Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:43:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31885.29 | 688.36 | 688.36 |
Net Site Energy | 31885.29 | 688.36 | 688.36 |
Total Source Energy | 98784.02 | 2132.63 | 2132.63 |
Net Source Energy | 98784.02 | 2132.63 | 2132.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 336.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3365.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3927.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2826.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 540.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1078.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9564.28 |
Humidification | 1786.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.47 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 718.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30830.71 | 1054.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12508.92 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 336.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3365.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3927.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 80.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2826.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 540.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1078.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9564.28 |
Humidification | General | 1786.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.47 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 718.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 336.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3365.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3927.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 695.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2826.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 540.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1078.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9564.28 |
Humidification | Unassigned | 1786.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 664.47 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 718.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 207.18 | 22.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 665.60 | 22.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 99.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 207.18 | 22.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Other | 358.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 665.60 | 22.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30830.712 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30830.712 | 100.00 |
Total On-Site and Utility Electric Sources | 30830.712 | 100.00 |
Total Electricity End Uses | 30830.712 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 12508.92 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 12508.92 | 100.00 |
Total Water End Uses | 12508.92 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 883.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5912.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 10.2732 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.2732 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 10.2732 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 10.2732 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.8735 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 10.2732 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 10.3445 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 10.2732 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 10.2732 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 10.2732 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 10.2732 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 10.2732 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 10.2732 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 10.2732 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 17.8735 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 10.2732 | 18.58 | 484.4232 | |
Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 10.3445 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 3.1788 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 23-AUG-15:00 | 27-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 15-JUN-12:30 |
Heating | 0.00 | 646583.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 414799.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 84450.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 221998.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49148.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 86451.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31370.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2067513.91 | 677954.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 646583.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 414799.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 332294.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 221998.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 49148.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 86451.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 31370.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 364.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10657.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12437.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2204.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6127.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8951.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1711.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3414.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5656.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 778.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97640.87 | 1143.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 73.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 122.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2107.95 | 24.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 268.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 47.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 73.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 122.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2107.95 | 24.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.86 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.548794 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.22 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.533772 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.70 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 7.12 | 0.267136 | 0.284000 | 2.02 | 0.712362 | 0.500000 | 0.001426 | 0.000154 | 2.02 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 67.30 | 0.282608 | 0.296000 | 19.92 | 0.753621 | 0.500000 | 0.001348 | 0.003596 | 19.92 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.65 | 0.285910 | 0.307000 | 2.04 | 0.762428 | 0.500000 | 0.001333 | 0.000710 | 2.79 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.29 | 0.185827 | 0.200000 | 0.257035 | 0.495539 | 0.500000 | 0.002050 | 0.000098 | 0.385538 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.23 | 0.124702 | 0.200000 | 0.246836 | 0.332540 | 0.500000 | 0.003055 | 0.000069 | 0.271908 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.43 | 0.166543 | 0.200000 | 0.286804 | 0.444115 | 0.500000 | 0.002288 | 0.000117 | 0.458531 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.59 | 0.096575 | 0.200000 | 0.318727 | 0.300000 | 0.500000 | 0.003945 | 0.000059 | 0.318727 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 12.34 | 0.193533 | 0.202000 | 2.49 | 0.516087 | 0.500000 | 0.001969 | 0.001813 | 7.13 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.82 | 0.120034 | 0.200000 | 2.56 | 0.320090 | 0.500000 | 0.003174 | 0.001204 | 4.73 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.77 | 0.173378 | 0.200000 | 2.75 | 0.462340 | 0.500000 | 0.002198 | 0.001791 | 7.04 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.98 | 0.110125 | 0.200000 | 2.80 | 0.300000 | 0.500000 | 0.003460 | 0.001125 | 4.42 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.39 | 0.171240 | 0.200000 | 0.278930 | 0.456641 | 0.500000 | 0.002225 | 0.000231 | 0.906979 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.31 | 0.117639 | 0.200000 | 0.261658 | 0.313703 | 0.500000 | 0.003239 | 0.000152 | 0.598505 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.53 | 0.156512 | 0.200000 | 0.305185 | 0.417366 | 0.500000 | 0.002434 | 0.000228 | 0.897910 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.50 | 0.102390 | 0.200000 | 0.300625 | 0.300000 | 0.500000 | 0.003721 | 0.000146 | 0.572787 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17657.79 | 0.000154 | 355.97 |
CORE_MID VAV BOX REHEAT COIL | 410999.60 | 0.003596 | 9587.90 |
CORE_TOP VAV BOX REHEAT COIL | 81164.55 | 0.000710 | 2142.54 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11225.97 | 0.000098 | 296.25 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7915.29 | 0.000069 | 208.86 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13345.83 | 0.000117 | 352.13 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6706.40 | 0.000059 | 157.32 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 207183.94 | 0.001813 | 5463.81 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 137571.42 | 0.001204 | 3627.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 204754.92 | 0.001791 | 5399.81 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 128650.48 | 0.001125 | 3392.84 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26358.94 | 0.000231 | 695.01 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17393.31 | 0.000152 | 458.60 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26095.76 | 0.000228 | 688.07 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16646.84 | 0.000146 | 438.93 |
VAV_BOT WITH REHEAT HEATING COIL | 49210.40 | 0.000431 | 821.65 |
VAV_MID WITH REHEAT HEATING COIL | 432533.93 | 0.003784 | 7258.23 |
VAV_TOP WITH REHEAT HEATING COIL | 42828.07 | 0.000375 | 724.80 |
CAV_BAS HEATING COIL | 294319.41 | 0.002575 | 6555.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.33 | 3.13 | 12.67 | 3.13 | 11.47 | 11.47 | 0.300000 | 0.273025 | 11.47 |
VAV_MID WITH REHEAT | 60.11 | 30.53 | 120.22 | 34.84 | 107.40 | 107.40 | 0.300000 | 0.324430 | 107.40 |
VAV_TOP WITH REHEAT | 6.19 | 3.19 | 12.38 | 5.76 | 11.91 | 11.91 | 0.300000 | 0.483940 | 11.91 |
CAV_BAS | 6.86 | 6.86 | 6.86 | 6.86 | 6.86 | 6.86 | 1.00 | 1.00 | 6.86 |
AIRLOOP DATACENTER BASEMENT | 24.70 | 24.70 | 24.70 | 24.70 | 24.70 | 24.70 | 1.00 | 0.999988 | 24.70 |
AIRLOOP DATACENTER BOT | 0.548794 | 0.548794 | 0.548794 | 0.548794 | 0.548794 | 0.548794 | 1.00 | 1.00 | 0.548794 |
AIRLOOP DATACENTER MID | 5.22 | 5.22 | 5.22 | 5.22 | 5.22 | 5.22 | 1.00 | 1.00 | 5.22 |
AIRLOOP DATACENTER TOP | 0.533772 | 0.533772 | 0.533772 | 0.533772 | 0.533772 | 0.533772 | 1.00 | 1.00 | 0.533772 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.47 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 107.40 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.91 | |
CAV_BAS_OA_CONTROLLER | 6.86 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.70 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.548794 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.22 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.533772 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.18 | 6.67 | 10.78 | 0.007217 | 0.007000 | 206598.19 | 0.008789 | 11.47 |
VAV_MID WITH REHEAT COOLING COIL | 27.48 | 6.67 | 10.78 | 0.007228 | 0.007000 | 1972450.33 | 0.083913 | 107.40 |
VAV_TOP WITH REHEAT COOLING COIL | 27.01 | 6.67 | 10.78 | 0.007206 | 0.007000 | 211993.39 | 0.009019 | 11.91 |
CAV_BAS COOLING COIL | 26.41 | 6.67 | 11.22 | 0.007344 | 0.007000 | 116985.15 | 0.004977 | 6.86 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.47 |
VAV_MID WITH REHEAT FAN | 107.40 |
VAV_TOP WITH REHEAT FAN | 11.91 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008789 | 0.000054 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000431 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.083913 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003784 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009019 | 0.000053 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000375 | |
CAV_BAS_COOLC_CONTROLLER | 0.004977 | 0.000096 |
CAV_BAS_HEATC_CONTROLLER | 0.002575 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.86 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.70 | 469001.64 | 261269.78 | 0.011486 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.548794 | 10230.20 | 5733.28 | 0.000251 |
AIRLOOP DATACENTER MID COOLING COIL | 5.22 | 97419.61 | 54578.42 | 0.002386 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.533772 | 9960.73 | 5579.49 | 0.000244 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.70 | 24.70 | 24.70 | 24.70 | 469001.64 | 469001.64 | 16051.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.548794 | 0.548794 | 0.548794 | 0.548794 | 10230.20 | 10230.20 | 741.49 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.22 | 5.22 | 5.22 | 5.22 | 97419.61 | 97419.61 | 7414.91 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.533772 | 0.533772 | 0.533772 | 0.533772 | 9960.73 | 9960.73 | 741.49 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.70 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.548794 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.22 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.533772 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.70 | 469001.64 | 0.011486 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.548794 | 10230.20 | 0.000251 |
AIRLOOP DATACENTER MID HEATING COIL | 5.22 | 97419.61 | 0.002386 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.533772 | 9960.73 | 0.000244 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16051.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 741.49 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7414.91 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 741.49 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000129 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.106697 | 17420.40 | |
HEATSYS1 PUMP | 0.018657 | 5618.55 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.106697 | 12.80 |
HEATSYS1 | 0.018657 | 2.24 |
COOLSYS1_SUPPLY | 0.106697 | 12.80 |
SINGLE WATER PLANT LOOP | 0.014366 | 1.72 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.106697 | 0.106697 | 447861.97 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2132562.87 | 2132562.87 | 0.018657 |
CENTRAL BOILER | 591759.93 | 578899.65 | 0.014366 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.053349 | 6030.37 |
COOLSYS1 CHILLER2 PUMP | 0.053349 | 6030.37 |
PLANT CIRC PUMP | 0.014366 | 3664.07 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.106697 | 0.054065 | 1273974.23 | 1279961.49 | 0.063341 |
COOLSYS1 CHILLER2 | 0.106697 | 0.054065 | 1273974.23 | 1279961.49 | 0.063341 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014366 | 139666.47 | 55648.86 | 69833.23 | 7879.72 | 21033.28 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.126681 | 15.20 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.126681 | 31363.44 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 56.45 | 1519888.95 | 11.29 | 189986.12 |
TOWERWATERSYS COOLTOWER 2 | 56.45 | 1519888.95 | 11.29 | 189986.12 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.065790 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 10.273 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 15.115 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 10.273 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.343 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 17.873 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 233.173 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 10.273 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 494.696 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 28553.717 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28553.717 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 25643.245 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 25643.245 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 3219.765 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.765 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 3219.836 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3219.836 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 2074.939 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2074.939 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 8050.927 | 10.273 | 190.864 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8050.927 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 647.068 | 17.873 | 332.067 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 647.068 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.16139 | 0.61139 | 0.61139 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.481 | 5.5005E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1171E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1186E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4245E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4257E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1429E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1438E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1512E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2504E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4531E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5392E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1670E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2376E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1046 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5444E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1167 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9584E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7802E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9439E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1526E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2563E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4545E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5451E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1681E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2419E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1170E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1185E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4243E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4256E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1427E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1437E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7230E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8919E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4998E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6774E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3991E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4831E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0418E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9583E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6941E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7389E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9505E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6208E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6765E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7445E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4405E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4897E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3722E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3912E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7687E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7701E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5106E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5117E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3393E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3401E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8005E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8814E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5362E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5996E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3593E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4028E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7601E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4452E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1211E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0963E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9006E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4006E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7996E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8793E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5354E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5976E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3584E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4002E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7687E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7700E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5105E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5116E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3392E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3400E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6193E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6876E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3702E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4196E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3221E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3409E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9425E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9203E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5731E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6928E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8586E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5853E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6643E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8278E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4278E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5987E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3486E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4314E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1024 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4396E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1104 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9704E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.4925E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4124E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8401E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8461E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4507E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5746E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7107E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4250E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4562E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2961E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7303E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8178E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4851E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3694E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7277E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7936E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3137E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5104E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6076E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3775E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1025 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4534E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1105 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9863E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5065E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4234E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8439E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8504E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4549E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5786E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7183E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4301E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4566E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2987E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7309E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8199E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4891E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3719E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7312E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7978E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3176E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5143E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6151E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3824E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82298.71515 | 82298.71515 | 6.85555 | 6.85555 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 85484.96847 | 85484.96847 | 7.12014 | 7.12014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 808210.41538 | 808210.41538 | 67.30324 | 67.30324 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 237036.39929 | 237036.39929 | 11.51954 | 11.51954 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 79887.62804 | 79887.62804 | 6.65259 | 6.65259 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 56838.64717 | 56838.64717 | 2.78573 | 2.78573 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15298.86352 | 15298.86352 | 1.28518 | 1.28518 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7861.85960 | 7861.85960 | 0.38554 | 0.38554 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14691.88027 | 14691.88027 | 1.23418 | 1.23418 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 32.05500 | 6.86186E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5542.44830 | 5542.44830 | 0.27191 | 0.27191 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17070.73456 | 17070.73456 | 1.43402 | 1.43402 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 37.77500 | 6.87096E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9343.89006 | 9343.89006 | 0.45853 | 0.45853 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18970.97514 | 18970.97514 | 1.59363 | 1.59363 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3926.69876 | 3926.69876 | 0.19225 | 0.19225 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 146897.92567 | 146897.92567 | 12.34007 | 12.34007 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 144991.84684 | 144991.84684 | 7.12611 | 7.12611 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 152633.48162 | 152633.48162 | 12.82180 | 12.82180 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 32.42333 | 6.86244E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 96273.15023 | 96273.15023 | 4.73205 | 4.73205 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 163978.47410 | 163978.47410 | 13.77489 | 13.77489 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 143293.75332 | 143293.75332 | 7.04240 | 7.04240 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 166367.97054 | 166367.97054 | 13.97554 | 13.97554 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 90036.35285 | 90036.35285 | 4.42468 | 4.42468 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16602.17279 | 16602.17279 | 1.39465 | 1.39465 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 18443.37449 | 18443.37449 | 0.90698 | 0.90698 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15574.16883 | 15574.16883 | 1.30829 | 1.30829 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12169.96197 | 12169.96197 | 0.59851 | 0.59851 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18164.87130 | 18164.87130 | 1.52592 | 1.52592 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18259.38125 | 18259.38125 | 0.89791 | 0.89791 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17893.55364 | 17893.55364 | 1.50312 | 1.50312 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11648.04100 | 11648.04100 | 0.57279 | 0.57279 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8283.63393 | 8283.63393 | 0.54879 | 0.54879 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 25.18667 | 6.85117E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78829.48035 | 78829.48035 | 5.22313 | 5.22313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 34.00500 | 6.86494E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8055.91469 | 8055.91469 | 0.53377 | 0.53377 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 34.33000 | 6.86546E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -5.20000 | 2.80840E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372737.33842 | 372737.33842 | 24.69646 | 24.69646 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 26.27000 | 6.85284E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 02:40:00 | -5.20000 | 2.80840E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 169785.21 | 11.46972 | 11.46972 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 45070.78 | 2.38605 | 2.38605 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1582281.10 | 107.40297 | 107.40297 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 475597.12 | 34.84478 | 34.84478 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 177165.96 | 11.90625 | 11.90625 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 47618.84 | 5.76191 | 5.76191 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
7 | CAV_BAS | Cooling | Sensible | 88315.29 | 6.85555 | 6.85555 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 56927.18 | 1.20016 | 1.20016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 371463.19 | 24.69676 | 24.69676 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16051.03 | 0.33839 | 0.33839 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8286.85 | 0.54879 | 0.54879 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 741.49 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79018.91 | 5.22313 | 5.22313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7414.91 | 0.15632 | 0.15632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8079.19 | 0.53377 | 0.53377 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 741.49 | 1.56323E-002 | 1.56323E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.85555 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.12014 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26714 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02212 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71236 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42624E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54478E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.02212 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17657.78743 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54478E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 355.96713 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 67.30324 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28261 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.92176 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75362 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34816E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.59560E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.92176 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 410999.60286 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.59560E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9587.90353 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.65259 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28591 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.04234 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76243 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33259E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.10063E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.78573 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81164.55222 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.10063E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2142.53958 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28518 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18583 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25704 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49554 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05029E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.82097E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38554 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11225.97027 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.82097E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 296.25275 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23418 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12470 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24684 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33254 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05527E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.92464E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27191 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7915.29381 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.92464E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 208.85948 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43402 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16654 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28680 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44411 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28770E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16755E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45853 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13345.83467 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16755E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 352.12908 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59363 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.65749E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31873 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.94513E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.86706E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31873 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6706.40492 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.86706E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 157.31977 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.34007 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19353 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49269 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51609 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96866E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81254E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.12611 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 207183.94383 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81254E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5463.81158 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.82180 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12003 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56436 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32009 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17410E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20353E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.73205 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 137571.41648 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20353E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3627.90921 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.77489 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17338 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.75498 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46234 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19752E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79129E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.04240 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 204754.91892 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79129E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5399.80937 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.97554 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11012 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79511 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45972E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12549E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.42468 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 128650.48193 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12549E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3392.83613 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39465 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17124 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27893 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45664 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22494E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30599E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90698 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26358.93853 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30599E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 695.00573 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30829 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11764 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26166 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31370 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23873E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52164E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59851 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17393.31306 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52164E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 458.60144 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52592 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15651 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30518 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41737 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43431E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28297E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89791 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26095.76440 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28297E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 688.07128 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50312 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10239 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30062 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72106E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45634E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57279 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16646.83916 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45634E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 438.93066 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.54879 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.22313 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53377 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.69646 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.33357 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13152 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.66714 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.13152 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.46972 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.46972 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27302 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 60.10777 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.52890 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 120.21554 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 34.84478 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 107.40297 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 107.40297 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32443 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.19228 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.18874 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.38457 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.76191 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.90625 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.90625 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.48394 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.85555 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.85555 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.85555 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.85555 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.85555 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.85555 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.69646 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.69646 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.69646 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.69646 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.69676 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.69676 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.54879 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.54879 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.54879 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.54879 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.54879 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.54879 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.22313 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.22313 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.22313 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.22313 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.22313 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.22313 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53377 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53377 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53377 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53377 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53377 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.53377 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.46972 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 107.40297 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.90625 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.85555 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.69676 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.54879 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.22313 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.53377 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.46972 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.17986 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.77868 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.21708E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 206598.18876 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.78916E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.46972 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 49210.39754 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30514E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 821.64914 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.46972 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.78916E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.41793E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.30514E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 107.40297 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.48455 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.77872 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.22778E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1972450.32881 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.39126E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 107.40297 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 432533.93153 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.78400E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7258.22853 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 107.40297 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.39126E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.67484E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.78400E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.90625 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.01171 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.77864 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.20639E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 211993.39034 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.01869E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.90625 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 42828.06882 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.74679E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 724.79589 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.90625 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.01869E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.28004E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.74679E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.85555 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40700 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.21609 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.34423E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 116985.14972 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.97682E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.85555 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 294319.41083 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57483E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6555.09648 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.85555 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.97682E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.56817E-005 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.57483E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.69676 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.69676 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 469001.63846 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 261269.77922 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.14858E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.69676 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.69676 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.69676 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.69676 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 469001.63846 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 469001.63846 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16051.03087 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.69676 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.69676 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 469001.63846 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.14858E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16051.03087 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.29251E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.54879 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54879 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10230.20302 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5733.27917 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50537E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.54879 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.54879 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.54879 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.54879 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10230.20302 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10230.20302 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 741.49113 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.54879 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54879 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10230.20302 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50537E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 741.49113 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.22313 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.22313 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 97419.60849 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 54578.41669 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38580E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.22313 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.22313 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.22313 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.22313 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 97419.60849 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 97419.60849 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7414.91130 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.22313 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.22313 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 97419.60849 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38580E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7414.91130 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53377 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53377 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9960.72984 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5579.49131 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43938E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.53377 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.53377 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.53377 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.53377 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9960.72984 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9960.72984 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 741.49113 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53377 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53377 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9960.72984 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43938E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 741.49113 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10670 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 17420.40369 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10670 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 12.80367 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10670 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10670 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 447861.97458 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.86566E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.23879 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.86566E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5618.54570 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2132562.87121 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2132562.87000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.86566E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10670 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 12.80367 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 5.33486E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 6030.36648 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 5.33486E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 6030.36648 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10670 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.40650E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1273974.23457 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1279961.48500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.33406E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10670 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.40650E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1273974.23457 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1279961.48500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.33406E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.43661E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.72393 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.43661E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3664.07252 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.43661E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55648.86400 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21033.28162 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 591759.93334 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 578899.65000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.43661E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12668 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.20173 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12668 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31363.43757 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 56.45007 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1519888.94914 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.29001 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 189986.11864 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 56.45007 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1519888.94914 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.29001 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 189986.11864 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.57900E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.57900E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16744.97 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 389505.40 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 76933.27 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10640.17 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7502.08 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12648.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6355.56 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 196347.13 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 130375.06 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 194045.53 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 121922.01 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24979.37 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16482.93 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24730.00 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15775.61 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 39006.41 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 346318.54 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 34870.11 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 233468.13 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 330203.69 | 200028.95 | 130174.73 | 0.61 | 62863.64 | 637.60 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 3107726.01 | 1879314.13 | 1228411.88 | 0.60 | 583207.19 | 5915.21 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 341704.14 | 207218.29 | 134485.84 | 0.61 | 65615.50 | 665.51 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 190551.16 | 116812.27 | 73738.88 | 0.61 | 34637.97 | 351.32 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.25 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.25 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3059688145 | 0.2585618145 | Pass | Pass | 1.0035571215 | 1.5127295539 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1064045959 | 0.1921565564 | Pass | Pass | 0.1471216140 | 0.3535461840 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.1325590988E-002 | 0.1004063112 | Pass | Pass | 0.1049770600 | 0.3057312006 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.4203482299E-002 | 7.0868982344E-002 | Pass | Pass | 4.8692223820E-002 | 0.2138092526 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.2610663233E-002 | 0.1340625404 | Pass | Pass | 0.1465478823 | 0.3526434468 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1599848927 | 0.2298732524 | Pass | Pass | 0.1489384631 | 0.3565244147 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2261729181 | 0.3892383363 | Pass | Pass | 0.1752211792 | 0.4087519006 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1797241852 | 0.3027641051 | Pass | Pass | 0.1482521920 | 0.3507867567 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.3242572284E-002 | 5.7982929755E-002 | Pass | Pass | 0.1041436183 | 0.3038557695 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1066711698 | 0.1378045554 | Pass | Pass | 0.1060360019 | 0.3080367671 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2133163227 | 0.3291106137 | Pass | Pass | 0.1182598679 | 0.3255331985 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1129235914 | 0.1703904218 | Pass | Pass | 0.1023271807 | 0.2955682901 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.2554410669E-002 | 4.4241001505E-002 | Pass | Pass | 4.8279739237E-002 | 0.2087004123 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.5571792695E-002 | 0.1129698752 | Pass | Pass | 4.9131650255E-002 | 0.2151165566 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1690464526 | 0.1815144727 | Pass | Pass | 6.5614216868E-002 | 0.2860097696 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1078676118 | 0.1437323241 | Pass | Pass | 4.6886084853E-002 | 0.2036567094 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2226961362E-002 | 2.9921195420E-002 | Pass | Pass | 0.2203958252 | 0.7050054636 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0916681913E-002 | 3.0780105181E-002 | Pass | Pass | 1.5077633252 | 10.1293171055 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6630095976E-002 | 5.9625133316E-002 | Pass | Pass | 4.9609632673E-002 | 0.2132180989 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7668763833E-006 | 6.3020680048E-006 | Pass | Pass | 5.5863561948E-003 | 6.7040918266E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.7395627313E-006 | 4.6343728669E-006 | Pass | Pass | 2.5961118956E-002 | 1.6005941441E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7392500231E-002 | 2.8969668723E-002 | Pass | Pass | 0.3470575389 | 2.3187720001 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9487422427E-005 | 1.0803343105E-004 | Pass | Pass | 6.2315472928E-005 | 1.0811693621E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5982.46 | 84.46 | 0.00 | 20769.75 | 20722.57 | 47559.23 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.498_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.498_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.498_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 2.831 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.831 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 10.2732 | 2779.43 | 28553.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 262.84 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 10.2732 | 24961.20 | 256432.45 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 2360.52 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 10.2732 | 2496.12 | 25643.24 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 236.05 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.83 | 0.0000 | Y | 17.42 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.65 | 0.0000 | Y | 11.16 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.17 | 0.0000 | Y | 17.03 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.25 | 0.0000 | Y | 11.00 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 10.2732 | 3134.13 | 32197.65 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.73 | 0.0000 | Y | 173.63 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.59 | 0.0000 | Y | 111.37 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 10.2732 | 3134.20 | 32198.36 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.13 | 0.0000 | Y | 170.04 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 10.2732 | 2019.75 | 20749.39 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 109.85 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 10.2732 | 313.41 | 3219.77 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.73 | 0.0000 | Y | 17.36 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.59 | 0.0000 | Y | 11.14 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 10.2732 | 313.42 | 3219.84 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.13 | 0.0000 | Y | 17.00 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 10.2732 | 201.98 | 2074.94 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.20 | 0.0000 | Y | 10.98 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 10.2732 | 783.68 | 8050.93 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 74.11 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 17.8735 | 362.03 | 6470.68 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 66.28 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 17.8735 | 36.20 | 647.07 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 6.63 |
