915E+12 | 214803.60 | 18-APR-17:00 | 666.61 | 0.168933E+13 | 0.00 | 0.193425E+13 | 5.93 | 7.57 | 14-APR-04:13 | 0.00 | 0.00 |
May | 0.307397E+12 | 223608.61 | 20-MAY-12:10 | 681.71 | 0.209922E+13 | 0.00 | 0.240662E+13 | 6.10 | 7.57 | 28-MAY-14:42 | 0.00 | 0.00 |
June | 0.335537E+12 | 240076.06 | 14-JUN-05:02 | 664.28 | 0.223438E+13 | 0.00 | 0.256992E+13 | 5.98 | 7.52 | 07-JUN-05:02 | 0.00 | 0.00 |
July | 0.368953E+12 | 247071.34 | 31-JUL-05:02 | 699.72 | 0.238619E+13 | 0.00 | 0.275515E+13 | 5.85 | 7.31 | 03-JUL-05:03 | 0.00 | 0.00 |
August | 0.356287E+12 | 252699.43 | 28-AUG-05:03 | 702.54 | 0.230034E+13 | 0.00 | 0.265663E+13 | 5.80 | 7.70 | 03-AUG-05:03 | 0.00 | 0.00 |
September | 0.294522E+12 | 234346.54 | 17-SEP-16:12 | 615.10 | 0.194973E+13 | 0.00 | 0.224425E+13 | 5.39 | 7.50 | 27-SEP-05:03 | 0.00 | 0.00 |
October | 0.216561E+12 | 210138.87 | 02-OCT-16:10 | 571.78 | 0.149308E+13 | 0.00 | 0.170965E+13 | 4.97 | 7.58 | 16-OCT-04:13 | 0.00 | 0.00 |
November | 0.163277E+12 | 207328.55 | 01-NOV-14:20 | 476.56 | 0.108961E+13 | 0.00 | 0.125289E+13 | 4.07 | 7.57 | 03-NOV-13:00 | 0.00 | 0.00 |
December | 0.101641E+12 | 131092.19 | 01-DEC-15:00 | 446.27 | 0.587197E+12 | 0.00 | 0.688838E+12 | 3.18 | 7.36 | 01-DEC-15:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277228E+13 | 6889.10 | 0.182569E+14 | 0.00 | 0.210292E+14 | 4.85 | 0.00 | 0.00 | ||||
Minimum of Months | 0.835654E+11 | 119100.72 | 404.58 | 0.457808E+12 | 0.00 | 0.541373E+12 | 2.83 | 7.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.368953E+12 | 252699.43 | 702.54 | 0.238619E+13 | 0.00 | 0.275515E+13 | 6.10 | 7.70 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.111889E+11 | 133761.35 | 13-MAR-12:10 | 26.67 | 0.793246E+11 | 0.00 | 0.905135E+11 | 0.25 | 7.35 | 13-MAR-12:10 | 0.00 | 0.00 |
April | 0.562364E+11 | 166735.42 | 30-APR-15:33 | 125.81 | 0.398095E+12 | 0.00 | 0.454331E+12 | 1.24 | 7.44 | 20-APR-05:05 | 0.00 | 0.00 |
May | 0.121891E+12 | 198670.75 | 25-MAY-05:04 | 247.29 | 0.838965E+12 | 0.00 | 0.960857E+12 | 2.28 | 7.44 | 06-MAY-17:04 | 0.00 | 0.00 |
June | 0.162598E+12 | 240076.06 | 14-JUN-05:02 | 304.40 | 0.108577E+13 | 0.00 | 0.124837E+13 | 2.82 | 7.41 | 12-JUN-05:05 | 0.00 | 0.00 |
July | 0.186749E+12 | 247071.34 | 31-JUL-05:02 | 341.74 | 0.121955E+13 | 0.00 | 0.140630E+13 | 2.99 | 7.31 | 03-JUL-05:03 | 0.00 | 0.00 |
August | 0.196774E+12 | 252699.43 | 28-AUG-05:03 | 359.06 | 0.128269E+13 | 0.00 | 0.147946E+13 | 3.13 | 7.70 | 03-AUG-05:03 | 0.00 | 0.00 |
September | 0.122660E+12 | 225119.68 | 13-SEP-03:04 | 243.85 | 0.817265E+12 | 0.00 | 0.939925E+12 | 2.24 | 7.09 | 26-SEP-08:40 | 0.00 | 0.00 |
October | 0.427959E+11 | 158781.32 | 06-OCT-04:15 | 96.92 | 0.301038E+12 | 0.00 | 0.343834E+12 | 0.91 | 7.43 | 03-OCT-04:15 | 0.00 | 0.00 |
November | 0.191966E+10 | 127371.20 | 09-NOV-14:00 | 5.50 | 0.130913E+11 | 0.00 | 0.150110E+11 | 0.05 | 7.26 | 09-NOV-13:20 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.902814E+12 | 1751.23 | 0.603579E+13 | 0.00 | 0.693860E+13 | 1.33 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.196774E+12 | 252699.43 | 359.06 | 0.128269E+13 | 0.00 | 0.147946E+13 | 3.13 | 7.70 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.660080E+11 | 744.00 | 49248.27 | 02-JAN-13:30 | 217150.55 | 12-JAN-17:00 | 22.60 | 19.08 | 14.84 |
February | 0.101260E+12 | 672.00 | 49248.27 | 01-FEB-10:20 | 381941.90 | 24-FEB-16:10 | 28.00 | 21.46 | 14.84 |
March | 0.131877E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 652509.72 | 31-MAR-24:00 | 37.00 | 27.30 | 14.84 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 725845.44 | 16-APR-17:11 | 48.70 | 35.80 | 14.84 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 383045.08 | 31-MAY-23:20 | 39.95 | 35.33 | 14.84 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:03 | 561047.14 | 30-JUN-23:42 | 45.45 | 37.62 | 14.84 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 693814.21 | 31-JUL-24:00 | 48.11 | 37.27 | 14.84 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 728198.72 | 25-AUG-14:30 | 50.25 | 36.93 | 14.84 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 378576.85 | 30-SEP-23:17 | 35.76 | 31.11 | 14.84 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 489388.15 | 31-OCT-23:40 | 35.86 | 28.71 | 14.84 |
November | 0.125600E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 554619.24 | 08-NOV-16:20 | 34.22 | 24.63 | 14.84 |
December | 0.122327E+12 | 744.00 | 49248.27 | 01-DEC-07:00 | 673876.20 | 28-DEC-16:40 | 33.50 | 21.49 | 14.84 |
Annual Sum or Average | 0.145765E+13 | 8760.00 | 38.34 | 29.77 | 14.84 | ||||
Minimum of Months | 0.660080E+11 | 672.00 | 49248.27 | 217150.55 | 22.60 | 19.08 | 14.84 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 728198.72 | 50.25 | 37.62 | 14.84 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.298410E+09 | 288.73 | 1381.03 | 13-JAN-15:00 | 995982.07 | 12-JAN-15:20 | 21.92 | 21.27 | 38.42 |
February | 0.983163E+09 | 348.68 | 4896.73 | 24-FEB-15:40 | 1530463.93 | 22-FEB-15:30 | 22.44 | 21.40 | 45.00 |
March | 0.101302E+11 | 494.77 | 22923.76 | 06-MAR-11:40 | 1704847.16 | 24-MAR-15:30 | 23.09 | 21.34 | 55.42 |
April | 0.269792E+11 | 608.08 | 22923.76 | 01-APR-09:00 | 1739483.85 | 06-APR-13:40 | 24.09 | 21.73 | 69.90 |
May | 0.510828E+11 | 681.35 | 22923.76 | 01-MAY-04:15 | 1651857.34 | 06-MAY-10:00 | 26.85 | 24.08 | 66.58 |
June | 0.545185E+11 | 664.28 | 22923.76 | 01-JUN-01:03 | 1659517.49 | 14-JUN-05:03 | 29.16 | 26.10 | 60.99 |
July | 0.577447E+11 | 699.72 | 22923.76 | 01-JUL-00:05 | 1671778.19 | 08-JUL-05:03 | 30.88 | 27.71 | 58.48 |
August | 0.579773E+11 | 702.54 | 22923.76 | 01-AUG-00:03 | 1758884.95 | 10-AUG-05:05 | 30.57 | 27.51 | 61.39 |
September | 0.506865E+11 | 615.10 | 22923.76 | 01-SEP-00:03 | 1568138.80 | 26-SEP-07:50 | 29.14 | 26.48 | 54.13 |
October | 0.271404E+11 | 543.56 | 22923.76 | 01-OCT-00:03 | 1630959.89 | 24-OCT-12:10 | 23.97 | 21.96 | 58.88 |
November | 0.484348E+10 | 438.39 | 22923.76 | 03-NOV-15:00 | 1784897.11 | 01-NOV-14:20 | 22.94 | 21.42 | 50.25 |
December | 0.485642E+09 | 337.75 | 2021.11 | 28-DEC-15:00 | 1113014.02 | 01-DEC-15:00 | 22.09 | 21.27 | 43.29 |
Annual Sum or Average | 0.342870E+12 | 6422.94 | 25.61 | 23.54 | 55.27 | ||||
Minimum of Months | 0.298410E+09 | 288.73 | 1381.03 | 995982.07 | 21.92 | 21.27 | 38.42 | ||
Maximum of Months | 0.579773E+11 | 702.54 | 22923.76 | 1784897.11 | 30.88 | 27.71 | 69.90 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 21.92 | 21.92 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 22.44 | 22.44 | 0.00 |
March | 0.180363E+10 | 22.67 | 22923.76 | 06-MAR-15:30 | 1442507.04 | 14-MAR-15:50 | 23.09 | 22.98 | 2.34 |
April | 0.885266E+10 | 114.73 | 22923.76 | 03-APR-09:30 | 1494337.38 | 19-APR-15:10 | 24.09 | 23.54 | 12.14 |
May | 0.283972E+11 | 344.24 | 22923.76 | 01-MAY-07:20 | 1474039.60 | 30-MAY-15:10 | 26.85 | 25.22 | 31.13 |
June | 0.420783E+11 | 509.88 | 22923.76 | 01-JUN-05:05 | 1659517.49 | 14-JUN-05:03 | 29.16 | 26.57 | 44.23 |
July | 0.518818E+11 | 628.68 | 22923.76 | 01-JUL-00:10 | 1671778.19 | 08-JUL-05:03 | 30.88 | 27.80 | 51.02 |
August | 0.492513E+11 | 596.80 | 22923.76 | 01-AUG-00:03 | 1758884.95 | 10-AUG-05:05 | 30.57 | 27.63 | 50.28 |
September | 0.394335E+11 | 477.83 | 22923.76 | 01-SEP-00:03 | 1470906.50 | 14-SEP-15:30 | 29.14 | 26.76 | 39.23 |
October | 0.841262E+10 | 103.05 | 22923.76 | 02-OCT-08:30 | 1461168.37 | 24-OCT-15:20 | 23.97 | 23.49 | 10.11 |
November | 0.194870E+09 | 2.67 | 22923.76 | 06-NOV-11:40 | 1468774.23 | 08-NOV-14:20 | 22.94 | 22.92 | 0.29 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 22.09 | 22.09 | 0.00 |
Annual Sum or Average | 0.230306E+12 | 2800.55 | 25.61 | 24.46 | 20.19 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 21.92 | 0.00 | ||
Maximum of Months | 0.518818E+11 | 628.68 | 22923.76 | 1758884.95 | 30.88 | 27.80 | 51.02 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.289975E+11 | 0.00 | 216.15 | 1019675.93 | 02-JAN-06:01 | 0.00 | 24.96 | 41.06 | 0.05 | 0.00 | 0.01 | 0.63 | 02-JAN-06:01 |
February | 0.490889E+10 | 0.00 | 78.07 | 882229.64 | 11-FEB-06:03 | 0.00 | 21.75 | 28.62 | 0.01 | 0.00 | 0.00 | 0.55 | 11-FEB-06:03 |
March | 10378307.71 | 0.00 | 4.65 | 1856.21 | 01-MAR-06:50 | 0.00 | 20.54 | 20.93 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.237221E+09 | 0.00 | 23.94 | 37313.25 | 27-NOV-06:03 | 0.00 | 20.64 | 22.68 | 0.00 | 0.00 | 0.00 | 0.02 | 27-NOV-06:03 |
December | 0.105569E+11 | 0.00 | 154.22 | 746886.08 | 23-DEC-06:02 | 0.00 | 22.10 | 34.24 | 0.02 | 0.00 | 0.00 | 0.46 | 23-DEC-06:02 |
Annual Sum or Average | 0.447110E+11 | 0.00 | 477.04 | 0.00 | 21.15 | 24.27 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.289975E+11 | 0.00 | 216.15 | 1019675.93 | 0.00 | 24.96 | 41.06 | 0.05 | 0.00 | 0.01 | 0.63 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 22.60 | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 28.00 | 28.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 37.00 | 37.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 48.70 | 48.70 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 39.95 | 39.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 45.45 | 45.45 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 48.11 | 48.11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 50.25 | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 35.76 | 35.76 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 35.86 | 35.86 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 34.22 | 34.22 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.50 | 33.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 | 38.34 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.472267E+11 | 0.00 | 391.32 | 0.471640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114581.97 | 02-JAN-06:02 | 90566.64 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.686908E+11 | 0.00 | 394.29 | 0.685364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162848.63 | 25-FEB-06:03 | 113949.36 | 21-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.132337E+12 | 0.00 | 526.96 | 0.130283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228804.89 | 11-MAR-06:02 | 172919.39 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.198110E+12 | 0.00 | 623.14 | 0.191193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284825.91 | 26-APR-05:02 | 204198.09 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.246116E+12 | 0.00 | 635.76 | 0.211679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 287383.55 | 22-MAY-05:02 | 222134.82 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.284024E+12 | 0.00 | 619.20 | 0.215838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 333922.72 | 14-JUN-05:02 | 216828.29 | 07-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.318965E+12 | 0.00 | 644.04 | 0.204584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342441.12 | 17-JUL-05:03 | 223626.97 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.340938E+12 | 0.00 | 659.82 | 0.215327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 338923.85 | 28-AUG-05:02 | 210820.66 | 07-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.241257E+12 | 0.00 | 561.16 | 0.158987E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314312.84 | 11-SEP-05:03 | 193918.23 | 18-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.163027E+12 | 0.00 | 532.10 | 0.146344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281243.44 | 12-OCT-04:12 | 187511.32 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.107665E+12 | 0.00 | 447.71 | 0.106280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 198365.97 | 09-NOV-05:12 | 137485.26 | 09-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.689612E+11 | 0.00 | 425.96 | 0.689612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111698.38 | 29-DEC-05:12 | 111698.38 | 29-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221732E+13 | 0.00 | 6461.45 | 0.176518E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.472267E+11 | 0.00 | 391.32 | 0.471640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111698.38 | 90566.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.340938E+12 | 0.00 | 659.82 | 0.215838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342441.12 | 223626.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.318146E+12 | 0.00 | 362.69 | 0.317968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 819663.95 | 14-JAN-06:03 | 819663.95 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.498530E+12 | 0.00 | 375.09 | 0.497502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1380325.61 | 25-FEB-06:03 | 956703.48 | 25-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.103554E+13 | 0.00 | 469.75 | 0.102043E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2120666.69 | 29-MAR-04:12 | 1714584.85 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.160523E+13 | 0.00 | 542.76 | 0.155063E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2508695.01 | 27-APR-05:02 | 1871239.98 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.231885E+13 | 0.00 | 621.58 | 0.198124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2574047.68 | 13-MAY-04:12 | 1898989.17 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.260231E+13 | 0.00 | 591.76 | 0.194533E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2696140.07 | 21-JUN-03:02 | 1972259.29 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.280961E+13 | 0.00 | 590.68 | 0.173293E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3367484.95 | 25-JUL-05:03 | 2027219.26 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.276165E+13 | 0.00 | 573.50 | 0.164733E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3243772.15 | 10-AUG-05:02 | 1859020.41 | 10-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.214980E+13 | 0.00 | 511.57 | 0.138912E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2750080.06 | 11-SEP-03:02 | 1693649.98 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.137653E+13 | 0.00 | 482.53 | 0.122808E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2596797.57 | 06-OCT-04:12 | 1780915.53 | 03-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.808469E+12 | 0.00 | 428.03 | 0.799017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1565929.79 | 09-NOV-06:03 | 1065780.66 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.410344E+12 | 0.00 | 396.42 | 0.410344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 890417.99 | 29-DEC-06:02 | 890417.99 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186950E+14 | 0.00 | 5946.36 | 0.145199E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.318146E+12 | 0.00 | 362.69 | 0.317968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 819663.95 | 819663.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.280961E+13 | 0.00 | 621.58 | 0.198124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3367484.95 | 2027219.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.268379E+11 | 0.00 | 336.06 | 0.268379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67792.39 | 12-JAN-15:30 | 67792.39 | 12-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.458764E+11 | 0.00 | 355.66 | 0.457822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111930.82 | 25-FEB-06:03 | 106148.32 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.105332E+12 | 0.00 | 458.50 | 0.103922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 205197.78 | 29-MAR-04:12 | 163415.63 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.174278E+12 | 0.00 | 537.52 | 0.168793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264531.04 | 19-APR-05:02 | 195956.19 | 20-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.254142E+12 | 0.00 | 621.11 | 0.220192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314696.72 | 22-MAY-05:02 | 222613.10 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.283420E+12 | 0.00 | 592.82 | 0.217581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 348930.61 | 26-JUN-05:02 | 224716.37 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.299312E+12 | 0.00 | 593.53 | 0.191068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 371858.15 | 03-JUL-05:02 | 236620.46 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.290858E+12 | 0.00 | 576.33 | 0.178975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 359456.19 | 10-AUG-05:02 | 209008.50 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.223382E+12 | 0.00 | 510.06 | 0.147533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 314321.55 | 14-SEP-03:02 | 189428.51 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.139219E+12 | 0.00 | 474.75 | 0.125154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256428.36 | 06-OCT-04:12 | 178253.85 | 01-OCT-15:21 | 0.00 | 0.00 | 0.00 |
November | 0.754145E+11 | 0.00 | 411.60 | 0.748530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143341.16 | 09-NOV-06:03 | 120539.27 | 09-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.332055E+11 | 0.00 | 374.85 | 0.332055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75917.33 | 01-DEC-15:00 | 75917.33 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195128E+13 | 0.00 | 5842.79 | 0.153390E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.268379E+11 | 0.00 | 336.06 | 0.268379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67792.39 | 67792.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.299312E+12 | 0.00 | 621.11 | 0.220192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 371858.15 | 236620.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.567563E+11 | 0.00 | 395.21 | 0.566693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139622.33 | 18-JAN-05:13 | 107550.07 | 23-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.591410E+11 | 0.00 | 368.58 | 0.590253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154470.65 | 25-FEB-05:12 | 119960.08 | 20-FEB-14:55 | 0.00 | 0.00 | 0.00 |
March | 0.818882E+11 | 0.00 | 433.72 | 0.815917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160265.79 | 31-MAR-04:12 | 117431.43 | 27-MAR-04:23 | 0.00 | 0.00 | 0.00 |
April | 0.943728E+11 | 0.00 | 423.07 | 0.923899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182743.33 | 27-APR-03:02 | 142880.60 | 16-APR-14:08 | 0.00 | 0.00 | 0.00 |
May | 0.119548E+12 | 0.00 | 461.31 | 0.107409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221779.55 | 22-MAY-03:03 | 142298.53 | 07-MAY-18:57 | 0.00 | 0.00 | 0.00 |
June | 0.139764E+12 | 0.00 | 462.22 | 0.111853E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240990.09 | 26-JUN-03:15 | 142138.07 | 04-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.160186E+12 | 0.00 | 478.40 | 0.110771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 252924.92 | 23-JUL-23:08 | 130775.98 | 04-JUL-19:37 | 0.00 | 0.00 | 0.00 |
August | 0.178808E+12 | 0.00 | 508.40 | 0.119605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261796.70 | 27-AUG-11:28 | 116517.20 | 06-AUG-13:28 | 0.00 | 0.00 | 0.00 |
September | 0.140860E+12 | 0.00 | 468.65 | 0.102199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247047.32 | 10-SEP-16:38 | 116982.13 | 24-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.104954E+12 | 0.00 | 471.84 | 0.982369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185895.85 | 04-OCT-03:02 | 133995.14 | 01-OCT-15:40 | 0.00 | 0.00 | 0.00 |
November | 0.819923E+11 | 0.00 | 429.75 | 0.816253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164453.65 | 09-NOV-05:12 | 130633.53 | 05-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 0.655413E+11 | 0.00 | 405.80 | 0.654821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133787.70 | 30-DEC-05:12 | 111269.28 | 29-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128381E+13 | 0.00 | 5306.95 | 0.108686E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.567563E+11 | 0.00 | 368.58 | 0.566693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133787.70 | 107550.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178808E+12 | 0.00 | 508.40 | 0.119605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261796.70 | 142880.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.338440E+12 | 0.877380E+11 | 744.00 | 0.324819E+12 | 0.136213E+11 | 0.00 | 0.36 | 12-JAN-16:00 | 0.32 | 22-JAN-06:00 | 132564.26 | 17-JAN-17:00 | 128192.77 | 12-JAN-15:00 | 6940.41 | 17-JAN-17:00 | 41551.86 | 12-JAN-15:00 | 0.00 |
February | 0.534272E+12 | 0.142331E+12 | 672.00 | 0.517423E+12 | 0.168484E+11 | 0.00 | 0.60 | 22-FEB-15:00 | 0.53 | 01-FEB-00:10 | 226618.31 | 24-FEB-17:00 | 221122.52 | 22-FEB-15:00 | 10350.30 | 27-FEB-09:40 | 78210.09 | 22-FEB-15:00 | 0.00 |
March | 0.837819E+12 | 0.255799E+12 | 744.00 | 0.823909E+12 | 0.139106E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.74 | 01-MAR-02:20 | 396620.16 | 31-MAR-24:00 | 394321.94 | 31-MAR-23:53 | 13892.45 | 05-MAR-06:00 | 137478.27 | 28-MAR-15:40 | 0.00 |
April | 0.103660E+13 | 0.372040E+12 | 720.00 | 0.103040E+13 | 0.620239E+10 | 0.00 | 1.00 | 01-APR-08:20 | 0.42 | 30-APR-24:00 | 410381.59 | 25-APR-04:53 | 404350.31 | 30-APR-04:27 | 8792.68 | 26-APR-21:00 | 174810.32 | 15-APR-15:00 | 0.00 |
May | 0.364838E+12 | 0.149824E+12 | 744.00 | 0.347927E+12 | 0.169107E+11 | 0.00 | 0.60 | 31-MAY-23:05 | 0.35 | 28-MAY-05:00 | 226879.34 | 31-MAY-23:05 | 213556.76 | 31-MAY-23:53 | 15377.73 | 22-MAY-23:00 | 79636.89 | 31-MAY-23:20 | 0.00 |
June | 0.600904E+12 | 0.247194E+12 | 720.00 | 0.575116E+12 | 0.257875E+11 | 0.00 | 0.85 | 30-JUN-23:53 | 0.58 | 18-JUN-05:00 | 319434.70 | 30-JUN-23:03 | 307906.16 | 30-JUN-23:53 | 18602.69 | 28-JUN-13:30 | 128334.26 | 30-JUN-23:35 | 0.00 |
July | 0.876224E+12 | 0.341473E+12 | 744.00 | 0.839584E+12 | 0.366403E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.80 | 19-JUL-03:00 | 402843.02 | 31-JUL-24:00 | 390956.17 | 31-JUL-24:00 | 19584.03 | 18-JUL-08:30 | 158723.08 | 07-JUL-15:00 | 0.00 |
August | 0.110196E+13 | 0.394249E+12 | 744.00 | 0.106643E+13 | 0.355306E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-24:00 | 422728.18 | 10-AUG-14:00 | 405609.62 | 15-AUG-23:57 | 20777.81 | 25-AUG-16:00 | 167483.12 | 07-AUG-15:00 | 0.00 |
September | 0.368369E+12 | 0.133192E+12 | 720.00 | 0.337081E+12 | 0.312885E+11 | 0.00 | 0.59 | 30-SEP-23:03 | 0.36 | 27-SEP-05:00 | 228325.83 | 30-SEP-23:03 | 214119.77 | 30-SEP-23:57 | 18132.42 | 12-SEP-16:00 | 76553.08 | 30-SEP-23:13 | 0.00 |
October | 0.603967E+12 | 0.199003E+12 | 744.00 | 0.587531E+12 | 0.164358E+11 | 0.00 | 0.76 | 31-OCT-23:30 | 0.55 | 29-OCT-05:00 | 311299.01 | 31-OCT-24:00 | 302968.78 | 31-OCT-24:00 | 11528.35 | 13-OCT-08:30 | 102591.59 | 02-OCT-15:00 | 0.00 |
November | 0.819233E+12 | 0.230997E+12 | 720.00 | 0.799831E+12 | 0.194023E+11 | 0.00 | 0.84 | 08-NOV-15:00 | 0.75 | 26-NOV-06:00 | 322206.10 | 24-NOV-08:15 | 315574.80 | 08-NOV-15:00 | 14609.43 | 23-NOV-07:55 | 119516.09 | 08-NOV-15:00 | 0.00 |
December | 0.110011E+13 | 0.271056E+12 | 744.00 | 0.106569E+13 | 0.344141E+11 | 0.00 | 1.00 | 27-DEC-14:30 | 0.93 | 01-DEC-00:10 | 422151.60 | 22-DEC-06:03 | 404968.29 | 28-DEC-17:00 | 25588.04 | 22-DEC-06:03 | 131230.97 | 28-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.858273E+13 | 0.282490E+13 | 8760.00 | 0.831574E+13 | 0.266992E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338440E+12 | 0.877380E+11 | 672.00 | 0.324819E+12 | 0.620239E+10 | 0.00 | 0.36 | 0.32 | 132564.26 | 128192.77 | 6940.41 | 41551.86 | 0.00 | ||||||
Maximum of Months | 0.110196E+13 | 0.394249E+12 | 744.00 | 0.106643E+13 | 0.366403E+11 | 0.00 | 1.00 | 0.93 | 422728.18 | 405609.62 | 25588.04 | 174810.32 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.480355E+10 | 0.126454E+10 | 744.00 | 0.464604E+10 | 0.157510E+09 | 0.00 | 0.31 | 12-JAN-17:00 | 0.15 | 03-JAN-07:00 | 2594.05 | 12-JAN-17:00 | 2455.13 | 12-JAN-17:00 | 260.78 | 17-JAN-17:00 | 774.65 | 12-JAN-16:00 | 0.00 |
February | 0.960852E+10 | 0.255985E+10 | 672.00 | 0.936734E+10 | 0.241180E+09 | 0.00 | 0.55 | 21-FEB-17:00 | 0.37 | 11-FEB-08:00 | 4677.30 | 21-FEB-17:00 | 4519.06 | 21-FEB-17:00 | 273.03 | 15-FEB-17:00 | 1550.23 | 22-FEB-15:00 | 0.00 |
March | 0.164126E+11 | 0.495430E+10 | 744.00 | 0.160633E+11 | 0.349255E+09 | 0.00 | 0.88 | 31-MAR-24:00 | 0.61 | 01-MAR-07:00 | 7841.60 | 31-MAR-24:00 | 7737.47 | 31-MAR-23:50 | 343.26 | 10-MAR-17:10 | 2839.79 | 28-MAR-16:00 | 0.00 |
April | 0.213523E+11 | 0.772003E+10 | 720.00 | 0.210274E+11 | 0.324882E+09 | 0.00 | 1.00 | 01-APR-17:01 | 0.39 | 30-APR-24:00 | 8815.66 | 16-APR-20:53 | 8555.39 | 16-APR-20:53 | 388.72 | 26-APR-08:00 | 3773.42 | 15-APR-15:00 | 0.00 |
May | 0.750106E+10 | 0.298414E+10 | 744.00 | 0.681688E+10 | 0.684182E+09 | 0.00 | 0.54 | 31-MAY-23:05 | 0.28 | 13-MAY-07:00 | 4677.16 | 31-MAY-23:05 | 4109.81 | 31-MAY-23:50 | 650.76 | 22-MAY-22:55 | 1724.03 | 01-MAY-16:00 | 0.00 |
June | 0.126159E+11 | 0.501280E+10 | 720.00 | 0.115140E+11 | 0.110184E+10 | 0.00 | 0.79 | 30-JUN-23:12 | 0.52 | 18-JUN-03:25 | 6649.22 | 30-JUN-23:03 | 6157.43 | 30-JUN-23:55 | 821.76 | 28-JUN-13:40 | 2690.38 | 08-JUN-16:00 | 0.00 |
July | 0.184611E+11 | 0.695154E+10 | 744.00 | 0.168323E+11 | 0.162882E+10 | 0.00 | 0.97 | 31-JUL-23:03 | 0.73 | 19-JUL-02:30 | 8725.89 | 31-JUL-23:03 | 7954.05 | 31-JUL-23:55 | 854.76 | 18-JUL-08:20 | 3408.07 | 02-JUL-16:50 | 0.00 |
August | 0.234810E+11 | 0.844187E+10 | 744.00 | 0.217565E+11 | 0.172454E+10 | 0.00 | 1.00 | 01-AUG-09:10 | 0.39 | 31-AUG-23:13 | 9129.87 | 10-AUG-15:00 | 8374.75 | 10-AUG-16:00 | 874.94 | 21-AUG-14:00 | 3620.85 | 07-AUG-15:00 | 0.00 |
September | 0.754858E+10 | 0.261063E+10 | 720.00 | 0.625710E+10 | 0.129148E+10 | 0.00 | 0.54 | 30-SEP-23:05 | 0.29 | 27-SEP-06:00 | 4695.92 | 30-SEP-23:03 | 4075.09 | 30-SEP-23:57 | 743.52 | 12-SEP-16:00 | 1508.11 | 30-SEP-23:13 | 0.00 |
October | 0.119305E+11 | 0.384951E+10 | 744.00 | 0.112921E+11 | 0.638388E+09 | 0.00 | 0.66 | 31-OCT-23:20 | 0.45 | 28-OCT-07:00 | 6019.39 | 31-OCT-23:10 | 5802.77 | 31-OCT-24:00 | 502.23 | 06-OCT-09:50 | 2139.85 | 02-OCT-15:20 | 0.00 |
November | 0.157137E+11 | 0.440467E+10 | 720.00 | 0.153857E+11 | 0.327980E+09 | 0.00 | 0.79 | 08-NOV-16:20 | 0.60 | 25-NOV-08:00 | 6753.21 | 08-NOV-16:50 | 6497.24 | 08-NOV-16:30 | 291.35 | 08-NOV-20:00 | 2412.29 | 08-NOV-15:00 | 0.00 |
December | 0.205383E+11 | 0.509511E+10 | 744.00 | 0.203534E+11 | 0.184904E+09 | 0.00 | 0.93 | 28-DEC-16:50 | 0.76 | 23-DEC-08:00 | 8405.12 | 28-DEC-17:00 | 8237.48 | 28-DEC-17:00 | 259.52 | 29-DEC-17:10 | 2629.94 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.169967E+12 | 0.558490E+11 | 8760.00 | 0.161312E+12 | 0.865496E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.480355E+10 | 0.126454E+10 | 672.00 | 0.464604E+10 | 0.157510E+09 | 0.00 | 0.31 | 0.15 | 2594.05 | 2455.13 | 259.52 | 774.65 | 0.00 | ||||||
Maximum of Months | 0.234810E+11 | 0.844187E+10 | 744.00 | 0.217565E+11 | 0.172454E+10 | 0.00 | 1.00 | 0.76 | 9129.87 | 8555.39 | 874.94 | 3773.42 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.320925E+11 | 0.866364E+10 | 725.00 | 0.308022E+11 | 0.129039E+10 | 0.00 | 0.31 | 12-JAN-17:00 | 0.00 | 01-JAN-00:40 | 23850.10 | 13-JAN-17:00 | 22545.32 | 12-JAN-17:00 | 2437.94 | 17-JAN-16:50 | 7091.51 | 12-JAN-16:50 | 0.00 |
February | 0.840515E+11 | 0.225268E+11 | 672.00 | 0.818280E+11 | 0.222347E+10 | 0.00 | 0.56 | 22-FEB-17:00 | 0.32 | 11-FEB-05:55 | 43922.37 | 22-FEB-17:00 | 42381.10 | 22-FEB-17:00 | 2632.37 | 15-FEB-17:00 | 14520.66 | 22-FEB-15:00 | 0.00 |
March | 0.154396E+12 | 0.464691E+11 | 744.00 | 0.151104E+12 | 0.329257E+10 | 0.00 | 0.91 | 31-MAR-24:00 | 0.59 | 01-MAR-07:00 | 75726.05 | 31-MAR-24:00 | 74722.03 | 31-MAR-23:53 | 3343.20 | 10-MAR-17:10 | 26891.41 | 28-MAR-16:00 | 0.00 |
April | 0.201164E+12 | 0.723220E+11 | 720.00 | 0.198084E+12 | 0.308051E+10 | 0.00 | 1.00 | 01-APR-15:30 | 0.34 | 30-APR-24:00 | 82575.14 | 12-APR-16:00 | 80366.38 | 12-APR-16:00 | 3816.56 | 26-APR-08:00 | 35152.70 | 15-APR-15:00 | 0.00 |
May | 0.708705E+11 | 0.280751E+11 | 744.00 | 0.642697E+11 | 0.660080E+10 | 0.00 | 0.56 | 31-MAY-23:05 | 0.28 | 13-MAY-07:00 | 45448.22 | 31-MAY-23:05 | 39878.67 | 31-MAY-23:53 | 6324.93 | 22-MAY-23:23 | 15853.43 | 01-MAY-16:00 | 0.00 |
June | 0.120174E+12 | 0.474557E+11 | 720.00 | 0.109391E+12 | 0.107829E+11 | 0.00 | 0.81 | 30-JUN-23:12 | 0.53 | 02-JUN-06:00 | 64074.66 | 30-JUN-23:03 | 59112.82 | 30-JUN-23:42 | 8111.91 | 28-JUN-13:40 | 25510.36 | 08-JUN-16:00 | 0.00 |
July | 0.175771E+12 | 0.657331E+11 | 744.00 | 0.159717E+12 | 0.160544E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 19-JUL-03:00 | 84021.83 | 31-JUL-23:03 | 76172.20 | 31-JUL-23:55 | 8432.95 | 18-JUL-08:20 | 31878.76 | 02-JUL-16:50 | 0.00 |
August | 0.220490E+12 | 0.787911E+11 | 744.00 | 0.203489E+12 | 0.170004E+11 | 0.00 | 1.00 | 01-AUG-07:50 | 0.34 | 31-AUG-23:13 | 85694.28 | 10-AUG-14:10 | 78082.64 | 10-AUG-16:00 | 8617.60 | 21-AUG-14:00 | 33734.87 | 07-AUG-15:00 | 0.00 |
September | 0.708500E+11 | 0.243837E+11 | 720.00 | 0.582543E+11 | 0.125957E+11 | 0.00 | 0.55 | 30-SEP-23:03 | 0.29 | 08-SEP-21:13 | 45175.31 | 30-SEP-23:03 | 38954.24 | 30-SEP-23:27 | 7304.50 | 12-SEP-16:00 | 14411.94 | 30-SEP-23:13 | 0.00 |
October | 0.112063E+12 | 0.360357E+11 | 744.00 | 0.105914E+12 | 0.614832E+10 | 0.00 | 0.67 | 31-OCT-23:20 | 0.44 | 31-OCT-06:00 | 56952.08 | 31-OCT-23:10 | 54767.05 | 31-OCT-24:00 | 4936.52 | 06-OCT-09:40 | 20175.56 | 02-OCT-15:30 | 0.00 |
November | 0.144745E+12 | 0.405812E+11 | 720.00 | 0.141662E+12 | 0.308320E+10 | 0.00 | 0.80 | 08-NOV-16:30 | 0.57 | 25-NOV-08:00 | 64021.56 | 08-NOV-16:50 | 61499.91 | 08-NOV-16:30 | 2800.88 | 08-NOV-20:00 | 22660.85 | 08-NOV-15:00 | 0.00 |
December | 0.184455E+12 | 0.459422E+11 | 744.00 | 0.182766E+12 | 0.168941E+10 | 0.00 | 0.93 | 28-DEC-17:00 | 0.70 | 24-DEC-06:00 | 79026.33 | 28-DEC-17:00 | 77430.86 | 28-DEC-17:00 | 2511.65 | 29-DEC-17:10 | 24607.42 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.157112E+13 | 0.516979E+12 | 8741.00 | 0.148728E+13 | 0.838421E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.320925E+11 | 0.866364E+10 | 672.00 | 0.308022E+11 | 0.129039E+10 | 0.00 | 0.31 | 0.00 | 23850.10 | 22545.32 | 2437.94 | 7091.51 | 0.00 | ||||||
Maximum of Months | 0.220490E+12 | 0.787911E+11 | 744.00 | 0.203489E+12 | 0.170004E+11 | 0.00 | 1.00 | 0.74 | 85694.28 | 80366.38 | 8617.60 | 35152.70 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.215532E+10 | 0.601248E+09 | 612.85 | 0.203872E+10 | 0.116599E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2420.34 | 12-JAN-17:00 | 2282.90 | 12-JAN-17:00 | 261.45 | 17-JAN-15:30 | 724.78 | 12-JAN-16:40 | 0.00 |
February | 0.779849E+10 | 0.212521E+10 | 672.00 | 0.756393E+10 | 0.234560E+09 | 0.00 | 0.55 | 22-FEB-17:00 | 0.22 | 11-FEB-05:55 | 4456.91 | 22-FEB-17:00 | 4294.97 | 22-FEB-17:00 | 270.86 | 15-FEB-17:00 | 1480.13 | 22-FEB-15:00 | 0.00 |
March | 0.152766E+11 | 0.464611E+10 | 744.00 | 0.149294E+11 | 0.347190E+09 | 0.00 | 0.88 | 31-MAR-24:00 | 0.53 | 01-MAR-07:00 | 7540.33 | 31-MAR-24:00 | 7433.10 | 31-MAR-23:53 | 341.74 | 10-MAR-17:10 | 2765.20 | 28-MAR-16:00 | 0.00 |
April | 0.202815E+11 | 0.735854E+10 | 720.00 | 0.199567E+11 | 0.324830E+09 | 0.00 | 1.00 | 01-APR-17:00 | 0.34 | 30-APR-24:00 | 8489.67 | 16-APR-20:35 | 8211.42 | 16-APR-20:35 | 388.60 | 26-APR-08:00 | 3644.05 | 15-APR-15:00 | 0.00 |
May | 0.730070E+10 | 0.290849E+10 | 744.00 | 0.662108E+10 | 0.679615E+09 | 0.00 | 0.54 | 31-MAY-23:05 | 0.26 | 13-MAY-07:00 | 4514.66 | 31-MAY-23:05 | 3948.53 | 31-MAY-23:53 | 634.76 | 22-MAY-23:23 | 1736.38 | 28-MAY-16:31 | 0.00 |
June | 0.122225E+11 | 0.485735E+10 | 720.00 | 0.111251E+11 | 0.109744E+10 | 0.00 | 0.79 | 30-JUN-23:12 | 0.51 | 24-JUN-13:50 | 6476.22 | 30-JUN-23:03 | 5974.44 | 30-JUN-23:42 | 822.52 | 28-JUN-13:40 | 2686.58 | 11-JUN-16:35 | 0.00 |
July | 0.177918E+11 | 0.669867E+10 | 744.00 | 0.161671E+11 | 0.162471E+10 | 0.00 | 0.97 | 31-JUL-23:03 | 0.72 | 19-JUL-03:00 | 8429.64 | 31-JUL-23:03 | 7647.05 | 31-JUL-23:55 | 850.14 | 18-JUL-08:20 | 3394.08 | 02-JUL-16:50 | 0.00 |
August | 0.223391E+11 | 0.806129E+10 | 744.00 | 0.206139E+11 | 0.172514E+10 | 0.00 | 1.00 | 01-AUG-09:50 | 0.33 | 31-AUG-23:13 | 8755.14 | 10-AUG-14:00 | 7979.87 | 20-AUG-15:45 | 874.35 | 21-AUG-14:00 | 3496.15 | 07-AUG-15:00 | 0.00 |
September | 0.716961E+10 | 0.248227E+10 | 720.00 | 0.589168E+10 | 0.127793E+10 | 0.00 | 0.54 | 30-SEP-23:03 | 0.27 | 09-SEP-17:13 | 4543.36 | 30-SEP-23:03 | 3912.09 | 30-SEP-23:17 | 737.14 | 12-SEP-16:00 | 1457.62 | 30-SEP-23:13 | 0.00 |