Interior Lighting Total | 10.3445 | 46320.38 | 479162.15 | 1234.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.84 | 1241.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.84 | 445.95 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 3219.77 | 1241.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 3219.77 | 445.94 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2074.94 | 800.30 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2074.94 | 287.38 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13279.00 | AstronomicalClock | - | 41.77 | 41.77 | 104.11 | |
EXTERIOR_LIGHTS_B | 44301.60 | AstronomicalClock | - | 83.77 | 71.17 | 591.83 | |
Exterior Lighting Total | 57580.60 | 695.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2502259.34 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2132562.87 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1279961.49 | 6.28 | 1225100.22 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1279961.49 | 6.28 | 1225100.22 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 578899.65 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1519888.95 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1519888.95 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 206598.19 | 330203.69 | 200028.95 | 130174.73 | 0.61 | - | 62863.64 | 637.60 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1972450.33 | 3107726.01 | 1879314.13 | 1228411.88 | 0.60 | - | 583207.19 | 5915.21 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 211993.39 | 341704.14 | 207218.29 | 134485.84 | 0.61 | - | 65615.50 | 665.51 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 116985.15 | 190551.16 | 116812.27 | 73738.88 | 0.61 | - | 34637.97 | 351.32 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 469001.64 | 261269.78 | 207731.86 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10230.20 | 5733.28 | 4496.92 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 97419.61 | 54578.42 | 42841.19 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9960.73 | 5579.49 | 4381.24 | 0.56 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17657.79 | 16744.97 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 410999.60 | 389505.40 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 81164.55 | 76933.27 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11225.97 | 10640.17 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7915.29 | 7502.08 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13345.83 | 12648.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6706.40 | 6355.56 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 207183.94 | 196347.13 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 137571.42 | 130375.06 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 204754.92 | 194045.53 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 128650.48 | 121922.01 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26358.94 | 24979.37 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17393.31 | 16482.93 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26095.76 | 24730.00 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16646.84 | 15775.61 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 49210.40 | 39006.41 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 432533.93 | 346318.54 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 42828.07 | 34870.11 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 294319.41 | 233468.13 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 469001.64 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10230.20 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 97419.61 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9960.73 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16051.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 741.49 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7414.91 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 741.49 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.47 | 24653.76 | 2149.46 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 107.40 | 230858.88 | 2149.46 | 1.00 | 1.08 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.91 | 25592.06 | 2149.46 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.86 | 11549.65 | 1684.71 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.70 | 40731.05 | 1649.25 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 614.71 | 1120.11 | 1.00 | 1.57 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.22 | 5850.47 | 1120.11 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 597.88 | 1120.11 | 1.00 | 1.58 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.106697 | 17420.40 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018657 | 5618.55 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.053349 | 6030.37 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.053349 | 6030.37 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014366 | 3664.07 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.126681 | 31363.44 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.48 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82298.72 | 82298.72 | 29.61 | 6.856 | 6.856 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 28.48 | 0.00686 | 1.200 | 0.00 |
CORE_BOTTOM | 85484.97 | 85484.97 | 34.25 | 7.120 | 7.120 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 28.48 | 0.00686 | 1.078 | 0.00 |
CORE_MID | 808210.42 | 808210.42 | 323.79 | 67.303 | 67.303 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 28.48 | 0.00686 | 10.778 | 0.00 |
CORE_TOP | 79887.63 | 79887.63 | 32.00 | 6.653 | 6.653 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 28.48 | 0.00686 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15298.86 | 15298.86 | 48.81 | 1.285 | 1.285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00724 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14691.88 | 14691.88 | 72.74 | 1.234 | 1.234 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00716 | 32.05 | 0.00686 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17070.73 | 17070.73 | 54.47 | 1.434 | 1.434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00722 | 37.77 | 0.00687 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18970.98 | 18970.98 | 93.93 | 1.594 | 1.594 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00713 | 36.80 | 0.00687 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 146897.93 | 146897.93 | 468.70 | 12.340 | 12.340 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00724 | 38.10 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 152633.48 | 152633.48 | 755.70 | 12.822 | 12.822 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00715 | 32.42 | 0.00686 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 163978.47 | 163978.47 | 523.19 | 13.775 | 13.775 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00722 | 37.88 | 0.00687 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 166367.97 | 166367.97 | 823.71 | 13.976 | 13.976 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00714 | 36.63 | 0.00687 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16602.17 | 16602.17 | 52.97 | 1.395 | 1.395 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00721 | 37.97 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15574.17 | 15574.17 | 77.11 | 1.308 | 1.308 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00715 | 33.16 | 0.00686 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18164.87 | 18164.87 | 57.96 | 1.526 | 1.526 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00720 | 38.10 | 0.00687 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17893.55 | 17893.55 | 88.59 | 1.503 | 1.503 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00713 | 36.63 | 0.00687 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8283.63 | 8283.63 | 228.81 | 0.549 | 0.549 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 25.19 | 0.00685 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78829.48 | 78829.48 | 2177.45 | 5.223 | 5.223 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00709 | 34.01 | 0.00686 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8055.91 | 8055.91 | 222.52 | 0.534 | 0.534 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 27.00 | 27.00 | 0.00709 | 34.33 | 0.00687 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372737.34 | 372737.34 | 475.62 | 24.696 | 24.696 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 26.27 | 0.00685 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 24.36 | 0.00281 | -5.20 | 0.00281 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19.60 | 21.81 | 0.00281 | -5.20 | 0.00281 | 1.078 | 0.00 |
CORE_MID | 237036.40 | 237036.40 | 94.96 | 11.520 | 11.520 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 10.778 | 0.00 |
CORE_TOP | 56838.65 | 56838.65 | 22.77 | 2.786 | 2.786 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7861.86 | 7861.86 | 25.08 | 0.386 | 0.386 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5542.45 | 5542.45 | 27.44 | 0.272 | 0.272 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9343.89 | 9343.89 | 29.81 | 0.459 | 0.459 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3926.70 | 3926.70 | 19.44 | 0.192 | 0.192 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 144991.85 | 144991.85 | 462.62 | 7.126 | 7.126 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 96273.15 | 96273.15 | 476.66 | 4.732 | 4.732 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 143293.75 | 143293.75 | 457.19 | 7.042 | 7.042 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 90036.35 | 90036.35 | 445.78 | 4.425 | 4.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -5.20 | 0.00281 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18443.37 | 18443.37 | 58.85 | 0.907 | 0.907 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12169.96 | 12169.96 | 60.25 | 0.599 | 0.599 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -5.20 | 0.00281 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18259.38 | 18259.38 | 58.26 | 0.898 | 0.898 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -5.20 | 0.00281 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11648.04 | 11648.04 | 57.67 | 0.573 | 0.573 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 18.00 | 26.08 | 0.00698 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.09 | 0.00386 | -5.20 | 0.00281 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.25 | 0.00321 | -5.20 | 0.00281 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 02:40:00 | 18.00 | 27.00 | 0.00700 | -5.20 | 0.00281 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.47 | 11.47 | 2.39 | 2.39 | 11.4697 | 3.1315 | 11.4697 | 0.2730 | 0.3000 |
VAV_MID WITH REHEAT | 107.40 | 107.40 | 34.84 | 34.84 | 107.4030 | 34.8448 | 107.4030 | 0.3244 | 0.3000 |
VAV_TOP WITH REHEAT | 11.91 | 11.91 | 5.76 | 5.76 | 11.9062 | 5.7619 | 11.9062 | 0.4839 | 0.3000 |
CAV_BAS | 6.86 | 6.86 | 1.20 | 1.20 | 6.8556 | 6.8556 | 6.8556 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.70 | 24.70 | 0.34 | 0.34 | 24.6968 | 24.6965 | 24.6968 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.55 | 0.55 | 0.02 | 0.02 | 0.5488 | 0.5488 | 0.5488 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.22 | 5.22 | 0.16 | 0.16 | 5.2231 | 5.2231 | 5.2231 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.53 | 0.53 | 0.02 | 0.02 | 0.5338 | 0.5338 | 0.5338 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17657.787 | 17657.787 | 2.022118 | 0.00015448 | 355.967 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 17657.79 | 17657.79 | 2.022118 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 17722.90 | 17722.90 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 410999.603 | 410999.603 | 19.921760 | 0.00359560 | 9587.904 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 410999.60 | 410999.60 | 19.921760 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 237036.40 | 0.00 | 412352.13 | 412352.13 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 81164.552 | 81164.552 | 2.785732 | 0.00071006 | 2142.540 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81164.55 | 81164.55 | 2.785732 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 56838.65 | 0.00 | 81445.34 | 81445.34 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 11225.970 | 11225.970 | 0.385538 | 0.00009821 | 296.253 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11225.97 | 11225.97 | 0.385538 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00765588 | 42.9495 | 7861.86 | 0.00 | 11264.20 | 11264.20 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7915.294 | 7915.294 | 0.271908 | 0.00006925 | 208.859 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7915.29 | 7915.29 | 0.271908 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00770582 | 43.2260 | 5542.45 | 0.00 | 7942.07 | 7942.07 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13345.835 | 13345.835 | 0.458531 | 0.00011676 | 352.129 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13345.83 | 13345.83 | 0.458531 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776541 | 43.5557 | 9343.89 | 0.00 | 13390.80 | 13390.80 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6706.405 | 6706.405 | 0.318727 | 0.00005867 | 157.320 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6706.40 | 6706.40 | 0.318727 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00739878 | 41.5250 | 3926.70 | 0.00 | 6728.41 | 6728.41 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 207183.944 | 207183.944 | 7.126107 | 0.00181254 | 5463.812 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 207183.94 | 207183.94 | 7.126107 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775789 | 43.5148 | 144991.85 | 0.00 | 207862.42 | 207862.42 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 137571.416 | 137571.416 | 4.732051 | 0.00120353 | 3627.909 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 137571.42 | 137571.42 | 4.732051 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775833 | 43.5172 | 96273.15 | 0.00 | 138021.24 | 138021.24 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 204754.919 | 204754.919 | 7.042402 | 0.00179129 | 5399.809 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 204754.92 | 204754.92 | 7.042402 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775456 | 43.4963 | 143293.75 | 0.00 | 205425.84 | 205425.84 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 128650.482 | 128650.482 | 4.424678 | 0.00112549 | 3392.836 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 128650.48 | 128650.48 | 4.424678 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00773840 | 43.4069 | 90036.35 | 0.00 | 129072.45 | 129072.45 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26358.939 | 26358.939 | 0.906979 | 0.00023060 | 695.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26358.94 | 26358.94 | 0.906979 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776926 | 43.5781 | 18443.37 | 0.00 | 26444.34 | 26444.34 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17393.313 | 17393.313 | 0.598505 | 0.00015216 | 458.601 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17393.31 | 17393.31 | 0.598505 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776711 | 43.5663 | 12169.96 | 0.00 | 17449.61 | 17449.61 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 26095.764 | 26095.764 | 0.897910 | 0.00022830 | 688.071 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26095.76 | 26095.76 | 0.897910 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776697 | 43.5654 | 18259.38 | 0.00 | 26180.35 | 26180.35 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16646.839 | 16646.839 | 0.572787 | 0.00014563 | 438.931 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16646.84 | 16646.84 | 0.572787 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775682 | 43.5093 | 11648.04 | 0.00 | 16700.80 | 16700.80 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 206598.189 | -999.000 | 11.469721 | 0.00878916 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 206598.19 | 201264.63 | 11.469721 | 27.18 | 14.95 | 0.00721708 | 10.78 | 8.48 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 22.1295 | 24.00 | 0.00731776 | 34.2302 | 133935.06 | 0.00 | 233083.68 | 225468.78 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 49210.398 | 49210.398 | 3.440916 | 0.00043051 | 821.649 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 49210.40 | 49210.40 | 3.440916 | -0.83 | -1.64 | 0.00350725 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 73.7649 | 21.28 | 0.00609393 | 33.6859 | 26674.90 | 0.00 | 47194.61 | 47194.61 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1972450.329 | -999.000 | 107.402970 | 0.08391260 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1972450.33 | 1919836.41 | 107.402970 | 27.48 | 15.06 | 0.00722778 | 10.78 | 8.48 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 23.6324 | 24.00 | 0.00734477 | 34.3551 | 1222284.42 | 0.00 | 2221249.74 | 2146391.11 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 432533.932 | 432533.932 | 32.220891 | 0.00378400 | 7258.229 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 432533.93 | 432533.93 | 32.220891 | 0.01 | -0.70 | 0.00385465 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 78.7748 | 19.60 | 0.00760717 | 46.5385 | 387177.64 | 0.00 | 419058.81 | 419058.81 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 211993.390 | -999.000 | 11.906249 | 0.00901869 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 211993.39 | 206742.20 | 11.906249 | 27.01 | 14.88 | 0.00720639 | 10.78 | 8.48 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 21.3181 | 24.00 | 0.00729739 | 34.1359 | 141411.32 | 0.00 | 239433.50 | 231898.68 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 42828.069 | 42828.069 | 3.571875 | 0.00037468 | 724.796 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 42828.07 | 42828.07 | 3.571875 | 1.37 | 0.58 | 0.00422521 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 71.0604 | 17.60 | 0.00762360 | 52.8595 | 49273.44 | 0.00 | 42198.95 | 42198.95 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 116985.150 | -999.000 | 6.855553 | 0.00497682 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 116985.15 | 112093.23 | 6.855553 | 26.41 | 14.79 | 0.00734423 | 11.22 | 8.66 | 0.00700000 | 36.41 | 0.00686877 | 17.66 | 17.5063 | 24.00 | 0.00745871 | 34.8820 | 73623.64 | 0.00 | 132437.76 | 127477.62 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 294319.411 | 294319.411 | 6.855553 | 0.00257483 | 6555.096 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 294319.41 | 294319.41 | 6.855553 | -0.91 | -2.74 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.5063 | 24.43 | 0.00280840 | 12.8963 | 0.00 | 0.00 | 246605.24 | 246605.24 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 469001.638 | 261269.779 | 24.696756 | 0.01148582 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 406878.53 | 405053.19 | -999.0 | 28.76 | 15.34 | 0.00703970 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | -999.0000 | 27.00 | 0.00704204 | 27.5791 | 372272.94 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10230.203 | 5733.279 | 0.548794 | 0.00025054 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 8844.85 | 8762.63 | -999.0 | 28.31 | 15.22 | 0.00708102 | 12.80 | 9.33 | 0.00700000 | 34.66 | 0.00686598 | 17.11 | -999.0000 | 27.00 | 0.00708734 | 27.7527 | 8266.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97419.608 | 54578.417 | 5.223132 | 0.00238580 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 84235.71 | 83416.11 | -999.0 | 28.31 | 15.22 | 0.00708484 | 12.80 | 9.33 | 0.00700000 | 34.33 | 0.00686546 | 17.01 | -999.0000 | 27.00 | 0.00709161 | 27.7694 | 78822.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9960.730 | 5579.491 | 0.533772 | 0.00024394 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 8613.62 | 8531.52 | -999.0 | 28.32 | 15.23 | 0.00708315 | 12.80 | 9.33 | 0.00700000 | 34.98 | 0.00686649 | 17.21 | -999.0000 | 27.00 | 0.00708969 | 27.7619 | 8051.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 469001.638 | 469001.638 | 24.696756 | 0.01148582 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 469001.64 | 469001.64 | 24.696756 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.3702 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10230.203 | 10230.203 | 0.548794 | 0.00025054 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10230.20 | 10230.20 | 0.548794 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.8485 | 26.53 | 0.00698396 | 28.1237 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97419.608 | 97419.608 | 5.223132 | 0.00238580 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 97419.61 | 97419.61 | 5.223132 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9929 | 24.26 | 0.00385694 | 17.8644 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9960.730 | 9960.730 | 0.533772 | 0.00024394 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9960.73 | 9960.73 | 0.533772 | -5.20 | -5.20 | 0.00280840 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9287 | 23.10 | 0.00320689 | 15.9365 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16051.031 | 16051.031 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16051.03 | 16051.03 | 24.696756 | -0.07 | -0.07 | 0.00694257 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 1.3702 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 741.49 | 741.49 | 0.548794 | -0.15 | -0.15 | 0.00686502 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.8485 | 26.53 | 0.00698396 | 28.1237 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7414.911 | 7414.911 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7414.91 | 7414.91 | 5.223132 | -0.16 | -0.83 | 0.00382556 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9929 | 24.26 | 0.00385694 | 17.8644 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 741.49 | 741.49 | 0.533772 | -0.15 | -1.75 | 0.00319522 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 2.9287 | 23.10 | 0.00320689 | 15.9365 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17657.787 | 17657.787 | 2.022118 | 0.00015448 | 355.967 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.8117 | 0.828008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | Sensible | 17657.79 | 17657.79 | 1.0000 | 2.11176249 | 2.022118 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.15446227 | 60.00 | 32.22 | 27.78 | 0.000 | 17657.79 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 17722.90 | 17722.90 | 2.11176249 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 410999.603 | 410999.603 | 19.921760 | 0.00359560 | 9587.904 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 18.8924 | 19.272567 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 410999.60 | 410999.60 | 1.0000 | 20.80492644 | 19.921760 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 3.59523703 | 60.00 | 32.22 | 27.78 | 0.000 | 410999.60 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.82 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 237036.40 | 0.00 | 412352.13 | 412352.13 | 20.80492644 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.77 | 0.00800000 | 52879.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 81164.552 | 81164.552 | 2.785732 | 0.00071006 | 2142.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 3.7309 | 3.805963 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 81164.55 | 81164.55 | 1.0000 | 2.90922824 | 2.785732 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.70999048 | 60.00 | 32.22 | 27.78 | 0.000 | 81164.55 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 56838.65 | 0.00 | 81445.34 | 81445.34 | 2.90922824 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61055.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11225.970 | 11225.970 | 0.385538 | 0.00009821 | 296.253 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.5160 | 0.526407 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11225.97 | 11225.97 | 1.0000 | 0.40262954 | 0.385538 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09819967 | 60.00 | 32.22 | 27.78 | 0.000 | 11225.97 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00765588 | 21.00 | 0.00765588 | 42.9495 | 7861.86 | 0.00 | 11264.20 | 11264.20 | 0.40262954 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61036.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7915.294 | 7915.294 | 0.271908 | 0.00006925 | 208.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.3638 | 0.371163 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7915.29 | 7915.29 | 1.0000 | 0.28396241 | 0.271908 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06923938 | 60.00 | 32.22 | 27.78 | 0.000 | 7915.29 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00770582 | 21.00 | 0.00770582 | 43.2260 | 5542.45 | 0.00 | 7942.07 | 7942.07 | 0.28396241 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61028.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13345.835 | 13345.835 | 0.458531 | 0.00011676 | 352.129 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.6135 | 0.625812 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13345.83 | 13345.83 | 1.0000 | 0.47885852 | 0.458531 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11674327 | 60.00 | 32.22 | 27.78 | 0.000 | 13345.83 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00776541 | 21.00 | 0.00776541 | 43.5557 | 9343.89 | 0.00 | 13390.80 | 13390.80 | 0.47885852 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6706.405 | 6706.405 | 0.318727 | 0.00005867 | 157.320 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.3083 | 0.314476 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6706.40 | 6706.40 | 1.0000 | 0.33285666 | 0.318727 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05866457 | 60.00 | 32.22 | 27.78 | 0.000 | 6706.40 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00739878 | 21.00 | 0.00739878 | 41.5250 | 3926.70 | 0.00 | 6728.41 | 6728.41 | 0.33285666 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.62 | 18.90 | 0.00800000 | 53274.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 207183.944 | 207183.944 | 7.126107 | 0.00181254 | 5463.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 9.5236 | 9.715256 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 207183.94 | 207183.94 | 1.0000 | 7.44201920 | 7.126107 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 1.81235062 | 60.00 | 32.22 | 27.78 | 0.000 | 207183.94 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775789 | 21.00 | 0.00775789 | 43.5148 | 144991.85 | 0.00 | 207862.42 | 207862.42 | 7.44201920 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 137571.416 | 137571.416 | 4.732051 | 0.00120353 | 3627.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 6.3237 | 6.450990 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 137571.42 | 137571.42 | 1.0000 | 4.94183080 | 4.732051 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 1.20341199 | 60.00 | 32.22 | 27.78 | 0.000 | 137571.42 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775833 | 21.00 | 0.00775833 | 43.5172 | 96273.15 | 0.00 | 138021.24 | 138021.24 | 4.94183080 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 204754.919 | 204754.919 | 7.042402 | 0.00179129 | 5399.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 9.4119 | 9.601354 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 204754.92 | 204754.92 | 1.0000 | 7.35460354 | 7.042402 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 1.79110262 | 60.00 | 32.22 | 27.78 | 0.000 | 204754.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775456 | 21.00 | 0.00775456 | 43.4963 | 143293.75 | 0.00 | 205425.84 | 205425.84 | 7.35460354 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 128650.482 | 128650.482 | 4.424678 | 0.00112549 | 3392.836 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 5.9137 | 6.032670 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 128650.48 | 128650.48 | 1.0000 | 4.62083214 | 4.424678 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 1.12537573 | 60.00 | 32.22 | 27.78 | 0.000 | 128650.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773840 | 21.00 | 0.00773840 | 43.4069 | 90036.35 | 0.00 | 129072.45 | 129072.45 | 4.62083214 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26358.939 | 26358.939 | 0.906979 | 0.00023060 | 695.006 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 1.2116 | 1.236022 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26358.94 | 26358.94 | 1.0000 | 0.94718712 | 0.906979 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.23057597 | 60.00 | 32.22 | 27.78 | 0.000 | 26358.94 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776926 | 21.00 | 0.00776926 | 43.5781 | 18443.37 | 0.00 | 26444.34 | 26444.34 | 0.94718712 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17393.313 | 17393.313 | 0.598505 | 0.00015216 | 458.601 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.7995 | 0.815606 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17393.31 | 17393.31 | 1.0000 | 0.62503783 | 0.598505 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.15214877 | 60.00 | 32.22 | 27.78 | 0.000 | 17393.31 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776711 | 21.00 | 0.00776711 | 43.5663 | 12169.96 | 0.00 | 17449.61 | 17449.61 | 0.62503783 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26095.764 | 26095.764 | 0.897910 | 0.00022830 | 688.071 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 1.1995 | 1.223681 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26095.76 | 26095.76 | 1.0000 | 0.93771627 | 0.897910 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.22827384 | 60.00 | 32.22 | 27.78 | 0.000 | 26095.76 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776697 | 21.00 | 0.00776697 | 43.5654 | 18259.38 | 0.00 | 26180.35 | 26180.35 | 0.93771627 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16646.839 | 16646.839 | 0.572787 | 0.00014563 | 438.931 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 0.7652 | 0.780603 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16646.84 | 16646.84 | 1.0000 | 0.59817965 | 0.572787 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.14561895 | 60.00 | 32.22 | 27.78 | 0.000 | 16646.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775682 | 21.00 | 0.00775682 | 43.5093 | 11648.04 | 0.00 | 16700.80 | 16700.80 | 0.59817965 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 206598.189 | -999.000 | 11.469721 | 0.00878916 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2562 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.469721 | 11.97819315 | 4197.9300 | 999.8980 | 106.68638462 | 12.27 | 6.67 | 5.60 | 2508027.06 | 8.2375 | 8.237478 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 206598.19 | 201264.63 | 1.0000 | 11.97819315 | 11.469721 | 27.18 | 14.95 | 0.00721708 | 45725.5 | 10.78 | 8.48 | 0.00700000 | 28477.7 | 8.78826796 | 6.67 | 12.27 | 5.60 | 24653.758 | 181944.43 | 38.10 | 0.00687148 | 18.17 | 2.53819000 | 22.1295 | 24.00 | 0.00731776 | 24.00 | 0.00731776 | 34.2302 | 133935.06 | 0.00 | 233083.68 | 225468.78 | 11.97819315 | 27.18 | 16.41 | 0.00721708 | 45725.5 | 8.69 | 8.68 | 0.00696452 | 26266.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 49210.398 | 49210.398 | 3.440916 | 0.00043051 | 821.649 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.469721 | 11.97819315 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 2.2620 | 2.307571 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 49210.40 | 49210.40 | 1.0000 | 3.59345795 | 3.440916 | -0.83 | -1.64 | 0.00350725 | 7933.8 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.43047011 | 60.00 | 32.22 | 27.78 | 0.000 | 49210.40 | -5.20 | 0.00280840 | -5.20 | 2.53819000 | 73.7649 | 11.46 | 0.00547220 | 21.28 | 0.00609393 | 33.6859 | 26674.90 | 0.00 | 47194.61 | 47194.61 | 3.59345795 | 2.80 | 1.25 | 0.00350725 | 11603.2 | 15.79 | 8.03 | 0.00350725 | 24736.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1972450.329 | -999.000 | 107.402970 | 0.08391260 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2761 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.402970 | 112.16433009 | 4197.9300 | 999.8980 | 106.68638462 | 12.27 | 6.67 | 5.60 | 2508027.06 | 78.6455 | 78.645496 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1972450.33 | 1919836.41 | 1.0000 | 112.16433009 | 107.402970 | 27.48 | 15.06 | 0.00722778 | 46063.1 | 10.78 | 8.48 | 0.00700000 | 28477.7 | 83.90403675 | 6.67 | 12.27 | 5.60 | 230858.879 | 1741591.45 | 38.10 | 0.00687148 | 18.17 | 25.38195000 | 23.6324 | 24.00 | 0.00734477 | 24.00 | 0.00734477 | 34.3551 | 1222284.42 | 0.00 | 2221249.74 | 2146391.11 | 112.16433009 | 27.48 | 16.53 | 0.00722778 | 46063.1 | 8.69 | 8.67 | 0.00696263 | 26259.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 432533.932 | 432533.932 | 32.220891 | 0.00378400 | 7258.229 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 107.402970 | 112.16433009 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 19.8822 | 20.282353 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 432533.93 | 432533.93 | 1.0000 | 33.64929903 | 32.220891 | 0.01 | -0.70 | 0.00385465 | 9648.3 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 3.78360951 | 60.00 | 32.22 | 27.78 | 0.000 | 432533.93 | -5.20 | 0.00280840 | -5.20 | 25.38195000 | 78.7748 | 19.34 | 0.00773769 | 19.60 | 0.00760717 | 46.5385 | 387177.64 | 0.00 | 419058.81 | 419058.81 | 33.64929903 | 2.80 | 1.74 | 0.00385465 | 12473.9 | 15.11 | 8.11 | 0.00385465 | 24927.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 211993.390 | -999.000 | 11.906249 | 0.00901869 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2363 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.906249 | 12.43407359 | 4197.9300 | 999.8980 | 106.68638462 | 12.27 | 6.67 | 5.60 | 2508027.06 | 8.4526 | 8.452596 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 211993.39 | 206742.20 | 1.0000 | 12.43407359 | 11.906249 | 27.01 | 14.88 | 0.00720639 | 45527.0 | 10.78 | 8.48 | 0.00700000 | 28477.6 | 9.01776889 | 6.67 | 12.27 | 5.60 | 25592.060 | 186401.33 | 38.10 | 0.00687148 | 18.17 | 2.53819000 | 21.3181 | 24.00 | 0.00729739 | 24.00 | 0.00729739 | 34.1359 | 141411.32 | 0.00 | 239433.50 | 231898.68 | 12.43407359 | 27.01 | 16.34 | 0.00720639 | 45527.0 | 8.70 | 8.68 | 0.00696564 | 26270.8 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 42828.069 | 42828.069 | 3.571875 | 0.00037468 | 724.796 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.906249 | 12.43407359 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 1.9687 | 2.008291 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 42828.07 | 42828.07 | 1.0000 | 3.73022208 | 3.571875 | 1.37 | 0.58 | 0.00422521 | 11958.6 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.37464041 | 60.00 | 32.22 | 27.78 | 0.000 | 42828.07 | -5.20 | 0.00280840 | -5.20 | 2.53819000 | 71.0604 | 17.52 | 0.00770416 | 17.60 | 0.00762360 | 52.8595 | 49273.44 | 0.00 | 42198.95 | 42198.95 | 3.73022208 | 2.80 | 2.26 | 0.00422521 | 13402.5 | 13.97 | 8.01 | 0.00422521 | 24715.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 116985.150 | -999.000 | 6.855553 | 0.00497682 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4926 | 1004.8586 | 1.0443 | CAV_BAS FAN | Fan:ConstantVolume | 6.855553 | 7.15947171 | 4197.9300 | 999.8980 | 106.68638462 | 12.27 | 6.67 | 5.60 | 2508027.06 | 4.6644 | 4.664429 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 116985.15 | 112093.23 | 1.0000 | 7.15947171 | 6.855553 | 26.41 | 14.79 | 0.00734423 | 45262.8 | 11.22 | 8.66 | 0.00700000 | 28922.9 | 4.97631102 | 6.67 | 12.27 | 5.60 | 11549.651 | 105435.50 | 36.41 | 0.00686877 | 17.66 | 1.20015641 | 17.5063 | 24.00 | 0.00745871 | 24.00 | 0.00745871 | 34.8820 | 73623.64 | 0.00 | 132437.76 | 127477.62 | 7.15947171 | 26.41 | 16.25 | 0.00734423 | 45262.8 | 8.92 | 8.90 | 0.00706904 | 26764.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 294319.411 | 294319.411 | 6.855553 | 0.00257483 | 6555.096 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | CAV_BAS FAN | Fan:ConstantVolume | 6.855553 | 7.15947171 | 4197.9300 | 999.8980 | 18.65468714 | 54.44 | 82.22 | 27.78 | 2175481.55 | 13.5289 | 13.801207 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 294319.41 | 294319.41 | 1.0000 | 7.15947171 | 6.855553 | -0.91 | -2.74 | 0.00280840 | 6104.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 2.57457194 | 60.00 | 32.22 | 27.78 | 0.000 | 294319.41 | -5.20 | 0.00280840 | -5.20 | 1.20015641 | 17.5063 | 0.00 | 0.00280840 | 24.43 | 0.00280840 | 12.8963 | 0.00 | 0.00 | 246605.24 | 246605.24 | 7.15947171 | 12.80 | 5.73 | 0.00280840 | 19952.4 | 46.90 | 19.39 | 0.00280840 | 54397.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 469001.638 | 261269.779 | 24.696756 | 0.01148582 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9265 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 406878.53 | 405053.19 | 0.8675 | -999.0 | -999.0 | 28.76 | 15.34 | 0.00703970 | 46878.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406878.53 | 38.10 | 0.00687148 | 18.17 | 0.33839277 | -999.0000 | 27.00 | 0.00704204 | 27.00 | 0.00704204 | 27.5791 | 372272.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10230.203 | 5733.279 | 0.548794 | 0.00025054 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0033 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 8844.85 | 8762.63 | 0.8646 | -999.0 | -999.0 | 28.31 | 15.22 | 0.00708102 | 46527.5 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8844.85 | 34.66 | 0.00686598 | 17.11 | 0.01563234 | -999.0000 | 27.00 | 0.00708734 | 27.00 | 0.00708734 | 27.7527 | 8266.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 97419.608 | 54578.417 | 5.223132 | 0.00238580 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0104 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 84235.71 | 83416.11 | 0.8647 | -999.0 | -999.0 | 28.31 | 15.22 | 0.00708484 | 46538.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84235.71 | 34.33 | 0.00686546 | 17.01 | 0.15632344 | -999.0000 | 27.00 | 0.00709161 | 27.00 | 0.00709161 | 27.7694 | 78822.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9960.730 | 5579.491 | 0.533772 | 0.00024394 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0072 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 8613.62 | 8531.52 | 0.8648 | -999.0 | -999.0 | 28.32 | 15.23 | 0.00708315 | 46548.6 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8613.62 | 34.98 | 0.00686649 | 17.21 | 0.01563234 | -999.0000 | 27.00 | 0.00708969 | 27.00 | 0.00708969 | 27.7619 | 8051.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 469001.638 | 469001.638 | 24.696756 | 0.01148582 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 469001.64 | 469001.64 | 1.0000 | 25.79160610 | 24.696756 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 469001.64 | -5.20 | 0.00280840 | -5.20 | 0.33839277 | 1.3702 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10230.203 | 10230.203 | 0.548794 | 0.00025054 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10230.20 | 10230.20 | 1.0000 | 0.57312274 | 0.548794 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10230.20 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.8485 | 0.00 | 0.00698396 | 26.53 | 0.00698396 | 28.1237 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97419.608 | 97419.608 | 5.223132 | 0.00238580 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 97419.61 | 97419.61 | 1.0000 | 5.45468238 | 5.223132 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97419.61 | -5.20 | 0.00280840 | -5.20 | 0.15632344 | 2.9929 | 0.00 | 0.00385694 | 24.26 | 0.00385694 | 17.8644 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9960.730 | 9960.730 | 0.533772 | 0.00024394 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9960.73 | 9960.73 | 1.0000 | 0.55743452 | 0.533772 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9960.73 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.9287 | 0.00 | 0.00320689 | 23.10 | 0.00320689 | 15.9365 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16051.031 | 16051.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.696756 | 25.79160610 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16051.03 | 16051.03 | 1.0000 | 25.79160610 | 24.696756 | -0.07 | -0.07 | 0.00694257 | 17290.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16051.03 | -5.20 | 0.00280840 | -5.20 | 0.33839277 | 1.3702 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.4118 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.548794 | 0.57312274 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 741.49 | 741.49 | 1.0000 | 0.57312274 | 0.548794 | -0.15 | -0.15 | 0.00686502 | 17018.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 741.49 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.8485 | 0.00 | 0.00698396 | 26.53 | 0.00698396 | 28.1237 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7414.911 | 7414.911 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.223132 | 5.45468238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7414.91 | 7414.91 | 1.0000 | 5.45468238 | 5.223132 | -0.16 | -0.83 | 0.00382556 | 9410.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7414.91 | -5.20 | 0.00280840 | -5.20 | 0.15632344 | 2.9929 | 0.00 | 0.00385694 | 24.26 | 0.00385694 | 17.8644 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 741.491 | 741.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.533772 | 0.55743452 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 741.49 | 741.49 | 1.0000 | 0.55743452 | 0.533772 | -0.15 | -1.75 | 0.00319522 | 7837.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 741.49 | -5.20 | 0.00280840 | -5.20 | 0.01563234 | 2.9287 | 0.00 | 0.00320689 | 23.10 | 0.00320689 | 15.9365 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.47 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 107.40 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.91 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.86 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.70 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2908.33 | 1605.33 | 746.33 |
CORE_BOTTOM | 2738.50 | 1360.50 | 616.50 |
CORE_MID | 2175.00 | 2897.33 | 715.00 |
CORE_TOP | 2366.17 | 3536.00 | 938.67 |
PERIMETER_BOT_ZN_3 | 2387.83 | 3169.50 | 510.00 |
PERIMETER_BOT_ZN_2 | 2766.83 | 2768.67 | 584.83 |
PERIMETER_BOT_ZN_1 | 3090.17 | 2147.83 | 607.33 |
PERIMETER_BOT_ZN_4 | 3378.83 | 1844.67 | 668.50 |
PERIMETER_MID_ZN_3 | 2850.50 | 3747.83 | 1308.17 |
PERIMETER_MID_ZN_2 | 2532.33 | 2838.83 | 924.67 |
PERIMETER_MID_ZN_1 | 3003.33 | 2515.17 | 808.83 |
PERIMETER_MID_ZN_4 | 2951.00 | 3241.67 | 992.83 |
PERIMETER_TOP_ZN_3 | 3422.50 | 3914.00 | 1936.00 |
PERIMETER_TOP_ZN_2 | 3349.33 | 3406.33 | 1456.67 |
PERIMETER_TOP_ZN_1 | 3182.00 | 2835.00 | 1143.00 |
PERIMETER_TOP_ZN_4 | 3345.33 | 3464.17 | 1488.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 878.67 | 878.67 |
DATACENTER_MID_ZN_6 | 5919.67 | 185.50 | 185.50 |
DATACENTER_TOP_ZN_6 | 5542.17 | 383.00 | 328.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5889.00 | 5889.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5937.67 | 5912.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 62.00 | 0.00 | 3.33 |
CORE_BOTTOM | 0.00 | 3.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 15.17 | 0.00 | 8.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 55.17 | 0.00 | 53.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 70.50 | 0.00 | 65.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 158.83 | 0.00 | 67.17 |
PERIMETER_MID_ZN_3 | 4.50 | 7.50 | 0.00 | 4.67 |
PERIMETER_MID_ZN_2 | 4.17 | 60.67 | 0.00 | 59.00 |
PERIMETER_MID_ZN_1 | 0.50 | 71.17 | 0.00 | 68.50 |
PERIMETER_MID_ZN_4 | 1.17 | 60.67 | 0.00 | 35.00 |
PERIMETER_TOP_ZN_3 | 24.67 | 26.50 | 0.83 | 16.83 |
PERIMETER_TOP_ZN_2 | 21.50 | 69.83 | 0.33 | 61.83 |
PERIMETER_TOP_ZN_1 | 14.17 | 60.17 | 0.00 | 51.00 |
PERIMETER_TOP_ZN_4 | 13.17 | 65.50 | 0.00 | 36.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 163.00 | 0.00 | 135.00 |
DATACENTER_MID_ZN_6 | 0.00 | 120.50 | 0.00 | 101.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 79.50 | 0.00 | 63.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 839.17 | 0.00 | 668.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 28.17 | 1184.33 | 0.83 | 883.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 1.545 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 1.106 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.850 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.772 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.945 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 1.509 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 1.582 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 2.086 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.783 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 1.364 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 1.428 | 0.094 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 1.419 | 0.097 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.803 | 0.116 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 1.409 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 1.363 | 0.116 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 1.418 | 0.120 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 31.022 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.43 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.97 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.60 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1034.72 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 65465319.79 | 0.00 | 65465319.79 | 0.00 | 65465319.79 | 37848132.68 | 3820.91 | 1681.46 | 3257.63 | 378.52 |
CORE_BOTTOM | 47850430.76 | 0.00 | 47850430.76 | 0.00 | 47850430.76 | 33990283.35 | 4987.61 | 10.79 | 3761.60 | 506.89 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 5717.17 | 30.22 | 3012.61 | 167.10 |
CORE_TOP | 31867394.18 | 0.00 | 31867394.18 | 0.00 | 31867394.18 | 33990283.35 | 6006.90 | 21.09 | 2732.00 | 209.88 |
PERIMETER_BOT_ZN_3 | 5177387.41 | 0.00 | 5177387.41 | 398322.03 | 5575709.44 | 4267819.30 | 3886.63 | 61.08 | 4812.30 | 506.89 |
PERIMETER_BOT_ZN_2 | 5294654.66 | 0.00 | 5294654.66 | 265547.84 | 5560202.50 | 2750345.05 | 3397.15 | 15.72 | 5347.13 | 506.89 |
PERIMETER_BOT_ZN_1 | 8433772.08 | 0.00 | 8433772.08 | 398322.03 | 8832094.12 | 4267912.63 | 3527.99 | 40.44 | 5191.56 | 506.89 |
PERIMETER_BOT_ZN_4 | 7329800.50 | 0.00 | 7329800.50 | 265547.84 | 7595348.34 | 2750345.05 | 3335.34 | 0.00 | 5424.66 | 506.89 |
PERIMETER_MID_ZN_3 | 40657610.66 | 0.00 | 40657610.66 | 934163.77 | 41591774.43 | 42678193.03 | 4491.51 | 58.44 | 4210.06 | 167.10 |
PERIMETER_MID_ZN_2 | 47961001.73 | 0.00 | 47961001.73 | 622775.42 | 48583777.15 | 27503450.52 | 3807.31 | 5.15 | 4947.54 | 1076.10 |
PERIMETER_MID_ZN_1 | 73158448.08 | 0.00 | 73158448.08 | 934163.77 | 74092611.85 | 42679126.28 | 3924.36 | 19.28 | 4816.36 | 167.10 |
PERIMETER_MID_ZN_4 | 47445604.45 | 0.00 | 47445604.45 | 622775.42 | 48068379.87 | 27503450.52 | 3794.93 | 5.43 | 4959.64 | 167.10 |
PERIMETER_TOP_ZN_3 | 4176821.36 | 0.00 | 4176821.36 | 1159847.75 | 5336669.11 | 4267819.30 | 4116.59 | 48.56 | 4594.85 | 209.88 |
PERIMETER_TOP_ZN_2 | 4687003.90 | 0.00 | 4687003.90 | 773231.30 | 5460235.20 | 2750345.05 | 3915.82 | 4.42 | 4839.76 | 209.88 |
PERIMETER_TOP_ZN_1 | 6995139.55 | 0.00 | 6995139.55 | 1159847.75 | 8154987.30 | 4267912.63 | 3971.12 | 8.29 | 4780.59 | 209.88 |
PERIMETER_TOP_ZN_4 | 4740708.52 | 0.00 | 4740708.52 | 773231.30 | 5513939.82 | 2750345.05 | 3897.87 | 9.19 | 4852.94 | 209.88 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.51E+09 | 0.00 | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 383.64 | 947.58 | 7428.78 | 2653.99 |
Total Facility | 0.63E+10 | 0.00 | 0.63E+10 | 36332681.67 | 0.64E+10 | 0.50E+10 | 6510.72 | 4387.09 | 8377.40 | 3563.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.8554 | 0.0000 | 2.8554 | 0.0000 | 2.8554 | 1.2002 | 1276.64 | 1677.64 | 2988.72 |
CORE_BOTTOM | 2.0655 | 0.0000 | 2.0655 | 0.0000 | 2.0655 | 1.0778 | 2633.74 | 9.60 | 3299.66 |
CORE_MID | 15.8628 | 0.0000 | 15.8628 | 0.0000 | 15.8628 | 10.7782 | 3030.98 | 30.19 | 2881.84 |
CORE_TOP | 1.4417 | 0.0000 | 1.4417 | 0.0000 | 1.4417 | 1.0778 | 3297.42 | 21.04 | 2624.54 |
PERIMETER_BOT_ZN_3 | 0.2215 | 0.0000 | 0.2215 | 0.0094 | 0.2309 | 0.1353 | 1530.05 | 59.04 | 4353.91 |
PERIMETER_BOT_ZN_2 | 0.2281 | 0.0000 | 0.2281 | 0.0063 | 0.2343 | 0.0872 | 1081.60 | 15.26 | 4846.13 |
PERIMETER_BOT_ZN_1 | 0.3714 | 0.0000 | 0.3714 | 0.0094 | 0.3808 | 0.1353 | 1183.12 | 37.79 | 4722.09 |
PERIMETER_BOT_ZN_4 | 0.3152 | 0.0000 | 0.3152 | 0.0063 | 0.3215 | 0.0872 | 1025.23 | 0.00 | 4917.77 |
PERIMETER_MID_ZN_3 | 1.8389 | 0.0000 | 1.8389 | 0.0220 | 1.8609 | 1.3533 | 1808.53 | 58.36 | 4076.11 |
PERIMETER_MID_ZN_2 | 2.0623 | 0.0000 | 2.0623 | 0.0156 | 2.0779 | 0.8721 | 1141.25 | 2.62 | 3890.12 |
PERIMETER_MID_ZN_1 | 3.3519 | 0.0000 | 3.3519 | 0.0220 | 3.3739 | 1.3533 | 1239.55 | 19.05 | 4684.40 |
PERIMETER_MID_ZN_4 | 2.1471 | 0.0000 | 2.1471 | 0.0147 | 2.1618 | 0.8721 | 1135.34 | 5.17 | 4802.49 |
PERIMETER_TOP_ZN_3 | 0.1887 | 0.0000 | 0.1887 | 0.0273 | 0.2161 | 0.1353 | 1414.10 | 48.28 | 4480.62 |
PERIMETER_TOP_ZN_2 | 0.2132 | 0.0000 | 0.2132 | 0.0182 | 0.2314 | 0.0872 | 1226.08 | 3.55 | 4713.37 |
PERIMETER_TOP_ZN_1 | 0.3200 | 0.0000 | 0.3200 | 0.0273 | 0.3473 | 0.1353 | 1267.23 | 7.99 | 4667.78 |
PERIMETER_TOP_ZN_4 | 0.2146 | 0.0000 | 0.2146 | 0.0182 | 0.2328 | 0.0872 | 1216.86 | 6.80 | 4719.34 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15.9745 | 0.0000 | 15.9745 | 0.0000 | 15.9745 | 0.3384 | 220.62 | 947.58 | 4774.79 |
Total Facility | 278.2044 | 0.0000 | 278.2044 | 0.8655 | 279.0699 | 158.4706 | 3693.72 | 4371.82 | 5723.14 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 80800389.22 | 0.00 | 80800389.22 | 48026705.38 | 3392.89 | 6.31 | 5360.81 | 506.89 |
VAV_MID WITH REHEAT | 0.61E+09 | 0.00 | 0.61E+09 | 0.48E+09 | 3877.27 | 3.06 | 4879.67 | 167.10 |
VAV_TOP WITH REHEAT | 57222094.37 | 0.00 | 57222094.37 | 48026705.38 | 3960.96 | 2.06 | 4796.98 | 209.88 |
CAV_BAS | 71398360.94 | 0.00 | 71398360.94 | 37848132.68 | 3807.50 | 3.62 | 4948.88 | 378.52 |
AIRLOOP DATACENTER BASEMENT | 0.56E+09 | 0.00 | 0.56E+09 | 10671554.30 | 383.64 | 0.00 | 8376.36 | 2653.99 |
AIRLOOP DATACENTER BOT | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2664362.65 | 0.00 | 2664362.65 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 266436.27 | 0.00 | 266436.27 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.4919 | 0.0000 | 3.4919 | 1.5229 | 1056.87 | 4.13 | 4882.00 |
VAV_MID WITH REHEAT | 27.6808 | 0.0000 | 27.6808 | 15.2292 | 1193.20 | 2.61 | 4747.19 |
VAV_TOP WITH REHEAT | 2.5937 | 0.0000 | 2.5937 | 1.5229 | 1255.45 | 1.63 | 4685.92 |
CAV_BAS | 3.1142 | 0.0000 | 3.1142 | 1.2002 | 1274.44 | 0.25 | 4668.31 |
AIRLOOP DATACENTER BASEMENT | 17.4222 | 0.0000 | 17.4222 | 0.3384 | 220.62 | 0.00 | 5722.38 |
AIRLOOP DATACENTER BOT | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1245 | 0.0000 | 0.1245 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0125 | 0.0000 | 0.0125 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.07 | 3814.82 | 0.00 | 0.00 | 0.00 | 1609.78 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.40 | 3216.88 | 0.00 | 0.00 | 0.00 | 1773.64 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3027.50 | 0.00 | 0.00 | 0.00 | 1976.78 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1677.50 | 3381.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 947.58 | 7428.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.4126 | 0.0000 | 0.0000 | 0.0000 | 1.7727 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 43.4395 | 0.0000 | 0.0000 | 0.0000 | 18.0648 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.2247 | 0.0000 | 0.0000 | 0.0000 | 1.7781 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3093 | 5.4337 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3693 | 21.6151 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0171 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1705 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0171 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1395 |
Defaulted Fields | 1182 |
Fields with Defaults | 3867 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
Electricity:Building | 18603.52 | 225766.98 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:50 |
Electricity:Zone:BASEMENT | 687.24 | 14732.47 | 01-JAN-00:10 | 36407.88 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 18603.52 | 225766.98 | 14-MAY-17:10 | 1164206.62 | 01-DEC-16:50 |
InteriorLights:Electricity | 3927.12 | 18459.50 | 01-JAN-09:10 | 385834.94 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3927.12 | 18459.50 | 01-JAN-09:10 | 385834.94 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 3927.12 | 18459.50 | 01-JAN-09:10 | 385834.94 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 262.84 | 1274.92 | 01-JAN-00:10 | 22950.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3927.12 | 18459.50 | 01-JAN-09:10 | 385834.94 | 17-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 525.67 | 5598.20 | 01-JAN-00:10 | 37817.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5256.66 | 55981.88 | 01-JAN-00:10 | 378175.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 2360.53 | 11449.71 | 01-JAN-00:10 | 206110.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 525.67 | 5598.19 | 01-JAN-00:10 | 37817.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 236.05 | 1144.97 | 01-JAN-00:10 | 20611.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 53.79 | 627.57 | 30-APR-17:10 | 4748.47 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.42 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.42 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.60 | 408.71 | 16-APR-17:10 | 3060.10 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.16 | 44.08 | 01-JAN-08:10 | 1667.75 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.16 | 44.08 | 01-JAN-08:10 | 1667.75 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 53.39 | 627.58 | 19-MAR-17:10 | 4748.56 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.03 | 68.40 | 01-JAN-08:20 | 2587.98 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.03 | 68.40 | 01-JAN-08:20 | 2587.98 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.44 | 404.43 | 12-MAR-17:10 | 3060.09 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.00 | 44.08 | 01-JAN-09:10 | 1667.75 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.00 | 44.08 | 01-JAN-09:10 | 1667.75 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 537.28 | 6275.73 | 30-APR-17:10 | 47484.70 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 173.63 | 684.02 | 01-JAN-09:10 | 25879.19 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 173.63 | 684.02 | 01-JAN-09:10 | 25879.19 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 345.72 | 4044.32 | 09-JUL-17:10 | 30600.95 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.37 | 440.81 | 01-JAN-08:10 | 16677.53 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 111.37 | 440.81 | 01-JAN-08:10 | 16677.53 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 533.71 | 6275.83 | 19-MAR-17:10 | 47485.60 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.05 | 684.04 | 01-JAN-08:20 | 25879.75 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.05 | 684.04 | 01-JAN-08:20 | 25879.75 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 344.20 | 4044.30 | 12-MAR-17:10 | 30600.86 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.85 | 440.81 | 01-JAN-09:10 | 16677.53 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 109.85 | 440.81 | 01-JAN-09:10 | 16677.53 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 53.73 | 627.57 | 30-APR-17:10 | 4748.47 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.36 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.36 | 68.40 | 01-JAN-09:10 | 2587.92 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.57 | 404.43 | 09-JUL-17:10 | 3060.10 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.14 | 44.08 | 01-JAN-08:10 | 1667.75 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.14 | 44.08 | 01-JAN-08:10 | 1667.75 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 53.37 | 627.58 | 19-MAR-17:10 | 4748.56 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.00 | 68.40 | 01-JAN-08:20 | 2587.98 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.00 | 68.40 | 01-JAN-08:20 | 2587.98 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.42 | 404.43 | 12-MAR-17:10 | 3060.09 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.98 | 44.08 | 01-JAN-09:10 | 1667.75 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.98 | 44.08 | 01-JAN-09:10 | 1667.75 | 17-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7568.97 | 95267.60 | 01-JAN-00:10 | 386103.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 74.11 | 359.47 | 01-JAN-00:10 | 6471.01 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1605.09 | 19807.58 | 01-JAN-00:10 | 83731.41 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 66.28 | 321.53 | 01-JAN-00:10 | 5787.18 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 160.51 | 1980.76 | 01-JAN-00:10 | 8373.14 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 6.63 | 32.15 | 01-JAN-00:10 | 578.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3041.20 | 4148.29 | 28-JAN-04:40 | 518036.56 | 21-JUL-09:50 |
HeatRejection:Electricity | 1078.17 | 320.17 | 27-JAN-07:20 | 86451.33 | 21-APR-13:50 |
General:HeatRejection:Electricity | 1078.17 | 320.17 | 27-JAN-07:20 | 86451.33 | 21-APR-13:50 |
Electricity:HVAC | 6635.44 | 51642.34 | 16-JAN-04:50 | 557157.78 | 23-AUG-15:20 |
ExteriorEquipment:Electricity | 1934.79 | 28603.11 | 01-JAN-00:10 | 118527.01 | 13-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 80.18 | 1421.04 | 01-JAN-00:10 | 5057.48 | 01-DEC-17:00 |
ElectricityPurchased:Facility | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
ElectricityPurchased:Plant | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
Cogeneration:ElectricityPurchased | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
ElectricityNet:Plant | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
Cogeneration:ElectricityNet | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
General:Cogeneration:ElectricityNet | 30830.71 | 338621.35 | 15-JAN-14:50 | 2067513.91 | 23-AUG-16:00 |
Fans:Electricity | 2826.39 | 47794.11 | 09-JAN-05:50 | 272666.80 | 03-JUL-14:30 |
General:Fans:Electricity | 2826.39 | 47794.11 | 09-JAN-05:50 | 272666.80 | 03-JUL-14:30 |
ExteriorLights:Electricity | 695.94 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 695.94 | 0.00 | 01-JAN-07:20 | 57580.60 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3365.31 | 2400.59 | 16-JAN-09:00 | 545030.27 | 21-JUL-09:50 |
General:Cooling:Electricity | 3365.31 | 2400.59 | 16-JAN-09:00 | 545030.27 | 21-JUL-09:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1786.22 | 0.00 | 15-JAN-13:20 | 100000.00 | 01-JAN-01:10 |
General:Humidifier:Electricity | 1786.22 | 0.00 | 15-JAN-13:20 | 100000.00 | 01-JAN-01:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 540.37 | 3664.07 | 01-JAN-00:10 | 57132.28 | 20-JUL-15:10 |
General:Pumps:Electricity | 540.37 | 3664.07 | 01-JAN-00:10 | 57132.28 | 20-JUL-15:10 |
WIRED_LTG_ELECTRICITY | 110.35 | 0.00 | 01-JAN-00:10 | 10841.96 | 17-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1054.57 | 8146.58 | 15-APR-16:10 | 677954.45 | 27-DEC-07:10 |
NaturalGas:Plant | 1054.57 | 8146.58 | 15-APR-16:10 | 677954.45 | 27-DEC-07:10 |
Heating:NaturalGas | 336.00 | 0.00 | 01-JAN-00:10 | 646583.87 | 27-DEC-07:10 |
Boiler:Heating:NaturalGas | 336.00 | 0.00 | 01-JAN-00:10 | 646583.87 | 27-DEC-07:10 |
WaterSystems:NaturalGas | 718.57 | 8146.58 | 01-MAR-05:10 | 80952.23 | 30-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 718.57 | 8146.58 | 01-MAR-05:10 | 80952.23 | 30-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 17333.13 | 10391.36 | 17-JAN-07:10 | 3794688.22 | 20-JUL-15:00 |
PlantLoopCoolingDemand:HVAC | 17333.13 | 10391.36 | 17-JAN-07:10 | 3794688.22 | 20-JUL-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 17333.13 | 10391.36 | 17-JAN-07:10 | 3794688.22 | 20-JUL-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 12508.92 | 0.00 | 16-JAN-00:10 | 0.00 | 15-JUN-12:30 |
Water:HVAC | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Humidifier:Water | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:Water | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
MainsWater:Facility | 12508.92 | 0.00 | 16-JAN-00:10 | 0.00 | 15-JUN-12:30 |
MainsWater:HVAC | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Humidifier:MainsWater | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
General:Humidifier:MainsWater | 664.47 | 0.00 | 15-JAN-13:20 | 0.00 | 01-FEB-05:10 |
Water:Plant | 11844.45 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-12:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 11844.45 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-12:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 9564.28 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:10 |
General:HeatRejection:Water | 9564.28 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:10 |
HeatRejection:MainsWater | 9564.28 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:10 |
General:HeatRejection:MainsWater | 9564.28 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JUN-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 67659.42 | 98429.95 | 16-JAN-05:50 | 13282495.61 | 20-JUL-15:00 |
EnergyTransfer:Building | 20794.27 | 89749.53 | 16-JAN-08:20 | 1695306.30 | 07-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 741.66 | 0.00 | 01-JAN-00:10 | 75651.90 | 10-OCT-05:10 |
Heating:EnergyTransfer | 111.16 | 0.00 | 01-JAN-15:50 | 338361.13 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.16 | 0.00 | 01-JAN-00:10 | 25710.91 | 01-JUL-16:10 |
General:Heating:EnergyTransfer | 111.16 | 0.00 | 01-JAN-15:50 | 338361.13 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.16 | 0.00 | 01-JAN-00:10 | 25710.91 | 01-JUL-16:10 |
Cooling:EnergyTransfer | 20683.11 | 89144.34 | 16-JAN-08:20 | 1695306.30 | 07-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 737.50 | 0.00 | 01-JAN-00:10 | 75651.90 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 20683.11 | 89144.34 | 16-JAN-08:20 | 1695306.30 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 737.50 | 0.00 | 01-JAN-00:10 | 75651.90 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 710.40 | 0.00 | 01-JAN-00:10 | 59239.59 | 07-AUG-10:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 710.40 | 0.00 | 01-JAN-00:10 | 59239.59 | 07-AUG-10:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 710.40 | 0.00 | 01-JAN-00:10 | 59239.59 | 07-AUG-10:30 |
EnergyTransfer:Zone:CORE_MID | 5250.16 | 0.00 | 01-JAN-00:10 | 459877.09 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5250.16 | 0.00 | 01-JAN-00:10 | 459877.09 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5250.16 | 0.00 | 01-JAN-00:10 | 459877.09 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 495.41 | 0.00 | 01-JAN-00:10 | 54258.64 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 1.41 | 0.00 | 01-JAN-00:10 | 42685.89 | 04-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 1.41 | 0.00 | 01-JAN-00:10 | 42685.89 | 04-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 494.00 | 0.00 | 01-JAN-00:10 | 54258.64 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 494.00 | 0.00 | 01-JAN-00:10 | 54258.64 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.42 | 0.00 | 01-JAN-00:10 | 11989.54 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2291.37 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2291.37 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.41 | 0.00 | 01-JAN-00:10 | 11989.54 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.41 | 0.00 | 01-JAN-00:10 | 11989.54 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.98 | 0.00 | 01-JAN-00:10 | 13141.02 | 30-MAY-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1800.18 | 28-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1800.18 | 28-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.94 | 0.00 | 01-JAN-00:10 | 13141.02 | 30-MAY-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.94 | 0.00 | 01-JAN-00:10 | 13141.02 | 30-MAY-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.32 | 0.00 | 01-JAN-00:10 | 17939.08 | 30-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2902.87 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2902.87 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.29 | 0.00 | 01-JAN-00:10 | 17939.08 | 30-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.29 | 0.00 | 01-JAN-00:10 | 17939.08 | 30-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.12 | 0.00 | 01-JAN-00:10 | 18318.47 | 04-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.12 | 0.00 | 01-JAN-00:10 | 18318.47 | 04-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.12 | 0.00 | 01-JAN-00:10 | 18318.47 | 04-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 668.88 | 0.00 | 01-JAN-00:10 | 109748.02 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.95 | 0.00 | 01-JAN-00:10 | 83159.16 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.95 | 0.00 | 01-JAN-00:10 | 83159.16 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 646.94 | 0.00 | 01-JAN-00:10 | 109748.02 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 646.94 | 0.00 | 01-JAN-00:10 | 109748.02 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 736.52 | 0.00 | 01-JAN-00:10 | 132945.08 | 07-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.41 | 0.00 | 01-JAN-00:10 | 55114.58 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.41 | 0.00 | 01-JAN-00:10 | 55114.58 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 726.10 | 0.00 | 01-JAN-00:10 | 132945.08 | 07-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 726.10 | 0.00 | 01-JAN-00:10 | 132945.08 | 07-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1130.04 | 0.00 | 01-JAN-00:10 | 175969.01 | 30-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.73 | 0.00 | 01-JAN-00:10 | 61528.05 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.73 | 0.00 | 01-JAN-00:10 | 61528.05 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1123.31 | 0.00 | 01-JAN-00:10 | 175969.01 | 30-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1123.31 | 0.00 | 01-JAN-00:10 | 175969.01 | 30-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 785.54 | 0.00 | 01-JAN-00:10 | 153866.88 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.96 | 0.00 | 01-JAN-00:10 | 40894.59 | 28-JAN-05:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.96 | 0.00 | 01-JAN-00:10 | 40894.59 | 28-JAN-05:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 778.58 | 0.00 | 01-JAN-00:10 | 153866.88 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 778.58 | 0.00 | 01-JAN-00:10 | 153866.88 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.82 | 0.00 | 01-JAN-00:10 | 15625.77 | 18-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.98 | 0.00 | 01-JAN-00:10 | 15625.77 | 18-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.98 | 0.00 | 01-JAN-00:10 | 15625.77 | 18-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.84 | 0.00 | 01-JAN-00:10 | 12225.25 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.84 | 0.00 | 01-JAN-00:10 | 12225.25 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.92 | 0.00 | 01-JAN-00:10 | 13668.55 | 03-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.04 | 0.00 | 01-JAN-00:10 | 10850.69 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.04 | 0.00 | 01-JAN-00:10 | 10850.69 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.89 | 0.00 | 01-JAN-00:10 | 13668.55 | 03-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.89 | 0.00 | 01-JAN-00:10 | 13668.55 | 03-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 112.29 | 0.00 | 01-JAN-00:10 | 18824.23 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.06 | 0.00 | 01-JAN-00:10 | 14359.45 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.06 | 0.00 | 01-JAN-00:10 | 14359.45 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.23 | 0.00 | 01-JAN-00:10 | 18824.23 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.23 | 0.00 | 01-JAN-00:10 | 18824.23 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.34 | 0.00 | 01-JAN-00:10 | 16246.54 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.16 | 0.00 | 01-JAN-00:10 | 8671.02 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.16 | 0.00 | 01-JAN-00:10 | 8671.02 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 77.18 | 0.00 | 01-JAN-00:10 | 16246.54 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 77.18 | 0.00 | 01-JAN-00:10 | 16246.54 | 15-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.02 | 0.00 | 01-JAN-00:10 | 12442.77 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.95 | 0.00 | 01-JAN-00:10 | 3178.07 | 31-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.95 | 0.00 | 01-JAN-00:10 | 3178.07 | 31-DEC-11:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.06 | 0.00 | 01-JAN-00:10 | 12442.77 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.06 | 0.00 | 01-JAN-00:10 | 12442.77 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 603.12 | 0.00 | 01-JAN-00:10 | 87521.48 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.26 | 0.00 | 01-JAN-00:10 | 29892.05 | 04-DEC-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.26 | 0.00 | 01-JAN-00:10 | 29892.05 | 04-DEC-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 581.85 | 0.00 | 01-JAN-00:10 | 87521.48 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 581.85 | 0.00 | 01-JAN-00:10 | 87521.48 | 03-JUL-14:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 111.96 | 0.00 | 01-JAN-00:10 | 22810.41 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.53 | 0.00 | 01-JAN-00:10 | 16581.50 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.53 | 0.00 | 01-JAN-00:10 | 16581.50 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.43 | 0.00 | 01-JAN-00:10 | 22810.41 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.43 | 0.00 | 01-JAN-00:10 | 22810.41 | 03-JUL-13:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.32 | 839.23 | 28-JAN-08:00 | 7938.92 | 18-DEC-16:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.32 | 839.23 | 28-JAN-08:00 | 7938.92 | 18-DEC-16:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.32 | 839.23 | 28-JAN-08:00 | 7938.92 | 18-DEC-16:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.34 | 893.35 | 16-JAN-08:30 | 75149.68 | 26-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.34 | 893.35 | 16-JAN-08:30 | 75149.68 | 26-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.34 | 893.35 | 16-JAN-08:30 | 75149.68 | 26-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.76 | 1.32 | 14-JAN-16:30 | 7585.24 | 26-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.48 | 0.00 | 01-JAN-15:00 | 623.19 | 30-JAN-04:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.48 | 0.00 | 01-JAN-15:00 | 623.19 | 30-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.29 | 0.00 | 01-JAN-00:10 | 7585.24 | 26-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.29 | 0.00 | 01-JAN-00:10 | 7585.24 | 26-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 87088.36 | 16-JAN-05:50 | 374043.47 | 27-AUG-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 87088.36 | 16-JAN-05:50 | 374043.47 | 27-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 87088.36 | 16-JAN-05:50 | 374043.47 | 27-AUG-21:00 |
PlantLoopHeatingDemand:Facility | 599.93 | 0.00 | 01-JAN-00:10 | 562768.55 | 27-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 359.12 | 0.00 | 01-JAN-00:10 | 46356.69 | 30-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 359.12 | 0.00 | 01-JAN-00:10 | 46356.69 | 30-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 359.12 | 0.00 | 01-JAN-00:10 | 46356.69 | 30-JAN-13:00 |
EnergyTransfer:HVAC | 15631.29 | 8517.58 | 16-JAN-09:00 | 3627004.57 | 20-JUL-15:00 |
HeatingCoils:EnergyTransfer | 240.81 | 0.00 | 01-JAN-00:10 | 547758.92 | 27-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 240.81 | 0.00 | 01-JAN-00:10 | 547758.92 | 27-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 240.81 | 0.00 | 01-JAN-00:10 | 547758.92 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 15390.48 | 7255.07 | 17-JAN-07:10 | 3627004.57 | 20-JUL-15:00 |
EnergyTransfer:Plant | 31233.85 | 0.00 | 01-JAN-00:10 | 8339623.32 | 20-JUL-15:00 |
LoopToLoop:EnergyTransfer | 9816.02 | 0.00 | 01-JAN-00:10 | 2848327.01 | 20-JUL-15:00 |
WaterSystems:EnergyTransfer | 359.12 | 0.00 | 01-JAN-00:10 | 46356.69 | 30-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 359.12 | 0.00 | 01-JAN-00:10 | 46356.69 | 30-JAN-13:00 |
Boilers:EnergyTransfer | 238.39 | 0.00 | 01-JAN-00:10 | 537099.17 | 27-DEC-07:10 |
Chillers:EnergyTransfer | 9698.83 | 0.00 | 01-JAN-00:10 | 2559922.97 | 20-JUL-15:00 |
HeatRejection:EnergyTransfer | 11121.49 | 0.00 | 01-JAN-00:10 | 2940310.90 | 21-JUL-09:50 |
General:HeatRejection:EnergyTransfer | 11121.49 | 0.00 | 01-JAN-00:10 | 2940310.90 | 21-JUL-09:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.159 | -737.500 | 0.000 | 0.000 | 92.687 | 262.844 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -46.587 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -710.396 | 0.000 | 0.000 | 83.417 | 236.053 | 289.614 | 0.000 | 0.000 | 0.000 | 101.312 | 0.000 | 0.000 | 0.000 | 0.000 | -0.012 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5250.136 | 0.000 | 0.000 | 837.214 | 2360.527 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -843.733 |
CORE_TOP | 0.000 | 0.000 | 1.412 | -493.998 | 0.000 | 0.000 | 85.307 | 236.053 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -118.386 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.017 | -86.407 | 0.000 | 0.000 | 10.651 | 17.422 | 36.365 | 32.109 | 0.000 | 0.404 | 49.285 | 0.000 | -56.793 | 0.000 | -3.053 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.032 | -81.944 | 0.000 | 0.000 | 6.839 | 11.160 | 23.435 | 66.484 | 0.000 | 0.283 | 9.565 | 0.000 | -33.839 | 0.000 | -2.016 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.029 | -130.287 | 0.000 | 0.000 | 10.545 | 17.027 | 36.366 | 113.563 | 0.000 | 0.400 | 7.185 | 0.000 | -51.665 | 0.000 | -3.163 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -122.115 | 0.000 | 0.000 | 6.794 | 11.005 | 23.435 | 65.808 | 0.000 | 0.241 | 58.473 | 0.000 | -41.323 | 0.000 | -2.318 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 21.948 | -646.931 | 0.000 | 0.000 | 110.295 | 173.630 | 363.654 | 335.054 | 0.000 | 9.253 | 204.653 | 0.000 | -508.713 | 0.000 | -62.842 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 10.414 | -726.103 | 0.000 | 0.000 | 51.341 | 111.372 | 234.352 | 664.393 | 0.000 | 6.048 | 10.149 | 0.000 | -318.036 | 0.000 | -43.931 | -0.008 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 6.728 | -1123.291 | 0.000 | 0.000 | 106.190 | 170.046 | 363.660 | 1132.665 | 0.000 | 8.932 | 0.002 | 0.000 | -499.793 | 0.000 | -71.115 | -94.020 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.959 | -778.561 | 0.000 | 0.000 | 70.551 | 109.852 | 234.351 | 673.271 | 0.000 | 5.651 | 78.863 | 0.000 | -354.866 | 0.000 | -46.070 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.982 | -64.835 | 0.000 | 0.000 | 11.206 | 17.361 | 36.365 | 33.784 | 0.000 | 1.107 | 10.474 | 0.000 | -47.288 | 0.000 | -7.156 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.039 | -71.886 | 0.000 | 0.000 | 7.060 | 11.137 | 23.435 | 66.691 | 0.000 | 0.716 | 0.003 | 0.000 | -29.909 | 0.000 | -5.072 | -6.211 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.057 | -108.232 | 0.000 | 0.000 | 10.746 | 17.004 | 36.366 | 113.614 | 0.000 | 1.066 | 0.001 | 0.000 | -47.083 | 0.000 | -8.245 | -19.293 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.164 | -77.176 | 0.000 | 0.000 | 7.141 | 10.984 | 23.435 | 67.313 | 0.000 | 0.682 | 3.414 | 0.000 | -33.580 | 0.000 | -5.377 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.323 | 0.000 | 0.000 | 0.947 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.133 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1280.336 | 0.000 | 0.000 | 9.477 | 66.280 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -334.226 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.476 | -121.285 | 0.000 | 0.000 | 0.949 | 6.628 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -40.648 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7165.949 | 0.000 | 0.000 | 19.735 | 74.111 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -422.754 |
GROUNDFLOOR_PLENUM | 0.953 | -86.064 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.743 | 91.164 | 0.000 | 0.000 | 0.000 | -6.795 | 0.000 |
MIDFLOOR_PLENUM | 21.263 | -581.851 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.642 | 662.525 | 0.000 | 0.000 | 0.000 | -115.579 | 0.000 |
TOPFLOOR_PLENUM | 16.532 | -95.428 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.305 | 89.355 | 0.000 | 0.000 | 0.000 | -11.764 | -0.001 |
Total Facility | 38.748 | -763.343 | 72.414 | -19919.692 | 0.000 | 0.000 | 1539.091 | 3927.125 | 14676.396 | 3364.749 | 0.000 | 50.472 | 1376.430 | 0.000 | -2022.889 | 0.000 | -394.497 | -1945.020 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | -121642.56 | 0.00 | 0.00 | 0.00 | 2550.13 | 13457.54 | 0.00 | 0.00 | 0.00 | 105634.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | -102012.55 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.65 | 0.00 | 0.00 | 0.00 | 93784.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:12 | 0.00 | 0.00 | 0.00 | -889422.26 | 0.00 | 0.00 | 0.00 | 22901.98 | 59376.23 | 0.00 | 0.00 | 0.00 | 807144.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-04:13 | 0.00 | 0.00 | 0.00 | -89691.06 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 81463.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:01 | 0.00 | 0.00 | 0.00 | -19495.60 | 0.00 | 0.00 | 0.00 | 68.40 | 559.17 | 5785.19 | 0.00 | 48.96 | 13033.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:51 | 0.00 | 0.00 | 0.00 | -20589.42 | 0.00 | 0.00 | 21.18 | 44.08 | 464.11 | 13470.56 | 0.00 | 0.00 | 6657.05 | 0.00 | -0.00 | 0.00 | -67.56 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:41 | 0.00 | 0.00 | 0.00 | -24586.92 | 0.00 | 0.00 | 31.89 | 68.40 | 720.19 | 22312.00 | 0.00 | 0.00 | 1636.13 | 0.00 | -0.00 | 0.00 | -181.70 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:41 | 0.00 | 0.00 | 0.00 | -28479.00 | 0.00 | 0.00 | 16.42 | 44.08 | 464.11 | 15719.98 | 0.00 | 30.19 | 12204.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -185911.23 | 0.00 | 0.00 | 418.69 | 684.02 | 7201.84 | 41502.03 | 0.00 | 4967.52 | 131137.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 | -214355.32 | 0.00 | 0.00 | 210.36 | 440.81 | 4641.14 | 147596.22 | 0.00 | 0.00 | 61658.30 | 0.00 | -0.00 | 0.00 | -191.50 | 0.00 |
PERIMETER_MID_ZN_1 | 22-OCT-13:11 | 0.00 | 0.00 | 0.00 | -236655.48 | 0.00 | 0.00 | 322.50 | 684.04 | 7201.95 | 186278.01 | 0.00 | 0.00 | 42392.84 | 0.00 | -0.00 | 0.00 | -223.86 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -251531.74 | 0.00 | 0.00 | 164.08 | 440.81 | 4641.11 | 143959.01 | 0.00 | 2267.33 | 100059.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -21744.97 | 0.00 | 0.00 | 39.37 | 68.40 | 720.18 | 3964.03 | 0.00 | 578.08 | 16374.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 | -21880.34 | 0.00 | 0.00 | 20.95 | 44.08 | 464.11 | 14699.65 | 0.00 | 0.00 | 6677.22 | 0.00 | -0.00 | 0.00 | -25.67 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:41 | 0.00 | 0.00 | 0.00 | -25987.04 | 0.00 | 0.00 | 32.31 | 68.40 | 720.19 | 17029.40 | 0.00 | 0.00 | 8193.23 | 0.00 | -0.00 | 0.00 | -56.49 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -27665.38 | 0.00 | 0.00 | 14.89 | 44.08 | 464.11 | 14250.23 | 0.00 | 260.96 | 12631.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 18-DEC-16:50 | 0.00 | 0.00 | 0.00 | -7939.00 | 0.00 | 0.00 | 100.85 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -534.99 |
DATACENTER_MID_ZN_6 | 26-APR-18:00 | 0.00 | 0.00 | 0.00 | -75145.05 | 0.00 | 0.00 | 106.16 | 1929.04 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4834.37 |
DATACENTER_TOP_ZN_6 | 26-APR-17:50 | 0.00 | 0.00 | 0.00 | -7584.79 | 0.00 | 0.00 | 10.62 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -413.15 |
DATACENTER_BASEMENT_ZN_6 | 21-AUG-23:13 | 0.00 | 0.00 | 0.00 | -378202.04 | 0.00 | 0.00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1789.96 |
GROUNDFLOOR_PLENUM | 07-AUG-05:15 | 0.00 | -16736.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 16736.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-JUN-05:02 | 0.00 | -90929.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91295.25 | 0.00 | -0.00 | 0.00 | -365.84 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:10 | 0.00 | -22809.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.90 | 22669.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-04:12 | 0.00 | 48087.72 | 0.00 | -2120656.28 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 1514590.50 | 0.00 | -72193.45 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUL-16:01 | 0.00 | 0.00 | 27225.97 | 0.00 | 0.00 | 0.00 | 520.13 | 1274.92 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -42478.56 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-DEC-05:01 | 0.00 | 0.00 | 76404.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2290.20 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84632.57 |
PERIMETER_BOT_ZN_3 | 28-JAN-06:01 | 0.00 | 0.00 | 9488.89 | 0.00 | 0.00 | 0.00 | 144.82 | 287.56 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6844.11 | 0.00 | -183.77 | -3853.64 |
PERIMETER_BOT_ZN_2 | 28-JAN-06:01 | 0.00 | 0.00 | 6797.61 | 0.00 | 0.00 | 0.00 | 93.79 | 185.31 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4549.03 | 0.00 | -122.18 | -3024.32 |
PERIMETER_BOT_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 11103.52 | 0.00 | 0.00 | 0.00 | 145.85 | 287.56 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6675.35 | 0.00 | -103.72 | -5718.13 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 142650.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.57 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52129.47 | 0.00 | -12534.73 | -88317.49 |
PERIMETER_MID_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 135365.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35084.77 | 0.00 | -8539.42 | -98399.37 |
PERIMETER_MID_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 151678.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2875.64 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52838.91 | 0.00 | -13194.88 | -95975.62 |
PERIMETER_MID_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 129487.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.13 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34965.01 | 0.00 | -8819.53 | -92361.04 |
PERIMETER_TOP_ZN_3 | 26-DEC-04:11 | 0.00 | 0.00 | 17984.36 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4266.43 | 0.00 | -1289.17 | -13318.08 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:11 | 0.00 | 0.00 | 16630.15 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2866.03 | 0.00 | -875.76 | -13461.48 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:11 | 0.00 | 0.00 | 19376.31 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4265.70 | 0.00 | -1317.37 | -14682.57 |
PERIMETER_TOP_ZN_4 | 26-DEC-04:11 | 0.00 | 0.00 | 17753.75 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2922.98 | 0.00 | -909.45 | -14494.43 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 30-JAN-04:00 | 0.00 | 0.00 | 623.19 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2603.95 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 12660.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2638.44 | -10022.02 |
MIDFLOOR_PLENUM | 06-AUG-14:51 | 90345.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7738.88 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -98084.63 |
TOPFLOOR_PLENUM | 04-DEC-05:13 | 20381.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -257.94 | -20123.19 |
Total Facility | 26-DEC-05:01 | -817821.79 | 760759.74 | 700028.09 | -760759.74 | 0.00 | 0.00 | 0.00 | 42872.09 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211021.73 | 0.00 | -76840.99 | -224515.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.6671 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.4697 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 120.2155 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 107.4030 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.3846 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.9062 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8556 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8556 | 0.1751 | 1.0000 | Not calculated | 1.2002 | 0.1751 | ||
AIRLOOP DATACENTER BASEMENT | 24.6965 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6968 | 0.0137 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5488 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5488 | 0.0285 | 1.0000 | Not calculated | 0.0156 | 0.0285 | ||
AIRLOOP DATACENTER MID | 5.2231 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.2231 | 0.0299 | 1.0000 | Not calculated | 0.1563 | 0.0299 | ||
AIRLOOP DATACENTER TOP | 0.5338 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5338 | 0.0293 | 1.0000 | Not calculated | 0.0156 | 0.0293 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.3336 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1315 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 60.1078 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.5289 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1923 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1887 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.8556 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.8556 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1751 | ||
AIRLOOP DATACENTER BASEMENT | 24.6965 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.6965 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5488 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5488 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0285 | ||
AIRLOOP DATACENTER MID | 5.2231 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.2231 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0299 | ||
AIRLOOP DATACENTER TOP | 0.5338 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5338 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0293 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8556 | 6.8556 | 6.8556 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1201 | 7.1201 | 2.0221 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 67.3032 | 67.3032 | 19.9218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6526 | 6.6526 | 2.0423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2852 | 1.2852 | 0.2570 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2342 | 1.2342 | 0.2468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4340 | 1.4340 | 0.2868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5936 | 1.5936 | 0.3187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3401 | 12.3401 | 2.4927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.8218 | 12.8218 | 2.5644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.7749 | 13.7749 | 2.7550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.9755 | 13.9755 | 2.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3947 | 1.3947 | 0.2789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3083 | 1.3083 | 0.2617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5259 | 1.5259 | 0.3052 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5031 | 1.5031 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5488 | 0.5488 | 0.5488 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2231 | 5.2231 | 5.2231 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5338 | 0.5338 | 0.5338 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6965 | 24.6965 | 24.6965 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.6671 | 11.4697 | 12.6671 | 3.1315 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 120.2155 | 107.4030 | 120.2155 | 30.5289 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.3846 | 11.9062 | 12.3846 | 3.1887 | 0.0000 | 1.0000 |
CAV_BAS | 6.8556 | 6.8556 | 6.8556 | 6.8556 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6965 | 24.6968 | 24.6965 | 24.6965 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5488 | 0.5488 | 0.5488 | 0.5488 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.2231 | 5.2231 | 5.2231 | 5.2231 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5338 | 0.5338 | 0.5338 | 0.5338 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.8556 | 6.8556 | 6.8556 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5601 | 3.5601 | 2.0221 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 33.6516 | 33.6516 | 19.9218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3263 | 3.3263 | 2.0423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6426 | 0.6426 | 0.2570 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6171 | 0.6171 | 0.2468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7170 | 0.7170 | 0.2868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7968 | 0.7968 | 0.3187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1700 | 6.1700 | 2.4927 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4109 | 6.4109 | 2.5644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8874 | 6.8874 | 2.7550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9878 | 6.9878 | 2.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6973 | 0.6973 | 0.2789 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6541 | 0.6541 | 0.2617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7630 | 0.7630 | 0.3052 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7516 | 0.7516 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5488 | 0.5488 | 0.5488 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2231 | 5.2231 | 5.2231 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5338 | 0.5338 | 0.5338 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.6965 | 24.6965 | 24.6965 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.3336 | 3.1315 | 3.1315 | 3.1315 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 60.1078 | 30.5289 | 30.5289 | 30.5289 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1923 | 3.1887 | 3.1887 | 3.1887 | 0.0000 | 1.0000 |
CAV_BAS | 6.8556 | 6.8556 | 6.8556 | 6.8556 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.6965 | 24.6965 | 24.6965 | 24.6965 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5488 | 0.5488 | 0.5488 | 0.5488 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.2231 | 5.2231 | 5.2231 | 5.2231 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5338 | 0.5338 | 0.5338 | 0.5338 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 883.00 |
Number of hours not met | 883.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 336.00 | 646583.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3365.31 | 545030.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3927.12 | 385834.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 695.94 | 57580.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 80.18 | 5057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2826.39 | 272666.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 540.37 | 57132.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1078.17 | 86451.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1786.22 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 718.57 | 80952.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30830.71 |
Natural Gas | 0.00 | 1054.57 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31885.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 84.78 |
Space Heating | 0.00 |
Space Cooling | 72.65 |
Fans (All) | 61.02 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 665.60 |
Subtotal | 665.60 |
Natural Gas [MJ/m2] | |
Space Heating | 7.25 |
Service Water Heating | 15.51 |
Miscellaneous (All) | 22.77 |
Subtotal | 22.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.32 |
Space Heating | 1.05 |
Space Cooling | 10.55 |
Fans (All) | 8.86 |
Service Water Heating | 2.25 |
Receptacle Equipment | 46.03 |
Miscellaneous | 18.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8363.83 | 396.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8314.50 | 445.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8649.83 | 110.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8679.83 | 80.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8527.50 | 232.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8717.33 | 42.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8632.67 | 127.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8511.33 | 248.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8609.50 | 150.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8642.67 | 117.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8672.17 | 87.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6925.00 | 1821.33 | 13.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8581.33 | 178.67 | 0.00 | 0.00 | 0.00 |
Min | 6925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1821.33 | 13.67 | 0.00 | 0.00 |
Average | 8567.58 | 191.83 | 0.59 | 0.00 | 0.00 |
Sum | 197054.33 | 4412.00 | 13.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367385.17 | 1230.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330774.00 | 39.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2202.00 | 66.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2212.17 | 55.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2230.00 | 38.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82523.83 | 20445.17 | 426.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367385.17 | 20445.17 | 426.00 | 0.00 | 0.00 |
Average | 79365.31 | 951.08 | 18.52 | 0.00 | 0.00 |
Sum | 1825402.17 | 21874.83 | 426.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7919.67 | 840.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8360.50 | 399.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8374.50 | 385.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8364.00 | 396.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8343.00 | 417.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8430.83 | 329.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8316.17 | 443.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7942.50 | 817.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8337.17 | 422.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8260.83 | 499.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8254.33 | 505.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8160.50 | 599.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8328.33 | 431.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8252.17 | 507.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8256.00 | 504.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8171.33 | 588.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7199.83 | 1560.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8224.83 | 535.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8304.83 | 455.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7796.67 | 963.33 | 0.00 | 0.00 | 0.00 |
Min | 7199.83 | 14.00 | 0.00 | 0.00 | 0.00 |
Max | 8746.00 | 1560.17 | 0.00 | 0.00 | 0.00 |
Average | 8252.86 | 507.14 | 0.00 | 0.00 | 0.00 |
Sum | 189815.67 | 11664.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 364479.00 | 4137.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330119.00 | 694.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330350.00 | 463.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330220.00 | 593.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38924.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2252.17 | 15.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2256.50 | 11.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2261.17 | 6.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85280.00 | 18115.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364479.00 | 18115.00 | 0.00 | 0.00 | 0.00 |
Average | 79289.81 | 1045.10 | 0.00 | 0.00 | 0.00 |
Sum | 1823665.67 | 24037.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:43:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552402E+11 | 120011.53 | 17-JAN-05:11 | 5.20 | 3.69 | 0.566546E+10 | 7499.10 | 02-JAN-10:20 | 5.20 | 3.69 |
February | 0.481773E+11 | 115637.10 | 27-FEB-05:11 | 8.90 | 7.68 | 0.513795E+10 | 7499.37 | 13-FEB-10:20 | 8.90 | 7.68 |
March | 0.566494E+11 | 115399.34 | 13-MAR-04:12 | 4.60 | 1.75 | 0.613098E+10 | 7499.06 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.553798E+11 | 117458.20 | 10-APR-04:12 | 15.40 | 6.96 | 0.544934E+10 | 7499.19 | 05-APR-09:00 | 15.40 | 6.96 |
May | 0.597072E+11 | 119266.47 | 01-MAY-04:11 | 15.20 | 5.46 | 0.590164E+10 | 7499.07 | 08-MAY-09:09 | 24.87 | 11.71 |
June | 0.610742E+11 | 115845.00 | 26-JUN-04:12 | 21.50 | 14.53 | 0.588240E+10 | 7499.03 | 22-JUN-09:20 | 21.50 | 14.53 |
July | 0.642458E+11 | 112574.48 | 05-JUL-04:12 | 19.27 | 16.16 | 0.547548E+10 | 7499.00 | 27-JUL-09:09 | 27.07 | 18.93 |
August | 0.745850E+11 | 117764.34 | 20-AUG-16:40 | 32.40 | 15.84 | 0.613951E+10 | 7499.13 | 23-AUG-09:30 | 27.50 | 14.99 |
September | 0.679098E+11 | 117892.39 | 18-SEP-04:12 | 17.97 | 13.70 | 0.545491E+10 | 7499.13 | 06-SEP-09:30 | 17.97 | 13.70 |
October | 0.692322E+11 | 121641.50 | 30-OCT-04:11 | 10.93 | 6.49 | 0.567365E+10 | 7499.22 | 17-OCT-09:00 | 10.93 | 6.49 |
November | 0.646933E+11 | 119867.90 | 20-NOV-05:11 | 3.90 | -1.7 | 0.561696E+10 | 7498.90 | 03-NOV-09:20 | 3.90 | -1.7 |
December | 0.606090E+11 | 117802.26 | 11-DEC-05:11 | 10.93 | 5.91 | 0.547241E+10 | 7499.06 | 04-DEC-10:09 | 10.93 | 5.91 |
Annual Sum or Average | 0.737503E+12 | 0.680007E+11 | ||||||||
Minimum of Months | 0.481773E+11 | 112574.48 | 3.90 | -1.7 | 0.513795E+10 | 7498.90 | 3.90 | -1.7 | ||
Maximum of Months | 0.745850E+11 | 121641.50 | 32.40 | 16.16 | 0.613951E+10 | 7499.37 | 27.50 | 18.93 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437792E+11 | 96859.57 | 02-JAN-05:11 | 2.40 | 1.50 | 0.507301E+10 | 6734.82 | 02-JAN-10:09 | 10.97 | 7.20 |
February | 0.439414E+11 | 94722.29 | 21-FEB-05:12 | 4.80 | 0.06 | 0.460230E+10 | 6735.11 | 13-FEB-10:09 | 4.80 | 0.06 |
March | 0.566410E+11 | 93470.97 | 13-MAR-04:12 | 4.60 | 1.75 | 0.549793E+10 | 6734.71 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.630913E+11 | 94962.28 | 24-APR-04:12 | 12.43 | 5.03 | 0.488075E+10 | 6734.84 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.603236E+11 | 98953.47 | 22-MAY-04:13 | 18.13 | 13.85 | 0.528618E+10 | 6734.88 | 08-MAY-09:09 | 18.13 | 13.85 |
June | 0.671415E+11 | 99758.80 | 09-JUN-04:13 | 22.43 | 14.45 | 0.526722E+10 | 6734.78 | 22-JUN-09:09 | 22.88 | 16.93 |
July | 0.713959E+11 | 91513.54 | 05-JUL-04:12 | 19.27 | 16.16 | 0.489333E+10 | 6734.71 | 11-JUL-09:09 | 29.18 | 18.50 |
August | 0.807417E+11 | 94570.18 | 14-AUG-05:04 | 17.30 | 16.19 | 0.549533E+10 | 6734.83 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.590200E+11 | 100914.36 | 18-SEP-04:13 | 17.97 | 13.70 | 0.488383E+10 | 6734.76 | 12-SEP-09:30 | 17.97 | 13.70 |
October | 0.592855E+11 | 100943.77 | 10-OCT-04:11 | 13.17 | 8.78 | 0.507912E+10 | 6735.04 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.540934E+11 | 102016.63 | 13-NOV-05:11 | 2.93 | 0.58 | 0.503015E+10 | 6734.67 | 24-NOV-10:09 | 17.48 | 6.61 |
December | 0.509430E+11 | 97221.68 | 11-DEC-05:11 | 10.93 | 5.91 | 0.490248E+10 | 6734.76 | 04-DEC-10:09 | 10.93 | 5.91 |
Annual Sum or Average | 0.710397E+12 | 0.608916E+11 | ||||||||
Minimum of Months | 0.437792E+11 | 91513.54 | 2.40 | 0.06 | 0.460230E+10 | 6734.67 | 4.80 | 0.06 | ||
Maximum of Months | 0.807417E+11 | 102016.63 | 22.43 | 16.19 | 0.549793E+10 | 6735.11 | 31.70 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311859E+11 | 76775.12 | 13-JAN-06:03 | 3.22 | 0.84 | 0.499919E+10 | 6734.72 | 23-JAN-10:20 | 5.97 | 4.15 |
February | 0.316620E+11 | 80460.28 | 23-FEB-06:03 | 10.60 | 5.29 | 0.455827E+10 | 6735.01 | 13-FEB-10:09 | 10.60 | 5.29 |
March | 0.406391E+11 | 82878.53 | 09-MAR-06:02 | 7.70 | 1.78 | 0.546903E+10 | 6734.71 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.443064E+11 | 86136.24 | 28-APR-04:11 | 15.53 | 9.82 | 0.487149E+10 | 6734.82 | 27-APR-09:09 | 15.53 | 9.82 |
May | 0.519055E+11 | 86673.17 | 24-MAY-04:12 | 17.60 | 13.85 | 0.528079E+10 | 6734.84 | 08-MAY-09:09 | 17.60 | 13.85 |
June | 0.548462E+11 | 87766.55 | 23-JUN-04:12 | 19.40 | 14.79 | 0.526581E+10 | 6734.78 | 22-JUN-09:09 | 19.40 | 14.79 |
July | 0.534501E+11 | 88960.68 | 05-JUL-04:12 | 19.27 | 16.16 | 0.489108E+10 | 6734.71 | 11-JUL-09:09 | 29.18 | 18.50 |
August | 0.561497E+11 | 88073.62 | 30-AUG-04:12 | 18.50 | 14.17 | 0.549429E+10 | 6734.77 | 17-AUG-13:20 | 18.50 | 14.17 |
September | 0.490694E+11 | 88725.13 | 06-SEP-04:12 | 16.50 | 15.71 | 0.487817E+10 | 6734.77 | 06-SEP-09:09 | 25.28 | 18.43 |
October | 0.451803E+11 | 86989.36 | 03-OCT-04:12 | 19.23 | 14.46 | 0.506432E+10 | 6734.99 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.360902E+11 | 81725.51 | 02-NOV-05:02 | 8.90 | 7.46 | 0.499324E+10 | 6734.61 | 02-NOV-09:09 | 9.50 | 8.56 |
December | 0.305307E+11 | 59875.97 | 02-DEC-06:02 | 4.40 | 0.38 | 0.482139E+10 | 6734.71 | 20-DEC-10:09 | 7.35 | -0.8 |
Annual Sum or Average | 0.525016E+12 | 0.605871E+11 | ||||||||
Minimum of Months | 0.305307E+11 | 59875.97 | 3.22 | 0.38 | 0.455827E+10 | 6734.61 | 5.97 | -0.8 | ||
Maximum of Months | 0.561497E+11 | 88960.68 | 19.40 | 16.16 | 0.549429E+10 | 6735.01 | 29.18 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225514E+11 | 33686.17 | 12-JAN-16:50 | 17.98 | 9.87 | 0.460377E+10 | 6734.46 | 11-JAN-14:00 | 17.98 | 9.87 |
February | 0.240562E+11 | 36412.72 | 23-FEB-15:30 | 20.00 | 7.14 | 0.430742E+10 | 6734.59 | 15-FEB-14:50 | 20.00 | 7.14 |
March | 0.333256E+11 | 67227.01 | 16-MAR-05:03 | 14.43 | 5.41 | 0.530477E+10 | 6734.70 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.418178E+11 | 84766.59 | 20-APR-04:12 | 20.00 | 9.61 | 0.483673E+10 | 6734.81 | 05-APR-09:00 | 20.00 | 9.61 |
May | 0.533134E+11 | 86502.65 | 22-MAY-04:12 | 18.13 | 13.85 | 0.527580E+10 | 6734.80 | 08-MAY-09:09 | 18.13 | 13.85 |
June | 0.603930E+11 | 86780.73 | 20-JUN-04:12 | 19.63 | 15.76 | 0.526794E+10 | 6734.77 | 22-JUN-09:09 | 22.88 | 16.93 |
July | 0.591334E+11 | 89716.88 | 24-JUL-04:13 | 22.80 | 18.81 | 0.489561E+10 | 6734.71 | 11-JUL-09:09 | 22.80 | 18.81 |
August | 0.600446E+11 | 88682.26 | 14-AUG-04:12 | 17.60 | 16.48 | 0.549619E+10 | 6734.79 | 11-AUG-09:09 | 17.60 | 16.48 |
September | 0.495560E+11 | 87795.16 | 05-SEP-04:12 | 16.50 | 15.67 | 0.487375E+10 | 6734.77 | 06-SEP-09:09 | 25.28 | 18.43 |
October | 0.408071E+11 | 85311.58 | 05-OCT-04:12 | 21.30 | 16.26 | 0.501602E+10 | 6734.92 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.275426E+11 | 53051.29 | 10-NOV-06:03 | 17.87 | 11.05 | 0.474133E+10 | 6734.62 | 01-NOV-09:09 | 17.87 | 11.05 |
December | 0.214600E+11 | 28908.93 | 01-DEC-16:50 | 10.87 | 4.97 | 0.438248E+10 | 6734.49 | 01-DEC-14:09 | 10.87 | 4.97 |
Annual Sum or Average | 0.494001E+12 | 0.590018E+11 | ||||||||
Minimum of Months | 0.214600E+11 | 28908.93 | 10.87 | 4.97 | 0.430742E+10 | 6734.46 | 10.87 | 4.97 | ||
Maximum of Months | 0.603930E+11 | 89716.88 | 22.80 | 18.81 | 0.549619E+10 | 6734.92 | 25.28 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285881E+10 | 3416.35 | 13-JAN-14:30 | 18.05 | 8.79 | 0.582503E+09 | 845.60 | 13-JAN-14:09 | 18.05 | 8.79 |
February | 0.318657E+10 | 5538.25 | 21-FEB-15:00 | 22.80 | 8.17 | 0.544594E+09 | 845.61 | 13-FEB-14:09 | 22.80 | 8.17 |
March | 0.476305E+10 | 6673.75 | 15-MAR-13:40 | 23.13 | 9.64 | 0.670767E+09 | 845.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.743756E+10 | 9884.99 | 03-APR-05:02 | 17.48 | 7.89 | 0.609766E+09 | 845.64 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.923805E+10 | 19008.58 | 29-MAY-17:31 | 31.67 | 15.75 | 0.663878E+09 | 845.64 | 08-MAY-09:09 | 31.67 | 15.75 |
June | 0.122395E+11 | 19495.95 | 25-JUN-18:01 | 31.02 | 16.46 | 0.662565E+09 | 845.63 | 27-JUN-09:09 | 25.10 | 15.77 |
July | 0.124685E+11 | 18994.24 | 30-JUL-16:31 | 31.13 | 20.00 | 0.616118E+09 | 845.75 | 03-JUL-13:39 | 31.13 | 20.00 |
August | 0.126044E+11 | 18934.05 | 06-AUG-17:01 | 36.02 | 18.72 | 0.690939E+09 | 845.65 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.825540E+10 | 16536.07 | 10-SEP-15:31 | 31.10 | 16.94 | 0.612710E+09 | 845.63 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.627583E+10 | 14445.05 | 02-OCT-05:02 | 23.72 | 15.10 | 0.632741E+09 | 845.66 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.401127E+10 | 5717.63 | 08-NOV-14:30 | 23.60 | 11.30 | 0.611613E+09 | 845.61 | 30-NOV-14:00 | 17.80 | 10.67 |
December | 0.306813E+10 | 3805.63 | 11-DEC-13:10 | 14.82 | 7.52 | 0.570340E+09 | 845.61 | 11-DEC-14:09 | 13.90 | 7.45 |
Annual Sum or Average | 0.864071E+11 | 0.746853E+10 | ||||||||
Minimum of Months | 0.285881E+10 | 3416.35 | 14.82 | 7.52 | 0.544594E+09 | 845.60 | 13.90 | 5.68 | ||
Maximum of Months | 0.126044E+11 | 19495.95 | 36.02 | 20.00 | 0.690939E+09 | 845.75 | 31.70 | 20.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299403E+10 | 5908.36 | 31-JAN-09:05 | 10.78 | 4.13 | 0.386608E+09 | 544.96 | 02-JAN-10:09 | 10.78 | 4.13 |
February | 0.347150E+10 | 8388.28 | 21-FEB-08:35 | 10.57 | 3.84 | 0.359077E+09 | 544.95 | 07-FEB-10:09 | 10.57 | 3.84 |
March | 0.518625E+10 | 9908.62 | 26-MAR-09:43 | 14.03 | 5.78 | 0.435106E+09 | 544.96 | 06-MAR-10:09 | 14.03 | 5.78 |
April | 0.752366E+10 | 19846.68 | 30-APR-07:42 | 17.93 | 12.21 | 0.393541E+09 | 545.71 | 27-APR-09:09 | 17.93 | 12.21 |
May | 0.922964E+10 | 20588.47 | 29-MAY-08:51 | 22.20 | 15.42 | 0.428253E+09 | 545.91 | 30-MAY-09:00 | 28.90 | 14.30 |
June | 0.110083E+11 | 19628.69 | 11-JUN-08:12 | 24.97 | 10.76 | 0.427042E+09 | 545.82 | 26-JUN-09:00 | 27.80 | 16.72 |
July | 0.106623E+11 | 19058.30 | 04-JUL-08:42 | 25.92 | 18.20 | 0.397041E+09 | 546.23 | 03-JUL-09:00 | 25.92 | 18.20 |
August | 0.105740E+11 | 18982.22 | 13-AUG-08:22 | 23.85 | 17.20 | 0.444742E+09 | 546.15 | 04-AUG-09:00 | 23.85 | 17.20 |
September | 0.828939E+10 | 20148.67 | 17-SEP-08:32 | 22.97 | 16.21 | 0.395209E+09 | 546.06 | 18-SEP-09:00 | 27.20 | 17.67 |
October | 0.602755E+10 | 16591.39 | 22-OCT-08:43 | 18.95 | 11.66 | 0.406895E+09 | 545.10 | 05-OCT-09:09 | 18.95 | 11.66 |
November | 0.405795E+10 | 9330.58 | 10-NOV-08:40 | 18.13 | 11.62 | 0.393620E+09 | 544.95 | 24-NOV-10:09 | 17.48 | 6.61 |
December | 0.291965E+10 | 4777.02 | 07-DEC-09:15 | 4.83 | 0.28 | 0.370454E+09 | 544.95 | 04-DEC-10:09 | 4.83 | 0.28 |
Annual Sum or Average | 0.819442E+11 | 0.483759E+10 | ||||||||
Minimum of Months | 0.291965E+10 | 4777.02 | 4.83 | 0.28 | 0.359077E+09 | 544.95 | 4.83 | 0.28 | ||
Maximum of Months | 0.110083E+11 | 20588.47 | 25.92 | 18.20 | 0.444742E+09 | 546.23 | 28.90 | 18.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.822533E+10 | 21704.64 | 01-JAN-14:53 | 16.10 | 9.46 | 0.617724E+09 | 846.67 | 03-JAN-14:00 | 20.60 | 8.39 |
February | 0.781395E+10 | 21744.60 | 20-FEB-13:42 | 22.02 | 8.45 | 0.565041E+09 | 848.00 | 07-FEB-14:00 | 22.02 | 8.45 |
March | 0.911686E+10 | 14996.91 | 26-MAR-12:33 | 19.07 | 7.95 | 0.677557E+09 | 847.29 | 22-MAR-13:00 | 19.07 | 7.95 |
April | 0.101279E+11 | 21562.76 | 30-APR-12:23 | 28.05 | 12.68 | 0.609440E+09 | 846.39 | 03-APR-13:00 | 28.05 | 12.68 |
May | 0.100110E+11 | 21115.02 | 29-MAY-14:51 | 32.20 | 16.37 | 0.663260E+09 | 845.66 | 08-MAY-09:09 | 32.20 | 16.37 |
June | 0.121733E+11 | 20647.34 | 11-JUN-16:11 | 32.60 | 15.18 | 0.662287E+09 | 845.65 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.128807E+11 | 21894.26 | 30-JUL-15:11 | 31.87 | 19.80 | 0.615950E+09 | 846.61 | 31-JUL-13:00 | 32.20 | 19.72 |
August | 0.148479E+11 | 21412.49 | 06-AUG-13:42 | 34.82 | 17.93 | 0.691166E+09 | 847.53 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.130857E+11 | 23367.11 | 17-SEP-12:32 | 31.50 | 15.75 | 0.613974E+09 | 854.43 | 29-SEP-13:30 | 28.05 | 14.65 |
October | 0.127560E+11 | 24581.89 | 29-OCT-12:41 | 23.80 | 11.56 | 0.636915E+09 | 895.58 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.106293E+11 | 24022.13 | 11-NOV-12:41 | 18.12 | 8.09 | 0.622678E+09 | 882.34 | 09-NOV-14:09 | 18.12 | 8.09 |
December | 0.862098E+10 | 21772.05 | 17-DEC-12:02 | 11.38 | 2.63 | 0.599234E+09 | 846.70 | 04-DEC-14:00 | 11.38 | 2.63 |
Annual Sum or Average | 0.130289E+12 | 0.757523E+10 | ||||||||
Minimum of Months | 0.781395E+10 | 14996.91 | 11.38 | 2.63 | 0.565041E+09 | 845.65 | 11.38 | 2.63 | ||
Maximum of Months | 0.148479E+11 | 24581.89 | 34.82 | 19.80 | 0.691166E+09 | 895.58 | 32.20 | 19.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454004E+10 | 8864.23 | 12-JAN-15:30 | 18.90 | 10.10 | 0.382399E+09 | 544.94 | 11-JAN-14:09 | 18.90 | 10.10 |
February | 0.517106E+10 | 18945.78 | 20-FEB-15:42 | 23.30 | 8.70 | 0.360552E+09 | 544.95 | 14-FEB-14:00 | 23.30 | 8.70 |
March | 0.841815E+10 | 24058.68 | 26-MAR-16:32 | 22.60 | 9.13 | 0.441929E+09 | 544.95 | 06-MAR-10:09 | 22.60 | 9.13 |
April | 0.123708E+11 | 26605.61 | 30-APR-16:21 | 30.30 | 12.75 | 0.396207E+09 | 544.98 | 24-APR-13:39 | 30.30 | 12.75 |
May | 0.112820E+11 | 27370.42 | 29-MAY-15:31 | 32.93 | 16.65 | 0.428579E+09 | 544.97 | 08-MAY-09:09 | 32.93 | 16.65 |
June | 0.143433E+11 | 28479.43 | 25-JUN-16:41 | 31.60 | 16.82 | 0.427591E+09 | 544.97 | 30-JUN-09:50 | 25.63 | 17.80 |
July | 0.153667E+11 | 27864.61 | 30-JUL-15:11 | 31.87 | 19.80 | 0.397906E+09 | 544.96 | 11-JUL-09:09 | 31.87 | 19.80 |
August | 0.178308E+11 | 26966.33 | 06-AUG-16:21 | 36.10 | 18.53 | 0.446448E+09 | 545.00 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.105092E+11 | 27038.38 | 17-SEP-15:11 | 32.80 | 16.07 | 0.395811E+09 | 544.97 | 25-SEP-13:50 | 24.90 | 13.77 |
October | 0.916778E+10 | 24345.72 | 01-OCT-15:22 | 32.25 | 15.71 | 0.410953E+09 | 544.98 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.711041E+10 | 24194.74 | 11-NOV-14:42 | 18.80 | 8.31 | 0.403940E+09 | 544.95 | 30-NOV-14:00 | 17.80 | 10.67 |
December | 0.600607E+10 | 10839.83 | 11-DEC-05:11 | 10.93 | 5.91 | 0.390765E+09 | 544.95 | 11-DEC-14:09 | 13.90 | 7.45 |
Annual Sum or Average | 0.122116E+12 | 0.488308E+10 | ||||||||
Minimum of Months | 0.454004E+10 | 8864.23 | 10.93 | 5.91 | 0.360552E+09 | 544.94 | 13.90 | 7.45 | ||
Maximum of Months | 0.178308E+11 | 28479.43 | 36.10 | 19.80 | 0.446448E+09 | 545.00 | 32.93 | 19.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162785E+10 | 2689.24 | 12-JAN-15:10 | 18.90 | 10.04 | 0.506187E+09 | 809.72 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.193403E+10 | 3373.70 | 23-FEB-14:30 | 21.65 | 7.41 | 0.486320E+09 | 845.58 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.297141E+10 | 4901.85 | 22-MAR-14:30 | 24.15 | 9.01 | 0.620436E+09 | 845.61 | 22-MAR-13:00 | 24.15 | 9.01 |
April | 0.492209E+10 | 8299.23 | 21-APR-15:00 | 32.20 | 15.49 | 0.595154E+09 | 845.63 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.800869E+10 | 12915.52 | 21-MAY-16:01 | 33.57 | 18.57 | 0.662038E+09 | 845.63 | 15-MAY-09:39 | 33.57 | 18.57 |
June | 0.107086E+11 | 17542.78 | 18-JUN-15:31 | 37.03 | 16.78 | 0.662566E+09 | 845.63 | 27-JUN-09:09 | 25.10 | 15.77 |
July | 0.101237E+11 | 18471.09 | 09-JUL-18:21 | 32.25 | 18.53 | 0.616121E+09 | 845.63 | 03-JUL-09:09 | 32.25 | 18.53 |
August | 0.920304E+10 | 18592.06 | 06-AUG-16:51 | 36.10 | 18.82 | 0.690493E+09 | 845.64 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.680271E+10 | 12087.49 | 23-SEP-05:03 | 21.10 | 18.18 | 0.610037E+09 | 845.62 | 11-SEP-09:39 | 21.10 | 18.18 |
October | 0.449706E+10 | 10786.06 | 02-OCT-05:02 | 23.72 | 15.10 | 0.615379E+09 | 845.64 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.246540E+10 | 3882.46 | 09-NOV-16:10 | 23.22 | 12.98 | 0.544685E+09 | 845.60 | 09-NOV-14:09 | 23.22 | 12.98 |
December | 0.142917E+10 | 2342.06 | 07-DEC-14:10 | 15.68 | 6.76 | 0.480421E+09 | 777.81 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.646937E+11 | 0.708984E+10 | ||||||||
Minimum of Months | 0.142917E+10 | 2342.06 | 15.68 | 6.76 | 0.480421E+09 | 777.81 | 17.20 | 7.10 | ||
Maximum of Months | 0.107086E+11 | 18592.06 | 37.03 | 18.82 | 0.690493E+09 | 845.64 | 33.57 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207062E+10 | 3782.49 | 31-JAN-09:40 | 11.33 | 4.37 | 0.256157E+09 | 521.19 | 12-JAN-11:09 | 11.33 | 4.37 |
February | 0.258917E+10 | 5866.35 | 21-FEB-10:00 | 16.70 | 6.62 | 0.248201E+09 | 521.20 | 14-FEB-11:09 | 16.70 | 6.62 |
March | 0.416114E+10 | 8115.61 | 31-MAR-09:00 | 15.00 | 4.82 | 0.308498E+09 | 521.21 | 22-MAR-12:09 | 15.00 | 4.82 |
April | 0.655325E+10 | 20615.95 | 30-APR-07:52 | 18.30 | 12.34 | 0.287907E+09 | 521.43 | 27-APR-08:00 | 18.30 | 12.34 |
May | 0.899448E+10 | 20890.24 | 28-MAY-08:22 | 22.75 | 16.82 | 0.314713E+09 | 521.45 | 30-MAY-10:09 | 28.98 | 14.35 |
June | 0.107309E+11 | 19901.28 | 18-JUN-09:32 | 30.57 | 16.80 | 0.314172E+09 | 523.69 | 07-JUN-07:19 | 30.57 | 16.80 |
July | 0.997584E+10 | 21034.22 | 09-JUL-08:22 | 25.25 | 18.80 | 0.293239E+09 | 523.52 | 03-JUL-07:19 | 25.25 | 18.80 |
August | 0.956586E+10 | 21436.17 | 06-AUG-08:11 | 27.23 | 17.51 | 0.326869E+09 | 521.54 | 09-AUG-08:00 | 28.30 | 18.95 |
September | 0.783246E+10 | 21320.07 | 17-SEP-09:21 | 25.55 | 16.11 | 0.290405E+09 | 521.54 | 15-SEP-08:00 | 25.55 | 16.11 |
October | 0.521645E+10 | 14580.96 | 22-OCT-09:13 | 19.97 | 12.06 | 0.294047E+09 | 521.24 | 17-OCT-10:09 | 19.97 | 12.06 |
November | 0.305446E+10 | 8083.53 | 10-NOV-09:00 | 18.30 | 11.76 | 0.271582E+09 | 521.21 | 09-NOV-11:20 | 18.30 | 11.76 |
December | 0.186566E+10 | 2867.35 | 07-DEC-09:40 | 5.77 | 0.97 | 0.241797E+09 | 521.19 | 07-DEC-09:30 | 5.77 | 0.97 |
Annual Sum or Average | 0.726103E+11 | 0.344759E+10 | ||||||||
Minimum of Months | 0.186566E+10 | 2867.35 | 5.77 | 0.97 | 0.241797E+09 | 521.19 | 5.77 | 0.97 | ||
Maximum of Months | 0.107309E+11 | 21436.17 | 30.57 | 18.80 | 0.326869E+09 | 523.69 | 30.57 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750268E+10 | 21091.84 | 01-JAN-13:13 | 15.20 | 9.09 | 0.606996E+09 | 870.96 | 12-JAN-14:30 | 18.60 | 9.87 |
February | 0.699109E+10 | 21733.66 | 19-FEB-14:42 | 22.70 | 8.52 | 0.553929E+09 | 846.77 | 07-FEB-14:00 | 22.70 | 8.52 |
March | 0.764475E+10 | 19199.36 | 19-MAR-14:13 | 23.30 | 8.99 | 0.663248E+09 | 846.65 | 22-MAR-13:00 | 24.40 | 9.14 |
April | 0.790886E+10 | 20977.53 | 30-APR-14:32 | 29.80 | 12.58 | 0.602080E+09 | 846.12 | 28-APR-13:00 | 29.80 | 12.58 |
May | 0.897304E+10 | 19889.79 | 21-MAY-15:21 | 34.40 | 18.05 | 0.661394E+09 | 845.66 | 04-MAY-13:20 | 34.40 | 18.05 |
June | 0.105876E+11 | 17323.39 | 18-JUN-15:31 | 37.03 | 16.78 | 0.662254E+09 | 845.65 | 22-JUN-09:09 | 22.88 | 16.93 |
July | 0.104702E+11 | 20098.89 | 09-JUL-16:21 | 33.05 | 19.34 | 0.616009E+09 | 845.77 | 31-JUL-13:30 | 32.50 | 19.82 |
August | 0.116391E+11 | 21387.95 | 06-AUG-15:31 | 36.10 | 18.34 | 0.690909E+09 | 846.99 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.122043E+11 | 22703.78 | 17-SEP-12:42 | 31.60 | 15.76 | 0.613270E+09 | 879.26 | 29-SEP-13:39 | 28.13 | 14.71 |
October | 0.117449E+11 | 23664.85 | 22-OCT-13:11 | 25.97 | 14.61 | 0.633833E+09 | 915.42 | 30-OCT-13:30 | 23.30 | 11.23 |
November | 0.949755E+10 | 22536.81 | 23-NOV-13:12 | 20.20 | 8.18 | 0.611984E+09 | 907.53 | 09-NOV-14:09 | 20.20 | 8.18 |
December | 0.716681E+10 | 20871.89 | 31-DEC-14:32 | 14.03 | 5.23 | 0.584826E+09 | 846.05 | 01-DEC-14:39 | 14.03 | 5.23 |
Annual Sum or Average | 0.112331E+12 | 0.750073E+10 | ||||||||
Minimum of Months | 0.699109E+10 | 17323.39 | 14.03 | 5.23 | 0.553929E+09 | 845.65 | 14.03 | 5.23 | ||
Maximum of Months | 0.122043E+11 | 23664.85 | 37.03 | 19.34 | 0.690909E+09 | 915.42 | 34.40 | 19.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250219E+10 | 6490.09 | 12-JAN-15:30 | 18.90 | 10.10 | 0.341999E+09 | 544.93 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.281359E+10 | 12936.86 | 19-FEB-16:42 | 22.30 | 8.28 | 0.320819E+09 | 544.93 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.464953E+10 | 20666.03 | 26-MAR-16:21 | 22.50 | 9.04 | 0.402993E+09 | 544.95 | 22-MAR-13:00 | 22.50 | 9.04 |
April | 0.685785E+10 | 24320.13 | 30-APR-16:31 | 30.20 | 12.69 | 0.383719E+09 | 544.96 | 24-APR-13:20 | 30.20 | 12.69 |
May | 0.926320E+10 | 23736.27 | 07-MAY-16:51 | 28.90 | 14.00 | 0.425830E+09 | 544.96 | 05-MAY-13:00 | 28.90 | 14.00 |
June | 0.109680E+11 | 22783.15 | 25-JUN-16:51 | 31.70 | 16.84 | 0.427213E+09 | 544.96 | 30-JUN-09:39 | 25.17 | 17.65 |
July | 0.102940E+11 | 24602.81 | 09-JUL-16:21 | 33.05 | 19.34 | 0.397296E+09 | 544.95 | 28-JUL-09:20 | 29.07 | 19.13 |
August | 0.100942E+11 | 25154.96 | 06-AUG-16:51 | 36.10 | 18.82 | 0.445187E+09 | 544.98 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.828280E+10 | 23668.41 | 17-SEP-16:41 | 31.88 | 15.56 | 0.393315E+09 | 544.96 | 25-SEP-13:39 | 24.80 | 13.70 |
October | 0.607952E+10 | 21315.95 | 22-OCT-15:51 | 27.20 | 14.77 | 0.395473E+09 | 544.96 | 02-OCT-09:09 | 27.20 | 14.77 |
November | 0.375257E+10 | 9702.69 | 09-NOV-15:30 | 23.30 | 12.82 | 0.359511E+09 | 544.94 | 09-NOV-14:00 | 23.30 | 12.82 |
December | 0.230025E+10 | 5572.55 | 15-DEC-15:50 | 15.60 | 6.12 | 0.328361E+09 | 544.93 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.778577E+11 | 0.462171E+10 | ||||||||