October | 0.111269E+11 | 0.361196E+10 | 744.00 | 0.104950E+11 | 0.631886E+09 | 0.00 | 0.64 | 01-OCT-16:52 | 0.39 | 28-OCT-07:00 | 5592.72 | 31-OCT-23:10 | 5347.44 | 31-OCT-23:50 | 502.14 | 06-OCT-09:50 | 2083.52 | 02-OCT-15:20 | 0.00 |
November | 0.139858E+11 | 0.397609E+10 | 720.00 | 0.136611E+11 | 0.324787E+09 | 0.00 | 0.78 | 08-NOV-16:20 | 0.47 | 26-NOV-07:40 | 6469.18 | 08-NOV-16:40 | 6214.65 | 08-NOV-16:30 | 287.01 | 08-NOV-20:00 | 2306.26 | 08-NOV-15:00 | 0.00 |
December | 0.173841E+11 | 0.440201E+10 | 744.00 | 0.172004E+11 | 0.183784E+09 | 0.00 | 0.91 | 28-DEC-16:50 | 0.57 | 31-DEC-08:00 | 7939.28 | 28-DEC-17:00 | 7772.47 | 28-DEC-17:00 | 257.54 | 29-DEC-17:10 | 2488.56 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.154833E+12 | 0.517293E+11 | 8628.85 | 0.146264E+12 | 0.856848E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.215532E+10 | 0.601248E+09 | 612.85 | 0.203872E+10 | 0.116599E+09 | 0.00 | 0.30 | 0.00 | 2420.34 | 2282.90 | 257.54 | 724.78 | 0.00 | ||||||
Maximum of Months | 0.223391E+11 | 0.806129E+10 | 744.00 | 0.206139E+11 | 0.172514E+10 | 0.00 | 1.00 | 0.72 | 8755.14 | 8211.42 | 874.35 | 3644.05 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.53 | 0.00 | 121.53 | 61.82 | 505.60 | 0.00 | 0.00 | 0.00 |
February | 144.12 | 0.00 | 144.12 | 130.10 | 391.73 | 0.00 | 0.00 | 0.00 |
March | 173.66 | 0.00 | 173.66 | 259.96 | 230.07 | 0.00 | 0.00 | 0.00 |
April | 188.44 | 0.64 | 187.80 | 457.15 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 208.78 | 5.86 | 202.92 | 645.07 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 216.12 | 8.01 | 208.11 | 699.73 | 9.83 | 0.00 | 0.00 | 0.00 |
July | 213.14 | 3.38 | 209.77 | 617.84 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 195.67 | 0.61 | 195.06 | 514.91 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 174.35 | 0.01 | 174.33 | 405.73 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 151.04 | 0.00 | 151.04 | 292.28 | 176.21 | 0.00 | 0.00 | 0.00 |
November | 127.93 | 0.00 | 127.93 | 152.54 | 350.47 | 0.00 | 0.00 | 0.00 |
December | 118.56 | 0.00 | 118.56 | 66.85 | 500.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.57 | 1.55 | 168.03 | 359.78 | 190.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.56 | 0.00 | 118.56 | 61.82 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.12 | 8.01 | 209.77 | 699.73 | 505.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.53 | 0.00 | 121.53 | 61.82 | 505.60 | 0.00 | 0.00 | 0.00 |
February | 144.12 | 0.00 | 144.12 | 130.10 | 391.73 | 0.00 | 0.00 | 0.00 |
March | 173.66 | 0.00 | 173.66 | 259.96 | 230.07 | 0.00 | 0.00 | 0.00 |
April | 188.44 | 0.64 | 187.80 | 457.15 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 208.78 | 5.86 | 202.92 | 645.07 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 216.12 | 8.01 | 208.11 | 699.73 | 9.83 | 0.00 | 0.00 | 0.00 |
July | 213.14 | 3.38 | 209.77 | 617.84 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 195.67 | 0.61 | 195.06 | 514.91 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 174.35 | 0.01 | 174.33 | 405.73 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 151.04 | 0.00 | 151.04 | 292.28 | 176.21 | 0.00 | 0.00 | 0.00 |
November | 127.93 | 0.00 | 127.93 | 152.54 | 350.47 | 0.00 | 0.00 | 0.00 |
December | 118.56 | 0.00 | 118.56 | 66.85 | 500.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.57 | 1.55 | 168.03 | 359.78 | 190.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.56 | 0.00 | 118.56 | 61.82 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.12 | 8.01 | 209.77 | 699.73 | 505.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.53 | 0.00 | 121.53 | 61.82 | 505.60 | 0.00 | 0.00 | 0.00 |
February | 144.12 | 0.00 | 144.12 | 130.10 | 391.73 | 0.00 | 0.00 | 0.00 |
March | 173.66 | 0.00 | 173.66 | 259.96 | 230.07 | 0.00 | 0.00 | 0.00 |
April | 188.44 | 0.64 | 187.80 | 457.15 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 208.78 | 5.86 | 202.92 | 645.07 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 216.12 | 8.01 | 208.11 | 699.73 | 9.83 | 0.00 | 0.00 | 0.00 |
July | 213.14 | 3.38 | 209.77 | 617.84 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 195.67 | 0.61 | 195.06 | 514.91 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 174.35 | 0.01 | 174.33 | 405.73 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 151.04 | 0.00 | 151.04 | 292.28 | 176.21 | 0.00 | 0.00 | 0.00 |
November | 127.93 | 0.00 | 127.93 | 152.54 | 350.47 | 0.00 | 0.00 | 0.00 |
December | 118.56 | 0.00 | 118.56 | 66.85 | 500.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.57 | 1.55 | 168.03 | 359.78 | 190.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.56 | 0.00 | 118.56 | 61.82 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.12 | 8.01 | 209.77 | 699.73 | 505.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.53 | 0.00 | 121.53 | 61.82 | 505.60 | 0.00 | 0.00 | 0.00 |
February | 144.12 | 0.00 | 144.12 | 130.10 | 391.73 | 0.00 | 0.00 | 0.00 |
March | 173.66 | 0.00 | 173.66 | 259.96 | 230.07 | 0.00 | 0.00 | 0.00 |
April | 188.44 | 0.64 | 187.80 | 457.15 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 208.78 | 5.86 | 202.92 | 645.07 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 216.12 | 8.01 | 208.11 | 699.73 | 9.83 | 0.00 | 0.00 | 0.00 |
July | 213.14 | 3.38 | 209.77 | 617.84 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 195.67 | 0.61 | 195.06 | 514.91 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 174.35 | 0.01 | 174.33 | 405.73 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 151.04 | 0.00 | 151.04 | 292.28 | 176.21 | 0.00 | 0.00 | 0.00 |
November | 127.93 | 0.00 | 127.93 | 152.54 | 350.47 | 0.00 | 0.00 | 0.00 |
December | 118.56 | 0.00 | 118.56 | 66.85 | 500.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.57 | 1.55 | 168.03 | 359.78 | 190.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.56 | 0.00 | 118.56 | 61.82 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.12 | 8.01 | 209.77 | 699.73 | 505.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.53 | 0.00 | 121.53 | 61.81 | 505.58 | 0.00 | 0.00 | 0.00 |
February | 144.11 | 0.00 | 144.11 | 130.09 | 391.71 | 0.00 | 0.00 | 0.00 |
March | 173.66 | 0.00 | 173.66 | 259.95 | 230.06 | 0.00 | 0.00 | 0.00 |
April | 188.43 | 0.64 | 187.79 | 457.13 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 208.77 | 5.86 | 202.91 | 645.05 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 216.11 | 8.00 | 208.10 | 699.70 | 9.83 | 0.00 | 0.00 | 0.00 |
July | 213.13 | 3.38 | 209.76 | 617.82 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 195.66 | 0.61 | 195.05 | 514.88 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 174.34 | 0.01 | 174.33 | 405.71 | 32.05 | 0.00 | 0.00 | 0.00 |
October | 151.03 | 0.00 | 151.03 | 292.27 | 176.20 | 0.00 | 0.00 | 0.00 |
November | 127.93 | 0.00 | 127.93 | 152.54 | 350.45 | 0.00 | 0.00 | 0.00 |
December | 118.55 | 0.00 | 118.55 | 66.85 | 500.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.57 | 1.55 | 168.02 | 359.76 | 190.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 118.55 | 0.00 | 118.55 | 61.81 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 216.11 | 8.00 | 209.76 | 699.70 | 505.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 289.27 | 116.11 | 173.16 | 281.23 | 510.40 | 0.00 | 0.00 | 0.00 |
February | 351.43 | 145.09 | 206.34 | 442.87 | 399.77 | 0.00 | 0.00 | 0.00 |
March | 428.71 | 176.96 | 251.75 | 690.37 | 237.39 | 0.00 | 0.00 | 0.00 |
April | 510.05 | 237.81 | 272.24 | 1042.21 | 81.01 | 0.00 | 0.00 | 0.00 |
May | 502.03 | 222.57 | 279.46 | 1191.15 | 13.69 | 0.00 | 0.00 | 0.00 |
June | 408.59 | 135.57 | 273.02 | 1081.87 | 9.59 | 0.00 | 0.00 | 0.00 |
July | 343.41 | 72.52 | 270.89 | 888.28 | 1.48 | 0.00 | 0.00 | 0.00 |
August | 309.42 | 53.85 | 255.58 | 751.40 | 6.01 | 0.00 | 0.00 | 0.00 |
September | 330.58 | 92.19 | 238.39 | 694.97 | 32.83 | 0.00 | 0.00 | 0.00 |
October | 361.62 | 146.07 | 215.55 | 666.61 | 187.51 | 0.00 | 0.00 | 0.00 |
November | 320.63 | 137.63 | 183.00 | 465.68 | 359.24 | 0.00 | 0.00 | 0.00 |
December | 279.58 | 110.77 | 168.81 | 296.53 | 502.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 369.51 | 137.05 | 232.46 | 708.70 | 194.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.58 | 53.85 | 168.81 | 281.23 | 1.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.05 | 237.81 | 279.46 | 1191.15 | 510.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 289.27 | 116.11 | 173.16 | 281.23 | 510.40 | 0.00 | 0.00 | 0.00 |
February | 351.43 | 145.09 | 206.34 | 442.87 | 399.77 | 0.00 | 0.00 | 0.00 |
March | 428.71 | 176.96 | 251.75 | 690.37 | 237.39 | 0.00 | 0.00 | 0.00 |
April | 510.05 | 237.81 | 272.24 | 1042.21 | 81.01 | 0.00 | 0.00 | 0.00 |
May | 502.03 | 222.57 | 279.46 | 1191.15 | 13.69 | 0.00 | 0.00 | 0.00 |
June | 408.59 | 135.57 | 273.02 | 1081.87 | 9.59 | 0.00 | 0.00 | 0.00 |
July | 343.41 | 72.52 | 270.89 | 888.28 | 1.48 | 0.00 | 0.00 | 0.00 |
August | 309.42 | 53.85 | 255.58 | 751.40 | 6.01 | 0.00 | 0.00 | 0.00 |
September | 330.58 | 92.19 | 238.39 | 694.97 | 32.83 | 0.00 | 0.00 | 0.00 |
October | 361.62 | 146.07 | 215.55 | 666.61 | 187.51 | 0.00 | 0.00 | 0.00 |
November | 320.63 | 137.63 | 183.00 | 465.68 | 359.24 | 0.00 | 0.00 | 0.00 |
December | 279.58 | 110.77 | 168.81 | 296.53 | 502.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 369.51 | 137.05 | 232.46 | 708.70 | 194.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.58 | 53.85 | 168.81 | 281.23 | 1.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.05 | 237.81 | 279.46 | 1191.15 | 510.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 289.27 | 116.11 | 173.16 | 281.23 | 510.39 | 0.00 | 0.00 | 0.00 |
February | 351.42 | 145.08 | 206.34 | 442.86 | 399.76 | 0.00 | 0.00 | 0.00 |
March | 428.70 | 176.95 | 251.75 | 690.36 | 237.39 | 0.00 | 0.00 | 0.00 |
April | 510.04 | 237.81 | 272.23 | 1042.19 | 81.01 | 0.00 | 0.00 | 0.00 |
May | 502.02 | 222.57 | 279.45 | 1191.13 | 13.69 | 0.00 | 0.00 | 0.00 |
June | 408.58 | 135.57 | 273.01 | 1081.85 | 9.59 | 0.00 | 0.00 | 0.00 |
July | 343.40 | 72.52 | 270.88 | 888.26 | 1.48 | 0.00 | 0.00 | 0.00 |
August | 309.42 | 53.85 | 255.57 | 751.39 | 6.01 | 0.00 | 0.00 | 0.00 |
September | 330.58 | 92.19 | 238.39 | 694.96 | 32.83 | 0.00 | 0.00 | 0.00 |
October | 361.61 | 146.07 | 215.55 | 666.60 | 187.50 | 0.00 | 0.00 | 0.00 |
November | 320.62 | 137.63 | 183.00 | 465.67 | 359.23 | 0.00 | 0.00 | 0.00 |
December | 279.57 | 110.77 | 168.80 | 296.53 | 502.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 369.50 | 137.05 | 232.46 | 708.69 | 194.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.57 | 53.85 | 168.80 | 281.23 | 1.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.04 | 237.81 | 279.45 | 1191.13 | 510.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.73 | 335.86 | 216.88 | 746.08 | 469.32 | 6.50 | 0.00 | 0.00 |
February | 525.57 | 291.92 | 233.65 | 774.93 | 383.91 | 0.00 | 0.00 | 0.00 |
March | 449.37 | 198.49 | 250.89 | 780.39 | 238.78 | 0.00 | 0.00 | 0.00 |
April | 315.64 | 89.08 | 226.56 | 735.12 | 86.36 | 0.00 | 0.00 | 0.00 |
May | 226.99 | 16.80 | 210.19 | 689.93 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 207.64 | 3.54 | 204.09 | 683.63 | 9.79 | 0.00 | 0.00 | 0.00 |
July | 216.58 | 2.98 | 213.61 | 627.60 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 229.75 | 12.27 | 217.48 | 585.57 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 308.00 | 79.94 | 228.06 | 663.89 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 529.88 | 295.88 | 234.00 | 982.03 | 191.32 | 0.00 | 0.00 | 0.00 |
November | 661.85 | 437.47 | 224.38 | 1066.14 | 356.08 | 0.00 | 0.00 | 0.00 |
December | 590.68 | 370.14 | 220.54 | 826.72 | 473.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.51 | 177.20 | 223.30 | 763.15 | 188.28 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 207.64 | 2.98 | 204.09 | 585.57 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.85 | 437.47 | 250.89 | 1066.14 | 473.27 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.73 | 335.85 | 216.88 | 746.08 | 469.32 | 6.50 | 0.00 | 0.00 |
February | 525.57 | 291.92 | 233.65 | 774.93 | 383.91 | 0.00 | 0.00 | 0.00 |
March | 449.37 | 198.48 | 250.89 | 780.39 | 238.78 | 0.00 | 0.00 | 0.00 |
April | 315.64 | 89.08 | 226.56 | 735.12 | 86.36 | 0.00 | 0.00 | 0.00 |
May | 226.99 | 16.80 | 210.18 | 689.93 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 207.64 | 3.54 | 204.09 | 683.63 | 9.79 | 0.00 | 0.00 | 0.00 |
July | 216.58 | 2.98 | 213.60 | 627.60 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 229.75 | 12.27 | 217.48 | 585.57 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 308.00 | 79.94 | 228.06 | 663.89 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 529.88 | 295.88 | 234.00 | 982.02 | 191.32 | 0.00 | 0.00 | 0.00 |
November | 661.85 | 437.47 | 224.38 | 1066.14 | 356.08 | 0.00 | 0.00 | 0.00 |
December | 590.68 | 370.14 | 220.54 | 826.71 | 473.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.51 | 177.20 | 223.30 | 763.15 | 188.28 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 207.64 | 2.98 | 204.09 | 585.57 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.85 | 437.47 | 250.89 | 1066.14 | 473.26 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.73 | 335.86 | 216.88 | 746.08 | 469.32 | 6.50 | 0.00 | 0.00 |
February | 525.57 | 291.92 | 233.65 | 774.93 | 383.91 | 0.00 | 0.00 | 0.00 |
March | 449.37 | 198.49 | 250.89 | 780.39 | 238.78 | 0.00 | 0.00 | 0.00 |
April | 315.64 | 89.08 | 226.56 | 735.12 | 86.36 | 0.00 | 0.00 | 0.00 |
May | 226.99 | 16.80 | 210.19 | 689.93 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 207.64 | 3.54 | 204.09 | 683.63 | 9.79 | 0.00 | 0.00 | 0.00 |
July | 216.58 | 2.98 | 213.61 | 627.60 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 229.75 | 12.27 | 217.48 | 585.57 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 308.00 | 79.94 | 228.06 | 663.89 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 529.88 | 295.88 | 234.00 | 982.03 | 191.32 | 0.00 | 0.00 | 0.00 |
November | 661.85 | 437.47 | 224.38 | 1066.14 | 356.08 | 0.00 | 0.00 | 0.00 |
December | 590.68 | 370.14 | 220.54 | 826.72 | 473.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.51 | 177.20 | 223.30 | 763.15 | 188.28 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 207.64 | 2.98 | 204.09 | 585.57 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.85 | 437.47 | 250.89 | 1066.14 | 473.27 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.73 | 335.85 | 216.88 | 746.08 | 469.32 | 6.50 | 0.00 | 0.00 |
February | 525.57 | 291.92 | 233.65 | 774.93 | 383.91 | 0.00 | 0.00 | 0.00 |
March | 449.37 | 198.48 | 250.89 | 780.39 | 238.78 | 0.00 | 0.00 | 0.00 |
April | 315.64 | 89.08 | 226.56 | 735.12 | 86.36 | 0.00 | 0.00 | 0.00 |
May | 226.99 | 16.80 | 210.18 | 689.93 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 207.64 | 3.54 | 204.09 | 683.63 | 9.79 | 0.00 | 0.00 | 0.00 |
July | 216.58 | 2.98 | 213.60 | 627.60 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 229.75 | 12.27 | 217.48 | 585.57 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 308.00 | 79.94 | 228.06 | 663.89 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 529.88 | 295.88 | 234.00 | 982.02 | 191.32 | 0.00 | 0.00 | 0.00 |
November | 661.85 | 437.47 | 224.38 | 1066.14 | 356.08 | 0.00 | 0.00 | 0.00 |
December | 590.68 | 370.14 | 220.54 | 826.71 | 473.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.51 | 177.20 | 223.30 | 763.15 | 188.28 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 207.64 | 2.98 | 204.09 | 585.57 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.85 | 437.47 | 250.89 | 1066.14 | 473.26 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.71 | 335.84 | 216.87 | 746.05 | 469.30 | 6.50 | 0.00 | 0.00 |
February | 525.55 | 291.90 | 233.64 | 774.90 | 383.89 | 0.00 | 0.00 | 0.00 |
March | 449.36 | 198.48 | 250.88 | 780.35 | 238.77 | 0.00 | 0.00 | 0.00 |
April | 315.63 | 89.08 | 226.55 | 735.09 | 86.36 | 0.00 | 0.00 | 0.00 |
May | 226.98 | 16.80 | 210.18 | 689.90 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 207.63 | 3.54 | 204.08 | 683.60 | 9.79 | 0.00 | 0.00 | 0.00 |
July | 216.58 | 2.98 | 213.60 | 627.57 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 229.74 | 12.27 | 217.47 | 585.54 | 8.94 | 0.00 | 0.00 | 0.00 |
September | 307.99 | 79.94 | 228.05 | 663.86 | 36.66 | 0.00 | 0.00 | 0.00 |
October | 529.86 | 295.87 | 233.99 | 981.99 | 191.31 | 0.00 | 0.00 | 0.00 |
November | 661.82 | 437.45 | 224.37 | 1066.10 | 356.07 | 0.00 | 0.00 | 0.00 |
December | 590.66 | 370.12 | 220.54 | 826.68 | 473.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 400.49 | 177.20 | 223.29 | 763.12 | 188.27 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 207.63 | 2.98 | 204.08 | 585.54 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.82 | 437.45 | 250.88 | 1066.10 | 473.25 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.01 | 110.14 | 172.87 | 306.59 | 592.83 | 0.00 | 0.00 | 0.00 |
February | 323.63 | 119.27 | 204.36 | 413.85 | 486.55 | 0.00 | 0.00 | 0.00 |
March | 419.66 | 167.75 | 251.91 | 669.97 | 309.27 | 0.00 | 0.00 | 0.00 |
April | 510.09 | 239.21 | 270.88 | 1008.82 | 134.05 | 0.00 | 0.00 | 0.00 |
May | 483.01 | 204.88 | 278.13 | 1137.90 | 24.59 | 0.00 | 0.00 | 0.00 |
June | 453.68 | 176.22 | 277.46 | 1122.32 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 336.65 | 65.48 | 271.17 | 818.81 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 309.18 | 54.95 | 254.23 | 687.13 | 30.74 | 0.00 | 0.00 | 0.00 |
September | 339.87 | 99.78 | 240.09 | 695.35 | 54.13 | 0.00 | 0.00 | 0.00 |
October | 353.75 | 140.86 | 212.89 | 648.76 | 235.93 | 0.00 | 0.00 | 0.00 |
November | 320.03 | 136.39 | 183.63 | 475.02 | 449.57 | 0.00 | 0.00 | 0.00 |
December | 273.85 | 104.42 | 169.42 | 291.13 | 628.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.13 | 134.77 | 232.37 | 690.42 | 246.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.85 | 54.95 | 169.42 | 291.13 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.09 | 239.21 | 278.13 | 1137.90 | 628.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.01 | 110.14 | 172.87 | 306.59 | 592.83 | 0.00 | 0.00 | 0.00 |
February | 323.63 | 119.27 | 204.36 | 413.85 | 486.55 | 0.00 | 0.00 | 0.00 |
March | 419.66 | 167.75 | 251.91 | 669.97 | 309.27 | 0.00 | 0.00 | 0.00 |
April | 510.09 | 239.21 | 270.88 | 1008.82 | 134.05 | 0.00 | 0.00 | 0.00 |
May | 483.01 | 204.88 | 278.13 | 1137.90 | 24.59 | 0.00 | 0.00 | 0.00 |
June | 453.68 | 176.22 | 277.46 | 1122.32 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 336.65 | 65.48 | 271.17 | 818.81 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 309.18 | 54.95 | 254.23 | 687.13 | 30.74 | 0.00 | 0.00 | 0.00 |
September | 339.87 | 99.78 | 240.09 | 695.35 | 54.13 | 0.00 | 0.00 | 0.00 |
October | 353.75 | 140.86 | 212.89 | 648.76 | 235.93 | 0.00 | 0.00 | 0.00 |
November | 320.03 | 136.39 | 183.63 | 475.02 | 449.57 | 0.00 | 0.00 | 0.00 |
December | 273.85 | 104.42 | 169.42 | 291.13 | 628.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.13 | 134.77 | 232.37 | 690.42 | 246.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.85 | 54.95 | 169.42 | 291.13 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.09 | 239.21 | 278.13 | 1137.90 | 628.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.00 | 110.13 | 172.87 | 306.59 | 592.82 | 0.00 | 0.00 | 0.00 |
February | 323.62 | 119.26 | 204.36 | 413.84 | 486.54 | 0.00 | 0.00 | 0.00 |
March | 419.65 | 167.75 | 251.90 | 669.96 | 309.26 | 0.00 | 0.00 | 0.00 |
April | 510.09 | 239.21 | 270.87 | 1008.80 | 134.05 | 0.00 | 0.00 | 0.00 |
May | 483.00 | 204.88 | 278.12 | 1137.87 | 24.59 | 0.00 | 0.00 | 0.00 |
June | 453.67 | 176.22 | 277.45 | 1122.30 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 336.65 | 65.48 | 271.17 | 818.80 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 309.17 | 54.95 | 254.22 | 687.12 | 30.74 | 0.00 | 0.00 | 0.00 |
September | 339.86 | 99.77 | 240.09 | 695.34 | 54.13 | 0.00 | 0.00 | 0.00 |
October | 353.74 | 140.86 | 212.88 | 648.75 | 235.92 | 0.00 | 0.00 | 0.00 |
November | 320.02 | 136.39 | 183.63 | 475.01 | 449.56 | 0.00 | 0.00 | 0.00 |
December | 273.84 | 104.42 | 169.42 | 291.12 | 628.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.13 | 134.77 | 232.36 | 690.40 | 246.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.84 | 54.95 | 169.42 | 291.12 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.09 | 239.21 | 278.12 | 1137.87 | 628.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 607.66 | 0.00 | 607.66 | 409.05 | 2183.51 | 0.00 | 0.00 | 0.00 |
February | 720.58 | 0.00 | 720.58 | 734.74 | 1734.14 | 0.00 | 0.00 | 0.00 |
March | 868.31 | 0.00 | 868.31 | 1342.35 | 1073.42 | 0.00 | 0.00 | 0.00 |
April | 942.18 | 3.20 | 938.99 | 2343.95 | 376.08 | 0.00 | 0.00 | 0.00 |
May | 1043.87 | 29.29 | 1014.58 | 3254.64 | 66.88 | 0.00 | 0.00 | 0.00 |
June | 1080.57 | 40.02 | 1040.55 | 3529.45 | 53.15 | 0.00 | 0.00 | 0.00 |
July | 1065.69 | 16.88 | 1048.81 | 3122.34 | 14.50 | 0.00 | 0.00 | 0.00 |
August | 978.33 | 3.05 | 975.29 | 2632.20 | 46.15 | 0.00 | 0.00 | 0.00 |
September | 871.72 | 0.06 | 871.66 | 2045.26 | 160.73 | 0.00 | 0.00 | 0.00 |
October | 755.19 | 0.00 | 755.19 | 1498.95 | 840.95 | 0.00 | 0.00 | 0.00 |
November | 639.66 | 0.00 | 639.66 | 836.47 | 1572.51 | 0.00 | 0.00 | 0.00 |
December | 592.78 | 0.00 | 592.78 | 451.86 | 2134.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 847.86 | 7.74 | 840.12 | 1855.56 | 850.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 592.78 | 0.00 | 592.78 | 409.05 | 14.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1080.57 | 40.02 | 1048.81 | 3529.45 | 2183.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 867.81 | 348.33 | 519.48 | 906.75 | 1369.74 | 0.00 | 0.00 | 0.00 |
February | 1054.28 | 435.26 | 619.02 | 1352.12 | 1118.23 | 0.00 | 0.00 | 0.00 |
March | 1286.11 | 530.86 | 755.25 | 2062.43 | 710.66 | 0.00 | 0.00 | 0.00 |
April | 1530.14 | 713.43 | 816.71 | 3107.12 | 266.93 | 0.00 | 0.00 | 0.00 |
May | 1506.08 | 667.71 | 838.36 | 3555.02 | 46.01 | 0.00 | 0.00 | 0.00 |
June | 1225.75 | 406.70 | 819.05 | 3227.30 | 36.16 | 0.00 | 0.00 | 0.00 |
July | 1030.21 | 217.55 | 812.66 | 2642.61 | 8.47 | 0.00 | 0.00 | 0.00 |
August | 928.26 | 161.54 | 766.72 | 2233.84 | 31.44 | 0.00 | 0.00 | 0.00 |
September | 991.74 | 276.57 | 715.17 | 2072.00 | 111.76 | 0.00 | 0.00 | 0.00 |
October | 1084.85 | 438.21 | 646.64 | 1993.57 | 569.01 | 0.00 | 0.00 | 0.00 |
November | 961.88 | 412.88 | 549.00 | 1413.56 | 1025.31 | 0.00 | 0.00 | 0.00 |
December | 838.72 | 332.30 | 506.41 | 945.93 | 1371.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1108.52 | 411.14 | 697.38 | 2128.78 | 552.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 838.72 | 161.54 | 506.41 | 906.75 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1530.14 | 713.43 | 838.36 | 3555.02 | 1371.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2763.64 | 1679.26 | 1084.38 | 3723.65 | 2258.67 | 0.00 | 0.00 | 0.00 |
February | 2627.81 | 1459.56 | 1168.25 | 3856.37 | 1859.79 | 0.00 | 0.00 | 0.00 |
March | 2246.85 | 992.41 | 1254.43 | 3885.42 | 1181.26 | 0.00 | 0.00 | 0.00 |
April | 1578.19 | 445.41 | 1132.78 | 3689.27 | 434.20 | 0.00 | 0.00 | 0.00 |
May | 1134.93 | 84.02 | 1050.91 | 3472.44 | 67.83 | 0.00 | 0.00 | 0.00 |
June | 1038.17 | 17.72 | 1020.45 | 3448.54 | 52.70 | 0.00 | 0.00 | 0.00 |
July | 1082.91 | 14.89 | 1068.01 | 3170.29 | 13.01 | 0.00 | 0.00 | 0.00 |
August | 1148.74 | 61.35 | 1087.38 | 2969.96 | 48.75 | 0.00 | 0.00 | 0.00 |
September | 1539.97 | 399.70 | 1140.27 | 3308.50 | 194.38 | 0.00 | 0.00 | 0.00 |
October | 2649.36 | 1479.39 | 1169.97 | 4884.82 | 970.27 | 0.00 | 0.00 | 0.00 |
November | 3309.19 | 2187.31 | 1121.89 | 5305.47 | 1750.17 | 0.00 | 0.00 | 0.00 |
December | 2953.37 | 1850.66 | 1102.71 | 4139.28 | 2266.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2002.51 | 886.01 | 1116.51 | 3819.60 | 920.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1038.17 | 14.89 | 1020.45 | 2969.96 | 13.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3309.19 | 2187.31 | 1254.43 | 5305.47 | 2266.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.01 | 330.40 | 518.61 | 990.18 | 1535.99 | 0.00 | 0.00 | 0.00 |
February | 970.87 | 357.79 | 613.08 | 1311.05 | 1244.88 | 0.00 | 0.00 | 0.00 |
March | 1258.97 | 503.26 | 755.72 | 2060.36 | 803.76 | 0.00 | 0.00 | 0.00 |
April | 1530.27 | 717.64 | 812.63 | 3105.19 | 318.19 | 0.00 | 0.00 | 0.00 |
May | 1449.02 | 614.64 | 834.38 | 3447.62 | 63.80 | 0.00 | 0.00 | 0.00 |
June | 1361.02 | 528.66 | 832.36 | 3434.43 | 46.57 | 0.00 | 0.00 | 0.00 |
July | 1009.94 | 196.43 | 813.51 | 2560.67 | 13.42 | 0.00 | 0.00 | 0.00 |
August | 927.53 | 164.85 | 762.68 | 2202.41 | 40.12 | 0.00 | 0.00 | 0.00 |
September | 1019.60 | 299.32 | 720.27 | 2112.46 | 137.72 | 0.00 | 0.00 | 0.00 |
October | 1061.24 | 422.59 | 638.66 | 1983.76 | 632.18 | 0.00 | 0.00 | 0.00 |
November | 960.07 | 409.18 | 550.89 | 1495.89 | 1142.12 | 0.00 | 0.00 | 0.00 |
December | 821.54 | 313.27 | 508.27 | 991.29 | 1504.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1101.39 | 404.30 | 697.09 | 2143.76 | 620.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 821.54 | 164.85 | 508.27 | 990.18 | 13.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1530.27 | 717.64 | 834.38 | 3447.62 | 1535.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 607.66 | 0.00 | 607.66 | 456.99 | 1986.72 | 0.00 | 0.00 | 0.00 |
February | 720.58 | 0.00 | 720.58 | 772.02 | 1613.33 | 0.00 | 0.00 | 0.00 |
March | 868.31 | 0.00 | 868.31 | 1344.41 | 1030.73 | 0.00 | 0.00 | 0.00 |
April | 942.18 | 3.20 | 938.99 | 2313.58 | 374.25 | 0.00 | 0.00 | 0.00 |
May | 1043.87 | 29.29 | 1014.58 | 3208.92 | 71.36 | 0.00 | 0.00 | 0.00 |
June | 1080.57 | 40.02 | 1040.55 | 3480.87 | 55.57 | 0.00 | 0.00 | 0.00 |
July | 1065.69 | 16.88 | 1048.81 | 3069.24 | 15.04 | 0.00 | 0.00 | 0.00 |
August | 978.33 | 3.05 | 975.29 | 2590.07 | 48.97 | 0.00 | 0.00 | 0.00 |
September | 871.72 | 0.06 | 871.66 | 2018.38 | 165.15 | 0.00 | 0.00 | 0.00 |
October | 755.19 | 0.00 | 755.19 | 1492.17 | 815.74 | 0.00 | 0.00 | 0.00 |
November | 639.66 | 0.00 | 639.66 | 870.08 | 1468.88 | 0.00 | 0.00 | 0.00 |
December | 592.78 | 0.00 | 592.78 | 509.17 | 1948.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 847.86 | 7.74 | 840.12 | 1849.05 | 795.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 592.78 | 0.00 | 592.78 | 456.99 | 15.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1080.57 | 40.02 | 1048.81 | 3480.87 | 1986.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 867.81 | 348.33 | 519.48 | 957.65 | 1254.82 | 0.00 | 0.00 | 0.00 |
February | 1054.28 | 435.26 | 619.02 | 1379.25 | 1055.05 | 0.00 | 0.00 | 0.00 |
March | 1286.11 | 530.86 | 755.25 | 2059.65 | 691.95 | 0.00 | 0.00 | 0.00 |
April | 1530.14 | 713.43 | 816.71 | 3083.03 | 268.63 | 0.00 | 0.00 | 0.00 |
May | 1506.08 | 667.71 | 838.36 | 3519.62 | 50.19 | 0.00 | 0.00 | 0.00 |
June | 1225.75 | 406.70 | 819.05 | 3190.64 | 38.31 | 0.00 | 0.00 | 0.00 |
July | 1030.21 | 217.55 | 812.66 | 2603.18 | 8.82 | 0.00 | 0.00 | 0.00 |
August | 928.26 | 161.54 | 766.72 | 2202.77 | 33.62 | 0.00 | 0.00 | 0.00 |
September | 991.74 | 276.57 | 715.17 | 2051.68 | 116.21 | 0.00 | 0.00 | 0.00 |
October | 1084.85 | 438.21 | 646.64 | 1987.18 | 557.89 | 0.00 | 0.00 | 0.00 |
November | 961.88 | 412.88 | 549.00 | 1434.02 | 974.02 | 0.00 | 0.00 | 0.00 |
December | 838.72 | 332.30 | 506.41 | 997.54 | 1266.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1108.52 | 411.14 | 697.38 | 2124.81 | 523.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 838.72 | 161.54 | 506.41 | 957.65 | 8.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1530.14 | 713.43 | 838.36 | 3519.62 | 1266.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2763.64 | 1679.26 | 1084.38 | 3783.08 | 2075.13 | 0.00 | 0.00 | 0.00 |
February | 2627.81 | 1459.56 | 1168.25 | 3881.90 | 1754.67 | 0.00 | 0.00 | 0.00 |
March | 2246.85 | 992.41 | 1254.43 | 3875.69 | 1145.31 | 0.00 | 0.00 | 0.00 |
April | 1578.19 | 445.41 | 1132.78 | 3655.82 | 432.65 | 0.00 | 0.00 | 0.00 |
May | 1134.93 | 84.02 | 1050.91 | 3426.83 | 72.19 | 0.00 | 0.00 | 0.00 |
June | 1038.17 | 17.72 | 1020.45 | 3399.63 | 55.42 | 0.00 | 0.00 | 0.00 |
July | 1082.91 | 14.89 | 1068.01 | 3116.92 | 13.39 | 0.00 | 0.00 | 0.00 |
August | 1148.74 | 61.35 | 1087.38 | 2927.52 | 51.69 | 0.00 | 0.00 | 0.00 |
September | 1539.97 | 399.70 | 1140.27 | 3278.89 | 199.46 | 0.00 | 0.00 | 0.00 |
October | 2649.36 | 1479.39 | 1169.97 | 4869.94 | 949.01 | 0.00 | 0.00 | 0.00 |
November | 3309.19 | 2187.31 | 1121.89 | 5317.84 | 1669.22 | 0.00 | 0.00 | 0.00 |
December | 2953.37 | 1850.66 | 1102.71 | 4195.85 | 2108.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2002.51 | 886.01 | 1116.51 | 3809.12 | 873.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1038.17 | 14.89 | 1020.45 | 2927.52 | 13.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3309.19 | 2187.31 | 1254.43 | 5317.84 | 2108.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.01 | 330.40 | 518.61 | 1012.89 | 1422.00 | 0.00 | 0.00 | 0.00 |
February | 970.87 | 357.79 | 613.08 | 1324.19 | 1177.17 | 0.00 | 0.00 | 0.00 |
March | 1258.97 | 503.26 | 755.72 | 2054.76 | 778.87 | 0.00 | 0.00 | 0.00 |
April | 1530.27 | 717.64 | 812.63 | 3082.87 | 316.28 | 0.00 | 0.00 | 0.00 |
May | 1449.02 | 614.64 | 834.38 | 3418.74 | 66.56 | 0.00 | 0.00 | 0.00 |
June | 1361.02 | 528.66 | 832.36 | 3403.39 | 47.66 | 0.00 | 0.00 | 0.00 |
July | 1009.94 | 196.43 | 813.51 | 2528.19 | 13.78 | 0.00 | 0.00 | 0.00 |
August | 927.53 | 164.85 | 762.68 | 2177.19 | 41.93 | 0.00 | 0.00 | 0.00 |
September | 1019.60 | 299.32 | 720.27 | 2095.01 | 140.26 | 0.00 | 0.00 | 0.00 |
October | 1061.24 | 422.59 | 638.66 | 1976.27 | 616.25 | 0.00 | 0.00 | 0.00 |
November | 960.07 | 409.18 | 550.89 | 1508.15 | 1084.38 | 0.00 | 0.00 | 0.00 |
December | 821.54 | 313.27 | 508.27 | 1017.87 | 1401.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1101.39 | 404.30 | 697.09 | 2135.68 | 589.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 821.54 | 164.85 | 508.27 | 1012.89 | 13.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1530.27 | 717.64 | 834.38 | 3418.74 | 1422.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325516E+09 | 0.00 | 0.325516E+09 | 0.165571E+09 | 0.135419E+10 |
February | 0.348651E+09 | 0.00 | 0.348651E+09 | 0.314738E+09 | 0.947664E+09 |
March | 0.465139E+09 | 0.00 | 0.465139E+09 | 0.696277E+09 | 0.616220E+09 |
April | 0.488432E+09 | 1656439.11 | 0.486776E+09 | 0.118494E+10 | 0.203717E+09 |
May | 0.559187E+09 | 15691820.25 | 0.543495E+09 | 0.172776E+10 | 34907428.45 |
June | 0.560175E+09 | 20748985.46 | 0.539426E+09 | 0.181370E+10 | 25479460.82 |
July | 0.570876E+09 | 9040164.91 | 0.561836E+09 | 0.165482E+10 | 6005937.24 |
August | 0.524081E+09 | 1633324.16 | 0.522447E+09 | 0.137912E+10 | 23104255.03 |
September | 0.451907E+09 | 31731.96 | 0.451875E+09 | 0.105165E+10 | 83086368.97 |
October | 0.404548E+09 | 0.00 | 0.404548E+09 | 0.782843E+09 | 0.471953E+09 |
November | 0.331602E+09 | 0.00 | 0.331602E+09 | 0.395389E+09 | 0.908413E+09 |
December | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.179054E+09 | 0.134071E+10 |
Annual Sum or Average | 0.534766E+10 | 48802465.84 | 0.529886E+10 | 0.113459E+11 | 0.601546E+10 |
Minimum of Months | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.165571E+09 | 6005937.24 |
Maximum of Months | 0.570876E+09 | 20748985.46 | 0.561836E+09 | 0.181370E+10 | 0.135419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325516E+09 | 0.00 | 0.325516E+09 | 0.165571E+09 | 0.135419E+10 |
February | 0.348651E+09 | 0.00 | 0.348651E+09 | 0.314738E+09 | 0.947663E+09 |
March | 0.465139E+09 | 0.00 | 0.465139E+09 | 0.696277E+09 | 0.616220E+09 |
April | 0.488432E+09 | 1656437.12 | 0.486776E+09 | 0.118494E+10 | 0.203717E+09 |
May | 0.559186E+09 | 15691801.42 | 0.543494E+09 | 0.172776E+10 | 34907362.54 |
June | 0.560174E+09 | 20748960.56 | 0.539425E+09 | 0.181370E+10 | 25479437.65 |
July | 0.570875E+09 | 9040154.06 | 0.561835E+09 | 0.165482E+10 | 6005923.31 |
August | 0.524080E+09 | 1633322.20 | 0.522447E+09 | 0.137912E+10 | 23104216.59 |