Minimum of Months | 0.230025E+10 | 5572.55 | 15.60 | 6.12 | 0.320819E+09 | 544.93 | 15.60 | 6.12 | ||
Maximum of Months | 0.109680E+11 | 25154.96 | 36.10 | 19.34 | 0.445187E+09 | 544.98 | 31.70 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102554E+10 | 2709.40 | 12-JAN-14:30 | 18.60 | 9.87 | 0.482622E+09 | 765.54 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.141716E+10 | 2760.56 | 22-FEB-13:30 | 21.15 | 7.71 | 0.459543E+09 | 845.59 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.262329E+10 | 4887.56 | 22-MAR-14:30 | 24.15 | 9.01 | 0.588859E+09 | 845.61 | 09-MAR-14:09 | 24.15 | 9.01 |
April | 0.489446E+10 | 9063.78 | 21-APR-15:00 | 32.20 | 15.49 | 0.580781E+09 | 845.63 | 03-APR-13:09 | 32.20 | 15.49 |
May | 0.835796E+10 | 15535.10 | 21-MAY-16:12 | 32.73 | 18.75 | 0.658687E+09 | 845.63 | 15-MAY-09:00 | 32.73 | 18.75 |
June | 0.116096E+11 | 20517.04 | 18-JUN-15:31 | 37.03 | 16.78 | 0.662410E+09 | 845.63 | 27-JUN-09:39 | 25.40 | 15.72 |
July | 0.110489E+11 | 21324.03 | 09-JUL-17:41 | 32.80 | 18.96 | 0.616189E+09 | 845.63 | 03-JUL-09:09 | 32.80 | 18.96 |
August | 0.985493E+10 | 21745.86 | 06-AUG-16:51 | 36.10 | 18.82 | 0.689611E+09 | 845.64 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.703358E+10 | 13564.72 | 13-SEP-05:03 | 23.12 | 17.44 | 0.605878E+09 | 845.63 | 26-SEP-13:09 | 25.78 | 15.08 |
October | 0.429539E+10 | 8984.84 | 02-OCT-05:02 | 23.72 | 15.10 | 0.595494E+09 | 845.63 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.189567E+10 | 3842.67 | 09-NOV-16:10 | 23.22 | 12.98 | 0.514184E+09 | 845.60 | 09-NOV-14:39 | 23.22 | 12.98 |
December | 0.778790E+09 | 2030.15 | 08-DEC-16:30 | 16.65 | 7.38 | 0.459501E+09 | 724.87 | 08-DEC-14:00 | 16.65 | 7.38 |
Annual Sum or Average | 0.648353E+11 | 0.691376E+10 | ||||||||
Minimum of Months | 0.778790E+09 | 2030.15 | 16.65 | 7.38 | 0.459501E+09 | 724.87 | 16.65 | 7.10 | ||
Maximum of Months | 0.116096E+11 | 21745.86 | 37.03 | 18.96 | 0.689611E+09 | 845.64 | 32.80 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155131E+10 | 2688.79 | 12-JAN-14:30 | 18.60 | 9.87 | 0.330971E+09 | 541.76 | 04-JAN-10:30 | 18.60 | 9.87 |
February | 0.204813E+10 | 4502.25 | 21-FEB-10:30 | 18.35 | 7.04 | 0.325554E+09 | 544.94 | 24-FEB-10:30 | 8.05 | 2.51 |
March | 0.360514E+10 | 7093.83 | 16-MAR-10:00 | 18.90 | 7.68 | 0.414238E+09 | 544.95 | 06-MAR-10:09 | 18.90 | 7.68 |
April | 0.636857E+10 | 19782.44 | 16-APR-09:12 | 21.33 | 10.32 | 0.390519E+09 | 545.00 | 19-APR-09:09 | 25.87 | 12.69 |
May | 0.928291E+10 | 19793.55 | 29-MAY-09:02 | 22.67 | 15.59 | 0.427430E+09 | 545.76 | 15-MAY-09:00 | 22.67 | 15.59 |
June | 0.114782E+11 | 20403.56 | 18-JUN-09:32 | 30.57 | 16.80 | 0.427290E+09 | 545.67 | 09-JUN-09:00 | 30.57 | 16.80 |
July | 0.107230E+11 | 21387.25 | 09-JUL-08:22 | 25.25 | 18.80 | 0.397554E+09 | 545.97 | 28-JUL-09:00 | 30.60 | 19.45 |
August | 0.101449E+11 | 21881.37 | 06-AUG-08:11 | 27.23 | 17.51 | 0.444542E+09 | 545.69 | 01-AUG-09:00 | 27.23 | 17.51 |
September | 0.803945E+10 | 19153.02 | 17-SEP-09:32 | 26.10 | 16.12 | 0.394059E+09 | 545.67 | 18-SEP-09:50 | 26.83 | 17.57 |
October | 0.490324E+10 | 10862.61 | 05-OCT-08:40 | 24.27 | 17.57 | 0.396889E+09 | 544.99 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.242196E+10 | 7270.11 | 10-NOV-09:20 | 18.67 | 11.91 | 0.358860E+09 | 544.95 | 09-NOV-10:50 | 18.67 | 11.91 |
December | 0.131970E+10 | 2107.81 | 01-DEC-10:20 | 12.77 | 4.87 | 0.309275E+09 | 505.97 | 01-DEC-10:30 | 13.05 | 5.08 |
Annual Sum or Average | 0.718865E+11 | 0.461718E+10 | ||||||||
Minimum of Months | 0.131970E+10 | 2107.81 | 12.77 | 4.87 | 0.309275E+09 | 505.97 | 8.05 | 2.51 | ||
Maximum of Months | 0.114782E+11 | 21881.37 | 30.57 | 18.80 | 0.444542E+09 | 545.97 | 30.60 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601423E+10 | 17301.22 | 12-JAN-14:20 | 18.50 | 9.82 | 0.587641E+09 | 845.87 | 03-JAN-14:50 | 18.50 | 9.82 |
February | 0.576857E+10 | 23252.83 | 19-FEB-14:42 | 22.70 | 8.52 | 0.535890E+09 | 846.52 | 22-FEB-14:30 | 21.95 | 7.96 |
March | 0.669027E+10 | 14627.79 | 16-MAR-13:30 | 22.50 | 9.16 | 0.643034E+09 | 846.23 | 22-MAR-13:39 | 24.60 | 9.18 |
April | 0.774631E+10 | 22956.19 | 30-APR-13:23 | 29.40 | 12.42 | 0.591878E+09 | 846.21 | 21-APR-13:39 | 29.40 | 12.42 |
May | 0.934660E+10 | 18049.82 | 21-MAY-15:32 | 34.40 | 18.15 | 0.657494E+09 | 845.65 | 03-MAY-13:00 | 34.40 | 18.15 |
June | 0.114963E+11 | 22291.74 | 18-JUN-15:31 | 37.03 | 16.78 | 0.661865E+09 | 845.65 | 29-JUN-13:30 | 25.85 | 17.55 |
July | 0.114089E+11 | 23158.54 | 09-JUL-16:21 | 33.05 | 19.34 | 0.615918E+09 | 845.64 | 03-JUL-09:09 | 33.05 | 19.34 |
August | 0.123578E+11 | 24475.35 | 06-AUG-15:31 | 36.10 | 18.34 | 0.689892E+09 | 847.25 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.124700E+11 | 23522.29 | 17-SEP-13:32 | 32.03 | 15.98 | 0.610613E+09 | 855.26 | 29-SEP-13:39 | 28.13 | 14.71 |
October | 0.112541E+11 | 25987.45 | 22-OCT-13:41 | 26.52 | 14.78 | 0.622715E+09 | 873.75 | 03-OCT-13:39 | 26.52 | 14.78 |
November | 0.812018E+10 | 23229.37 | 05-NOV-14:12 | 17.07 | 8.66 | 0.592326E+09 | 870.46 | 09-NOV-14:09 | 23.30 | 12.48 |
December | 0.556087E+10 | 14643.93 | 07-DEC-14:10 | 15.68 | 6.76 | 0.564053E+09 | 845.85 | 06-DEC-14:50 | 15.68 | 6.76 |
Annual Sum or Average | 0.108234E+12 | 0.737332E+10 | ||||||||
Minimum of Months | 0.556087E+10 | 14627.79 | 15.68 | 6.76 | 0.535890E+09 | 845.64 | 15.68 | 6.76 | ||
Maximum of Months | 0.124700E+11 | 25987.45 | 37.03 | 19.34 | 0.689892E+09 | 873.75 | 34.40 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190348E+10 | 6263.90 | 12-JAN-15:30 | 18.90 | 10.10 | 0.332349E+09 | 544.92 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.230892E+10 | 12733.56 | 20-FEB-15:52 | 23.30 | 8.66 | 0.309401E+09 | 544.93 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.418934E+10 | 14951.39 | 26-MAR-16:32 | 22.60 | 9.13 | 0.387415E+09 | 544.94 | 09-MAR-14:09 | 22.60 | 9.13 |
April | 0.679199E+10 | 24515.07 | 23-APR-16:51 | 22.80 | 8.36 | 0.375585E+09 | 544.96 | 26-APR-13:50 | 26.32 | 13.73 |
May | 0.954407E+10 | 25629.64 | 07-MAY-16:51 | 28.90 | 14.00 | 0.422848E+09 | 544.96 | 05-MAY-13:00 | 28.90 | 14.00 |
June | 0.116368E+11 | 24509.67 | 25-JUN-16:51 | 31.70 | 16.84 | 0.426871E+09 | 544.96 | 27-JUN-09:39 | 25.40 | 15.72 |
July | 0.109783E+11 | 27029.35 | 09-JUL-16:21 | 33.05 | 19.34 | 0.397157E+09 | 544.95 | 03-JUL-09:09 | 33.05 | 19.34 |
August | 0.105969E+11 | 27666.70 | 06-AUG-16:51 | 36.10 | 18.82 | 0.444204E+09 | 544.97 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.848724E+10 | 23652.06 | 17-SEP-15:32 | 32.80 | 15.98 | 0.390408E+09 | 544.96 | 26-SEP-13:09 | 25.78 | 15.08 |
October | 0.587478E+10 | 23790.69 | 22-OCT-15:42 | 27.12 | 14.75 | 0.384785E+09 | 544.96 | 02-OCT-09:09 | 27.12 | 14.75 |
November | 0.320747E+10 | 9724.00 | 09-NOV-15:30 | 23.30 | 12.82 | 0.346273E+09 | 544.94 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.165876E+10 | 4958.75 | 15-DEC-15:50 | 15.60 | 6.12 | 0.318572E+09 | 544.93 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.771780E+11 | 0.453587E+10 | ||||||||
Minimum of Months | 0.165876E+10 | 4958.75 | 15.60 | 6.12 | 0.309401E+09 | 544.92 | 15.60 | 6.12 | ||
Maximum of Months | 0.116368E+11 | 27666.70 | 36.10 | 19.34 | 0.444204E+09 | 544.97 | 33.05 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261074E+10 | 5850.90 | 02-JAN-06:10 | -0.4 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | -0.4 | -1.2 |
February | 0.310506E+10 | 6130.79 | 21-FEB-06:15 | 5.20 | 0.40 | 0.00 | 0.00 | 01-FEB-00:10 | 5.20 | 0.40 |
March | 0.500071E+10 | 5878.08 | 16-MAR-15:20 | 22.60 | 8.60 | 0.00 | 0.00 | 01-MAR-00:10 | 22.60 | 8.60 |
April | 0.750076E+10 | 7741.23 | 21-APR-16:00 | 31.10 | 14.82 | 0.00 | 0.00 | 01-APR-00:10 | 31.10 | 14.82 |
May | 0.898887E+10 | 10005.49 | 30-MAY-15:20 | 34.23 | 17.67 | 0.00 | 0.00 | 01-MAY-00:10 | 34.23 | 17.67 |
June | 0.110047E+11 | 9777.13 | 19-JUN-14:30 | 34.70 | 18.56 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 18.56 |
July | 0.111329E+11 | 10936.93 | 03-JUL-14:40 | 37.40 | 18.90 | 0.00 | 0.00 | 01-JUL-00:10 | 37.40 | 18.90 |
August | 0.121322E+11 | 16738.61 | 07-AUG-05:15 | 25.73 | 16.21 | 0.00 | 0.00 | 01-AUG-00:10 | 25.73 | 16.21 |
September | 0.915914E+10 | 12531.27 | 05-SEP-05:02 | 16.20 | 15.65 | 0.00 | 0.00 | 01-SEP-00:10 | 16.20 | 15.65 |
October | 0.741532E+10 | 8891.34 | 10-OCT-05:15 | 12.97 | 8.53 | 0.00 | 0.00 | 01-OCT-00:10 | 12.97 | 8.53 |
November | 0.481771E+10 | 7881.36 | 13-NOV-06:08 | 2.30 | 0.06 | 0.00 | 0.00 | 01-NOV-00:10 | 2.30 | 0.06 |
December | 0.319602E+10 | 5259.50 | 11-DEC-06:15 | 10.77 | 5.99 | 0.00 | 0.00 | 01-DEC-00:10 | 10.77 | 5.99 |
Annual Sum or Average | 0.860642E+11 | 0.00 | ||||||||
Minimum of Months | 0.261074E+10 | 5259.50 | -0.4 | -1.2 | 0.00 | 0.00 | -0.4 | -1.2 | ||
Maximum of Months | 0.121322E+11 | 16738.61 | 37.40 | 18.90 | 0.00 | 0.00 | 37.40 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869646E+09 | 7240.85 | 28-JAN-05:01 | -2.9 | -6.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.9 | -6.3 |
February | 0.121903E+10 | 8372.48 | 09-FEB-05:01 | -0.4 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -0.4 | -2.4 |
March | 0.227825E+10 | 6275.01 | 02-MAR-06:01 | -3.5 | -6.2 | 0.00 | 0.00 | 01-MAR-00:10 | -3.5 | -6.2 |
April | 0.458001E+10 | 6396.53 | 21-APR-15:20 | 31.83 | 15.27 | 0.00 | 0.00 | 01-APR-00:10 | 31.83 | 15.27 |
May | 0.727088E+10 | 7822.56 | 30-MAY-15:50 | 33.98 | 17.51 | 0.00 | 0.00 | 01-MAY-00:10 | 33.98 | 17.51 |
June | 0.931706E+10 | 9093.03 | 10-JUN-05:02 | 23.90 | 12.19 | 0.00 | 0.00 | 01-JUN-00:10 | 23.90 | 12.19 |
July | 0.887301E+10 | 8752.15 | 03-JUL-14:30 | 37.50 | 18.90 | 0.00 | 0.00 | 01-JUL-00:10 | 37.50 | 18.90 |
August | 0.884441E+10 | 8452.34 | 28-AUG-05:03 | 21.42 | 14.06 | 0.00 | 0.00 | 01-AUG-00:10 | 21.42 | 14.06 |
September | 0.726351E+10 | 7957.90 | 05-SEP-15:20 | 31.10 | 19.29 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 19.29 |
October | 0.474437E+10 | 6873.18 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.206217E+10 | 7021.12 | 27-NOV-05:11 | 3.30 | -1.2 | 0.00 | 0.00 | 01-NOV-00:10 | 3.30 | -1.2 |
December | 0.862906E+09 | 6986.47 | 27-DEC-05:01 | -3.8 | -4.9 | 0.00 | 0.00 | 01-DEC-00:10 | -3.8 | -4.9 |
Annual Sum or Average | 0.581852E+11 | 0.00 | ||||||||
Minimum of Months | 0.862906E+09 | 6275.01 | -3.8 | -6.3 | 0.00 | 0.00 | -3.8 | -6.3 | ||
Maximum of Months | 0.931706E+10 | 9093.03 | 37.50 | 19.29 | 0.00 | 0.00 | 37.50 | 19.29 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524157E+09 | 5383.76 | 12-JAN-15:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.07 |
February | 0.136667E+10 | 8053.86 | 22-FEB-14:20 | 21.87 | 7.95 | 0.00 | 0.00 | 01-FEB-00:10 | 21.87 | 7.95 |
March | 0.350036E+10 | 11246.59 | 16-MAR-15:00 | 22.80 | 8.72 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 8.72 |
April | 0.792781E+10 | 17702.26 | 28-APR-14:30 | 28.90 | 14.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 14.03 |
May | 0.128066E+11 | 20987.20 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.174190E+11 | 22611.95 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.163455E+11 | 22810.41 | 03-JUL-13:10 | 36.88 | 18.64 | 0.00 | 0.00 | 01-JUL-00:10 | 36.88 | 18.64 |
August | 0.152392E+11 | 21797.57 | 07-AUG-14:20 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.117086E+11 | 18784.11 | 15-SEP-14:00 | 32.20 | 17.96 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 17.96 |
October | 0.630752E+10 | 16490.86 | 03-OCT-14:20 | 32.43 | 19.47 | 0.00 | 0.00 | 01-OCT-00:10 | 32.43 | 19.47 |
November | 0.200443E+10 | 8971.02 | 09-NOV-15:10 | 23.30 | 12.70 | 0.00 | 0.00 | 01-NOV-00:10 | 23.30 | 12.70 |
December | 0.279807E+09 | 2602.33 | 01-DEC-14:00 | 14.40 | 6.57 | 0.00 | 0.00 | 01-DEC-00:10 | 14.40 | 6.57 |
Annual Sum or Average | 0.954295E+11 | 0.00 | ||||||||
Minimum of Months | 0.279807E+09 | 2602.33 | 14.40 | 6.57 | 0.00 | 0.00 | 14.40 | 6.57 | ||
Maximum of Months | 0.174190E+11 | 22810.41 | 38.13 | 19.47 | 0.00 | 0.00 | 38.13 | 19.47 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363552E+10 | 2203.02 | 30-JAN-17:00 | 15.60 | 6.12 | 95231212.45 | 126.83 | 17-JAN-10:00 | 15.60 | 6.12 |
February | 0.816330E+10 | 4137.56 | 21-FEB-17:00 | 22.20 | 7.81 | 86397397.65 | 126.84 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.144484E+11 | 7124.22 | 31-MAR-24:00 | 11.20 | 2.36 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.20 | 2.36 |
April | 0.190984E+11 | 7918.78 | 22-APR-17:55 | 18.30 | 6.65 | 92127417.63 | 138.02 | 21-APR-13:00 | 18.30 | 6.65 |
May | 0.477311E+10 | 3522.58 | 31-MAY-23:43 | 25.37 | 11.81 | 99237485.88 | 126.86 | 24-MAY-13:09 | 25.37 | 11.81 |
June | 0.956014E+10 | 5368.68 | 30-JUN-23:55 | 27.70 | 17.05 | 98962624.18 | 126.85 | 29-JUN-09:30 | 27.70 | 17.05 |
July | 0.149428E+11 | 7287.16 | 31-JUL-24:00 | 27.50 | 18.10 | 91887938.81 | 126.85 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.200549E+11 | 7878.75 | 27-AUG-20:33 | 26.83 | 14.31 | 0.105703E+09 | 140.02 | 04-AUG-13:00 | 26.83 | 14.31 |
September | 0.468235E+10 | 3486.10 | 30-SEP-24:00 | 16.10 | 8.62 | 91617176.73 | 126.86 | 05-SEP-09:00 | 16.10 | 8.62 |
October | 0.971578E+10 | 5292.03 | 31-OCT-24:00 | 10.60 | 4.98 | 95238199.73 | 126.86 | 13-OCT-13:00 | 10.60 | 4.98 |
November | 0.140002E+11 | 6191.39 | 09-NOV-16:50 | 22.88 | 12.85 | 94301893.82 | 126.84 | 03-NOV-09:30 | 22.88 | 12.85 |
December | 0.192481E+11 | 7938.92 | 18-DEC-16:50 | 9.08 | 0.00 | 91880916.87 | 126.82 | 14-DEC-14:00 | 9.08 | 0.00 |
Annual Sum or Average | 0.142323E+12 | 0.114582E+10 | ||||||||
Minimum of Months | 0.363552E+10 | 2203.02 | 9.08 | 0.00 | 86397397.65 | 126.82 | 9.08 | 0.00 | ||
Maximum of Months | 0.200549E+11 | 7938.92 | 27.70 | 18.10 | 0.105703E+09 | 140.02 | 27.70 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204676E+10 | 1954.09 | 30-JAN-17:00 | 15.60 | 6.12 | 95231072.99 | 126.83 | 02-JAN-14:00 | 15.60 | 6.12 |
February | 0.673819E+10 | 3828.96 | 21-FEB-17:00 | 22.20 | 7.81 | 86397305.96 | 126.84 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.129499E+11 | 6590.17 | 31-MAR-23:40 | 11.27 | 2.40 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.27 | 2.40 |
April | 0.179099E+11 | 7514.97 | 26-APR-18:00 | 25.60 | 12.63 | 92074704.68 | 138.06 | 21-APR-13:00 | 25.60 | 12.63 |
May | 0.433828E+10 | 3420.18 | 31-MAY-23:55 | 25.20 | 11.70 | 99236980.92 | 126.85 | 24-MAY-13:00 | 25.20 | 11.70 |
June | 0.908749E+10 | 5232.69 | 30-JUN-23:55 | 27.70 | 17.05 | 98962817.59 | 126.85 | 29-JUN-09:39 | 27.70 | 17.05 |
July | 0.142060E+11 | 7015.92 | 31-JUL-24:00 | 27.50 | 18.10 | 91888975.08 | 126.85 | 19-JUL-09:09 | 27.50 | 18.10 |
August | 0.188880E+11 | 7440.07 | 31-AUG-17:50 | 27.98 | 16.89 | 0.105207E+09 | 138.41 | 04-AUG-13:00 | 27.98 | 16.89 |
September | 0.419554E+10 | 3235.94 | 30-SEP-23:50 | 16.20 | 8.79 | 91614353.93 | 126.86 | 13-SEP-13:00 | 16.20 | 8.79 |
October | 0.870212E+10 | 4814.11 | 31-OCT-24:00 | 10.60 | 4.98 | 95237813.59 | 126.85 | 04-OCT-09:00 | 10.60 | 4.98 |
November | 0.122429E+11 | 5830.82 | 09-NOV-16:50 | 22.88 | 12.85 | 94301852.58 | 126.84 | 01-NOV-13:00 | 22.88 | 12.85 |
December | 0.167285E+11 | 7407.44 | 15-DEC-16:50 | 15.10 | 5.92 | 91880984.29 | 126.82 | 14-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.128034E+12 | 0.114527E+10 | ||||||||
Minimum of Months | 0.204676E+10 | 1954.09 | 10.60 | 2.40 | 86397305.96 | 126.82 | 10.60 | 2.40 | ||
Maximum of Months | 0.188880E+11 | 7514.97 | 27.98 | 18.10 | 0.105207E+09 | 138.41 | 27.98 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102079E+10 | 1901.99 | 19-JAN-17:00 | 12.80 | 6.10 | 94873781.96 | 128.92 | 17-JAN-10:00 | 12.80 | 6.10 |
February | 0.556294E+10 | 3823.92 | 21-FEB-17:00 | 22.20 | 7.81 | 86397289.31 | 126.84 | 13-FEB-14:00 | 22.20 | 7.81 |
March | 0.120568E+11 | 6299.05 | 31-MAR-23:20 | 11.33 | 2.45 | 0.103236E+09 | 126.82 | 13-MAR-09:09 | 11.33 | 2.45 |
April | 0.176356E+11 | 7585.24 | 26-APR-17:50 | 25.78 | 12.75 | 91842350.32 | 135.86 | 21-APR-13:00 | 25.78 | 12.75 |
May | 0.428465E+10 | 3445.65 | 31-MAY-24:00 | 25.20 | 11.70 | 99237133.36 | 126.86 | 24-MAY-13:39 | 25.20 | 11.70 |
June | 0.917828E+10 | 5204.79 | 30-JUN-23:55 | 27.70 | 17.05 | 98962833.57 | 126.85 | 28-JUN-13:09 | 27.70 | 17.05 |
July | 0.143363E+11 | 7023.76 | 31-JUL-24:00 | 27.50 | 18.10 | 91888961.34 | 126.85 | 17-JUL-09:20 | 27.50 | 18.10 |
August | 0.189639E+11 | 7569.58 | 31-AUG-17:50 | 27.98 | 16.89 | 0.104602E+09 | 136.59 | 04-AUG-13:00 | 27.98 | 16.89 |
September | 0.412486E+10 | 3069.77 | 30-SEP-23:20 | 16.50 | 9.30 | 91614588.71 | 126.86 | 13-SEP-13:39 | 16.50 | 9.30 |
October | 0.821645E+10 | 4489.70 | 31-OCT-23:20 | 10.60 | 4.70 | 95237832.50 | 126.85 | 04-OCT-09:00 | 10.60 | 4.70 |
November | 0.109799E+11 | 5864.83 | 09-NOV-16:50 | 22.88 | 12.85 | 94301897.97 | 126.84 | 01-NOV-13:00 | 22.88 | 12.85 |
December | 0.149249E+11 | 7337.73 | 15-DEC-16:50 | 15.10 | 5.92 | 91881022.29 | 126.82 | 14-DEC-14:00 | 15.10 | 5.92 |
Annual Sum or Average | 0.121285E+12 | 0.114408E+10 | ||||||||
Minimum of Months | 0.102079E+10 | 1901.99 | 10.60 | 2.45 | 86397289.31 | 126.82 | 10.60 | 2.45 | ||
Maximum of Months | 0.189639E+11 | 7585.24 | 27.98 | 18.10 | 0.104602E+09 | 136.59 | 27.98 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238951E+12 | 92695.52 | 02-JAN-17:00 | 16.70 | 8.66 | 0.206151E+10 | 2745.44 | 05-JAN-10:50 | 6.23 | -1.4 |
February | 0.434947E+12 | 183584.79 | 21-FEB-17:00 | 22.20 | 7.81 | 0.187026E+10 | 2745.55 | 16-FEB-10:09 | 22.20 | 7.81 |
March | 0.726886E+12 | 357804.24 | 31-MAR-24:00 | 11.20 | 2.36 | 0.223477E+10 | 2745.58 | 27-MAR-09:09 | 11.20 | 2.36 |
April | 0.939206E+12 | 373697.62 | 29-APR-19:33 | 25.53 | 13.14 | 0.209797E+10 | 4157.68 | 21-APR-13:00 | 25.53 | 13.14 |
May | 0.241048E+12 | 175801.07 | 31-MAY-24:00 | 25.20 | 11.70 | 0.214849E+10 | 2748.16 | 18-MAY-13:30 | 25.20 | 11.70 |
June | 0.469863E+12 | 267483.98 | 30-JUN-23:55 | 27.70 | 17.05 | 0.214295E+10 | 2749.24 | 27-JUN-13:09 | 27.70 | 17.05 |
July | 0.731358E+12 | 354825.05 | 31-JUL-23:08 | 28.33 | 17.73 | 0.207930E+10 | 3629.96 | 17-JUL-13:00 | 28.33 | 17.73 |
August | 0.968359E+12 | 378142.40 | 21-AUG-23:13 | 27.73 | 15.65 | 0.286044E+10 | 4497.60 | 03-AUG-13:09 | 27.73 | 15.65 |
September | 0.238792E+12 | 177017.19 | 30-SEP-24:00 | 16.10 | 8.62 | 0.198342E+10 | 2748.37 | 18-SEP-13:09 | 16.10 | 8.62 |
October | 0.489875E+12 | 269200.49 | 31-OCT-24:00 | 10.60 | 4.98 | 0.206188E+10 | 2749.38 | 19-OCT-09:39 | 10.60 | 4.98 |
November | 0.709846E+12 | 277745.51 | 10-NOV-17:00 | 14.40 | 9.20 | 0.204160E+10 | 2750.31 | 03-NOV-13:09 | 14.40 | 9.20 |
December | 0.976818E+12 | 368496.82 | 18-DEC-16:55 | 8.90 | -0.7 | 0.198907E+10 | 2746.83 | 04-DEC-14:00 | 8.90 | -0.7 |
Annual Sum or Average | 0.716595E+13 | 0.255717E+11 | ||||||||
Minimum of Months | 0.238792E+12 | 92695.52 | 8.90 | -0.7 | 0.187026E+10 | 2745.44 | 6.23 | -1.4 | ||
Maximum of Months | 0.976818E+12 | 378142.40 | 28.33 | 17.73 | 0.286044E+10 | 4497.60 | 28.33 | 17.73 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265003E+09 | 13893.82 | 04-JAN-05:15 | 8.53 |
February | 0.162832E+09 | 13918.62 | 22-FEB-05:15 | 3.13 |
March | 0.147756E+09 | 13904.81 | 28-MAR-04:15 | 7.60 |
April | 0.275931E+09 | 18303.32 | 29-APR-16:02 | 31.02 |
May | 0.378675E+09 | 20258.52 | 20-MAY-16:01 | 32.20 |
June | 0.374237E+09 | 24688.15 | 17-JUN-16:01 | 35.68 |
July | 0.576123E+09 | 27226.15 | 01-JUL-16:01 | 37.88 |
August | 0.479283E+09 | 22389.21 | 12-AUG-16:01 | 33.90 |
September | 0.532046E+09 | 19902.32 | 02-SEP-16:01 | 32.23 |
October | 0.414748E+09 | 15804.77 | 22-OCT-15:02 | 26.78 |
November | 0.259388E+09 | 13906.81 | 21-NOV-05:55 | 2.20 |
December | 0.293279E+09 | 13913.20 | 26-DEC-04:05 | -0.1 |
Annual Sum or Average | 0.415930E+10 | |||
Minimum of Months | 0.147756E+09 | 13893.82 | -0.1 | |
Maximum of Months | 0.576123E+09 | 27226.15 | 37.88 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457138E+09 | 74524.75 | 17-JAN-05:11 | 5.20 |
February | 25698400.68 | 67508.27 | 27-FEB-06:03 | 8.80 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.233695E+09 | 74399.62 | 27-NOV-05:11 | 3.30 |
December | 0.695337E+09 | 76404.79 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.141187E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.695337E+09 | 76404.79 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10395742.73 | 9488.94 | 28-JAN-06:01 | -3.3 |
February | 5537006.37 | 9245.62 | 02-FEB-06:01 | -3.5 |
March | 220468.71 | 2361.12 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 443951.93 | 2804.63 | 30-DEC-06:01 | -2.9 |
Annual Sum or Average | 16597169.74 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 10395742.73 | 9488.94 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9685937.94 | 6797.66 | 28-JAN-06:01 | -3.3 |
February | 8409213.76 | 6650.13 | 02-FEB-06:01 | -3.5 |
March | 1287668.67 | 6442.25 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 527587.07 | 4959.19 | 28-NOV-06:01 | 1.02 |
December | 11860448.74 | 6657.75 | 28-DEC-06:01 | -3.8 |
Annual Sum or Average | 31770856.18 | |||
Minimum of Months | 0.00 | 0.00 | -3.8 | |
Maximum of Months | 11860448.74 | 6797.66 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7200636.58 | 10947.54 | 28-JAN-06:01 | -3.3 |
February | 5460381.31 | 9806.53 | 02-FEB-06:01 | -3.5 |
March | 591844.46 | 4930.02 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 2702988.52 | 10679.95 | 28-NOV-06:01 | 1.02 |
December | 13477620.26 | 11103.63 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 29433471.11 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 13477620.26 | 11103.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.660879E+09 | 13946.31 | 28-JAN-05:01 | -2.9 |
February | 0.363589E+09 | 13849.59 | 02-FEB-05:01 | -2.4 |
March | 0.132677E+09 | 13599.14 | 02-MAR-05:01 | -3.9 |
April | 1859176.10 | 9132.17 | 11-APR-05:02 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.207470E+09 | 13936.41 | 28-NOV-05:01 | -0.3 |
December | 0.828277E+09 | 14265.53 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.219475E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.828277E+09 | 14265.53 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333155E+09 | 13203.90 | 28-JAN-05:01 | -2.9 |
February | 0.157042E+09 | 13118.71 | 02-FEB-05:01 | -2.4 |
March | 56192826.31 | 12885.63 | 02-MAR-05:01 | -3.9 |
April | 1134077.82 | 5554.71 | 11-APR-05:02 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 87689098.23 | 13406.88 | 28-NOV-05:01 | -0.3 |
December | 0.406179E+09 | 13537.29 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.104139E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.406179E+09 | 13537.29 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194171E+09 | 14841.56 | 26-JAN-05:01 | 1.20 |
February | 0.117221E+09 | 14739.66 | 09-FEB-05:01 | -0.4 |
March | 37434265.06 | 14052.31 | 02-MAR-06:01 | -3.5 |
April | 959971.99 | 6413.88 | 11-APR-05:02 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 53850219.86 | 15091.59 | 28-NOV-05:01 | -0.3 |
December | 0.269113E+09 | 15168.39 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.672749E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.269113E+09 | 15168.39 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226623E+09 | 12679.85 | 26-JAN-05:01 | 1.20 |
February | 0.127522E+09 | 12563.12 | 09-FEB-05:01 | -0.4 |
March | 30160426.54 | 11998.80 | 01-MAR-05:01 | 1.20 |
April | 353516.67 | 2894.49 | 11-APR-05:02 | 4.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 47823561.89 | 12670.60 | 28-NOV-05:01 | -0.3 |
December | 0.263411E+09 | 12949.52 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.695894E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.263411E+09 | 12949.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245925E+10 | 17796.04 | 09-JAN-05:11 | 3.13 |
February | 0.145977E+10 | 16865.33 | 02-FEB-04:02 | -1.3 |
March | 0.789616E+09 | 16478.86 | 02-MAR-04:02 | -3.0 |
April | 64203177.58 | 15128.83 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 14743781.22 | 13130.90 | 25-OCT-05:03 | 7.12 |
November | 0.114207E+10 | 17605.09 | 27-NOV-05:11 | 3.30 |
December | 0.305195E+10 | 17984.31 | 26-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.898160E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.305195E+10 | 17984.31 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115340E+10 | 16371.41 | 09-JAN-05:11 | 3.13 |
February | 0.595003E+09 | 15431.08 | 02-FEB-04:02 | -1.3 |
March | 0.336546E+09 | 15039.99 | 01-MAR-05:01 | 1.20 |
April | 24862271.46 | 13883.51 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 7191436.78 | 9293.06 | 25-OCT-05:03 | 7.12 |
November | 0.502013E+09 | 16302.02 | 27-NOV-05:11 | 3.30 |
December | 0.141950E+10 | 16630.06 | 26-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.403852E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.3 | |
Maximum of Months | 0.141950E+10 | 16630.06 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110721E+10 | 18450.54 | 09-JAN-05:11 | 3.13 |
February | 0.673388E+09 | 17260.05 | 09-FEB-05:01 | -0.4 |
March | 0.395955E+09 | 17404.07 | 01-MAR-05:01 | 1.20 |
April | 48008489.85 | 16312.52 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 1150863.11 | 2579.06 | 25-OCT-05:03 | 7.12 |
November | 0.491406E+09 | 19182.72 | 27-NOV-05:11 | 3.30 |
December | 0.134021E+10 | 19376.24 | 26-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.405734E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.4 | |
Maximum of Months | 0.134021E+10 | 19376.24 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930475E+09 | 17183.72 | 09-JAN-05:11 | 3.13 |
February | 0.550313E+09 | 15915.32 | 02-FEB-05:01 | -2.4 |
March | 0.222244E+09 | 16149.56 | 01-MAR-05:01 | 1.20 |
April | 16088343.83 | 10652.76 | 11-APR-04:12 | 5.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 7029.65 | 46.86 | 25-OCT-05:03 | 7.12 |
November | 0.369481E+09 | 17609.31 | 27-NOV-05:11 | 3.30 |
December | 0.107519E+10 | 17753.64 | 26-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.316380E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.4 | |
Maximum of Months | 0.107519E+10 | 17753.64 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58577109.11 | 9665.05 | 17-JAN-05:11 | 5.20 |
February | 82768049.63 | 9854.29 | 27-FEB-05:11 | 8.90 |
March | 84640968.56 | 9445.90 | 01-MAR-05:01 | 1.20 |
April | 0.102197E+09 | 9902.92 | 14-APR-04:12 | 14.43 |
May | 62121873.67 | 8045.47 | 21-MAY-15:11 | 34.40 |
June | 62535004.93 | 7979.04 | 11-JUN-16:11 | 32.60 |
July | 81550327.66 | 9058.78 | 02-JUL-15:51 | 38.30 |
August | 81122435.73 | 9378.65 | 06-AUG-16:21 | 36.10 |
September | 61853653.44 | 7873.73 | 10-SEP-15:31 | 31.10 |
October | 83397396.48 | 8767.86 | 16-OCT-04:12 | 13.67 |
November | 89799303.09 | 11229.60 | 27-NOV-05:11 | 3.30 |
December | 0.102021E+09 | 12660.00 | 18-DEC-05:11 | 4.03 |
Annual Sum or Average | 0.952585E+09 | |||
Minimum of Months | 58577109.11 | 7873.73 | 1.20 | |
Maximum of Months | 0.102197E+09 | 12660.00 | 38.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676461E+09 | 6775.65 | 01-JAN-14:32 | 15.93 |
February | 0.208401E+09 | 7861.75 | 19-FEB-16:42 | 22.30 |
March | 81546345.68 | 6984.17 | 04-MAR-06:02 | 11.10 |
April | 51643087.14 | 6557.80 | 30-APR-16:31 | 30.20 |
May | 48513337.17 | 8121.11 | 21-MAY-15:21 | 34.40 |
June | 40753023.65 | 7954.80 | 18-JUN-15:31 | 37.03 |
July | 53153835.60 | 8327.96 | 02-JUL-16:11 | 38.13 |
August | 50700614.56 | 9034.64 | 06-AUG-14:51 | 36.10 |
September | 40883421.37 | 6926.75 | 17-SEP-15:21 | 32.80 |
October | 60162506.97 | 7873.95 | 15-OCT-15:21 | 20.60 |
November | 0.190827E+09 | 6751.18 | 10-NOV-05:12 | 17.47 |
December | 0.623284E+09 | 6349.62 | 31-DEC-14:32 | 14.03 |
Annual Sum or Average | 0.212633E+10 | |||
Minimum of Months | 40753023.65 | 6349.62 | 11.10 | |
Maximum of Months | 0.676461E+09 | 9034.64 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365176E+10 | 17562.03 | 09-JAN-06:03 | 2.98 |
February | 0.254466E+10 | 11429.69 | 02-FEB-06:15 | -3.7 |
March | 0.194687E+10 | 13650.37 | 16-MAR-05:03 | 14.43 |
April | 0.584046E+09 | 15973.45 | 22-APR-05:03 | 8.80 |
May | 0.184423E+09 | 15354.87 | 06-MAY-05:03 | 10.50 |
June | 64453594.20 | 11352.03 | 12-JUN-04:12 | 17.57 |
July | 42669533.08 | 11951.49 | 05-JUL-04:12 | 19.27 |
August | 54378373.82 | 10869.34 | 17-AUG-05:03 | 17.20 |
September | 0.167168E+09 | 16334.07 | 25-SEP-05:03 | 9.08 |
October | 0.585090E+09 | 14745.27 | 20-OCT-05:03 | 11.60 |
November | 0.219205E+10 | 16221.18 | 27-NOV-06:03 | 3.30 |
December | 0.451442E+10 | 20381.15 | 04-DEC-05:13 | -0.8 |
Annual Sum or Average | 0.165320E+11 | |||
Minimum of Months | 42669533.08 | 10869.34 | -3.7 | |
Maximum of Months | 0.451442E+10 | 20381.15 | 19.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475860E+09 | 623.19 | 30-JAN-04:00 | -0.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.475860E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.475860E+09 | 623.19 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.219312E+11 | 22950.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.198933E+11 | 22950.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.236388E+11 | 22950.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.211142E+11 | 22950.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.227850E+11 | 22950.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.226748E+11 | 22950.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.212244E+11 | 22950.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.236388E+11 | 22950.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.211142E+11 | 22950.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.219312E+11 | 22950.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.216742E+11 | 22950.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.212244E+11 | 22950.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.262844E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.198933E+11 | 22950.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.236388E+11 | 22950.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196958E+11 | 20611.01 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.178655E+11 | 20611.01 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.212293E+11 | 20611.01 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.189620E+11 | 20611.01 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.204625E+11 | 20611.01 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.203636E+11 | 20611.01 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.190610E+11 | 20611.01 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.212293E+11 | 20611.01 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.189620E+11 | 20611.01 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.196958E+11 | 20611.01 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.194649E+11 | 20611.01 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.190610E+11 | 20611.01 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.236053E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.178655E+11 | 20611.01 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.212293E+11 | 20611.01 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.160882E+10 | 2587.92 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139783E+10 | 2255.20 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154720E+10 | 2255.20 | 10-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.132034E+10 | 1803.00 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.139804E+10 | 1350.81 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137267E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130152E+10 | 1470.28 | 03-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147548E+10 | 1470.28 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135768E+10 | 1803.00 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.148471E+10 | 2255.20 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.157615E+10 | 2587.92 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.158179E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.174222E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130152E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.160882E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101078E+10 | 1667.75 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.887910E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.988172E+09 | 1453.34 | 10-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.855426E+09 | 947.51 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.910779E+09 | 870.51 | 02-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.896947E+09 | 870.51 | 02-JUN-14:39 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.850936E+09 | 947.51 | 03-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.956154E+09 | 947.51 | 16-AUG-15:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.865899E+09 | 870.51 | 05-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.942582E+09 | 1453.34 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.996659E+09 | 1667.75 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.997905E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111602E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.850936E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.101078E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.149397E+10 | 2587.98 | 17-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133284E+10 | 2255.25 | 13-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151930E+10 | 2255.25 | 10-MAR-16:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132789E+10 | 1803.04 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141461E+10 | 1350.84 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139342E+10 | 1231.36 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132434E+10 | 1803.04 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148506E+10 | 1470.31 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134452E+10 | 1350.84 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143922E+10 | 2255.25 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147339E+10 | 2587.98 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.147895E+10 | 2587.98 | 01-DEC-16:49 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170275E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.132434E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151930E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.982601E+09 | 1667.75 | 17-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.869723E+09 | 1453.34 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.983871E+09 | 1453.34 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.851394E+09 | 1161.92 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.900713E+09 | 947.51 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.886407E+09 | 870.51 | 22-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.841728E+09 | 1161.92 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.953473E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.868841E+09 | 1161.92 | 05-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.936011E+09 | 1667.75 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.960705E+09 | 1667.75 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.969074E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.110045E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.841728E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.983871E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159917E+10 | 2587.92 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139155E+10 | 2255.20 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154131E+10 | 2255.20 | 10-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131873E+10 | 1803.00 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.139717E+10 | 1350.81 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137194E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130031E+10 | 1470.28 | 03-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147358E+10 | 1470.28 | 16-AUG-15:50 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135210E+10 | 1803.00 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147771E+10 | 2255.20 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.156620E+10 | 2587.92 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.157320E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173630E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130031E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.159917E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100769E+10 | 1667.75 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.885386E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.986151E+09 | 1453.34 | 10-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.854714E+09 | 947.51 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.909867E+09 | 870.51 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.895674E+09 | 870.51 | 19-JUN-15:20 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.849432E+09 | 947.51 | 03-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.954448E+09 | 947.51 | 16-AUG-15:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.864331E+09 | 870.51 | 05-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.940401E+09 | 1453.34 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.993110E+09 | 1667.75 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.996048E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111372E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.849432E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.100769E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.149330E+10 | 2587.98 | 17-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133105E+10 | 2255.25 | 13-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151703E+10 | 2255.25 | 10-MAR-16:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132636E+10 | 1803.04 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141302E+10 | 1350.84 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139146E+10 | 1231.36 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132188E+10 | 1803.04 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148301E+10 | 1470.31 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134182E+10 | 1350.84 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143523E+10 | 2255.25 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147174E+10 | 2587.98 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.147865E+10 | 2587.98 | 01-DEC-16:49 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170046E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.132188E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151703E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.980919E+09 | 1667.75 | 17-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.867301E+09 | 1453.34 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.982151E+09 | 1453.34 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.850261E+09 | 1161.92 | 20-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.899990E+09 | 947.51 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.885735E+09 | 870.51 | 22-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.840116E+09 | 1161.92 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.952193E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.866706E+09 | 1161.92 | 18-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.933846E+09 | 1667.75 | 13-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.958631E+09 | 1667.75 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.967380E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109852E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.840116E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.982151E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.159908E+10 | 2587.92 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.139119E+10 | 2255.20 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.154114E+10 | 2255.20 | 10-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.131860E+10 | 1803.00 | 20-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.139709E+10 | 1350.81 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.137189E+10 | 1231.33 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.130022E+10 | 1470.28 | 03-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.147343E+10 | 1470.28 | 16-AUG-15:50 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.135201E+10 | 1803.00 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.147749E+10 | 2255.20 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.156614E+10 | 2587.92 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.157312E+10 | 2587.92 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.173614E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.130022E+10 | 1231.33 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.159908E+10 | 2587.92 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.100767E+10 | 1667.75 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.885354E+09 | 1453.34 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.986084E+09 | 1453.34 | 10-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.854714E+09 | 947.51 | 20-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.909780E+09 | 870.51 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.895688E+09 | 870.51 | 19-JUN-15:20 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.849386E+09 | 947.51 | 03-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.954423E+09 | 947.51 | 16-AUG-15:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.864331E+09 | 870.51 | 05-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.940419E+09 | 1453.34 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.993139E+09 | 1667.75 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.996001E+09 | 1667.75 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.111370E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.849386E+09 | 870.51 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.100767E+10 | 1667.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.149330E+10 | 2587.98 | 17-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.133095E+10 | 2255.25 | 13-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.151696E+10 | 2255.25 | 10-MAR-16:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.132629E+10 | 1803.04 | 20-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.141302E+10 | 1350.84 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.139144E+10 | 1231.36 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.132187E+10 | 1803.04 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.148292E+10 | 1470.31 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.134179E+10 | 1350.84 | 01-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.143523E+10 | 2255.25 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.147167E+10 | 2587.98 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.147865E+10 | 2587.98 | 01-DEC-16:49 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.170041E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.132187E+10 | 1231.36 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.151696E+10 | 2587.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.980814E+09 | 1667.75 | 17-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.867197E+09 | 1453.34 | 13-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.982064E+09 | 1453.34 | 10-MAR-16:00 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.850261E+09 | 1161.92 | 20-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.899975E+09 | 947.51 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.885713E+09 | 870.51 | 22-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.840015E+09 | 1161.92 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.952061E+09 | 1161.92 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.866660E+09 | 1161.92 | 18-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.933717E+09 | 1453.34 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.958616E+09 | 1667.75 | 22-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.967365E+09 | 1667.75 | 01-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.109845E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.840015E+09 | 870.51 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.982064E+09 | 1667.75 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553024E+09 | 578.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.501634E+09 | 578.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.596080E+09 | 578.72 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.532421E+09 | 578.72 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.574552E+09 | 578.72 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.571774E+09 | 578.72 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.535199E+09 | 578.72 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.596080E+09 | 578.72 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.532421E+09 | 578.72 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.553024E+09 | 578.72 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.546542E+09 | 578.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.535199E+09 | 578.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.662795E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.501634E+09 | 578.72 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.596080E+09 | 578.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618367E+10 | 6471.01 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.560905E+10 | 6471.01 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.666512E+10 | 6471.01 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.595330E+10 | 6471.01 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.642439E+10 | 6471.01 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.639333E+10 | 6471.01 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.598436E+10 | 6471.01 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.666512E+10 | 6471.01 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.595330E+10 | 6471.01 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.618367E+10 | 6471.01 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.611120E+10 | 6471.01 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.598436E+10 | 6471.01 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.741109E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.560905E+10 | 6471.01 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.666512E+10 | 6471.01 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.227850E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.226748E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.211142E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.219312E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.216742E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.212244E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.262844E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.198933E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.236388E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.196958E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.189620E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.204625E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.203636E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.190610E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.189620E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.196958E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.194649E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.190610E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.236053E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.178655E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.212293E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.160882E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513120E+09 |
February | 0.136985E+10 | 0.139783E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433612E+09 |
March | 0.163685E+10 | 0.154720E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140781.07 | 0.455433E+09 |
April | 0.145243E+10 | 0.132034E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23399524.79 | 0.237873E+09 |
May | 0.157338E+10 | 0.139804E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70168519.59 | 0.133411E+09 |
June | 0.156900E+10 | 0.137267E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111828E+09 | 42695597.50 |
July | 0.145680E+10 | 0.130152E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92686330.43 | 28205137.49 |
August | 0.163685E+10 | 0.147548E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73389252.62 | 40547504.34 |
September | 0.145243E+10 | 0.135768E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23059687.94 | 66519993.85 |
October | 0.150991E+10 | 0.148471E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8855909.78 | 0.217977E+09 |
November | 0.149516E+10 | 0.157615E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425223E+09 |
December | 0.145680E+10 | 0.158179E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458409E+09 |
Annual Sum or Average | 0.181194E+11 | 0.174222E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403528E+09 | 0.305303E+10 |
Minimum of Months | 0.136985E+10 | 0.130152E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28205137.49 |
Maximum of Months | 0.163685E+10 | 0.160882E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111828E+09 | 0.513120E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101078E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343206E+09 |
February | 0.882782E+09 | 0.887910E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288477E+09 |
March | 0.105485E+10 | 0.988172E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93879.30 | 0.303817E+09 |
April | 0.936002E+09 | 0.855426E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16303759.42 | 0.153765E+09 |
May | 0.101394E+10 | 0.910779E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47498286.21 | 90087668.81 |
June | 0.101113E+10 | 0.896947E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78141833.73 | 26033587.80 |
July | 0.938820E+09 | 0.850936E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66581274.53 | 15176231.53 |
August | 0.105485E+10 | 0.956154E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53234163.84 | 22098001.35 |
September | 0.936002E+09 | 0.865899E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15203250.74 | 45391701.99 |
October | 0.973041E+09 | 0.942582E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5951711.13 | 0.144306E+09 |
November | 0.963541E+09 | 0.996659E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282551E+09 |
December | 0.938820E+09 | 0.997905E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300600E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111602E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283008E+09 | 0.201551E+10 |
Minimum of Months | 0.882782E+09 | 0.850936E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15176231.53 |
Maximum of Months | 0.105485E+10 | 0.101078E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78141833.73 | 0.343206E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.149397E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533737E+09 |
February | 0.136988E+10 | 0.133284E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450083E+09 |
March | 0.163688E+10 | 0.151930E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139751.85 | 0.474533E+09 |
April | 0.145246E+10 | 0.132789E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20851297.21 | 0.241987E+09 |
May | 0.157341E+10 | 0.141461E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70025355.58 | 0.131971E+09 |
June | 0.156904E+10 | 0.139342E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114203E+09 | 41187217.62 |
July | 0.145684E+10 | 0.132434E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94446137.92 | 26667448.67 |
August | 0.163688E+10 | 0.148506E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72503010.75 | 40594356.31 |
September | 0.145246E+10 | 0.134452E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20927606.93 | 72152755.26 |
October | 0.150994E+10 | 0.143922E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6994969.43 | 0.233119E+09 |
November | 0.149520E+10 | 0.147339E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445655E+09 |
December | 0.145684E+10 | 0.147895E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471578E+09 |
Annual Sum or Average | 0.181198E+11 | 0.170275E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400091E+09 | 0.316326E+10 |
Minimum of Months | 0.136988E+10 | 0.132434E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26667448.67 |
Maximum of Months | 0.163688E+10 | 0.151930E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114203E+09 | 0.533737E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.982601E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364465E+09 |
February | 0.882782E+09 | 0.869723E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317770E+09 |
March | 0.105485E+10 | 0.983871E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93843.23 | 0.348134E+09 |
April | 0.936002E+09 | 0.851394E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12298236.60 | 0.192435E+09 |
May | 0.101394E+10 | 0.900713E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42455086.40 | 0.105922E+09 |
June | 0.101113E+10 | 0.886407E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69162202.26 | 36930687.25 |
July | 0.938820E+09 | 0.841728E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55726756.01 | 27053003.23 |
August | 0.105485E+10 | 0.953473E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42524039.20 | 38592138.04 |
September | 0.936002E+09 | 0.868841E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14144587.40 | 53229085.99 |
October | 0.973041E+09 | 0.936011E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4875191.47 | 0.168737E+09 |
November | 0.963541E+09 | 0.960705E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320458E+09 |
December | 0.938820E+09 | 0.969074E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344243E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110045E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241280E+09 | 0.231797E+10 |
Minimum of Months | 0.882782E+09 | 0.841728E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27053003.23 |
Maximum of Months | 0.105485E+10 | 0.983871E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69162202.26 | 0.364465E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.159917E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103618E+10 |
February | 0.136985E+10 | 0.139155E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 545851.11 | 0.883959E+09 |
March | 0.163685E+10 | 0.154131E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617462.10 | 0.924317E+09 |
April | 0.145243E+10 | 0.131873E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59823688.10 | 0.508281E+09 |
May | 0.157338E+10 | 0.139717E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161411E+09 | 0.293164E+09 |
June | 0.156900E+10 | 0.137194E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248622E+09 | 0.108241E+09 |
July | 0.145680E+10 | 0.130031E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206715E+09 | 82713241.12 |
August | 0.163685E+10 | 0.147358E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167840E+09 | 0.108386E+09 |
September | 0.145243E+10 | 0.135210E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55729161.85 | 0.145144E+09 |
October | 0.150991E+10 | 0.147771E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23980192.33 | 0.445691E+09 |
November | 0.149516E+10 | 0.156620E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843132E+09 |
December | 0.145680E+10 | 0.157320E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905014E+09 |
Annual Sum or Average | 0.181194E+11 | 0.173630E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925284E+09 | 0.628422E+10 |
Minimum of Months | 0.136985E+10 | 0.130031E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82713241.12 |
Maximum of Months | 0.163685E+10 | 0.159917E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248622E+09 | 0.103618E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.100769E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712599E+09 |
February | 0.649041E+09 | 0.885386E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613410E+09 |
March | 0.773965E+09 | 0.986151E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177820.07 | 0.657847E+09 |
April | 0.688021E+09 | 0.854714E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35276834.27 | 0.360839E+09 |
May | 0.744847E+09 | 0.909867E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105578E+09 | 0.207166E+09 |
June | 0.742030E+09 | 0.895674E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166402E+09 | 74804313.45 |
July | 0.690839E+09 | 0.849432E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138960E+09 | 57661404.28 |
August | 0.773965E+09 | 0.954448E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110542E+09 | 76445845.41 |
September | 0.688021E+09 | 0.864331E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34361908.50 | 0.105979E+09 |
October | 0.715730E+09 | 0.940401E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13524091.51 | 0.312445E+09 |
November | 0.708685E+09 | 0.993110E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591116E+09 |
December | 0.690839E+09 | 0.996048E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622821E+09 |
Annual Sum or Average | 0.858171E+10 | 0.111372E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604823E+09 | 0.439313E+10 |
Minimum of Months | 0.649041E+09 | 0.849432E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57661404.28 |
Maximum of Months | 0.773965E+09 | 0.100769E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166402E+09 | 0.712599E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.149330E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119223E+10 |
February | 0.136988E+10 | 0.133105E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100478E+10 |
March | 0.163688E+10 | 0.151703E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259711.98 | 0.105415E+10 |
April | 0.145246E+10 | 0.132636E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46987096.07 | 0.546447E+09 |
May | 0.157341E+10 | 0.141302E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158867E+09 | 0.295671E+09 |
June | 0.156904E+10 | 0.139146E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253290E+09 | 0.105545E+09 |
July | 0.145684E+10 | 0.132188E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209603E+09 | 80813681.41 |
August | 0.163688E+10 | 0.148301E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162143E+09 | 0.114287E+09 |
September | 0.145246E+10 | 0.134182E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47149996.85 | 0.167202E+09 |
October | 0.150994E+10 | 0.143523E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14941125.78 | 0.524662E+09 |
November | 0.149520E+10 | 0.147174E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987272E+09 |
December | 0.145684E+10 | 0.147865E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103849E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170046E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893240E+09 | 0.711154E+10 |
Minimum of Months | 0.136988E+10 | 0.132188E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80813681.41 |
Maximum of Months | 0.163688E+10 | 0.151703E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253290E+09 | 0.119223E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.980919E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735778E+09 |
February | 0.882782E+09 | 0.867301E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632836E+09 |
March | 0.105485E+10 | 0.982151E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174303.59 | 0.684503E+09 |
April | 0.936002E+09 | 0.850261E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30053427.64 | 0.385197E+09 |
May | 0.101394E+10 | 0.899990E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97293378.20 | 0.222592E+09 |
June | 0.101113E+10 | 0.885735E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158487E+09 | 85991324.88 |
July | 0.938820E+09 | 0.840116E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131048E+09 | 68809669.26 |
August | 0.105485E+10 | 0.952193E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102925E+09 | 86869192.41 |
September | 0.936002E+09 | 0.866706E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33519035.26 | 0.113242E+09 |
October | 0.973041E+09 | 0.933846E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11592186.32 | 0.334507E+09 |
November | 0.963541E+09 | 0.958631E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611950E+09 |
December | 0.938820E+09 | 0.967380E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644774E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109852E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565092E+09 | 0.460705E+10 |
Minimum of Months | 0.882782E+09 | 0.840116E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68809669.26 |
Maximum of Months | 0.105485E+10 | 0.982151E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158487E+09 | 0.735778E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.159908E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114935E+10 |
February | 0.136985E+10 | 0.139119E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2408484.07 | 0.998425E+09 |
March | 0.163685E+10 | 0.154114E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1951752.59 | 0.105040E+10 |
April | 0.145243E+10 | 0.131860E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71762475.35 | 0.597445E+09 |
May | 0.157338E+10 | 0.139709E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191064E+09 | 0.355043E+09 |
June | 0.156900E+10 | 0.137189E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298882E+09 | 0.137995E+09 |
July | 0.145680E+10 | 0.130022E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245152E+09 | 0.107410E+09 |
August | 0.163685E+10 | 0.147343E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200119E+09 | 0.135919E+09 |
September | 0.145243E+10 | 0.135201E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64954129.87 | 0.177649E+09 |
October | 0.150991E+10 | 0.147749E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30534610.41 | 0.511426E+09 |
November | 0.149516E+10 | 0.156614E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13422.92 | 0.928171E+09 |
December | 0.145680E+10 | 0.157312E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100693E+10 |
Annual Sum or Average | 0.181194E+11 | 0.173614E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110684E+10 | 0.715617E+10 |
Minimum of Months | 0.136985E+10 | 0.130022E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107410E+09 |
Maximum of Months | 0.163685E+10 | 0.159908E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298882E+09 | 0.114935E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.100767E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795031E+09 |
February | 0.882782E+09 | 0.885354E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19562.64 | 0.699315E+09 |
March | 0.105485E+10 | 0.986084E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165864.53 | 0.763253E+09 |
April | 0.936002E+09 | 0.854714E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40910601.29 | 0.434725E+09 |
May | 0.101394E+10 | 0.909780E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124444E+09 | 0.254936E+09 |
June | 0.101113E+10 | 0.895688E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199088E+09 | 96056005.09 |
July | 0.938820E+09 | 0.849386E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164056E+09 | 75292213.08 |
August | 0.105485E+10 | 0.954423E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131445E+09 | 96569762.69 |
September | 0.936002E+09 | 0.864331E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40021936.89 | 0.131759E+09 |
October | 0.973041E+09 | 0.940419E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16277789.36 | 0.367383E+09 |
November | 0.963541E+09 | 0.993139E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661916E+09 |
December | 0.938820E+09 | 0.996001E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695575E+09 |
Annual Sum or Average | 0.116768E+11 | 0.111370E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716429E+09 | 0.507181E+10 |
Minimum of Months | 0.882782E+09 | 0.849386E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75292213.08 |
Maximum of Months | 0.105485E+10 | 0.100767E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199088E+09 | 0.795031E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.149330E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134936E+10 |
February | 0.136988E+10 | 0.133095E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115666E+10 |
March | 0.163688E+10 | 0.151696E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246462.30 | 0.122505E+10 |
April | 0.145246E+10 | 0.132629E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55847582.94 | 0.649908E+09 |
May | 0.157341E+10 | 0.141302E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188914E+09 | 0.358181E+09 |
June | 0.156904E+10 | 0.139144E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303920E+09 | 0.134580E+09 |
July | 0.145684E+10 | 0.132187E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248272E+09 | 0.104950E+09 |
August | 0.163688E+10 | 0.148292E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194341E+09 | 0.143451E+09 |
September | 0.145246E+10 | 0.134179E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56172520.63 | 0.206124E+09 |
October | 0.150994E+10 | 0.143523E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18090429.75 | 0.620171E+09 |
November | 0.149520E+10 | 0.147167E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112232E+10 |
December | 0.145684E+10 | 0.147865E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117413E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170041E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106580E+10 | 0.824489E+10 |
Minimum of Months | 0.136988E+10 | 0.132187E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104950E+09 |
Maximum of Months | 0.163688E+10 | 0.151696E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303920E+09 | 0.134936E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.980814E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840258E+09 |
February | 0.882782E+09 | 0.867197E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732446E+09 |
March | 0.105485E+10 | 0.982064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184794.82 | 0.799614E+09 |
April | 0.936002E+09 | 0.850261E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36204043.58 | 0.460971E+09 |
May | 0.101394E+10 | 0.899975E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116937E+09 | 0.270934E+09 |
June | 0.101113E+10 | 0.885713E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192372E+09 | 0.108548E+09 |
July | 0.938820E+09 | 0.840015E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157434E+09 | 87562694.22 |
August | 0.105485E+10 | 0.952061E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124530E+09 | 0.108041E+09 |
September | 0.936002E+09 | 0.866660E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40141828.01 | 0.139565E+09 |
October | 0.973041E+09 | 0.933717E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14073317.91 | 0.395342E+09 |
November | 0.963541E+09 | 0.958616E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696377E+09 |
December | 0.938820E+09 | 0.967365E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736929E+09 |
Annual Sum or Average | 0.116768E+11 | 0.109845E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681877E+09 | 0.537659E+10 |
Minimum of Months | 0.882782E+09 | 0.840015E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87562694.22 |
Maximum of Months | 0.105485E+10 | 0.982064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192372E+09 | 0.840258E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.553024E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.501634E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.596080E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.532421E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.574552E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.571774E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.535199E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.596080E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.532421E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.553024E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.546542E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.535199E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.662795E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.501634E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.596080E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.618367E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.560905E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.666512E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.595330E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.642439E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.639333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.598436E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.666512E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.595330E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.618367E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.611120E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.598436E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.741109E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.560905E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.666512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114330E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964673E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50862.48 | 0.101001E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38909610.54 | 0.531329E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128797E+09 | 0.289989E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209505E+09 | 96079733.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175584E+09 | 67931398.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135700E+09 | 99387965.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40013157.26 | 0.146414E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14375590.51 | 0.483439E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947383E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101544E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742936E+09 | 0.679538E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67931398.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209505E+09 | 0.114330E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192830E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164110E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162555.91 | 0.171355E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78001466.34 | 0.916952E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238057E+09 | 0.506042E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375702E+09 | 0.174907E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318368E+09 | 0.127123E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249596E+09 | 0.181299E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75487278.96 | 0.255396E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28776251.49 | 0.820780E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160060E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169184E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136415E+10 | 0.115579E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127123E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375702E+09 | 0.192830E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189425E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165407E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178627E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59520822.98 | 0.978953E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216294E+09 | 0.538872E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384658E+09 | 0.199453E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307516E+09 | 0.152999E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246826E+09 | 0.204973E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63191773.27 | 0.284204E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26694173.83 | 0.862846E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156884E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163819E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130470E+10 | 0.117639E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152999E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384658E+09 | 0.189425E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 22950.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 22950.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 22950.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 22950.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 22950.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 22950.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 22950.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 22950.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 22950.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 22950.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 22950.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 22950.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 22950.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 20611.01 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 20611.01 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 20611.01 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 20611.01 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 20611.01 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 20611.01 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 20611.01 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 20611.01 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 20611.01 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 20611.01 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 20611.01 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 20611.01 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1377.79 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1689.56 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 10-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 | 22-MAR-13:00 | 1345.61 | 19-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.88 | 01-APR-17:02 | 1378.72 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.10 | 14-MAY-15:40 | 645.35 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.10 | 04-JUN-19:00 | 467.46 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 03-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.90 | 02-JUL-21:20 | 236.93 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.37 | 26-AUG-17:30 | 388.33 | 14-AUG-01:00 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.67 | 10-SEP-15:00 | 240.38 | 24-SEP-07:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.01 | 01-OCT-15:00 | 627.62 | 24-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 872.26 | 26-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1171.15 | 18-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.93 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 479.90 | 1689.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 900.98 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1113.39 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 10-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 22-MAR-13:00 | 904.52 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.37 | 01-APR-17:02 | 899.40 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 02-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.67 | 14-MAY-15:40 | 417.55 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 02-JUN-14:39 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.18 | 04-JUN-19:00 | 303.65 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 03-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.62 | 02-JUL-21:20 | 151.55 | 18-JUL-21:10 |
August | 1295.83 | 01-AUG-09:09 | 947.51 | 16-AUG-15:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.77 | 26-AUG-17:50 | 239.56 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 870.51 | 05-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.93 | 10-SEP-15:00 | 184.17 | 24-SEP-10:30 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.70 | 01-OCT-15:00 | 413.76 | 24-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 658.25 | 26-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 766.89 | 18-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 344.62 | 1113.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 17-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1363.13 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 13-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1698.19 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 10-MAR-16:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 22-MAR-13:00 | 1377.59 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.65 | 01-APR-17:02 | 1369.40 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.74 | 14-MAY-15:34 | 636.89 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1231.36 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.85 | 04-JUN-19:00 | 464.24 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.06 | 02-JUL-21:20 | 237.98 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.66 | 26-AUG-17:30 | 393.81 | 14-AUG-01:00 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.87 | 10-SEP-14:54 | 266.10 | 24-SEP-10:30 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.68 | 01-OCT-14:57 | 646.94 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 959.85 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:49 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1164.66 | 18-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.98 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 486.06 | 1698.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 17-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 958.77 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1202.51 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 22-MAR-13:00 | 1032.59 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.06 | 21-APR-15:00 | 1027.12 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.41 | 14-MAY-16:00 | 497.19 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 22-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.24 | 04-JUN-19:00 | 372.48 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.17 | 02-JUL-21:17 | 215.04 | 04-JUL-19:20 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.39 | 27-AUG-12:52 | 321.32 | 14-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 05-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 | 10-SEP-14:53 | 175.40 | 24-SEP-15:50 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.79 | 01-OCT-14:57 | 466.36 | 24-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 658.09 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.64 | 18-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.40 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 331.17 | 1202.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2794.74 | 25-JAN-23:00 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.74 | 20-FEB-15:50 | 3478.14 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 10-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.21 | 19-MAR-13:53 | 2513.06 | 19-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.15 | 01-APR-17:02 | 2828.77 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 975.14 | 14-MAY-16:00 | 1306.94 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 929.98 | 04-JUN-19:00 | 1040.23 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 03-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.26 | 02-JUL-20:57 | 526.74 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 16-AUG-15:50 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 733.10 | 26-AUG-17:01 | 851.81 | 14-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.86 | 10-SEP-15:10 | 503.97 | 24-SEP-07:00 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.25 | 01-OCT-14:51 | 1311.32 | 23-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1648.85 | 26-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2454.45 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.97 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.26 | 3478.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1667.75 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1855.80 | 25-JAN-23:00 |
February | 1239.33 | 01-FEB-08:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2332.50 | 09-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 1453.34 | 10-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 22-MAR-13:00 | 1800.89 | 19-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 947.51 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.93 | 01-APR-17:02 | 1898.70 | 10-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 870.51 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 673.36 | 14-MAY-16:00 | 863.27 | 04-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 870.51 | 19-JUN-15:20 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 663.71 | 04-JUN-19:00 | 700.23 | 28-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 947.51 | 03-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 817.76 | 02-JUL-21:00 | 347.05 | 18-JUL-21:10 |
August | 1239.33 | 01-AUG-07:10 | 947.51 | 16-AUG-15:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.12 | 26-AUG-17:50 | 583.28 | 14-AUG-00:53 |
September | 1239.33 | 01-SEP-07:10 | 870.51 | 05-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.35 | 10-SEP-15:10 | 431.14 | 24-SEP-10:00 |
October | 1239.33 | 02-OCT-07:10 | 1453.34 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.93 | 01-OCT-14:51 | 882.99 | 23-OCT-21:10 |
November | 1239.33 | 01-NOV-07:10 | 1667.75 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1307.22 | 26-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1642.70 | 18-DEC-05:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.05 | |||||
Maximum of Months | 1239.33 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 817.76 | 2332.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 17-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2879.57 | 25-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 13-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3626.87 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 10-MAR-16:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 22-MAR-13:00 | 2859.09 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.83 | 01-APR-17:02 | 2886.41 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 976.49 | 14-MAY-16:00 | 1322.29 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1231.36 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.35 | 04-JUN-19:00 | 1030.84 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.16 | 02-JUL-20:57 | 530.97 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.60 | 26-AUG-17:01 | 891.03 | 14-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.32 | 10-SEP-15:04 | 612.63 | 24-SEP-10:47 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.55 | 01-OCT-15:10 | 1443.06 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2017.81 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:49 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2454.42 | 18-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.97 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.16 | 3626.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 17-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1880.21 | 25-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2375.13 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 22-MAR-13:00 | 1870.17 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 20-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.45 | 21-APR-15:00 | 1944.82 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.60 | 14-MAY-16:00 | 927.81 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 22-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 640.82 | 04-JUN-18:57 | 762.94 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.72 | 02-JUL-20:57 | 433.98 | 04-JUL-19:23 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.79 | 26-AUG-17:46 | 647.68 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.41 | 10-SEP-15:04 | 402.15 | 24-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 1667.75 | 13-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.89 | 01-OCT-15:04 | 941.39 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1188.22 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1636.31 | 18-DEC-05:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.15 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 834.72 | 2375.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2587.92 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3299.53 | 25-JAN-22:03 |
February | 2010.79 | 01-FEB-10:09 | 2255.20 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.56 | 20-FEB-16:00 | 3962.37 | 09-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2255.20 | 10-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.40 | 19-MAR-14:45 | 2850.85 | 01-MAR-22:03 |
April | 2010.79 | 03-APR-09:09 | 1803.00 | 20-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.47 | 01-APR-17:02 | 3247.70 | 10-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1350.81 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.38 | 14-MAY-16:00 | 1498.53 | 04-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1231.33 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.04 | 04-JUN-18:57 | 1293.26 | 28-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1470.28 | 03-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.45 | 02-JUL-20:57 | 666.09 | 18-JUL-21:10 |
August | 2010.79 | 01-AUG-09:09 | 1470.28 | 16-AUG-15:50 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 872.16 | 26-AUG-17:01 | 1101.74 | 14-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 1803.00 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.55 | 10-SEP-15:10 | 626.13 | 23-SEP-17:10 |
October | 2010.79 | 02-OCT-09:09 | 2255.20 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 744.28 | 01-OCT-15:00 | 1551.22 | 23-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2587.92 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 23-NOV-15:50 | 1840.42 | 28-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 2587.92 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3067.29 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.13 | |||||
Maximum of Months | 2010.79 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.45 | 3962.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2198.84 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | 20-FEB-16:00 | 2671.64 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 10-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 22-MAR-13:00 | 1960.10 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 947.51 | 20-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.63 | 01-APR-17:02 | 2189.06 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 870.51 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.06 | 14-MAY-15:45 | 992.70 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 19-JUN-15:20 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 798.14 | 04-JUN-19:00 | 871.73 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 947.51 | 03-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 997.66 | 02-JUL-20:57 | 449.20 | 04-JUL-19:20 |
August | 1295.83 | 01-AUG-09:09 | 947.51 | 16-AUG-15:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.62 | 26-AUG-17:01 | 751.38 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 870.51 | 05-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.61 | 10-SEP-15:10 | 533.12 | 24-SEP-10:30 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.34 | 01-OCT-14:53 | 1056.31 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1347.37 | 26-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2044.86 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.20 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 997.66 | 2671.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2587.98 | 17-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3311.19 | 25-JAN-22:03 |
February | 2010.83 | 01-FEB-10:09 | 2255.25 | 13-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4145.46 | 09-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2255.25 | 10-MAR-16:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 22-MAR-13:00 | 3132.60 | 19-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1803.04 | 20-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.69 | 01-APR-17:02 | 3322.88 | 10-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1350.84 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.59 | 14-MAY-15:45 | 1517.50 | 04-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1231.36 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.07 | 04-JUN-18:57 | 1281.57 | 28-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1803.04 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.09 | 02-JUL-20:57 | 671.49 | 18-JUL-21:10 |
August | 2010.83 | 01-AUG-09:09 | 1470.31 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 837.59 | 26-AUG-17:01 | 1141.90 | 14-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 1350.84 | 01-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.00 | 10-SEP-15:04 | 752.24 | 24-SEP-11:00 |
October | 2010.83 | 02-OCT-09:09 | 2255.25 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.72 | 01-OCT-14:57 | 1729.14 | 23-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2587.98 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2104.59 | 26-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 2587.98 | 01-DEC-16:49 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3067.17 | 18-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.49 | |||||
Maximum of Months | 2010.83 | 2587.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1445.09 | 4145.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1667.75 | 17-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2203.51 | 25-JAN-22:03 |
February | 1295.83 | 01-FEB-10:09 | 1453.34 | 13-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2732.31 | 09-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1453.34 | 10-MAR-16:00 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 22-MAR-13:00 | 2078.46 | 19-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1161.92 | 20-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.96 | 21-APR-15:00 | 2248.59 | 10-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 947.51 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 728.18 | 14-MAY-16:00 | 1072.45 | 04-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 870.51 | 22-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 781.49 | 04-JUN-18:57 | 949.65 | 28-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 1161.92 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.33 | 02-JUL-20:57 | 562.88 | 04-JUL-19:20 |
August | 1295.83 | 01-AUG-09:09 | 1161.92 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 548.38 | 27-AUG-13:04 | 815.67 | 14-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1161.92 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.22 | 10-SEP-15:04 | 487.44 | 24-SEP-15:50 |
October | 1295.83 | 02-OCT-09:09 | 1453.34 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.67 | 01-OCT-14:51 | 1126.74 | 23-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1667.75 | 22-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1256.82 | 26-NOV-16:55 |
December | 1295.83 | 01-DEC-10:09 | 1667.75 | 01-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2044.78 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 870.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.44 | |||||
Maximum of Months | 1295.83 | 1667.75 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1029.33 | 2732.31 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 578.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 578.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 578.72 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 578.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 578.72 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 578.72 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 578.72 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 578.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 578.72 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 578.72 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 578.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 578.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 6471.01 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 6471.01 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 6471.01 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 6471.01 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 6471.01 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 6471.01 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 6471.01 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 6471.01 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 6471.01 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 6471.01 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 6471.01 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 6471.01 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 6471.01 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3057.41 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3800.12 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 22-MAR-13:00 | 3023.94 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.33 | 01-APR-17:02 | 3047.24 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882.28 | 14-MAY-16:00 | 1396.11 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.77 | 04-JUN-19:00 | 1003.33 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.03 | 02-JUL-20:55 | 490.88 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.29 | 26-AUG-17:01 | 806.20 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.38 | 10-SEP-15:00 | 514.77 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.98 | 01-OCT-15:00 | 1393.31 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1917.37 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2657.78 | 18-DEC-05:13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.03 | 3800.12 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5191.95 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6586.95 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 22-MAR-13:00 | 4986.03 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 820.25 | 01-APR-17:02 | 5259.08 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.31 | 14-MAY-16:00 | 2394.72 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.33 | 04-JUN-19:00 | 1774.57 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1799.72 | 02-JUL-21:10 | 880.89 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.82 | 27-AUG-12:52 | 1384.77 | 14-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.33 | 10-SEP-14:51 | 900.46 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.35 | 01-OCT-14:51 | 2410.22 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3200.17 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4245.82 | 18-DEC-05:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1799.72 | 6586.95 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5276.97 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6581.43 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4616.06 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.62 | 01-APR-17:02 | 5246.36 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.91 | 14-MAY-16:00 | 2398.21 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.45 | 10-JUN-17:01 | 2085.06 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1838.77 | 02-JUL-21:20 | 1041.17 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.00 | 26-AUG-17:01 | 1724.14 | 14-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.66 | 10-SEP-14:51 | 1008.69 | 23-SEP-17:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.87 | 01-OCT-15:00 | 2570.77 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2850.49 | 04-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3991.31 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.69 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1838.77 | 6581.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 120011.53 | 17-JAN-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 115637.10 | 27-FEB-05:11 | 0.00 | 20401.06 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115399.34 | 13-MAR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 117458.20 | 10-APR-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 119266.47 | 01-MAY-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115845.00 | 26-JUN-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 112574.48 | 05-JUL-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 117764.34 | 20-AUG-16:40 | 8976.13 | 12749.23 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117892.39 | 18-SEP-04:12 | 0.00 | 15300.79 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 121641.50 | 30-OCT-04:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 119867.90 | 20-NOV-05:11 | 0.00 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117802.26 | 11-DEC-05:11 | 0.00 | 17850.93 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 112574.48 | 0.00 | 12749.23 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 121641.50 | 8976.13 | 25501.32 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96859.57 | 02-JAN-05:11 | 0.00 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94722.29 | 21-FEB-05:12 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93470.97 | 13-MAR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94962.28 | 24-APR-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98953.47 | 22-MAY-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99758.80 | 09-JUN-04:13 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 91513.54 | 05-JUL-04:12 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94570.18 | 14-AUG-05:04 | 8061.19 | 11450.99 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100914.36 | 18-SEP-04:13 | 0.00 | 13741.19 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 100943.77 | 10-OCT-04:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102016.63 | 13-NOV-05:11 | 0.00 | 20611.78 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 97221.68 | 11-DEC-05:11 | 0.00 | 16031.39 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91513.54 | 0.00 | 11450.99 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 102016.63 | 8061.19 | 22901.98 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76775.12 | 13-JAN-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80460.28 | 23-FEB-06:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82878.53 | 09-MAR-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86136.24 | 28-APR-04:11 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86673.17 | 24-MAY-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87766.55 | 23-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88960.68 | 05-JUL-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88073.62 | 30-AUG-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88725.13 | 06-SEP-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86989.36 | 03-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81725.51 | 02-NOV-05:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 59875.97 | 02-DEC-06:02 | 8061.19 | 11450.99 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 59875.97 | 0.00 | 9160.79 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88960.68 | 8061.19 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 33686.17 | 12-JAN-16:50 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36412.72 | 23-FEB-15:30 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67227.01 | 16-MAR-05:03 | 6448.95 | 9160.79 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84766.59 | 20-APR-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86502.65 | 22-MAY-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86780.73 | 20-JUN-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89716.88 | 24-JUL-04:13 | 0.00 | 16031.39 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88682.26 | 14-AUG-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87795.16 | 05-SEP-04:12 | 0.00 | 11450.99 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85311.58 | 05-OCT-04:12 | 0.00 | 13741.19 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53051.29 | 10-NOV-06:03 | 4836.72 | 6870.59 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28908.93 | 01-DEC-16:50 | 15316.26 | 20611.01 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 28908.93 | 0.00 | 6870.59 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89716.88 | 15316.26 | 20611.01 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3416.35 | 13-JAN-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
February | 5538.25 | 21-FEB-15:00 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
March | 6673.75 | 15-MAR-13:40 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
April | 9884.99 | 03-APR-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 |
May | 19008.58 | 29-MAY-17:31 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 143.51 | 0.00 |
June | 19495.95 | 25-JUN-18:01 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 | 0.00 |
July | 18994.24 | 30-JUL-16:31 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 | 0.00 |
August | 18934.05 | 06-AUG-17:01 | 0.00 | 547.22 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 223.36 | 0.00 |
September | 16536.07 | 10-SEP-15:31 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 | 0.00 |
October | 14445.05 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
November | 5717.63 | 08-NOV-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 |
December | 3805.63 | 11-DEC-13:10 | 1923.11 | 1350.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3416.35 | 0.00 | 547.22 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19495.95 | 2010.79 | 1437.79 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 223.36 | 109.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5908.36 | 31-JAN-09:05 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 |
February | 8388.28 | 21-FEB-08:35 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
March | 9908.62 | 26-MAR-09:43 | 195.68 | 132.24 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 |
April | 19846.68 | 30-APR-07:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.88 |
May | 20588.47 | 29-MAY-08:51 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.56 |
June | 19628.69 | 11-JUN-08:12 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 |
July | 19058.30 | 04-JUL-08:42 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
August | 18982.22 | 13-AUG-08:22 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 |
September | 20148.67 | 17-SEP-08:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.75 |
October | 16591.39 | 22-OCT-08:43 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.84 |
November | 9330.58 | 10-NOV-08:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.90 |
December | 4777.02 | 07-DEC-09:15 | 2478.65 | 1587.03 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4777.02 | 195.68 | 132.24 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | |
Maximum of Months | 20588.47 | 2478.65 | 1587.03 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21704.64 | 01-JAN-14:53 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.14 |
February | 21744.60 | 20-FEB-13:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.56 |
March | 14996.91 | 26-MAR-12:33 | 303.66 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.24 |
April | 21562.76 | 30-APR-12:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | 0.00 |
May | 21115.02 | 29-MAY-14:51 | 809.75 | 547.23 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 97.41 | 0.00 |
June | 20647.34 | 11-JUN-16:11 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 266.82 | 0.00 |
July | 21894.26 | 30-JUL-15:11 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
August | 21412.49 | 06-AUG-13:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 113.34 | 0.00 |
September | 23367.11 | 17-SEP-12:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 0.00 |
October | 24581.89 | 29-OCT-12:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.70 |
November | 24022.13 | 11-NOV-12:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.28 |
December | 21772.05 | 17-DEC-12:02 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14996.91 | 303.66 | 205.21 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24581.89 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 266.82 | 471.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8864.23 | 12-JAN-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 |
February | 18945.78 | 20-FEB-15:42 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 |
March | 24058.68 | 26-MAR-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.40 |
April | 26605.61 | 30-APR-16:21 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
May | 27370.42 | 29-MAY-15:31 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 0.00 |
June | 28479.43 | 25-JUN-16:41 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 0.00 |
July | 27864.61 | 30-JUL-15:11 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 0.00 |
August | 26966.33 | 06-AUG-16:21 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 80.07 | 0.00 |
September | 27038.38 | 17-SEP-15:11 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 45.63 | 0.00 |
October | 24345.72 | 01-OCT-15:22 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 98.04 | 0.00 |
November | 24194.74 | 11-NOV-14:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.82 |
December | 10839.83 | 11-DEC-05:11 | 0.00 | 1297.19 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8864.23 | 0.00 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28479.43 | 1239.33 | 1297.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 98.04 | 219.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2689.24 | 12-JAN-15:10 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
February | 3373.70 | 23-FEB-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 |
March | 4901.85 | 22-MAR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
April | 8299.23 | 21-APR-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 423.68 | 0.00 |
May | 12915.52 | 21-MAY-16:01 | 809.73 | 547.22 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 725.41 | 0.00 |
June | 17542.78 | 18-JUN-15:31 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 318.32 | 0.00 |
July | 18471.09 | 09-JUL-18:21 | 0.00 | 600.31 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 335.72 | 0.00 |
August | 18592.06 | 06-AUG-16:51 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 496.75 | 0.00 |
September | 12087.49 | 23-SEP-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 |
October | 10786.06 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
November | 3882.46 | 09-NOV-16:10 | 1923.11 | 2135.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
December | 2342.06 | 07-DEC-14:10 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2342.06 | 0.00 | 478.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18592.06 | 2010.79 | 2135.72 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 725.41 | 141.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3782.49 | 31-JAN-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.26 |
February | 5866.35 | 21-FEB-10:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
March | 8115.61 | 31-MAR-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 |
April | 20615.95 | 30-APR-07:52 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.98 |
May | 20890.24 | 28-MAY-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.24 |
June | 19901.28 | 18-JUN-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 101.59 | 0.00 |
July | 21034.22 | 09-JUL-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.48 |
August | 21436.17 | 06-AUG-08:11 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 |
September | 21320.07 | 17-SEP-09:21 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 |
October | 14580.96 | 22-OCT-09:13 | 260.91 | 176.32 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.70 |
November | 8083.53 | 10-NOV-09:00 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.22 |
December | 2867.35 | 07-DEC-09:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2867.35 | 260.91 | 176.32 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21436.17 | 1239.33 | 793.52 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 101.59 | 216.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21091.84 | 01-JAN-13:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.78 |
February | 21733.66 | 19-FEB-14:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.27 |
March | 19199.36 | 19-MAR-14:13 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.05 |
April | 20977.53 | 30-APR-14:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 0.00 |
May | 19889.79 | 21-MAY-15:21 | 910.97 | 615.63 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 598.62 | 0.00 |
June | 17323.39 | 18-JUN-15:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 318.35 | 0.00 |
July | 20098.89 | 09-JUL-16:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 245.77 | 0.00 |
August | 21387.95 | 06-AUG-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 254.92 | 0.00 |
September | 22703.78 | 17-SEP-12:42 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 95.20 | 0.00 |
October | 23664.85 | 22-OCT-13:11 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
November | 22536.81 | 23-NOV-13:12 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.14 |
December | 20871.89 | 31-DEC-14:32 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17323.39 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23664.85 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 598.62 | 843.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6490.09 | 12-JAN-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 |
February | 12936.86 | 19-FEB-16:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 |
March | 20666.03 | 26-MAR-16:21 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.28 |
April | 24320.13 | 30-APR-16:31 | 587.05 | 396.73 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 0.00 |
May | 23736.27 | 07-MAY-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 |
June | 22783.15 | 25-JUN-16:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 151.51 | 0.00 |
July | 24602.81 | 09-JUL-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 88.14 | 0.00 |
August | 25154.96 | 06-AUG-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 226.73 | 0.00 |
September | 23668.41 | 17-SEP-16:41 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 76.36 | 0.00 |
October | 21315.95 | 22-OCT-15:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
November | 9702.69 | 09-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 |
December | 5572.55 | 15-DEC-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5572.55 | 391.37 | 264.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25154.96 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 226.73 | 256.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2709.40 | 12-JAN-14:30 | 2010.79 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 |
February | 2760.56 | 22-FEB-13:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
March | 4887.56 | 22-MAR-14:30 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
April | 9063.78 | 21-APR-15:00 | 1923.11 | 1231.33 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 518.95 | 0.00 |
May | 15535.10 | 21-MAY-16:12 | 607.30 | 410.41 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.89 | 0.00 |
June | 20517.04 | 18-JUN-15:31 | 708.51 | 478.82 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 382.37 | 0.00 |
July | 21324.03 | 09-JUL-17:41 | 0.00 | 615.62 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 421.69 | 0.00 |
August | 21745.86 | 06-AUG-16:51 | 1012.16 | 684.02 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 578.08 | 0.00 |
September | 13564.72 | 13-SEP-05:03 | 809.73 | 1150.23 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
October | 8984.84 | 02-OCT-05:02 | 1012.16 | 1437.79 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
November | 3842.67 | 09-NOV-16:10 | 1923.11 | 2135.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 |
December | 2030.15 | 08-DEC-16:30 | 1923.11 | 2587.92 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2030.15 | 0.00 | 410.41 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21745.86 | 2010.79 | 2587.92 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 867.89 | 86.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2688.79 | 12-JAN-14:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 |
February | 4502.25 | 21-FEB-10:30 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.66 |
March | 7093.83 | 16-MAR-10:00 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.70 |
April | 19782.44 | 16-APR-09:12 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.55 |
May | 19793.55 | 29-MAY-09:02 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.45 |
June | 20403.56 | 18-JUN-09:32 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 119.10 | 0.00 |
July | 21387.25 | 09-JUL-08:22 | 391.37 | 264.49 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.00 |
August | 21881.37 | 06-AUG-08:11 | 456.59 | 308.57 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 |
September | 19153.02 | 17-SEP-09:32 | 326.14 | 220.40 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 |
October | 10862.61 | 05-OCT-08:40 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
November | 7270.11 | 10-NOV-09:20 | 1239.33 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.29 |
December | 2107.81 | 01-DEC-10:20 | 1295.83 | 793.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2107.81 | 326.14 | 220.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21881.37 | 1295.83 | 793.52 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 119.10 | 202.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17301.22 | 12-JAN-14:20 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 |
February | 23252.83 | 19-FEB-14:42 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.80 |
March | 14627.79 | 16-MAR-13:30 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 |
April | 22956.19 | 30-APR-13:23 | 404.87 | 273.61 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 77.94 | 0.00 |
May | 18049.82 | 21-MAY-15:32 | 607.31 | 410.42 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 775.53 | 0.00 |
June | 22291.74 | 18-JUN-15:31 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 386.12 | 0.00 |
July | 23158.54 | 09-JUL-16:21 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 275.26 | 0.00 |
August | 24475.35 | 06-AUG-15:31 | 1012.19 | 684.04 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 296.10 | 0.00 |
September | 23522.29 | 17-SEP-13:32 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 247.71 | 0.00 |
October | 25987.45 | 22-OCT-13:41 | 708.53 | 478.83 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 |
November | 23229.37 | 05-NOV-14:12 | 506.09 | 342.02 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.90 |
December | 14643.93 | 07-DEC-14:10 | 2010.83 | 1231.36 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14627.79 | 404.87 | 273.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25987.45 | 2010.83 | 1231.36 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 775.53 | 475.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6263.90 | 12-JAN-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
February | 12733.56 | 20-FEB-15:52 | 326.14 | 220.40 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.76 |
March | 14951.39 | 26-MAR-16:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 |
April | 24515.07 | 23-APR-16:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.47 |
May | 25629.64 | 07-MAY-16:51 | 521.82 | 352.65 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
June | 24509.67 | 25-JUN-16:51 | 456.59 | 308.57 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 174.32 | 0.00 |
July | 27029.35 | 09-JUL-16:21 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 96.04 | 0.00 |
August | 27666.70 | 06-AUG-16:51 | 652.28 | 440.81 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 260.96 | 0.00 |
September | 23652.06 | 17-SEP-15:32 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 187.78 | 0.00 |
October | 23790.69 | 22-OCT-15:42 | 391.37 | 264.49 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
November | 9724.00 | 09-NOV-15:30 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 |
December | 4958.75 | 15-DEC-15:50 | 1239.33 | 793.52 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4958.75 | 326.14 | 220.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27666.70 | 1239.33 | 793.52 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 260.96 | 312.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5850.90 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.70 |
February | 6130.79 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.61 |
March | 5878.08 | 16-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.11 |
April | 7741.23 | 21-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.18 | 0.00 |
May | 10005.49 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.85 | 0.00 |
June | 9777.13 | 19-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 | 0.00 |
July | 10936.93 | 03-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 0.00 |
August | 16738.61 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
September | 12531.27 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.91 |
October | 8891.34 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.84 |
November | 7881.36 | 13-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 5259.50 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16738.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.18 | 258.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7240.85 | 28-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.01 |
February | 8372.48 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2628.99 |
March | 6275.01 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.98 |
April | 6396.53 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.12 | 0.00 |
May | 7822.56 | 30-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.41 | 0.00 |
June | 9093.03 | 10-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 |