September | 0.451907E+09 | 31731.92 | 0.451875E+09 | 0.105165E+10 | 83086256.65 |
October | 0.404547E+09 | 0.00 | 0.404547E+09 | 0.782843E+09 | 0.471952E+09 |
November | 0.331602E+09 | 0.00 | 0.331602E+09 | 0.395389E+09 | 0.908413E+09 |
December | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.179054E+09 | 0.134071E+10 |
Annual Sum or Average | 0.534766E+10 | 48802407.29 | 0.529885E+10 | 0.113459E+11 | 0.601545E+10 |
Minimum of Months | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.165571E+09 | 6005923.31 |
Maximum of Months | 0.570875E+09 | 20748960.56 | 0.561835E+09 | 0.181370E+10 | 0.135419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325516E+09 | 0.00 | 0.325516E+09 | 0.165571E+09 | 0.135419E+10 |
February | 0.348651E+09 | 0.00 | 0.348651E+09 | 0.314738E+09 | 0.947664E+09 |
March | 0.465139E+09 | 0.00 | 0.465139E+09 | 0.696277E+09 | 0.616220E+09 |
April | 0.488432E+09 | 1656439.11 | 0.486776E+09 | 0.118494E+10 | 0.203717E+09 |
May | 0.559187E+09 | 15691820.25 | 0.543495E+09 | 0.172776E+10 | 34907428.45 |
June | 0.560175E+09 | 20748985.46 | 0.539426E+09 | 0.181370E+10 | 25479460.82 |
July | 0.570876E+09 | 9040164.91 | 0.561836E+09 | 0.165482E+10 | 6005937.24 |
August | 0.524081E+09 | 1633324.16 | 0.522447E+09 | 0.137912E+10 | 23104255.03 |
September | 0.451907E+09 | 31731.96 | 0.451875E+09 | 0.105165E+10 | 83086368.97 |
October | 0.404548E+09 | 0.00 | 0.404548E+09 | 0.782843E+09 | 0.471953E+09 |
November | 0.331602E+09 | 0.00 | 0.331602E+09 | 0.395389E+09 | 0.908413E+09 |
December | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.179054E+09 | 0.134071E+10 |
Annual Sum or Average | 0.534766E+10 | 48802465.84 | 0.529886E+10 | 0.113459E+11 | 0.601546E+10 |
Minimum of Months | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.165571E+09 | 6005937.24 |
Maximum of Months | 0.570876E+09 | 20748985.46 | 0.561836E+09 | 0.181370E+10 | 0.135419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325516E+09 | 0.00 | 0.325516E+09 | 0.165571E+09 | 0.135419E+10 |
February | 0.348651E+09 | 0.00 | 0.348651E+09 | 0.314738E+09 | 0.947663E+09 |
March | 0.465139E+09 | 0.00 | 0.465139E+09 | 0.696277E+09 | 0.616220E+09 |
April | 0.488432E+09 | 1656437.12 | 0.486776E+09 | 0.118494E+10 | 0.203717E+09 |
May | 0.559186E+09 | 15691801.42 | 0.543494E+09 | 0.172776E+10 | 34907362.54 |
June | 0.560174E+09 | 20748960.56 | 0.539425E+09 | 0.181370E+10 | 25479437.65 |
July | 0.570875E+09 | 9040154.06 | 0.561835E+09 | 0.165482E+10 | 6005923.31 |
August | 0.524080E+09 | 1633322.20 | 0.522447E+09 | 0.137912E+10 | 23104216.59 |
September | 0.451907E+09 | 31731.92 | 0.451875E+09 | 0.105165E+10 | 83086256.65 |
October | 0.404547E+09 | 0.00 | 0.404547E+09 | 0.782843E+09 | 0.471952E+09 |
November | 0.331602E+09 | 0.00 | 0.331602E+09 | 0.395389E+09 | 0.908413E+09 |
December | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.179054E+09 | 0.134071E+10 |
Annual Sum or Average | 0.534766E+10 | 48802407.29 | 0.529885E+10 | 0.113459E+11 | 0.601545E+10 |
Minimum of Months | 0.317546E+09 | 0.00 | 0.317546E+09 | 0.165571E+09 | 6005923.31 |
Maximum of Months | 0.570875E+09 | 20748960.56 | 0.561835E+09 | 0.181370E+10 | 0.135419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.325503E+09 | 0.00 | 0.325503E+09 | 0.165564E+09 | 0.135414E+10 |
February | 0.348637E+09 | 0.00 | 0.348637E+09 | 0.314726E+09 | 0.947625E+09 |
March | 0.465121E+09 | 0.00 | 0.465121E+09 | 0.696249E+09 | 0.616195E+09 |
April | 0.488413E+09 | 1656372.35 | 0.486756E+09 | 0.118489E+10 | 0.203709E+09 |
May | 0.559164E+09 | 15691187.80 | 0.543473E+09 | 0.172769E+10 | 34906021.53 |
June | 0.560152E+09 | 20748149.18 | 0.539404E+09 | 0.181363E+10 | 25478433.88 |
July | 0.570853E+09 | 9039800.55 | 0.561813E+09 | 0.165476E+10 | 6005695.17 |
August | 0.524060E+09 | 1633258.33 | 0.522426E+09 | 0.137907E+10 | 23103323.82 |
September | 0.451889E+09 | 31730.68 | 0.451857E+09 | 0.105161E+10 | 83083020.22 |
October | 0.404531E+09 | 0.00 | 0.404531E+09 | 0.782812E+09 | 0.471933E+09 |
November | 0.331589E+09 | 0.00 | 0.331589E+09 | 0.395374E+09 | 0.908377E+09 |
December | 0.317534E+09 | 0.00 | 0.317534E+09 | 0.179047E+09 | 0.134066E+10 |
Annual Sum or Average | 0.534744E+10 | 48800498.89 | 0.529864E+10 | 0.113454E+11 | 0.601521E+10 |
Minimum of Months | 0.317534E+09 | 0.00 | 0.317534E+09 | 0.165564E+09 | 6005695.17 |
Maximum of Months | 0.570853E+09 | 20748149.18 | 0.561813E+09 | 0.181363E+10 | 0.135414E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.774791E+09 | 0.310990E+09 | 0.463800E+09 | 0.753250E+09 | 0.136705E+10 |
February | 0.850181E+09 | 0.350995E+09 | 0.499187E+09 | 0.107140E+10 | 0.967119E+09 |
March | 0.114825E+10 | 0.473959E+09 | 0.674294E+09 | 0.184909E+10 | 0.635827E+09 |
April | 0.132205E+10 | 0.616410E+09 | 0.705645E+09 | 0.270141E+10 | 0.209969E+09 |
May | 0.134464E+10 | 0.596140E+09 | 0.748500E+09 | 0.319039E+10 | 36676680.29 |
June | 0.105906E+10 | 0.351395E+09 | 0.707664E+09 | 0.280421E+10 | 24853698.78 |
July | 0.919782E+09 | 0.194233E+09 | 0.725548E+09 | 0.237917E+10 | 3977012.41 |
August | 0.828761E+09 | 0.144224E+09 | 0.684537E+09 | 0.201255E+10 | 16099425.70 |
September | 0.856875E+09 | 0.238961E+09 | 0.617914E+09 | 0.180137E+10 | 85087671.54 |
October | 0.968564E+09 | 0.391236E+09 | 0.577328E+09 | 0.178545E+10 | 0.502221E+09 |
November | 0.831070E+09 | 0.356733E+09 | 0.474337E+09 | 0.120704E+10 | 0.931147E+09 |
December | 0.748814E+09 | 0.296684E+09 | 0.452129E+09 | 0.794229E+09 | 0.134538E+10 |
Annual Sum or Average | 0.116528E+11 | 0.432196E+10 | 0.733088E+10 | 0.223496E+11 | 0.612541E+10 |
Minimum of Months | 0.748814E+09 | 0.144224E+09 | 0.452129E+09 | 0.753250E+09 | 3977012.41 |
Maximum of Months | 0.134464E+10 | 0.616410E+09 | 0.748500E+09 | 0.319039E+10 | 0.136705E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.774791E+09 | 0.310990E+09 | 0.463800E+09 | 0.753250E+09 | 0.136705E+10 |
February | 0.850181E+09 | 0.350995E+09 | 0.499187E+09 | 0.107140E+10 | 0.967119E+09 |
March | 0.114825E+10 | 0.473959E+09 | 0.674294E+09 | 0.184909E+10 | 0.635827E+09 |
April | 0.132205E+10 | 0.616410E+09 | 0.705645E+09 | 0.270141E+10 | 0.209969E+09 |
May | 0.134464E+10 | 0.596140E+09 | 0.748500E+09 | 0.319039E+10 | 36676680.29 |
June | 0.105906E+10 | 0.351395E+09 | 0.707664E+09 | 0.280421E+10 | 24853698.78 |
July | 0.919782E+09 | 0.194233E+09 | 0.725548E+09 | 0.237917E+10 | 3977012.41 |
August | 0.828761E+09 | 0.144224E+09 | 0.684537E+09 | 0.201255E+10 | 16099425.70 |
September | 0.856875E+09 | 0.238961E+09 | 0.617914E+09 | 0.180137E+10 | 85087671.54 |
October | 0.968564E+09 | 0.391236E+09 | 0.577328E+09 | 0.178545E+10 | 0.502221E+09 |
November | 0.831070E+09 | 0.356733E+09 | 0.474337E+09 | 0.120704E+10 | 0.931147E+09 |
December | 0.748814E+09 | 0.296684E+09 | 0.452129E+09 | 0.794229E+09 | 0.134538E+10 |
Annual Sum or Average | 0.116528E+11 | 0.432196E+10 | 0.733088E+10 | 0.223496E+11 | 0.612541E+10 |
Minimum of Months | 0.748814E+09 | 0.144224E+09 | 0.452129E+09 | 0.753250E+09 | 3977012.41 |
Maximum of Months | 0.134464E+10 | 0.616410E+09 | 0.748500E+09 | 0.319039E+10 | 0.136705E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.774776E+09 | 0.310985E+09 | 0.463792E+09 | 0.753236E+09 | 0.136703E+10 |
February | 0.850166E+09 | 0.350988E+09 | 0.499178E+09 | 0.107138E+10 | 0.967101E+09 |
March | 0.114823E+10 | 0.473950E+09 | 0.674282E+09 | 0.184906E+10 | 0.635816E+09 |
April | 0.132203E+10 | 0.616398E+09 | 0.705632E+09 | 0.270136E+10 | 0.209965E+09 |
May | 0.134462E+10 | 0.596129E+09 | 0.748486E+09 | 0.319033E+10 | 36676010.13 |
June | 0.105904E+10 | 0.351388E+09 | 0.707651E+09 | 0.280416E+10 | 24853244.65 |
July | 0.919765E+09 | 0.194230E+09 | 0.725535E+09 | 0.237913E+10 | 3976939.74 |
August | 0.828746E+09 | 0.144221E+09 | 0.684525E+09 | 0.201251E+10 | 16099131.53 |
September | 0.856859E+09 | 0.238957E+09 | 0.617902E+09 | 0.180134E+10 | 85086116.80 |
October | 0.968546E+09 | 0.391229E+09 | 0.577317E+09 | 0.178541E+10 | 0.502211E+09 |
November | 0.831055E+09 | 0.356726E+09 | 0.474329E+09 | 0.120702E+10 | 0.931130E+09 |
December | 0.748800E+09 | 0.296679E+09 | 0.452121E+09 | 0.794214E+09 | 0.134536E+10 |
Annual Sum or Average | 0.116526E+11 | 0.432188E+10 | 0.733075E+10 | 0.223492E+11 | 0.612530E+10 |
Minimum of Months | 0.748800E+09 | 0.144221E+09 | 0.452121E+09 | 0.753236E+09 | 3976939.74 |
Maximum of Months | 0.134462E+10 | 0.616398E+09 | 0.748486E+09 | 0.319033E+10 | 0.136703E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148044E+10 | 0.899555E+09 | 0.580887E+09 | 0.199829E+10 | 0.125703E+10 |
February | 0.127146E+10 | 0.706203E+09 | 0.565254E+09 | 0.187472E+10 | 0.928756E+09 |
March | 0.120360E+10 | 0.531622E+09 | 0.671983E+09 | 0.209019E+10 | 0.639544E+09 |
April | 0.818144E+09 | 0.230906E+09 | 0.587239E+09 | 0.190543E+10 | 0.223850E+09 |
May | 0.607966E+09 | 45005984.73 | 0.562960E+09 | 0.184791E+10 | 35536156.00 |
June | 0.538192E+09 | 9184103.82 | 0.529008E+09 | 0.177196E+10 | 25383616.16 |
July | 0.580099E+09 | 7978783.19 | 0.572120E+09 | 0.168096E+10 | 5540549.57 |
August | 0.615362E+09 | 32864967.22 | 0.582497E+09 | 0.156838E+10 | 23943720.90 |
September | 0.798331E+09 | 0.207209E+09 | 0.591123E+09 | 0.172079E+10 | 95034428.17 |
October | 0.141923E+10 | 0.792491E+09 | 0.626737E+09 | 0.263026E+10 | 0.512429E+09 |
November | 0.171551E+10 | 0.113391E+10 | 0.581593E+09 | 0.276344E+10 | 0.922968E+09 |
December | 0.158208E+10 | 0.991376E+09 | 0.590705E+09 | 0.221427E+10 | 0.126759E+10 |
Annual Sum or Average | 0.126304E+11 | 0.558831E+10 | 0.704211E+10 | 0.240666E+11 | 0.593761E+10 |
Minimum of Months | 0.538192E+09 | 7978783.19 | 0.529008E+09 | 0.156838E+10 | 5540549.57 |
Maximum of Months | 0.171551E+10 | 0.113391E+10 | 0.671983E+09 | 0.276344E+10 | 0.126759E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148044E+10 | 0.899554E+09 | 0.580887E+09 | 0.199829E+10 | 0.125703E+10 |
February | 0.127146E+10 | 0.706202E+09 | 0.565253E+09 | 0.187472E+10 | 0.928756E+09 |
March | 0.120360E+10 | 0.531622E+09 | 0.671982E+09 | 0.209018E+10 | 0.639544E+09 |
April | 0.818144E+09 | 0.230905E+09 | 0.587238E+09 | 0.190543E+10 | 0.223849E+09 |
May | 0.607965E+09 | 45005930.72 | 0.562959E+09 | 0.184791E+10 | 35536089.67 |
June | 0.538192E+09 | 9184092.80 | 0.529008E+09 | 0.177196E+10 | 25383594.58 |
July | 0.580098E+09 | 7978773.62 | 0.572119E+09 | 0.168096E+10 | 5540537.52 |
August | 0.615361E+09 | 32864927.79 | 0.582496E+09 | 0.156838E+10 | 23943683.55 |
September | 0.798330E+09 | 0.207208E+09 | 0.591122E+09 | 0.172079E+10 | 95034308.08 |
October | 0.141923E+10 | 0.792490E+09 | 0.626736E+09 | 0.263026E+10 | 0.512429E+09 |
November | 0.171551E+10 | 0.113391E+10 | 0.581593E+09 | 0.276344E+10 | 0.922967E+09 |
December | 0.158208E+10 | 0.991375E+09 | 0.590705E+09 | 0.221427E+10 | 0.126759E+10 |
Annual Sum or Average | 0.126304E+11 | 0.558830E+10 | 0.704210E+10 | 0.240666E+11 | 0.593761E+10 |
Minimum of Months | 0.538192E+09 | 7978773.62 | 0.529008E+09 | 0.156838E+10 | 5540537.52 |
Maximum of Months | 0.171551E+10 | 0.113391E+10 | 0.671982E+09 | 0.276344E+10 | 0.126759E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148044E+10 | 0.899555E+09 | 0.580887E+09 | 0.199829E+10 | 0.125703E+10 |
February | 0.127146E+10 | 0.706203E+09 | 0.565254E+09 | 0.187472E+10 | 0.928756E+09 |
March | 0.120360E+10 | 0.531622E+09 | 0.671983E+09 | 0.209019E+10 | 0.639544E+09 |
April | 0.818144E+09 | 0.230906E+09 | 0.587239E+09 | 0.190543E+10 | 0.223850E+09 |
May | 0.607966E+09 | 45005984.73 | 0.562960E+09 | 0.184791E+10 | 35536156.00 |
June | 0.538192E+09 | 9184103.82 | 0.529008E+09 | 0.177196E+10 | 25383616.16 |
July | 0.580099E+09 | 7978783.19 | 0.572120E+09 | 0.168096E+10 | 5540549.57 |
August | 0.615362E+09 | 32864967.22 | 0.582497E+09 | 0.156838E+10 | 23943720.90 |
September | 0.798331E+09 | 0.207209E+09 | 0.591123E+09 | 0.172079E+10 | 95034428.17 |
October | 0.141923E+10 | 0.792491E+09 | 0.626737E+09 | 0.263026E+10 | 0.512429E+09 |
November | 0.171551E+10 | 0.113391E+10 | 0.581593E+09 | 0.276344E+10 | 0.922968E+09 |
December | 0.158208E+10 | 0.991376E+09 | 0.590705E+09 | 0.221427E+10 | 0.126759E+10 |
Annual Sum or Average | 0.126304E+11 | 0.558831E+10 | 0.704211E+10 | 0.240666E+11 | 0.593761E+10 |
Minimum of Months | 0.538192E+09 | 7978783.19 | 0.529008E+09 | 0.156838E+10 | 5540549.57 |
Maximum of Months | 0.171551E+10 | 0.113391E+10 | 0.671983E+09 | 0.276344E+10 | 0.126759E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148044E+10 | 0.899554E+09 | 0.580887E+09 | 0.199829E+10 | 0.125703E+10 |
February | 0.127146E+10 | 0.706202E+09 | 0.565253E+09 | 0.187472E+10 | 0.928756E+09 |
March | 0.120360E+10 | 0.531622E+09 | 0.671982E+09 | 0.209018E+10 | 0.639544E+09 |
April | 0.818144E+09 | 0.230905E+09 | 0.587238E+09 | 0.190543E+10 | 0.223849E+09 |
May | 0.607965E+09 | 45005930.72 | 0.562959E+09 | 0.184791E+10 | 35536089.67 |
June | 0.538192E+09 | 9184092.80 | 0.529008E+09 | 0.177196E+10 | 25383594.58 |
July | 0.580098E+09 | 7978773.62 | 0.572119E+09 | 0.168096E+10 | 5540537.52 |
August | 0.615361E+09 | 32864927.79 | 0.582496E+09 | 0.156838E+10 | 23943683.55 |
September | 0.798330E+09 | 0.207208E+09 | 0.591122E+09 | 0.172079E+10 | 95034308.08 |
October | 0.141923E+10 | 0.792490E+09 | 0.626736E+09 | 0.263026E+10 | 0.512429E+09 |
November | 0.171551E+10 | 0.113391E+10 | 0.581593E+09 | 0.276344E+10 | 0.922967E+09 |
December | 0.158208E+10 | 0.991375E+09 | 0.590705E+09 | 0.221427E+10 | 0.126759E+10 |
Annual Sum or Average | 0.126304E+11 | 0.558830E+10 | 0.704210E+10 | 0.240666E+11 | 0.593761E+10 |
Minimum of Months | 0.538192E+09 | 7978773.62 | 0.529008E+09 | 0.156838E+10 | 5540537.52 |
Maximum of Months | 0.171551E+10 | 0.113391E+10 | 0.671982E+09 | 0.276344E+10 | 0.126759E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148038E+10 | 0.899518E+09 | 0.580864E+09 | 0.199821E+10 | 0.125698E+10 |
February | 0.127141E+10 | 0.706175E+09 | 0.565231E+09 | 0.187464E+10 | 0.928718E+09 |
March | 0.120356E+10 | 0.531601E+09 | 0.671955E+09 | 0.209010E+10 | 0.639519E+09 |
April | 0.818111E+09 | 0.230896E+09 | 0.587215E+09 | 0.190535E+10 | 0.223841E+09 |
May | 0.607941E+09 | 45004170.79 | 0.562937E+09 | 0.184784E+10 | 35534723.73 |
June | 0.538171E+09 | 9183733.66 | 0.528987E+09 | 0.177189E+10 | 25382593.09 |
July | 0.580075E+09 | 7978461.61 | 0.572097E+09 | 0.168089E+10 | 5540326.26 |
August | 0.615337E+09 | 32863642.62 | 0.582473E+09 | 0.156832E+10 | 23942755.86 |
September | 0.798299E+09 | 0.207200E+09 | 0.591099E+09 | 0.172072E+10 | 95030597.86 |
October | 0.141917E+10 | 0.792459E+09 | 0.626712E+09 | 0.263015E+10 | 0.512408E+09 |
November | 0.171544E+10 | 0.113387E+10 | 0.581570E+09 | 0.276333E+10 | 0.922930E+09 |
December | 0.158202E+10 | 0.991336E+09 | 0.590682E+09 | 0.221419E+10 | 0.126754E+10 |
Annual Sum or Average | 0.126299E+11 | 0.558808E+10 | 0.704182E+10 | 0.240656E+11 | 0.593737E+10 |
Minimum of Months | 0.538171E+09 | 7978461.61 | 0.528987E+09 | 0.156832E+10 | 5540326.26 |
Maximum of Months | 0.171544E+10 | 0.113387E+10 | 0.671955E+09 | 0.276333E+10 | 0.126754E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.758008E+09 | 0.294988E+09 | 0.463020E+09 | 0.821181E+09 | 0.158784E+10 |
February | 0.782918E+09 | 0.288526E+09 | 0.494392E+09 | 0.100119E+10 | 0.117705E+10 |
March | 0.112402E+10 | 0.449311E+09 | 0.674711E+09 | 0.179444E+10 | 0.828341E+09 |
April | 0.132216E+10 | 0.620045E+09 | 0.702120E+09 | 0.261486E+10 | 0.347461E+09 |
May | 0.129370E+10 | 0.548760E+09 | 0.744938E+09 | 0.304774E+10 | 65872261.53 |
June | 0.117593E+10 | 0.456763E+09 | 0.719167E+09 | 0.290906E+10 | 49124849.30 |
July | 0.901687E+09 | 0.175379E+09 | 0.726309E+09 | 0.219310E+10 | 21908516.35 |
August | 0.828105E+09 | 0.147180E+09 | 0.680926E+09 | 0.184041E+10 | 82330708.83 |
September | 0.880940E+09 | 0.258619E+09 | 0.622321E+09 | 0.180236E+10 | 0.140316E+09 |
October | 0.947487E+09 | 0.377288E+09 | 0.570199E+09 | 0.173765E+10 | 0.631906E+09 |
November | 0.829508E+09 | 0.353531E+09 | 0.475977E+09 | 0.123125E+10 | 0.116529E+10 |
December | 0.733476E+09 | 0.279691E+09 | 0.453785E+09 | 0.779750E+09 | 0.168243E+10 |
Annual Sum or Average | 0.115779E+11 | 0.425008E+10 | 0.732787E+10 | 0.217730E+11 | 0.777988E+10 |
Minimum of Months | 0.733476E+09 | 0.147180E+09 | 0.453785E+09 | 0.779750E+09 | 21908516.35 |
Maximum of Months | 0.132216E+10 | 0.620045E+09 | 0.744938E+09 | 0.304774E+10 | 0.168243E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.758008E+09 | 0.294988E+09 | 0.463020E+09 | 0.821181E+09 | 0.158784E+10 |
February | 0.782918E+09 | 0.288526E+09 | 0.494392E+09 | 0.100119E+10 | 0.117705E+10 |
March | 0.112402E+10 | 0.449311E+09 | 0.674711E+09 | 0.179444E+10 | 0.828341E+09 |
April | 0.132216E+10 | 0.620045E+09 | 0.702120E+09 | 0.261486E+10 | 0.347461E+09 |
May | 0.129370E+10 | 0.548760E+09 | 0.744938E+09 | 0.304774E+10 | 65872261.53 |
June | 0.117593E+10 | 0.456763E+09 | 0.719167E+09 | 0.290906E+10 | 49124849.30 |
July | 0.901687E+09 | 0.175379E+09 | 0.726309E+09 | 0.219310E+10 | 21908516.35 |
August | 0.828105E+09 | 0.147180E+09 | 0.680926E+09 | 0.184041E+10 | 82330708.83 |
September | 0.880940E+09 | 0.258619E+09 | 0.622321E+09 | 0.180236E+10 | 0.140316E+09 |
October | 0.947487E+09 | 0.377288E+09 | 0.570199E+09 | 0.173765E+10 | 0.631906E+09 |
November | 0.829508E+09 | 0.353531E+09 | 0.475977E+09 | 0.123125E+10 | 0.116529E+10 |
December | 0.733476E+09 | 0.279691E+09 | 0.453785E+09 | 0.779750E+09 | 0.168243E+10 |
Annual Sum or Average | 0.115779E+11 | 0.425008E+10 | 0.732787E+10 | 0.217730E+11 | 0.777988E+10 |
Minimum of Months | 0.733476E+09 | 0.147180E+09 | 0.453785E+09 | 0.779750E+09 | 21908516.35 |
Maximum of Months | 0.132216E+10 | 0.620045E+09 | 0.744938E+09 | 0.304774E+10 | 0.168243E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.757994E+09 | 0.294982E+09 | 0.463012E+09 | 0.821166E+09 | 0.158781E+10 |
February | 0.782904E+09 | 0.288521E+09 | 0.494383E+09 | 0.100117E+10 | 0.117703E+10 |
March | 0.112400E+10 | 0.449303E+09 | 0.674698E+09 | 0.179441E+10 | 0.828326E+09 |
April | 0.132214E+10 | 0.620034E+09 | 0.702107E+09 | 0.261481E+10 | 0.347454E+09 |
May | 0.129367E+10 | 0.548750E+09 | 0.744924E+09 | 0.304768E+10 | 65871057.90 |
June | 0.117591E+10 | 0.456755E+09 | 0.719154E+09 | 0.290901E+10 | 49123951.68 |
July | 0.901671E+09 | 0.175375E+09 | 0.726296E+09 | 0.219306E+10 | 21908116.04 |
August | 0.828090E+09 | 0.147177E+09 | 0.680913E+09 | 0.184038E+10 | 82329204.47 |
September | 0.880924E+09 | 0.258614E+09 | 0.622310E+09 | 0.180233E+10 | 0.140314E+09 |
October | 0.947470E+09 | 0.377281E+09 | 0.570189E+09 | 0.173762E+10 | 0.631894E+09 |
November | 0.829493E+09 | 0.353525E+09 | 0.475968E+09 | 0.123123E+10 | 0.116527E+10 |
December | 0.733463E+09 | 0.279686E+09 | 0.453777E+09 | 0.779735E+09 | 0.168240E+10 |
Annual Sum or Average | 0.115777E+11 | 0.425000E+10 | 0.732773E+10 | 0.217726E+11 | 0.777974E+10 |
Minimum of Months | 0.733463E+09 | 0.147177E+09 | 0.453777E+09 | 0.779735E+09 | 21908116.04 |
Maximum of Months | 0.132214E+10 | 0.620034E+09 | 0.744924E+09 | 0.304768E+10 | 0.168240E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162756E+10 | 0.00 | 0.162756E+10 | 0.109560E+10 | 0.584832E+10 |
February | 0.174323E+10 | 0.00 | 0.174323E+10 | 0.177749E+10 | 0.419523E+10 |
March | 0.232567E+10 | 0.00 | 0.232567E+10 | 0.359535E+10 | 0.287505E+10 |
April | 0.244213E+10 | 8282095.40 | 0.243385E+10 | 0.607551E+10 | 0.974795E+09 |
May | 0.279590E+10 | 78458152.52 | 0.271744E+10 | 0.871723E+10 | 0.179127E+09 |
June | 0.280084E+10 | 0.103744E+09 | 0.269710E+10 | 0.914833E+10 | 0.137765E+09 |
July | 0.285434E+10 | 45200277.98 | 0.280914E+10 | 0.836287E+10 | 38829269.35 |
August | 0.262037E+10 | 8166522.05 | 0.261221E+10 | 0.705009E+10 | 0.123614E+09 |
September | 0.225951E+10 | 158657.88 | 0.225935E+10 | 0.530131E+10 | 0.416618E+09 |
October | 0.202271E+10 | 0.00 | 0.202271E+10 | 0.401478E+10 | 0.225240E+10 |
November | 0.165799E+10 | 0.00 | 0.165799E+10 | 0.216813E+10 | 0.407595E+10 |
December | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.121027E+10 | 0.571782E+10 |
Annual Sum or Average | 0.267380E+11 | 0.244009E+09 | 0.264940E+11 | 0.585169E+11 | 0.268355E+11 |
Minimum of Months | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.109560E+10 | 38829269.35 |
Maximum of Months | 0.285434E+10 | 0.103744E+09 | 0.280914E+10 | 0.914833E+10 | 0.584832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232435E+10 | 0.932961E+09 | 0.139139E+10 | 0.242865E+10 | 0.366871E+10 |
February | 0.255052E+10 | 0.105297E+10 | 0.149754E+10 | 0.327104E+10 | 0.270522E+10 |
March | 0.344472E+10 | 0.142186E+10 | 0.202286E+10 | 0.552401E+10 | 0.190344E+10 |
April | 0.396612E+10 | 0.184921E+10 | 0.211691E+10 | 0.805365E+10 | 0.691895E+09 |
May | 0.403388E+10 | 0.178840E+10 | 0.224548E+10 | 0.952175E+10 | 0.123236E+09 |
June | 0.317714E+10 | 0.105417E+10 | 0.212297E+10 | 0.836517E+10 | 93730693.01 |
July | 0.275932E+10 | 0.582694E+09 | 0.217662E+10 | 0.707798E+10 | 22698715.29 |
August | 0.248626E+10 | 0.432667E+09 | 0.205359E+10 | 0.598311E+10 | 84222193.87 |
September | 0.257060E+10 | 0.716876E+09 | 0.185372E+10 | 0.537061E+10 | 0.289678E+09 |
October | 0.290566E+10 | 0.117370E+10 | 0.173197E+10 | 0.533957E+10 | 0.152402E+10 |
November | 0.249319E+10 | 0.107019E+10 | 0.142300E+10 | 0.366394E+10 | 0.265760E+10 |
December | 0.224642E+10 | 0.890044E+09 | 0.135637E+10 | 0.253357E+10 | 0.367257E+10 |
Annual Sum or Average | 0.349582E+11 | 0.129657E+11 | 0.219924E+11 | 0.671331E+11 | 0.174370E+11 |
Minimum of Months | 0.224642E+10 | 0.432667E+09 | 0.135637E+10 | 0.242865E+10 | 22698715.29 |
Maximum of Months | 0.403388E+10 | 0.184921E+10 | 0.224548E+10 | 0.952175E+10 | 0.367257E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.740212E+10 | 0.449772E+10 | 0.290440E+10 | 0.997342E+10 | 0.604961E+10 |
February | 0.635721E+10 | 0.353097E+10 | 0.282624E+10 | 0.932933E+10 | 0.449920E+10 |
March | 0.601795E+10 | 0.265808E+10 | 0.335987E+10 | 0.104067E+11 | 0.316388E+10 |
April | 0.409067E+10 | 0.115451E+10 | 0.293616E+10 | 0.956259E+10 | 0.112546E+10 |
May | 0.303979E+10 | 0.225027E+09 | 0.281476E+10 | 0.930058E+10 | 0.181671E+09 |
June | 0.269093E+10 | 45919963.82 | 0.264501E+10 | 0.893863E+10 | 0.136589E+09 |
July | 0.290046E+10 | 39893433.56 | 0.286057E+10 | 0.849131E+10 | 34836743.03 |
August | 0.307677E+10 | 0.164323E+09 | 0.291245E+10 | 0.795474E+10 | 0.130574E+09 |
September | 0.399161E+10 | 0.103603E+10 | 0.295558E+10 | 0.857564E+10 | 0.503827E+09 |
October | 0.709605E+10 | 0.396241E+10 | 0.313365E+10 | 0.130835E+11 | 0.259877E+10 |
November | 0.857743E+10 | 0.566950E+10 | 0.290793E+10 | 0.137518E+11 | 0.453645E+10 |
December | 0.791031E+10 | 0.495682E+10 | 0.295349E+10 | 0.110867E+11 | 0.607131E+10 |
Annual Sum or Average | 0.631513E+11 | 0.279412E+11 | 0.352101E+11 | 0.120455E+12 | 0.290322E+11 |
Minimum of Months | 0.269093E+10 | 39893433.56 | 0.264501E+10 | 0.795474E+10 | 34836743.03 |
Maximum of Months | 0.857743E+10 | 0.566950E+10 | 0.335987E+10 | 0.137518E+11 | 0.607131E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227400E+10 | 0.884954E+09 | 0.138905E+10 | 0.265210E+10 | 0.411400E+10 |
February | 0.234873E+10 | 0.865571E+09 | 0.148316E+10 | 0.317170E+10 | 0.301162E+10 |
March | 0.337203E+10 | 0.134792E+10 | 0.202411E+10 | 0.551848E+10 | 0.215279E+10 |
April | 0.396645E+10 | 0.186012E+10 | 0.210634E+10 | 0.804864E+10 | 0.824757E+09 |
May | 0.388106E+10 | 0.164626E+10 | 0.223479E+10 | 0.923410E+10 | 0.170877E+09 |
June | 0.352776E+10 | 0.137028E+10 | 0.215748E+10 | 0.890203E+10 | 0.120698E+09 |
July | 0.270503E+10 | 0.526130E+09 | 0.217890E+10 | 0.685850E+10 | 35945764.56 |
August | 0.248429E+10 | 0.441534E+09 | 0.204276E+10 | 0.589894E+10 | 0.107454E+09 |
September | 0.264279E+10 | 0.775849E+09 | 0.186695E+10 | 0.547551E+10 | 0.356971E+09 |
October | 0.284243E+10 | 0.113185E+10 | 0.171058E+10 | 0.531330E+10 | 0.169324E+10 |
November | 0.248850E+10 | 0.106058E+10 | 0.142792E+10 | 0.387734E+10 | 0.296036E+10 |
December | 0.220041E+10 | 0.839065E+09 | 0.136134E+10 | 0.265507E+10 | 0.403004E+10 |
Annual Sum or Average | 0.347335E+11 | 0.127501E+11 | 0.219834E+11 | 0.676057E+11 | 0.195787E+11 |
Minimum of Months | 0.220041E+10 | 0.441534E+09 | 0.136134E+10 | 0.265210E+10 | 35945764.56 |
Maximum of Months | 0.396645E+10 | 0.186012E+10 | 0.223479E+10 | 0.923410E+10 | 0.411400E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162756E+10 | 0.00 | 0.162756E+10 | 0.122401E+10 | 0.532124E+10 |
February | 0.174323E+10 | 0.00 | 0.174323E+10 | 0.186768E+10 | 0.390297E+10 |
March | 0.232567E+10 | 0.00 | 0.232567E+10 | 0.360088E+10 | 0.276072E+10 |
April | 0.244213E+10 | 8282095.40 | 0.243385E+10 | 0.599680E+10 | 0.970051E+09 |
May | 0.279590E+10 | 78458152.52 | 0.271744E+10 | 0.859478E+10 | 0.191127E+09 |
June | 0.280084E+10 | 0.103744E+09 | 0.269710E+10 | 0.902242E+10 | 0.144029E+09 |
July | 0.285434E+10 | 45200277.98 | 0.280914E+10 | 0.822067E+10 | 40292424.74 |
August | 0.262037E+10 | 8166522.05 | 0.261221E+10 | 0.693724E+10 | 0.131152E+09 |
September | 0.225951E+10 | 158657.88 | 0.225935E+10 | 0.523164E+10 | 0.428056E+09 |
October | 0.202271E+10 | 0.00 | 0.202271E+10 | 0.399662E+10 | 0.218487E+10 |
November | 0.165799E+10 | 0.00 | 0.165799E+10 | 0.225526E+10 | 0.380734E+10 |
December | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.136376E+10 | 0.521761E+10 |
Annual Sum or Average | 0.267380E+11 | 0.244009E+09 | 0.264940E+11 | 0.583118E+11 | 0.250995E+11 |
Minimum of Months | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.122401E+10 | 40292424.74 |
Maximum of Months | 0.285434E+10 | 0.103744E+09 | 0.280914E+10 | 0.902242E+10 | 0.532124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232435E+10 | 0.932961E+09 | 0.139139E+10 | 0.256497E+10 | 0.336090E+10 |
February | 0.255052E+10 | 0.105297E+10 | 0.149754E+10 | 0.333668E+10 | 0.255237E+10 |
March | 0.344472E+10 | 0.142186E+10 | 0.202286E+10 | 0.551658E+10 | 0.185331E+10 |
April | 0.396612E+10 | 0.184921E+10 | 0.211691E+10 | 0.799120E+10 | 0.696296E+09 |
May | 0.403388E+10 | 0.178840E+10 | 0.224548E+10 | 0.942695E+10 | 0.134418E+09 |
June | 0.317714E+10 | 0.105417E+10 | 0.212297E+10 | 0.827014E+10 | 99287164.84 |
July | 0.275932E+10 | 0.582694E+09 | 0.217662E+10 | 0.697235E+10 | 23636277.11 |
August | 0.248626E+10 | 0.432667E+09 | 0.205359E+10 | 0.589989E+10 | 90039609.23 |
September | 0.257060E+10 | 0.716876E+09 | 0.185372E+10 | 0.531794E+10 | 0.301224E+09 |
October | 0.290566E+10 | 0.117370E+10 | 0.173197E+10 | 0.532246E+10 | 0.149425E+10 |
November | 0.249319E+10 | 0.107019E+10 | 0.142300E+10 | 0.371698E+10 | 0.252467E+10 |
December | 0.224642E+10 | 0.890044E+09 | 0.135637E+10 | 0.267181E+10 | 0.339224E+10 |
Annual Sum or Average | 0.349582E+11 | 0.129657E+11 | 0.219924E+11 | 0.670080E+11 | 0.165226E+11 |
Minimum of Months | 0.224642E+10 | 0.432667E+09 | 0.135637E+10 | 0.256497E+10 | 23636277.11 |
Maximum of Months | 0.403388E+10 | 0.184921E+10 | 0.224548E+10 | 0.942695E+10 | 0.339224E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.740212E+10 | 0.449772E+10 | 0.290440E+10 | 0.101326E+11 | 0.555802E+10 |
February | 0.635721E+10 | 0.353097E+10 | 0.282624E+10 | 0.939110E+10 | 0.424491E+10 |
March | 0.601795E+10 | 0.265808E+10 | 0.335987E+10 | 0.103807E+11 | 0.306759E+10 |
April | 0.409067E+10 | 0.115451E+10 | 0.293616E+10 | 0.947588E+10 | 0.112144E+10 |
May | 0.303979E+10 | 0.225027E+09 | 0.281476E+10 | 0.917842E+10 | 0.193359E+09 |
June | 0.269093E+10 | 45919963.82 | 0.264501E+10 | 0.881184E+10 | 0.143643E+09 |
July | 0.290046E+10 | 39893433.56 | 0.286057E+10 | 0.834836E+10 | 35875567.13 |
August | 0.307677E+10 | 0.164323E+09 | 0.291245E+10 | 0.784106E+10 | 0.138446E+09 |
September | 0.399161E+10 | 0.103603E+10 | 0.295558E+10 | 0.849889E+10 | 0.517011E+09 |
October | 0.709605E+10 | 0.396241E+10 | 0.313365E+10 | 0.130437E+11 | 0.254184E+10 |
November | 0.857743E+10 | 0.566950E+10 | 0.290793E+10 | 0.137838E+11 | 0.432661E+10 |
December | 0.791031E+10 | 0.495682E+10 | 0.295349E+10 | 0.112382E+11 | 0.564664E+10 |
Annual Sum or Average | 0.631513E+11 | 0.279412E+11 | 0.352101E+11 | 0.120124E+12 | 0.275354E+11 |
Minimum of Months | 0.269093E+10 | 39893433.56 | 0.264501E+10 | 0.784106E+10 | 35875567.13 |
Maximum of Months | 0.857743E+10 | 0.566950E+10 | 0.335987E+10 | 0.137838E+11 | 0.564664E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227400E+10 | 0.884954E+09 | 0.138905E+10 | 0.271292E+10 | 0.380868E+10 |
February | 0.234873E+10 | 0.865571E+09 | 0.148316E+10 | 0.320348E+10 | 0.284782E+10 |
March | 0.337203E+10 | 0.134792E+10 | 0.202411E+10 | 0.550348E+10 | 0.208612E+10 |
April | 0.396645E+10 | 0.186012E+10 | 0.210634E+10 | 0.799080E+10 | 0.819798E+09 |
May | 0.388106E+10 | 0.164626E+10 | 0.223479E+10 | 0.915675E+10 | 0.178285E+09 |
June | 0.352776E+10 | 0.137028E+10 | 0.215748E+10 | 0.882160E+10 | 0.123523E+09 |
July | 0.270503E+10 | 0.526130E+09 | 0.217890E+10 | 0.677151E+10 | 36912117.39 |
August | 0.248429E+10 | 0.441534E+09 | 0.204276E+10 | 0.583139E+10 | 0.112298E+09 |
September | 0.264279E+10 | 0.775849E+09 | 0.186695E+10 | 0.543027E+10 | 0.363558E+09 |
October | 0.284243E+10 | 0.113185E+10 | 0.171058E+10 | 0.529325E+10 | 0.165056E+10 |
November | 0.248850E+10 | 0.106058E+10 | 0.142792E+10 | 0.390912E+10 | 0.281070E+10 |
December | 0.220041E+10 | 0.839065E+09 | 0.136134E+10 | 0.272626E+10 | 0.375473E+10 |
Annual Sum or Average | 0.347335E+11 | 0.127501E+11 | 0.219834E+11 | 0.673508E+11 | 0.185930E+11 |
Minimum of Months | 0.220041E+10 | 0.441534E+09 | 0.136134E+10 | 0.271292E+10 | 36912117.39 |
Maximum of Months | 0.396645E+10 | 0.186012E+10 | 0.223479E+10 | 0.915675E+10 | 0.380868E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.08 | 2527.97 | 607.66 | 0.00 | 607.66 | 0.00 | 0.00 |
February | 650.50 | 1958.61 | 720.59 | 0.00 | 720.59 | 0.00 | 0.00 |
March | 1299.79 | 1150.34 | 868.31 | 0.00 | 868.31 | 0.00 | 0.00 |
April | 2285.75 | 392.97 | 942.18 | 3.20 | 938.99 | 0.00 | 0.00 |
May | 3225.33 | 65.16 | 1043.87 | 29.29 | 1014.58 | 0.00 | 0.00 |
June | 3498.63 | 49.15 | 1080.57 | 40.02 | 1040.55 | 0.00 | 0.00 |
July | 3089.18 | 11.21 | 1065.69 | 16.88 | 1048.82 | 0.00 | 0.00 |
August | 2574.51 | 43.13 | 978.34 | 3.05 | 975.29 | 0.00 | 0.00 |
September | 2028.64 | 160.27 | 871.73 | 0.06 | 871.67 | 0.00 | 0.00 |
October | 1461.39 | 881.03 | 755.20 | 0.00 | 755.20 | 0.00 | 0.00 |
November | 762.70 | 1752.33 | 639.66 | 0.00 | 639.66 | 0.00 | 0.00 |
December | 334.25 | 2502.80 | 592.79 | 0.00 | 592.79 | 0.00 | 0.00 |
Annual Sum or Average | 1798.86 | 953.74 | 847.86 | 7.74 | 840.12 | 0.00 | 0.00 |
Minimum of Months | 309.08 | 11.21 | 592.79 | 0.00 | 592.79 | 0.00 | 0.00 |
Maximum of Months | 3498.63 | 2527.97 | 1080.57 | 40.02 | 1048.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 843.69 | 1531.19 | 867.82 | 348.33 | 519.49 | 0.00 | 0.00 |
February | 1328.61 | 1199.30 | 1054.29 | 435.26 | 619.03 | 0.00 | 0.00 |
March | 2071.10 | 712.17 | 1286.12 | 530.86 | 755.25 | 0.00 | 0.00 |
April | 3126.62 | 243.02 | 1530.15 | 713.43 | 816.71 | 0.00 | 0.00 |
May | 3573.44 | 41.08 | 1506.08 | 667.72 | 838.37 | 0.00 | 0.00 |
June | 3245.60 | 28.77 | 1225.75 | 406.70 | 819.05 | 0.00 | 0.00 |
July | 2664.83 | 4.45 | 1030.21 | 217.55 | 812.66 | 0.00 | 0.00 |
August | 2254.19 | 18.03 | 928.27 | 161.54 | 766.73 | 0.00 | 0.00 |
September | 2084.91 | 98.48 | 991.75 | 276.57 | 715.17 | 0.00 | 0.00 |
October | 1999.82 | 562.52 | 1084.85 | 438.21 | 646.64 | 0.00 | 0.00 |
November | 1397.03 | 1077.71 | 961.88 | 412.88 | 549.00 | 0.00 | 0.00 |
December | 889.59 | 1506.91 | 838.72 | 332.31 | 506.41 | 0.00 | 0.00 |
Annual Sum or Average | 2126.09 | 582.70 | 1108.52 | 411.14 | 697.38 | 0.00 | 0.00 |
Minimum of Months | 843.69 | 4.45 | 838.72 | 161.54 | 506.41 | 0.00 | 0.00 |
Maximum of Months | 3573.44 | 1531.19 | 1530.15 | 713.43 | 838.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3730.35 | 2346.59 | 2763.65 | 1679.26 | 1084.38 | 0.00 | 0.00 |
February | 3874.64 | 1919.54 | 2627.82 | 1459.57 | 1168.26 | 0.00 | 0.00 |
March | 3901.90 | 1193.88 | 2246.85 | 992.42 | 1254.44 | 0.00 | 0.00 |
April | 3675.56 | 431.81 | 1578.20 | 445.42 | 1132.78 | 0.00 | 0.00 |
May | 3449.63 | 66.34 | 1134.93 | 84.02 | 1050.92 | 0.00 | 0.00 |
June | 3418.11 | 48.96 | 1038.17 | 17.72 | 1020.45 | 0.00 | 0.00 |