July | 8752.15 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.23 | 0.00 |
August | 8452.34 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 |
September | 7957.90 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 | 0.00 |
October | 6873.18 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.92 | 0.00 |
November | 7021.12 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.47 |
December | 6986.47 | 27-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6275.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9093.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.12 | 2628.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5383.76 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 |
February | 8053.86 | 22-FEB-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11246.59 | 16-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.98 |
April | 17702.26 | 28-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 | 0.00 |
May | 20987.20 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.71 | 0.00 |
June | 22611.95 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.17 | 0.00 |
July | 22810.41 | 03-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.90 | 0.00 |
August | 21797.57 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.57 | 0.00 |
September | 18784.11 | 15-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.65 | 0.00 |
October | 16490.86 | 03-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.94 | 0.00 |
November | 8971.02 | 09-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 |
December | 2602.33 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2602.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22810.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.17 | 479.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2203.02 | 30-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4137.56 | 21-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7124.22 | 31-MAR-24:00 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7918.78 | 22-APR-17:55 | 23.38 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3522.58 | 31-MAY-23:43 | 0.00 | 96.46 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5368.68 | 30-JUN-23:55 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7287.16 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7878.75 | 27-AUG-20:33 | 0.00 | 128.61 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3486.10 | 30-SEP-24:00 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5292.03 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6191.39 | 09-NOV-16:50 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7938.92 | 18-DEC-16:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2203.02 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7938.92 | 222.14 | 578.72 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1954.09 | 30-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3828.96 | 21-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6590.17 | 31-MAR-23:40 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7514.97 | 26-APR-18:00 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3420.18 | 31-MAY-23:55 | 0.00 | 64.31 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5232.69 | 30-JUN-23:55 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7015.92 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7440.07 | 31-AUG-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3235.94 | 30-SEP-23:50 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4814.11 | 31-OCT-24:00 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5830.82 | 09-NOV-16:50 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7407.44 | 15-DEC-16:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1954.09 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7514.97 | 222.14 | 578.72 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1901.99 | 19-JAN-17:00 | 222.14 | 578.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3823.92 | 21-FEB-17:00 | 222.14 | 578.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6299.05 | 31-MAR-23:20 | 0.00 | 32.15 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7585.24 | 26-APR-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3445.65 | 31-MAY-24:00 | 0.00 | 64.31 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5204.79 | 30-JUN-23:55 | 0.00 | 64.31 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7023.76 | 31-JUL-24:00 | 0.00 | 64.31 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7569.58 | 31-AUG-17:50 | 23.38 | 192.90 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3069.77 | 30-SEP-23:20 | 0.00 | 32.15 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4489.70 | 31-OCT-23:20 | 0.00 | 32.15 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5864.83 | 09-NOV-16:50 | 222.14 | 578.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7337.73 | 15-DEC-16:50 | 222.14 | 578.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1901.99 | 0.00 | 32.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7585.24 | 222.14 | 578.72 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92695.52 | 02-JAN-17:00 | 4808.68 | 6471.01 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183584.79 | 21-FEB-17:00 | 4808.68 | 6471.01 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357804.24 | 31-MAR-24:00 | 0.00 | 359.47 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373697.62 | 29-APR-19:33 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175801.07 | 31-MAY-24:00 | 0.00 | 718.95 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267483.98 | 30-JUN-23:55 | 0.00 | 718.95 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 354825.05 | 31-JUL-23:08 | 0.00 | 1437.90 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 378142.40 | 21-AUG-23:13 | 0.00 | 1078.42 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177017.19 | 30-SEP-24:00 | 0.00 | 359.47 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269200.49 | 31-OCT-24:00 | 0.00 | 359.47 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277745.51 | 10-NOV-17:00 | 4808.68 | 6471.01 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368496.82 | 18-DEC-16:55 | 9617.36 | 12942.03 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92695.52 | 0.00 | 359.47 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 378142.40 | 9617.36 | 12942.03 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.176199E+13 | 1240827.23 | 03-JAN-16:00 | 0.159607E+12 | 608187.62 | 27-JAN-07:10 |
February | 0.199381E+13 | 1457009.53 | 21-FEB-16:30 | 0.115769E+12 | 618550.25 | 03-FEB-07:10 |
March | 0.267850E+13 | 1697479.06 | 21-MAR-15:00 | 0.962573E+11 | 495359.74 | 02-MAR-07:10 |
April | 0.318688E+13 | 2067437.13 | 21-APR-15:09 | 0.619171E+11 | 232194.74 | 11-APR-05:10 |
May | 0.218014E+13 | 1517979.77 | 30-MAY-15:50 | 0.601091E+11 | 73569.07 | 11-MAY-11:30 |
June | 0.262363E+13 | 1709476.08 | 07-JUN-15:00 | 0.561302E+11 | 70247.32 | 02-JUN-11:00 |
July | 0.314576E+13 | 1934063.26 | 20-JUL-15:20 | 0.536244E+11 | 67102.92 | 07-JUL-11:00 |
August | 0.357502E+13 | 2067513.91 | 23-AUG-15:00 | 0.565546E+11 | 67401.56 | 28-AUG-11:39 |
September | 0.202280E+13 | 1507756.00 | 01-SEP-15:30 | 0.543178E+11 | 70573.25 | 27-SEP-11:20 |
October | 0.230479E+13 | 1620949.03 | 20-OCT-15:50 | 0.594388E+11 | 73986.98 | 30-OCT-11:50 |
November | 0.251088E+13 | 1674383.18 | 09-NOV-16:49 | 0.935420E+11 | 515103.77 | 28-NOV-05:10 |
December | 0.284650E+13 | 1673577.54 | 08-DEC-16:00 | 0.187307E+12 | 677954.45 | 27-DEC-07:10 |
Annual Sum or Average | 0.308307E+14 | 0.105457E+13 | ||||
Minimum of Months | 0.176199E+13 | 1240827.23 | 0.536244E+11 | 67102.92 | ||
Maximum of Months | 0.357502E+13 | 2067513.91 | 0.187307E+12 | 677954.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.332088E+12 | 0.711366E+11 | 0.766053E+12 | 0.164270E+12 | 0.193303E+12 | 0.188741E+11 | 0.00 | 0.228170E+11 | 0.668789E+10 | 0.186763E+12 | 0.00 | 0.00 | 0.00 |
February | 0.299624E+12 | 0.600063E+11 | 0.978954E+12 | 0.148382E+12 | 0.180472E+12 | 0.216235E+11 | 0.00 | 0.554035E+11 | 0.242709E+11 | 0.225075E+12 | 0.00 | 0.00 | 0.00 |
March | 0.352539E+12 | 0.603920E+11 | 0.141687E+13 | 0.164522E+12 | 0.214809E+12 | 0.299485E+11 | 0.00 | 0.129798E+12 | 0.489324E+11 | 0.260682E+12 | 0.00 | 0.00 | 0.00 |
April | 0.313207E+12 | 0.523634E+11 | 0.165903E+13 | 0.158945E+12 | 0.231333E+12 | 0.471291E+11 | 0.00 | 0.372631E+12 | 0.104842E+12 | 0.247410E+12 | 0.00 | 0.00 | 0.00 |
May | 0.337099E+12 | 0.488874E+11 | 0.774844E+12 | 0.164394E+12 | 0.266598E+12 | 0.568356E+11 | 0.00 | 0.270716E+12 | 0.124709E+12 | 0.136060E+12 | 0.00 | 0.00 | 0.00 |
June | 0.334835E+12 | 0.446936E+11 | 0.106252E+13 | 0.159182E+12 | 0.288328E+12 | 0.698703E+11 | 0.00 | 0.475044E+12 | 0.147733E+12 | 0.414278E+11 | 0.00 | 0.00 | 0.00 |
July | 0.314110E+12 | 0.473327E+11 | 0.139340E+13 | 0.164156E+12 | 0.283529E+12 | 0.771187E+11 | 0.00 | 0.684089E+12 | 0.176395E+12 | 0.562866E+10 | 0.00 | 0.00 | 0.00 |
August | 0.350573E+12 | 0.517895E+11 | 0.173200E+13 | 0.164521E+12 | 0.291804E+12 | 0.756132E+11 | 0.00 | 0.701346E+12 | 0.164045E+12 | 0.433272E+11 | 0.00 | 0.00 | 0.00 |
September | 0.314112E+12 | 0.557491E+11 | 0.740713E+12 | 0.158944E+12 | 0.254148E+12 | 0.569632E+11 | 0.00 | 0.276891E+12 | 0.134515E+12 | 0.307600E+11 | 0.00 | 0.00 | 0.00 |
October | 0.328562E+12 | 0.639505E+11 | 0.108340E+13 | 0.164269E+12 | 0.228581E+12 | 0.430386E+11 | 0.00 | 0.200318E+12 | 0.861653E+11 | 0.106505E+12 | 0.00 | 0.00 | 0.00 |
November | 0.327817E+12 | 0.671846E+11 | 0.135889E+13 | 0.159044E+12 | 0.199275E+12 | 0.253178E+11 | 0.00 | 0.100651E+12 | 0.376768E+11 | 0.235026E+12 | 0.00 | 0.00 | 0.00 |
December | 0.322558E+12 | 0.724494E+11 | 0.170972E+13 | 0.164159E+12 | 0.194212E+12 | 0.180419E+11 | 0.00 | 0.756035E+11 | 0.221991E+11 | 0.267557E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392712E+13 | 0.695935E+12 | 0.146764E+14 | 0.193479E+13 | 0.282639E+13 | 0.540374E+12 | 0.00 | 0.336531E+13 | 0.107817E+13 | 0.178622E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299624E+12 | 0.446936E+11 | 0.740713E+12 | 0.148382E+12 | 0.180472E+12 | 0.180419E+11 | 0.00 | 0.228170E+11 | 0.668789E+10 | 0.562866E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352539E+12 | 0.724494E+11 | 0.173200E+13 | 0.164522E+12 | 0.291804E+12 | 0.771187E+11 | 0.00 | 0.701346E+12 | 0.176395E+12 | 0.267557E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.931579E+11 | 0.00 | 0.664490E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.555347E+11 | 0.00 | 0.602340E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.285538E+11 | 0.00 | 0.677035E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.180580E+10 | 0.00 | 0.601113E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 165232.08 | 0.00 | 0.601090E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.561302E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.536244E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.565546E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 568965.17 | 0.00 | 0.543172E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.555503E+09 | 0.00 | 0.588833E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.329425E+11 | 0.00 | 0.605995E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.123449E+12 | 0.00 | 0.638574E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.336000E+12 | 0.00 | 0.718573E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.536244E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.123449E+12 | 0.00 | 0.677035E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 385834.94 | 17-JAN-16:40 | 57580.60 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 118509.21 | 09-JAN-08:20 | 135623.85 | 12-JAN-16:10 | 26869.53 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 372703.55 | 23-FEB-16:49 | 57580.60 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 118522.65 | 13-FEB-08:20 | 155844.43 | 21-FEB-16:30 | 25928.60 | 24-FEB-05:19 | 0.00 | 01-FEB-00:10 |
March | 372703.55 | 10-MAR-16:00 | 57580.60 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 118513.95 | 22-MAR-07:19 | 190431.53 | 16-MAR-15:39 | 26461.21 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 352283.84 | 20-APR-07:10 | 57580.60 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 118509.21 | 20-APR-07:19 | 242391.22 | 21-APR-14:39 | 49153.65 | 27-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 337010.14 | 03-MAY-07:10 | 57580.60 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 118497.31 | 03-MAY-07:19 | 254532.04 | 30-MAY-14:50 | 49333.40 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 333218.76 | 19-JUN-15:20 | 57580.60 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 118494.36 | 22-JUN-07:19 | 269458.10 | 15-JUN-14:30 | 49940.27 | 07-JUN-14:39 | 0.00 | 01-JUN-00:10 |
July | 348291.20 | 07-JUL-07:30 | 57580.60 | 01-JUL-19:19 | 660080.29 | 03-JUL-07:10 | 118506.10 | 07-JUL-07:40 | 272666.80 | 03-JUL-14:30 | 57132.28 | 20-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 343451.53 | 17-AUG-07:30 | 57580.60 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 118502.32 | 17-AUG-07:40 | 261298.24 | 08-AUG-14:00 | 49236.01 | 23-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 345009.50 | 18-SEP-07:10 | 57580.60 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 118503.54 | 18-SEP-07:19 | 245559.73 | 12-SEP-15:39 | 48888.97 | 18-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 375062.14 | 13-OCT-07:10 | 57580.60 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 118527.01 | 13-OCT-07:19 | 215734.74 | 03-OCT-15:39 | 48663.76 | 19-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 385834.94 | 22-NOV-16:00 | 57580.60 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 118525.16 | 01-NOV-07:19 | 180799.03 | 09-NOV-16:30 | 26995.38 | 27-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 385834.94 | 01-DEC-16:49 | 57580.60 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 118502.42 | 13-DEC-08:20 | 133769.44 | 15-DEC-15:30 | 27242.55 | 26-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 333218.76 | 57580.60 | 423497.50 | 118494.36 | 133769.44 | 25928.60 | 0.00 | |||||||
Maximum of Months | 385834.94 | 57580.60 | 778371.69 | 118527.01 | 272666.80 | 57132.28 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 83563.74 | 03-JAN-14:30 | 49609.77 | 03-JAN-13:50 | 100000.00 | 01-JAN-01:10 | 0.00 | 0.00 | 0.00 |
February | 168557.38 | 21-FEB-15:00 | 49847.29 | 21-FEB-15:00 | 100000.00 | 01-FEB-04:19 | 0.00 | 0.00 | 0.00 |
March | 272544.15 | 21-MAR-15:00 | 51001.30 | 14-MAR-15:00 | 100000.00 | 01-MAR-05:19 | 0.00 | 0.00 | 0.00 |
April | 403433.97 | 21-APR-14:39 | 86451.33 | 21-APR-13:50 | 100000.00 | 01-APR-04:49 | 0.00 | 0.00 | 0.00 |
May | 295318.24 | 30-MAY-14:00 | 86451.33 | 08-MAY-12:20 | 100000.00 | 01-MAY-01:49 | 0.00 | 0.00 | 0.00 |
June | 368909.11 | 15-JUN-14:39 | 86451.33 | 01-JUN-14:50 | 100000.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 545030.27 | 21-JUL-09:50 | 86451.33 | 01-JUL-09:09 | 39581.16 | 15-JUL-11:09 | 0.00 | 0.00 | 0.00 |
August | 476490.06 | 02-AUG-08:20 | 86451.33 | 01-AUG-07:49 | 100000.00 | 19-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 354167.96 | 14-SEP-09:50 | 86451.33 | 01-SEP-07:30 | 100000.00 | 10-SEP-21:00 | 0.00 | 0.00 | 0.00 |
October | 345985.65 | 03-OCT-13:00 | 86451.33 | 02-OCT-10:39 | 100000.00 | 09-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 247496.34 | 03-NOV-15:00 | 52153.19 | 03-NOV-15:00 | 100000.00 | 05-NOV-06:49 | 0.00 | 0.00 | 0.00 |
December | 138274.49 | 20-DEC-14:00 | 49333.25 | 08-DEC-14:09 | 100000.00 | 01-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 83563.74 | 49333.25 | 39581.16 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 545030.27 | 86451.33 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1240827.23 | 03-JAN-16:00 | 369421.86 | 423497.50 | 0.00 | 84467.11 | 110929.51 | 25405.10 | 0.00 | 77667.87 | 49438.30 |
February | 1457009.53 | 21-FEB-16:30 | 334652.47 | 541788.89 | 0.00 | 84450.40 | 155844.43 | 25523.46 | 0.00 | 164948.91 | 49800.97 |
March | 1697479.06 | 21-MAR-15:00 | 334652.47 | 660080.29 | 0.00 | 84452.08 | 169258.18 | 25646.73 | 0.00 | 272544.15 | 50845.15 |
April | 2067437.13 | 21-APR-15:09 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 239122.98 | 47505.34 | 0.00 | 399240.71 | 86451.33 |
May | 1517979.77 | 30-MAY-15:50 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 250436.96 | 48986.25 | 0.00 | 291862.66 | 86451.33 |
June | 1709476.08 | 07-JUN-15:00 | 332294.83 | 541788.89 | 0.00 | 84450.25 | 250775.71 | 49789.53 | 0.00 | 363925.53 | 86451.33 |
July | 1934063.26 | 20-JUL-15:20 | 332294.83 | 660080.29 | 0.00 | 84450.25 | 180343.31 | 50203.03 | 0.00 | 540240.22 | 86451.33 |
August | 2067513.91 | 23-AUG-15:00 | 332294.83 | 778371.69 | 0.00 | 84450.25 | 221998.34 | 49148.30 | 0.00 | 414799.18 | 86451.33 |
September | 1507756.00 | 01-SEP-15:30 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 242175.40 | 48132.35 | 0.00 | 290754.34 | 86451.33 |
October | 1620949.03 | 20-OCT-15:50 | 334652.47 | 541788.89 | 0.00 | 84452.08 | 195494.11 | 47382.41 | 0.00 | 264341.22 | 52837.84 |
November | 1674383.18 | 09-NOV-16:49 | 374338.52 | 660080.29 | 0.00 | 84467.37 | 169992.57 | 25566.44 | 0.00 | 219237.16 | 51425.07 |
December | 1673577.54 | 08-DEC-16:00 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 107836.70 | 25328.28 | 0.00 | 84885.01 | 49248.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1240827.23 | 332294.83 | 423497.50 | 0.00 | 84450.25 | 107836.70 | 25328.28 | 0.00 | 77667.87 | 49248.27 | |
Maximum of Months | 2067513.91 | 385834.94 | 778371.69 | 57580.60 | 84492.05 | 250775.71 | 50203.03 | 0.00 | 540240.22 | 86451.33 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 576786.60 | 27-JAN-07:10 | 0.00 | 80952.23 | 30-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 587083.95 | 03-FEB-07:10 | 0.00 | 80825.00 | 10-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 463982.42 | 02-MAR-07:10 | 0.00 | 80234.21 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 203161.26 | 11-APR-05:10 | 0.00 | 77911.38 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 180.06 | 02-MAY-05:00 | 0.00 | 73569.07 | 11-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 70247.32 | 02-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 67102.92 | 07-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 67401.56 | 28-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 508.79 | 25-SEP-05:49 | 0.00 | 70573.25 | 27-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 44928.12 | 25-OCT-05:10 | 0.00 | 73986.98 | 30-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 506957.19 | 28-NOV-05:10 | 0.00 | 78117.48 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 646583.87 | 27-DEC-07:10 | 0.00 | 80185.41 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67102.92 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 646583.87 | 0.00 | 80952.23 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.11 | 0.83 | 27.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.79 | 0.00 | 26.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.73 | 0.00 | 25.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.79 | 0.00 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.26 | 0.00 | 26.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.88 | 0.00 | 25.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.37 | 0.17 | 26.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.13 | 0.17 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.51 | 0.17 | 26.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.61 | 0.33 | 26.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.64 | 0.33 | 26.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.77 | 1.33 | 26.86 |
Annual Sum or Average | 0.00 | 0.00 | 62.00 | 26.54 | 3.33 | 26.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.11 | 1.33 | 27.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.67 | 0.00 | 25.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.73 | 0.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.60 | 0.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 25.65 | 0.00 | 25.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.73 | 0.00 | 25.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Annual Sum or Average | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.17 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.24 | 2.00 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.20 | 2.83 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.16 | 3.83 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 27.20 | 8.83 | 27.28 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.31 | 3.83 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.46 | 0.50 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.51 | 1.67 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.94 | 4.67 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.89 | 9.33 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.89 | 9.33 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.92 | 10.17 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.78 | 8.00 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.90 | 6.17 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 3.50 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 55.17 | 27.85 | 53.83 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.94 | 10.17 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.71 | 3.67 | 27.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.86 | 5.67 | 27.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 3.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.60 | 4.83 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.39 | 3.67 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.32 | 1.83 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.42 | 6.83 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.54 | 6.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.90 | 8.00 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.85 | 10.00 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.97 | 8.00 | 27.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.77 | 3.17 | 27.77 |
Annual Sum or Average | 0.00 | 0.00 | 70.50 | 27.70 | 65.83 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.32 | 1.83 | 27.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.97 | 10.00 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.06 | 3.00 | 28.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.29 | 3.33 | 28.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.87 | 6.67 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.09 | 6.17 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.50 | 6.17 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.70 | 11.50 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 27.84 | 13.83 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.84 | 5.67 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.01 | 5.33 | 28.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.09 | 3.67 | 28.09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.58 | 1.67 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 158.83 | 27.82 | 67.17 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 28.29 | 13.83 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.40 | 1.83 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.27 | 1.17 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.36 | 1.67 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 1.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 4.50 | 19.24 | 0.00 | 19.24 | 7.50 | 24.30 | 4.67 | 25.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.29 | 0.00 | 19.29 | 2.83 | 27.40 | 1.83 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.92 | 4.83 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.92 | 11.00 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.03 | 10.17 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.94 | 14.50 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.98 | 9.83 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.88 | 6.83 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.69 | 1.83 | 27.69 |
November | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
December | 1.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 4.17 | 19.26 | 0.00 | 19.26 | 60.67 | 27.39 | 59.00 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 0.00 | 19.19 |
Maximum of Months | 1.67 | 19.32 | 0.00 | 19.32 | 15.33 | 28.03 | 14.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 3.50 | 27.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.93 | 5.50 | 27.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 2.83 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.51 | 3.67 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.38 | 3.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.40 | 4.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.68 | 6.17 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.91 | 7.67 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.93 | 14.00 | 26.93 |
November | 0.17 | 19.38 | 0.00 | 19.38 | 14.17 | 26.45 | 14.17 | 26.49 |
December | 0.33 | 19.24 | 0.00 | 19.24 | 2.50 | 26.81 | 2.50 | 27.29 |
Annual Sum or Average | 0.50 | 19.28 | 0.00 | 19.28 | 71.17 | 27.24 | 68.50 | 27.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.45 | 1.33 | 26.49 |
Maximum of Months | 0.33 | 19.38 | 0.00 | 19.38 | 14.67 | 27.93 | 14.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.17 | 19.37 | 0.00 | 19.37 | 1.00 | 26.48 | 1.00 | 27.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.78 | 1.33 | 27.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.38 | 4.00 | 28.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.32 | 5.50 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.25 | 4.50 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.03 | 6.17 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.29 | 4.83 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.19 | 4.67 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.21 | 3.00 | 28.22 |
November | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 1.17 | 19.33 | 0.00 | 19.33 | 60.67 | 28.03 | 35.00 | 28.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 | 0.00 | 19.29 |
Maximum of Months | 0.50 | 19.42 | 0.00 | 19.42 | 14.50 | 28.38 | 6.17 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.44 | 0.17 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
February | 4.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
March | 1.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
April | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.40 | 2.50 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.53 | 3.83 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.49 | 6.33 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.48 | 4.17 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
December | 8.50 | 17.86 | 0.67 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
Annual Sum or Average | 24.67 | 18.26 | 0.83 | 18.23 | 26.50 | 22.95 | 16.83 | 24.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 19.30 | 0.67 | 19.30 | 10.67 | 27.53 | 6.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
February | 4.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
March | 1.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
April | 0.17 | 19.34 | 0.00 | 19.34 | 3.83 | 27.51 | 3.83 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.01 | 11.17 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.11 | 10.67 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28.03 | 16.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.11 | 10.00 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.86 | 9.50 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.67 | 27.68 |
November | 2.67 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
December | 7.00 | 17.95 | 0.33 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
Annual Sum or Average | 21.50 | 18.34 | 0.33 | 18.29 | 69.83 | 25.70 | 61.83 | 26.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | 0.00 | 17.82 |
Maximum of Months | 7.00 | 19.34 | 0.33 | 19.34 | 19.33 | 28.11 | 16.00 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 2.50 | 18.88 | 0.00 | 18.88 | 3.67 | 24.13 | 3.67 | 25.46 |
March | 0.67 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
April | 0.17 | 19.39 | 0.00 | 19.39 | 3.33 | 27.22 | 3.17 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.56 | 4.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 4.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.59 | 7.83 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.77 | 6.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.01 | 7.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.16 | 7.67 | 28.20 |
November | 1.50 | 18.63 | 0.00 | 18.63 | 5.50 | 25.83 | 5.50 | 26.69 |
December | 5.00 | 18.38 | 0.00 | 18.38 | 0.33 | 18.93 | 0.33 | 19.43 |
Annual Sum or Average | 14.17 | 18.67 | 0.00 | 18.67 | 60.17 | 26.04 | 51.00 | 26.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 | 18.85 |
Maximum of Months | 5.00 | 19.39 | 0.00 | 19.39 | 11.00 | 28.16 | 7.83 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 2.33 | 18.82 | 0.00 | 18.82 | 0.33 | 19.89 | 0.33 | 20.73 |
March | 0.50 | 18.77 | 0.00 | 18.77 | 1.17 | 24.96 | 0.83 | 25.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.37 | 4.17 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.53 | 5.33 | 28.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.47 | 4.83 | 28.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.24 | 7.33 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.41 | 5.33 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.27 | 5.00 | 28.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.06 | 3.33 | 28.07 |
November | 1.50 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
December | 4.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 13.17 | 18.66 | 0.00 | 18.66 | 65.50 | 26.72 | 36.50 | 27.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 | 0.00 | 18.47 |
Maximum of Months | 4.83 | 18.82 | 0.00 | 18.82 | 16.67 | 28.53 | 7.33 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.99 | 30.83 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 119.00 | 28.06 | 104.17 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 163.00 | 28.04 | 135.00 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 119.00 | 28.06 | 104.17 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.93 | 20.17 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 27.95 | 81.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 120.50 | 27.95 | 101.83 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 27.95 | 81.67 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.04 | 8.67 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 28.02 | 54.33 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 79.50 | 28.03 | 63.00 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 28.04 | 54.33 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 | 29.40 | 125.00 | 29.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 116.33 | 28.71 | 100.00 | 28.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 585.33 | 30.26 | 443.50 | 30.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 839.17 | 29.90 | 668.50 | 29.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 585.33 | 30.26 | 443.50 | 30.35 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.33 | 24.00 | 96.17 | 24.88 | 0.00 | 24.88 |
February | 204.17 | 24.00 | 81.83 | 24.53 | 0.00 | 24.53 |
March | 233.83 | 24.00 | 62.33 | 24.45 | 0.00 | 24.45 |
April | 110.83 | 24.00 | 105.67 | 24.97 | 0.00 | 24.97 |
May | 30.67 | 24.00 | 218.00 | 24.98 | 14.17 | 24.93 |
June | 36.50 | 24.55 | 320.00 | 24.69 | 33.67 | 24.68 |
July | 270.50 | 24.45 | 494.17 | 24.57 | 270.50 | 24.54 |
August | 197.00 | 24.18 | 500.50 | 24.42 | 197.00 | 24.37 |
September | 176.00 | 24.69 | 450.17 | 24.64 | 176.00 | 24.65 |
October | 55.00 | 24.60 | 321.83 | 24.92 | 55.00 | 24.88 |
November | 24.33 | 24.00 | 156.33 | 25.62 | 0.00 | 25.62 |
December | 116.17 | 24.00 | 101.33 | 25.19 | 0.00 | 25.19 |
Annual Sum or Average | 1605.33 | 24.21 | 2908.33 | 24.72 | 746.33 | 24.68 |
Minimum of Months | 24.33 | 24.00 | 62.33 | 24.42 | 0.00 | 24.37 |
Maximum of Months | 270.50 | 24.69 | 500.50 | 25.62 | 270.50 | 25.62 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.33 | 23.96 | 59.50 | 24.34 | 0.00 | 24.34 |
February | 177.00 | 23.99 | 36.17 | 24.18 | 0.00 | 24.18 |
March | 130.17 | 24.00 | 43.33 | 24.46 | 0.00 | 24.46 |
April | 66.00 | 24.00 | 107.50 | 24.49 | 0.00 | 24.49 |
May | 31.00 | 24.00 | 208.00 | 24.50 | 18.33 | 24.47 |
June | 29.67 | 24.00 | 330.33 | 24.25 | 28.83 | 24.23 |
July | 261.00 | 24.26 | 495.17 | 24.25 | 261.00 | 24.25 |
August | 132.50 | 24.14 | 506.83 | 24.19 | 132.50 | 24.18 |
September | 148.00 | 24.50 | 437.17 | 24.41 | 148.00 | 24.42 |
October | 31.50 | 24.47 | 308.00 | 24.58 | 27.83 | 24.58 |
November | 41.50 | 24.00 | 134.67 | 24.91 | 0.00 | 24.91 |
December | 127.83 | 24.00 | 71.83 | 24.74 | 0.00 | 24.74 |
Annual Sum or Average | 1360.50 | 24.12 | 2738.50 | 24.38 | 616.50 | 24.37 |
Minimum of Months | 29.67 | 23.96 | 36.17 | 24.18 | 0.00 | 24.18 |
Maximum of Months | 261.00 | 24.50 | 506.83 | 24.91 | 261.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.67 | 23.63 | 0.00 | 23.63 | 0.00 | 23.63 |
February | 367.17 | 23.75 | 6.83 | 23.76 | 0.00 | 23.76 |
March | 370.67 | 23.85 | 1.83 | 23.86 | 0.00 | 23.86 |
April | 181.67 | 23.94 | 38.50 | 24.08 | 0.00 | 24.08 |
May | 65.00 | 23.96 | 172.83 | 24.33 | 15.00 | 24.31 |
June | 41.83 | 24.07 | 300.83 | 24.24 | 30.17 | 24.23 |
July | 290.00 | 24.15 | 491.67 | 24.18 | 290.00 | 24.18 |
August | 201.83 | 24.13 | 481.83 | 24.18 | 201.83 | 24.17 |
September | 154.33 | 24.27 | 414.67 | 24.27 | 148.00 | 24.28 |
October | 74.17 | 24.00 | 223.67 | 24.28 | 30.00 | 24.28 |
November | 279.67 | 23.80 | 42.33 | 23.88 | 0.00 | 23.88 |
December | 442.33 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
Annual Sum or Average | 2897.33 | 23.86 | 2175.00 | 24.04 | 715.00 | 24.05 |
Minimum of Months | 41.83 | 23.63 | 0.00 | 23.63 | 0.00 | 23.63 |
Maximum of Months | 442.33 | 24.27 | 491.67 | 24.33 | 290.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 22.36 | 80.00 | 22.09 | 80.00 | 21.89 |
February | 437.83 | 22.80 | 26.83 | 22.69 | 26.83 | 22.60 |
March | 463.33 | 23.31 | 2.00 | 23.30 | 2.00 | 23.29 |
April | 236.33 | 23.72 | 45.33 | 23.83 | 0.00 | 23.83 |
May | 90.83 | 23.87 | 194.17 | 24.21 | 17.67 | 24.20 |
June | 38.83 | 24.04 | 326.17 | 24.27 | 27.00 | 24.25 |
July | 279.17 | 24.24 | 494.50 | 24.26 | 279.17 | 24.26 |
August | 197.00 | 24.11 | 492.50 | 24.21 | 197.00 | 24.19 |
September | 183.17 | 24.23 | 411.83 | 24.26 | 161.33 | 24.28 |
October | 212.17 | 23.48 | 160.67 | 23.76 | 34.33 | 23.79 |
November | 409.17 | 22.83 | 35.67 | 22.81 | 16.83 | 22.75 |
December | 494.50 | 22.21 | 96.50 | 21.91 | 96.50 | 21.70 |
Annual Sum or Average | 3536.00 | 23.13 | 2366.17 | 23.45 | 938.67 | 23.43 |
Minimum of Months | 38.83 | 22.21 | 2.00 | 21.91 | 0.00 | 21.70 |
Maximum of Months | 494.50 | 24.24 | 494.50 | 24.27 | 279.17 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.67 | 22.64 | 16.17 | 22.59 | 16.17 | 22.55 |
February | 428.67 | 22.99 | 7.67 | 22.95 | 7.67 | 22.92 |
March | 469.83 | 23.46 | 2.00 | 23.45 | 2.00 | 23.44 |
April | 186.67 | 23.81 | 80.00 | 24.05 | 0.00 | 24.05 |
May | 64.17 | 24.03 | 247.83 | 24.48 | 12.83 | 24.48 |
June | 26.00 | 25.02 | 407.17 | 24.48 | 22.50 | 24.51 |
July | 193.50 | 24.82 | 496.00 | 24.56 | 193.50 | 24.62 |
August | 104.50 | 24.61 | 509.00 | 24.38 | 104.50 | 24.41 |
September | 134.83 | 24.52 | 405.50 | 24.41 | 120.83 | 24.45 |
October | 153.33 | 23.72 | 202.00 | 24.06 | 24.00 | 24.07 |
November | 412.67 | 23.28 | 8.50 | 23.30 | 0.00 | 23.30 |
December | 494.67 | 22.83 | 6.00 | 22.81 | 6.00 | 22.78 |
Annual Sum or Average | 3169.50 | 23.37 | 2387.83 | 23.80 | 510.00 | 23.86 |
Minimum of Months | 26.00 | 22.64 | 2.00 | 22.59 | 0.00 | 22.55 |
Maximum of Months | 500.67 | 25.02 | 509.00 | 24.56 | 193.50 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.17 | 22.63 | 19.33 | 22.62 | 13.83 | 22.57 |
February | 346.00 | 22.89 | 25.00 | 22.99 | 7.00 | 22.95 |
March | 325.50 | 23.13 | 38.50 | 23.32 | 3.17 | 23.31 |
April | 135.17 | 23.77 | 157.00 | 24.30 | 9.67 | 24.39 |
May | 66.83 | 25.15 | 345.67 | 24.68 | 36.17 | 24.82 |
June | 45.67 | 26.14 | 442.33 | 24.57 | 40.83 | 24.72 |
July | 190.00 | 24.98 | 496.33 | 24.60 | 190.00 | 24.68 |
August | 116.50 | 24.79 | 502.00 | 24.37 | 113.67 | 24.44 |
September | 129.33 | 24.95 | 431.67 | 24.56 | 117.33 | 24.65 |
October | 177.83 | 23.59 | 251.83 | 24.10 | 34.50 | 24.18 |
November | 332.33 | 22.98 | 34.67 | 23.17 | 0.00 | 23.17 |
December | 453.33 | 22.60 | 22.50 | 22.56 | 18.67 | 22.50 |
Annual Sum or Average | 2768.67 | 23.36 | 2766.83 | 23.89 | 584.83 | 23.99 |
Minimum of Months | 45.67 | 22.60 | 19.33 | 22.56 | 0.00 | 22.50 |
Maximum of Months | 453.33 | 26.14 | 502.00 | 24.68 | 190.00 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 296.00 | 22.77 | 95.17 | 23.17 | 19.67 | 23.15 |
February | 254.00 | 23.12 | 77.00 | 23.52 | 14.00 | 23.53 |
March | 277.83 | 23.36 | 59.17 | 23.66 | 3.50 | 23.67 |
April | 144.67 | 23.77 | 140.00 | 24.27 | 5.67 | 24.33 |
May | 82.00 | 24.13 | 265.00 | 24.47 | 18.83 | 24.51 |
June | 32.67 | 25.07 | 405.67 | 24.44 | 23.83 | 24.49 |
July | 193.67 | 24.79 | 495.50 | 24.53 | 193.67 | 24.59 |
August | 111.83 | 24.86 | 508.83 | 24.44 | 111.83 | 24.50 |
September | 136.00 | 25.03 | 441.00 | 24.63 | 125.50 | 24.72 |
October | 119.17 | 24.66 | 335.67 | 24.61 | 55.33 | 24.79 |
November | 221.17 | 23.53 | 172.17 | 24.08 | 20.00 | 24.21 |
December | 278.83 | 22.88 | 95.00 | 23.25 | 15.50 | 23.20 |
Annual Sum or Average | 2147.83 | 23.67 | 3090.17 | 24.17 | 607.33 | 24.25 |
Minimum of Months | 32.67 | 22.77 | 59.17 | 23.17 | 3.50 | 23.15 |
Maximum of Months | 296.00 | 25.07 | 508.83 | 24.63 | 193.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.17 | 22.83 | 32.50 | 22.97 | 3.33 | 22.96 |
February | 262.83 | 23.33 | 46.33 | 23.63 | 5.50 | 23.70 |
March | 135.50 | 23.80 | 124.50 | 24.32 | 10.33 | 24.43 |
April | 40.50 | 26.06 | 304.50 | 25.02 | 26.83 | 25.17 |
May | 48.67 | 25.56 | 362.00 | 24.77 | 33.17 | 24.90 |
June | 39.33 | 26.57 | 466.00 | 24.67 | 39.33 | 24.81 |
July | 208.17 | 25.28 | 497.00 | 24.81 | 208.17 | 24.92 |
August | 155.83 | 25.45 | 514.00 | 24.75 | 155.83 | 24.88 |
September | 136.67 | 25.15 | 447.67 | 24.69 | 131.67 | 24.78 |
October | 63.50 | 25.22 | 360.83 | 24.75 | 44.17 | 24.87 |
November | 137.50 | 23.81 | 157.17 | 24.29 | 9.50 | 24.38 |
December | 228.00 | 23.55 | 66.33 | 23.95 | 0.67 | 23.95 |
Annual Sum or Average | 1844.67 | 24.11 | 3378.83 | 24.46 | 668.50 | 24.59 |
Minimum of Months | 39.33 | 22.83 | 32.50 | 22.97 | 0.67 | 22.96 |
Maximum of Months | 388.17 | 26.57 | 514.00 | 25.02 | 208.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.19 | 219.67 | 20.99 | 219.67 | 20.89 |
February | 454.00 | 21.75 | 121.00 | 21.54 | 121.00 | 21.40 |
March | 514.00 | 22.47 | 58.00 | 22.31 | 58.00 | 22.18 |
April | 303.83 | 23.30 | 32.67 | 23.37 | 4.00 | 23.34 |
May | 105.00 | 23.75 | 210.50 | 24.27 | 11.00 | 24.26 |
June | 28.50 | 24.56 | 385.33 | 24.48 | 22.50 | 24.49 |
July | 226.00 | 24.63 | 495.83 | 24.52 | 226.00 | 24.55 |
August | 141.00 | 24.19 | 493.83 | 24.30 | 140.83 | 24.28 |
September | 178.67 | 24.13 | 371.33 | 24.22 | 136.83 | 24.25 |
October | 328.50 | 23.09 | 121.00 | 23.35 | 27.00 | 23.38 |
November | 469.33 | 21.87 | 84.17 | 21.66 | 84.17 | 21.51 |
December | 497.00 | 21.04 | 257.17 | 20.86 | 257.17 | 20.77 |
Annual Sum or Average | 3747.83 | 22.39 | 2850.50 | 22.83 | 1308.17 | 22.73 |
Minimum of Months | 28.50 | 21.04 | 32.67 | 20.86 | 4.00 | 20.77 |
Maximum of Months | 514.00 | 24.63 | 495.83 | 24.52 | 257.17 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.33 | 21.54 | 115.00 | 21.32 | 115.00 | 21.18 |
February | 350.33 | 22.14 | 59.33 | 22.02 | 51.67 | 21.88 |
March | 336.83 | 22.54 | 47.83 | 22.56 | 30.83 | 22.43 |
April | 154.50 | 23.44 | 119.83 | 24.12 | 11.17 | 24.21 |
May | 78.67 | 24.93 | 274.00 | 24.78 | 35.50 | 24.96 |
June | 47.50 | 26.25 | 362.83 | 24.80 | 43.00 | 24.97 |
July | 191.00 | 25.12 | 421.33 | 24.80 | 191.00 | 24.88 |
August | 131.50 | 24.89 | 420.67 | 24.57 | 130.33 | 24.63 |
September | 132.17 | 24.83 | 346.33 | 24.60 | 109.83 | 24.71 |
October | 211.17 | 22.97 | 170.50 | 23.64 | 27.00 | 23.71 |
November | 360.83 | 22.14 | 49.00 | 22.12 | 33.67 | 22.00 |
December | 422.00 | 21.45 | 145.67 | 21.22 | 145.67 | 21.08 |
Annual Sum or Average | 2838.83 | 22.73 | 2532.33 | 23.34 | 924.67 | 23.34 |
Minimum of Months | 47.50 | 21.45 | 47.83 | 21.22 | 11.17 | 21.08 |
Maximum of Months | 422.33 | 26.25 | 421.33 | 24.80 | 191.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.17 | 22.31 | 126.17 | 22.57 | 54.17 | 22.42 |
February | 276.50 | 22.65 | 86.67 | 22.98 | 34.67 | 22.91 |
March | 311.33 | 22.84 | 55.17 | 23.06 | 17.33 | 22.97 |
April | 196.50 | 23.35 | 110.17 | 23.86 | 6.83 | 23.88 |
May | 107.83 | 23.81 | 236.67 | 24.31 | 15.33 | 24.34 |
June | 34.50 | 24.58 | 376.00 | 24.45 | 23.50 | 24.48 |
July | 223.33 | 24.64 | 495.33 | 24.51 | 223.33 | 24.54 |
August | 147.67 | 24.59 | 497.67 | 24.43 | 147.50 | 24.46 |
September | 150.33 | 24.80 | 426.50 | 24.55 | 134.67 | 24.63 |
October | 171.67 | 24.04 | 304.83 | 24.38 | 55.83 | 24.55 |
November | 267.17 | 22.96 | 163.00 | 23.55 | 34.00 | 23.61 |
December | 313.17 | 22.29 | 125.17 | 22.45 | 61.67 | 22.25 |
Annual Sum or Average | 2515.17 | 23.26 | 3003.33 | 23.85 | 808.83 | 23.88 |
Minimum of Months | 34.50 | 22.29 | 55.17 | 22.45 | 6.83 | 22.25 |
Maximum of Months | 315.17 | 24.80 | 497.67 | 24.55 | 223.33 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.00 | 21.57 | 112.67 | 21.40 | 111.17 | 21.29 |
February | 398.17 | 21.97 | 72.17 | 21.92 | 61.83 | 21.81 |
March | 394.67 | 22.50 | 52.83 | 22.63 | 19.00 | 22.58 |
April | 203.50 | 23.37 | 141.17 | 23.92 | 13.17 | 24.02 |
May | 99.83 | 24.32 | 302.50 | 24.52 | 32.67 | 24.66 |
June | 38.83 | 25.72 | 426.00 | 24.60 | 34.00 | 24.69 |
July | 225.33 | 24.80 | 495.83 | 24.61 | 225.33 | 24.65 |
August | 145.83 | 24.67 | 504.33 | 24.48 | 145.50 | 24.51 |
September | 169.50 | 24.45 | 418.83 | 24.41 | 145.17 | 24.47 |
October | 242.17 | 23.24 | 223.50 | 23.78 | 37.00 | 23.86 |
November | 394.17 | 22.10 | 68.00 | 22.17 | 34.83 | 22.07 |
December | 470.67 | 21.57 | 133.17 | 21.36 | 133.17 | 21.22 |
Annual Sum or Average | 3241.67 | 22.68 | 2951.00 | 23.33 | 992.83 | 23.34 |
Minimum of Months | 38.83 | 21.57 | 52.83 | 21.36 | 13.17 | 21.22 |
Maximum of Months | 470.67 | 25.72 | 504.33 | 24.61 | 225.33 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 331.67 | 20.33 | 331.67 | 20.25 |
February | 454.00 | 21.12 | 245.33 | 20.88 | 245.33 | 20.77 |
March | 514.00 | 21.91 | 142.00 | 21.63 | 142.00 | 21.44 |
April | 321.00 | 22.90 | 53.83 | 22.93 | 19.83 | 22.83 |
May | 127.83 | 23.58 | 218.17 | 24.17 | 15.17 | 24.20 |
June | 38.17 | 25.03 | 400.67 | 24.51 | 28.83 | 24.56 |
July | 235.33 | 24.68 | 495.83 | 24.55 | 235.33 | 24.58 |
August | 166.67 | 24.26 | 486.67 | 24.31 | 159.50 | 24.31 |
September | 214.50 | 23.90 | 362.50 | 24.12 | 148.33 | 24.15 |
October | 362.33 | 22.56 | 105.67 | 22.88 | 29.83 | 22.91 |
November | 481.17 | 21.19 | 200.17 | 20.88 | 200.17 | 20.71 |
December | 497.00 | 20.37 | 380.00 | 20.24 | 380.00 | 20.18 |
Annual Sum or Average | 3914.00 | 21.96 | 3422.50 | 22.34 | 1936.00 | 22.18 |
Minimum of Months | 38.17 | 20.37 | 53.83 | 20.24 | 15.17 | 20.18 |
Maximum of Months | 514.00 | 25.03 | 495.83 | 24.55 | 380.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.97 | 227.83 | 20.67 | 227.83 | 20.51 |
February | 434.00 | 21.77 | 118.83 | 21.47 | 118.17 | 21.28 |
March | 399.50 | 22.29 | 71.83 | 22.11 | 66.17 | 21.93 |
April | 168.50 | 23.17 | 145.67 | 23.89 | 13.17 | 23.91 |
May | 93.17 | 24.71 | 343.33 | 24.62 | 41.00 | 24.78 |
June | 56.83 | 25.95 | 446.33 | 24.67 | 47.83 | 24.82 |
July | 226.50 | 24.98 | 496.17 | 24.70 | 226.50 | 24.77 |
August | 164.50 | 24.71 | 500.83 | 24.47 | 160.17 | 24.52 |
September | 179.33 | 24.56 | 415.33 | 24.46 | 146.83 | 24.55 |
October | 238.50 | 22.51 | 191.83 | 23.30 | 29.50 | 23.33 |
November | 446.50 | 21.75 | 115.50 | 21.52 | 103.67 | 21.32 |
December | 497.00 | 20.78 | 275.83 | 20.53 | 275.83 | 20.42 |
Annual Sum or Average | 3406.33 | 22.34 | 3349.33 | 22.90 | 1456.67 | 22.81 |
Minimum of Months | 56.83 | 20.78 | 71.83 | 20.53 | 13.17 | 20.42 |
Maximum of Months | 502.00 | 25.95 | 500.83 | 24.70 | 275.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.33 | 21.63 | 173.33 | 21.56 | 122.00 | 21.26 |
February | 304.50 | 21.98 | 120.83 | 22.06 | 81.17 | 21.83 |
March | 340.00 | 22.36 | 101.00 | 22.33 | 69.83 | 22.11 |
April | 223.33 | 22.98 | 121.50 | 23.46 | 19.83 | 23.41 |
May | 128.67 | 23.64 | 243.17 | 24.22 | 20.83 | 24.29 |
June | 47.50 | 24.74 | 390.83 | 24.47 | 28.33 | 24.53 |
July | 231.50 | 24.66 | 495.17 | 24.52 | 231.50 | 24.55 |
August | 165.67 | 24.49 | 489.67 | 24.40 | 158.17 | 24.43 |
September | 177.33 | 24.51 | 413.83 | 24.46 | 148.17 | 24.53 |
October | 209.67 | 23.39 | 277.67 | 24.05 | 52.50 | 24.22 |
November | 292.17 | 22.13 | 183.00 | 22.54 | 72.67 | 22.32 |
December | 360.33 | 21.61 | 172.00 | 21.45 | 138.00 | 21.18 |
Annual Sum or Average | 2835.00 | 22.78 | 3182.00 | 23.36 | 1143.00 | 23.29 |
Minimum of Months | 47.50 | 21.61 | 101.00 | 21.45 | 19.83 | 21.18 |
Maximum of Months | 360.33 | 24.74 | 495.17 | 24.52 | 231.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.33 | 21.11 | 221.17 | 20.83 | 220.17 | 20.68 |
February | 408.67 | 21.51 | 150.50 | 21.33 | 143.83 | 21.18 |
March | 403.33 | 22.02 | 116.00 | 21.99 | 84.50 | 21.82 |
April | 235.33 | 23.00 | 147.50 | 23.56 | 22.17 | 23.61 |
May | 128.17 | 23.98 | 302.50 | 24.39 | 33.50 | 24.53 |
June | 43.50 | 25.65 | 425.83 | 24.59 | 35.67 | 24.70 |
July | 232.67 | 24.80 | 495.83 | 24.61 | 232.67 | 24.66 |
August | 161.50 | 24.58 | 496.33 | 24.45 | 157.17 | 24.48 |
September | 198.33 | 24.18 | 399.83 | 24.30 | 157.00 | 24.36 |
October | 282.67 | 22.78 | 200.00 | 23.43 | 36.67 | 23.53 |
November | 412.17 | 21.57 | 136.33 | 21.43 | 111.17 | 21.24 |
December | 481.50 | 21.05 | 253.50 | 20.78 | 253.50 | 20.66 |
Annual Sum or Average | 3464.17 | 22.32 | 3345.33 | 22.89 | 1488.00 | 22.80 |
Minimum of Months | 43.50 | 21.05 | 116.00 | 20.78 | 22.17 | 20.66 |
Maximum of Months | 481.50 | 25.65 | 496.33 | 24.61 | 253.50 | 24.70 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 3.17 | 27.00 | 514.00 | 27.00 | 3.17 | 27.00 |
April | 108.00 | 27.34 | 485.00 | 27.13 | 108.00 | 27.16 |
May | 2.17 | 27.00 | 508.00 | 27.00 | 2.17 | 27.00 |
June | 64.33 | 27.00 | 496.00 | 27.00 | 64.33 | 27.00 |
July | 217.00 | 27.00 | 497.00 | 27.00 | 217.00 | 27.00 |
August | 375.83 | 27.35 | 514.00 | 27.29 | 375.83 | 27.31 |
September | 31.67 | 27.00 | 485.00 | 27.00 | 31.67 | 27.00 |
October | 34.67 | 27.00 | 502.00 | 27.00 | 34.67 | 27.00 |
November | 27.33 | 27.00 | 489.00 | 27.00 | 27.33 | 27.00 |
December | 14.50 | 27.00 | 497.00 | 27.00 | 14.50 | 27.00 |
Annual Sum or Average | 878.67 | 27.19 | 5943.00 | 27.05 | 878.67 | 27.07 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 375.83 | 27.35 | 514.00 | 27.29 | 375.83 | 27.31 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 482.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 453.50 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 23.33 | 27.55 | 485.00 | 27.09 | 23.33 | 27.11 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.00 | 27.00 | 496.00 | 27.00 | 1.00 | 27.00 |
July | 25.00 | 27.00 | 497.00 | 27.00 | 25.00 | 27.00 |
August | 127.67 | 27.72 | 514.00 | 27.30 | 127.67 | 27.37 |
September | 3.67 | 27.00 | 485.00 | 27.00 | 3.67 | 27.00 |
October | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
November | 1.33 | 27.00 | 489.00 | 27.00 | 1.33 | 27.00 |
December | 0.00 | 0.00 | 494.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 185.50 | 27.57 | 5919.67 | 27.04 | 185.50 | 27.05 |
Minimum of Months | 0.00 | 0.00 | 453.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 127.67 | 27.72 | 514.00 | 27.30 | 127.67 | 27.37 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.67 | 25.99 | 361.50 | 26.88 | 0.00 | 26.88 |
February | 0.00 | 0.00 | 367.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 494.67 | 27.00 | 0.00 | 27.00 |
April | 29.50 | 27.32 | 485.00 | 27.05 | 29.50 | 27.07 |
May | 3.83 | 27.00 | 508.00 | 27.00 | 3.83 | 27.00 |
June | 39.67 | 27.00 | 496.00 | 27.00 | 39.67 | 27.00 |
July | 98.50 | 27.00 | 497.00 | 27.00 | 98.50 | 27.00 |
August | 130.17 | 27.56 | 514.00 | 27.23 | 130.17 | 27.28 |
September | 18.67 | 27.00 | 485.00 | 27.00 | 18.67 | 27.00 |
October | 6.17 | 27.00 | 502.00 | 27.00 | 6.17 | 27.00 |
November | 2.17 | 27.00 | 452.67 | 27.00 | 2.17 | 27.00 |
December | 3.67 | 27.00 | 379.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 383.00 | 27.08 | 5542.17 | 27.02 | 328.67 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 361.50 | 26.88 | 0.00 | 26.88 |
Maximum of Months | 130.17 | 27.56 | 514.00 | 27.23 | 130.17 | 27.28 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.83 | 27.00 | 502.00 | 27.00 | 483.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.64 | 485.00 | 27.64 | 485.00 | 27.64 |
May | 472.17 | 27.00 | 508.00 | 27.00 | 472.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.40 | 497.00 | 27.40 | 497.00 | 27.40 |
August | 514.00 | 30.01 | 514.00 | 30.01 | 514.00 | 30.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5889.00 | 27.35 | 5943.00 | 27.35 | 5889.00 | 27.35 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.01 | 514.00 | 30.01 | 514.00 | 30.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00009 | 19.50326 | 0.75947 | 17.25936 |
February | 454.00000 | 27.00009 | 17.65743 | 0.79276 | 18.34635 |
March | 514.00000 | 27.00001 | 18.48470 | 0.85425 | 20.47035 |
April | 485.00000 | 27.08674 | 20.22634 | 0.94273 | 23.90023 |
May | 508.00000 | 27.00035 | 25.31126 | 0.22991 | 6.20585 |
June | 496.00000 | 27.00043 | 26.63696 | 0.29939 | 6.94534 |
July | 497.00000 | 27.00066 | 29.46143 | 0.36773 | 7.88071 |
August | 514.00000 | 27.25510 | 28.58758 | 0.48303 | 10.38355 |
September | 485.00000 | 27.00114 | 28.33367 | 0.26434 | 6.55352 |
October | 502.00000 | 27.00072 | 25.57355 | 0.91066 | 22.57159 |
November | 489.00000 | 27.00013 | 21.07126 | 0.87824 | 21.37196 |
December | 497.00000 | 27.00000 | 17.85985 | 0.85727 | 20.59551 |
Annual Sum or Average | 5943.00000 | 27.02944 | 23.26844 | 0.63515 | 15.16984 |
Minimum of Months | 454.00000 | 27.00000 | 17.65743 | 0.22991 | 6.20585 |
Maximum of Months | 514.00000 | 27.25510 | 29.46143 | 0.94273 | 23.90023 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00008 | 19.53503 | 0.66566 | 14.45240 |
February | 454.00000 | 27.00008 | 17.64704 | 0.68854 | 15.10879 |
March | 514.00000 | 27.00001 | 18.46297 | 0.74553 | 16.82149 |
April | 485.00000 | 27.06261 | 20.22114 | 0.83475 | 19.88044 |
May | 508.00000 | 27.00031 | 25.32493 | 0.17429 | 5.77664 |
June | 496.00000 | 27.00045 | 26.64920 | 0.23147 | 6.20899 |
July | 497.00000 | 27.00073 | 29.50098 | 0.27328 | 6.63182 |
August | 514.00000 | 27.19149 | 28.66735 | 0.32976 | 7.67172 |
September | 485.00000 | 27.00090 | 28.46106 | 0.20114 | 5.97611 |
October | 502.00000 | 27.00069 | 25.61424 | 0.83041 | 19.64439 |
November | 489.00000 | 27.00013 | 21.06246 | 0.75127 | 17.04562 |
December | 497.00000 | 27.00001 | 17.82516 | 0.68890 | 15.13959 |
Annual Sum or Average | 5943.00000 | 27.02195 | 23.29064 | 0.53301 | 12.49803 |
Minimum of Months | 454.00000 | 27.00001 | 17.64704 | 0.17429 | 5.77664 |
Maximum of Months | 514.00000 | 27.19149 | 29.50098 | 0.83475 | 19.88044 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.87302 | 19.85847 | 0.57267 | 12.37853 |
February | 454.00000 | 27.00008 | 17.67199 | 0.62898 | 13.57268 |
March | 514.00000 | 27.00001 | 18.47426 | 0.70312 | 15.63943 |
April | 485.00000 | 27.03544 | 20.24579 | 0.81715 | 19.35138 |
May | 508.00000 | 27.00033 | 25.32441 | 0.17900 | 5.91978 |
June | 496.00000 | 27.00045 | 26.64140 | 0.25112 | 6.47060 |
July | 497.00000 | 27.00073 | 29.48725 | 0.29539 | 6.94962 |
August | 514.00000 | 27.14473 | 28.68337 | 0.33195 | 7.76219 |
September | 485.00000 | 27.00093 | 28.44997 | 0.20302 | 6.09310 |
October | 502.00000 | 27.00069 | 25.64283 | 0.80701 | 18.92257 |
November | 489.00000 | 27.00013 | 21.07517 | 0.69085 | 15.35203 |
December | 497.00000 | 27.00001 | 17.83999 | 0.60764 | 13.06334 |
Annual Sum or Average | 5943.00000 | 27.00496 | 23.32619 | 0.50599 | 11.76416 |
Minimum of Months | 454.00000 | 26.87302 | 17.67199 | 0.17900 | 5.91978 |
Maximum of Months | 514.00000 | 27.14473 | 29.48725 | 0.81715 | 19.35138 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00035 | 28.86304 | 1.04987 | 28.27845 |
February | 454.00000 | 27.00013 | 22.49327 | 1.13892 | 32.35314 |
March | 514.00000 | 27.00005 | 18.88162 | 1.25041 | 37.75725 |
April | 485.00000 | 27.63927 | 19.75153 | 1.52278 | 51.94021 |
May | 508.00000 | 27.00213 | 28.31189 | 0.47309 | 9.76053 |
June | 496.00000 | 27.00441 | 31.16457 | 0.72136 | 16.00461 |
July | 497.00000 | 27.39899 | 35.09115 | 1.08769 | 30.67678 |
August | 514.00000 | 30.01138 | 30.94121 | 2.01034 | 73.27376 |
September | 485.00000 | 27.00241 | 36.31165 | 0.62789 | 13.41548 |
October | 502.00000 | 27.00203 | 31.63973 | 1.28723 | 39.64798 |
November | 489.00000 | 27.00129 | 23.12686 | 1.34090 | 42.41139 |
December | 497.00000 | 27.00058 | 19.44825 | 1.42140 | 46.66583 |
Annual Sum or Average | 5943.00000 | 27.34710 | 27.19823 | 1.16275 | 35.27342 |
Minimum of Months | 454.00000 | 27.00005 | 18.88162 | 0.47309 | 9.76053 |
Maximum of Months | 514.00000 | 30.01138 | 36.31165 | 2.01034 | 73.27376 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51082 | 18.33098 | 0.34048 | 8.03357 |
February | 454.00000 | 24.48014 | 16.23007 | 0.31295 | 7.48822 |
March | 514.00000 | 24.38439 | 15.71218 | 0.29270 | 7.12509 |
April | 485.00000 | 24.50027 | 20.32883 | 0.35591 | 8.10889 |
May | 508.00000 | 24.49541 | 30.27334 | -0.4211 | 9.76047 |
June | 496.00000 | 24.45972 | 36.95584 | -0.3758 | 8.89435 |
July | 497.00000 | 24.62991 | 54.90945 | -0.1865 | 6.95520 |
August | 514.00000 | 24.50094 | 50.31827 | -0.2379 | 7.07956 |
September | 485.00000 | 24.58179 | 47.43625 | -0.2362 | 7.59931 |
October | 502.00000 | 24.62762 | 35.93540 | 0.52091 | 11.53831 |
November | 489.00000 | 24.62087 | 20.82026 | 0.40481 | 9.12045 |
December | 497.00000 | 24.58442 | 15.64139 | 0.34896 | 8.12662 |
Annual Sum or Average | 5943.00000 | 24.53107 | 30.34994 | 0.09071 | 8.32406 |
Minimum of Months | 454.00000 | 24.38439 | 15.64139 | -0.4211 | 6.95520 |
Maximum of Months | 514.00000 | 24.62991 | 54.90945 | 0.52091 | 11.53831 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.28044 | 20.16309 | 0.29696 | 7.14292 |
February | 454.00000 | 24.26671 | 17.07108 | 0.28526 | 6.89847 |
March | 514.00000 | 24.25610 | 16.32570 | 0.29397 | 6.98707 |
April | 485.00000 | 24.28165 | 20.97894 | 0.34972 | 7.77720 |
May | 508.00000 | 24.27590 | 31.23732 | -0.4443 | 9.64828 |
June | 496.00000 | 24.20603 | 38.56618 | -0.3979 | 8.65979 |
July | 497.00000 | 24.23610 | 53.81966 | -0.2753 | 6.78719 |
August | 514.00000 | 24.20517 | 50.55981 | -0.2893 | 6.94569 |
September | 485.00000 | 24.33926 | 47.40762 | -0.3016 | 7.51422 |
October | 502.00000 | 24.37070 | 36.70230 | 0.47614 | 10.19248 |
November | 489.00000 | 24.38991 | 21.84340 | 0.36507 | 8.11488 |
December | 497.00000 | 24.39594 | 16.98220 | 0.31951 | 7.44994 |
Annual Sum or Average | 5943.00000 | 24.29166 | 31.08038 | 0.05398 | 7.85002 |
Minimum of Months | 454.00000 | 24.20517 | 16.32570 | -0.4443 | 6.78719 |
Maximum of Months | 514.00000 | 24.39594 | 53.81966 | 0.47614 | 10.19248 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70174 | 21.88597 | 0.13288 | 5.67511 |
February | 454.00000 | 23.84418 | 18.20244 | 0.15595 | 5.79889 |
March | 514.00000 | 23.98970 | 17.35222 | 0.19826 | 5.98285 |
April | 485.00000 | 24.13692 | 21.64417 | 0.28185 | 6.85793 |
May | 508.00000 | 24.18490 | 31.46091 | -0.5001 | 10.64192 |
June | 496.00000 | 24.17870 | 38.37644 | -0.4399 | 9.39928 |
July | 497.00000 | 24.19756 | 54.08690 | -0.3293 | 7.49175 |
August | 514.00000 | 24.19560 | 50.90170 | -0.3510 | 7.81622 |
September | 485.00000 | 24.23277 | 47.73040 | -0.3673 | 8.23801 |
October | 502.00000 | 24.15346 | 37.59445 | 0.39501 | 8.54312 |
November | 489.00000 | 23.99563 | 23.28884 | 0.23373 | 6.43673 |
December | 497.00000 | 23.70279 | 19.03474 | 0.11374 | 5.60926 |
Annual Sum or Average | 5943.00000 | 24.04409 | 31.90288 | -0.0419 | 7.38876 |
Minimum of Months | 454.00000 | 23.70174 | 17.35222 | -0.5001 | 5.60926 |
Maximum of Months | 514.00000 | 24.23277 | 54.08690 | 0.39501 | 10.64192 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38603 | 24.54939 | -0.1995 | 7.62038 |
February | 454.00000 | 22.84020 | 19.95216 | -0.1012 | 6.63371 |
March | 514.00000 | 23.38653 | 18.59876 | 0.03896 | 5.90708 |
April | 485.00000 | 23.95546 | 21.79402 | 0.23468 | 6.59081 |
May | 508.00000 | 24.16975 | 31.47384 | -0.4957 | 10.68970 |
June | 496.00000 | 24.21521 | 38.35938 | -0.4040 | 8.82609 |
July | 497.00000 | 24.27656 | 53.95160 | -0.2796 | 6.95774 |
August | 514.00000 | 24.23376 | 50.98026 | -0.3217 | 7.44918 |
September | 485.00000 | 24.22430 | 48.00023 | -0.3642 | 8.30078 |
October | 502.00000 | 23.83986 | 38.53532 | 0.31282 | 7.57915 |
November | 489.00000 | 23.03436 | 25.06884 | -0.0154 | 6.62204 |
December | 497.00000 | 22.21501 | 21.24173 | -0.2627 | 8.53198 |
Annual Sum or Average | 5943.00000 | 23.57024 | 32.80925 | -0.1559 | 7.65170 |
Minimum of Months | 454.00000 | 22.21501 | 18.59876 | -0.4957 | 5.90708 |
Maximum of Months | 514.00000 | 24.27656 | 53.95160 | 0.31282 | 10.68970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64803 | 21.71295 | -0.1339 | 6.34460 |
February | 454.00000 | 23.04428 | 18.29687 | -0.0506 | 6.07743 |
March | 514.00000 | 23.50785 | 16.84745 | 0.06731 | 5.74015 |
April | 485.00000 | 24.10163 | 20.67695 | 0.27837 | 7.09170 |
May | 508.00000 | 24.31992 | 30.18960 | -0.4230 | 9.71810 |
June | 496.00000 | 24.36570 | 37.31312 | -0.2955 | 7.64512 |
July | 497.00000 | 24.45980 | 52.54436 | -0.1591 | 6.50356 |
August | 514.00000 | 24.32444 | 49.57499 | -0.2362 | 6.89187 |
September | 485.00000 | 24.31560 | 46.75931 | -0.3195 | 8.07958 |
October | 502.00000 | 24.03850 | 36.95476 | 0.35961 | 8.24928 |
November | 489.00000 | 23.39780 | 22.90366 | 0.07281 | 5.82305 |
December | 497.00000 | 22.83873 | 18.67017 | -0.1061 | 6.09931 |
Annual Sum or Average | 5943.00000 | 23.78524 | 31.13627 | -0.0798 | 7.02946 |
Minimum of Months | 454.00000 | 22.64803 | 16.84745 | -0.4230 | 5.74015 |
Maximum of Months | 514.00000 | 24.45980 | 52.54436 | 0.35961 | 9.71810 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.79914 | 20.83427 | -0.0705 | 6.52888 |
February | 454.00000 | 23.23343 | 17.47358 | 0.03275 | 6.58892 |
March | 514.00000 | 23.54750 | 16.17988 | 0.12830 | 6.72911 |
April | 485.00000 | 24.14920 | 20.31217 | 0.35402 | 8.76188 |
May | 508.00000 | 24.40600 | 29.84659 | -0.2952 | 8.78051 |
June | 496.00000 | 24.37104 | 37.14093 | -0.2053 | 7.44993 |
July | 497.00000 | 24.45388 | 52.42274 | -0.0887 | 6.98257 |
August | 514.00000 | 24.26251 | 49.64218 | -0.1891 | 7.19444 |
September | 485.00000 | 24.38514 | 46.22443 | -0.2010 | 7.76347 |
October | 502.00000 | 24.00638 | 36.68656 | 0.39954 | 9.59740 |
November | 489.00000 | 23.38687 | 22.40579 | 0.10923 | 6.56577 |
December | 497.00000 | 22.76099 | 18.06552 | -0.0990 | 6.63943 |
Annual Sum or Average | 5943.00000 | 23.81728 | 30.70576 | -0.0115 | 7.47009 |
Minimum of Months | 454.00000 | 22.76099 | 16.17988 | -0.2952 | 6.52888 |