July | 3137.97 | 10.34 | 1082.91 | 14.89 | 1068.02 | 0.00 | 0.00 |
August | 2927.81 | 44.70 | 1148.74 | 61.35 | 1087.39 | 0.00 | 0.00 |
September | 3319.40 | 183.32 | 1539.98 | 399.70 | 1140.27 | 0.00 | 0.00 |
October | 4910.09 | 956.59 | 2649.37 | 1479.40 | 1169.97 | 0.00 | 0.00 |
November | 5330.67 | 1780.40 | 3309.21 | 2187.31 | 1121.89 | 0.00 | 0.00 |
December | 4133.54 | 2366.31 | 2953.38 | 1850.67 | 1102.71 | 0.00 | 0.00 |
Annual Sum or Average | 3815.70 | 941.39 | 2002.52 | 886.01 | 1116.51 | 0.00 | 0.00 |
Minimum of Months | 2927.81 | 10.34 | 1038.17 | 14.89 | 1020.45 | 0.00 | 0.00 |
Maximum of Months | 5330.67 | 2366.31 | 3309.21 | 2187.31 | 1254.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 919.78 | 1778.49 | 849.02 | 330.41 | 518.61 | 0.00 | 0.00 |
February | 1241.54 | 1459.63 | 970.87 | 357.79 | 613.08 | 0.00 | 0.00 |
March | 2009.89 | 927.80 | 1258.98 | 503.26 | 755.72 | 0.00 | 0.00 |
April | 3026.44 | 402.15 | 1530.27 | 717.64 | 812.63 | 0.00 | 0.00 |
May | 3413.67 | 73.78 | 1449.03 | 614.65 | 834.38 | 0.00 | 0.00 |
June | 3366.95 | 56.86 | 1361.02 | 528.66 | 832.36 | 0.00 | 0.00 |
July | 2456.42 | 24.54 | 1009.95 | 196.44 | 813.51 | 0.00 | 0.00 |
August | 2061.38 | 92.22 | 927.53 | 164.85 | 762.68 | 0.00 | 0.00 |
September | 2086.05 | 162.40 | 1019.60 | 299.33 | 720.27 | 0.00 | 0.00 |
October | 1946.28 | 707.78 | 1061.25 | 422.59 | 638.66 | 0.00 | 0.00 |
November | 1425.05 | 1348.71 | 960.07 | 409.18 | 550.90 | 0.00 | 0.00 |
December | 873.37 | 1884.44 | 821.54 | 313.27 | 508.27 | 0.00 | 0.00 |
Annual Sum or Average | 2071.24 | 740.09 | 1101.40 | 404.31 | 697.09 | 0.00 | 0.00 |
Minimum of Months | 873.37 | 24.54 | 821.54 | 164.85 | 508.27 | 0.00 | 0.00 |
Maximum of Months | 3413.67 | 1884.44 | 1530.27 | 717.64 | 834.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.05 | 2183.51 | 607.66 | 0.00 | 607.66 | 0.00 | 0.00 |
February | 734.74 | 1734.14 | 720.58 | 0.00 | 720.58 | 0.00 | 0.00 |
March | 1342.35 | 1073.42 | 868.31 | 0.00 | 868.31 | 0.00 | 0.00 |
April | 2343.95 | 376.08 | 942.18 | 3.20 | 938.99 | 0.00 | 0.00 |
May | 3254.64 | 66.88 | 1043.87 | 29.29 | 1014.58 | 0.00 | 0.00 |
June | 3529.45 | 53.15 | 1080.57 | 40.02 | 1040.55 | 0.00 | 0.00 |
July | 3122.34 | 14.50 | 1065.69 | 16.88 | 1048.81 | 0.00 | 0.00 |
August | 2632.20 | 46.15 | 978.33 | 3.05 | 975.29 | 0.00 | 0.00 |
September | 2045.26 | 160.73 | 871.72 | 0.06 | 871.66 | 0.00 | 0.00 |
October | 1498.95 | 840.95 | 755.19 | 0.00 | 755.19 | 0.00 | 0.00 |
November | 836.47 | 1572.51 | 639.66 | 0.00 | 639.66 | 0.00 | 0.00 |
December | 451.86 | 2134.79 | 592.78 | 0.00 | 592.78 | 0.00 | 0.00 |
Annual Sum or Average | 1855.56 | 850.95 | 847.86 | 7.74 | 840.12 | 0.00 | 0.00 |
Minimum of Months | 409.05 | 14.50 | 592.78 | 0.00 | 592.78 | 0.00 | 0.00 |
Maximum of Months | 3529.45 | 2183.51 | 1080.57 | 40.02 | 1048.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 906.75 | 1369.74 | 867.81 | 348.33 | 519.48 | 0.00 | 0.00 |
February | 1352.12 | 1118.23 | 1054.28 | 435.26 | 619.02 | 0.00 | 0.00 |
March | 2062.43 | 710.66 | 1286.11 | 530.86 | 755.25 | 0.00 | 0.00 |
April | 3107.12 | 266.93 | 1530.14 | 713.43 | 816.71 | 0.00 | 0.00 |
May | 3555.02 | 46.01 | 1506.08 | 667.71 | 838.36 | 0.00 | 0.00 |
June | 3227.30 | 36.16 | 1225.75 | 406.70 | 819.05 | 0.00 | 0.00 |
July | 2642.61 | 8.47 | 1030.21 | 217.55 | 812.66 | 0.00 | 0.00 |
August | 2233.84 | 31.44 | 928.26 | 161.54 | 766.72 | 0.00 | 0.00 |
September | 2072.00 | 111.76 | 991.74 | 276.57 | 715.17 | 0.00 | 0.00 |
October | 1993.57 | 569.01 | 1084.85 | 438.21 | 646.64 | 0.00 | 0.00 |
November | 1413.56 | 1025.31 | 961.88 | 412.88 | 549.00 | 0.00 | 0.00 |
December | 945.93 | 1371.18 | 838.72 | 332.30 | 506.41 | 0.00 | 0.00 |
Annual Sum or Average | 2128.78 | 552.92 | 1108.52 | 411.14 | 697.38 | 0.00 | 0.00 |
Minimum of Months | 906.75 | 8.47 | 838.72 | 161.54 | 506.41 | 0.00 | 0.00 |
Maximum of Months | 3555.02 | 1371.18 | 1530.14 | 713.43 | 838.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3723.65 | 2258.67 | 2763.64 | 1679.26 | 1084.38 | 0.00 | 0.00 |
February | 3856.37 | 1859.79 | 2627.81 | 1459.56 | 1168.25 | 0.00 | 0.00 |
March | 3885.42 | 1181.26 | 2246.85 | 992.41 | 1254.43 | 0.00 | 0.00 |
April | 3689.27 | 434.20 | 1578.19 | 445.41 | 1132.78 | 0.00 | 0.00 |
May | 3472.44 | 67.83 | 1134.93 | 84.02 | 1050.91 | 0.00 | 0.00 |
June | 3448.54 | 52.70 | 1038.17 | 17.72 | 1020.45 | 0.00 | 0.00 |
July | 3170.29 | 13.01 | 1082.91 | 14.89 | 1068.01 | 0.00 | 0.00 |
August | 2969.96 | 48.75 | 1148.74 | 61.35 | 1087.38 | 0.00 | 0.00 |
September | 3308.50 | 194.38 | 1539.97 | 399.70 | 1140.27 | 0.00 | 0.00 |
October | 4884.82 | 970.27 | 2649.36 | 1479.39 | 1169.97 | 0.00 | 0.00 |
November | 5305.47 | 1750.17 | 3309.19 | 2187.31 | 1121.89 | 0.00 | 0.00 |
December | 4139.28 | 2266.77 | 2953.37 | 1850.66 | 1102.71 | 0.00 | 0.00 |
Annual Sum or Average | 3819.60 | 920.60 | 2002.51 | 886.01 | 1116.51 | 0.00 | 0.00 |
Minimum of Months | 2969.96 | 13.01 | 1038.17 | 14.89 | 1020.45 | 0.00 | 0.00 |
Maximum of Months | 5305.47 | 2266.77 | 3309.19 | 2187.31 | 1254.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 990.18 | 1535.99 | 849.01 | 330.40 | 518.61 | 0.00 | 0.00 |
February | 1311.05 | 1244.88 | 970.87 | 357.79 | 613.08 | 0.00 | 0.00 |
March | 2060.36 | 803.76 | 1258.97 | 503.26 | 755.72 | 0.00 | 0.00 |
April | 3105.19 | 318.19 | 1530.27 | 717.64 | 812.63 | 0.00 | 0.00 |
May | 3447.62 | 63.80 | 1449.02 | 614.64 | 834.38 | 0.00 | 0.00 |
June | 3434.43 | 46.57 | 1361.02 | 528.66 | 832.36 | 0.00 | 0.00 |
July | 2560.67 | 13.42 | 1009.94 | 196.43 | 813.51 | 0.00 | 0.00 |
August | 2202.41 | 40.12 | 927.53 | 164.85 | 762.68 | 0.00 | 0.00 |
September | 2112.46 | 137.72 | 1019.60 | 299.32 | 720.27 | 0.00 | 0.00 |
October | 1983.76 | 632.18 | 1061.24 | 422.59 | 638.66 | 0.00 | 0.00 |
November | 1495.89 | 1142.12 | 960.07 | 409.18 | 550.89 | 0.00 | 0.00 |
December | 991.29 | 1504.64 | 821.54 | 313.27 | 508.27 | 0.00 | 0.00 |
Annual Sum or Average | 2143.76 | 620.84 | 1101.39 | 404.30 | 697.09 | 0.00 | 0.00 |
Minimum of Months | 990.18 | 13.42 | 821.54 | 164.85 | 508.27 | 0.00 | 0.00 |
Maximum of Months | 3447.62 | 1535.99 | 1530.27 | 717.64 | 834.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.99 | 1986.72 | 607.66 | 0.00 | 607.66 | 0.00 | 0.00 |
February | 772.02 | 1613.33 | 720.58 | 0.00 | 720.58 | 0.00 | 0.00 |
March | 1344.41 | 1030.73 | 868.31 | 0.00 | 868.31 | 0.00 | 0.00 |
April | 2313.58 | 374.25 | 942.18 | 3.20 | 938.99 | 0.00 | 0.00 |
May | 3208.92 | 71.36 | 1043.87 | 29.29 | 1014.58 | 0.00 | 0.00 |
June | 3480.87 | 55.57 | 1080.57 | 40.02 | 1040.55 | 0.00 | 0.00 |
July | 3069.24 | 15.04 | 1065.69 | 16.88 | 1048.81 | 0.00 | 0.00 |
August | 2590.07 | 48.97 | 978.33 | 3.05 | 975.29 | 0.00 | 0.00 |
September | 2018.38 | 165.15 | 871.72 | 0.06 | 871.66 | 0.00 | 0.00 |
October | 1492.17 | 815.74 | 755.19 | 0.00 | 755.19 | 0.00 | 0.00 |
November | 870.08 | 1468.88 | 639.66 | 0.00 | 639.66 | 0.00 | 0.00 |
December | 509.17 | 1948.03 | 592.78 | 0.00 | 592.78 | 0.00 | 0.00 |
Annual Sum or Average | 1849.05 | 795.90 | 847.86 | 7.74 | 840.12 | 0.00 | 0.00 |
Minimum of Months | 456.99 | 15.04 | 592.78 | 0.00 | 592.78 | 0.00 | 0.00 |
Maximum of Months | 3480.87 | 1986.72 | 1080.57 | 40.02 | 1048.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 957.65 | 1254.82 | 867.81 | 348.33 | 519.48 | 0.00 | 0.00 |
February | 1379.25 | 1055.05 | 1054.28 | 435.26 | 619.02 | 0.00 | 0.00 |
March | 2059.65 | 691.95 | 1286.11 | 530.86 | 755.25 | 0.00 | 0.00 |
April | 3083.03 | 268.63 | 1530.14 | 713.43 | 816.71 | 0.00 | 0.00 |
May | 3519.62 | 50.19 | 1506.08 | 667.71 | 838.36 | 0.00 | 0.00 |
June | 3190.64 | 38.31 | 1225.75 | 406.70 | 819.05 | 0.00 | 0.00 |
July | 2603.18 | 8.82 | 1030.21 | 217.55 | 812.66 | 0.00 | 0.00 |
August | 2202.77 | 33.62 | 928.26 | 161.54 | 766.72 | 0.00 | 0.00 |
September | 2051.68 | 116.21 | 991.74 | 276.57 | 715.17 | 0.00 | 0.00 |
October | 1987.18 | 557.89 | 1084.85 | 438.21 | 646.64 | 0.00 | 0.00 |
November | 1434.02 | 974.02 | 961.88 | 412.88 | 549.00 | 0.00 | 0.00 |
December | 997.54 | 1266.52 | 838.72 | 332.30 | 506.41 | 0.00 | 0.00 |
Annual Sum or Average | 2124.81 | 523.93 | 1108.52 | 411.14 | 697.38 | 0.00 | 0.00 |
Minimum of Months | 957.65 | 8.82 | 838.72 | 161.54 | 506.41 | 0.00 | 0.00 |
Maximum of Months | 3519.62 | 1266.52 | 1530.14 | 713.43 | 838.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3783.08 | 2075.13 | 2763.64 | 1679.26 | 1084.38 | 0.00 | 0.00 |
February | 3881.90 | 1754.67 | 2627.81 | 1459.56 | 1168.25 | 0.00 | 0.00 |
March | 3875.69 | 1145.31 | 2246.85 | 992.41 | 1254.43 | 0.00 | 0.00 |
April | 3655.82 | 432.65 | 1578.19 | 445.41 | 1132.78 | 0.00 | 0.00 |
May | 3426.83 | 72.19 | 1134.93 | 84.02 | 1050.91 | 0.00 | 0.00 |
June | 3399.63 | 55.42 | 1038.17 | 17.72 | 1020.45 | 0.00 | 0.00 |
July | 3116.92 | 13.39 | 1082.91 | 14.89 | 1068.01 | 0.00 | 0.00 |
August | 2927.52 | 51.69 | 1148.74 | 61.35 | 1087.38 | 0.00 | 0.00 |
September | 3278.89 | 199.46 | 1539.97 | 399.70 | 1140.27 | 0.00 | 0.00 |
October | 4869.94 | 949.01 | 2649.36 | 1479.39 | 1169.97 | 0.00 | 0.00 |
November | 5317.84 | 1669.22 | 3309.19 | 2187.31 | 1121.89 | 0.00 | 0.00 |
December | 4195.85 | 2108.21 | 2953.37 | 1850.66 | 1102.71 | 0.00 | 0.00 |
Annual Sum or Average | 3809.12 | 873.14 | 2002.51 | 886.01 | 1116.51 | 0.00 | 0.00 |
Minimum of Months | 2927.52 | 13.39 | 1038.17 | 14.89 | 1020.45 | 0.00 | 0.00 |
Maximum of Months | 5317.84 | 2108.21 | 3309.19 | 2187.31 | 1254.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1012.89 | 1422.00 | 849.01 | 330.40 | 518.61 | 0.00 | 0.00 |
February | 1324.19 | 1177.17 | 970.87 | 357.79 | 613.08 | 0.00 | 0.00 |
March | 2054.76 | 778.87 | 1258.97 | 503.26 | 755.72 | 0.00 | 0.00 |
April | 3082.87 | 316.28 | 1530.27 | 717.64 | 812.63 | 0.00 | 0.00 |
May | 3418.74 | 66.56 | 1449.02 | 614.64 | 834.38 | 0.00 | 0.00 |
June | 3403.39 | 47.66 | 1361.02 | 528.66 | 832.36 | 0.00 | 0.00 |
July | 2528.19 | 13.78 | 1009.94 | 196.43 | 813.51 | 0.00 | 0.00 |
August | 2177.19 | 41.93 | 927.53 | 164.85 | 762.68 | 0.00 | 0.00 |
September | 2095.01 | 140.26 | 1019.60 | 299.32 | 720.27 | 0.00 | 0.00 |
October | 1976.27 | 616.25 | 1061.24 | 422.59 | 638.66 | 0.00 | 0.00 |
November | 1508.15 | 1084.38 | 960.07 | 409.18 | 550.89 | 0.00 | 0.00 |
December | 1017.87 | 1401.85 | 821.54 | 313.27 | 508.27 | 0.00 | 0.00 |
Annual Sum or Average | 2135.68 | 589.58 | 1101.39 | 404.30 | 697.09 | 0.00 | 0.00 |
Minimum of Months | 1012.89 | 13.78 | 821.54 | 164.85 | 508.27 | 0.00 | 0.00 |
Maximum of Months | 3418.74 | 1422.00 | 1530.27 | 717.64 | 834.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.827847E+09 | 0.677091E+10 | 0.162757E+10 | 0.00 | 0.162757E+10 | 0.00 | 0.00 |
February | 0.157368E+10 | 0.473828E+10 | 0.174324E+10 | 0.00 | 0.174324E+10 | 0.00 | 0.00 |
March | 0.348136E+10 | 0.308108E+10 | 0.232568E+10 | 0.00 | 0.232568E+10 | 0.00 | 0.00 |
April | 0.592465E+10 | 0.101858E+10 | 0.244214E+10 | 8282124.81 | 0.243386E+10 | 0.00 | 0.00 |
May | 0.863873E+10 | 0.174536E+09 | 0.279591E+10 | 78458431.13 | 0.271745E+10 | 0.00 | 0.00 |
June | 0.906844E+10 | 0.127396E+09 | 0.280085E+10 | 0.103744E+09 | 0.269711E+10 | 0.00 | 0.00 |
July | 0.827405E+10 | 30029416.26 | 0.285436E+10 | 45200438.49 | 0.280915E+10 | 0.00 | 0.00 |
August | 0.689556E+10 | 0.115520E+09 | 0.262038E+10 | 8166551.05 | 0.261221E+10 | 0.00 | 0.00 |
September | 0.525823E+10 | 0.415428E+09 | 0.225952E+10 | 158658.44 | 0.225936E+10 | 0.00 | 0.00 |
October | 0.391418E+10 | 0.235974E+10 | 0.202272E+10 | 0.00 | 0.202272E+10 | 0.00 | 0.00 |
November | 0.197693E+10 | 0.454203E+10 | 0.165800E+10 | 0.00 | 0.165800E+10 | 0.00 | 0.00 |
December | 0.895263E+09 | 0.670351E+10 | 0.158772E+10 | 0.00 | 0.158772E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567289E+11 | 0.300770E+11 | 0.267381E+11 | 0.244010E+09 | 0.264941E+11 | 0.00 | 0.00 |
Minimum of Months | 0.827847E+09 | 30029416.26 | 0.158772E+10 | 0.00 | 0.158772E+10 | 0.00 | 0.00 |
Maximum of Months | 0.906844E+10 | 0.677091E+10 | 0.285436E+10 | 0.103744E+09 | 0.280915E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.225974E+10 | 0.410114E+10 | 0.232436E+10 | 0.932965E+09 | 0.139139E+10 | 0.00 | 0.00 |
February | 0.321418E+10 | 0.290134E+10 | 0.255053E+10 | 0.105298E+10 | 0.149755E+10 | 0.00 | 0.00 |
March | 0.554724E+10 | 0.190747E+10 | 0.344474E+10 | 0.142187E+10 | 0.202287E+10 | 0.00 | 0.00 |
April | 0.810419E+10 | 0.629903E+09 | 0.396614E+10 | 0.184922E+10 | 0.211692E+10 | 0.00 | 0.00 |
May | 0.957110E+10 | 0.110029E+09 | 0.403390E+10 | 0.178841E+10 | 0.224549E+10 | 0.00 | 0.00 |
June | 0.841259E+10 | 74560642.21 | 0.317716E+10 | 0.105418E+10 | 0.212298E+10 | 0.00 | 0.00 |
July | 0.713747E+10 | 11930964.56 | 0.275933E+10 | 0.582696E+09 | 0.217663E+10 | 0.00 | 0.00 |
August | 0.603762E+10 | 48297982.94 | 0.248627E+10 | 0.432669E+09 | 0.205360E+10 | 0.00 | 0.00 |
September | 0.540408E+10 | 0.255261E+09 | 0.257061E+10 | 0.716879E+09 | 0.185373E+10 | 0.00 | 0.00 |
October | 0.535631E+10 | 0.150665E+10 | 0.290567E+10 | 0.117370E+10 | 0.173197E+10 | 0.00 | 0.00 |
November | 0.362109E+10 | 0.279342E+10 | 0.249320E+10 | 0.107019E+10 | 0.142300E+10 | 0.00 | 0.00 |
December | 0.238267E+10 | 0.403612E+10 | 0.224643E+10 | 0.890047E+09 | 0.135638E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670483E+11 | 0.183761E+11 | 0.349583E+11 | 0.129658E+11 | 0.219925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225974E+10 | 11930964.56 | 0.224643E+10 | 0.432669E+09 | 0.135638E+10 | 0.00 | 0.00 |
Maximum of Months | 0.957110E+10 | 0.410114E+10 | 0.403390E+10 | 0.184922E+10 | 0.224549E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999138E+10 | 0.628510E+10 | 0.740215E+10 | 0.449773E+10 | 0.290441E+10 | 0.00 | 0.00 |
February | 0.937352E+10 | 0.464374E+10 | 0.635723E+10 | 0.353099E+10 | 0.282625E+10 | 0.00 | 0.00 |
March | 0.104508E+11 | 0.319770E+10 | 0.601797E+10 | 0.265809E+10 | 0.335988E+10 | 0.00 | 0.00 |
April | 0.952706E+10 | 0.111924E+10 | 0.409069E+10 | 0.115452E+10 | 0.293617E+10 | 0.00 | 0.00 |
May | 0.923950E+10 | 0.177679E+09 | 0.303980E+10 | 0.225028E+09 | 0.281478E+10 | 0.00 | 0.00 |
June | 0.885974E+10 | 0.126917E+09 | 0.269094E+10 | 45920126.88 | 0.264502E+10 | 0.00 | 0.00 |
July | 0.840473E+10 | 27702500.46 | 0.290047E+10 | 39893575.22 | 0.286058E+10 | 0.00 | 0.00 |
August | 0.784184E+10 | 0.119718E+09 | 0.307678E+10 | 0.164323E+09 | 0.291246E+10 | 0.00 | 0.00 |
September | 0.860389E+10 | 0.475168E+09 | 0.399162E+10 | 0.103603E+10 | 0.295559E+10 | 0.00 | 0.00 |
October | 0.131512E+11 | 0.256212E+10 | 0.709608E+10 | 0.396242E+10 | 0.313366E+10 | 0.00 | 0.00 |
November | 0.138171E+11 | 0.461480E+10 | 0.857746E+10 | 0.566952E+10 | 0.290794E+10 | 0.00 | 0.00 |
December | 0.110713E+11 | 0.633791E+10 | 0.791034E+10 | 0.495684E+10 | 0.295350E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120332E+12 | 0.296878E+11 | 0.631515E+11 | 0.279413E+11 | 0.352102E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784184E+10 | 27702500.46 | 0.269094E+10 | 39893575.22 | 0.264502E+10 | 0.00 | 0.00 |
Maximum of Months | 0.138171E+11 | 0.633791E+10 | 0.857746E+10 | 0.566952E+10 | 0.335988E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246353E+10 | 0.476350E+10 | 0.227401E+10 | 0.884958E+09 | 0.138905E+10 | 0.00 | 0.00 |
February | 0.300354E+10 | 0.353113E+10 | 0.234874E+10 | 0.865574E+09 | 0.148317E+10 | 0.00 | 0.00 |
March | 0.538329E+10 | 0.248501E+10 | 0.337204E+10 | 0.134792E+10 | 0.202412E+10 | 0.00 | 0.00 |
April | 0.784453E+10 | 0.104238E+10 | 0.396647E+10 | 0.186012E+10 | 0.210635E+10 | 0.00 | 0.00 |
May | 0.914316E+10 | 0.197616E+09 | 0.388107E+10 | 0.164627E+10 | 0.223480E+10 | 0.00 | 0.00 |
June | 0.872713E+10 | 0.147374E+09 | 0.352777E+10 | 0.137028E+10 | 0.215749E+10 | 0.00 | 0.00 |
July | 0.657927E+10 | 65725148.74 | 0.270505E+10 | 0.526133E+09 | 0.217891E+10 | 0.00 | 0.00 |
August | 0.552120E+10 | 0.246991E+09 | 0.248430E+10 | 0.441536E+09 | 0.204276E+10 | 0.00 | 0.00 |
September | 0.540704E+10 | 0.420947E+09 | 0.264281E+10 | 0.775852E+09 | 0.186695E+10 | 0.00 | 0.00 |
October | 0.521292E+10 | 0.189571E+10 | 0.284244E+10 | 0.113186E+10 | 0.171059E+10 | 0.00 | 0.00 |
November | 0.369372E+10 | 0.349585E+10 | 0.248851E+10 | 0.106059E+10 | 0.142792E+10 | 0.00 | 0.00 |
December | 0.233923E+10 | 0.504727E+10 | 0.220042E+10 | 0.839068E+09 | 0.136135E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.653186E+11 | 0.233395E+11 | 0.347336E+11 | 0.127502E+11 | 0.219835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233923E+10 | 65725148.74 | 0.220042E+10 | 0.441536E+09 | 0.136135E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914316E+10 | 0.504727E+10 | 0.396647E+10 | 0.186012E+10 | 0.223480E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109560E+10 | 0.584832E+10 | 0.162756E+10 | 0.00 | 0.162756E+10 | 0.00 | 0.00 |
February | 0.177749E+10 | 0.419523E+10 | 0.174323E+10 | 0.00 | 0.174323E+10 | 0.00 | 0.00 |
March | 0.359535E+10 | 0.287505E+10 | 0.232567E+10 | 0.00 | 0.232567E+10 | 0.00 | 0.00 |
April | 0.607551E+10 | 0.974795E+09 | 0.244213E+10 | 8282095.40 | 0.243385E+10 | 0.00 | 0.00 |
May | 0.871723E+10 | 0.179127E+09 | 0.279590E+10 | 78458152.52 | 0.271744E+10 | 0.00 | 0.00 |
June | 0.914833E+10 | 0.137765E+09 | 0.280084E+10 | 0.103744E+09 | 0.269710E+10 | 0.00 | 0.00 |
July | 0.836287E+10 | 38829269.35 | 0.285434E+10 | 45200277.98 | 0.280914E+10 | 0.00 | 0.00 |
August | 0.705009E+10 | 0.123614E+09 | 0.262037E+10 | 8166522.05 | 0.261221E+10 | 0.00 | 0.00 |
September | 0.530131E+10 | 0.416618E+09 | 0.225951E+10 | 158657.88 | 0.225935E+10 | 0.00 | 0.00 |
October | 0.401478E+10 | 0.225240E+10 | 0.202271E+10 | 0.00 | 0.202271E+10 | 0.00 | 0.00 |
November | 0.216813E+10 | 0.407595E+10 | 0.165799E+10 | 0.00 | 0.165799E+10 | 0.00 | 0.00 |
December | 0.121027E+10 | 0.571782E+10 | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585169E+11 | 0.268355E+11 | 0.267380E+11 | 0.244009E+09 | 0.264940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109560E+10 | 38829269.35 | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914833E+10 | 0.584832E+10 | 0.285434E+10 | 0.103744E+09 | 0.280914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.242865E+10 | 0.366871E+10 | 0.232435E+10 | 0.932961E+09 | 0.139139E+10 | 0.00 | 0.00 |
February | 0.327104E+10 | 0.270522E+10 | 0.255052E+10 | 0.105297E+10 | 0.149754E+10 | 0.00 | 0.00 |
March | 0.552401E+10 | 0.190344E+10 | 0.344472E+10 | 0.142186E+10 | 0.202286E+10 | 0.00 | 0.00 |
April | 0.805365E+10 | 0.691895E+09 | 0.396612E+10 | 0.184921E+10 | 0.211691E+10 | 0.00 | 0.00 |
May | 0.952175E+10 | 0.123236E+09 | 0.403388E+10 | 0.178840E+10 | 0.224548E+10 | 0.00 | 0.00 |
June | 0.836517E+10 | 93730693.01 | 0.317714E+10 | 0.105417E+10 | 0.212297E+10 | 0.00 | 0.00 |
July | 0.707798E+10 | 22698715.29 | 0.275932E+10 | 0.582694E+09 | 0.217662E+10 | 0.00 | 0.00 |
August | 0.598311E+10 | 84222193.87 | 0.248626E+10 | 0.432667E+09 | 0.205359E+10 | 0.00 | 0.00 |
September | 0.537061E+10 | 0.289678E+09 | 0.257060E+10 | 0.716876E+09 | 0.185372E+10 | 0.00 | 0.00 |
October | 0.533957E+10 | 0.152402E+10 | 0.290566E+10 | 0.117370E+10 | 0.173197E+10 | 0.00 | 0.00 |
November | 0.366394E+10 | 0.265760E+10 | 0.249319E+10 | 0.107019E+10 | 0.142300E+10 | 0.00 | 0.00 |
December | 0.253357E+10 | 0.367257E+10 | 0.224642E+10 | 0.890044E+09 | 0.135637E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.671331E+11 | 0.174370E+11 | 0.349582E+11 | 0.129657E+11 | 0.219924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242865E+10 | 22698715.29 | 0.224642E+10 | 0.432667E+09 | 0.135637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.952175E+10 | 0.367257E+10 | 0.403388E+10 | 0.184921E+10 | 0.224548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.997342E+10 | 0.604961E+10 | 0.740212E+10 | 0.449772E+10 | 0.290440E+10 | 0.00 | 0.00 |
February | 0.932933E+10 | 0.449920E+10 | 0.635721E+10 | 0.353097E+10 | 0.282624E+10 | 0.00 | 0.00 |
March | 0.104067E+11 | 0.316388E+10 | 0.601795E+10 | 0.265808E+10 | 0.335987E+10 | 0.00 | 0.00 |
April | 0.956259E+10 | 0.112546E+10 | 0.409067E+10 | 0.115451E+10 | 0.293616E+10 | 0.00 | 0.00 |
May | 0.930058E+10 | 0.181671E+09 | 0.303979E+10 | 0.225027E+09 | 0.281476E+10 | 0.00 | 0.00 |
June | 0.893863E+10 | 0.136589E+09 | 0.269093E+10 | 45919963.82 | 0.264501E+10 | 0.00 | 0.00 |
July | 0.849131E+10 | 34836743.03 | 0.290046E+10 | 39893433.56 | 0.286057E+10 | 0.00 | 0.00 |
August | 0.795474E+10 | 0.130574E+09 | 0.307677E+10 | 0.164323E+09 | 0.291245E+10 | 0.00 | 0.00 |
September | 0.857564E+10 | 0.503827E+09 | 0.399161E+10 | 0.103603E+10 | 0.295558E+10 | 0.00 | 0.00 |
October | 0.130835E+11 | 0.259877E+10 | 0.709605E+10 | 0.396241E+10 | 0.313365E+10 | 0.00 | 0.00 |
November | 0.137518E+11 | 0.453645E+10 | 0.857743E+10 | 0.566950E+10 | 0.290793E+10 | 0.00 | 0.00 |
December | 0.110867E+11 | 0.607131E+10 | 0.791031E+10 | 0.495682E+10 | 0.295349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120455E+12 | 0.290322E+11 | 0.631513E+11 | 0.279412E+11 | 0.352101E+11 | 0.00 | 0.00 |
Minimum of Months | 0.795474E+10 | 34836743.03 | 0.269093E+10 | 39893433.56 | 0.264501E+10 | 0.00 | 0.00 |
Maximum of Months | 0.137518E+11 | 0.607131E+10 | 0.857743E+10 | 0.566950E+10 | 0.335987E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265210E+10 | 0.411400E+10 | 0.227400E+10 | 0.884954E+09 | 0.138905E+10 | 0.00 | 0.00 |
February | 0.317170E+10 | 0.301162E+10 | 0.234873E+10 | 0.865571E+09 | 0.148316E+10 | 0.00 | 0.00 |
March | 0.551848E+10 | 0.215279E+10 | 0.337203E+10 | 0.134792E+10 | 0.202411E+10 | 0.00 | 0.00 |
April | 0.804864E+10 | 0.824757E+09 | 0.396645E+10 | 0.186012E+10 | 0.210634E+10 | 0.00 | 0.00 |
May | 0.923410E+10 | 0.170877E+09 | 0.388106E+10 | 0.164626E+10 | 0.223479E+10 | 0.00 | 0.00 |
June | 0.890203E+10 | 0.120698E+09 | 0.352776E+10 | 0.137028E+10 | 0.215748E+10 | 0.00 | 0.00 |
July | 0.685850E+10 | 35945764.56 | 0.270503E+10 | 0.526130E+09 | 0.217890E+10 | 0.00 | 0.00 |
August | 0.589894E+10 | 0.107454E+09 | 0.248429E+10 | 0.441534E+09 | 0.204276E+10 | 0.00 | 0.00 |
September | 0.547551E+10 | 0.356971E+09 | 0.264279E+10 | 0.775849E+09 | 0.186695E+10 | 0.00 | 0.00 |
October | 0.531330E+10 | 0.169324E+10 | 0.284243E+10 | 0.113185E+10 | 0.171058E+10 | 0.00 | 0.00 |
November | 0.387734E+10 | 0.296036E+10 | 0.248850E+10 | 0.106058E+10 | 0.142792E+10 | 0.00 | 0.00 |
December | 0.265507E+10 | 0.403004E+10 | 0.220041E+10 | 0.839065E+09 | 0.136134E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.676057E+11 | 0.195787E+11 | 0.347335E+11 | 0.127501E+11 | 0.219834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265210E+10 | 35945764.56 | 0.220041E+10 | 0.441534E+09 | 0.136134E+10 | 0.00 | 0.00 |
Maximum of Months | 0.923410E+10 | 0.411400E+10 | 0.396645E+10 | 0.186012E+10 | 0.223479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122401E+10 | 0.532124E+10 | 0.162756E+10 | 0.00 | 0.162756E+10 | 0.00 | 0.00 |
February | 0.186768E+10 | 0.390297E+10 | 0.174323E+10 | 0.00 | 0.174323E+10 | 0.00 | 0.00 |
March | 0.360088E+10 | 0.276072E+10 | 0.232567E+10 | 0.00 | 0.232567E+10 | 0.00 | 0.00 |
April | 0.599680E+10 | 0.970051E+09 | 0.244213E+10 | 8282095.40 | 0.243385E+10 | 0.00 | 0.00 |
May | 0.859478E+10 | 0.191127E+09 | 0.279590E+10 | 78458152.52 | 0.271744E+10 | 0.00 | 0.00 |
June | 0.902242E+10 | 0.144029E+09 | 0.280084E+10 | 0.103744E+09 | 0.269710E+10 | 0.00 | 0.00 |
July | 0.822067E+10 | 40292424.74 | 0.285434E+10 | 45200277.98 | 0.280914E+10 | 0.00 | 0.00 |
August | 0.693724E+10 | 0.131152E+09 | 0.262037E+10 | 8166522.05 | 0.261221E+10 | 0.00 | 0.00 |
September | 0.523164E+10 | 0.428056E+09 | 0.225951E+10 | 158657.88 | 0.225935E+10 | 0.00 | 0.00 |
October | 0.399662E+10 | 0.218487E+10 | 0.202271E+10 | 0.00 | 0.202271E+10 | 0.00 | 0.00 |
November | 0.225526E+10 | 0.380734E+10 | 0.165799E+10 | 0.00 | 0.165799E+10 | 0.00 | 0.00 |
December | 0.136376E+10 | 0.521761E+10 | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.583118E+11 | 0.250995E+11 | 0.267380E+11 | 0.244009E+09 | 0.264940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122401E+10 | 40292424.74 | 0.158771E+10 | 0.00 | 0.158771E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902242E+10 | 0.532124E+10 | 0.285434E+10 | 0.103744E+09 | 0.280914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256497E+10 | 0.336090E+10 | 0.232435E+10 | 0.932961E+09 | 0.139139E+10 | 0.00 | 0.00 |
February | 0.333668E+10 | 0.255237E+10 | 0.255052E+10 | 0.105297E+10 | 0.149754E+10 | 0.00 | 0.00 |
March | 0.551658E+10 | 0.185331E+10 | 0.344472E+10 | 0.142186E+10 | 0.202286E+10 | 0.00 | 0.00 |
April | 0.799120E+10 | 0.696296E+09 | 0.396612E+10 | 0.184921E+10 | 0.211691E+10 | 0.00 | 0.00 |
May | 0.942695E+10 | 0.134418E+09 | 0.403388E+10 | 0.178840E+10 | 0.224548E+10 | 0.00 | 0.00 |
June | 0.827014E+10 | 99287164.84 | 0.317714E+10 | 0.105417E+10 | 0.212297E+10 | 0.00 | 0.00 |
July | 0.697235E+10 | 23636277.11 | 0.275932E+10 | 0.582694E+09 | 0.217662E+10 | 0.00 | 0.00 |
August | 0.589989E+10 | 90039609.23 | 0.248626E+10 | 0.432667E+09 | 0.205359E+10 | 0.00 | 0.00 |
September | 0.531794E+10 | 0.301224E+09 | 0.257060E+10 | 0.716876E+09 | 0.185372E+10 | 0.00 | 0.00 |
October | 0.532246E+10 | 0.149425E+10 | 0.290566E+10 | 0.117370E+10 | 0.173197E+10 | 0.00 | 0.00 |
November | 0.371698E+10 | 0.252467E+10 | 0.249319E+10 | 0.107019E+10 | 0.142300E+10 | 0.00 | 0.00 |
December | 0.267181E+10 | 0.339224E+10 | 0.224642E+10 | 0.890044E+09 | 0.135637E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670080E+11 | 0.165226E+11 | 0.349582E+11 | 0.129657E+11 | 0.219924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256497E+10 | 23636277.11 | 0.224642E+10 | 0.432667E+09 | 0.135637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942695E+10 | 0.339224E+10 | 0.403388E+10 | 0.184921E+10 | 0.224548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101326E+11 | 0.555802E+10 | 0.740212E+10 | 0.449772E+10 | 0.290440E+10 | 0.00 | 0.00 |
February | 0.939110E+10 | 0.424491E+10 | 0.635721E+10 | 0.353097E+10 | 0.282624E+10 | 0.00 | 0.00 |
March | 0.103807E+11 | 0.306759E+10 | 0.601795E+10 | 0.265808E+10 | 0.335987E+10 | 0.00 | 0.00 |
April | 0.947588E+10 | 0.112144E+10 | 0.409067E+10 | 0.115451E+10 | 0.293616E+10 | 0.00 | 0.00 |
May | 0.917842E+10 | 0.193359E+09 | 0.303979E+10 | 0.225027E+09 | 0.281476E+10 | 0.00 | 0.00 |
June | 0.881184E+10 | 0.143643E+09 | 0.269093E+10 | 45919963.82 | 0.264501E+10 | 0.00 | 0.00 |
July | 0.834836E+10 | 35875567.13 | 0.290046E+10 | 39893433.56 | 0.286057E+10 | 0.00 | 0.00 |
August | 0.784106E+10 | 0.138446E+09 | 0.307677E+10 | 0.164323E+09 | 0.291245E+10 | 0.00 | 0.00 |
September | 0.849889E+10 | 0.517011E+09 | 0.399161E+10 | 0.103603E+10 | 0.295558E+10 | 0.00 | 0.00 |
October | 0.130437E+11 | 0.254184E+10 | 0.709605E+10 | 0.396241E+10 | 0.313365E+10 | 0.00 | 0.00 |
November | 0.137838E+11 | 0.432661E+10 | 0.857743E+10 | 0.566950E+10 | 0.290793E+10 | 0.00 | 0.00 |
December | 0.112382E+11 | 0.564664E+10 | 0.791031E+10 | 0.495682E+10 | 0.295349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120124E+12 | 0.275354E+11 | 0.631513E+11 | 0.279412E+11 | 0.352101E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784106E+10 | 35875567.13 | 0.269093E+10 | 39893433.56 | 0.264501E+10 | 0.00 | 0.00 |
Maximum of Months | 0.137838E+11 | 0.564664E+10 | 0.857743E+10 | 0.566950E+10 | 0.335987E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271292E+10 | 0.380868E+10 | 0.227400E+10 | 0.884954E+09 | 0.138905E+10 | 0.00 | 0.00 |
February | 0.320348E+10 | 0.284782E+10 | 0.234873E+10 | 0.865571E+09 | 0.148316E+10 | 0.00 | 0.00 |
March | 0.550348E+10 | 0.208612E+10 | 0.337203E+10 | 0.134792E+10 | 0.202411E+10 | 0.00 | 0.00 |
April | 0.799080E+10 | 0.819798E+09 | 0.396645E+10 | 0.186012E+10 | 0.210634E+10 | 0.00 | 0.00 |
May | 0.915675E+10 | 0.178285E+09 | 0.388106E+10 | 0.164626E+10 | 0.223479E+10 | 0.00 | 0.00 |
June | 0.882160E+10 | 0.123523E+09 | 0.352776E+10 | 0.137028E+10 | 0.215748E+10 | 0.00 | 0.00 |
July | 0.677151E+10 | 36912117.39 | 0.270503E+10 | 0.526130E+09 | 0.217890E+10 | 0.00 | 0.00 |
August | 0.583139E+10 | 0.112298E+09 | 0.248429E+10 | 0.441534E+09 | 0.204276E+10 | 0.00 | 0.00 |
September | 0.543027E+10 | 0.363558E+09 | 0.264279E+10 | 0.775849E+09 | 0.186695E+10 | 0.00 | 0.00 |
October | 0.529325E+10 | 0.165056E+10 | 0.284243E+10 | 0.113185E+10 | 0.171058E+10 | 0.00 | 0.00 |
November | 0.390912E+10 | 0.281070E+10 | 0.248850E+10 | 0.106058E+10 | 0.142792E+10 | 0.00 | 0.00 |
December | 0.272626E+10 | 0.375473E+10 | 0.220041E+10 | 0.839065E+09 | 0.136134E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.673508E+11 | 0.185930E+11 | 0.347335E+11 | 0.127501E+11 | 0.219834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271292E+10 | 36912117.39 | 0.220041E+10 | 0.441534E+09 | 0.136134E+10 | 0.00 | 0.00 |
Maximum of Months | 0.915675E+10 | 0.380868E+10 | 0.396645E+10 | 0.186012E+10 | 0.223479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.312934E+11 | -0.302738E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101956E+10 | 58.97 | 0.00 | 0.00 |
February | 0.278494E+11 | -0.269280E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921341423.1 | 58.97 | 0.00 | 0.00 |
March | 0.305678E+11 | -0.295447E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102303E+10 | 58.97 | 0.00 | 0.00 |
April | 0.250257E+11 | -0.240388E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986873060.7 | 58.97 | 0.00 | 0.00 |
May | 0.237009E+11 | -0.226796E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102130E+10 | 58.97 | 0.00 | 0.00 |
June | 0.211348E+11 | -0.201459E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988831005.8 | 58.96 | 0.00 | 0.00 |
July | 0.192769E+11 | -0.182607E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101613E+10 | 58.96 | 0.00 | 0.00 |
August | 0.217355E+11 | -0.207150E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102048E+10 | 58.97 | 0.00 | 0.00 |
September | 0.217884E+11 | -0.208032E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985187426.6 | 58.97 | 0.00 | 0.00 |
October | 0.253230E+11 | -0.243072E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101575E+10 | 58.97 | 0.00 | 0.00 |
November | 0.276733E+11 | -0.266901E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983167941.4 | 58.97 | 0.00 | 0.00 |
December | 0.297090E+11 | -0.286925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101654E+10 | 58.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.305078E+12 | -0.293080E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.119982E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.192769E+11 | -0.302738E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102303E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.312934E+11 | -0.182607E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -921341423.1 | 58.97 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 6098.71 | 35.63 | 298.67 | 289.17 | 1354.46 | 25.97 | 291.83 | 270.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:09 | 3669.18 | 29.55 | 208.50 | 273.50 | 1200.10 | 21.94 | 226.00 | 247.50 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:49 | 1905.96 | 20.74 | 113.33 | 327.83 | 1033.17 | 21.79 | 264.83 | 296.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1294.00 | 19.16 | 37.50 | 332.00 | 764.14 | 20.46 | 207.50 | 302.17 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1098.20 | 19.00 | 4.33 | 353.00 | 643.79 | 20.39 | 185.67 | 316.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:49 | 1086.79 | 18.65 | 0.00 | 338.33 | 622.37 | 20.01 | 179.50 | 297.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1215.02 | 19.17 | 6.50 | 338.17 | 631.49 | 20.43 | 180.50 | 291.17 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:19 | 1365.10 | 19.15 | 50.67 | 326.17 | 684.65 | 20.41 | 198.17 | 279.67 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:30 | 1662.78 | 19.88 | 98.17 | 305.00 | 860.09 | 21.20 | 220.67 | 269.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2810.24 | 21.80 | 133.50 | 307.67 | 1159.08 | 21.41 | 241.33 | 282.17 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 8247.83 | 36.84 | 310.83 | 289.00 | 1415.15 | 23.87 | 274.50 | 268.33 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 6440.18 | 36.94 | 308.83 | 288.83 | 1592.79 | 28.12 | 310.33 | 280.33 |