Maximum of Months | 514.00000 | 24.45388 | 52.42274 | 0.39954 | 9.59740 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.40918 | 19.75944 | 0.12055 | 7.94749 |
February | 454.00000 | 23.67566 | 16.72479 | 0.17031 | 7.79304 |
March | 514.00000 | 23.79932 | 15.82596 | 0.19830 | 7.31742 |
April | 485.00000 | 24.18198 | 20.34278 | 0.33762 | 8.39261 |
May | 508.00000 | 24.30090 | 30.16133 | -0.4146 | 9.90297 |
June | 496.00000 | 24.32940 | 37.39131 | -0.3114 | 7.86363 |
July | 497.00000 | 24.43274 | 52.60057 | -0.1624 | 6.63092 |
August | 514.00000 | 24.34030 | 49.42922 | -0.1898 | 6.78009 |
September | 485.00000 | 24.44814 | 46.03386 | -0.1751 | 7.48412 |
October | 502.00000 | 24.33107 | 35.76559 | 0.52012 | 12.18640 |
November | 489.00000 | 23.96539 | 21.30281 | 0.30202 | 9.08892 |
December | 497.00000 | 23.53791 | 16.84674 | 0.13652 | 7.75736 |
Annual Sum or Average | 5943.00000 | 24.06469 | 30.28788 | 0.04239 | 8.26487 |
Minimum of Months | 454.00000 | 23.40918 | 15.82596 | -0.4146 | 6.63092 |
Maximum of Months | 514.00000 | 24.44814 | 52.60057 | 0.52012 | 12.18640 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16715 | 19.93658 | 0.04624 | 6.42043 |
February | 454.00000 | 23.75218 | 16.58261 | 0.18830 | 7.05325 |
March | 514.00000 | 24.18378 | 15.24977 | 0.33507 | 8.26284 |
April | 485.00000 | 24.55355 | 19.63886 | 0.53319 | 12.13891 |
May | 508.00000 | 24.47100 | 29.63460 | -0.2242 | 8.21109 |
June | 496.00000 | 24.48080 | 36.82786 | -0.0906 | 6.99108 |
July | 497.00000 | 24.61473 | 51.81742 | 0.07235 | 7.14308 |
August | 514.00000 | 24.53241 | 48.69161 | 0.06302 | 7.06620 |
September | 485.00000 | 24.49334 | 45.93708 | -0.1057 | 7.12281 |
October | 502.00000 | 24.45944 | 35.48998 | 0.56477 | 12.80181 |
November | 489.00000 | 24.19884 | 20.86242 | 0.35655 | 8.58197 |
December | 497.00000 | 24.06549 | 16.22841 | 0.25983 | 7.26536 |
Annual Sum or Average | 5943.00000 | 24.25054 | 29.84424 | 0.16571 | 8.25664 |
Minimum of Months | 454.00000 | 23.16715 | 15.24977 | -0.2242 | 6.42043 |
Maximum of Months | 514.00000 | 24.61473 | 51.81742 | 0.56477 | 12.80181 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.18668 | 23.63926 | -0.5005 | 11.17070 |
February | 454.00000 | 21.75323 | 20.05784 | -0.3725 | 9.23863 |
March | 514.00000 | 22.47369 | 18.33145 | -0.1954 | 7.16904 |
April | 485.00000 | 23.62781 | 21.45729 | 0.13868 | 6.45260 |
May | 508.00000 | 24.20731 | 30.14603 | -0.4870 | 11.08892 |
June | 496.00000 | 24.37200 | 36.87374 | -0.3232 | 7.98082 |
July | 497.00000 | 24.46622 | 52.90158 | -0.1906 | 6.68727 |
August | 514.00000 | 24.31602 | 49.82118 | -0.2933 | 7.47266 |
September | 485.00000 | 24.15370 | 47.26384 | -0.4022 | 9.37254 |
October | 502.00000 | 23.41866 | 38.81782 | 0.19416 | 6.82191 |
November | 489.00000 | 21.94880 | 25.10475 | -0.2843 | 8.40317 |
December | 497.00000 | 21.04021 | 20.86405 | -0.5580 | 12.59635 |
Annual Sum or Average | 5943.00000 | 23.09057 | 32.19943 | -0.2727 | 8.70140 |
Minimum of Months | 454.00000 | 21.04021 | 18.33145 | -0.5580 | 6.45260 |
Maximum of Months | 514.00000 | 24.46622 | 52.90158 | 0.19416 | 12.59635 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.56324 | 22.16783 | -0.3875 | 9.57029 |
February | 385.00000 | 22.35631 | 18.09690 | -0.1982 | 7.98980 |
March | 433.00000 | 22.95781 | 16.54212 | -0.0365 | 7.17116 |
April | 410.00000 | 24.05489 | 20.08174 | 0.30467 | 8.74534 |
May | 430.00000 | 24.44383 | 29.20499 | -0.3116 | 9.68244 |
June | 418.00000 | 24.52668 | 35.94351 | -0.1845 | 7.75964 |
July | 422.00000 | 24.65599 | 51.82251 | -0.0481 | 7.49553 |
August | 433.00000 | 24.44460 | 48.78476 | -0.1684 | 7.56965 |
September | 410.00000 | 24.39051 | 45.83979 | -0.2346 | 8.73599 |
October | 427.00000 | 23.61877 | 37.50279 | 0.28532 | 8.65129 |
November | 417.00000 | 22.43455 | 23.25328 | -0.1377 | 7.57442 |
December | 422.00000 | 21.45291 | 19.26326 | -0.4384 | 10.54174 |
Annual Sum or Average | 5034.00000 | 23.41357 | 30.79825 | -0.1299 | 8.45928 |
Minimum of Months | 385.00000 | 21.45291 | 16.54212 | -0.4384 | 7.17116 |
Maximum of Months | 433.00000 | 24.65599 | 51.82251 | 0.30467 | 10.54174 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05687 | 20.38792 | 0.03067 | 8.70115 |
February | 454.00000 | 23.33469 | 17.41578 | 0.08294 | 8.30186 |
March | 514.00000 | 23.43719 | 16.37412 | 0.10005 | 7.49257 |
April | 485.00000 | 23.94853 | 20.66470 | 0.26048 | 7.89724 |
May | 508.00000 | 24.21418 | 30.05432 | -0.4646 | 11.01372 |
June | 496.00000 | 24.34036 | 36.94484 | -0.3380 | 8.23041 |
July | 497.00000 | 24.44989 | 52.91312 | -0.1900 | 6.80969 |
August | 514.00000 | 24.36253 | 49.53875 | -0.2294 | 7.17972 |
September | 485.00000 | 24.39317 | 46.13001 | -0.2086 | 7.93342 |
October | 502.00000 | 24.15228 | 36.25547 | 0.46806 | 11.62644 |
November | 489.00000 | 23.58618 | 21.96749 | 0.20418 | 9.34077 |
December | 497.00000 | 23.04974 | 17.79742 | 0.00623 | 8.66478 |
Annual Sum or Average | 5943.00000 | 23.86375 | 30.64006 | -0.0250 | 8.60317 |
Minimum of Months | 454.00000 | 23.04974 | 16.37412 | -0.4646 | 6.80969 |
Maximum of Months | 514.00000 | 24.44989 | 52.91312 | 0.46806 | 11.62644 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78159 | 22.01808 | -0.3199 | 9.05363 |
February | 454.00000 | 22.27309 | 18.67925 | -0.2056 | 8.13855 |
March | 514.00000 | 22.91324 | 16.94354 | -0.0274 | 7.23858 |
April | 485.00000 | 23.90220 | 20.57764 | 0.28648 | 8.63133 |
May | 508.00000 | 24.28617 | 29.77073 | -0.3411 | 10.07024 |
June | 496.00000 | 24.42514 | 36.60403 | -0.1931 | 7.56890 |
July | 497.00000 | 24.51852 | 52.50916 | -0.0696 | 6.92998 |
August | 514.00000 | 24.40576 | 49.36908 | -0.1478 | 7.21937 |
September | 485.00000 | 24.28287 | 46.54877 | -0.2363 | 8.28775 |
October | 502.00000 | 23.72075 | 37.41923 | 0.33657 | 9.13713 |
November | 489.00000 | 22.50657 | 23.38888 | -0.0986 | 7.65109 |
December | 497.00000 | 21.69751 | 19.30844 | -0.3630 | 9.71103 |
Annual Sum or Average | 5943.00000 | 23.40118 | 31.19107 | -0.1149 | 8.30315 |
Minimum of Months | 454.00000 | 21.69751 | 16.94354 | -0.3630 | 6.92998 |
Maximum of Months | 514.00000 | 24.51852 | 52.50916 | 0.33657 | 10.07024 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52305 | 24.69978 | -0.6967 | 17.18533 |
February | 454.00000 | 21.11878 | 20.67841 | -0.5527 | 13.30288 |
March | 514.00000 | 21.90896 | 18.76675 | -0.3453 | 9.56382 |
April | 485.00000 | 23.33295 | 21.57527 | 0.06894 | 6.95517 |
May | 508.00000 | 24.11960 | 30.24189 | -0.5054 | 12.18543 |
June | 496.00000 | 24.36678 | 37.02162 | -0.3033 | 7.93032 |
July | 497.00000 | 24.48107 | 53.06050 | -0.1631 | 6.77183 |
August | 514.00000 | 24.29666 | 50.10054 | -0.2835 | 7.67456 |
September | 485.00000 | 24.05602 | 47.80152 | -0.4251 | 10.51931 |
October | 502.00000 | 22.97365 | 39.80616 | 0.08750 | 7.04712 |
November | 489.00000 | 21.23802 | 25.93462 | -0.4784 | 12.60533 |
December | 497.00000 | 20.37259 | 21.72022 | -0.7623 | 19.42817 |
Annual Sum or Average | 5943.00000 | 22.74490 | 32.70893 | -0.3624 | 10.91181 |
Minimum of Months | 454.00000 | 20.37259 | 18.76675 | -0.7623 | 6.77183 |
Maximum of Months | 514.00000 | 24.48107 | 53.06050 | 0.08750 | 19.42817 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97008 | 23.60902 | -0.5533 | 13.77011 |
February | 454.00000 | 21.88069 | 19.33552 | -0.3293 | 9.93479 |
March | 514.00000 | 22.70686 | 17.23720 | -0.1066 | 7.84343 |
April | 485.00000 | 23.94176 | 20.32678 | 0.28862 | 8.74338 |
May | 508.00000 | 24.34487 | 29.61286 | -0.3098 | 9.69010 |
June | 496.00000 | 24.44196 | 36.66387 | -0.1613 | 7.46577 |
July | 497.00000 | 24.56956 | 52.49390 | -0.0287 | 7.38114 |
August | 514.00000 | 24.36705 | 49.67011 | -0.1493 | 7.47596 |
September | 485.00000 | 24.29288 | 46.64964 | -0.2310 | 8.80634 |
October | 502.00000 | 23.39933 | 38.24561 | 0.23742 | 8.58991 |
November | 489.00000 | 21.95459 | 24.49971 | -0.2719 | 9.56700 |
December | 497.00000 | 20.77984 | 20.72328 | -0.6268 | 15.50957 |
Annual Sum or Average | 5943.00000 | 23.14688 | 31.68453 | -0.1864 | 9.55771 |
Minimum of Months | 454.00000 | 20.77984 | 17.23720 | -0.6268 | 7.38114 |
Maximum of Months | 514.00000 | 24.56956 | 52.49390 | 0.28862 | 15.50957 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41522 | 21.61099 | -0.1573 | 10.90977 |
February | 454.00000 | 22.79466 | 18.23804 | -0.0746 | 9.69593 |
March | 514.00000 | 23.02630 | 16.87728 | -0.0179 | 8.35353 |
April | 485.00000 | 23.71632 | 20.78872 | 0.20394 | 8.16822 |
May | 508.00000 | 24.11688 | 30.17923 | -0.4854 | 12.21368 |
June | 496.00000 | 24.32920 | 37.10620 | -0.3197 | 8.25337 |
July | 497.00000 | 24.45744 | 53.10258 | -0.1646 | 6.93345 |
August | 514.00000 | 24.33623 | 49.85395 | -0.2211 | 7.44989 |
September | 485.00000 | 24.31600 | 46.66666 | -0.2242 | 8.73954 |
October | 502.00000 | 23.85594 | 37.02869 | 0.39236 | 11.17900 |
November | 489.00000 | 23.04758 | 22.78275 | 0.04760 | 10.13126 |
December | 497.00000 | 22.33413 | 18.90185 | -0.2026 | 11.23496 |
Annual Sum or Average | 5943.00000 | 23.56743 | 31.19562 | -0.1031 | 9.43898 |
Minimum of Months | 454.00000 | 22.33413 | 16.87728 | -0.4854 | 6.93345 |
Maximum of Months | 514.00000 | 24.45744 | 53.10258 | 0.39236 | 12.21368 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25535 | 22.99204 | -0.4776 | 12.72154 |
February | 454.00000 | 21.80196 | 19.28079 | -0.3438 | 10.39347 |
March | 514.00000 | 22.50192 | 17.34132 | -0.1409 | 8.49881 |
April | 485.00000 | 23.66148 | 20.68873 | 0.22997 | 8.86952 |
May | 508.00000 | 24.18645 | 29.91965 | -0.3622 | 11.24922 |
June | 496.00000 | 24.40423 | 36.81330 | -0.1783 | 7.76268 |
July | 497.00000 | 24.51845 | 52.73715 | -0.0477 | 7.20608 |
August | 514.00000 | 24.37057 | 49.70940 | -0.1432 | 7.60411 |
September | 485.00000 | 24.18798 | 47.10105 | -0.2568 | 9.29265 |
October | 502.00000 | 23.38763 | 38.17673 | 0.25547 | 8.99374 |
November | 489.00000 | 21.97032 | 24.13700 | -0.2482 | 9.84420 |
December | 497.00000 | 21.13958 | 20.18044 | -0.5323 | 13.92001 |
Annual Sum or Average | 5943.00000 | 23.12554 | 31.68500 | -0.1866 | 9.68932 |
Minimum of Months | 454.00000 | 21.13958 | 17.34132 | -0.5323 | 7.20608 |
Maximum of Months | 514.00000 | 24.51845 | 52.73715 | 0.25547 | 13.92001 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.644631E+10 | 74276.05 | 03-JAN-14:30 | 111.35 | 0.323188E+11 | 0.00 | 0.387651E+11 | 0.67 | 6.64 | 03-JAN-14:30 | 0.00 | 0.00 |
February | 0.192729E+11 | 106884.46 | 21-FEB-16:00 | 160.37 | 0.107248E+12 | 0.00 | 0.126521E+12 | 1.15 | 7.38 | 21-FEB-16:00 | 0.00 | 0.00 |
March | 0.437127E+11 | 142154.86 | 21-MAR-16:00 | 255.72 | 0.262024E+12 | 0.00 | 0.305737E+12 | 1.79 | 7.57 | 21-MAR-16:00 | 0.00 | 0.00 |
April | 0.990389E+11 | 168925.63 | 28-APR-13:00 | 447.58 | 0.649776E+12 | 0.00 | 0.748815E+12 | 3.58 | 7.57 | 03-APR-13:30 | 0.00 | 0.00 |
May | 0.149945E+12 | 169053.17 | 30-MAY-16:10 | 505.05 | 0.103001E+13 | 0.00 | 0.117995E+13 | 4.36 | 7.57 | 30-MAY-05:04 | 0.00 | 0.00 |
June | 0.177127E+12 | 174701.06 | 06-JUN-17:30 | 589.39 | 0.123626E+13 | 0.00 | 0.141339E+13 | 5.30 | 7.57 | 02-JUN-07:40 | 0.00 | 0.00 |
July | 0.193260E+12 | 191012.62 | 21-JUL-09:50 | 649.28 | 0.132690E+13 | 0.00 | 0.152016E+13 | 5.50 | 7.57 | 06-JUL-04:13 | 0.00 | 0.00 |
August | 0.182858E+12 | 167405.33 | 23-AUG-17:10 | 675.17 | 0.125708E+13 | 0.00 | 0.143993E+13 | 5.62 | 7.57 | 23-AUG-09:20 | 0.00 | 0.00 |
September | 0.145910E+12 | 169034.92 | 28-SEP-13:30 | 472.13 | 0.100799E+13 | 0.00 | 0.115390E+13 | 4.26 | 7.57 | 28-SEP-11:50 | 0.00 | 0.00 |
October | 0.941344E+11 | 160894.77 | 05-OCT-16:10 | 387.11 | 0.616854E+12 | 0.00 | 0.710989E+12 | 3.05 | 7.57 | 20-OCT-13:40 | 0.00 | 0.00 |
November | 0.325932E+11 | 136717.03 | 09-NOV-15:30 | 200.01 | 0.194471E+12 | 0.00 | 0.227065E+12 | 1.44 | 7.56 | 09-NOV-15:30 | 0.00 | 0.00 |
December | 0.329841E+10 | 52562.93 | 20-DEC-15:00 | 99.43 | 0.140745E+11 | 0.00 | 0.173729E+11 | 0.57 | 4.29 | 19-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.114760E+13 | 4552.58 | 0.773500E+13 | 0.00 | 0.888260E+13 | 3.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.329841E+10 | 52562.93 | 99.43 | 0.140745E+11 | 0.00 | 0.173729E+11 | 0.57 | 4.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.193260E+12 | 191012.62 | 675.17 | 0.132690E+13 | 0.00 | 0.152016E+13 | 5.62 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.877805E+10 | 111510.37 | 28-APR-12:20 | 26.17 | 0.627520E+11 | 0.00 | 0.715300E+11 | 0.26 | 7.42 | 21-APR-10:45 | 0.00 | 0.00 |
May | 0.268374E+11 | 111803.38 | 12-MAY-15:10 | 78.17 | 0.192186E+12 | 0.00 | 0.219023E+12 | 0.75 | 7.43 | 12-MAY-15:10 | 0.00 | 0.00 |
June | 0.584203E+11 | 121955.20 | 17-JUN-16:02 | 163.54 | 0.421290E+12 | 0.00 | 0.479710E+12 | 1.63 | 7.46 | 15-JUN-14:40 | 0.00 | 0.00 |
July | 0.728534E+11 | 191012.62 | 21-JUL-09:50 | 189.35 | 0.514969E+12 | 0.00 | 0.587822E+12 | 1.79 | 7.50 | 20-JUL-15:10 | 0.00 | 0.00 |
August | 0.548195E+11 | 152201.81 | 02-AUG-08:20 | 148.25 | 0.391255E+12 | 0.00 | 0.446075E+12 | 1.42 | 7.40 | 23-AUG-09:15 | 0.00 | 0.00 |
September | 0.425413E+11 | 149077.26 | 14-SEP-09:50 | 118.64 | 0.304205E+12 | 0.00 | 0.346746E+12 | 1.18 | 7.38 | 25-SEP-14:10 | 0.00 | 0.00 |
October | 0.108110E+11 | 112953.15 | 03-OCT-14:00 | 30.50 | 0.771721E+11 | 0.00 | 0.879831E+11 | 0.29 | 7.28 | 05-OCT-15:20 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.275061E+12 | 754.61 | 0.196383E+13 | 0.00 | 0.223889E+13 | 0.61 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.728534E+11 | 191012.62 | 189.35 | 0.514969E+12 | 0.00 | 0.587822E+12 | 1.79 | 7.50 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.667787E+10 | 744.00 | 49248.27 | 03-JAN-12:40 | 49185.44 | 12-JAN-16:30 | 18.88 | 18.35 | 15.30 |
February | 0.242267E+11 | 672.00 | 49248.27 | 04-FEB-14:30 | 244500.65 | 20-FEB-16:03 | 20.01 | 18.72 | 15.30 |
March | 0.487623E+11 | 744.00 | 49248.27 | 03-MAR-12:10 | 477573.22 | 21-MAR-16:00 | 22.22 | 19.55 | 15.30 |
April | 0.103478E+12 | 720.00 | 49248.27 | 01-APR-08:00 | 712747.96 | 29-APR-17:03 | 32.42 | 24.86 | 15.30 |
May | 0.116173E+12 | 744.00 | 49248.27 | 01-MAY-00:10 | 334247.96 | 31-MAY-23:20 | 28.06 | 25.57 | 15.30 |
June | 0.126928E+12 | 720.00 | 49248.27 | 01-JUN-00:03 | 541579.51 | 30-JUN-23:55 | 37.73 | 31.39 | 15.30 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 759485.79 | 20-JUL-15:00 | 45.23 | 33.90 | 15.30 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 762698.85 | 02-AUG-18:00 | 46.19 | 33.44 | 15.30 |
September | 0.111879E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 360802.10 | 01-SEP-10:30 | 27.63 | 25.14 | 15.30 |
October | 0.794326E+11 | 744.00 | 49248.27 | 01-OCT-07:53 | 508105.73 | 04-OCT-11:30 | 24.57 | 21.75 | 15.30 |
November | 0.374827E+11 | 720.00 | 49248.27 | 02-NOV-13:20 | 448445.57 | 03-NOV-16:00 | 21.30 | 18.99 | 15.30 |
December | 0.221981E+11 | 744.00 | 49248.27 | 07-DEC-14:10 | 354212.39 | 10-DEC-15:03 | 20.87 | 18.39 | 15.30 |
Annual Sum or Average | 0.941052E+12 | 8760.00 | 28.82 | 24.21 | 15.30 | ||||
Minimum of Months | 0.667787E+10 | 672.00 | 49248.27 | 49185.44 | 18.88 | 18.35 | 15.30 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 762698.85 | 46.19 | 33.90 | 15.30 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 10023195.60 | 17.67 | 361.50 | 03-JAN-13:50 | 580801.43 | 03-JAN-14:30 | 21.04 | 20.97 | 3.84 |
February | 44187824.07 | 70.47 | 599.02 | 21-FEB-16:00 | 908171.08 | 21-FEB-16:10 | 21.20 | 20.99 | 10.28 |
March | 0.170043E+09 | 157.02 | 1753.03 | 14-MAR-16:00 | 1230654.92 | 21-MAR-16:00 | 21.48 | 21.02 | 17.65 |
April | 0.115771E+10 | 323.04 | 18601.53 | 18-APR-15:30 | 1405638.48 | 27-APR-13:10 | 22.26 | 21.09 | 33.77 |
May | 0.641701E+10 | 459.69 | 18601.53 | 08-MAY-12:20 | 1379436.39 | 26-MAY-10:10 | 23.28 | 21.48 | 41.74 |
June | 0.145903E+11 | 525.50 | 18601.53 | 01-JUN-14:50 | 1366070.14 | 09-JUN-18:10 | 23.61 | 21.35 | 50.44 |
July | 0.306215E+11 | 635.94 | 18601.53 | 01-JUL-05:05 | 1474619.67 | 21-JUL-10:00 | 24.55 | 22.37 | 54.19 |
August | 0.229368E+11 | 589.25 | 18601.53 | 01-AUG-04:16 | 1330809.90 | 23-AUG-09:10 | 23.77 | 21.67 | 55.05 |
September | 0.160820E+11 | 449.26 | 18601.53 | 01-SEP-07:00 | 1393378.24 | 25-SEP-15:20 | 23.56 | 21.79 | 40.98 |
October | 0.498962E+10 | 330.66 | 18601.53 | 02-OCT-09:20 | 1348066.31 | 20-OCT-15:30 | 22.38 | 21.33 | 31.08 |
November | 0.194123E+09 | 120.93 | 2904.92 | 03-NOV-16:00 | 1183434.82 | 09-NOV-15:30 | 21.34 | 20.99 | 13.81 |
December | 1016328.12 | 7.00 | 84.98 | 08-DEC-14:10 | 291496.71 | 20-DEC-15:10 | 21.02 | 20.99 | 2.56 |
Annual Sum or Average | 0.972144E+11 | 3686.43 | 22.46 | 21.34 | 29.72 | ||||
Minimum of Months | 1016328.12 | 7.00 | 84.98 | 291496.71 | 21.02 | 20.97 | 2.56 | ||
Maximum of Months | 0.306215E+11 | 635.94 | 18601.53 | 1474619.67 | 24.55 | 22.37 | 55.05 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.04 | 21.04 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.20 | 21.20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.48 | 21.48 | 0.00 |
April | 0.205464E+09 | 18.25 | 18601.53 | 21-APR-13:50 | 1218491.80 | 21-APR-15:50 | 22.26 | 22.15 | 1.60 |
May | 0.211861E+10 | 64.17 | 18601.53 | 08-MAY-12:20 | 1228911.69 | 25-MAY-13:30 | 23.28 | 22.94 | 5.43 |
June | 0.621485E+10 | 144.37 | 18601.53 | 01-JUN-14:50 | 1308054.29 | 01-JUN-14:10 | 23.61 | 22.82 | 12.58 |
July | 0.138671E+11 | 207.08 | 18601.53 | 01-JUL-09:10 | 1474619.67 | 21-JUL-10:00 | 24.55 | 23.57 | 16.75 |
August | 0.920173E+10 | 139.22 | 18601.53 | 01-AUG-07:50 | 1226620.75 | 02-AUG-08:20 | 23.77 | 23.13 | 11.70 |
September | 0.655390E+10 | 110.86 | 18601.53 | 01-SEP-07:30 | 1299954.03 | 25-SEP-14:10 | 23.56 | 23.02 | 9.65 |
October | 0.174313E+10 | 28.00 | 18601.53 | 02-OCT-10:40 | 1205227.32 | 20-OCT-14:20 | 22.38 | 22.25 | 2.35 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.34 | 21.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.02 | 21.02 | 0.00 |
Annual Sum or Average | 0.399048E+11 | 711.95 | 22.46 | 22.17 | 5.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | ||
Maximum of Months | 0.138671E+11 | 207.08 | 18601.53 | 1474619.67 | 24.55 | 23.57 | 16.75 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.663891E+11 | 0.00 | 292.41 | 1344044.31 | 09-JAN-05:11 | 0.00 | 26.88 | 48.66 | 0.12 | 0.00 | 0.01 | 0.63 | 09-JAN-05:11 |
February | 0.390696E+11 | 0.00 | 216.89 | 1150083.89 | 09-FEB-05:01 | 0.00 | 25.01 | 42.90 | 0.08 | 0.00 | 0.01 | 0.54 | 09-FEB-05:01 |
March | 0.197616E+11 | 0.00 | 130.95 | 1145992.18 | 01-MAR-05:01 | 0.00 | 25.18 | 34.97 | 0.03 | 0.00 | 0.00 | 0.54 | 01-MAR-05:01 |
April | 0.117488E+10 | 0.00 | 20.24 | 626068.80 | 11-APR-05:02 | 0.00 | 24.15 | 25.75 | 0.00 | 0.00 | 0.00 | 0.29 | 11-APR-05:02 |
May | 105864.57 | 0.00 | 0.33 | 115.37 | 02-MAY-06:00 | 0.00 | 23.73 | 23.76 | 0.00 | 0.00 | 0.00 | 0.00 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 23.73 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 23.73 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 23.73 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 364537.30 | 0.00 | 0.50 | 325.98 | 25-SEP-05:50 | 0.00 | 23.73 | 23.77 | 0.00 | 0.00 | 0.00 | 0.00 | 25-SEP-05:50 |
October | 0.355912E+09 | 0.00 | 34.60 | 66463.86 | 25-OCT-05:03 | 0.00 | 22.43 | 25.21 | 0.00 | 0.00 | 0.00 | 0.03 | 25-OCT-05:03 |
November | 0.227152E+11 | 0.00 | 175.24 | 1394787.39 | 27-NOV-05:11 | 0.00 | 25.00 | 38.64 | 0.04 | 0.00 | 0.00 | 0.65 | 27-NOV-05:11 |
December | 0.889256E+11 | 0.00 | 335.80 | 1238762.04 | 26-DEC-05:01 | 0.00 | 25.58 | 50.27 | 0.16 | 0.00 | 0.02 | 0.58 | 26-DEC-05:01 |
Annual Sum or Average | 0.238392E+12 | 0.00 | 1206.95 | 0.00 | 24.40 | 32.05 | 0.04 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.889256E+11 | 0.00 | 335.80 | 1394787.39 | 0.00 | 26.88 | 50.27 | 0.16 | 0.00 | 0.02 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.88 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 20.01 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 22.22 | 22.22 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 32.42 | 32.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 28.06 | 28.06 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 37.73 | 37.73 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 45.23 | 45.23 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 46.19 | 46.19 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 27.63 | 27.63 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.57 | 24.57 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.30 | 21.30 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.87 | 20.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.82 | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.19 | 46.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.313937E+10 | 0.00 | 58.08 | 0.313937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51148.21 | 03-JAN-14:30 | 51148.21 | 03-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.106476E+11 | 0.00 | 123.53 | 0.106476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82745.02 | 21-FEB-15:00 | 82745.02 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.266127E+11 | 0.00 | 232.56 | 0.266127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100059.21 | 21-MAR-15:40 | 100059.21 | 21-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.743385E+11 | 0.00 | 428.32 | 0.743385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132281.06 | 21-APR-14:40 | 132281.06 | 21-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.108249E+12 | 0.00 | 482.09 | 0.108119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 166933.71 | 30-MAY-05:02 | 166933.71 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.148427E+12 | 0.00 | 563.82 | 0.147948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 168188.08 | 15-JUN-05:02 | 168188.08 | 15-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.179061E+12 | 0.00 | 618.49 | 0.152596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307151.84 | 21-JUL-04:11 | 172896.23 | 03-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.169649E+12 | 0.00 | 648.18 | 0.158795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263323.93 | 05-AUG-05:02 | 184677.81 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.116011E+12 | 0.00 | 452.68 | 0.108614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 269341.04 | 22-SEP-04:12 | 139025.98 | 13-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.656806E+11 | 0.00 | 364.52 | 0.636688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152602.46 | 02-OCT-05:02 | 152602.46 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.197779E+11 | 0.00 | 176.70 | 0.197779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95134.22 | 03-NOV-16:00 | 95134.22 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.149962E+10 | 0.00 | 47.15 | 0.149962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29449.25 | 20-DEC-15:00 | 29449.25 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923094E+12 | 0.00 | 4196.12 | 0.875756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.149962E+10 | 0.00 | 47.15 | 0.149962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29449.25 | 29449.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.179061E+12 | 0.00 | 648.18 | 0.158795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307151.84 | 184677.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.240568E+11 | 0.00 | 107.88 | 0.240568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 386451.01 | 12-JAN-15:10 | 386451.01 | 12-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 0.820405E+11 | 0.00 | 147.30 | 0.820405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 595718.39 | 21-FEB-16:00 | 595718.39 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.198652E+12 | 0.00 | 238.71 | 0.198652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 785414.82 | 21-MAR-16:00 | 785414.82 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.544898E+12 | 0.00 | 361.00 | 0.544898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1151159.63 | 21-APR-14:40 | 1151159.63 | 21-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.956922E+12 | 0.00 | 466.27 | 0.955881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1421958.93 | 30-MAY-05:02 | 1421958.93 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.127592E+13 | 0.00 | 493.93 | 0.127284E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1589350.87 | 08-JUN-05:03 | 1589350.87 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.140363E+13 | 0.00 | 503.02 | 0.121636E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2601361.98 | 22-JUL-05:03 | 1442422.12 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.123496E+13 | 0.00 | 505.18 | 0.117112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2388025.96 | 03-AUG-04:12 | 1512867.98 | 24-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.100094E+13 | 0.00 | 429.91 | 0.938879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2279057.40 | 22-SEP-04:12 | 1286759.33 | 13-SEP-04:12 | 0.00 | 0.00 | 0.00 |
October | 0.527279E+12 | 0.00 | 350.36 | 0.510767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1349520.18 | 05-OCT-05:03 | 1269987.22 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.146898E+12 | 0.00 | 186.27 | 0.146898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 766119.75 | 03-NOV-16:00 | 766119.75 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.986204E+10 | 0.00 | 93.56 | 0.986204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187655.69 | 20-DEC-15:00 | 187655.69 | 20-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740606E+13 | 0.00 | 3883.38 | 0.707225E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.986204E+10 | 0.00 | 93.56 | 0.986204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187655.69 | 187655.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.140363E+13 | 0.00 | 505.18 | 0.127284E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2601361.98 | 1589350.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.171071E+10 | 0.00 | 49.50 | 0.171071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34247.32 | 12-JAN-15:00 | 34247.32 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.700477E+10 | 0.00 | 111.16 | 0.700477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58167.55 | 20-FEB-15:52 | 58167.55 | 20-FEB-15:52 | 0.00 | 0.00 | 0.00 |
March | 0.183589E+11 | 0.00 | 211.59 | 0.183589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83212.67 | 21-MAR-16:00 | 83212.67 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.579875E+11 | 0.00 | 350.11 | 0.579875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133405.18 | 21-APR-14:40 | 133405.18 | 21-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.105098E+12 | 0.00 | 462.00 | 0.104989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 150772.59 | 30-MAY-15:00 | 150772.59 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.144505E+12 | 0.00 | 499.30 | 0.144208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 162786.81 | 15-JUN-14:40 | 162786.81 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.157299E+12 | 0.00 | 508.53 | 0.138001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281139.19 | 17-JUL-04:12 | 163137.73 | 03-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.136363E+12 | 0.00 | 508.48 | 0.130098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257758.16 | 03-AUG-05:03 | 173043.89 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.107119E+12 | 0.00 | 427.53 | 0.101362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251230.91 | 22-SEP-05:03 | 143736.10 | 20-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.531269E+11 | 0.00 | 340.15 | 0.516958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144849.96 | 03-OCT-14:00 | 132438.80 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.121347E+11 | 0.00 | 160.99 | 0.121347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77683.81 | 09-NOV-15:00 | 77683.81 | 09-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.588364E+09 | 0.00 | 30.08 | 0.588364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12790.80 | 23-DEC-15:00 | 12790.80 | 23-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.801296E+12 | 0.00 | 3659.42 | 0.768138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.588364E+09 | 0.00 | 30.08 | 0.588364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12790.80 | 12790.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.157299E+12 | 0.00 | 508.53 | 0.144208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281139.19 | 173043.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.132977E+10 | 0.00 | 26.64 | 0.132977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34443.83 | 03-JAN-15:00 | 34443.83 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.473085E+10 | 0.00 | 56.16 | 0.473085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57543.37 | 21-FEB-15:00 | 57543.37 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.128680E+11 | 0.00 | 141.76 | 0.128680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56880.91 | 21-MAR-16:00 | 56880.91 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.382977E+11 | 0.00 | 266.93 | 0.382977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84773.55 | 20-APR-05:03 | 84773.55 | 20-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.663555E+11 | 0.00 | 377.94 | 0.663136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152843.04 | 29-MAY-15:37 | 129453.12 | 29-MAY-15:37 | 0.00 | 0.00 | 0.00 |
June | 0.836771E+11 | 0.00 | 410.99 | 0.835703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131407.12 | 19-JUN-04:12 | 124365.21 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.972112E+11 | 0.00 | 416.82 | 0.861303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217753.16 | 09-JUL-18:16 | 125683.14 | 03-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.944098E+11 | 0.00 | 460.93 | 0.908657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182355.28 | 02-AUG-05:03 | 132797.03 | 20-AUG-16:40 | 0.00 | 0.00 | 0.00 |
September | 0.763854E+11 | 0.00 | 391.71 | 0.738102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189456.38 | 10-SEP-15:30 | 127300.52 | 17-SEP-16:34 | 0.00 | 0.00 | 0.00 |
October | 0.425616E+11 | 0.00 | 292.48 | 0.421428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136050.02 | 05-OCT-04:12 | 116657.03 | 02-OCT-04:03 | 0.00 | 0.00 | 0.00 |
November | 0.111115E+11 | 0.00 | 126.19 | 0.111097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68843.08 | 10-NOV-06:03 | 68843.08 | 10-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.229426E+09 | 0.00 | 11.25 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.84 | 11-DEC-05:11 | 18332.84 | 11-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529168E+12 | 0.00 | 2979.78 | 0.511398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.229426E+09 | 0.00 | 11.25 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.84 | 18332.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.972112E+11 | 0.00 | 460.93 | 0.908657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217753.16 | 132797.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101543E+11 | 0.547675E+10 | 727.50 | 0.911856E+10 | 0.103575E+10 | 0.00 | 0.03 | 03-JAN-17:00 | 0.00 | 15-JAN-11:00 | 5414.64 | 13-JAN-11:50 | 4912.11 | 31-JAN-22:25 | 543.95 | 13-JAN-11:00 | 2787.44 | 03-JAN-17:00 | 0.00 |
February | 0.256980E+11 | 0.112104E+11 | 656.69 | 0.250695E+11 | 0.628585E+09 | 0.00 | 0.41 | 20-FEB-16:00 | 0.00 | 28-FEB-01:00 | 128301.16 | 20-FEB-16:00 | 128301.16 | 20-FEB-16:00 | 1015.12 | 17-FEB-05:01 | 49260.22 | 20-FEB-16:00 | 0.00 |
March | 0.112760E+12 | 0.421446E+11 | 734.08 | 0.112448E+12 | 0.312115E+09 | 0.00 | 0.81 | 22-MAR-13:00 | 0.00 | 11-MAR-06:03 | 267878.53 | 21-MAR-16:00 | 267878.53 | 21-MAR-16:00 | 5063.57 | 11-MAR-16:00 | 105931.13 | 22-MAR-13:00 | 0.00 |
April | 0.539616E+12 | 0.197180E+12 | 720.00 | 0.522498E+12 | 0.171189E+11 | 0.00 | 1.00 | 01-APR-11:40 | 0.03 | 30-APR-23:55 | 410472.26 | 29-APR-17:10 | 396199.34 | 29-APR-12:20 | 103959.23 | 17-APR-01:55 | 158096.04 | 21-APR-15:00 | 0.00 |
May | 0.180490E+12 | 0.701734E+11 | 693.62 | 0.172468E+12 | 0.802247E+10 | 0.00 | 0.56 | 31-MAY-23:10 | 0.01 | 26-MAY-04:27 | 195342.30 | 31-MAY-23:10 | 195342.30 | 31-MAY-23:10 | 57957.45 | 24-MAY-12:10 | 72607.96 | 31-MAY-23:10 | 0.00 |
June | 0.500169E+12 | 0.191855E+12 | 712.62 | 0.457419E+12 | 0.427501E+11 | 0.00 | 0.82 | 30-JUN-23:33 | 0.01 | 29-JUN-04:43 | 353265.71 | 03-JUN-17:43 | 308823.23 | 30-JUN-24:00 | 138536.13 | 19-JUN-18:10 | 116970.61 | 30-JUN-23:20 | 0.00 |
July | 0.100828E+13 | 0.346586E+12 | 744.00 | 0.714642E+12 | 0.293633E+12 | 0.00 | 1.00 | 02-JUL-07:33 | 0.41 | 05-JUL-06:00 | 493319.77 | 20-JUL-15:00 | 392258.55 | 31-JUL-23:20 | 356296.74 | 20-JUL-21:53 | 158404.12 | 21-JUL-18:00 | 0.00 |
August | 0.111355E+13 | 0.376121E+12 | 744.00 | 0.831517E+12 | 0.282035E+12 | 0.00 | 1.00 | 01-AUG-00:05 | 0.15 | 31-AUG-23:07 | 467863.14 | 01-AUG-21:12 | 415259.36 | 27-AUG-12:27 | 298767.09 | 02-AUG-05:00 | 173681.25 | 07-AUG-16:10 | 0.00 |
September | 0.175296E+12 | 0.655103E+11 | 592.99 | 0.149452E+12 | 0.258440E+11 | 0.00 | 0.56 | 01-SEP-10:30 | 0.00 | 11-SEP-04:55 | 239126.63 | 01-SEP-10:30 | 141617.22 | 01-SEP-15:00 | 99100.34 | 01-SEP-10:30 | 75536.66 | 01-SEP-10:30 | 0.00 |
October | 0.173641E+12 | 0.610449E+11 | 613.79 | 0.145069E+12 | 0.285723E+11 | 0.00 | 0.76 | 04-OCT-11:30 | 0.00 | 06-OCT-20:20 | 325605.05 | 04-OCT-11:30 | 228814.20 | 03-OCT-14:00 | 134118.33 | 03-OCT-20:00 | 105581.42 | 04-OCT-11:30 | 0.00 |
November | 0.767010E+11 | 0.276972E+11 | 693.32 | 0.720714E+11 | 0.462965E+10 | 0.00 | 0.69 | 08-NOV-15:00 | 0.01 | 03-NOV-05:00 | 254750.03 | 03-NOV-16:00 | 241569.05 | 08-NOV-15:00 | 49188.55 | 03-NOV-11:50 | 87378.11 | 03-NOV-16:00 | 0.00 |
December | 0.548677E+11 | 0.206855E+11 | 744.00 | 0.530672E+11 | 0.180043E+10 | 0.00 | 0.58 | 20-DEC-15:00 | 0.02 | 13-DEC-01:00 | 182371.19 | 23-DEC-15:00 | 182371.19 | 23-DEC-15:00 | 12492.30 | 25-DEC-14:55 | 62299.37 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.397122E+13 | 0.141568E+13 | 8376.62 | 0.326484E+13 | 0.706383E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101543E+11 | 0.547675E+10 | 592.99 | 0.911856E+10 | 0.312115E+09 | 0.00 | 0.03 | 0.00 | 5414.64 | 4912.11 | 543.95 | 2787.44 | 0.00 | ||||||
Maximum of Months | 0.111355E+13 | 0.376121E+12 | 744.00 | 0.831517E+12 | 0.293633E+12 | 0.00 | 1.00 | 0.41 | 493319.77 | 415259.36 | 356296.74 | 173681.25 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.493147E+10 | 0.132884E+10 | 744.00 | 0.491787E+10 | 13600401.44 | 0.00 | 0.33 | 30-JAN-17:00 | 0.14 | 28-JAN-07:50 | 2703.51 | 02-JAN-17:00 | 2629.49 | 30-JAN-17:00 | 95.60 | 12-JAN-17:00 | 700.62 | 03-JAN-17:00 | 0.00 |
February | 0.937033E+10 | 0.243253E+10 | 672.00 | 0.935466E+10 | 15675323.54 | 0.00 | 0.58 | 19-FEB-17:13 | 0.38 | 01-FEB-07:10 | 4741.73 | 20-FEB-17:17 | 4741.73 | 20-FEB-17:17 | 220.28 | 13-FEB-16:10 | 1424.32 | 21-FEB-17:00 | 0.00 |
March | 0.158150E+11 | 0.401764E+10 | 744.00 | 0.158115E+11 | 3508917.22 | 0.00 | 0.88 | 31-MAR-24:00 | 0.59 | 01-MAR-07:05 | 7738.93 | 31-MAR-24:00 | 7738.93 | 31-MAR-24:00 | 112.47 | 11-MAR-10:20 | 2203.37 | 21-MAR-16:00 | 0.00 |
April | 0.205816E+11 | 0.595370E+10 | 720.00 | 0.205644E+11 | 17204376.68 | 0.00 | 1.00 | 01-APR-12:40 | 0.33 | 30-APR-24:00 | 8533.49 | 22-APR-17:55 | 8533.49 | 22-APR-17:55 | 155.01 | 18-APR-10:20 | 3308.71 | 21-APR-15:00 | 0.00 |
May | 0.645726E+10 | 0.212368E+10 | 744.00 | 0.639522E+10 | 62036415.54 | 0.00 | 0.51 | 31-MAY-23:43 | 0.22 | 06-MAY-06:05 | 4146.67 | 31-MAY-24:00 | 4137.31 | 31-MAY-24:00 | 258.35 | 24-MAY-13:00 | 1402.83 | 31-MAY-23:20 | 0.00 |
June | 0.113381E+11 | 0.414859E+10 | 720.00 | 0.112266E+11 | 0.111526E+09 | 0.00 | 0.74 | 30-JUN-23:55 | 0.46 | 13-JUN-06:10 | 5983.39 | 30-JUN-23:55 | 5983.39 | 30-JUN-23:55 | 324.12 | 28-JUN-11:00 | 2386.64 | 02-JUN-16:00 | 0.00 |
July | 0.169686E+11 | 0.621870E+10 | 744.00 | 0.166445E+11 | 0.324118E+09 | 0.00 | 0.94 | 31-JUL-23:30 | 0.68 | 05-JUL-06:10 | 7907.73 | 31-JUL-24:00 | 7901.87 | 31-JUL-24:00 | 616.20 | 20-JUL-15:00 | 3136.19 | 03-JUL-16:00 | 0.00 |
August | 0.219816E+11 | 0.767341E+10 | 744.00 | 0.217116E+11 | 0.270017E+09 | 0.00 | 1.00 | 01-AUG-10:00 | 0.33 | 31-AUG-24:00 | 8723.41 | 08-AUG-17:00 | 8513.63 | 27-AUG-20:33 | 472.35 | 01-AUG-20:55 | 3627.78 | 07-AUG-16:10 | 0.00 |
September | 0.647558E+10 | 0.206622E+10 | 720.00 | 0.625878E+10 | 0.216794E+09 | 0.00 | 0.48 | 30-SEP-24:00 | 0.22 | 30-SEP-06:40 | 4100.80 | 30-SEP-24:00 | 4100.80 | 30-SEP-24:00 | 372.95 | 22-SEP-09:10 | 1261.51 | 01-SEP-16:00 | 0.00 |
October | 0.113754E+11 | 0.312441E+10 | 744.00 | 0.112119E+11 | 0.163506E+09 | 0.00 | 0.68 | 31-OCT-24:00 | 0.43 | 25-OCT-07:00 | 5906.74 | 31-OCT-24:00 | 5906.74 | 31-OCT-24:00 | 390.09 | 04-OCT-10:00 | 1960.66 | 03-OCT-14:10 | 0.00 |
November | 0.153572E+11 | 0.376760E+10 | 720.00 | 0.153169E+11 | 40383935.65 | 0.00 | 0.79 | 09-NOV-16:50 | 0.60 | 28-NOV-07:10 | 6845.62 | 09-NOV-16:50 | 6737.90 | 09-NOV-16:50 | 246.52 | 02-NOV-15:50 | 2090.29 | 03-NOV-16:00 | 0.00 |
December | 0.205152E+11 | 0.484953E+10 | 744.00 | 0.205091E+11 | 6164393.29 | 0.00 | 0.95 | 17-DEC-16:43 | 0.78 | 05-DEC-07:05 | 8348.47 | 17-DEC-16:47 | 8348.47 | 17-DEC-16:47 | 91.04 | 14-DEC-16:00 | 2122.56 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.161168E+12 | 0.477049E+11 | 8760.00 | 0.159923E+12 | 0.124454E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.493147E+10 | 0.132884E+10 | 672.00 | 0.491787E+10 | 3508917.22 | 0.00 | 0.33 | 0.14 | 2703.51 | 2629.49 | 91.04 | 700.62 | 0.00 | ||||||
Maximum of Months | 0.219816E+11 | 0.767341E+10 | 744.00 | 0.217116E+11 | 0.324118E+09 | 0.00 | 1.00 | 0.78 | 8723.41 | 8533.49 | 616.20 | 3627.78 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.326242E+11 | 0.905275E+10 | 744.00 | 0.324971E+11 | 0.127085E+09 | 0.00 | 0.31 | 30-JAN-17:00 | 0.06 | 28-JAN-07:10 | 23756.19 | 12-JAN-16:50 | 23509.16 | 30-JAN-17:00 | 926.47 | 12-JAN-17:00 | 6315.16 | 03-JAN-17:00 | 0.00 |
February | 0.787327E+11 | 0.206921E+11 | 672.00 | 0.785782E+11 | 0.154485E+09 | 0.00 | 0.57 | 21-FEB-17:00 | 0.31 | 02-FEB-07:10 | 43343.64 | 21-FEB-17:00 | 43343.64 | 21-FEB-17:00 | 2165.36 | 13-FEB-16:30 | 13252.26 | 21-FEB-17:00 | 0.00 |
March | 0.142371E+12 | 0.364592E+11 | 744.00 | 0.142336E+12 | 35299479.29 | 0.00 | 0.86 | 31-MAR-23:40 | 0.53 | 01-MAR-07:05 | 71752.19 | 31-MAR-23:40 | 71752.19 | 31-MAR-23:40 | 1113.08 | 11-MAR-10:20 | 20759.47 | 21-MAR-16:00 | 0.00 |
April | 0.193166E+12 | 0.560965E+11 | 720.00 | 0.192993E+12 | 0.173302E+09 | 0.00 | 1.00 | 01-APR-13:40 | 0.30 | 30-APR-24:00 | 80802.46 | 28-APR-16:00 | 80771.12 | 26-APR-17:50 | 1549.04 | 18-APR-11:00 | 31509.53 | 21-APR-15:00 | 0.00 |
May | 0.594215E+11 | 0.196614E+11 | 744.00 | 0.588093E+11 | 0.612146E+09 | 0.00 | 0.52 | 31-MAY-23:33 | 0.19 | 06-MAY-06:05 | 40120.61 | 31-MAY-24:00 | 40052.32 | 31-MAY-24:00 | 2576.08 | 24-MAY-13:00 | 13544.98 | 31-MAY-23:20 | 0.00 |
June | 0.107878E+12 | 0.394876E+11 | 720.00 | 0.106771E+12 | 0.110763E+10 | 0.00 | 0.75 | 30-JUN-23:55 | 0.45 | 29-JUN-06:10 | 58177.32 | 30-JUN-23:55 | 58177.32 | 30-JUN-23:55 | 3232.18 | 28-JUN-11:00 | 22774.93 | 02-JUN-16:00 | 0.00 |
July | 0.161515E+12 | 0.591777E+11 | 744.00 | 0.158282E+12 | 0.323258E+10 | 0.00 | 0.95 | 31-JUL-23:30 | 0.68 | 05-JUL-06:10 | 76071.92 | 31-JUL-24:00 | 76009.74 | 31-JUL-24:00 | 6120.74 | 20-JUL-15:00 | 29852.83 | 03-JUL-16:00 | 0.00 |
August | 0.207371E+12 | 0.725502E+11 | 744.00 | 0.204668E+12 | 0.270263E+10 | 0.00 | 1.00 | 01-AUG-10:00 | 0.30 | 31-AUG-24:00 | 82829.70 | 08-AUG-17:00 | 80521.20 | 31-AUG-18:10 | 4652.04 | 01-AUG-20:55 | 34538.96 | 07-AUG-16:10 | 0.00 |
September | 0.590833E+11 | 0.189644E+11 | 720.00 | 0.569499E+11 | 0.213344E+10 | 0.00 | 0.47 | 30-SEP-23:50 | 0.19 | 30-SEP-06:40 | 38209.92 | 30-SEP-23:50 | 38209.92 | 30-SEP-23:50 | 3666.33 | 22-SEP-09:10 | 11744.20 | 19-SEP-16:00 | 0.00 |
October | 0.102798E+12 | 0.284539E+11 | 744.00 | 0.101188E+12 | 0.161035E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.38 | 25-OCT-07:00 | 53991.54 | 31-OCT-24:00 | 53991.54 | 31-OCT-24:00 | 3874.38 | 04-OCT-10:00 | 18547.79 | 03-OCT-14:10 | 0.00 |
November | 0.135228E+12 | 0.335062E+11 | 720.00 | 0.134827E+12 | 0.400357E+09 | 0.00 | 0.78 | 09-NOV-16:50 | 0.51 | 28-NOV-07:10 | 64551.65 | 09-NOV-16:50 | 63476.81 | 09-NOV-16:50 | 2427.77 | 02-NOV-15:50 | 19669.69 | 03-NOV-16:00 | 0.00 |
December | 0.179164E+12 | 0.428508E+11 | 744.00 | 0.179101E+12 | 62942399.57 | 0.00 | 0.93 | 20-DEC-16:40 | 0.69 | 27-DEC-07:10 | 77950.28 | 15-DEC-16:50 | 77950.28 | 15-DEC-16:50 | 910.53 | 14-DEC-16:00 | 19735.11 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.145935E+13 | 0.436953E+12 | 8760.00 | 0.144700E+13 | 0.123522E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.326242E+11 | 0.905275E+10 | 672.00 | 0.324971E+11 | 35299479.29 | 0.00 | 0.31 | 0.06 | 23756.19 | 23509.16 | 910.53 | 6315.16 | 0.00 | ||||||
Maximum of Months | 0.207371E+12 | 0.725502E+11 | 744.00 | 0.204668E+12 | 0.323258E+10 | 0.00 | 1.00 | 0.69 | 82829.70 | 80771.12 | 6120.74 | 34538.96 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.179570E+10 | 0.512343E+09 | 574.68 | 0.178466E+10 | 11044875.34 | 0.00 | 0.30 | 12-JAN-16:40 | 0.00 | 01-JAN-00:45 | 2393.90 | 12-JAN-16:50 | 2304.02 | 12-JAN-16:40 | 92.40 | 12-JAN-17:00 | 629.08 | 03-JAN-17:00 | 0.00 |
February | 0.672875E+10 | 0.179554E+10 | 672.00 | 0.671366E+10 | 15089202.39 | 0.00 | 0.56 | 21-FEB-17:00 | 0.19 | 02-FEB-07:10 | 4342.18 | 21-FEB-17:00 | 4342.18 | 21-FEB-17:00 | 214.62 | 13-FEB-17:00 | 1330.41 | 21-FEB-17:00 | 0.00 |
March | 0.133783E+11 | 0.346416E+10 | 744.00 | 0.133749E+11 | 3456890.32 | 0.00 | 0.82 | 31-MAR-23:20 | 0.43 | 02-MAR-07:10 | 6896.93 | 31-MAR-23:20 | 6896.93 | 31-MAR-23:20 | 109.91 | 11-MAR-10:20 | 2096.12 | 21-MAR-16:00 | 0.00 |
April | 0.190763E+11 | 0.558368E+10 | 720.00 | 0.190591E+11 | 17250039.35 | 0.00 | 1.00 | 01-APR-14:40 | 0.29 | 30-APR-24:00 | 8207.61 | 28-APR-16:00 | 8187.76 | 30-APR-19:03 | 155.36 | 18-APR-11:00 | 3220.97 | 21-APR-15:00 | 0.00 |
May | 0.592297E+10 | 0.197469E+10 | 744.00 | 0.586170E+10 | 61276339.01 | 0.00 | 0.51 | 31-MAY-23:55 | 0.14 | 02-MAY-06:05 | 4051.74 | 31-MAY-24:00 | 4043.55 | 31-MAY-24:00 | 260.50 | 24-MAY-13:00 | 1369.04 | 31-MAY-23:20 | 0.00 |
June | 0.109120E+11 | 0.400579E+10 | 720.00 | 0.108011E+11 | 0.110883E+09 | 0.00 | 0.74 | 30-JUN-23:20 | 0.43 | 29-JUN-06:10 | 5802.67 | 30-JUN-23:55 | 5802.67 | 30-JUN-23:55 | 323.76 | 28-JUN-11:00 | 2331.75 | 14-JUN-16:00 | 0.00 |
July | 0.163163E+11 | 0.599261E+10 | 744.00 | 0.159929E+11 | 0.323359E+09 | 0.00 | 0.94 | 31-JUL-23:30 | 0.66 | 05-JUL-06:10 | 7628.00 | 31-JUL-24:00 | 7621.65 | 31-JUL-24:00 | 612.41 | 20-JUL-15:00 | 3114.04 | 02-JUL-16:00 | 0.00 |
August | 0.208498E+11 | 0.732335E+10 | 744.00 | 0.205789E+11 | 0.270892E+09 | 0.00 | 1.00 | 01-AUG-11:20 | 0.29 | 31-AUG-24:00 | 8439.08 | 08-AUG-17:00 | 8207.43 | 27-AUG-20:05 | 464.54 | 01-AUG-20:55 | 3530.91 | 07-AUG-16:10 | 0.00 |
September | 0.587118E+10 | 0.189865E+10 | 720.00 | 0.565761E+10 | 0.213568E+09 | 0.00 | 0.45 | 30-SEP-23:20 | 0.14 | 30-SEP-07:00 | 3667.65 | 30-SEP-23:20 | 3667.65 | 30-SEP-23:20 | 365.64 | 22-SEP-09:10 | 1216.70 | 19-SEP-16:00 | 0.00 |
October | 0.982794E+10 | 0.274959E+10 | 744.00 | 0.966752E+10 | 0.160415E+09 | 0.00 | 0.62 | 05-OCT-17:00 | 0.31 | 25-OCT-06:50 | 5087.59 | 31-OCT-23:20 | 5087.59 | 31-OCT-23:20 | 387.98 | 04-OCT-10:00 | 1891.26 | 03-OCT-14:10 | 0.00 |
November | 0.122928E+11 | 0.308705E+10 | 720.00 | 0.122530E+11 | 39805474.34 | 0.00 | 0.77 | 09-NOV-16:50 | 0.34 | 27-NOV-05:11 | 6502.09 | 09-NOV-16:50 | 6394.54 | 09-NOV-16:50 | 242.82 | 02-NOV-15:50 | 1983.27 | 03-NOV-16:00 | 0.00 |
December | 0.161471E+11 | 0.391932E+10 | 744.00 | 0.161409E+11 | 6217142.54 | 0.00 | 0.90 | 20-DEC-16:40 | 0.55 | 26-DEC-04:25 | 7738.19 | 15-DEC-16:50 | 7738.19 | 15-DEC-16:50 | 91.00 | 14-DEC-16:00 | 1945.67 | 20-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.139119E+12 | 0.423068E+11 | 8590.67 | 0.137886E+12 | 0.123326E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.179570E+10 | 0.512343E+09 | 574.68 | 0.178466E+10 | 3456890.32 | 0.00 | 0.30 | 0.00 | 2393.90 | 2304.02 | 91.00 | 629.08 | 0.00 | ||||||
Maximum of Months | 0.208498E+11 | 0.732335E+10 | 744.00 | 0.205789E+11 | 0.323359E+09 | 0.00 | 1.00 | 0.66 | 8439.08 | 8207.43 | 612.41 | 3530.91 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 7.32 | 673.18 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 35.91 | 597.43 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 88.17 | 501.89 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 198.49 | 288.77 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 354.08 | 162.16 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 507.59 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 465.68 | 66.00 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 356.13 | 94.42 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 268.70 | 192.86 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 126.11 | 325.30 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 20.63 | 583.76 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 4.43 | 766.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 203.64 | 360.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 4.43 | 66.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 507.59 | 766.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 7.32 | 673.18 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 35.91 | 597.43 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 88.17 | 501.89 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 198.49 | 288.77 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 354.08 | 162.16 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 507.59 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 465.68 | 66.00 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 356.13 | 94.42 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 268.70 | 192.86 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 126.11 | 325.30 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 20.63 | 583.76 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 4.43 | 766.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 203.64 | 360.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 4.43 | 66.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 507.59 | 766.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 7.32 | 673.18 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 35.91 | 597.43 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 88.17 | 501.89 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 198.49 | 288.77 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 354.08 | 162.16 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 507.59 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 465.68 | 66.00 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 356.13 | 94.42 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 268.70 | 192.86 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 126.11 | 325.30 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 20.63 | 583.76 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 4.43 | 766.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 203.64 | 360.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 4.43 | 66.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 507.59 | 766.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 7.32 | 673.18 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 35.91 | 597.43 | 0.00 | 0.00 | 0.00 |
March | 164.30 | 0.00 | 164.30 | 88.17 | 501.89 | 0.00 | 0.00 | 0.00 |
April | 189.70 | 1.49 | 188.21 | 198.49 | 288.77 | 0.00 | 0.00 | 0.00 |
May | 224.99 | 16.27 | 208.72 | 354.08 | 162.16 | 0.00 | 0.00 | 0.00 |
June | 239.24 | 29.45 | 209.79 | 507.59 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 221.10 | 21.52 | 199.58 | 465.68 | 66.00 | 0.00 | 0.00 | 0.00 |
August | 186.44 | 3.81 | 182.63 | 356.13 | 94.42 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.62 | 268.70 | 192.86 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 126.11 | 325.30 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 20.63 | 583.76 | 0.00 | 0.00 | 0.00 |
December | 102.02 | 0.00 | 102.02 | 4.43 | 766.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 203.64 | 360.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.02 | 0.00 | 102.02 | 4.43 | 66.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.24 | 29.45 | 209.79 | 507.59 | 766.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.81 | 0.00 | 102.81 | 7.32 | 673.15 | 0.00 | 0.00 | 0.00 |
February | 125.54 | 0.00 | 125.54 | 35.90 | 597.41 | 0.00 | 0.00 | 0.00 |
March | 164.29 | 0.00 | 164.29 | 88.16 | 501.87 | 0.00 | 0.00 | 0.00 |
April | 189.69 | 1.49 | 188.20 | 198.48 | 288.76 | 0.00 | 0.00 | 0.00 |
May | 224.98 | 16.27 | 208.71 | 354.07 | 162.15 | 0.00 | 0.00 | 0.00 |
June | 239.23 | 29.45 | 209.78 | 507.57 | 83.48 | 0.00 | 0.00 | 0.00 |
July | 221.09 | 21.52 | 199.57 | 465.66 | 66.00 | 0.00 | 0.00 | 0.00 |
August | 186.43 | 3.81 | 182.62 | 356.12 | 94.42 | 0.00 | 0.00 | 0.00 |
September | 162.68 | 0.06 | 162.61 | 268.69 | 192.85 | 0.00 | 0.00 | 0.00 |
October | 135.07 | 0.00 | 135.07 | 126.11 | 325.29 | 0.00 | 0.00 | 0.00 |
November | 109.04 | 0.00 | 109.04 | 20.63 | 583.73 | 0.00 | 0.00 | 0.00 |
December | 102.01 | 0.00 | 102.01 | 4.43 | 766.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.76 | 6.08 | 157.68 | 203.63 | 360.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.01 | 0.00 | 102.01 | 4.43 | 66.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.23 | 29.45 | 209.78 | 507.57 | 766.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.54 | 165.74 | 139.79 | 262.97 | 672.00 | 0.00 | 0.00 | 0.00 |
February | 408.78 | 233.00 | 175.78 | 425.47 | 590.80 | 0.00 | 0.00 | 0.00 |
March | 504.71 | 278.08 | 226.63 | 586.38 | 493.02 | 0.00 | 0.00 | 0.00 |
April | 608.15 | 337.39 | 270.76 | 867.87 | 286.00 | 0.00 | 0.00 | 0.00 |
May | 627.58 | 341.07 | 286.51 | 1023.85 | 177.48 | 0.00 | 0.00 | 0.00 |
June | 627.93 | 349.33 | 278.60 | 1172.48 | 86.12 | 0.00 | 0.00 | 0.00 |
July | 563.12 | 294.39 | 268.73 | 1057.30 | 65.31 | 0.00 | 0.00 | 0.00 |
August | 535.84 | 274.24 | 261.60 | 965.66 | 91.46 | 0.00 | 0.00 | 0.00 |
September | 530.87 | 302.90 | 227.97 | 883.87 | 197.96 | 0.00 | 0.00 | 0.00 |
October | 408.27 | 220.34 | 187.93 | 558.21 | 332.21 | 0.00 | 0.00 | 0.00 |
November | 365.98 | 213.06 | 152.92 | 372.50 | 569.36 | 0.00 | 0.00 | 0.00 |
December | 305.28 | 161.74 | 143.53 | 245.10 | 743.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.72 | 264.13 | 218.59 | 702.73 | 357.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.28 | 161.74 | 139.79 | 245.10 | 65.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.93 | 349.33 | 286.51 | 1172.48 | 743.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.54 | 165.74 | 139.79 | 262.97 | 672.00 | 0.00 | 0.00 | 0.00 |
February | 408.78 | 233.00 | 175.78 | 425.47 | 590.80 | 0.00 | 0.00 | 0.00 |
March | 504.71 | 278.08 | 226.63 | 586.38 | 493.02 | 0.00 | 0.00 | 0.00 |
April | 608.15 | 337.39 | 270.76 | 867.87 | 286.00 | 0.00 | 0.00 | 0.00 |
May | 627.58 | 341.07 | 286.51 | 1023.85 | 177.48 | 0.00 | 0.00 | 0.00 |
June | 627.93 | 349.33 | 278.60 | 1172.48 | 86.12 | 0.00 | 0.00 | 0.00 |
July | 563.12 | 294.39 | 268.73 | 1057.30 | 65.31 | 0.00 | 0.00 | 0.00 |
August | 535.84 | 274.24 | 261.60 | 965.66 | 91.46 | 0.00 | 0.00 | 0.00 |
September | 530.87 | 302.90 | 227.97 | 883.87 | 197.96 | 0.00 | 0.00 | 0.00 |
October | 408.27 | 220.34 | 187.93 | 558.21 | 332.21 | 0.00 | 0.00 | 0.00 |
November | 365.98 | 213.06 | 152.92 | 372.50 | 569.36 | 0.00 | 0.00 | 0.00 |
December | 305.28 | 161.74 | 143.53 | 245.10 | 743.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.72 | 264.13 | 218.59 | 702.73 | 357.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.28 | 161.74 | 139.79 | 245.10 | 65.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.93 | 349.33 | 286.51 | 1172.48 | 743.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.53 | 165.74 | 139.79 | 262.97 | 671.99 | 0.00 | 0.00 | 0.00 |
February | 408.77 | 233.00 | 175.78 | 425.46 | 590.79 | 0.00 | 0.00 | 0.00 |
March | 504.70 | 278.07 | 226.63 | 586.37 | 493.01 | 0.00 | 0.00 | 0.00 |
April | 608.14 | 337.38 | 270.76 | 867.85 | 285.99 | 0.00 | 0.00 | 0.00 |
May | 627.57 | 341.06 | 286.51 | 1023.83 | 177.47 | 0.00 | 0.00 | 0.00 |
June | 627.92 | 349.32 | 278.60 | 1172.46 | 86.12 | 0.00 | 0.00 | 0.00 |
July | 563.11 | 294.38 | 268.72 | 1057.28 | 65.31 | 0.00 | 0.00 | 0.00 |
August | 535.83 | 274.23 | 261.60 | 965.64 | 91.45 | 0.00 | 0.00 | 0.00 |
September | 530.86 | 302.89 | 227.97 | 883.86 | 197.96 | 0.00 | 0.00 | 0.00 |
October | 408.26 | 220.34 | 187.93 | 558.20 | 332.20 | 0.00 | 0.00 | 0.00 |
November | 365.97 | 213.06 | 152.92 | 372.49 | 569.35 | 0.00 | 0.00 | 0.00 |
December | 305.27 | 161.74 | 143.53 | 245.09 | 743.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 482.71 | 264.13 | 218.59 | 702.72 | 357.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.27 | 161.74 | 139.79 | 245.09 | 65.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.92 | 349.32 | 286.51 | 1172.46 | 743.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.49 | 906.27 | 579.95 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 855.14 | 526.76 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 714.21 | 467.03 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 553.32 | 293.45 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 442.43 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 481.05 | 85.43 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 485.37 | 68.23 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 576.27 | 99.22 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 816.60 | 197.43 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 935.78 | 313.29 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 986.02 | 505.48 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 901.75 | 634.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.21 | 327.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.49 | 442.43 | 68.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 986.02 | 634.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.48 | 906.27 | 579.95 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 855.14 | 526.76 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 714.21 | 467.03 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 553.32 | 293.45 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 442.43 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 481.05 | 85.43 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 485.37 | 68.23 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 576.27 | 99.22 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 816.60 | 197.43 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 935.78 | 313.29 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 986.02 | 505.48 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 901.74 | 634.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.21 | 327.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.48 | 442.43 | 68.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 986.02 | 634.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.49 | 906.27 | 579.95 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 855.14 | 526.76 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 714.21 | 467.03 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 553.32 | 293.45 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 442.43 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 481.05 | 85.43 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 485.37 | 68.23 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 576.27 | 99.22 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 816.60 | 197.43 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 935.78 | 313.29 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 986.02 | 505.48 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 901.75 | 634.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.21 | 327.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.49 | 442.43 | 68.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 986.02 | 634.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.33 | 532.85 | 170.48 | 906.27 | 579.95 | 0.00 | 0.00 | 0.00 |
February | 652.42 | 459.95 | 192.47 | 855.14 | 526.76 | 0.00 | 0.00 | 0.00 |
March | 530.23 | 305.73 | 224.50 | 714.21 | 467.03 | 0.00 | 0.00 | 0.00 |
April | 359.49 | 134.14 | 225.36 | 553.32 | 293.45 | 0.00 | 0.00 | 0.00 |
May | 254.05 | 35.56 | 218.49 | 442.43 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 219.18 | 13.91 | 205.27 | 481.05 | 85.43 | 0.00 | 0.00 | 0.00 |
July | 223.43 | 20.71 | 202.72 | 485.37 | 68.23 | 0.00 | 0.00 | 0.00 |
August | 284.81 | 75.39 | 209.42 | 576.27 | 99.22 | 0.00 | 0.00 | 0.00 |
September | 444.56 | 230.96 | 213.60 | 816.60 | 197.43 | 0.00 | 0.00 | 0.00 |
October | 604.02 | 408.36 | 195.66 | 935.78 | 313.29 | 0.00 | 0.00 | 0.00 |
November | 726.89 | 554.16 | 172.73 | 986.02 | 505.48 | 0.00 | 0.00 | 0.00 |
December | 720.37 | 540.75 | 179.63 | 901.74 | 634.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.89 | 275.00 | 200.89 | 720.21 | 327.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 13.91 | 170.48 | 442.43 | 68.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.89 | 554.16 | 225.36 | 986.02 | 634.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 703.31 | 532.83 | 170.48 | 906.24 | 579.93 | 0.00 | 0.00 | 0.00 |
February | 652.39 | 459.93 | 192.47 | 855.11 | 526.74 | 0.00 | 0.00 | 0.00 |
March | 530.21 | 305.72 | 224.49 | 714.18 | 467.01 | 0.00 | 0.00 | 0.00 |
April | 359.48 | 134.13 | 225.35 | 553.30 | 293.44 | 0.00 | 0.00 | 0.00 |
May | 254.04 | 35.56 | 218.48 | 442.41 | 173.16 | 0.00 | 0.00 | 0.00 |
June | 219.17 | 13.91 | 205.26 | 481.03 | 85.42 | 0.00 | 0.00 | 0.00 |
July | 223.42 | 20.71 | 202.71 | 485.35 | 68.23 | 0.00 | 0.00 | 0.00 |
August | 284.80 | 75.39 | 209.41 | 576.25 | 99.21 | 0.00 | 0.00 | 0.00 |
September | 444.54 | 230.95 | 213.59 | 816.57 | 197.42 | 0.00 | 0.00 | 0.00 |
October | 604.00 | 408.34 | 195.66 | 935.75 | 313.28 | 0.00 | 0.00 | 0.00 |
November | 726.86 | 554.14 | 172.72 | 985.98 | 505.46 | 0.00 | 0.00 | 0.00 |
December | 720.35 | 540.72 | 179.62 | 901.71 | 634.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 475.87 | 274.98 | 200.88 | 720.19 | 327.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.17 | 13.91 | 170.48 | 442.41 | 68.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 726.86 | 554.14 | 225.35 | 985.98 | 634.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.85 | 181.26 | 140.59 | 318.17 | 747.85 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.04 | 170.14 | 384.28 | 693.73 | 0.00 | 0.00 | 0.00 |
March | 494.90 | 265.25 | 229.65 | 588.66 | 604.13 | 0.00 | 0.00 | 0.00 |
April | 568.85 | 307.25 | 261.60 | 809.69 | 382.99 | 0.00 | 0.00 | 0.00 |
May | 612.71 | 327.83 | 284.88 | 1007.59 | 222.24 | 0.00 | 0.00 | 0.00 |
June | 596.42 | 320.34 | 276.08 | 1109.87 | 122.55 | 0.00 | 0.00 | 0.00 |
July | 529.28 | 263.01 | 266.27 | 979.16 | 105.57 | 0.00 | 0.00 | 0.00 |
August | 512.58 | 261.23 | 251.35 | 900.25 | 152.88 | 0.00 | 0.00 | 0.00 |
September | 524.20 | 292.03 | 232.17 | 888.91 | 246.37 | 0.00 | 0.00 | 0.00 |
October | 451.25 | 263.36 | 187.88 | 644.30 | 402.06 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 427.81 | 687.18 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.81 | 139.42 | 272.94 | 888.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.99 | 256.09 | 215.90 | 695.59 | 436.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.81 | 139.42 | 272.94 | 105.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.71 | 327.83 | 284.88 | 1109.87 | 888.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.85 | 181.26 | 140.59 | 318.17 | 747.85 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.04 | 170.14 | 384.28 | 693.73 | 0.00 | 0.00 | 0.00 |