Annual Sum or Average | 4237.50 | 0.53 | 2899.50 | 24.14 | 1570.83 | 3768.67 | 970.38 | 22.01 | 2780.83 | 3402.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1086.79 | 18.65 | 0.00 | 273.50 | 622.37 | 20.01 | 179.50 | 247.50 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 8247.83 | 36.94 | 310.83 | 353.00 | 1592.79 | 28.12 | 310.33 | 316.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1805.40 | 24.14 | 111.33 | 273.50 | 952.58 | 24.21 | 178.17 | 230.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-07:49 | 2236.54 | 24.27 | 100.83 | 261.00 | 1179.76 | 24.38 | 166.00 | 230.50 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 2151.29 | 23.74 | 101.50 | 323.33 | 1113.00 | 23.99 | 189.50 | 293.33 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2606.22 | 23.16 | 110.67 | 331.67 | 1371.37 | 23.50 | 131.50 | 305.83 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2703.19 | 23.55 | 128.50 | 360.83 | 1053.47 | 22.71 | 133.83 | 331.33 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2159.23 | 22.29 | 108.33 | 341.67 | 907.15 | 21.80 | 134.83 | 306.33 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:10 | 1787.05 | 22.26 | 102.33 | 342.83 | 798.00 | 21.86 | 136.67 | 298.33 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:40 | 1636.96 | 21.73 | 98.83 | 327.17 | 755.36 | 21.39 | 149.00 | 278.17 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1828.22 | 22.74 | 91.67 | 302.33 | 925.74 | 23.15 | 167.33 | 266.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 2010.78 | 23.45 | 103.83 | 301.00 | 1017.93 | 23.53 | 176.67 | 271.67 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-07:10 | 1815.58 | 23.88 | 95.67 | 272.33 | 923.45 | 23.87 | 166.83 | 246.17 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1888.01 | 24.77 | 116.33 | 267.50 | 1003.79 | 24.76 | 181.50 | 235.67 |
Annual Sum or Average | 4237.50 | 0.53 | 2065.30 | 23.28 | 1269.83 | 3705.17 | 999.34 | 23.19 | 1911.83 | 3294.50 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1636.96 | 21.73 | 91.67 | 261.00 | 755.36 | 21.39 | 131.50 | 230.50 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2703.19 | 24.77 | 128.50 | 360.83 | 1371.37 | 24.76 | 189.50 | 331.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.57 | 0.48 | 01-JAN-09:39 | 605.39 | 16.88 | 0.00 | 255.83 | 371.83 | 18.42 | 0.00 | 183.67 |
February | 303.83 | 0.55 | 0.48 | 01-FEB-09:09 | 698.37 | 17.74 | 0.00 | 254.33 | 427.74 | 19.21 | 0.00 | 197.17 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:30 | 825.86 | 18.80 | 0.00 | 319.33 | 505.01 | 20.19 | 9.83 | 273.17 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 892.51 | 18.78 | 0.00 | 334.17 | 554.48 | 20.10 | 112.50 | 307.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1059.57 | 19.47 | 38.00 | 368.50 | 621.98 | 20.80 | 183.67 | 341.50 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1171.07 | 21.05 | 98.00 | 350.50 | 654.53 | 20.63 | 198.33 | 317.83 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1185.80 | 20.72 | 56.17 | 348.33 | 619.84 | 21.31 | 180.17 | 305.67 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 1060.44 | 18.86 | 3.17 | 329.67 | 554.18 | 20.07 | 123.83 | 282.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 925.68 | 18.74 | 0.00 | 302.83 | 514.66 | 20.01 | 92.67 | 255.50 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:49 | 732.72 | 17.66 | 0.00 | 293.00 | 458.66 | 19.16 | 1.33 | 244.33 |
November | 317.83 | 0.55 | 0.48 | 01-NOV-08:30 | 624.80 | 17.29 | 0.00 | 258.33 | 405.58 | 18.96 | 0.00 | 207.00 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:09 | 596.78 | 16.98 | 0.00 | 250.67 | 369.88 | 18.58 | 0.00 | 184.33 |
Annual Sum or Average | 4237.50 | 0.54 | 881.20 | 18.68 | 195.33 | 3665.50 | 512.80 | 19.86 | 902.33 | 3099.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 596.78 | 16.88 | 0.00 | 250.67 | 369.88 | 18.42 | 0.00 | 183.67 | |
Maximum of Months | 406.00 | 0.57 | 0.48 | 1185.80 | 21.05 | 98.00 | 368.50 | 654.53 | 21.31 | 198.33 | 341.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1808.90 | 23.91 | 109.33 | 272.17 | 938.54 | 23.94 | 178.67 | 229.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:20 | 2141.82 | 23.90 | 104.50 | 266.83 | 860.54 | 22.70 | 159.83 | 232.00 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:39 | 2098.94 | 23.65 | 101.33 | 323.50 | 1081.30 | 23.89 | 190.33 | 295.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:09 | 2388.93 | 21.43 | 84.67 | 335.33 | 1247.12 | 21.90 | 105.50 | 309.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:40 | 2293.08 | 17.70 | 0.00 | 356.00 | 1189.32 | 19.84 | 93.00 | 329.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:20 | 2280.94 | 17.72 | 0.00 | 341.67 | 943.92 | 19.67 | 99.33 | 308.33 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:40 | 1730.80 | 18.44 | 3.67 | 340.67 | 788.63 | 20.02 | 110.67 | 296.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:00 | 1615.36 | 19.71 | 55.33 | 326.67 | 804.16 | 19.89 | 112.00 | 280.83 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:30 | 1794.50 | 21.93 | 83.17 | 305.33 | 903.51 | 22.30 | 166.17 | 266.83 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:00 | 2133.32 | 23.55 | 105.17 | 297.67 | 1076.77 | 23.64 | 166.50 | 269.33 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1870.37 | 24.00 | 99.17 | 274.00 | 941.59 | 23.98 | 168.50 | 247.17 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-08:00 | 1648.32 | 24.07 | 111.33 | 271.83 | 852.47 | 24.05 | 182.33 | 239.83 |
Annual Sum or Average | 4237.50 | 0.53 | 1993.24 | 21.47 | 857.67 | 3711.67 | 974.46 | 22.03 | 1732.83 | 3305.00 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1615.36 | 17.70 | 0.00 | 266.83 | 788.63 | 19.67 | 93.00 | 229.50 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2388.93 | 24.07 | 111.33 | 356.00 | 1247.12 | 24.05 | 190.33 | 329.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 6136.81 | 35.11 | 297.33 | 289.33 | 1444.14 | 21.79 | 85.50 | 272.17 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:09 | 3712.01 | 26.81 | 196.50 | 273.83 | 1285.21 | 17.10 | 0.00 | 250.50 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:49 | 1942.84 | 14.59 | 7.50 | 328.00 | 1105.82 | 17.71 | 0.00 | 299.00 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1323.79 | 13.47 | 0.00 | 332.00 | 817.74 | 16.86 | 0.00 | 306.67 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1119.44 | 13.11 | 0.00 | 353.17 | 686.68 | 16.57 | 0.00 | 321.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:40 | 1105.36 | 12.68 | 0.00 | 339.00 | 662.82 | 16.05 | 0.00 | 304.00 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1228.04 | 12.77 | 0.00 | 338.33 | 670.56 | 16.09 | 0.00 | 295.17 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 1375.91 | 12.73 | 0.00 | 326.83 | 726.04 | 15.98 | 0.00 | 284.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 1682.16 | 13.47 | 0.00 | 305.50 | 914.66 | 16.85 | 0.00 | 273.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2863.69 | 15.95 | 42.67 | 308.83 | 1245.31 | 17.15 | 10.00 | 285.00 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 8307.60 | 36.43 | 310.50 | 289.17 | 1528.38 | 20.98 | 74.33 | 276.50 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 6478.90 | 36.53 | 308.83 | 289.00 | 1688.66 | 24.39 | 123.50 | 281.83 |
Annual Sum or Average | 4237.50 | 0.52 | 2930.45 | 19.56 | 1163.33 | 3773.00 | 1036.36 | 17.97 | 293.33 | 3450.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1105.36 | 12.68 | 0.00 | 273.83 | 662.82 | 15.98 | 0.00 | 250.50 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 8307.60 | 36.53 | 310.50 | 353.17 | 1688.66 | 24.39 | 123.50 | 321.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1833.91 | 21.70 | 106.83 | 274.17 | 993.23 | 22.36 | 77.33 | 235.00 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-07:49 | 2276.21 | 21.64 | 100.50 | 262.33 | 1227.31 | 22.38 | 74.33 | 235.17 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 2204.08 | 20.77 | 101.50 | 324.17 | 1168.38 | 21.66 | 70.83 | 297.00 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2635.93 | 20.26 | 110.67 | 332.17 | 1430.87 | 21.18 | 81.17 | 308.50 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2723.26 | 19.61 | 117.00 | 360.33 | 1112.98 | 20.06 | 66.50 | 334.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2190.05 | 19.22 | 107.50 | 342.83 | 958.68 | 19.16 | 52.00 | 311.00 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:10 | 1810.04 | 18.66 | 96.33 | 343.17 | 846.84 | 19.25 | 48.17 | 303.33 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:30 | 1659.89 | 18.63 | 97.83 | 328.83 | 860.49 | 19.82 | 69.33 | 284.67 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1863.94 | 19.74 | 90.17 | 303.00 | 970.63 | 20.82 | 64.83 | 271.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 2053.19 | 20.56 | 100.83 | 301.33 | 1067.45 | 21.44 | 72.33 | 274.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-07:10 | 1841.93 | 20.34 | 88.00 | 273.33 | 969.84 | 21.90 | 64.83 | 249.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1915.51 | 22.41 | 112.50 | 268.17 | 1044.18 | 23.03 | 81.67 | 240.17 |
Annual Sum or Average | 4237.50 | 0.53 | 2096.71 | 20.22 | 1229.67 | 3713.83 | 1054.12 | 21.00 | 823.33 | 3343.50 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1659.89 | 18.63 | 88.00 | 262.33 | 846.84 | 19.16 | 48.17 | 235.00 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2723.26 | 22.41 | 117.00 | 360.33 | 1430.87 | 23.03 | 81.67 | 334.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.56 | 0.48 | 01-JAN-09:30 | 614.55 | 11.33 | 0.00 | 256.67 | 395.65 | 14.84 | 0.00 | 193.00 |
February | 303.83 | 0.55 | 0.48 | 01-FEB-08:00 | 709.90 | 12.21 | 0.00 | 254.33 | 455.41 | 15.70 | 0.00 | 206.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:20 | 840.99 | 13.48 | 0.00 | 319.83 | 538.08 | 16.94 | 0.00 | 278.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 911.69 | 13.58 | 0.00 | 334.17 | 591.74 | 16.98 | 0.00 | 311.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1081.07 | 13.64 | 1.17 | 368.83 | 663.36 | 17.17 | 1.17 | 344.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:19 | 1192.26 | 15.86 | 39.67 | 350.50 | 700.01 | 19.04 | 41.17 | 324.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1201.12 | 15.00 | 29.33 | 348.67 | 658.90 | 18.14 | 29.83 | 312.17 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:00 | 1073.72 | 12.65 | 0.00 | 329.67 | 588.32 | 15.92 | 0.00 | 287.83 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 939.11 | 12.95 | 0.00 | 303.00 | 547.08 | 16.26 | 0.00 | 262.17 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:49 | 745.75 | 12.26 | 0.00 | 293.50 | 488.66 | 15.70 | 0.00 | 252.83 |
November | 317.83 | 0.55 | 0.48 | 01-NOV-08:20 | 635.16 | 11.74 | 0.00 | 258.50 | 432.05 | 15.39 | 0.00 | 214.50 |
December | 315.50 | 0.56 | 0.48 | 01-DEC-08:50 | 605.60 | 11.39 | 0.00 | 251.33 | 393.51 | 14.98 | 0.00 | 195.67 |
Annual Sum or Average | 4237.50 | 0.53 | 895.86 | 13.10 | 70.17 | 3669.00 | 546.22 | 16.51 | 72.17 | 3183.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 605.60 | 11.33 | 0.00 | 251.33 | 393.51 | 14.84 | 0.00 | 193.00 | |
Maximum of Months | 406.00 | 0.56 | 0.48 | 1201.12 | 15.86 | 39.67 | 368.83 | 700.01 | 19.04 | 41.17 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-09:30 | 1837.35 | 21.49 | 104.17 | 272.83 | 979.04 | 22.08 | 74.50 | 232.67 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:20 | 2177.37 | 21.37 | 103.50 | 267.33 | 905.33 | 20.41 | 48.00 | 235.50 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:39 | 2149.65 | 20.70 | 101.17 | 323.33 | 1135.57 | 21.56 | 69.33 | 298.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:09 | 2418.44 | 18.18 | 84.50 | 335.17 | 1305.76 | 19.28 | 54.67 | 313.00 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:30 | 2319.96 | 13.11 | 0.00 | 356.83 | 1247.73 | 16.55 | 0.00 | 332.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:09 | 2314.34 | 13.19 | 0.00 | 342.17 | 999.78 | 16.43 | 0.00 | 312.00 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:40 | 1754.98 | 13.96 | 3.50 | 341.67 | 832.35 | 16.83 | 0.00 | 301.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:49 | 1638.37 | 15.98 | 53.00 | 327.50 | 845.04 | 16.80 | 4.83 | 285.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:20 | 1830.18 | 18.76 | 80.67 | 306.67 | 949.00 | 19.80 | 52.50 | 270.17 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:00 | 2176.44 | 20.90 | 105.00 | 297.83 | 1125.57 | 21.59 | 74.50 | 271.83 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1902.32 | 21.25 | 95.83 | 274.17 | 987.67 | 22.04 | 67.17 | 250.33 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-08:50 | 1663.58 | 20.48 | 90.33 | 272.50 | 892.38 | 22.22 | 70.17 | 244.17 |
Annual Sum or Average | 4237.50 | 0.53 | 2024.72 | 18.03 | 821.67 | 3718.00 | 1022.98 | 19.47 | 515.67 | 3348.67 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1638.37 | 13.11 | 0.00 | 267.33 | 832.35 | 16.43 | 0.00 | 232.67 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2418.44 | 21.49 | 105.00 | 356.83 | 1305.76 | 22.22 | 74.50 | 332.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 6139.03 | 35.10 | 297.33 | 289.33 | 1446.28 | 21.78 | 85.50 | 272.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:09 | 3714.93 | 26.80 | 196.50 | 274.00 | 1287.19 | 17.09 | 0.00 | 250.67 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:49 | 1945.49 | 14.56 | 7.50 | 328.17 | 1107.47 | 17.69 | 0.00 | 299.17 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1325.38 | 13.44 | 0.00 | 332.00 | 818.82 | 16.85 | 0.00 | 306.67 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1120.77 | 13.08 | 0.00 | 353.33 | 687.61 | 16.55 | 0.00 | 321.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:40 | 1106.78 | 12.65 | 0.00 | 339.00 | 663.77 | 16.04 | 0.00 | 304.17 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1230.15 | 12.74 | 0.00 | 338.33 | 671.73 | 16.08 | 0.00 | 295.33 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 1378.45 | 12.70 | 0.00 | 327.00 | 727.42 | 15.97 | 0.00 | 284.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 1684.99 | 13.44 | 0.00 | 305.50 | 916.29 | 16.83 | 0.00 | 273.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2866.36 | 15.92 | 42.67 | 308.83 | 1247.08 | 17.14 | 10.00 | 285.00 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 8309.87 | 36.42 | 310.50 | 289.17 | 1530.41 | 20.96 | 74.33 | 276.50 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 6481.09 | 36.52 | 308.83 | 289.00 | 1690.93 | 24.38 | 123.50 | 281.83 |
Annual Sum or Average | 4237.50 | 0.52 | 2932.65 | 19.54 | 1163.33 | 3773.67 | 1037.90 | 17.95 | 293.33 | 3451.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1106.78 | 12.65 | 0.00 | 274.00 | 663.77 | 15.97 | 0.00 | 250.67 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 8309.87 | 36.52 | 310.50 | 353.33 | 1690.93 | 24.38 | 123.50 | 321.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1834.94 | 21.67 | 106.83 | 274.17 | 994.27 | 22.35 | 77.33 | 235.17 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-07:49 | 2277.50 | 21.62 | 100.50 | 262.50 | 1228.51 | 22.37 | 74.33 | 235.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 2205.48 | 20.75 | 101.50 | 324.17 | 1169.69 | 21.65 | 70.83 | 297.17 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2637.28 | 20.23 | 110.67 | 332.33 | 1432.13 | 21.16 | 81.17 | 308.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2724.73 | 19.58 | 117.00 | 360.33 | 1114.25 | 20.04 | 66.50 | 334.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2191.83 | 19.19 | 107.50 | 342.83 | 959.98 | 19.15 | 52.00 | 311.00 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:10 | 1812.37 | 18.63 | 96.33 | 343.00 | 848.25 | 19.24 | 48.17 | 303.50 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:30 | 1662.28 | 18.61 | 97.83 | 329.00 | 861.92 | 19.81 | 69.33 | 285.17 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1865.98 | 19.71 | 90.17 | 303.00 | 972.06 | 20.81 | 64.83 | 271.17 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 2054.40 | 20.53 | 100.83 | 301.33 | 1068.65 | 21.43 | 72.33 | 274.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-07:10 | 1842.84 | 20.32 | 88.00 | 273.50 | 970.86 | 21.88 | 64.83 | 249.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1916.51 | 22.38 | 112.50 | 268.17 | 1045.22 | 23.02 | 81.67 | 240.17 |
Annual Sum or Average | 4237.50 | 0.53 | 2098.26 | 20.19 | 1229.67 | 3714.33 | 1055.38 | 20.98 | 823.33 | 3345.00 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1662.28 | 18.61 | 88.00 | 262.50 | 848.25 | 19.15 | 48.17 | 235.17 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2724.73 | 22.38 | 117.00 | 360.33 | 1432.13 | 23.02 | 81.67 | 334.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.56 | 0.48 | 01-JAN-09:30 | 615.03 | 11.30 | 0.00 | 257.00 | 396.13 | 14.83 | 0.00 | 193.00 |
February | 303.83 | 0.55 | 0.48 | 01-FEB-08:00 | 710.49 | 12.18 | 0.00 | 254.33 | 455.97 | 15.68 | 0.00 | 206.67 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:20 | 841.72 | 13.44 | 0.00 | 319.83 | 538.74 | 16.93 | 0.00 | 279.17 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 912.44 | 13.55 | 0.00 | 334.33 | 592.44 | 16.97 | 0.00 | 311.17 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1082.19 | 13.61 | 1.17 | 368.83 | 664.23 | 17.16 | 1.17 | 344.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:19 | 1193.72 | 15.84 | 39.67 | 350.50 | 701.03 | 19.02 | 41.17 | 324.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1203.05 | 14.97 | 29.33 | 348.83 | 660.04 | 18.13 | 29.83 | 312.17 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:00 | 1075.48 | 12.63 | 0.00 | 330.00 | 589.37 | 15.90 | 0.00 | 287.83 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 940.36 | 12.92 | 0.00 | 303.00 | 547.93 | 16.25 | 0.00 | 262.33 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:49 | 746.30 | 12.23 | 0.00 | 293.50 | 489.22 | 15.68 | 0.00 | 252.83 |
November | 317.83 | 0.55 | 0.48 | 01-NOV-08:20 | 635.49 | 11.71 | 0.00 | 258.50 | 432.51 | 15.37 | 0.00 | 214.67 |
December | 315.50 | 0.56 | 0.48 | 01-DEC-08:50 | 606.04 | 11.36 | 0.00 | 251.33 | 393.99 | 14.96 | 0.00 | 196.33 |
Annual Sum or Average | 4237.50 | 0.53 | 896.84 | 13.07 | 70.17 | 3670.00 | 546.97 | 16.50 | 72.17 | 3185.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 606.04 | 11.30 | 0.00 | 251.33 | 393.99 | 14.83 | 0.00 | 193.00 | |
Maximum of Months | 406.00 | 0.56 | 0.48 | 1203.05 | 15.84 | 39.67 | 368.83 | 701.03 | 19.02 | 41.17 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-09:30 | 1838.39 | 21.46 | 104.17 | 273.00 | 980.09 | 22.06 | 74.50 | 232.83 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:20 | 2178.69 | 21.35 | 103.50 | 267.33 | 906.51 | 20.40 | 48.00 | 235.50 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:39 | 2151.06 | 20.67 | 101.17 | 323.33 | 1136.87 | 21.54 | 69.33 | 298.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:09 | 2419.77 | 18.15 | 84.50 | 335.17 | 1307.00 | 19.26 | 54.67 | 313.00 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:30 | 2321.45 | 13.08 | 0.00 | 357.00 | 1249.02 | 16.53 | 0.00 | 332.83 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:09 | 2316.12 | 13.16 | 0.00 | 342.17 | 1001.12 | 16.41 | 0.00 | 312.50 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:40 | 1757.35 | 13.93 | 3.50 | 341.67 | 833.78 | 16.82 | 0.00 | 302.17 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:49 | 1640.76 | 15.95 | 53.00 | 327.50 | 846.46 | 16.79 | 4.83 | 285.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:20 | 1832.27 | 18.73 | 80.67 | 306.67 | 950.43 | 19.79 | 52.50 | 270.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:00 | 2177.71 | 20.88 | 105.00 | 297.83 | 1126.75 | 21.58 | 74.50 | 272.00 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1903.23 | 21.22 | 95.83 | 274.17 | 988.68 | 22.03 | 67.17 | 250.50 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-08:50 | 1664.62 | 20.46 | 90.33 | 272.50 | 893.40 | 22.21 | 70.17 | 244.17 |
Annual Sum or Average | 4237.50 | 0.53 | 2026.28 | 18.01 | 821.67 | 3718.33 | 1024.23 | 19.45 | 515.67 | 3350.50 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1640.76 | 13.08 | 0.00 | 267.33 | 833.78 | 16.41 | 0.00 | 232.83 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2419.77 | 21.46 | 105.00 | 357.00 | 1307.00 | 22.21 | 74.50 | 332.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121805E+09 | 4430.03 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10707143.85 | 2776.24 | 23-DEC-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121805E+09 | 4430.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5136526.94 | 628.82 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5136526.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5136526.94 | 628.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11893276.82 | 1444.59 | 03-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1268715.83 | 748.66 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2270583.75 | 967.99 | 23-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15432576.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11893276.82 | 1444.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15077516.35 | 14609.88 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1907556.73 | 1115.88 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16985073.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15077516.35 | 14609.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.408492E+10 | 75470.86 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67771993.91 | 14149.46 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590467E+09 | 45792.70 | 23-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408492E+10 | 75470.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70003532.72 | 25475.36 | 02-JAN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 70003532.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70003532.72 | 25475.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.807292E+10 | 193256.93 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150408E+10 | 145747.09 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35791479.56 | 8112.54 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352051E+10 | 198707.95 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.807292E+10 | 198707.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348313E+10 | 141059.16 | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690207E+09 | 112402.00 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142985E+10 | 139613.13 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348313E+10 | 141059.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165053E+10 | 192947.68 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339258E+09 | 141660.26 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315113E+09 | 28642.46 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165053E+10 | 192947.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379269E+10 | 139301.23 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739221E+09 | 75433.40 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133955E+10 | 100556.60 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379269E+10 | 139301.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165506E+10 | 13328.23 | 02-JAN-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170820E+09 | 6907.63 | 02-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 270448.57 | 585.20 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397524E+09 | 11730.62 | 23-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165506E+10 | 13328.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107469E+10 | 82899.32 | 02-JAN-05:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 438400.03 | 567.69 | 11-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56548648.58 | 5303.62 | 11-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107469E+10 | 82899.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238343E+10 | 22683.80 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627267E+09 | 22570.88 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9121201.56 | 1635.62 | 01-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120310E+09 | 16308.79 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138845E+10 | 22566.14 | 02-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238343E+10 | 22683.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.999233E+09 | 16099.69 | 02-JAN-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269594E+09 | 16016.99 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1471940.96 | 623.24 | 01-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41962419.24 | 4365.38 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581026E+09 | 16018.71 | 18-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.999233E+09 | 16099.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.850351E+09 | 22651.28 | 02-JAN-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249959E+09 | 22537.79 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4818827.99 | 809.90 | 25-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415312E+09 | 22513.03 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.850351E+09 | 22651.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108396E+10 | 16590.26 | 02-JAN-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306272E+09 | 16491.49 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 332054.02 | 212.67 | 01-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33541348.88 | 2040.24 | 25-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605749E+09 | 16491.65 | 23-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108396E+10 | 16590.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.472267E+11 | 0.471640E+11 | 114581.97 | 02-JAN-06:02 | 70747.14 | 0.44 |
February | 0.00 | 0.00 | 0.686908E+11 | 0.685364E+11 | 162848.63 | 25-FEB-06:03 | 113339.61 | 0.54 |
March | 0.00 | 0.00 | 0.132337E+12 | 0.130283E+12 | 228804.89 | 11-MAR-06:02 | 172919.39 | 0.70 |
April | 0.00 | 0.00 | 0.198110E+12 | 0.191193E+12 | 284825.91 | 26-APR-05:02 | 191749.33 | 0.83 |
May | 0.00 | 0.00 | 0.246116E+12 | 0.211679E+12 | 287383.55 | 22-MAY-05:02 | 192835.30 | 0.85 |
June | 0.00 | 0.00 | 0.284024E+12 | 0.215838E+12 | 333922.72 | 14-JUN-05:02 | 216465.79 | 0.86 |
July | 0.00 | 0.00 | 0.318965E+12 | 0.204584E+12 | 342441.12 | 17-JUL-05:03 | 213520.50 | 0.87 |
August | 0.00 | 0.00 | 0.340938E+12 | 0.215327E+12 | 338923.85 | 28-AUG-05:02 | 207253.67 | 0.89 |
September | 0.00 | 0.00 | 0.241257E+12 | 0.158987E+12 | 314312.84 | 11-SEP-05:03 | 191224.18 | 0.78 |
October | 0.00 | 0.00 | 0.163027E+12 | 0.146344E+12 | 281243.44 | 12-OCT-04:12 | 176154.55 | 0.72 |
November | 0.00 | 0.00 | 0.107665E+12 | 0.106280E+12 | 198365.97 | 09-NOV-05:12 | 137485.26 | 0.61 |
December | 0.00 | 0.00 | 0.689612E+11 | 0.689612E+11 | 111698.38 | 29-DEC-05:12 | 111698.38 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.221732E+13 | 0.176518E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.472267E+11 | 0.471640E+11 | 111698.38 | 70747.14 | 0.44 | |
Maximum of Months | 0.00 | 0.00 | 0.340938E+12 | 0.215838E+12 | 342441.12 | 216465.79 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.318146E+12 | 0.317968E+12 | 819663.95 | 14-JAN-06:03 | 819663.95 | 0.40 |
February | 0.00 | 0.00 | 0.498530E+12 | 0.497502E+12 | 1380325.61 | 25-FEB-06:03 | 956703.48 | 0.51 |
March | 0.00 | 0.00 | 0.103554E+13 | 0.102043E+13 | 2120666.69 | 29-MAR-04:12 | 1714584.85 | 0.62 |
April | 0.00 | 0.00 | 0.160523E+13 | 0.155063E+13 | 2508695.01 | 27-APR-05:02 | 1871239.98 | 0.72 |
May | 0.00 | 0.00 | 0.231885E+13 | 0.198124E+13 | 2574047.68 | 13-MAY-04:12 | 1641529.54 | 0.83 |
June | 0.00 | 0.00 | 0.260231E+13 | 0.194533E+13 | 2696140.07 | 21-JUN-03:02 | 1721185.98 | 0.82 |
July | 0.00 | 0.00 | 0.280961E+13 | 0.173293E+13 | 3367484.95 | 25-JUL-05:03 | 1852012.04 | 0.79 |
August | 0.00 | 0.00 | 0.276165E+13 | 0.164733E+13 | 3243772.15 | 10-AUG-05:02 | 1859020.41 | 0.77 |
September | 0.00 | 0.00 | 0.214980E+13 | 0.138912E+13 | 2750080.06 | 11-SEP-03:02 | 1610314.50 | 0.71 |
October | 0.00 | 0.00 | 0.137653E+13 | 0.122808E+13 | 2596797.57 | 06-OCT-04:12 | 1768371.34 | 0.65 |
November | 0.00 | 0.00 | 0.808469E+12 | 0.799017E+12 | 1565929.79 | 09-NOV-06:03 | 1065780.66 | 0.58 |
December | 0.00 | 0.00 | 0.410344E+12 | 0.410344E+12 | 890417.99 | 29-DEC-06:02 | 890417.99 | 0.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.186950E+14 | 0.145199E+14 | 0.66 | |||
Minimum of Months | 0.00 | 0.00 | 0.318146E+12 | 0.317968E+12 | 819663.95 | 819663.95 | 0.40 | |
Maximum of Months | 0.00 | 0.00 | 0.280961E+13 | 0.198124E+13 | 3367484.95 | 1871239.98 | 0.83 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.268379E+11 | 0.268379E+11 | 67792.39 | 12-JAN-15:30 | 67792.39 | 0.37 |
February | 0.00 | 0.00 | 0.458764E+11 | 0.457822E+11 | 111930.82 | 25-FEB-06:03 | 79828.54 | 0.49 |
March | 0.00 | 0.00 | 0.105332E+12 | 0.103922E+12 | 205197.78 | 29-MAR-04:12 | 163415.63 | 0.61 |
April | 0.00 | 0.00 | 0.174278E+12 | 0.168793E+12 | 264531.04 | 19-APR-05:02 | 187225.43 | 0.72 |
May | 0.00 | 0.00 | 0.254142E+12 | 0.220192E+12 | 314696.72 | 22-MAY-05:02 | 203206.48 | 0.83 |
June | 0.00 | 0.00 | 0.283420E+12 | 0.217581E+12 | 348930.61 | 26-JUN-05:02 | 203662.92 | 0.82 |
July | 0.00 | 0.00 | 0.299312E+12 | 0.191068E+12 | 371858.15 | 03-JUL-05:02 | 228221.77 | 0.80 |
August | 0.00 | 0.00 | 0.290858E+12 | 0.178975E+12 | 359456.19 | 10-AUG-05:02 | 207810.11 | 0.77 |
September | 0.00 | 0.00 | 0.223382E+12 | 0.147533E+12 | 314321.55 | 14-SEP-03:02 | 188450.89 | 0.71 |
October | 0.00 | 0.00 | 0.139219E+12 | 0.125154E+12 | 256428.36 | 06-OCT-04:12 | 172288.53 | 0.64 |
November | 0.00 | 0.00 | 0.754145E+11 | 0.748530E+11 | 143341.16 | 09-NOV-06:03 | 94914.49 | 0.56 |
December | 0.00 | 0.00 | 0.332055E+11 | 0.332055E+11 | 75917.33 | 01-DEC-15:00 | 75917.33 | 0.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.195128E+13 | 0.153390E+13 | 0.65 | |||
Minimum of Months | 0.00 | 0.00 | 0.268379E+11 | 0.268379E+11 | 67792.39 | 67792.39 | 0.37 | |
Maximum of Months | 0.00 | 0.00 | 0.299312E+12 | 0.220192E+12 | 371858.15 | 228221.77 | 0.83 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.567563E+11 | 0.566693E+11 | 139622.33 | 18-JAN-05:13 | 102887.89 | 0.47 |
February | 0.00 | 0.00 | 0.591410E+11 | 0.590253E+11 | 154470.65 | 25-FEB-05:12 | 103742.31 | 0.53 |
March | 0.00 | 0.00 | 0.818882E+11 | 0.815917E+11 | 160265.79 | 31-MAR-04:12 | 100591.01 | 0.58 |
April | 0.00 | 0.00 | 0.943728E+11 | 0.923899E+11 | 182743.33 | 27-APR-03:02 | 111505.04 | 0.55 |
May | 0.00 | 0.00 | 0.119548E+12 | 0.107409E+12 | 221779.55 | 22-MAY-03:03 | 103777.99 | 0.62 |
June | 0.00 | 0.00 | 0.139764E+12 | 0.111853E+12 | 240990.09 | 26-JUN-03:15 | 94444.53 | 0.64 |
July | 0.00 | 0.00 | 0.160186E+12 | 0.110771E+12 | 252924.92 | 23-JUL-23:08 | 98459.38 | 0.64 |
August | 0.00 | 0.00 | 0.178808E+12 | 0.119605E+12 | 261796.70 | 27-AUG-11:28 | 103667.17 | 0.68 |
September | 0.00 | 0.00 | 0.140860E+12 | 0.102199E+12 | 247047.32 | 10-SEP-16:38 | 97915.42 | 0.65 |
October | 0.00 | 0.00 | 0.104954E+12 | 0.982369E+11 | 185895.85 | 04-OCT-03:02 | 106441.52 | 0.63 |
November | 0.00 | 0.00 | 0.819923E+11 | 0.816253E+11 | 164453.65 | 09-NOV-05:12 | 103382.87 | 0.59 |
December | 0.00 | 0.00 | 0.655413E+11 | 0.654821E+11 | 133787.70 | 30-DEC-05:12 | 99757.11 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.128381E+13 | 0.108686E+13 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.567563E+11 | 0.566693E+11 | 133787.70 | 94444.53 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.178808E+12 | 0.119605E+12 | 261796.70 | 111505.04 | 0.68 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.338440E+12 | 0.324819E+12 | 132564.26 | 17-JAN-17:00 | 125623.85 | 0.00 |
February | 0.00 | 0.00 | 0.534272E+12 | 0.517423E+12 | 226618.31 | 24-FEB-17:00 | 220567.68 | 0.00 |
March | 0.00 | 0.00 | 0.837819E+12 | 0.823909E+12 | 396620.16 | 31-MAR-24:00 | 394321.76 | 0.00 |
April | 0.00 | 0.00 | 0.103660E+13 | 0.103040E+13 | 410381.59 | 25-APR-04:53 | 402737.06 | 0.00 |
May | 0.00 | 0.00 | 0.364838E+12 | 0.347927E+12 | 226879.34 | 31-MAY-23:05 | 212970.58 | 0.00 |
June | 0.00 | 0.00 | 0.600904E+12 | 0.575116E+12 | 319434.70 | 30-JUN-23:03 | 307288.60 | 0.00 |
July | 0.00 | 0.00 | 0.876224E+12 | 0.839584E+12 | 402843.02 | 31-JUL-24:00 | 390956.17 | 0.00 |
August | 0.00 | 0.00 | 0.110196E+13 | 0.106643E+13 | 422728.18 | 10-AUG-14:00 | 402931.71 | 0.00 |
September | 0.00 | 0.00 | 0.368369E+12 | 0.337081E+12 | 228325.83 | 30-SEP-23:03 | 213499.17 | 0.00 |
October | 0.00 | 0.00 | 0.603967E+12 | 0.587531E+12 | 311299.01 | 31-OCT-24:00 | 302968.78 | 0.00 |
November | 0.00 | 0.00 | 0.819233E+12 | 0.799831E+12 | 322206.10 | 24-NOV-08:15 | 308023.49 | 0.00 |
December | 0.00 | 0.00 | 0.110011E+13 | 0.106569E+13 | 422151.60 | 22-DEC-06:03 | 396563.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.858273E+13 | 0.831574E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338440E+12 | 0.324819E+12 | 132564.26 | 125623.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110196E+13 | 0.106643E+13 | 422728.18 | 402931.71 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.480355E+10 | 0.464604E+10 | 2594.05 | 12-JAN-17:00 | 2455.13 | 0.00 |
February | 0.00 | 0.00 | 0.960852E+10 | 0.936734E+10 | 4677.30 | 21-FEB-17:00 | 4519.06 | 0.00 |
March | 0.00 | 0.00 | 0.164126E+11 | 0.160633E+11 | 7841.60 | 31-MAR-24:00 | 7734.48 | 0.00 |
April | 0.00 | 0.00 | 0.213523E+11 | 0.210274E+11 | 8815.66 | 16-APR-20:53 | 8555.39 | 0.00 |
May | 0.00 | 0.00 | 0.750106E+10 | 0.681688E+10 | 4677.16 | 31-MAY-23:05 | 4066.91 | 0.00 |
June | 0.00 | 0.00 | 0.126159E+11 | 0.115140E+11 | 6649.22 | 30-JUN-23:03 | 6125.67 | 0.00 |
July | 0.00 | 0.00 | 0.184611E+11 | 0.168323E+11 | 8725.89 | 31-JUL-23:03 | 7915.65 | 0.00 |
August | 0.00 | 0.00 | 0.234810E+11 | 0.217565E+11 | 9129.87 | 10-AUG-15:00 | 8340.40 | 0.00 |
September | 0.00 | 0.00 | 0.754858E+10 | 0.625710E+10 | 4695.92 | 30-SEP-23:03 | 4055.02 | 0.00 |
October | 0.00 | 0.00 | 0.119305E+11 | 0.112921E+11 | 6019.39 | 31-OCT-23:10 | 5762.25 | 0.00 |
November | 0.00 | 0.00 | 0.157137E+11 | 0.153857E+11 | 6753.21 | 08-NOV-16:50 | 6482.82 | 0.00 |
December | 0.00 | 0.00 | 0.205383E+11 | 0.203534E+11 | 8405.12 | 28-DEC-17:00 | 8237.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169967E+12 | 0.161312E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.480355E+10 | 0.464604E+10 | 2594.05 | 2455.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.234810E+11 | 0.217565E+11 | 9129.87 | 8555.39 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.320925E+11 | 0.308022E+11 | 23850.10 | 13-JAN-17:00 | 21938.85 | 0.00 |
February | 0.00 | 0.00 | 0.840515E+11 | 0.818280E+11 | 43922.37 | 22-FEB-17:00 | 42381.10 | 0.00 |
March | 0.00 | 0.00 | 0.154396E+12 | 0.151104E+12 | 75726.05 | 31-MAR-24:00 | 74721.60 | 0.00 |
April | 0.00 | 0.00 | 0.201164E+12 | 0.198084E+12 | 82575.14 | 12-APR-16:00 | 80366.38 | 0.00 |
May | 0.00 | 0.00 | 0.708705E+11 | 0.642697E+11 | 45448.22 | 31-MAY-23:05 | 39280.99 | 0.00 |
June | 0.00 | 0.00 | 0.120174E+12 | 0.109391E+12 | 64074.66 | 30-JUN-23:03 | 58892.66 | 0.00 |
July | 0.00 | 0.00 | 0.175771E+12 | 0.159717E+12 | 84021.83 | 31-JUL-23:03 | 75932.49 | 0.00 |
August | 0.00 | 0.00 | 0.220490E+12 | 0.203489E+12 | 85694.28 | 10-AUG-14:10 | 77488.61 | 0.00 |
September | 0.00 | 0.00 | 0.708500E+11 | 0.582543E+11 | 45175.31 | 30-SEP-23:03 | 38753.71 | 0.00 |
October | 0.00 | 0.00 | 0.112063E+12 | 0.105914E+12 | 56952.08 | 31-OCT-23:10 | 54416.80 | 0.00 |
November | 0.00 | 0.00 | 0.144745E+12 | 0.141662E+12 | 64021.56 | 08-NOV-16:50 | 61413.91 | 0.00 |
December | 0.00 | 0.00 | 0.184455E+12 | 0.182766E+12 | 79026.33 | 28-DEC-17:00 | 77430.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157112E+13 | 0.148728E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.320925E+11 | 0.308022E+11 | 23850.10 | 21938.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220490E+12 | 0.203489E+12 | 85694.28 | 80366.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.215532E+10 | 0.203872E+10 | 2420.34 | 12-JAN-17:00 | 2282.90 | 0.00 |
February | 0.00 | 0.00 | 0.779849E+10 | 0.756393E+10 | 4456.91 | 22-FEB-17:00 | 4294.97 | 0.00 |
March | 0.00 | 0.00 | 0.152766E+11 | 0.149294E+11 | 7540.33 | 31-MAR-24:00 | 7433.04 | 0.00 |
April | 0.00 | 0.00 | 0.202815E+11 | 0.199567E+11 | 8489.67 | 16-APR-20:35 | 8211.42 | 0.00 |
May | 0.00 | 0.00 | 0.730070E+10 | 0.662108E+10 | 4514.66 | 31-MAY-23:05 | 3883.86 | 0.00 |
June | 0.00 | 0.00 | 0.122225E+11 | 0.111251E+11 | 6476.22 | 30-JUN-23:03 | 5949.11 | 0.00 |
July | 0.00 | 0.00 | 0.177918E+11 | 0.161671E+11 | 8429.64 | 31-JUL-23:03 | 7613.93 | 0.00 |
August | 0.00 | 0.00 | 0.223391E+11 | 0.206139E+11 | 8755.14 | 10-AUG-14:00 | 7921.85 | 0.00 |
September | 0.00 | 0.00 | 0.716961E+10 | 0.589168E+10 | 4543.36 | 30-SEP-23:03 | 3896.76 | 0.00 |
October | 0.00 | 0.00 | 0.111269E+11 | 0.104950E+11 | 5592.72 | 31-OCT-23:10 | 5327.98 | 0.00 |
November | 0.00 | 0.00 | 0.139858E+11 | 0.136611E+11 | 6469.18 | 08-NOV-16:40 | 6209.86 | 0.00 |
December | 0.00 | 0.00 | 0.173841E+11 | 0.172004E+11 | 7939.28 | 28-DEC-17:00 | 7772.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154833E+12 | 0.146264E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.215532E+10 | 0.203872E+10 | 2420.34 | 2282.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223391E+11 | 0.206139E+11 | 8755.14 | 8211.42 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 10826.44 | 1019675.93 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2029.14 | 882229.64 | 11-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.87 | 1856.21 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 91.52 | 37313.25 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3941.51 | 746886.08 | 23-DEC-06:02 |
Annual Sum or Average | 0.00 | 1417.78 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 10826.44 | 1019675.93 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 170925.77 | 860188.94 | 12-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 283504.71 | 1337215.44 | 22-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 528434.62 | 1967120.80 | 13-MAR-12:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 835804.21 | 2476090.51 | 30-APR-15:33 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1128211.82 | 2764325.25 | 25-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1305086.79 | 3535742.87 | 14-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1365018.20 | 4286164.64 | 03-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1362334.66 | 4602893.85 | 03-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1096273.93 | 2979845.89 | 13-SEP-03:04 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 696750.87 | 2341256.05 | 06-OCT-04:15 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 438843.24 | 1848646.98 | 09-NOV-13:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 219234.30 | 965327.19 | 01-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 788538.61 | 0.00 | ||||
Minimum of Months | 170925.77 | 860188.94 | 0.00 | 0.00 | ||
Maximum of Months | 1365018.20 | 4602893.85 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167241.64 | 1155527.39 | 14-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 279676.11 | 2108713.26 | 25-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 521367.19 | 3497472.57 | 13-MAR-04:12 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 825084.32 | 5220768.15 | 27-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1116907.38 | 5726823.23 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1294510.73 | 5936216.04 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1354964.25 | 5958180.27 | 20-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1350730.82 | 5930366.49 | 05-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1086701.76 | 6373082.05 | 11-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 689036.00 | 5497701.76 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 432726.72 | 2373596.34 | 09-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 215317.41 | 1331690.39 | 29-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 780504.50 | 0.00 | ||||
Minimum of Months | 167241.64 | 1155527.39 | 0.00 | 0.00 | ||
Maximum of Months | 1354964.25 | 6373082.05 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 220429.59 | 592607.64 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 502253.69 | 1032257.32 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 978235.96 | 1787132.67 | 28-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1607827.17 | 2254068.01 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1135380.54 | 1805169.18 | 01-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1431203.88 | 2096746.57 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1575107.92 | 2118387.19 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1691595.28 | 2115575.99 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 911488.56 | 1413760.45 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 917394.36 | 1599819.23 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 830274.08 | 1444789.48 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 791841.80 | 1341014.40 | 28-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1052319.08 | 0.00 | ||||
Minimum of Months | 220429.59 | 592607.64 | 0.00 | 0.00 | ||
Maximum of Months | 1691595.28 | 2254068.01 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12725.24 | 41926.50 | 18-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12553.99 | 41682.57 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12447.41 | 39940.06 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 10696.57 | 36277.01 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9896.24 | 32609.93 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9207.84 | 28990.17 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 8255.75 | 26812.52 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 9171.12 | 28568.18 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 9458.85 | 31751.44 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10500.42 | 35892.60 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11718.70 | 39405.76 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12136.16 | 41492.68 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 10720.75 | ||||
Minimum of Months | 0.00 | 0.00 | 8255.75 | 26812.52 | ||
Maximum of Months | 0.00 | 0.00 | 12725.24 | 41926.50 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 197578.66 | 995982.07 | 12-JAN-15:20 | 3535.93 | 158200.63 | 21-JAN-07:10 |
February | 332803.19 | 1530463.93 | 22-FEB-15:30 | 912.38 | 155660.61 | 04-FEB-05:40 |
March | 646942.91 | 3238929.38 | 10-MAR-17:00 | 277.50 | 59626.16 | 25-MAR-21:10 |
April | 1235199.48 | 5472451.23 | 18-APR-14:00 | 396.09 | 57167.94 | 10-APR-03:00 |
May | 2559558.00 | 7386686.56 | 17-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3748470.81 | 8438067.01 | 22-JUN-15:40 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4593455.08 | 8571103.28 | 08-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4602843.50 | 8796213.50 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3290130.94 | 7982332.51 | 14-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1078965.96 | 5037288.39 | 04-OCT-11:00 | 100.19 | 60765.69 | 23-OCT-03:10 |
November | 509317.59 | 3063674.25 | 08-NOV-14:20 | 363.53 | 77123.15 | 24-NOV-03:15 |
December | 254432.80 | 1113014.02 | 01-DEC-15:00 | 1454.95 | 153537.76 | 23-DEC-07:20 |
Annual Sum or Average | 1930846.95 | 588.39 | ||||
Minimum of Months | 197578.66 | 995982.07 | 0.00 | 0.00 | ||
Maximum of Months | 4602843.50 | 8796213.50 | 3535.93 | 158200.63 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165372E+11 | 0.82 | 10670.52 | 01-JAN-00:40 | 1.42 |
February | 0.149016E+11 | 0.82 | 10670.52 | 01-FEB-05:13 | 1.42 |
March | 0.170579E+11 | 0.84 | 10670.52 | 01-MAR-05:12 | 1.42 |
April | 0.165915E+11 | 0.85 | 10670.52 | 01-APR-04:12 | 1.42 |
May | 0.179259E+11 | 0.88 | 10670.52 | 01-MAY-00:23 | 1.42 |
June | 0.179743E+11 | 0.91 | 10670.52 | 01-JUN-03:02 | 1.41 |
July | 0.186392E+11 | 0.92 | 10670.52 | 01-JUL-03:02 | 1.41 |
August | 0.197369E+11 | 0.97 | 10670.52 | 01-AUG-03:02 | 1.41 |
September | 0.183416E+11 | 0.93 | 10670.52 | 01-SEP-03:02 | 1.41 |
October | 0.186115E+11 | 0.92 | 10670.52 | 01-OCT-08:40 | 1.40 |
November | 0.176856E+11 | 0.90 | 10670.52 | 01-NOV-04:12 | 1.42 |
December | 0.171725E+11 | 0.85 | 10670.52 | 01-DEC-05:12 | 1.42 |
Annual Sum or Average | 0.211176E+12 | 0.89 | |||
Minimum of Months | 0.149016E+11 | 0.82 | 10670.52 | 1.40 | |
Maximum of Months | 0.197369E+11 | 0.97 | 10670.52 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.507476E+10 | 0.33 | 10669.90 | 02-JAN-06:01 | 1.08 |
February | 0.635898E+10 | 0.39 | 12873.93 | 21-FEB-15:50 | 1.21 |
March | 0.109605E+11 | 0.53 | 21916.38 | 11-MAR-06:02 | 1.68 |
April | 0.148515E+11 | 0.70 | 24144.69 | 03-APR-05:02 | 1.79 |
May | 0.147370E+11 | 0.68 | 24144.69 | 01-MAY-05:02 | 1.79 |
June | 0.156377E+11 | 0.71 | 24144.69 | 03-JUN-05:02 | 1.79 |
July | 0.152496E+11 | 0.69 | 24144.69 | 03-JUL-05:02 | 1.79 |
August | 0.183226E+11 | 0.77 | 24144.69 | 01-AUG-05:02 | 1.79 |
September | 0.113819E+11 | 0.58 | 24144.69 | 01-SEP-05:02 | 1.79 |
October | 0.106992E+11 | 0.53 | 24144.69 | 03-OCT-05:02 | 1.79 |
November | 0.876518E+10 | 0.45 | 16598.86 | 06-NOV-05:11 | 1.41 |
December | 0.718588E+10 | 0.39 | 11829.31 | 29-DEC-05:12 | 1.15 |
Annual Sum or Average | 0.139225E+12 | 0.56 | |||
Minimum of Months | 0.507476E+10 | 0.33 | 10669.90 | 1.08 | |
Maximum of Months | 0.183226E+11 | 0.77 | 24144.69 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.359629E+11 | 0.29 | 101211.78 | 31-JAN-06:03 | 1.08 |
February | 0.433440E+11 | 0.33 | 91594.25 | 01-FEB-06:02 | 1.02 |
March | 0.784129E+11 | 0.44 | 230250.12 | 29-MAR-04:12 | 1.79 |
April | 0.107881E+12 | 0.57 | 230250.12 | 04-APR-04:12 | 1.79 |
May | 0.130255E+12 | 0.64 | 230250.12 | 11-MAY-05:02 | 1.79 |
June | 0.129531E+12 | 0.65 | 230250.12 | 21-JUN-03:02 | 1.79 |
July | 0.114252E+12 | 0.59 | 230250.12 | 11-JUL-05:03 | 1.79 |
August | 0.115877E+12 | 0.58 | 230250.12 | 02-AUG-05:03 | 1.79 |
September | 0.945003E+11 | 0.51 | 230250.12 | 01-SEP-05:02 | 1.79 |
October | 0.816184E+11 | 0.45 | 230250.12 | 02-OCT-04:12 | 1.79 |
November | 0.577211E+11 | 0.38 | 104808.66 | 09-NOV-06:03 | 1.10 |
December | 0.406110E+11 | 0.31 | 119562.59 | 23-DEC-06:02 | 1.19 |
Annual Sum or Average | 0.102997E+13 | 0.48 | |||
Minimum of Months | 0.359629E+11 | 0.29 | 91594.25 | 1.02 | |
Maximum of Months | 0.130255E+12 | 0.65 | 230250.12 | 1.79 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.328126E+10 | 0.29 | 4924.61 | 02-JAN-05:21 | 0.67 |
February | 0.377104E+10 | 0.31 | 8581.03 | 22-FEB-15:30 | 0.90 |
March | 0.729222E+10 | 0.40 | 19408.70 | 29-MAR-04:12 | 1.48 |
April | 0.112170E+11 | 0.54 | 26197.65 | 19-APR-05:02 | 1.79 |
May | 0.140698E+11 | 0.63 | 26197.65 | 08-MAY-05:02 | 1.79 |
June | 0.141065E+11 | 0.64 | 26197.65 | 05-JUN-04:12 | 1.79 |
July | 0.120087E+11 | 0.57 | 26197.65 | 03-JUL-05:02 | 1.79 |
August | 0.117437E+11 | 0.56 | 26197.65 | 03-AUG-05:02 | 1.79 |
September | 0.945298E+10 | 0.49 | 25084.65 | 25-SEP-05:02 | 1.74 |
October | 0.780259E+10 | 0.42 | 20756.15 | 06-OCT-04:12 | 1.55 |
November | 0.507994E+10 | 0.34 | 10132.29 | 09-NOV-15:50 | 0.99 |
December | 0.338498E+10 | 0.28 | 5575.38 | 01-DEC-15:00 | 0.71 |
Annual Sum or Average | 0.103211E+12 | 0.45 | |||
Minimum of Months | 0.328126E+10 | 0.28 | 4924.61 | 0.67 | |
Maximum of Months | 0.141065E+11 | 0.64 | 26197.65 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.972689E+11 | 1.38 | 36316.05 | 01-JAN-00:10 | 1.38 |
February | 0.878558E+11 | 1.38 | 36316.05 | 01-FEB-00:10 | 1.38 |
March | 0.972689E+11 | 1.38 | 36316.05 | 01-MAR-00:10 | 1.38 |
April | 0.941312E+11 | 1.38 | 36316.05 | 01-APR-00:03 | 1.38 |
May | 0.972689E+11 | 1.38 | 36316.05 | 01-MAY-00:03 | 1.38 |
June | 0.941312E+11 | 1.38 | 36316.05 | 01-JUN-00:03 | 1.38 |
July | 0.972689E+11 | 1.38 | 36316.05 | 01-JUL-00:05 | 1.38 |
August | 0.972689E+11 | 1.38 | 36316.05 | 01-AUG-00:03 | 1.38 |
September | 0.941312E+11 | 1.38 | 36316.05 | 01-SEP-00:03 | 1.38 |
October | 0.972689E+11 | 1.38 | 36316.05 | 01-OCT-00:03 | 1.38 |
November | 0.941312E+11 | 1.38 | 36316.05 | 01-NOV-00:10 | 1.38 |
December | 0.972689E+11 | 1.38 | 36316.05 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.114526E+13 | 1.38 | |||
Minimum of Months | 0.878558E+11 | 1.38 | 36316.05 | 1.38 | |
Maximum of Months | 0.972689E+11 | 1.38 | 36316.05 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149464E+10 | 0.94 | 558.04 | 01-JAN-00:10 | 0.94 |
February | 0.135000E+10 | 0.94 | 558.04 | 01-FEB-00:10 | 0.94 |
March | 0.149464E+10 | 0.94 | 558.04 | 01-MAR-00:10 | 0.94 |
April | 0.144643E+10 | 0.94 | 558.04 | 01-APR-00:03 | 0.94 |
May | 0.149464E+10 | 0.93 | 558.04 | 01-MAY-00:03 | 0.94 |
June | 0.144643E+10 | 0.93 | 558.04 | 01-JUN-00:03 | 0.94 |
July | 0.149464E+10 | 0.93 | 558.04 | 01-JUL-00:05 | 0.94 |
August | 0.149464E+10 | 0.94 | 558.04 | 01-AUG-00:03 | 0.94 |
September | 0.144643E+10 | 0.93 | 558.04 | 01-SEP-00:03 | 0.93 |
October | 0.149464E+10 | 0.94 | 558.04 | 01-OCT-00:03 | 0.94 |
November | 0.144643E+10 | 0.94 | 558.04 | 01-NOV-00:10 | 0.94 |
December | 0.149464E+10 | 0.94 | 558.04 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.175982E+11 | 0.94 | |||
Minimum of Months | 0.135000E+10 | 0.93 | 558.04 | 0.93 | |
Maximum of Months | 0.149464E+10 | 0.94 | 558.04 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142684E+11 | 0.94 | 5327.19 | 01-JAN-00:10 | 0.94 |
February | 0.128875E+11 | 0.94 | 5327.19 | 01-FEB-00:10 | 0.94 |
March | 0.142684E+11 | 0.94 | 5327.19 | 01-MAR-00:10 | 0.94 |
April | 0.138081E+11 | 0.94 | 5327.19 | 01-APR-00:03 | 0.94 |
May | 0.142684E+11 | 0.93 | 5327.19 | 01-MAY-00:03 | 0.94 |
June | 0.138081E+11 | 0.93 | 5327.19 | 01-JUN-00:03 | 0.94 |
July | 0.142684E+11 | 0.93 | 5327.19 | 01-JUL-00:05 | 0.93 |
August | 0.142684E+11 | 0.93 | 5327.19 | 01-AUG-00:03 | 0.94 |
September | 0.138081E+11 | 0.93 | 5327.19 | 01-SEP-00:03 | 0.93 |
October | 0.142684E+11 | 0.94 | 5327.19 | 01-OCT-00:03 | 0.94 |
November | 0.138081E+11 | 0.94 | 5327.19 | 01-NOV-00:10 | 0.94 |
December | 0.142684E+11 | 0.94 | 5327.19 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.167998E+12 | 0.94 | |||
Minimum of Months | 0.128875E+11 | 0.93 | 5327.19 | 0.93 | |
Maximum of Months | 0.142684E+11 | 0.94 | 5327.19 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144231E+10 | 0.94 | 538.50 | 01-JAN-00:10 | 0.94 |
February | 0.130273E+10 | 0.94 | 538.50 | 01-FEB-00:10 | 0.94 |
March | 0.144231E+10 | 0.94 | 538.50 | 01-MAR-00:10 | 0.94 |
April | 0.139578E+10 | 0.94 | 538.50 | 01-APR-00:03 | 0.94 |
May | 0.144231E+10 | 0.93 | 538.50 | 01-MAY-00:03 | 0.94 |
June | 0.139578E+10 | 0.93 | 538.50 | 01-JUN-00:03 | 0.94 |
July | 0.144231E+10 | 0.93 | 538.50 | 01-JUL-00:05 | 0.94 |
August | 0.144231E+10 | 0.94 | 538.50 | 01-AUG-00:03 | 0.94 |
September | 0.139578E+10 | 0.93 | 538.50 | 01-SEP-00:07 | 0.93 |
October | 0.144231E+10 | 0.94 | 538.50 | 01-OCT-00:03 | 0.94 |
November | 0.139578E+10 | 0.94 | 538.50 | 01-NOV-00:10 | 0.94 |
December | 0.144231E+10 | 0.94 | 538.50 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.169820E+11 | 0.94 | |||
Minimum of Months | 0.130273E+10 | 0.93 | 538.50 | 0.93 | |
Maximum of Months | 0.144231E+10 | 0.94 | 538.50 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.125453E+09 | 0.112908E+09 | 3105.10 | 02-JAN-06:01 | 2794.59 | 2794.59 | 43.01 | 6.26 |
February | 19601509.43 | 17641358.49 | 2650.80 | 11-FEB-06:03 | 2385.72 | 2385.72 | 33.04 | 4.31 |
March | 39620.46 | 35658.42 | 7.09 | 01-MAR-06:50 | 6.38 | 6.38 | 20.64 | 0.01 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 20.54 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 20.54 | 0.00 |
November | 910267.44 | 819240.70 | 141.88 | 27-NOV-06:03 | 127.69 | 127.69 | 21.26 | 0.15 |
December | 43137297.14 | 38823567.42 | 2557.83 | 23-DEC-06:02 | 2302.05 | 2302.05 | 37.62 | 4.03 |
Annual Sum or Average | 0.189142E+09 | 0.170227E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 0.00 | |
Maximum of Months | 0.125453E+09 | 0.112908E+09 | 3105.10 | 2794.59 | 2794.59 | 43.01 | 6.26 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.145733E+09 | 0.131160E+09 | 1313.73 | 12-JAN-06:03 | 1182.36 | 1182.36 | 6.70 | 40.42 |
February | 0.276281E+09 | 0.248653E+09 | 2333.22 | 25-FEB-06:03 | 2099.90 | 2099.90 | 6.70 | 52.41 |
March | 0.705924E+09 | 0.635332E+09 | 6962.83 | 11-MAR-06:02 | 6266.55 | 6266.55 | 7.58 | 83.73 |
April | 0.133948E+10 | 0.120553E+10 | 19235.44 | 27-APR-05:02 | 17311.89 | 17311.89 | 9.05 | 126.23 |
May | 0.185154E+10 | 0.166639E+10 | 21769.63 | 08-MAY-05:02 | 19592.67 | 19592.67 | 9.14 | 132.54 |
June | 0.214608E+10 | 0.193147E+10 | 21769.63 | 08-JUN-05:02 | 19592.67 | 19592.67 | 9.36 | 132.54 |
July | 0.225194E+10 | 0.202674E+10 | 21769.63 | 18-JUL-05:02 | 19592.67 | 19592.67 | 7.29 | 132.54 |
August | 0.231913E+10 | 0.208721E+10 | 21769.63 | 01-AUG-05:02 | 19592.67 | 19592.67 | 9.70 | 132.54 |
September | 0.164791E+10 | 0.148311E+10 | 21769.63 | 05-SEP-05:02 | 19592.67 | 19592.67 | 9.70 | 132.54 |
October | 0.106210E+10 | 0.955894E+09 | 21769.63 | 04-OCT-05:02 | 19592.67 | 19592.67 | 9.53 | 132.54 |
November | 0.637235E+09 | 0.573511E+09 | 3128.01 | 09-NOV-06:03 | 2815.21 | 2815.21 | 6.71 | 59.61 |
December | 0.210269E+09 | 0.189243E+09 | 1271.41 | 29-DEC-06:02 | 1144.27 | 1144.27 | 6.70 | 39.81 |
Annual Sum or Average | 0.145936E+11 | 0.131342E+11 | ||||||
Minimum of Months | 0.145733E+09 | 0.131160E+09 | 1271.41 | 1144.27 | 1144.27 | 6.70 | 39.81 | |
Maximum of Months | 0.231913E+10 | 0.208721E+10 | 21769.63 | 19592.67 | 19592.67 | 9.70 | 132.54 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112430E+11 | 0.101187E+11 | 7491.72 | 01-JAN-00:45 | 6742.55 | 6742.55 | 6.74 | 66.27 |
February | 0.109117E+11 | 0.982053E+10 | 7491.72 | 01-FEB-05:13 | 6742.55 | 6742.55 | 7.40 | 66.27 |
March | 0.146471E+11 | 0.131824E+11 | 7491.72 | 01-MAR-05:12 | 6742.55 | 6742.55 | 8.68 | 66.27 |
April | 0.179786E+11 | 0.161807E+11 | 7491.72 | 01-APR-00:10 | 6742.55 | 6742.55 | 6.84 | 66.27 |
May | 0.183858E+11 | 0.165472E+11 | 7491.72 | 01-MAY-00:03 | 6742.55 | 6742.55 | 8.00 | 66.27 |
June | 0.179159E+11 | 0.161243E+11 | 7491.72 | 01-JUN-01:03 | 6742.55 | 6742.55 | 6.96 | 66.27 |
July | 0.188716E+11 | 0.169844E+11 | 7491.72 | 01-JUL-00:05 | 6742.55 | 6742.55 | 9.14 | 66.27 |
August | 0.189476E+11 | 0.170528E+11 | 7491.72 | 01-AUG-00:03 | 6742.55 | 6742.55 | 10.80 | 66.27 |
September | 0.165894E+11 | 0.149305E+11 | 7491.72 | 01-SEP-00:03 | 6742.55 | 6742.55 | 8.72 | 66.27 |
October | 0.154210E+11 | 0.138789E+11 | 7491.72 | 01-OCT-00:03 | 6742.55 | 6742.55 | 8.88 | 66.27 |
November | 0.128528E+11 | 0.115675E+11 | 7491.72 | 01-NOV-04:12 | 6742.55 | 6742.55 | 10.05 | 66.27 |
December | 0.120361E+11 | 0.108324E+11 | 7491.72 | 01-DEC-05:12 | 6742.55 | 6742.55 | 8.39 | 66.27 |
Annual Sum or Average | 0.185800E+12 | 0.167220E+12 | ||||||
Minimum of Months | 0.109117E+11 | 0.982053E+10 | 7491.72 | 6742.55 | 6742.55 | 6.74 | 66.27 | |
Maximum of Months | 0.189476E+11 | 0.170528E+11 | 7491.72 | 6742.55 | 6742.55 | 10.80 | 66.27 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 6.74 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 7.09 | 0.00 |
March | 0.144740E+10 | 0.130266E+10 | 7491.72 | 06-MAR-14:00 | 6742.55 | 6742.55 | 12.05 | 33.14 |
April | 0.448544E+10 | 0.403690E+10 | 7491.72 | 03-APR-08:50 | 6742.55 | 6742.55 | 11.97 | 33.14 |
May | 0.777330E+10 | 0.699597E+10 | 7491.72 | 01-MAY-07:10 | 6742.55 | 6742.55 | 12.31 | 33.14 |
June | 0.898120E+10 | 0.808308E+10 | 7491.72 | 01-JUN-05:05 | 6742.55 | 6742.55 | 12.71 | 33.14 |
July | 0.975171E+10 | 0.877654E+10 | 7491.72 | 01-JUL-05:03 | 6742.55 | 6742.55 | 12.82 | 33.14 |
August | 0.103755E+11 | 0.933797E+10 | 7491.72 | 01-AUG-05:04 | 6742.55 | 6742.55 | 13.69 | 33.14 |
September | 0.748105E+10 | 0.673295E+10 | 7491.72 | 01-SEP-05:03 | 6742.55 | 6742.55 | 13.90 | 33.14 |
October | 0.360030E+10 | 0.324027E+10 | 7491.72 | 02-OCT-08:70 | 6742.55 | 6742.55 | 12.10 | 33.14 |
November | 0.602335E+09 | 0.542101E+09 | 7491.72 | 01-NOV-14:30 | 6742.55 | 6742.55 | 12.39 | 33.14 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 7.35 | 0.00 |
Annual Sum or Average | 0.544983E+11 | 0.490484E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 0.00 | |
Maximum of Months | 0.103755E+11 | 0.933797E+10 | 7491.72 | 6742.55 | 6742.55 | 13.90 | 33.14 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-JAN-00:10 | 3198.09 | 3198.09 | 21.45 | 14.84 |
February | 0.859646E+10 | 0.773682E+10 | 3553.43 | 01-FEB-00:10 | 3198.09 | 3198.09 | 24.16 | 14.84 |
March | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-MAR-00:10 | 3198.09 | 3198.09 | 28.60 | 14.84 |
April | 0.921050E+10 | 0.828945E+10 | 3553.43 | 01-APR-00:03 | 3198.09 | 3198.09 | 42.46 | 14.84 |
May | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-MAY-00:03 | 3198.09 | 3198.09 | 37.85 | 14.84 |
June | 0.921050E+10 | 0.828945E+10 | 3553.43 | 01-JUN-00:03 | 3198.09 | 3198.09 | 38.99 | 14.84 |
July | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-JUL-00:05 | 3198.09 | 3198.09 | 49.09 | 14.84 |
August | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-AUG-00:03 | 3198.09 | 3198.09 | 49.26 | 14.84 |
September | 0.921050E+10 | 0.828945E+10 | 3553.43 | 01-SEP-00:03 | 3198.09 | 3198.09 | 36.36 | 14.84 |
October | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-OCT-00:03 | 3198.09 | 3198.09 | 37.36 | 14.84 |
November | 0.921050E+10 | 0.828945E+10 | 3553.43 | 01-NOV-00:10 | 3198.09 | 3198.09 | 31.85 | 14.84 |
December | 0.951751E+10 | 0.856576E+10 | 3553.43 | 01-DEC-00:10 | 3198.09 | 3198.09 | 29.82 | 14.84 |
Annual Sum or Average | 0.112061E+12 | 0.100855E+12 | ||||||
Minimum of Months | 0.859646E+10 | 0.773682E+10 | 3553.43 | 3198.09 | 3198.09 | 21.45 | 14.84 | |
Maximum of Months | 0.951751E+10 | 0.856576E+10 | 3553.43 | 3198.09 | 3198.09 | 49.26 | 14.84 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.33 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.08 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.06 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.34 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.69 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.77 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.55 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.40 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.55 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.11 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.25 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.06 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.77 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.289638E+11 | 0.260674E+11 | 19327.50 | 12-JAN-15:20 | 17394.75 | 17394.75 | 24.15 | 78.16 |
February | 0.281230E+11 | 0.253107E+11 | 19352.09 | 22-FEB-15:30 | 17416.88 | 17416.88 | 25.79 | 78.16 |
March | 0.396419E+11 | 0.356777E+11 | 38713.11 | 10-MAR-17:00 | 34841.80 | 34841.80 | 26.06 | 156.31 |
April | 0.552937E+11 | 0.497643E+11 | 38802.56 | 18-APR-12:20 | 34922.30 | 34922.30 | 28.89 | 156.31 |
May | 0.649527E+11 | 0.584574E+11 | 38802.56 | 01-MAY-15:00 | 34922.30 | 34922.30 | 28.82 | 156.31 |
June | 0.676664E+11 | 0.608997E+11 | 38802.56 | 05-JUN-14:10 | 34922.30 | 34922.30 | 28.85 | 156.31 |
July | 0.727953E+11 | 0.655158E+11 | 38802.56 | 01-JUL-05:05 | 34922.30 | 34922.30 | 28.93 | 156.31 |
August | 0.742363E+11 | 0.668127E+11 | 38802.56 | 01-AUG-05:04 | 34922.30 | 34922.30 | 29.05 | 156.31 |
September | 0.600467E+11 | 0.540420E+11 | 38802.56 | 01-SEP-05:03 | 34922.30 | 34922.30 | 28.98 | 156.31 |
October | 0.465984E+11 | 0.419386E+11 | 38802.56 | 04-OCT-11:00 | 34922.30 | 34922.30 | 28.81 | 156.31 |
November | 0.335819E+11 | 0.302237E+11 | 38704.41 | 08-NOV-14:20 | 34833.97 | 34833.97 | 25.79 | 156.31 |
December | 0.310119E+11 | 0.279107E+11 | 19332.48 | 01-DEC-15:00 | 17399.23 | 17399.23 | 24.51 | 78.16 |
Annual Sum or Average | 0.602912E+12 | 0.542621E+12 | ||||||
Minimum of Months | 0.281230E+11 | 0.253107E+11 | 19327.50 | 17394.75 | 17394.75 | 24.15 | 78.16 | |
Maximum of Months | 0.742363E+11 | 0.668127E+11 | 38802.56 | 34922.30 | 34922.30 | 29.05 | 156.31 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.12 | 52.12 | 10826.44 | 1019675.93 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 25.21 | 25.21 | 2029.14 | 882229.64 | 11-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 20.67 | 20.67 | 3.87 | 1856.21 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 20.54 | 20.54 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 20.54 | 20.54 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 20.54 | 20.54 | 91.52 | 37313.25 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.25 | 21.25 | 3941.51 | 746886.08 | 23-DEC-06:02 |
Annual Sum or Average | 0.00 | 1417.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 52.12 | 52.12 | 10826.44 | 1019675.93 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 170925.77 | 860188.94 | 12-JAN-15:20 | 9.80 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 283504.71 | 1337215.44 | 22-FEB-15:30 | 11.52 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 528434.62 | 1967120.80 | 13-MAR-12:10 | 10.24 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 835804.21 | 2476090.51 | 30-APR-15:33 | 11.16 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1128211.82 | 2764325.25 | 25-MAY-05:04 | 11.68 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1305086.79 | 3535742.87 | 14-JUN-05:02 | 13.07 | 7.36 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1365018.20 | 4286164.64 | 03-JUL-05:03 | 14.43 | 8.71 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1362334.66 | 4602893.85 | 03-AUG-05:03 | 15.00 | 9.28 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1096273.93 | 2979845.89 | 13-SEP-03:04 | 12.07 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 696750.87 | 2341256.05 | 06-OCT-04:15 | 10.92 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 438843.24 | 1848646.98 | 09-NOV-13:10 | 13.36 | 8.23 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 219234.30 | 965327.19 | 01-DEC-15:00 | 10.18 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 788538.61 | 0.00 | ||||||
Minimum of Months | 170925.77 | 860188.94 | 9.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1365018.20 | 4602893.85 | 15.00 | 9.28 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 167241.64 | 1155527.39 | 14-JAN-06:03 | 14.84 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 279676.11 | 2108713.26 | 25-FEB-06:03 | 16.32 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 521367.19 | 3497472.57 | 13-MAR-04:12 | 16.97 | 8.59 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 825084.32 | 5220768.15 | 27-APR-05:02 | 16.59 | 11.38 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1116907.38 | 5726823.23 | 24-MAY-05:02 | 17.03 | 11.85 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1294510.73 | 5936216.04 | 29-JUN-05:02 | 17.41 | 12.04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1354964.25 | 5958180.27 | 20-JUL-05:02 | 17.55 | 12.06 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1350730.82 | 5930366.49 | 05-AUG-05:02 | 17.40 | 12.03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1086701.76 | 6373082.05 | 11-SEP-03:02 | 18.20 | 12.43 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 689036.00 | 5497701.76 | 04-OCT-05:02 | 16.61 | 11.64 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 432726.72 | 2373596.34 | 09-NOV-06:03 | 16.22 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 215317.41 | 1331690.39 | 29-DEC-06:02 | 14.69 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 780504.50 | 0.00 | ||||||
Minimum of Months | 167241.64 | 1155527.39 | 14.69 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1354964.25 | 6373082.05 | 18.20 | 12.43 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 220429.59 | 592607.64 | 12-JAN-15:00 | 29.74 | 25.65 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 502253.69 | 1032257.32 | 22-FEB-15:00 | 38.04 | 30.79 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 978235.96 | 1787132.67 | 28-MAR-15:20 | 52.01 | 41.19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1607827.17 | 2254068.01 | 15-APR-15:00 | 60.48 | 47.26 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1135380.54 | 1805169.18 | 01-MAY-15:00 | 52.34 | 46.98 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1431203.88 | 2096746.57 | 08-JUN-16:00 | 57.64 | 49.08 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1575107.92 | 2118387.19 | 07-JUL-15:00 | 58.03 | 46.46 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1691595.28 | 2115575.99 | 07-AUG-15:00 | 57.98 | 44.41 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 911488.56 | 1413760.45 | 17-SEP-20:00 | 45.15 | 40.10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 917394.36 | 1599819.23 | 02-OCT-15:00 | 48.58 | 40.55 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 830274.08 | 1444789.48 | 08-NOV-15:00 | 45.72 | 35.27 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 791841.80 | 1341014.40 | 28-DEC-14:30 | 43.80 | 31.07 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1052319.08 | 0.00 | ||||||
Minimum of Months | 220429.59 | 592607.64 | 29.74 | 25.65 | 0.00 | 0.00 | ||
Maximum of Months | 1691595.28 | 2254068.01 | 60.48 | 49.08 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.15 | 58.15 | 12725.24 | 41926.50 | 18-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.31 | 57.31 | 12553.99 | 41682.57 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.48 | 56.48 | 12447.41 | 39940.06 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.69 | 57.69 | 10696.57 | 36277.01 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.08 | 57.08 | 9896.24 | 32609.93 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.06 | 58.06 | 9207.84 | 28990.17 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 58.35 | 58.35 | 8255.75 | 26812.52 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.62 | 57.62 | 9171.12 | 28568.18 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.77 | 57.77 | 9458.85 | 31751.44 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.66 | 57.66 | 10500.42 | 35892.60 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.74 | 57.74 | 11718.70 | 39405.76 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.96 | 56.96 | 12136.16 | 41492.68 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 10720.75 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.48 | 56.48 | 8255.75 | 26812.52 | ||
Maximum of Months | 0.00 | 0.00 | 58.35 | 58.35 | 12725.24 | 41926.50 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 197578.66 | 995982.07 | 12-JAN-15:20 | 24.15 | 21.10 | 3535.93 | 158200.63 | 21-JAN-07:10 |
February | 332803.19 | 1530463.93 | 22-FEB-15:30 | 25.79 | 21.10 | 912.38 | 155660.61 | 04-FEB-05:40 |
March | 646942.91 | 3238929.38 | 10-MAR-17:00 | 26.06 | 23.16 | 277.50 | 59626.16 | 25-MAR-21:10 |
April | 1235199.48 | 5472451.23 | 18-APR-14:00 | 29.48 | 25.66 | 396.09 | 57167.94 | 10-APR-03:00 |
May | 2559558.00 | 7386686.56 | 17-MAY-15:30 | 32.41 | 27.94 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3748470.81 | 8438067.01 | 22-JUN-15:40 | 34.01 | 29.04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4593455.08 | 8571103.28 | 08-JUL-05:03 | 34.22 | 29.10 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4602843.50 | 8796213.50 | 28-AUG-05:03 | 34.56 | 29.21 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3290130.94 | 7982332.51 | 14-SEP-15:30 | 33.32 | 28.81 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1078965.96 | 5037288.39 | 04-OCT-11:00 | 28.81 | 25.19 | 100.19 | 60765.69 | 23-OCT-03:10 |
November | 509317.59 | 3063674.25 | 08-NOV-14:20 | 25.79 | 21.29 | 363.53 | 77123.15 | 24-NOV-03:15 |
December | 254432.80 | 1113014.02 | 01-DEC-15:00 | 24.51 | 21.10 | 1454.95 | 153537.76 | 23-DEC-07:20 |
Annual Sum or Average | 1930846.95 | 588.39 | ||||||
Minimum of Months | 197578.66 | 995982.07 | 24.15 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 4602843.50 | 8796213.50 | 34.56 | 29.21 | 3535.93 | 158200.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.153912E+09 | 0.00 | 0.472267E+11 | 0.507476E+10 | 0.00 | 0.00 |
February | 3176272.56 | 0.00 | 0.686908E+11 | 0.635898E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.132337E+12 | 0.109605E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.198110E+12 | 0.148515E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.246116E+12 | 0.147370E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.284024E+12 | 0.156377E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.318965E+12 | 0.152496E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.340938E+12 | 0.183226E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.241257E+12 | 0.113819E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.163027E+12 | 0.106992E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.107665E+12 | 0.876518E+10 | 0.00 | 0.00 |
December | 12977727.60 | 0.00 | 0.689612E+11 | 0.718588E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.170066E+09 | 0.00 | 0.221732E+13 | 0.139225E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.472267E+11 | 0.507476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153912E+09 | 0.00 | 0.340938E+12 | 0.183226E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.211542E+11 | 0.00 | 0.318146E+12 | 0.359629E+11 | 0.00 | 0.00 |
February | 0.334054E+10 | 0.00 | 0.498530E+12 | 0.433440E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.103554E+13 | 0.784129E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.160523E+13 | 0.107881E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.231885E+13 | 0.130255E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.260231E+13 | 0.129531E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.280961E+13 | 0.114252E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276165E+13 | 0.115877E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.214980E+13 | 0.945003E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.137653E+13 | 0.816184E+11 | 0.00 | 0.00 |
November | 35791479.56 | 0.00 | 0.808469E+12 | 0.577211E+11 | 0.00 | 0.00 |
December | 0.719548E+10 | 0.00 | 0.410344E+12 | 0.406110E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.317260E+11 | 0.00 | 0.186950E+14 | 0.102997E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.318146E+12 | 0.359629E+11 | 0.00 | 0.00 |
Maximum of Months | 0.211542E+11 | 0.00 | 0.280961E+13 | 0.130255E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.804671E+10 | 0.00 | 0.268379E+11 | 0.328126E+10 | 0.00 | 0.00 |
February | 0.162435E+10 | 0.00 | 0.458764E+11 | 0.377104E+10 | 0.00 | 0.00 |
March | 10925196.54 | 0.00 | 0.105332E+12 | 0.729222E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.174278E+12 | 0.112170E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.254142E+12 | 0.140698E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.283420E+12 | 0.141065E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.299312E+12 | 0.120087E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290858E+12 | 0.117437E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.223382E+12 | 0.945298E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.139219E+12 | 0.780259E+10 | 0.00 | 0.00 |
November | 0.200903E+09 | 0.00 | 0.754145E+11 | 0.507994E+10 | 0.00 | 0.00 |
December | 0.344461E+10 | 0.00 | 0.332055E+11 | 0.338498E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.133275E+11 | 0.00 | 0.195128E+13 | 0.103211E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.268379E+11 | 0.328126E+10 | 0.00 | 0.00 |
Maximum of Months | 0.804671E+10 | 0.00 | 0.299312E+12 | 0.141065E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.567563E+11 | 0.165372E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.591410E+11 | 0.149016E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.818882E+11 | 0.170579E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.943728E+11 | 0.165915E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.119548E+12 | 0.179259E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139764E+12 | 0.179743E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.160186E+12 | 0.186392E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.178808E+12 | 0.197369E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.140860E+12 | 0.183416E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104954E+12 | 0.186115E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.819923E+11 | 0.176856E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.655413E+11 | 0.171725E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128381E+13 | 0.211176E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.567563E+11 | 0.149016E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.178808E+12 | 0.197369E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.426178E+12 | 0.196978E+12 | 0.00 | 4.45 |
February | 0.00 | 0.00 | 0.676603E+12 | 0.243217E+12 | 0.00 | 4.85 |
March | 0.00 | 0.00 | 0.109362E+13 | 0.359701E+12 | 0.00 | 2.47 |
April | 0.00 | 0.00 | 0.140864E+13 | 0.467091E+12 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.514662E+12 | 0.247110E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.848098E+12 | 0.341325E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.121770E+13 | 0.438742E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149621E+13 | 0.491518E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.501562E+12 | 0.227323E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.802970E+12 | 0.297562E+12 | 0.00 | 0.48 |
November | 0.00 | 0.00 | 0.105023E+13 | 0.338628E+12 | 0.00 | 5.02 |
December | 0.00 | 0.00 | 0.137116E+13 | 0.402581E+12 | 0.00 | 12.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.114076E+14 | 0.405178E+13 | 0.00 | 30.36 |
Minimum of Months | 0.00 | 0.00 | 0.426178E+12 | 0.196978E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149621E+13 | 0.491518E+12 | 0.00 | 12.74 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.606809E+10 | 0.275919E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121684E+11 | 0.390986E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213669E+11 | 0.644895E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.290723E+11 | 0.916646E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.104852E+11 | 0.447878E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.176287E+11 | 0.645923E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.254127E+11 | 0.844618E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.319229E+11 | 0.993652E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.101592E+11 | 0.405706E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157800E+11 | 0.534415E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.201184E+11 | 0.585110E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256334E+11 | 0.658975E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.225816E+12 | 0.734472E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.606809E+10 | 0.275919E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.319229E+11 | 0.993652E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.407562E+11 | 0.229320E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.106578E+12 | 0.354143E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.200865E+12 | 0.607375E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.273486E+12 | 0.861301E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.989456E+11 | 0.423435E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167630E+12 | 0.612638E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.241504E+12 | 0.800015E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.299281E+12 | 0.930594E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.952337E+11 | 0.381918E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148098E+12 | 0.503040E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.185327E+12 | 0.543892E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.230398E+12 | 0.602105E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208810E+13 | 0.684978E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.407562E+11 | 0.229320E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.299281E+12 | 0.930594E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.275657E+10 | 0.204356E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.992371E+10 | 0.342794E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199227E+11 | 0.608842E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.276400E+11 | 0.875432E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.102092E+11 | 0.435080E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.170799E+11 | 0.625313E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.244905E+11 | 0.814098E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.304004E+11 | 0.950360E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.965188E+10 | 0.387805E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.147389E+11 | 0.505427E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179619E+11 | 0.537187E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.217862E+11 | 0.584432E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206562E+12 | 0.687113E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.275657E+10 | 0.204356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.304004E+11 | 0.950360E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.507476E+10 | 0.472267E+11 | 0.153912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635898E+10 | 0.686908E+11 | 3176272.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109605E+11 | 0.132337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148515E+11 | 0.198110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147370E+11 | 0.246116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156377E+11 | 0.284024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152496E+11 | 0.318965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183226E+11 | 0.340938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113819E+11 | 0.241257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106992E+11 | 0.163027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876518E+10 | 0.107665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718588E+10 | 0.689612E+11 | 12977727.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139225E+12 | 0.221732E+13 | 0.170066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.507476E+10 | 0.472267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183226E+11 | 0.340938E+12 | 0.153912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.359629E+11 | 0.318146E+12 | 0.211542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433440E+11 | 0.498530E+12 | 0.334054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784129E+11 | 0.103554E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107881E+12 | 0.160523E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130255E+12 | 0.231885E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129531E+12 | 0.260231E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114252E+12 | 0.280961E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115877E+12 | 0.276165E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945003E+11 | 0.214980E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816184E+11 | 0.137653E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.577211E+11 | 0.808469E+12 | 35791479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406110E+11 | 0.410344E+12 | 0.719548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102997E+13 | 0.186950E+14 | 0.317260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359629E+11 | 0.318146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130255E+12 | 0.280961E+13 | 0.211542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.328126E+10 | 0.268379E+11 | 0.804671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.377104E+10 | 0.458764E+11 | 0.162435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729222E+10 | 0.105332E+12 | 10925196.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112170E+11 | 0.174278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140698E+11 | 0.254142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141065E+11 | 0.283420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120087E+11 | 0.299312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117437E+11 | 0.290858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945298E+10 | 0.223382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780259E+10 | 0.139219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507994E+10 | 0.754145E+11 | 0.200903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338498E+10 | 0.332055E+11 | 0.344461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103211E+12 | 0.195128E+13 | 0.133275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328126E+10 | 0.268379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141065E+11 | 0.299312E+12 | 0.804671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165372E+11 | 0.567563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149016E+11 | 0.591410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170579E+11 | 0.818882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165915E+11 | 0.943728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179259E+11 | 0.119548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179743E+11 | 0.139764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186392E+11 | 0.160186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197369E+11 | 0.178808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183416E+11 | 0.140860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186115E+11 | 0.104954E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176856E+11 | 0.819923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171725E+11 | 0.655413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211176E+12 | 0.128381E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149016E+11 | 0.567563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197369E+11 | 0.178808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.972689E+11 | 0.338440E+12 | 0.00 | 0.00 | 0.00 | 0.119170E+11 | 0.00 | 0.00 |
February | 0.878558E+11 | 0.534272E+12 | 0.00 | 0.00 | 0.00 | 0.129713E+11 | 0.00 | 0.00 |
March | 0.972689E+11 | 0.837819E+12 | 0.00 | 0.00 | 0.00 | 0.660291E+10 | 0.00 | 0.00 |
April | 0.941312E+11 | 0.103660E+13 | 0.00 | 0.00 | 0.00 | 0.916485E+09 | 0.00 | 0.00 |
May | 0.972689E+11 | 0.364838E+12 | 0.00 | 0.00 | 0.00 | 16596933.57 | 0.00 | 0.00 |
June | 0.941312E+11 | 0.600904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.972689E+11 | 0.876224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.972689E+11 | 0.110196E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.941312E+11 | 0.368369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.972689E+11 | 0.603967E+12 | 0.00 | 0.00 | 0.00 | 0.128431E+10 | 0.00 | 0.00 |
November | 0.941312E+11 | 0.819233E+12 | 0.00 | 0.00 | 0.00 | 0.134384E+11 | 0.00 | 0.00 |
December | 0.972689E+11 | 0.110011E+13 | 0.00 | 0.00 | 0.00 | 0.341035E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.114526E+13 | 0.858273E+13 | 0.00 | 0.00 | 0.00 | 0.812505E+11 | 0.00 | 0.00 |
Minimum of Months | 0.878558E+11 | 0.338440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972689E+11 | 0.110196E+13 | 0.00 | 0.00 | 0.00 | 0.341035E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149464E+10 | 0.480355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135000E+10 | 0.960852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149464E+10 | 0.164126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144643E+10 | 0.213523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149464E+10 | 0.750106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144643E+10 | 0.126159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149464E+10 | 0.184611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149464E+10 | 0.234810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144643E+10 | 0.754858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149464E+10 | 0.119305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144643E+10 | 0.157137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149464E+10 | 0.205383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175982E+11 | 0.169967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135000E+10 | 0.480355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149464E+10 | 0.234810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142684E+11 | 0.320925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128875E+11 | 0.840515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142684E+11 | 0.154396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138081E+11 | 0.201164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142684E+11 | 0.708705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138081E+11 | 0.120174E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142684E+11 | 0.175771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142684E+11 | 0.220490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138081E+11 | 0.708500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142684E+11 | 0.112063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138081E+11 | 0.144745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142684E+11 | 0.184455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167998E+12 | 0.157112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128875E+11 | 0.320925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142684E+11 | 0.220490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144231E+10 | 0.215532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130273E+10 | 0.779849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144231E+10 | 0.152766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139578E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144231E+10 | 0.730070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139578E+10 | 0.122225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144231E+10 | 0.177918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144231E+10 | 0.223391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139578E+10 | 0.716961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144231E+10 | 0.111269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139578E+10 | 0.139858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144231E+10 | 0.173841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169820E+11 | 0.154833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130273E+10 | 0.215532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144231E+10 | 0.223391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.507476E+10 | 0.153912E+09 | 0.472267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.635898E+10 | 3176272.56 | 0.686908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109605E+11 | 0.00 | 0.132337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148515E+11 | 0.00 | 0.198110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147370E+11 | 0.00 | 0.246116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156377E+11 | 0.00 | 0.284024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152496E+11 | 0.00 | 0.318965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.183226E+11 | 0.00 | 0.340938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113819E+11 | 0.00 | 0.241257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106992E+11 | 0.00 | 0.163027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876518E+10 | 0.00 | 0.107665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718588E+10 | 12977727.60 | 0.689612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139225E+12 | 0.170066E+09 | 0.221732E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.507476E+10 | 0.00 | 0.472267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.183226E+11 | 0.153912E+09 | 0.340938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.359629E+11 | 0.211542E+11 | 0.318146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433440E+11 | 0.334054E+10 | 0.498530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784129E+11 | 0.00 | 0.103554E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107881E+12 | 0.00 | 0.160523E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130255E+12 | 0.00 | 0.231885E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129531E+12 | 0.00 | 0.260231E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114252E+12 | 0.00 | 0.280961E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115877E+12 | 0.00 | 0.276165E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945003E+11 | 0.00 | 0.214980E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816184E+11 | 0.00 | 0.137653E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.577211E+11 | 35791479.56 | 0.808469E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406110E+11 | 0.719548E+10 | 0.410344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102997E+13 | 0.317260E+11 | 0.186950E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359629E+11 | 0.00 | 0.318146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130255E+12 | 0.211542E+11 | 0.280961E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.328126E+10 | 0.804671E+10 | 0.268379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.377104E+10 | 0.162435E+10 | 0.458764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729222E+10 | 10925196.54 | 0.105332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112170E+11 | 0.00 | 0.174278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140698E+11 | 0.00 | 0.254142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141065E+11 | 0.00 | 0.283420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120087E+11 | 0.00 | 0.299312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117437E+11 | 0.00 | 0.290858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945298E+10 | 0.00 | 0.223382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780259E+10 | 0.00 | 0.139219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507994E+10 | 0.200903E+09 | 0.754145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338498E+10 | 0.344461E+10 | 0.332055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103211E+12 | 0.133275E+11 | 0.195128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328126E+10 | 0.00 | 0.268379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141065E+11 | 0.804671E+10 | 0.299312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165372E+11 | 0.00 | 0.567563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149016E+11 | 0.00 | 0.591410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170579E+11 | 0.00 | 0.818882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165915E+11 | 0.00 | 0.943728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179259E+11 | 0.00 | 0.119548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179743E+11 | 0.00 | 0.139764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.186392E+11 | 0.00 | 0.160186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197369E+11 | 0.00 | 0.178808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.183416E+11 | 0.00 | 0.140860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186115E+11 | 0.00 | 0.104954E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176856E+11 | 0.00 | 0.819923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171725E+11 | 0.00 | 0.655413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211176E+12 | 0.00 | 0.128381E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149016E+11 | 0.00 | 0.567563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197369E+11 | 0.00 | 0.178808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.972689E+11 | 0.00 | 0.426178E+12 | 0.00 | 0.877380E+11 | 0.00 | 0.00 | 0.00 | 0.119707E+11 | 0.00 | 0.00 | 0.00 |
February | 0.878558E+11 | 0.00 | 0.676603E+12 | 0.00 | 0.142331E+12 | 0.00 | 0.00 | 0.00 | 0.130297E+11 | 0.00 | 0.00 | 0.00 |
March | 0.972689E+11 | 0.00 | 0.109362E+13 | 0.00 | 0.255799E+12 | 0.00 | 0.00 | 0.00 | 0.663263E+10 | 0.00 | 0.00 | 0.00 |
April | 0.941312E+11 | 0.00 | 0.140864E+13 | 0.00 | 0.372040E+12 | 0.00 | 0.00 | 0.00 | 0.920610E+09 | 0.00 | 0.00 | 0.00 |
May | 0.972689E+11 | 0.00 | 0.514662E+12 | 0.00 | 0.149824E+12 | 0.00 | 0.00 | 0.00 | 16671643.09 | 0.00 | 0.00 | 0.00 |
June | 0.941312E+11 | 0.00 | 0.848098E+12 | 0.00 | 0.247194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.972689E+11 | 0.00 | 0.121770E+13 | 0.00 | 0.341473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.972689E+11 | 0.00 | 0.149621E+13 | 0.00 | 0.394249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.941312E+11 | 0.00 | 0.501562E+12 | 0.00 | 0.133192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.972689E+11 | 0.00 | 0.802970E+12 | 0.00 | 0.199003E+12 | 0.00 | 0.00 | 0.00 | 0.129009E+10 | 0.00 | 0.00 | 0.00 |
November | 0.941312E+11 | 0.00 | 0.105023E+13 | 0.00 | 0.230997E+12 | 0.00 | 0.00 | 0.00 | 0.134989E+11 | 0.00 | 0.00 | 0.00 |
December | 0.972689E+11 | 0.00 | 0.137116E+13 | 0.00 | 0.271056E+12 | 0.00 | 0.00 | 0.00 | 0.342570E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114526E+13 | 0.00 | 0.114076E+14 | 0.00 | 0.282490E+13 | 0.00 | 0.00 | 0.00 | 0.816162E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.878558E+11 | 0.00 | 0.426178E+12 | 0.00 | 0.877380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972689E+11 | 0.00 | 0.149621E+13 | 0.00 | 0.394249E+12 | 0.00 | 0.00 | 0.00 | 0.342570E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149464E+10 | 0.00 | 0.606809E+10 | 0.00 | 0.126454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135000E+10 | 0.00 | 0.121684E+11 | 0.00 | 0.255985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149464E+10 | 0.00 | 0.213669E+11 | 0.00 | 0.495430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144643E+10 | 0.00 | 0.290723E+11 | 0.00 | 0.772003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149464E+10 | 0.00 | 0.104852E+11 | 0.00 | 0.298414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144643E+10 | 0.00 | 0.176287E+11 | 0.00 | 0.501280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149464E+10 | 0.00 | 0.254127E+11 | 0.00 | 0.695154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149464E+10 | 0.00 | 0.319229E+11 | 0.00 | 0.844187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144643E+10 | 0.00 | 0.101592E+11 | 0.00 | 0.261063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149464E+10 | 0.00 | 0.157800E+11 | 0.00 | 0.384951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144643E+10 | 0.00 | 0.201184E+11 | 0.00 | 0.440467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149464E+10 | 0.00 | 0.256334E+11 | 0.00 | 0.509511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175982E+11 | 0.00 | 0.225816E+12 | 0.00 | 0.558490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135000E+10 | 0.00 | 0.606809E+10 | 0.00 | 0.126454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149464E+10 | 0.00 | 0.319229E+11 | 0.00 | 0.844187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142684E+11 | 0.00 | 0.407562E+11 | 0.00 | 0.866364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128875E+11 | 0.00 | 0.106578E+12 | 0.00 | 0.225268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142684E+11 | 0.00 | 0.200865E+12 | 0.00 | 0.464691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138081E+11 | 0.00 | 0.273486E+12 | 0.00 | 0.723220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142684E+11 | 0.00 | 0.989456E+11 | 0.00 | 0.280751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138081E+11 | 0.00 | 0.167630E+12 | 0.00 | 0.474557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142684E+11 | 0.00 | 0.241504E+12 | 0.00 | 0.657331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142684E+11 | 0.00 | 0.299281E+12 | 0.00 | 0.787911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138081E+11 | 0.00 | 0.952337E+11 | 0.00 | 0.243837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142684E+11 | 0.00 | 0.148098E+12 | 0.00 | 0.360357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138081E+11 | 0.00 | 0.185327E+12 | 0.00 | 0.405812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142684E+11 | 0.00 | 0.230398E+12 | 0.00 | 0.459422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167998E+12 | 0.00 | 0.208810E+13 | 0.00 | 0.516979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128875E+11 | 0.00 | 0.407562E+11 | 0.00 | 0.866364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142684E+11 | 0.00 | 0.299281E+12 | 0.00 | 0.787911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144231E+10 | 0.00 | 0.275657E+10 | 0.00 | 0.601248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130273E+10 | 0.00 | 0.992371E+10 | 0.00 | 0.212521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144231E+10 | 0.00 | 0.199227E+11 | 0.00 | 0.464611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139578E+10 | 0.00 | 0.276400E+11 | 0.00 | 0.735854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144231E+10 | 0.00 | 0.102092E+11 | 0.00 | 0.290849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139578E+10 | 0.00 | 0.170799E+11 | 0.00 | 0.485735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144231E+10 | 0.00 | 0.244905E+11 | 0.00 | 0.669867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144231E+10 | 0.00 | 0.304004E+11 | 0.00 | 0.806129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139578E+10 | 0.00 | 0.965188E+10 | 0.00 | 0.248227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144231E+10 | 0.00 | 0.147389E+11 | 0.00 | 0.361196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139578E+10 | 0.00 | 0.179619E+11 | 0.00 | 0.397609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144231E+10 | 0.00 | 0.217862E+11 | 0.00 | 0.440201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169820E+11 | 0.00 | 0.206562E+12 | 0.00 | 0.517293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130273E+10 | 0.00 | 0.275657E+10 | 0.00 | 0.601248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144231E+10 | 0.00 | 0.304004E+11 | 0.00 | 0.806129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142726E+10 | 0.00 | 0.00 | 0.121055E+09 | 0.00 | 0.00 | 0.250508E+11 | 0.00 | 0.38 |
February | 0.541811E+09 | 0.00 | 0.00 | 0.110970E+09 | 0.00 | 0.00 | 0.159582E+11 | 0.00 | 0.38 |
March | 0.257812E+09 | 0.152984E+10 | 0.00 | 0.102973E+09 | 26491169.62 | 0.00 | 0.800814E+10 | 0.00 | 0.39 |
April | 34857709.36 | 0.109486E+11 | 0.00 | 25099292.64 | 0.272078E+09 | 0.00 | 0.512085E+09 | 0.00 | 0.40 |
May | 8731022.02 | 0.301793E+11 | 0.00 | 4173592.50 | 0.536399E+09 | 0.00 | 80404049.99 | 0.00 | 0.42 |
June | 0.00 | 0.469263E+11 | 0.00 | 418843.90 | 0.757957E+09 | 0.00 | 349605.40 | 0.00 | 0.43 |
July | 0.00 | 0.638015E+11 | 0.00 | 0.00 | 0.148267E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.708264E+11 | 0.00 | 0.00 | 0.119444E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.461466E+11 | 0.00 | 0.00 | 0.967504E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.184777E+09 | 0.892597E+10 | 0.00 | 64787222.92 | 0.124557E+09 | 0.00 | 0.273162E+10 | 0.00 | 0.43 |
November | 0.112640E+10 | 0.237015E+09 | 0.00 | 0.149814E+09 | 23186980.05 | 0.00 | 0.122337E+11 | 0.00 | 0.42 |
December | 0.143351E+10 | 0.00 | 0.00 | 0.137263E+09 | 0.00 | 0.00 | 0.232734E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.501516E+10 | 0.279522E+12 | 0.00 | 0.716553E+09 | 0.538528E+10 | 0.00 | 0.878487E+11 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.143351E+10 | 0.708264E+11 | 0.00 | 0.149814E+09 | 0.148267E+10 | 0.00 | 0.250508E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160489E+10 | 0.00 | 0.00 | 78711850.25 | 0.00 | 0.00 | 0.227503E+11 | 0.00 | 0.35 |
February | 0.114814E+10 | 0.00 | 0.00 | 85351717.53 | 1603846.68 | 0.00 | 0.153101E+11 | 0.00 | 0.35 |
March | 0.136026E+10 | 0.109928E+10 | 0.00 | 93661486.72 | 0.370496E+09 | 0.00 | 0.849987E+10 | 0.00 | 0.39 |
April | 0.723939E+09 | 0.657679E+10 | 0.00 | 27267055.03 | 0.362879E+10 | 0.00 | 0.777094E+09 | 0.00 | 0.44 |
May | 24623097.78 | 0.225020E+11 | 0.00 | 734357.17 | 0.107581E+11 | 0.00 | 13894827.47 | 0.00 | 0.43 |
June | 0.00 | 0.343768E+11 | 0.00 | 0.00 | 0.187304E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.441586E+11 | 0.00 | 0.00 | 0.317338E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.507351E+11 | 0.00 | 0.00 | 0.285553E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.344175E+11 | 0.00 | 0.00 | 0.175451E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.475919E+09 | 0.741994E+10 | 0.00 | 36833987.00 | 0.168957E+10 | 0.00 | 0.233626E+10 | 0.00 | 0.38 |
November | 0.115128E+10 | 0.182376E+09 | 0.00 | 0.104876E+09 | 78931224.95 | 0.00 | 0.116302E+11 | 0.00 | 0.36 |
December | 0.141632E+10 | 0.00 | 0.00 | 0.102678E+09 | 0.00 | 0.00 | 0.221500E+11 | 0.00 | 0.37 |
Annual Sum or Average | 0.790538E+10 | 0.201468E+12 | 0.00 | 0.530114E+09 | 0.113092E+12 | 0.00 | 0.834678E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.160489E+10 | 0.507351E+11 | 0.00 | 0.104876E+09 | 0.317338E+11 | 0.00 | 0.227503E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.821604E+11 | 0.00 | 0.00 | 0.362044E+09 | 0.00 | 0.00 | 0.116396E+12 | 0.00 | 0.31 |
February | 0.241968E+11 | 0.00 | 0.00 | 0.524858E+09 | 0.124975E+09 | 0.00 | 0.113373E+12 | 0.00 | 0.33 |
March | 0.659407E+10 | 0.110625E+11 | 0.00 | 0.726367E+09 | 0.359180E+10 | 0.00 | 0.762768E+11 | 0.00 | 0.35 |
April | 0.199549E+10 | 0.626957E+11 | 0.00 | 0.215497E+09 | 0.349981E+11 | 0.00 | 0.640680E+10 | 0.00 | 0.38 |
May | 0.209853E+09 | 0.218426E+12 | 0.00 | 4499652.88 | 0.101763E+12 | 0.00 | 0.118805E+09 | 0.00 | 0.41 |
June | 0.00 | 0.329388E+12 | 0.00 | 0.00 | 0.168127E+12 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.417662E+12 | 0.00 | 0.00 | 0.261805E+12 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.475955E+12 | 0.00 | 0.00 | 0.200958E+12 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.334590E+12 | 0.00 | 0.00 | 0.129949E+12 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.235977E+10 | 0.725622E+11 | 0.00 | 0.285985E+09 | 0.148183E+11 | 0.00 | 0.208172E+11 | 0.00 | 0.34 |
November | 0.103002E+11 | 0.167015E+10 | 0.00 | 0.694773E+09 | 0.118652E+10 | 0.00 | 0.957297E+11 | 0.00 | 0.34 |
December | 0.425765E+11 | 0.00 | 0.00 | 0.475351E+09 | 77903482.55 | 0.00 | 0.141920E+12 | 0.00 | 0.32 |
Annual Sum or Average | 0.170393E+12 | 0.192401E+13 | 0.00 | 0.328938E+10 | 0.917401E+12 | 0.00 | 0.571039E+12 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.821604E+11 | 0.475955E+12 | 0.00 | 0.726367E+09 | 0.261805E+12 | 0.00 | 0.141920E+12 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122037E+11 | 0.00 | 0.00 | 15088769.59 | 0.00 | 0.325196E+09 | 0.516799E+10 | 0.00 | 0.30 |
February | 0.519836E+10 | 0.00 | 0.00 | 33385995.71 | 2355827.85 | 0.00 | 0.687618E+10 | 0.00 | 0.30 |
March | 0.122582E+10 | 0.808072E+09 | 0.00 | 61116349.61 | 0.257844E+09 | 0.00 | 0.627880E+10 | 0.00 | 0.33 |
April | 0.177351E+09 | 0.561382E+10 | 0.00 | 24872911.69 | 0.311040E+10 | 0.00 | 0.694804E+09 | 0.00 | 0.37 |
May | 15271463.07 | 0.213404E+11 | 0.00 | 341840.35 | 0.942287E+10 | 0.00 | 8837130.59 | 0.00 | 0.41 |
June | 0.00 | 0.326857E+11 | 0.00 | 0.00 | 0.160249E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.417542E+11 | 0.00 | 0.00 | 0.251672E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.474702E+11 | 0.00 | 0.00 | 0.195173E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.327656E+11 | 0.00 | 0.00 | 0.128492E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.411689E+09 | 0.649171E+10 | 0.00 | 23154173.84 | 0.126351E+10 | 0.00 | 0.146610E+10 | 0.00 | 0.33 |
November | 0.291007E+10 | 45846506.11 | 0.00 | 50102326.66 | 93526105.14 | 0.00 | 0.604914E+10 | 0.00 | 0.31 |
December | 0.955433E+10 | 0.00 | 0.00 | 21808825.15 | 5821495.50 | 0.00 | 0.611628E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.316966E+11 | 0.188976E+12 | 0.00 | 0.229871E+09 | 0.877149E+11 | 0.325196E+09 | 0.326581E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.122037E+11 | 0.474702E+11 | 0.00 | 61116349.61 | 0.251672E+11 | 0.325196E+09 | 0.687618E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208385E+10 | 0.00 | 0.00 | 1698103.59 | 0.00 | 0.00 | 0.453778E+09 | 0.00 | 0.28 |
February | 0.992803E+09 | 0.00 | 0.00 | 4794446.04 | 230611.37 | 0.00 | 0.707189E+09 | 0.00 | 0.30 |
March | 0.398424E+09 | 0.202017E+09 | 0.00 | 8945830.23 | 53272356.51 | 0.00 | 0.740639E+09 | 0.00 | 0.41 |
April | 0.105901E+09 | 0.155773E+10 | 0.00 | 4098989.78 | 0.417332E+09 | 0.00 | 0.101625E+09 | 0.00 | 0.60 |
May | 2292072.04 | 0.600905E+10 | 0.00 | 232829.62 | 0.111449E+10 | 0.00 | 4550124.13 | 0.00 | 0.70 |
June | 0.00 | 0.945382E+10 | 0.00 | 0.00 | 0.191650E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.121314E+11 | 0.00 | 0.00 | 0.305775E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.117714E+11 | 0.00 | 0.00 | 0.310373E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.700427E+10 | 0.00 | 0.00 | 0.222979E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.117793E+09 | 0.126113E+10 | 0.00 | 3034962.26 | 0.238796E+09 | 0.00 | 0.187565E+09 | 0.00 | 0.44 |
November | 0.610852E+09 | 26801150.09 | 0.00 | 7403855.50 | 11349237.93 | 0.00 | 0.665360E+09 | 0.00 | 0.32 |
December | 0.150896E+10 | 0.00 | 0.00 | 3723277.17 | 0.00 | 0.00 | 0.682046E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.582088E+10 | 0.494177E+11 | 0.00 | 33932294.17 | 0.121432E+11 | 0.00 | 0.354275E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.208385E+10 | 0.121314E+11 | 0.00 | 8945830.23 | 0.310373E+10 | 0.00 | 0.740639E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132346E+10 | 0.00 | 0.00 | 2804124.51 | 0.00 | 0.00 | 0.773629E+09 | 0.00 | 0.36 |
February | 0.682250E+09 | 0.00 | 0.00 | 5239620.97 | 182575.67 | 0.00 | 0.833485E+09 | 0.00 | 0.41 |
March | 0.315082E+09 | 0.160179E+09 | 0.00 | 8639101.88 | 37759225.65 | 0.00 | 0.706489E+09 | 0.00 | 0.55 |
April | 79997437.47 | 0.130076E+10 | 0.00 | 4063800.33 | 0.323945E+09 | 0.00 | 0.102054E+09 | 0.00 | 0.78 |
May | 1804335.84 | 0.498126E+10 | 0.00 | 147646.74 | 0.860219E+09 | 0.00 | 3302519.05 | 0.00 | 0.91 |
June | 0.00 | 0.678661E+10 | 0.00 | 0.00 | 0.165156E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
July | 0.00 | 0.795134E+10 | 0.00 | 0.00 | 0.280949E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
August | 0.00 | 0.709671E+10 | 0.00 | 0.00 | 0.293076E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.518132E+10 | 0.00 | 0.00 | 0.182136E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.103709E+09 | 0.100481E+10 | 0.00 | 3126233.25 | 0.170227E+09 | 0.00 | 0.172063E+09 | 0.00 | 0.56 |
November | 0.481438E+09 | 20079491.00 | 0.00 | 6845969.47 | 8985223.60 | 0.00 | 0.634029E+09 | 0.00 | 0.41 |
December | 0.113387E+10 | 0.00 | 0.00 | 3474586.32 | 0.00 | 0.00 | 0.657209E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.412161E+10 | 0.344831E+11 | 0.00 | 34341083.46 | 0.106145E+11 | 0.00 | 0.388226E+10 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.132346E+10 | 0.795134E+10 | 0.00 | 8639101.88 | 0.293076E+10 | 0.00 | 0.833485E+09 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124035E+10 | 0.00 | 0.00 | 12064515.86 | 0.00 | 11543171.81 | 0.280151E+10 | 0.00 | 0.50 |
February | 0.686911E+09 | 321854.40 | 0.00 | 16135150.18 | 41128.33 | 0.00 | 0.196893E+10 | 0.00 | 0.52 |
March | 0.334456E+09 | 0.381834E+09 | 0.00 | 16092684.85 | 23474079.17 | 0.00 | 0.126188E+10 | 0.00 | 0.61 |
April | 0.103697E+09 | 0.213337E+10 | 0.00 | 5542967.34 | 0.316514E+09 | 0.00 | 0.125592E+09 | 0.00 | 0.72 |
May | 2252492.74 | 0.640139E+10 | 0.00 | 244934.21 | 0.105906E+10 | 0.00 | 4621342.63 | 0.00 | 0.73 |
June | 0.00 | 0.937139E+10 | 0.00 | 0.00 | 0.194882E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.122027E+11 | 0.00 | 0.00 | 0.308237E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.124579E+11 | 0.00 | 0.00 | 0.304188E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.911809E+10 | 0.00 | 0.00 | 0.185436E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 80978136.09 | 0.231405E+10 | 0.00 | 8394806.15 | 0.119839E+09 | 0.00 | 0.326064E+09 | 0.00 | 0.71 |
November | 0.339672E+09 | 81039363.70 | 0.00 | 28365143.39 | 3835870.18 | 0.00 | 0.190099E+10 | 0.00 | 0.64 |
December | 0.841305E+09 | 0.00 | 0.00 | 16919571.09 | 0.00 | 0.00 | 0.279917E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.362962E+10 | 0.544621E+11 | 0.00 | 0.103760E+09 | 0.114502E+11 | 11543171.81 | 0.111888E+11 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.124035E+10 | 0.124579E+11 | 0.00 | 28365143.39 | 0.308237E+10 | 11543171.81 | 0.280151E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163909E+10 | 0.00 | 0.00 | 4301550.64 | 0.00 | 0.00 | 0.117434E+10 | 0.00 | 0.50 |
February | 0.591145E+09 | 331632.09 | 0.00 | 9162173.21 | 13829.43 | 0.00 | 0.137071E+10 | 0.00 | 0.57 |
March | 0.173434E+09 | 0.319851E+09 | 0.00 | 15235686.50 | 20198620.09 | 0.00 | 0.128640E+10 | 0.00 | 0.83 |
April | 39148169.70 | 0.258177E+10 | 0.00 | 8032397.90 | 76464945.51 | 0.00 | 0.213868E+09 | 0.00 | 1.23 |
May | 1807034.21 | 0.654492E+10 | 0.00 | 302221.57 | 0.666458E+09 | 0.00 | 4968558.28 | 0.00 | 1.10 |
June | 0.00 | 0.105818E+11 | 0.00 | 0.00 | 0.104893E+10 | 0.00 | 0.00 | 0.00 | 1.16 |
July | 0.00 | 0.139395E+11 | 0.00 | 0.00 | 0.160499E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 0.00 | 0.164390E+11 | 0.00 | 0.00 | 0.739517E+09 | 0.00 | 0.00 | 0.00 | 1.21 |
September | 0.00 | 0.751481E+10 | 0.00 | 0.00 | 0.169210E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
October | 70410389.63 | 0.155398E+10 | 0.00 | 5070479.91 | 0.137055E+09 | 0.00 | 0.273633E+09 | 0.00 | 0.78 |
November | 0.198294E+09 | 50313682.68 | 0.00 | 14778983.18 | 4625935.38 | 0.00 | 0.140328E+10 | 0.00 | 0.65 |
December | 0.426494E+09 | 0.00 | 0.00 | 11258077.80 | 0.00 | 0.00 | 0.240956E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.313983E+10 | 0.595263E+11 | 0.00 | 68141570.72 | 0.599036E+10 | 0.00 | 0.813676E+10 | 0.00 | 0.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.163909E+10 | 0.164390E+11 | 0.00 | 15235686.50 | 0.169210E+10 | 0.00 | 0.240956E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194162E+11 | 0.00 | 0.00 | 926923.36 | 0.00 | 0.573545E+10 | 0.325103E+09 | 0.00 | 0.30 |
February | 0.125586E+11 | 0.00 | 0.00 | 16492612.58 | 18108467.92 | 0.117655E+10 | 0.240077E+10 | 0.00 | 0.31 |
March | 0.448827E+10 | 0.212346E+10 | 0.00 | 58328885.80 | 0.520439E+09 | 0.00 | 0.523170E+10 | 0.00 | 0.37 |
April | 0.335577E+09 | 0.165124E+11 | 0.00 | 29764540.30 | 0.432420E+10 | 0.00 | 0.846751E+09 | 0.00 | 0.57 |
May | 18748139.93 | 0.662643E+11 | 0.00 | 2095813.73 | 0.961777E+10 | 0.00 | 46403527.15 | 0.00 | 0.74 |
June | 0.00 | 0.104125E+12 | 0.00 | 0.00 | 0.152570E+11 | 0.00 | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.132855E+12 | 0.00 | 0.00 | 0.225671E+11 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.124896E+12 | 0.00 | 0.00 | 0.210566E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.730111E+11 | 0.00 | 0.00 | 0.161736E+11 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.149609E+10 | 0.127045E+11 | 0.00 | 18498242.48 | 0.214118E+10 | 0.00 | 0.112288E+10 | 0.00 | 0.40 |
November | 0.940876E+10 | 0.237714E+09 | 0.00 | 33162132.62 | 0.155760E+09 | 0.00 | 0.275769E+10 | 0.00 | 0.31 |
December | 0.198924E+11 | 0.00 | 0.00 | 1543853.44 | 11287923.42 | 0.175439E+10 | 0.510527E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.676146E+11 | 0.532729E+12 | 0.00 | 0.160813E+09 | 0.918431E+11 | 0.866639E+10 | 0.132418E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.198924E+11 | 0.132855E+12 | 0.00 | 58328885.80 | 0.225671E+11 | 0.573545E+10 | 0.523170E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157215E+11 | 0.00 | 0.00 | 5641668.36 | 0.00 | 0.285651E+10 | 0.260441E+10 | 0.00 | 0.39 |
February | 0.821932E+10 | 0.00 | 0.00 | 35091895.40 | 15038245.20 | 0.276331E+09 | 0.628702E+10 | 0.00 | 0.44 |
March | 0.269188E+10 | 0.198673E+10 | 0.00 | 78655588.77 | 0.349095E+09 | 0.00 | 0.739984E+10 | 0.00 | 0.58 |
April | 0.192545E+09 | 0.167753E+11 | 0.00 | 40093449.24 | 0.294921E+10 | 0.00 | 0.109423E+10 | 0.00 | 0.86 |
May | 14569313.19 | 0.581255E+11 | 0.00 | 1522483.50 | 0.744276E+10 | 0.00 | 35644144.41 | 0.00 | 1.02 |
June | 0.00 | 0.810161E+11 | 0.00 | 0.00 | 0.130301E+11 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.00 | 0.986658E+11 | 0.00 | 0.00 | 0.195681E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.916506E+11 | 0.00 | 0.00 | 0.174819E+11 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 0.00 | 0.591104E+11 | 0.00 | 0.00 | 0.127390E+11 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 0.104624E+10 | 0.114023E+11 | 0.00 | 27598300.51 | 0.154004E+10 | 0.00 | 0.165044E+10 | 0.00 | 0.59 |
November | 0.605558E+10 | 0.221510E+09 | 0.00 | 51006184.03 | 0.125516E+09 | 0.00 | 0.540263E+10 | 0.00 | 0.46 |
December | 0.142352E+11 | 0.00 | 0.00 | 10646751.85 | 9374098.40 | 0.708501E+09 | 0.352644E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.481768E+11 | 0.418954E+12 | 0.00 | 0.250256E+09 | 0.752503E+11 | 0.384134E+10 | 0.280007E+11 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.157215E+11 | 0.986658E+11 | 0.00 | 78655588.77 | 0.195681E+11 | 0.285651E+10 | 0.739984E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127524E+11 | 0.00 | 0.00 | 0.106204E+09 | 0.00 | 0.104245E+10 | 0.259350E+11 | 0.00 | 0.54 |
February | 0.753389E+10 | 32513391.44 | 0.00 | 0.139136E+09 | 1141282.42 | 0.179941E+09 | 0.186576E+11 | 0.00 | 0.58 |
March | 0.282557E+10 | 0.456326E+10 | 0.00 | 0.144953E+09 | 0.151332E+09 | 0.00 | 0.124697E+11 | 0.00 | 0.64 |
April | 0.298556E+09 | 0.240714E+11 | 0.00 | 43822179.05 | 0.305629E+10 | 0.00 | 0.112188E+10 | 0.00 | 0.73 |
May | 18039448.50 | 0.707320E+11 | 0.00 | 2275265.36 | 0.887109E+10 | 0.00 | 48121112.84 | 0.00 | 0.77 |
June | 0.00 | 0.102928E+12 | 0.00 | 0.00 | 0.155595E+11 | 0.00 | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.134334E+12 | 0.00 | 0.00 | 0.223926E+11 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.136185E+12 | 0.00 | 0.00 | 0.191165E+11 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.996068E+11 | 0.00 | 0.00 | 0.115282E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.527486E+09 | 0.265494E+11 | 0.00 | 58619383.33 | 0.737727E+09 | 0.00 | 0.340456E+10 | 0.00 | 0.76 |
November | 0.412507E+10 | 0.104978E+10 | 0.00 | 0.265218E+09 | 49595172.05 | 0.00 | 0.193281E+11 | 0.00 | 0.76 |
December | 0.102666E+11 | 13623599.93 | 0.00 | 0.134844E+09 | 2974217.41 | 0.138322E+09 | 0.263778E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.383476E+11 | 0.600066E+12 | 0.00 | 0.895073E+09 | 0.814669E+11 | 0.136071E+10 | 0.107343E+12 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.127524E+11 | 0.136185E+12 | 0.00 | 0.265218E+09 | 0.223926E+11 | 0.104245E+10 | 0.263778E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170346E+11 | 0.00 | 0.00 | 13496168.06 | 0.00 | 0.325786E+10 | 0.346925E+10 | 0.00 | 0.45 |
February | 0.106983E+11 | 10669519.98 | 0.00 | 32189513.67 | 7028210.19 | 0.224342E+09 | 0.469837E+10 | 0.00 | 0.48 |
March | 0.325597E+10 | 0.279232E+10 | 0.00 | 74844418.62 | 0.235808E+09 | 0.00 | 0.667369E+10 | 0.00 | 0.62 |
April | 0.238765E+09 | 0.202072E+11 | 0.00 | 33610525.13 | 0.227240E+10 | 0.00 | 0.863420E+09 | 0.00 | 0.93 |
May | 12646349.12 | 0.649136E+11 | 0.00 | 2348462.24 | 0.570799E+10 | 0.00 | 43808926.63 | 0.00 | 1.07 |
June | 0.00 | 0.961810E+11 | 0.00 | 0.00 | 0.971517E+10 | 0.00 | 0.00 | 0.00 | 1.06 |
July | 0.00 | 0.110675E+12 | 0.00 | 0.00 | 0.174719E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
August | 0.00 | 0.106300E+12 | 0.00 | 0.00 | 0.156497E+11 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 0.00 | 0.672898E+11 | 0.00 | 0.00 | 0.116807E+11 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 0.111121E+10 | 0.133849E+11 | 0.00 | 20933836.39 | 0.133525E+10 | 0.00 | 0.128115E+10 | 0.00 | 0.62 |
November | 0.687855E+10 | 0.385344E+09 | 0.00 | 51533910.30 | 0.118400E+09 | 0.00 | 0.481094E+10 | 0.00 | 0.51 |
December | 0.164109E+11 | 0.00 | 0.00 | 17665552.53 | 10283891.46 | 0.746049E+09 | 0.373741E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.556409E+11 | 0.482140E+12 | 0.00 | 0.246622E+09 | 0.642046E+11 | 0.422825E+10 | 0.255780E+11 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.170346E+11 | 0.110675E+12 | 0.00 | 74844418.62 | 0.174719E+11 | 0.325786E+10 | 0.667369E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170477E+10 | 0.00 | 0.00 | 47863.33 | 0.00 | 0.962066E+09 | 21158134.07 | 0.00 | 0.35 |
February | 0.122245E+10 | 0.00 | 0.00 | 1374288.49 | 367714.75 | 0.261974E+09 | 0.196113E+09 | 0.00 | 0.33 |
March | 0.479665E+09 | 0.150221E+09 | 0.00 | 5551919.92 | 38728563.83 | 0.00 | 0.505786E+09 | 0.00 | 0.37 |
April | 39137549.78 | 0.138896E+10 | 0.00 | 3775935.88 | 0.407760E+09 | 0.00 | 0.100612E+09 | 0.00 | 0.56 |
May | 1538252.02 | 0.603014E+10 | 0.00 | 150523.98 | 0.944993E+09 | 0.00 | 3364897.28 | 0.00 | 0.73 |
June | 0.00 | 0.964206E+10 | 0.00 | 0.00 | 0.152946E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.126843E+11 | 0.00 | 0.00 | 0.221189E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.119846E+11 | 0.00 | 0.00 | 0.210306E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.696661E+10 | 0.00 | 0.00 | 0.165035E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.176878E+09 | 0.108250E+10 | 0.00 | 1959265.83 | 0.228413E+09 | 0.00 | 79051800.10 | 0.00 | 0.41 |
November | 0.926378E+09 | 7567187.23 | 0.00 | 3053018.94 | 13374458.84 | 41449947.86 | 0.239348E+09 | 0.00 | 0.33 |
December | 0.163495E+10 | 0.00 | 0.00 | 51359.69 | 908661.37 | 0.646981E+09 | 23263124.36 | 0.00 | 0.34 |
Annual Sum or Average | 0.618577E+10 | 0.499369E+11 | 0.00 | 15964176.06 | 0.912931E+10 | 0.191247E+10 | 0.116870E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.170477E+10 | 0.126843E+11 | 0.00 | 5551919.92 | 0.221189E+10 | 0.962066E+09 | 0.505786E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147227E+10 | 0.00 | 0.00 | 299115.55 | 0.00 | 0.463659E+09 | 0.138314E+09 | 0.00 | 0.42 |
February | 0.717264E+09 | 0.00 | 0.00 | 2985782.22 | 284872.73 | 0.136092E+09 | 0.568039E+09 | 0.00 | 0.44 |
March | 0.237581E+09 | 0.138470E+09 | 0.00 | 7862344.67 | 23952227.49 | 0.00 | 0.748977E+09 | 0.00 | 0.57 |
April | 18765333.80 | 0.141271E+10 | 0.00 | 4819072.96 | 0.256619E+09 | 0.00 | 0.127133E+09 | 0.00 | 0.84 |
May | 1120251.93 | 0.527164E+10 | 0.00 | 117358.34 | 0.661326E+09 | 0.00 | 2558065.92 | 0.00 | 0.98 |
June | 0.00 | 0.751318E+10 | 0.00 | 0.00 | 0.118469E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.945462E+10 | 0.00 | 0.00 | 0.174068E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.885619E+10 | 0.00 | 0.00 | 0.161807E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.569318E+10 | 0.00 | 0.00 | 0.120194E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.102111E+09 | 0.997043E+09 | 0.00 | 3037576.61 | 0.144571E+09 | 0.00 | 0.149585E+09 | 0.00 | 0.59 |
November | 0.529688E+09 | 8156348.30 | 0.00 | 4967992.95 | 9652891.54 | 15308840.45 | 0.509213E+09 | 0.00 | 0.45 |
December | 0.126549E+10 | 0.00 | 0.00 | 498502.75 | 703950.13 | 0.328249E+09 | 0.192010E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.434429E+10 | 0.393452E+11 | 0.00 | 24587746.05 | 0.684250E+10 | 0.943309E+09 | 0.243583E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.147227E+10 | 0.945462E+10 | 0.00 | 7862344.67 | 0.174068E+10 | 0.463659E+09 | 0.748977E+09 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114728E+10 | 0.00 | 0.00 | 8348735.09 | 0.00 | 0.471436E+09 | 0.221824E+10 | 0.00 | 0.54 |
February | 0.746187E+09 | 412174.61 | 0.00 | 12745584.56 | 96101.10 | 0.117281E+09 | 0.178057E+10 | 0.00 | 0.57 |
March | 0.293169E+09 | 0.297224E+09 | 0.00 | 14452707.08 | 16142772.50 | 0.00 | 0.127458E+10 | 0.00 | 0.62 |
April | 33172766.18 | 0.195269E+10 | 0.00 | 5834474.33 | 0.299652E+09 | 0.00 | 0.143254E+09 | 0.00 | 0.70 |
May | 1395398.67 | 0.638300E+10 | 0.00 | 163921.40 | 0.877651E+09 | 0.00 | 3579163.43 | 0.00 | 0.75 |
June | 0.00 | 0.953029E+10 | 0.00 | 0.00 | 0.155164E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.128243E+11 | 0.00 | 0.00 | 0.217077E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.129947E+11 | 0.00 | 0.00 | 0.190586E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.927865E+10 | 0.00 | 0.00 | 0.121552E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 98502379.12 | 0.215580E+10 | 0.00 | 10037048.69 | 0.105655E+09 | 0.00 | 0.291128E+09 | 0.00 | 0.74 |
November | 0.409368E+09 | 43712877.30 | 0.00 | 26315382.82 | 5118819.81 | 0.00 | 0.194493E+10 | 0.00 | 0.73 |
December | 0.101057E+10 | 530364.15 | 0.00 | 10480620.76 | 499048.17 | 0.228162E+09 | 0.225643E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.373964E+10 | 0.554613E+11 | 0.00 | 88378474.74 | 0.814861E+10 | 0.816879E+09 | 0.991272E+10 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.114728E+10 | 0.129947E+11 | 0.00 | 26315382.82 | 0.217077E+10 | 0.471436E+09 | 0.225643E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150112E+10 | 0.00 | 0.00 | 1129449.63 | 0.00 | 0.567747E+09 | 0.331831E+09 | 0.00 | 0.49 |
February | 0.100681E+10 | 127699.79 | 0.00 | 2941038.65 | 224397.81 | 0.136919E+09 | 0.444752E+09 | 0.00 | 0.50 |
March | 0.336194E+09 | 0.190390E+09 | 0.00 | 7310280.92 | 18130587.15 | 0.00 | 0.663171E+09 | 0.00 | 0.61 |
April | 26899845.14 | 0.161718E+10 | 0.00 | 4512895.24 | 0.223068E+09 | 0.00 | 0.104715E+09 | 0.00 | 0.88 |
May | 1127338.00 | 0.570544E+10 | 0.00 | 169203.97 | 0.559643E+09 | 0.00 | 3068596.56 | 0.00 | 1.01 |
June | 0.00 | 0.861523E+10 | 0.00 | 0.00 | 0.102713E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 0.00 | 0.102911E+11 | 0.00 | 0.00 | 0.175804E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.00 | 0.993265E+10 | 0.00 | 0.00 | 0.160104E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.628239E+10 | 0.00 | 0.00 | 0.120763E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 0.126016E+09 | 0.111120E+10 | 0.00 | 2845576.90 | 0.145276E+09 | 0.00 | 0.104475E+09 | 0.00 | 0.62 |
November | 0.706843E+09 | 15224647.35 | 0.00 | 5155161.69 | 10210131.29 | 233544.86 | 0.445436E+09 | 0.00 | 0.51 |
December | 0.139252E+10 | 0.00 | 0.00 | 1408719.43 | 802934.19 | 0.358264E+09 | 0.332085E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.509753E+10 | 0.437609E+11 | 0.00 | 25472326.43 | 0.655119E+10 | 0.106316E+10 | 0.242953E+10 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.150112E+10 | 0.102911E+11 | 0.00 | 7310280.92 | 0.175804E+10 | 0.567747E+09 | 0.663171E+09 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 7634970.32 | 0.00 | 0.00 | 0.611969E+09 | 0.00 | 0.58 |
February | 0.00 | 6823177.30 | 0.00 | 16381637.87 | 0.00 | 0.00 | 0.295789E+09 | 0.00 | 0.59 |
March | 0.00 | 0.114580E+09 | 0.00 | 16251637.53 | 0.00 | 0.00 | 0.101220E+09 | 0.00 | 0.59 |
April | 0.00 | 0.346165E+09 | 0.00 | 7812987.61 | 0.00 | 0.00 | 7905698.82 | 0.00 | 0.59 |
May | 0.00 | 0.858997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.176974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.126847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.420466E+09 | 0.00 | 1692095.73 | 0.00 | 0.00 | 4951630.38 | 0.00 | 0.59 |
November | 0.00 | 42025430.22 | 0.00 | 23077633.78 | 0.00 | 0.00 | 0.154317E+09 | 0.00 | 0.59 |
December | 0.00 | 34666.29 | 0.00 | 42344812.69 | 0.00 | 0.00 | 0.490912E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.789225E+10 | 0.00 | 0.115196E+09 | 0.00 | 0.00 | 0.166706E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.176974E+10 | 0.00 | 42344812.69 | 0.00 | 0.00 | 0.611969E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327481E+09 | 0.00 | 0.00 | 44782972.58 | 0.00 | 0.00 | 0.611081E+10 | 0.00 | 0.58 |
February | 0.00 | 52678584.04 | 0.00 | 0.143669E+09 | 0.00 | 0.00 | 0.314430E+10 | 0.00 | 0.59 |
March | 0.00 | 0.105536E+10 | 0.00 | 0.160209E+09 | 0.00 | 0.00 | 0.111030E+10 | 0.00 | 0.59 |
April | 0.00 | 0.326937E+10 | 0.00 | 83703960.99 | 0.00 | 0.00 | 95714077.76 | 0.00 | 0.59 |
May | 0.00 | 0.837321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.174493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.174022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.401078E+10 | 0.00 | 17778829.21 | 0.00 | 0.00 | 66179034.61 | 0.00 | 0.59 |
November | 0.00 | 0.366745E+09 | 0.00 | 0.217823E+09 | 0.00 | 0.00 | 0.169040E+10 | 0.00 | 0.59 |
December | 0.00 | 26098.82 | 0.00 | 0.380053E+09 | 0.00 | 0.00 | 0.511294E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.327481E+09 | 0.771231E+11 | 0.00 | 0.104802E+10 | 0.00 | 0.00 | 0.173307E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.327481E+09 | 0.174493E+11 | 0.00 | 0.380053E+09 | 0.00 | 0.00 | 0.611081E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232721E+09 | 0.00 | 0.00 | 2528347.48 | 0.00 | 0.00 | 0.415624E+09 | 0.00 | 0.58 |
February | 0.00 | 6317331.74 | 0.00 | 12815158.48 | 0.00 | 0.00 | 0.304974E+09 | 0.00 | 0.59 |
March | 0.00 | 0.113959E+09 | 0.00 | 14908639.01 | 0.00 | 0.00 | 0.103184E+09 | 0.00 | 0.59 |
April | 0.00 | 0.346951E+09 | 0.00 | 7491117.80 | 0.00 | 0.00 | 8162689.71 | 0.00 | 0.59 |
May | 0.00 | 0.855264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.177851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.416603E+09 | 0.00 | 1530851.49 | 0.00 | 0.00 | 5642723.36 | 0.00 | 0.59 |
November | 0.00 | 41467866.15 | 0.00 | 20024817.45 | 0.00 | 0.00 | 0.159216E+09 | 0.00 | 0.59 |
December | 0.00 | 28289.50 | 0.00 | 35390794.91 | 0.00 | 0.00 | 0.498823E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.232721E+09 | 0.787340E+10 | 0.00 | 94689726.61 | 0.00 | 0.00 | 0.149563E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.232721E+09 | 0.177851E+10 | 0.00 | 35390794.91 | 0.00 | 0.00 | 0.498823E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.487953E+09 | 0.00 | 0.00 | 0.140061E+11 | 0.00 | 0.66 |
February | 0.00 | 0.160991E+09 | 0.00 | 0.848401E+09 | 0.00 | 0.00 | 0.677898E+10 | 0.00 | 0.66 |
March | 0.00 | 0.246191E+10 | 0.00 | 0.769005E+09 | 0.00 | 0.00 | 0.213709E+10 | 0.00 | 0.66 |
April | 0.00 | 0.467451E+10 | 0.00 | 0.620418E+09 | 0.00 | 0.00 | 0.373130E+09 | 0.00 | 0.67 |
May | 0.00 | 0.196915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.289655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.390154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.330526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.299025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.947891E+10 | 0.00 | 79241494.86 | 0.00 | 0.00 | 98125380.42 | 0.00 | 0.66 |
November | 0.00 | 0.888061E+09 | 0.00 | 0.110986E+10 | 0.00 | 0.00 | 0.338246E+10 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 0.208295E+10 | 0.00 | 0.00 | 0.111731E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.168292E+12 | 0.00 | 0.599783E+10 | 0.00 | 0.00 | 0.379489E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.390154E+11 | 0.00 | 0.208295E+10 | 0.00 | 0.00 | 0.140061E+11 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:31
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.285690E+12 | 0.280010E+10 | 0.00 | 0.801593E+12 | 0.113554E+13 |
February | 0.325614E+12 | 0.335491E+10 | 0.00 | 0.532301E+12 | 0.174987E+13 |
March | 0.431265E+12 | 0.206416E+10 | 0.00 | 0.256159E+12 | 0.313192E+13 |
April | 0.458673E+12 | -0.153475E+10 | 0.00 | -0.253779E+12 | 0.437708E+13 |
May | 0.490974E+12 | -0.725927E+10 | 0.00 | -0.906865E+12 | 0.427630E+13 |
June | 0.459071E+12 | -0.829778E+10 | 0.00 | -0.141858E+13 | 0.516495E+13 |
July | 0.369006E+12 | -0.178103E+11 | 0.00 | -0.195333E+13 | 0.599754E+13 |
August | 0.309950E+12 | -0.124046E+11 | 0.00 | -0.195885E+13 | 0.632689E+13 |
September | 0.339551E+12 | -0.717364E+10 | 0.00 | -0.142630E+13 | 0.407771E+13 |
October | 0.326019E+12 | -625270984.1 | 0.00 | -0.145756E+12 | 0.327816E+13 |
November | 0.288721E+12 | 0.841279E+09 | 0.00 | 0.437233E+12 | 0.273035E+13 |
December | 0.259364E+12 | 0.283405E+10 | 0.00 | 0.762845E+12 | 0.252786E+13 |
Annual Sum or Average | 0.434390E+13 | -0.432110E+11 | 0.00 | -0.527333E+13 | 0.447742E+14 |
Minimum of Months | 0.259364E+12 | -0.178103E+11 | 0.00 | -0.195885E+13 | 0.113554E+13 |
Maximum of Months | 0.490974E+12 | 0.335491E+10 | 0.00 | 0.801593E+12 | 0.632689E+13 |