March | 494.90 | 265.25 | 229.65 | 588.66 | 604.13 | 0.00 | 0.00 | 0.00 |
April | 568.85 | 307.25 | 261.60 | 809.69 | 382.99 | 0.00 | 0.00 | 0.00 |
May | 612.71 | 327.83 | 284.88 | 1007.59 | 222.24 | 0.00 | 0.00 | 0.00 |
June | 596.42 | 320.34 | 276.08 | 1109.87 | 122.55 | 0.00 | 0.00 | 0.00 |
July | 529.28 | 263.01 | 266.27 | 979.16 | 105.57 | 0.00 | 0.00 | 0.00 |
August | 512.58 | 261.23 | 251.35 | 900.25 | 152.88 | 0.00 | 0.00 | 0.00 |
September | 524.20 | 292.03 | 232.17 | 888.91 | 246.37 | 0.00 | 0.00 | 0.00 |
October | 451.25 | 263.36 | 187.88 | 644.30 | 402.06 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 427.81 | 687.18 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.81 | 139.42 | 272.94 | 888.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.99 | 256.09 | 215.90 | 695.59 | 436.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.81 | 139.42 | 272.94 | 105.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.71 | 327.83 | 284.88 | 1109.87 | 888.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.84 | 181.25 | 140.59 | 318.17 | 747.84 | 0.00 | 0.00 | 0.00 |
February | 363.17 | 193.03 | 170.14 | 384.27 | 693.72 | 0.00 | 0.00 | 0.00 |
March | 494.89 | 265.25 | 229.65 | 588.65 | 604.12 | 0.00 | 0.00 | 0.00 |
April | 568.84 | 307.24 | 261.60 | 809.67 | 382.98 | 0.00 | 0.00 | 0.00 |
May | 612.69 | 327.82 | 284.88 | 1007.57 | 222.23 | 0.00 | 0.00 | 0.00 |
June | 596.41 | 320.34 | 276.07 | 1109.85 | 122.54 | 0.00 | 0.00 | 0.00 |
July | 529.27 | 263.01 | 266.27 | 979.15 | 105.56 | 0.00 | 0.00 | 0.00 |
August | 512.57 | 261.23 | 251.35 | 900.23 | 152.88 | 0.00 | 0.00 | 0.00 |
September | 524.19 | 292.02 | 232.16 | 888.89 | 246.37 | 0.00 | 0.00 | 0.00 |
October | 451.24 | 263.36 | 187.88 | 644.29 | 402.06 | 0.00 | 0.00 | 0.00 |
November | 378.75 | 230.62 | 148.13 | 427.81 | 687.16 | 0.00 | 0.00 | 0.00 |
December | 305.22 | 165.80 | 139.41 | 272.93 | 888.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 471.98 | 256.08 | 215.90 | 695.58 | 436.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.22 | 165.80 | 139.41 | 272.93 | 105.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.69 | 327.82 | 284.88 | 1109.85 | 888.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.06 | 0.00 | 514.06 | 80.09 | 2975.17 | 0.00 | 0.00 | 0.00 |
February | 627.72 | 0.00 | 627.72 | 242.73 | 2668.82 | 0.00 | 0.00 | 0.00 |
March | 821.48 | 0.00 | 821.48 | 509.32 | 2257.11 | 0.00 | 0.00 | 0.00 |
April | 948.49 | 7.47 | 941.01 | 1051.45 | 1321.37 | 0.00 | 0.00 | 0.00 |
May | 1124.94 | 81.35 | 1043.59 | 1795.99 | 769.94 | 0.00 | 0.00 | 0.00 |
June | 1196.18 | 147.26 | 1048.92 | 2563.30 | 416.01 | 0.00 | 0.00 | 0.00 |
July | 1105.50 | 107.61 | 997.89 | 2356.65 | 331.54 | 0.00 | 0.00 | 0.00 |
August | 932.18 | 19.06 | 913.12 | 1827.96 | 451.49 | 0.00 | 0.00 | 0.00 |
September | 813.41 | 0.32 | 813.09 | 1372.98 | 911.88 | 0.00 | 0.00 | 0.00 |
October | 675.36 | 0.00 | 675.36 | 685.72 | 1467.64 | 0.00 | 0.00 | 0.00 |
November | 545.21 | 0.00 | 545.21 | 159.99 | 2541.88 | 0.00 | 0.00 | 0.00 |
December | 510.07 | 0.00 | 510.07 | 52.86 | 3306.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 30.41 | 788.40 | 1062.45 | 1613.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.07 | 0.00 | 510.07 | 52.86 | 331.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.18 | 147.26 | 1048.92 | 2563.30 | 3306.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 916.61 | 497.23 | 419.38 | 818.61 | 1831.63 | 0.00 | 0.00 | 0.00 |
February | 1226.33 | 699.00 | 527.33 | 1295.32 | 1645.25 | 0.00 | 0.00 | 0.00 |
March | 1514.12 | 834.23 | 679.89 | 1765.18 | 1396.12 | 0.00 | 0.00 | 0.00 |
April | 1824.43 | 1012.15 | 812.28 | 2584.00 | 841.26 | 0.00 | 0.00 | 0.00 |
May | 1882.72 | 1023.19 | 859.53 | 3048.97 | 520.50 | 0.00 | 0.00 | 0.00 |
June | 1883.78 | 1047.98 | 835.80 | 3492.69 | 275.28 | 0.00 | 0.00 | 0.00 |
July | 1689.34 | 883.16 | 806.18 | 3146.03 | 222.89 | 0.00 | 0.00 | 0.00 |
August | 1607.50 | 822.70 | 784.79 | 2875.04 | 302.08 | 0.00 | 0.00 | 0.00 |
September | 1592.59 | 908.69 | 683.90 | 2636.57 | 582.61 | 0.00 | 0.00 | 0.00 |
October | 1224.80 | 661.01 | 563.79 | 1677.08 | 936.02 | 0.00 | 0.00 | 0.00 |
November | 1097.93 | 639.18 | 458.75 | 1140.06 | 1563.20 | 0.00 | 0.00 | 0.00 |
December | 915.82 | 485.22 | 430.60 | 769.22 | 2021.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1448.16 | 792.39 | 655.77 | 2106.77 | 1008.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.82 | 485.22 | 419.38 | 769.22 | 222.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1883.78 | 1047.98 | 859.53 | 3492.69 | 2021.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3516.63 | 2664.21 | 852.41 | 4489.37 | 2820.67 | 0.00 | 0.00 | 0.00 |
February | 3262.06 | 2299.70 | 962.36 | 4237.90 | 2558.17 | 0.00 | 0.00 | 0.00 |
March | 2651.10 | 1528.62 | 1122.48 | 3542.29 | 2248.10 | 0.00 | 0.00 | 0.00 |
April | 1797.44 | 670.67 | 1126.77 | 2764.41 | 1403.14 | 0.00 | 0.00 | 0.00 |
May | 1270.23 | 177.79 | 1092.44 | 2221.97 | 832.54 | 0.00 | 0.00 | 0.00 |
June | 1095.89 | 69.53 | 1026.35 | 2437.14 | 423.98 | 0.00 | 0.00 | 0.00 |
July | 1117.14 | 103.56 | 1013.58 | 2454.39 | 343.81 | 0.00 | 0.00 | 0.00 |
August | 1424.04 | 376.95 | 1047.09 | 2903.52 | 487.06 | 0.00 | 0.00 | 0.00 |
September | 2222.77 | 1154.81 | 1067.96 | 4060.84 | 968.24 | 0.00 | 0.00 | 0.00 |
October | 3020.09 | 2041.78 | 978.31 | 4644.69 | 1518.93 | 0.00 | 0.00 | 0.00 |
November | 3634.40 | 2770.78 | 863.62 | 4901.60 | 2433.77 | 0.00 | 0.00 | 0.00 |
December | 3601.83 | 2703.70 | 898.13 | 4497.74 | 3038.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2379.41 | 1374.96 | 1004.45 | 3591.66 | 1584.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1095.89 | 69.53 | 852.41 | 2221.97 | 343.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3634.40 | 2770.78 | 1126.77 | 4901.60 | 3038.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 965.54 | 543.77 | 421.78 | 994.76 | 1984.57 | 0.00 | 0.00 | 0.00 |
February | 1089.51 | 579.10 | 510.41 | 1206.21 | 1807.72 | 0.00 | 0.00 | 0.00 |
March | 1484.69 | 795.74 | 688.95 | 1825.10 | 1558.40 | 0.00 | 0.00 | 0.00 |
April | 1706.53 | 921.73 | 784.80 | 2490.72 | 979.40 | 0.00 | 0.00 | 0.00 |
May | 1838.10 | 983.47 | 854.63 | 3030.33 | 611.63 | 0.00 | 0.00 | 0.00 |
June | 1789.25 | 961.02 | 828.22 | 3363.55 | 333.34 | 0.00 | 0.00 | 0.00 |
July | 1587.83 | 789.02 | 798.81 | 2990.64 | 273.06 | 0.00 | 0.00 | 0.00 |
August | 1537.73 | 783.69 | 754.04 | 2772.99 | 363.12 | 0.00 | 0.00 | 0.00 |
September | 1572.57 | 876.08 | 696.49 | 2683.91 | 678.79 | 0.00 | 0.00 | 0.00 |
October | 1353.73 | 790.08 | 563.65 | 1977.89 | 1049.19 | 0.00 | 0.00 | 0.00 |
November | 1136.25 | 691.86 | 444.40 | 1346.18 | 1723.71 | 0.00 | 0.00 | 0.00 |
December | 915.65 | 497.41 | 418.24 | 890.38 | 2181.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1415.96 | 768.26 | 647.70 | 2134.93 | 1125.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.65 | 497.41 | 418.24 | 890.38 | 273.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1838.10 | 983.47 | 854.63 | 3363.55 | 2181.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.06 | 0.00 | 514.06 | 117.95 | 2700.61 | 0.00 | 0.00 | 0.00 |
February | 627.72 | 0.00 | 627.72 | 286.69 | 2450.90 | 0.00 | 0.00 | 0.00 |
March | 821.48 | 0.00 | 821.48 | 552.23 | 2097.38 | 0.00 | 0.00 | 0.00 |
April | 948.49 | 7.47 | 941.01 | 1062.12 | 1258.48 | 0.00 | 0.00 | 0.00 |
May | 1124.94 | 81.35 | 1043.59 | 1783.45 | 757.89 | 0.00 | 0.00 | 0.00 |
June | 1196.18 | 147.26 | 1048.92 | 2531.10 | 422.01 | 0.00 | 0.00 | 0.00 |
July | 1105.50 | 107.61 | 997.89 | 2317.48 | 341.76 | 0.00 | 0.00 | 0.00 |
August | 932.18 | 19.06 | 913.12 | 1799.38 | 452.74 | 0.00 | 0.00 | 0.00 |
September | 813.41 | 0.32 | 813.09 | 1361.08 | 895.09 | 0.00 | 0.00 | 0.00 |
October | 675.36 | 0.00 | 675.36 | 711.26 | 1369.55 | 0.00 | 0.00 | 0.00 |
November | 545.21 | 0.00 | 545.21 | 198.82 | 2296.04 | 0.00 | 0.00 | 0.00 |
December | 510.07 | 0.00 | 510.07 | 85.90 | 3007.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 818.81 | 30.41 | 788.40 | 1071.28 | 1499.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 510.07 | 0.00 | 510.07 | 85.90 | 341.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.18 | 147.26 | 1048.92 | 2531.10 | 3007.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 916.61 | 497.23 | 419.38 | 864.35 | 1670.19 | 0.00 | 0.00 | 0.00 |
February | 1226.33 | 699.00 | 527.33 | 1338.68 | 1524.29 | 0.00 | 0.00 | 0.00 |
March | 1514.12 | 834.23 | 679.89 | 1793.00 | 1319.45 | 0.00 | 0.00 | 0.00 |
April | 1824.43 | 1012.15 | 812.28 | 2579.93 | 817.35 | 0.00 | 0.00 | 0.00 |
May | 1882.72 | 1023.19 | 859.53 | 3030.98 | 516.73 | 0.00 | 0.00 | 0.00 |
June | 1883.78 | 1047.98 | 835.80 | 3464.99 | 280.16 | 0.00 | 0.00 | 0.00 |
July | 1689.34 | 883.16 | 806.18 | 3114.35 | 230.19 | 0.00 | 0.00 | 0.00 |
August | 1607.50 | 822.70 | 784.79 | 2850.62 | 305.00 | 0.00 | 0.00 | 0.00 |
September | 1592.59 | 908.69 | 683.90 | 2622.60 | 578.69 | 0.00 | 0.00 | 0.00 |
October | 1224.80 | 661.01 | 563.79 | 1686.00 | 890.37 | 0.00 | 0.00 | 0.00 |
November | 1097.93 | 639.18 | 458.75 | 1181.00 | 1436.15 | 0.00 | 0.00 | 0.00 |
December | 915.82 | 485.22 | 430.60 | 820.47 | 1846.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1448.16 | 792.39 | 655.77 | 2114.77 | 948.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.82 | 485.22 | 419.38 | 820.47 | 230.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1883.78 | 1047.98 | 859.53 | 3464.99 | 1846.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3516.63 | 2664.21 | 852.41 | 4547.14 | 2589.71 | 0.00 | 0.00 | 0.00 |
February | 3262.06 | 2299.70 | 962.36 | 4284.27 | 2375.61 | 0.00 | 0.00 | 0.00 |
March | 2651.10 | 1528.62 | 1122.48 | 3573.91 | 2118.51 | 0.00 | 0.00 | 0.00 |
April | 1797.44 | 670.67 | 1126.77 | 2762.24 | 1347.96 | 0.00 | 0.00 | 0.00 |
May | 1270.23 | 177.79 | 1092.44 | 2203.89 | 816.64 | 0.00 | 0.00 | 0.00 |
June | 1095.89 | 69.53 | 1026.35 | 2405.76 | 428.89 | 0.00 | 0.00 | 0.00 |
July | 1117.14 | 103.56 | 1013.58 | 2414.77 | 353.51 | 0.00 | 0.00 | 0.00 |
August | 1424.04 | 376.95 | 1047.09 | 2872.69 | 488.78 | 0.00 | 0.00 | 0.00 |
September | 2222.77 | 1154.81 | 1067.96 | 4039.51 | 956.30 | 0.00 | 0.00 | 0.00 |
October | 3020.09 | 2041.78 | 978.31 | 4653.92 | 1446.63 | 0.00 | 0.00 | 0.00 |
November | 3634.40 | 2770.78 | 863.62 | 4954.76 | 2253.36 | 0.00 | 0.00 | 0.00 |
December | 3601.83 | 2703.70 | 898.13 | 4577.08 | 2793.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2379.41 | 1374.96 | 1004.45 | 3602.67 | 1492.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1095.89 | 69.53 | 852.41 | 2203.89 | 353.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3634.40 | 2770.78 | 1126.77 | 4954.76 | 2793.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 965.54 | 543.77 | 421.78 | 1015.27 | 1840.13 | 0.00 | 0.00 | 0.00 |
February | 1089.51 | 579.10 | 510.41 | 1224.23 | 1691.80 | 0.00 | 0.00 | 0.00 |
March | 1484.69 | 795.74 | 688.95 | 1837.55 | 1471.97 | 0.00 | 0.00 | 0.00 |
April | 1706.53 | 921.73 | 784.80 | 2486.60 | 944.52 | 0.00 | 0.00 | 0.00 |
May | 1838.10 | 983.47 | 854.63 | 3013.49 | 601.27 | 0.00 | 0.00 | 0.00 |
June | 1789.25 | 961.02 | 828.22 | 3340.11 | 335.72 | 0.00 | 0.00 | 0.00 |
July | 1587.83 | 789.02 | 798.81 | 2964.96 | 278.24 | 0.00 | 0.00 | 0.00 |
August | 1537.73 | 783.69 | 754.04 | 2752.89 | 363.25 | 0.00 | 0.00 | 0.00 |
September | 1572.57 | 876.08 | 696.49 | 2671.29 | 669.85 | 0.00 | 0.00 | 0.00 |
October | 1353.73 | 790.08 | 563.65 | 1983.63 | 998.99 | 0.00 | 0.00 | 0.00 |
November | 1136.25 | 691.86 | 444.40 | 1365.21 | 1597.02 | 0.00 | 0.00 | 0.00 |
December | 915.65 | 497.41 | 418.24 | 913.36 | 2022.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1415.96 | 768.26 | 647.70 | 2134.50 | 1064.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 915.65 | 497.41 | 418.24 | 913.36 | 278.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1838.10 | 983.47 | 854.63 | 3340.11 | 2022.86 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 19615792.53 | 0.180304E+10 |
February | 0.303718E+09 | 0.00 | 0.303718E+09 | 86862339.22 | 0.144531E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.236147E+09 | 0.134427E+10 |
April | 0.491702E+09 | 3873897.34 | 0.487828E+09 | 0.514490E+09 | 0.748485E+09 |
May | 0.602615E+09 | 43577493.91 | 0.559038E+09 | 0.948377E+09 | 0.434316E+09 |
June | 0.620108E+09 | 76342543.16 | 0.543765E+09 | 0.131568E+10 | 0.216393E+09 |
July | 0.592204E+09 | 57646476.54 | 0.534557E+09 | 0.124729E+10 | 0.176783E+09 |
August | 0.499356E+09 | 10210545.39 | 0.489146E+09 | 0.953871E+09 | 0.252901E+09 |
September | 0.421677E+09 | 168264.50 | 0.421509E+09 | 0.696483E+09 | 0.499899E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.337783E+09 | 0.871293E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 53471684.69 | 0.151310E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875155.66 | 0.205295E+10 |
Annual Sum or Average | 0.516447E+10 | 0.191819E+09 | 0.497265E+10 | 0.642194E+10 | 0.113587E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875155.66 | 0.176783E+09 |
Maximum of Months | 0.620108E+09 | 76342543.16 | 0.559038E+09 | 0.131568E+10 | 0.205295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 19615721.70 | 0.180304E+10 |
February | 0.303717E+09 | 0.00 | 0.303717E+09 | 86862229.16 | 0.144531E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.236147E+09 | 0.134427E+10 |
April | 0.491701E+09 | 3873892.69 | 0.487827E+09 | 0.514490E+09 | 0.748485E+09 |
May | 0.602615E+09 | 43577441.62 | 0.559037E+09 | 0.948377E+09 | 0.434316E+09 |
June | 0.620108E+09 | 76342451.56 | 0.543765E+09 | 0.131568E+10 | 0.216393E+09 |
July | 0.592203E+09 | 57646407.37 | 0.534557E+09 | 0.124728E+10 | 0.176783E+09 |
August | 0.499356E+09 | 10210533.14 | 0.489146E+09 | 0.953870E+09 | 0.252901E+09 |
September | 0.421677E+09 | 168264.30 | 0.421509E+09 | 0.696483E+09 | 0.499899E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.337782E+09 | 0.871293E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 53471619.35 | 0.151310E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875115.75 | 0.205295E+10 |
Annual Sum or Average | 0.516446E+10 | 0.191819E+09 | 0.497264E+10 | 0.642193E+10 | 0.113587E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875115.75 | 0.176783E+09 |
Maximum of Months | 0.620108E+09 | 76342451.56 | 0.559037E+09 | 0.131568E+10 | 0.205295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 19615792.53 | 0.180304E+10 |
February | 0.303718E+09 | 0.00 | 0.303718E+09 | 86862339.22 | 0.144531E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.236147E+09 | 0.134427E+10 |
April | 0.491702E+09 | 3873897.34 | 0.487828E+09 | 0.514490E+09 | 0.748485E+09 |
May | 0.602615E+09 | 43577493.91 | 0.559038E+09 | 0.948377E+09 | 0.434316E+09 |
June | 0.620108E+09 | 76342543.16 | 0.543765E+09 | 0.131568E+10 | 0.216393E+09 |
July | 0.592204E+09 | 57646476.54 | 0.534557E+09 | 0.124729E+10 | 0.176783E+09 |
August | 0.499356E+09 | 10210545.39 | 0.489146E+09 | 0.953871E+09 | 0.252901E+09 |
September | 0.421677E+09 | 168264.50 | 0.421509E+09 | 0.696483E+09 | 0.499899E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.337783E+09 | 0.871293E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 53471684.69 | 0.151310E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875155.66 | 0.205295E+10 |
Annual Sum or Average | 0.516447E+10 | 0.191819E+09 | 0.497265E+10 | 0.642194E+10 | 0.113587E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875155.66 | 0.176783E+09 |
Maximum of Months | 0.620108E+09 | 76342543.16 | 0.559038E+09 | 0.131568E+10 | 0.205295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275372E+09 | 0.00 | 0.275372E+09 | 19615721.70 | 0.180304E+10 |
February | 0.303717E+09 | 0.00 | 0.303717E+09 | 86862229.16 | 0.144531E+10 |
March | 0.440054E+09 | 0.00 | 0.440054E+09 | 0.236147E+09 | 0.134427E+10 |
April | 0.491701E+09 | 3873892.69 | 0.487827E+09 | 0.514490E+09 | 0.748485E+09 |
May | 0.602615E+09 | 43577441.62 | 0.559037E+09 | 0.948377E+09 | 0.434316E+09 |
June | 0.620108E+09 | 76342451.56 | 0.543765E+09 | 0.131568E+10 | 0.216393E+09 |
July | 0.592203E+09 | 57646407.37 | 0.534557E+09 | 0.124728E+10 | 0.176783E+09 |
August | 0.499356E+09 | 10210533.14 | 0.489146E+09 | 0.953870E+09 | 0.252901E+09 |
September | 0.421677E+09 | 168264.30 | 0.421509E+09 | 0.696483E+09 | 0.499899E+09 |
October | 0.361779E+09 | 0.00 | 0.361779E+09 | 0.337782E+09 | 0.871293E+09 |
November | 0.282641E+09 | 0.00 | 0.282641E+09 | 53471619.35 | 0.151310E+10 |
December | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875115.75 | 0.205295E+10 |
Annual Sum or Average | 0.516446E+10 | 0.191819E+09 | 0.497264E+10 | 0.642193E+10 | 0.113587E+11 |
Minimum of Months | 0.273240E+09 | 0.00 | 0.273240E+09 | 11875115.75 | 0.176783E+09 |
Maximum of Months | 0.620108E+09 | 76342451.56 | 0.559037E+09 | 0.131568E+10 | 0.205295E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275361E+09 | 0.00 | 0.275361E+09 | 19615001.93 | 0.180297E+10 |
February | 0.303705E+09 | 0.00 | 0.303705E+09 | 86858838.29 | 0.144525E+10 |
March | 0.440036E+09 | 0.00 | 0.440036E+09 | 0.236137E+09 | 0.134421E+10 |
April | 0.491682E+09 | 3873741.21 | 0.487808E+09 | 0.514469E+09 | 0.748455E+09 |
May | 0.602591E+09 | 43575737.54 | 0.559015E+09 | 0.948339E+09 | 0.434299E+09 |
June | 0.620083E+09 | 76339466.22 | 0.543744E+09 | 0.131562E+10 | 0.216384E+09 |
July | 0.592180E+09 | 57644153.13 | 0.534536E+09 | 0.124723E+10 | 0.176776E+09 |
August | 0.499336E+09 | 10210133.86 | 0.489126E+09 | 0.953832E+09 | 0.252891E+09 |
September | 0.421660E+09 | 168257.72 | 0.421492E+09 | 0.696455E+09 | 0.499879E+09 |
October | 0.361765E+09 | 0.00 | 0.361765E+09 | 0.337769E+09 | 0.871258E+09 |
November | 0.282630E+09 | 0.00 | 0.282630E+09 | 53469529.54 | 0.151304E+10 |
December | 0.273229E+09 | 0.00 | 0.273229E+09 | 11874677.04 | 0.205287E+10 |
Annual Sum or Average | 0.516426E+10 | 0.191811E+09 | 0.497245E+10 | 0.642168E+10 | 0.113583E+11 |
Minimum of Months | 0.273229E+09 | 0.00 | 0.273229E+09 | 11874677.04 | 0.176776E+09 |
Maximum of Months | 0.620083E+09 | 76339466.22 | 0.559015E+09 | 0.131562E+10 | 0.205287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818354E+09 | 0.443927E+09 | 0.374426E+09 | 0.704342E+09 | 0.179988E+10 |
February | 0.988923E+09 | 0.563680E+09 | 0.425243E+09 | 0.102929E+10 | 0.142927E+10 |
March | 0.135182E+10 | 0.744808E+09 | 0.607009E+09 | 0.157057E+10 | 0.132051E+10 |
April | 0.157633E+10 | 0.874509E+09 | 0.701818E+09 | 0.224952E+10 | 0.741309E+09 |
May | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.274227E+10 | 0.475354E+09 |
June | 0.162760E+10 | 0.905465E+09 | 0.722134E+09 | 0.303907E+10 | 0.223219E+09 |
July | 0.150826E+10 | 0.788490E+09 | 0.719765E+09 | 0.283187E+10 | 0.174929E+09 |
August | 0.143519E+10 | 0.734516E+09 | 0.700671E+09 | 0.258641E+10 | 0.244954E+09 |
September | 0.137601E+10 | 0.785116E+09 | 0.590897E+09 | 0.229100E+10 | 0.513118E+09 |
October | 0.109352E+10 | 0.590160E+09 | 0.503356E+09 | 0.149510E+10 | 0.889780E+09 |
November | 0.948620E+09 | 0.552256E+09 | 0.396364E+09 | 0.965511E+09 | 0.147577E+10 |
December | 0.817651E+09 | 0.433210E+09 | 0.384441E+09 | 0.656472E+09 | 0.199159E+10 |
Annual Sum or Average | 0.152232E+11 | 0.832965E+10 | 0.689352E+10 | 0.221614E+11 | 0.112797E+11 |
Minimum of Months | 0.817651E+09 | 0.433210E+09 | 0.374426E+09 | 0.656472E+09 | 0.174929E+09 |
Maximum of Months | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.303907E+10 | 0.199159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818354E+09 | 0.443927E+09 | 0.374426E+09 | 0.704342E+09 | 0.179988E+10 |
February | 0.988923E+09 | 0.563680E+09 | 0.425243E+09 | 0.102929E+10 | 0.142927E+10 |
March | 0.135182E+10 | 0.744808E+09 | 0.607009E+09 | 0.157057E+10 | 0.132051E+10 |
April | 0.157633E+10 | 0.874509E+09 | 0.701818E+09 | 0.224952E+10 | 0.741309E+09 |
May | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.274227E+10 | 0.475354E+09 |
June | 0.162760E+10 | 0.905465E+09 | 0.722134E+09 | 0.303907E+10 | 0.223219E+09 |
July | 0.150826E+10 | 0.788490E+09 | 0.719765E+09 | 0.283187E+10 | 0.174929E+09 |
August | 0.143519E+10 | 0.734516E+09 | 0.700671E+09 | 0.258641E+10 | 0.244954E+09 |
September | 0.137601E+10 | 0.785116E+09 | 0.590897E+09 | 0.229100E+10 | 0.513118E+09 |
October | 0.109352E+10 | 0.590160E+09 | 0.503356E+09 | 0.149510E+10 | 0.889780E+09 |
November | 0.948620E+09 | 0.552256E+09 | 0.396364E+09 | 0.965511E+09 | 0.147577E+10 |
December | 0.817651E+09 | 0.433210E+09 | 0.384441E+09 | 0.656472E+09 | 0.199159E+10 |
Annual Sum or Average | 0.152232E+11 | 0.832965E+10 | 0.689352E+10 | 0.221614E+11 | 0.112797E+11 |
Minimum of Months | 0.817651E+09 | 0.433210E+09 | 0.374426E+09 | 0.656472E+09 | 0.174929E+09 |
Maximum of Months | 0.168091E+10 | 0.913510E+09 | 0.767396E+09 | 0.303907E+10 | 0.199159E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818339E+09 | 0.443919E+09 | 0.374419E+09 | 0.704329E+09 | 0.179985E+10 |
February | 0.988905E+09 | 0.563669E+09 | 0.425235E+09 | 0.102927E+10 | 0.142924E+10 |
March | 0.135179E+10 | 0.744794E+09 | 0.606998E+09 | 0.157054E+10 | 0.132049E+10 |
April | 0.157630E+10 | 0.874493E+09 | 0.701805E+09 | 0.224948E+10 | 0.741295E+09 |
May | 0.168088E+10 | 0.913494E+09 | 0.767382E+09 | 0.274222E+10 | 0.475345E+09 |
June | 0.162757E+10 | 0.905449E+09 | 0.722121E+09 | 0.303902E+10 | 0.223215E+09 |
July | 0.150823E+10 | 0.788476E+09 | 0.719752E+09 | 0.283181E+10 | 0.174926E+09 |
August | 0.143516E+10 | 0.734502E+09 | 0.700659E+09 | 0.258636E+10 | 0.244949E+09 |
September | 0.137599E+10 | 0.785102E+09 | 0.590886E+09 | 0.229096E+10 | 0.513109E+09 |
October | 0.109350E+10 | 0.590149E+09 | 0.503347E+09 | 0.149507E+10 | 0.889764E+09 |
November | 0.948603E+09 | 0.552246E+09 | 0.396357E+09 | 0.965494E+09 | 0.147574E+10 |
December | 0.817636E+09 | 0.433202E+09 | 0.384434E+09 | 0.656460E+09 | 0.199155E+10 |
Annual Sum or Average | 0.152229E+11 | 0.832950E+10 | 0.689340E+10 | 0.221610E+11 | 0.112795E+11 |
Minimum of Months | 0.817636E+09 | 0.433202E+09 | 0.374419E+09 | 0.656460E+09 | 0.174926E+09 |
Maximum of Months | 0.168088E+10 | 0.913494E+09 | 0.767382E+09 | 0.303902E+10 | 0.199155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.242736E+10 | 0.155335E+10 |
February | 0.157834E+10 | 0.111270E+10 | 0.465634E+09 | 0.206877E+10 | 0.127435E+10 |
March | 0.142016E+10 | 0.818860E+09 | 0.601300E+09 | 0.191293E+10 | 0.125089E+10 |
April | 0.931803E+09 | 0.347679E+09 | 0.584124E+09 | 0.143421E+10 | 0.760633E+09 |
May | 0.680445E+09 | 95239968.29 | 0.585205E+09 | 0.118501E+10 | 0.463800E+09 |
June | 0.568115E+09 | 36047082.62 | 0.532068E+09 | 0.124689E+10 | 0.221428E+09 |
July | 0.598435E+09 | 55475984.25 | 0.542959E+09 | 0.130001E+10 | 0.182758E+09 |
August | 0.762840E+09 | 0.201928E+09 | 0.560912E+09 | 0.154349E+10 | 0.265741E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553639E+09 | 0.211663E+10 | 0.511737E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524066E+09 | 0.250640E+10 | 0.839123E+09 |
November | 0.188410E+10 | 0.143639E+10 | 0.447704E+09 | 0.255576E+10 | 0.131021E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.241524E+10 | 0.169897E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867225E+10 | 0.633535E+10 | 0.227127E+11 | 0.103330E+11 |
Minimum of Months | 0.568115E+09 | 36047082.62 | 0.447704E+09 | 0.118501E+10 | 0.182758E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601300E+09 | 0.255576E+10 | 0.169897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.242736E+10 | 0.155335E+10 |
February | 0.157833E+10 | 0.111270E+10 | 0.465633E+09 | 0.206876E+10 | 0.127435E+10 |
March | 0.142016E+10 | 0.818859E+09 | 0.601299E+09 | 0.191293E+10 | 0.125089E+10 |
April | 0.931802E+09 | 0.347679E+09 | 0.584123E+09 | 0.143421E+10 | 0.760632E+09 |
May | 0.680444E+09 | 95239854.01 | 0.585204E+09 | 0.118501E+10 | 0.463800E+09 |
June | 0.568115E+09 | 36047039.37 | 0.532068E+09 | 0.124689E+10 | 0.221428E+09 |
July | 0.598435E+09 | 55475917.69 | 0.542959E+09 | 0.130001E+10 | 0.182758E+09 |
August | 0.762839E+09 | 0.201928E+09 | 0.560911E+09 | 0.154349E+10 | 0.265741E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553638E+09 | 0.211663E+10 | 0.511737E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524065E+09 | 0.250640E+10 | 0.839122E+09 |
November | 0.188409E+10 | 0.143639E+10 | 0.447704E+09 | 0.255575E+10 | 0.131021E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.241523E+10 | 0.169897E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867224E+10 | 0.633535E+10 | 0.227127E+11 | 0.103330E+11 |
Minimum of Months | 0.568115E+09 | 36047039.37 | 0.447704E+09 | 0.118501E+10 | 0.182758E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601299E+09 | 0.255575E+10 | 0.169897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.242736E+10 | 0.155335E+10 |
February | 0.157834E+10 | 0.111270E+10 | 0.465634E+09 | 0.206877E+10 | 0.127435E+10 |
March | 0.142016E+10 | 0.818860E+09 | 0.601300E+09 | 0.191293E+10 | 0.125089E+10 |
April | 0.931803E+09 | 0.347679E+09 | 0.584124E+09 | 0.143421E+10 | 0.760633E+09 |
May | 0.680445E+09 | 95239968.29 | 0.585205E+09 | 0.118501E+10 | 0.463800E+09 |
June | 0.568115E+09 | 36047082.62 | 0.532068E+09 | 0.124689E+10 | 0.221428E+09 |
July | 0.598435E+09 | 55475984.25 | 0.542959E+09 | 0.130001E+10 | 0.182758E+09 |
August | 0.762840E+09 | 0.201928E+09 | 0.560912E+09 | 0.154349E+10 | 0.265741E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553639E+09 | 0.211663E+10 | 0.511737E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524066E+09 | 0.250640E+10 | 0.839123E+09 |
November | 0.188410E+10 | 0.143639E+10 | 0.447704E+09 | 0.255576E+10 | 0.131021E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.241524E+10 | 0.169897E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867225E+10 | 0.633535E+10 | 0.227127E+11 | 0.103330E+11 |
Minimum of Months | 0.568115E+09 | 36047082.62 | 0.447704E+09 | 0.118501E+10 | 0.182758E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601300E+09 | 0.255576E+10 | 0.169897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188381E+10 | 0.142718E+10 | 0.456627E+09 | 0.242736E+10 | 0.155335E+10 |
February | 0.157833E+10 | 0.111270E+10 | 0.465633E+09 | 0.206876E+10 | 0.127435E+10 |
March | 0.142016E+10 | 0.818859E+09 | 0.601299E+09 | 0.191293E+10 | 0.125089E+10 |
April | 0.931802E+09 | 0.347679E+09 | 0.584123E+09 | 0.143421E+10 | 0.760632E+09 |
May | 0.680444E+09 | 95239854.01 | 0.585204E+09 | 0.118501E+10 | 0.463800E+09 |
June | 0.568115E+09 | 36047039.37 | 0.532068E+09 | 0.124689E+10 | 0.221428E+09 |
July | 0.598435E+09 | 55475917.69 | 0.542959E+09 | 0.130001E+10 | 0.182758E+09 |
August | 0.762839E+09 | 0.201928E+09 | 0.560911E+09 | 0.154349E+10 | 0.265741E+09 |
September | 0.115230E+10 | 0.598658E+09 | 0.553638E+09 | 0.211663E+10 | 0.511737E+09 |
October | 0.161782E+10 | 0.109375E+10 | 0.524065E+09 | 0.250640E+10 | 0.839122E+09 |
November | 0.188409E+10 | 0.143639E+10 | 0.447704E+09 | 0.255575E+10 | 0.131021E+10 |
December | 0.192945E+10 | 0.144833E+10 | 0.481117E+09 | 0.241523E+10 | 0.169897E+10 |
Annual Sum or Average | 0.150076E+11 | 0.867224E+10 | 0.633535E+10 | 0.227127E+11 | 0.103330E+11 |
Minimum of Months | 0.568115E+09 | 36047039.37 | 0.447704E+09 | 0.118501E+10 | 0.182758E+09 |
Maximum of Months | 0.192945E+10 | 0.144833E+10 | 0.601299E+09 | 0.255575E+10 | 0.169897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188373E+10 | 0.142712E+10 | 0.456609E+09 | 0.242726E+10 | 0.155328E+10 |
February | 0.157827E+10 | 0.111266E+10 | 0.465615E+09 | 0.206868E+10 | 0.127430E+10 |
March | 0.142010E+10 | 0.818827E+09 | 0.601276E+09 | 0.191286E+10 | 0.125084E+10 |
April | 0.931765E+09 | 0.347665E+09 | 0.584100E+09 | 0.143415E+10 | 0.760602E+09 |
May | 0.680417E+09 | 95236129.70 | 0.585181E+09 | 0.118496E+10 | 0.463781E+09 |
June | 0.568092E+09 | 36045629.76 | 0.532047E+09 | 0.124684E+10 | 0.221419E+09 |
July | 0.598411E+09 | 55473748.32 | 0.542937E+09 | 0.129996E+10 | 0.182751E+09 |
August | 0.762809E+09 | 0.201920E+09 | 0.560889E+09 | 0.154343E+10 | 0.265730E+09 |
September | 0.115225E+10 | 0.598634E+09 | 0.553616E+09 | 0.211655E+10 | 0.511716E+09 |
October | 0.161776E+10 | 0.109371E+10 | 0.524045E+09 | 0.250630E+10 | 0.839089E+09 |
November | 0.188402E+10 | 0.143633E+10 | 0.447686E+09 | 0.255565E+10 | 0.131016E+10 |
December | 0.192937E+10 | 0.144828E+10 | 0.481098E+09 | 0.241514E+10 | 0.169891E+10 |
Annual Sum or Average | 0.150070E+11 | 0.867190E+10 | 0.633510E+10 | 0.227118E+11 | 0.103326E+11 |
Minimum of Months | 0.568092E+09 | 36045629.76 | 0.447686E+09 | 0.118496E+10 | 0.182751E+09 |
Maximum of Months | 0.192937E+10 | 0.144828E+10 | 0.601276E+09 | 0.255565E+10 | 0.169891E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862044E+09 | 0.485479E+09 | 0.376565E+09 | 0.852192E+09 | 0.200304E+10 |
February | 0.878592E+09 | 0.466991E+09 | 0.411602E+09 | 0.929649E+09 | 0.167827E+10 |
March | 0.132555E+10 | 0.710448E+09 | 0.615100E+09 | 0.157666E+10 | 0.161809E+10 |
April | 0.147446E+10 | 0.796382E+09 | 0.678077E+09 | 0.209871E+10 | 0.992697E+09 |
May | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.269873E+10 | 0.595234E+09 |
June | 0.154592E+10 | 0.830332E+09 | 0.715593E+09 | 0.287679E+10 | 0.317641E+09 |
July | 0.141763E+10 | 0.704448E+09 | 0.713181E+09 | 0.262259E+10 | 0.282750E+09 |
August | 0.137290E+10 | 0.699683E+09 | 0.673218E+09 | 0.241123E+10 | 0.409468E+09 |
September | 0.135871E+10 | 0.756941E+09 | 0.601773E+09 | 0.230405E+10 | 0.638594E+09 |
October | 0.120862E+10 | 0.705389E+09 | 0.503229E+09 | 0.172570E+10 | 0.107689E+10 |
November | 0.981733E+09 | 0.597771E+09 | 0.383962E+09 | 0.110890E+10 | 0.178116E+10 |
December | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.731035E+09 | 0.238064E+10 |
Annual Sum or Average | 0.148847E+11 | 0.807600E+10 | 0.680873E+10 | 0.219362E+11 | 0.137745E+11 |
Minimum of Months | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.731035E+09 | 0.282750E+09 |
Maximum of Months | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.287679E+10 | 0.238064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862044E+09 | 0.485479E+09 | 0.376565E+09 | 0.852192E+09 | 0.200304E+10 |
February | 0.878592E+09 | 0.466991E+09 | 0.411602E+09 | 0.929649E+09 | 0.167827E+10 |
March | 0.132555E+10 | 0.710448E+09 | 0.615100E+09 | 0.157666E+10 | 0.161809E+10 |
April | 0.147446E+10 | 0.796382E+09 | 0.678077E+09 | 0.209871E+10 | 0.992697E+09 |
May | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.269873E+10 | 0.595234E+09 |
June | 0.154592E+10 | 0.830332E+09 | 0.715593E+09 | 0.287679E+10 | 0.317641E+09 |
July | 0.141763E+10 | 0.704448E+09 | 0.713181E+09 | 0.262259E+10 | 0.282750E+09 |
August | 0.137290E+10 | 0.699683E+09 | 0.673218E+09 | 0.241123E+10 | 0.409468E+09 |
September | 0.135871E+10 | 0.756941E+09 | 0.601773E+09 | 0.230405E+10 | 0.638594E+09 |
October | 0.120862E+10 | 0.705389E+09 | 0.503229E+09 | 0.172570E+10 | 0.107689E+10 |
November | 0.981733E+09 | 0.597771E+09 | 0.383962E+09 | 0.110890E+10 | 0.178116E+10 |
December | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.731035E+09 | 0.238064E+10 |
Annual Sum or Average | 0.148847E+11 | 0.807600E+10 | 0.680873E+10 | 0.219362E+11 | 0.137745E+11 |
Minimum of Months | 0.817504E+09 | 0.444094E+09 | 0.373409E+09 | 0.731035E+09 | 0.282750E+09 |
Maximum of Months | 0.164107E+10 | 0.878047E+09 | 0.763024E+09 | 0.287679E+10 | 0.238064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862028E+09 | 0.485470E+09 | 0.376558E+09 | 0.852176E+09 | 0.200301E+10 |
February | 0.878576E+09 | 0.466982E+09 | 0.411594E+09 | 0.929632E+09 | 0.167824E+10 |
March | 0.132552E+10 | 0.710435E+09 | 0.615088E+09 | 0.157663E+10 | 0.161806E+10 |
April | 0.147443E+10 | 0.796367E+09 | 0.678065E+09 | 0.209868E+10 | 0.992679E+09 |
May | 0.164104E+10 | 0.878031E+09 | 0.763010E+09 | 0.269868E+10 | 0.595223E+09 |
June | 0.154590E+10 | 0.830316E+09 | 0.715580E+09 | 0.287674E+10 | 0.317635E+09 |
July | 0.141760E+10 | 0.704435E+09 | 0.713168E+09 | 0.262254E+10 | 0.282745E+09 |
August | 0.137288E+10 | 0.699670E+09 | 0.673206E+09 | 0.241118E+10 | 0.409461E+09 |
September | 0.135869E+10 | 0.756927E+09 | 0.601762E+09 | 0.230401E+10 | 0.638583E+09 |
October | 0.120860E+10 | 0.705376E+09 | 0.503220E+09 | 0.172567E+10 | 0.107687E+10 |
November | 0.981715E+09 | 0.597760E+09 | 0.383955E+09 | 0.110888E+10 | 0.178113E+10 |
December | 0.817489E+09 | 0.444086E+09 | 0.373403E+09 | 0.731022E+09 | 0.238060E+10 |
Annual Sum or Average | 0.148845E+11 | 0.807586E+10 | 0.680861E+10 | 0.219358E+11 | 0.137742E+11 |
Minimum of Months | 0.817489E+09 | 0.444086E+09 | 0.373403E+09 | 0.731022E+09 | 0.282745E+09 |
Maximum of Months | 0.164104E+10 | 0.878031E+09 | 0.763010E+09 | 0.287674E+10 | 0.238060E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.214516E+09 | 0.796871E+10 |
February | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.587223E+09 | 0.645642E+10 |
March | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.136417E+10 | 0.604543E+10 |
April | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.272535E+10 | 0.342498E+10 |
May | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.481039E+10 | 0.206222E+10 |
June | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.664408E+10 | 0.107831E+10 |
July | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.631204E+10 | 0.887985E+09 |
August | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.489600E+10 | 0.120927E+10 |
September | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.355877E+10 | 0.236359E+10 |
October | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.183664E+10 | 0.393093E+10 |
November | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.414693E+09 | 0.658856E+10 |
December | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.141570E+09 | 0.885494E+10 |
Annual Sum or Average | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.335054E+11 | 0.508713E+11 |
Minimum of Months | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.141570E+09 | 0.887985E+09 |
Maximum of Months | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.664408E+10 | 0.885494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.219256E+10 | 0.490584E+10 |
February | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.313364E+10 | 0.398019E+10 |
March | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.472786E+10 | 0.373936E+10 |
April | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.669774E+10 | 0.218056E+10 |
May | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.816636E+10 | 0.139412E+10 |
June | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.905306E+10 | 0.713532E+09 |
July | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.842634E+10 | 0.596976E+09 |
August | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.770051E+10 | 0.809078E+09 |
September | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.683400E+10 | 0.151012E+10 |
October | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.449190E+10 | 0.250704E+10 |
November | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.295503E+10 | 0.405182E+10 |
December | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.206027E+10 | 0.541498E+10 |
Annual Sum or Average | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.664393E+11 | 0.318036E+11 |
Minimum of Months | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.206027E+10 | 0.596976E+09 |
Maximum of Months | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.905306E+10 | 0.541498E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.120243E+11 | 0.755488E+10 |
February | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.102523E+11 | 0.618873E+10 |
March | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.948768E+10 | 0.602132E+10 |
April | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.716534E+10 | 0.363693E+10 |
May | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.595134E+10 | 0.222987E+10 |
June | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.631707E+10 | 0.109896E+10 |
July | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.657385E+10 | 0.920851E+09 |
August | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.777678E+10 | 0.130453E+10 |
September | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.105257E+11 | 0.250967E+10 |
October | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.124403E+11 | 0.406830E+10 |
November | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.127049E+11 | 0.630832E+10 |
December | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.120468E+11 | 0.813698E+10 |
Annual Sum or Average | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.113266E+12 | 0.499793E+11 |
Minimum of Months | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.595134E+10 | 0.920851E+09 |
Maximum of Months | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.127049E+11 | 0.813698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.266435E+10 | 0.531547E+10 |
February | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.291805E+10 | 0.437325E+10 |
March | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.488834E+10 | 0.417401E+10 |
April | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.645595E+10 | 0.253860E+10 |
May | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.811644E+10 | 0.163820E+10 |
June | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.871831E+10 | 0.864014E+09 |
July | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.801013E+10 | 0.731372E+09 |
August | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.742717E+10 | 0.972570E+09 |
September | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.695669E+10 | 0.175942E+10 |
October | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.529757E+10 | 0.281014E+10 |
November | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.348931E+10 | 0.446785E+10 |
December | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.238480E+10 | 0.584170E+10 |
Annual Sum or Average | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.673271E+11 | 0.354866E+11 |
Minimum of Months | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.238480E+10 | 0.731372E+09 |
Maximum of Months | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.871831E+10 | 0.584170E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.315927E+09 | 0.723330E+10 |
February | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.693571E+09 | 0.592921E+10 |
March | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.147909E+10 | 0.561761E+10 |
April | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.275300E+10 | 0.326199E+10 |
May | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.477678E+10 | 0.202992E+10 |
June | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.656061E+10 | 0.109385E+10 |
July | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.620713E+10 | 0.915371E+09 |
August | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.481946E+10 | 0.121261E+10 |
September | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.352793E+10 | 0.232007E+10 |
October | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.190503E+10 | 0.366820E+10 |
November | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.515331E+09 | 0.595133E+10 |
December | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.230079E+09 | 0.805489E+10 |
Annual Sum or Average | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.337839E+11 | 0.472884E+11 |
Minimum of Months | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.230079E+09 | 0.915371E+09 |
Maximum of Months | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.656061E+10 | 0.805489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.231507E+10 | 0.447344E+10 |
February | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.323855E+10 | 0.368757E+10 |
March | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.480237E+10 | 0.353403E+10 |
April | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.668719E+10 | 0.211856E+10 |
May | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.811819E+10 | 0.138400E+10 |
June | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.898125E+10 | 0.726172E+09 |
July | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.834146E+10 | 0.616549E+09 |
August | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.763509E+10 | 0.816924E+09 |
September | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.679779E+10 | 0.149996E+10 |
October | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.451578E+10 | 0.238477E+10 |
November | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.306116E+10 | 0.372251E+10 |
December | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.219756E+10 | 0.494451E+10 |
Annual Sum or Average | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.666915E+11 | 0.299090E+11 |
Minimum of Months | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.219756E+10 | 0.616549E+09 |
Maximum of Months | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.898125E+10 | 0.494451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.121791E+11 | 0.693629E+10 |
February | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.103645E+11 | 0.574708E+10 |
March | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.957237E+10 | 0.567421E+10 |
April | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.715973E+10 | 0.349391E+10 |
May | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.590291E+10 | 0.218730E+10 |
June | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.623572E+10 | 0.111168E+10 |
July | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.646773E+10 | 0.946846E+09 |
August | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.769420E+10 | 0.130915E+10 |
September | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.104704E+11 | 0.247872E+10 |
October | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.124651E+11 | 0.387464E+10 |
November | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.128427E+11 | 0.584072E+10 |
December | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.122592E+11 | 0.748230E+10 |
Annual Sum or Average | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.113614E+12 | 0.470829E+11 |
Minimum of Months | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.590291E+10 | 0.946846E+09 |
Maximum of Months | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.128427E+11 | 0.748230E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.271930E+10 | 0.492860E+10 |
February | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.296165E+10 | 0.409279E+10 |
March | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.492171E+10 | 0.394253E+10 |
April | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.644528E+10 | 0.244819E+10 |
May | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.807132E+10 | 0.161043E+10 |
June | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.865757E+10 | 0.870188E+09 |
July | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.794136E+10 | 0.745240E+09 |
August | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.737335E+10 | 0.972937E+09 |
September | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.692399E+10 | 0.173625E+10 |
October | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.531296E+10 | 0.267568E+10 |
November | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.353861E+10 | 0.413949E+10 |
December | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.244635E+10 | 0.541802E+10 |
Annual Sum or Average | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.673134E+11 | 0.335803E+11 |
Minimum of Months | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.244635E+10 | 0.745240E+09 |
Maximum of Months | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.865757E+10 | 0.541802E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.62 | 3365.87 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 179.53 | 2987.14 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 440.83 | 2509.44 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 992.45 | 1443.83 | 948.49 | 7.47 | 941.02 | 0.00 | 0.00 |
May | 1770.40 | 810.77 | 1124.94 | 81.35 | 1043.60 | 0.00 | 0.00 |
June | 2537.94 | 417.42 | 1196.19 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2328.40 | 330.01 | 1105.51 | 107.61 | 997.90 | 0.00 | 0.00 |
August | 1780.66 | 472.11 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1343.51 | 964.30 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 630.56 | 1626.50 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 103.15 | 2918.76 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 22.17 | 3832.40 | 510.08 | 0.00 | 510.08 | 0.00 | 0.00 |
Annual Sum or Average | 1018.18 | 1800.90 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 22.17 | 330.01 | 510.08 | 0.00 | 510.08 | 0.00 | 0.00 |
Maximum of Months | 2537.94 | 3832.40 | 1196.19 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 788.91 | 2015.98 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1276.39 | 1772.40 | 1226.34 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1759.14 | 1479.06 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2603.59 | 857.99 | 1824.44 | 1012.16 | 812.28 | 0.00 | 0.00 |
May | 3071.52 | 532.43 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3517.42 | 258.35 | 1883.78 | 1047.99 | 835.80 | 0.00 | 0.00 |
July | 3171.87 | 195.93 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2896.95 | 274.36 | 1607.50 | 822.71 | 784.80 | 0.00 | 0.00 |
September | 2651.60 | 593.88 | 1592.60 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1674.61 | 996.61 | 1224.81 | 661.02 | 563.79 | 0.00 | 0.00 |
November | 1117.48 | 1708.06 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 735.29 | 2230.71 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2108.19 | 1073.02 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 735.29 | 195.93 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3517.42 | 2230.71 | 1883.78 | 1047.99 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4531.33 | 2899.74 | 3516.64 | 2664.22 | 852.42 | 0.00 | 0.00 |
February | 4275.69 | 2633.80 | 3262.08 | 2299.71 | 962.36 | 0.00 | 0.00 |
March | 3571.00 | 2335.12 | 2651.11 | 1528.62 | 1122.49 | 0.00 | 0.00 |
April | 2766.58 | 1467.26 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2212.14 | 865.81 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2405.25 | 427.13 | 1095.89 | 69.53 | 1026.36 | 0.00 | 0.00 |
July | 2426.82 | 341.17 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2881.34 | 496.08 | 1424.05 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4082.98 | 987.14 | 2222.78 | 1154.81 | 1067.97 | 0.00 | 0.00 |
October | 4678.88 | 1566.45 | 3020.10 | 2041.79 | 978.31 | 0.00 | 0.00 |
November | 4930.04 | 2527.40 | 3634.41 | 2770.79 | 863.62 | 0.00 | 0.00 |
December | 4508.69 | 3171.60 | 3601.84 | 2703.71 | 898.14 | 0.00 | 0.00 |
Annual Sum or Average | 3601.04 | 1638.27 | 2379.42 | 1374.97 | 1004.46 | 0.00 | 0.00 |
Minimum of Months | 2212.14 | 341.17 | 1095.89 | 69.53 | 852.42 | 0.00 | 0.00 |
Maximum of Months | 4930.04 | 3171.60 | 3634.41 | 2770.79 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 954.51 | 2243.54 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1152.83 | 2081.17 | 1089.52 | 579.10 | 510.42 | 0.00 | 0.00 |
March | 1765.96 | 1812.37 | 1484.70 | 795.75 | 688.95 | 0.00 | 0.00 |
April | 2429.05 | 1148.95 | 1706.54 | 921.73 | 784.81 | 0.00 | 0.00 |
May | 3022.75 | 666.70 | 1838.11 | 983.47 | 854.64 | 0.00 | 0.00 |
June | 3329.60 | 367.64 | 1789.25 | 961.03 | 828.23 | 0.00 | 0.00 |
July | 2937.47 | 316.70 | 1587.84 | 789.03 | 798.81 | 0.00 | 0.00 |
August | 2700.73 | 458.63 | 1537.74 | 783.69 | 754.05 | 0.00 | 0.00 |
September | 2666.71 | 739.11 | 1572.58 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 1932.90 | 1206.18 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1283.44 | 2061.51 | 1136.26 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 818.81 | 2666.47 | 915.66 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2086.77 | 1310.35 | 1415.97 | 768.26 | 647.71 | 0.00 | 0.00 |
Minimum of Months | 818.81 | 316.70 | 915.66 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3329.60 | 2666.47 | 1838.11 | 983.47 | 854.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 80.09 | 2975.17 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 242.73 | 2668.82 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 509.32 | 2257.11 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 1051.45 | 1321.37 | 948.49 | 7.47 | 941.01 | 0.00 | 0.00 |
May | 1795.99 | 769.94 | 1124.94 | 81.35 | 1043.59 | 0.00 | 0.00 |
June | 2563.30 | 416.01 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2356.65 | 331.54 | 1105.50 | 107.61 | 997.89 | 0.00 | 0.00 |
August | 1827.96 | 451.49 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1372.98 | 911.88 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 685.72 | 1467.64 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 159.99 | 2541.88 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 52.86 | 3306.06 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Annual Sum or Average | 1062.45 | 1613.12 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 52.86 | 331.54 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Maximum of Months | 2563.30 | 3306.06 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 818.61 | 1831.63 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1295.32 | 1645.25 | 1226.33 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1765.18 | 1396.12 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2584.00 | 841.26 | 1824.43 | 1012.15 | 812.28 | 0.00 | 0.00 |
May | 3048.97 | 520.50 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3492.69 | 275.28 | 1883.78 | 1047.98 | 835.80 | 0.00 | 0.00 |
July | 3146.03 | 222.89 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2875.04 | 302.08 | 1607.50 | 822.70 | 784.79 | 0.00 | 0.00 |
September | 2636.57 | 582.61 | 1592.59 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1677.08 | 936.02 | 1224.80 | 661.01 | 563.79 | 0.00 | 0.00 |
November | 1140.06 | 1563.20 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 769.22 | 2021.72 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2106.77 | 1008.49 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 769.22 | 222.89 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3492.69 | 2021.72 | 1883.78 | 1047.98 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4489.37 | 2820.67 | 3516.63 | 2664.21 | 852.41 | 0.00 | 0.00 |
February | 4237.90 | 2558.17 | 3262.06 | 2299.70 | 962.36 | 0.00 | 0.00 |
March | 3542.29 | 2248.10 | 2651.10 | 1528.62 | 1122.48 | 0.00 | 0.00 |
April | 2764.41 | 1403.14 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2221.97 | 832.54 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2437.14 | 423.98 | 1095.89 | 69.53 | 1026.35 | 0.00 | 0.00 |
July | 2454.39 | 343.81 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2903.52 | 487.06 | 1424.04 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4060.84 | 968.24 | 2222.77 | 1154.81 | 1067.96 | 0.00 | 0.00 |
October | 4644.69 | 1518.93 | 3020.09 | 2041.78 | 978.31 | 0.00 | 0.00 |
November | 4901.60 | 2433.77 | 3634.40 | 2770.78 | 863.62 | 0.00 | 0.00 |
December | 4497.74 | 3038.00 | 3601.83 | 2703.70 | 898.13 | 0.00 | 0.00 |
Annual Sum or Average | 3591.66 | 1584.83 | 2379.41 | 1374.96 | 1004.45 | 0.00 | 0.00 |
Minimum of Months | 2221.97 | 343.81 | 1095.89 | 69.53 | 852.41 | 0.00 | 0.00 |
Maximum of Months | 4901.60 | 3038.00 | 3634.40 | 2770.78 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 994.76 | 1984.57 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1206.21 | 1807.72 | 1089.51 | 579.10 | 510.41 | 0.00 | 0.00 |
March | 1825.10 | 1558.40 | 1484.69 | 795.74 | 688.95 | 0.00 | 0.00 |
April | 2490.72 | 979.40 | 1706.53 | 921.73 | 784.80 | 0.00 | 0.00 |
May | 3030.33 | 611.63 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
June | 3363.55 | 333.34 | 1789.25 | 961.02 | 828.22 | 0.00 | 0.00 |
July | 2990.64 | 273.06 | 1587.83 | 789.02 | 798.81 | 0.00 | 0.00 |
August | 2772.99 | 363.12 | 1537.73 | 783.69 | 754.04 | 0.00 | 0.00 |
September | 2683.91 | 678.79 | 1572.57 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 1977.89 | 1049.19 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1346.18 | 1723.71 | 1136.25 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 890.38 | 2181.04 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2134.93 | 1125.27 | 1415.96 | 768.26 | 647.70 | 0.00 | 0.00 |
Minimum of Months | 890.38 | 273.06 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3363.55 | 2181.04 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.95 | 2700.61 | 514.06 | 0.00 | 514.06 | 0.00 | 0.00 |
February | 286.69 | 2450.90 | 627.72 | 0.00 | 627.72 | 0.00 | 0.00 |
March | 552.23 | 2097.38 | 821.48 | 0.00 | 821.48 | 0.00 | 0.00 |
April | 1062.12 | 1258.48 | 948.49 | 7.47 | 941.01 | 0.00 | 0.00 |
May | 1783.45 | 757.89 | 1124.94 | 81.35 | 1043.59 | 0.00 | 0.00 |
June | 2531.10 | 422.01 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
July | 2317.48 | 341.76 | 1105.50 | 107.61 | 997.89 | 0.00 | 0.00 |
August | 1799.38 | 452.74 | 932.18 | 19.06 | 913.12 | 0.00 | 0.00 |
September | 1361.08 | 895.09 | 813.41 | 0.32 | 813.09 | 0.00 | 0.00 |
October | 711.26 | 1369.55 | 675.36 | 0.00 | 675.36 | 0.00 | 0.00 |
November | 198.82 | 2296.04 | 545.21 | 0.00 | 545.21 | 0.00 | 0.00 |
December | 85.90 | 3007.35 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Annual Sum or Average | 1071.28 | 1499.50 | 818.81 | 30.41 | 788.40 | 0.00 | 0.00 |
Minimum of Months | 85.90 | 341.76 | 510.07 | 0.00 | 510.07 | 0.00 | 0.00 |
Maximum of Months | 2531.10 | 3007.35 | 1196.18 | 147.26 | 1048.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 864.35 | 1670.19 | 916.61 | 497.23 | 419.38 | 0.00 | 0.00 |
February | 1338.68 | 1524.29 | 1226.33 | 699.00 | 527.33 | 0.00 | 0.00 |
March | 1793.00 | 1319.45 | 1514.12 | 834.23 | 679.89 | 0.00 | 0.00 |
April | 2579.93 | 817.35 | 1824.43 | 1012.15 | 812.28 | 0.00 | 0.00 |
May | 3030.98 | 516.73 | 1882.72 | 1023.19 | 859.53 | 0.00 | 0.00 |
June | 3464.99 | 280.16 | 1883.78 | 1047.98 | 835.80 | 0.00 | 0.00 |
July | 3114.35 | 230.19 | 1689.34 | 883.16 | 806.18 | 0.00 | 0.00 |
August | 2850.62 | 305.00 | 1607.50 | 822.70 | 784.79 | 0.00 | 0.00 |
September | 2622.60 | 578.69 | 1592.59 | 908.69 | 683.90 | 0.00 | 0.00 |
October | 1686.00 | 890.37 | 1224.80 | 661.01 | 563.79 | 0.00 | 0.00 |
November | 1181.00 | 1436.15 | 1097.93 | 639.18 | 458.75 | 0.00 | 0.00 |
December | 820.47 | 1846.07 | 915.82 | 485.22 | 430.60 | 0.00 | 0.00 |
Annual Sum or Average | 2114.77 | 948.41 | 1448.16 | 792.39 | 655.77 | 0.00 | 0.00 |
Minimum of Months | 820.47 | 230.19 | 915.82 | 485.22 | 419.38 | 0.00 | 0.00 |
Maximum of Months | 3464.99 | 1846.07 | 1883.78 | 1047.98 | 859.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4547.14 | 2589.71 | 3516.63 | 2664.21 | 852.41 | 0.00 | 0.00 |
February | 4284.27 | 2375.61 | 3262.06 | 2299.70 | 962.36 | 0.00 | 0.00 |
March | 3573.91 | 2118.51 | 2651.10 | 1528.62 | 1122.48 | 0.00 | 0.00 |
April | 2762.24 | 1347.96 | 1797.44 | 670.67 | 1126.77 | 0.00 | 0.00 |
May | 2203.89 | 816.64 | 1270.23 | 177.79 | 1092.44 | 0.00 | 0.00 |
June | 2405.76 | 428.89 | 1095.89 | 69.53 | 1026.35 | 0.00 | 0.00 |
July | 2414.77 | 353.51 | 1117.14 | 103.56 | 1013.58 | 0.00 | 0.00 |
August | 2872.69 | 488.78 | 1424.04 | 376.95 | 1047.09 | 0.00 | 0.00 |
September | 4039.51 | 956.30 | 2222.77 | 1154.81 | 1067.96 | 0.00 | 0.00 |
October | 4653.92 | 1446.63 | 3020.09 | 2041.78 | 978.31 | 0.00 | 0.00 |
November | 4954.76 | 2253.36 | 3634.40 | 2770.78 | 863.62 | 0.00 | 0.00 |
December | 4577.08 | 2793.57 | 3601.83 | 2703.70 | 898.13 | 0.00 | 0.00 |
Annual Sum or Average | 3602.67 | 1492.99 | 2379.41 | 1374.96 | 1004.45 | 0.00 | 0.00 |
Minimum of Months | 2203.89 | 353.51 | 1095.89 | 69.53 | 852.41 | 0.00 | 0.00 |
Maximum of Months | 4954.76 | 2793.57 | 3634.40 | 2770.78 | 1126.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1015.27 | 1840.13 | 965.54 | 543.77 | 421.78 | 0.00 | 0.00 |
February | 1224.23 | 1691.80 | 1089.51 | 579.10 | 510.41 | 0.00 | 0.00 |
March | 1837.55 | 1471.97 | 1484.69 | 795.74 | 688.95 | 0.00 | 0.00 |
April | 2486.60 | 944.52 | 1706.53 | 921.73 | 784.80 | 0.00 | 0.00 |
May | 3013.49 | 601.27 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
June | 3340.11 | 335.72 | 1789.25 | 961.02 | 828.22 | 0.00 | 0.00 |
July | 2964.96 | 278.24 | 1587.83 | 789.02 | 798.81 | 0.00 | 0.00 |
August | 2752.89 | 363.25 | 1537.73 | 783.69 | 754.04 | 0.00 | 0.00 |
September | 2671.29 | 669.85 | 1572.57 | 876.08 | 696.49 | 0.00 | 0.00 |
October | 1983.63 | 998.99 | 1353.73 | 790.08 | 563.65 | 0.00 | 0.00 |
November | 1365.21 | 1597.02 | 1136.25 | 691.86 | 444.40 | 0.00 | 0.00 |
December | 913.36 | 2022.86 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Annual Sum or Average | 2134.50 | 1064.83 | 1415.96 | 768.26 | 647.70 | 0.00 | 0.00 |
Minimum of Months | 913.36 | 278.24 | 915.65 | 497.41 | 418.24 | 0.00 | 0.00 |
Maximum of Months | 3340.11 | 2022.86 | 1838.10 | 983.47 | 854.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 98078030.40 | 0.901514E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.434308E+09 | 0.722648E+10 | 0.151858E+10 | 0.00 | 0.151858E+10 | 0.00 | 0.00 |
March | 0.118072E+10 | 0.672128E+10 | 0.220025E+10 | 0.00 | 0.220025E+10 | 0.00 | 0.00 |
April | 0.257243E+10 | 0.374239E+10 | 0.245849E+10 | 19369321.27 | 0.243912E+10 | 0.00 | 0.00 |
May | 0.474185E+10 | 0.217156E+10 | 0.301305E+10 | 0.217886E+09 | 0.279517E+10 | 0.00 | 0.00 |
June | 0.657833E+10 | 0.108196E+10 | 0.310051E+10 | 0.381709E+09 | 0.271880E+10 | 0.00 | 0.00 |
July | 0.623637E+10 | 0.883906E+09 | 0.296099E+10 | 0.288230E+09 | 0.267276E+10 | 0.00 | 0.00 |
August | 0.476931E+10 | 0.126449E+10 | 0.249676E+10 | 51052290.93 | 0.244571E+10 | 0.00 | 0.00 |
September | 0.348239E+10 | 0.249948E+10 | 0.210837E+10 | 841315.33 | 0.210753E+10 | 0.00 | 0.00 |
October | 0.168890E+10 | 0.435643E+10 | 0.180888E+10 | 0.00 | 0.180888E+10 | 0.00 | 0.00 |
November | 0.267356E+09 | 0.756543E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 59375219.88 | 0.102647E+11 | 0.136619E+10 | 0.00 | 0.136619E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.321094E+11 | 0.567932E+11 | 0.258221E+11 | 0.959088E+09 | 0.248630E+11 | 0.00 | 0.00 |
Minimum of Months | 59375219.88 | 0.883906E+09 | 0.136619E+10 | 0.00 | 0.136619E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657833E+10 | 0.102647E+11 | 0.310051E+10 | 0.381709E+09 | 0.279517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.211301E+10 | 0.539961E+10 | 0.245505E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.308785E+10 | 0.428778E+10 | 0.296675E+10 | 0.169103E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.471169E+10 | 0.396151E+10 | 0.405542E+10 | 0.223441E+10 | 0.182102E+10 | 0.00 | 0.00 |
April | 0.674851E+10 | 0.222391E+10 | 0.472895E+10 | 0.262351E+10 | 0.210544E+10 | 0.00 | 0.00 |
May | 0.822676E+10 | 0.142605E+10 | 0.504269E+10 | 0.274051E+10 | 0.230217E+10 | 0.00 | 0.00 |
June | 0.911716E+10 | 0.669653E+09 | 0.488277E+10 | 0.271638E+10 | 0.216639E+10 | 0.00 | 0.00 |
July | 0.849554E+10 | 0.524784E+09 | 0.452474E+10 | 0.236546E+10 | 0.215928E+10 | 0.00 | 0.00 |
August | 0.775919E+10 | 0.734856E+09 | 0.430553E+10 | 0.220353E+10 | 0.210200E+10 | 0.00 | 0.00 |
September | 0.687296E+10 | 0.153935E+10 | 0.412802E+10 | 0.235533E+10 | 0.177268E+10 | 0.00 | 0.00 |
October | 0.448528E+10 | 0.266932E+10 | 0.328053E+10 | 0.177047E+10 | 0.151006E+10 | 0.00 | 0.00 |
November | 0.289652E+10 | 0.442729E+10 | 0.284584E+10 | 0.165676E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.196940E+10 | 0.597474E+10 | 0.245294E+10 | 0.129962E+10 | 0.115332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.664839E+11 | 0.338389E+11 | 0.456692E+11 | 0.249888E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196940E+10 | 0.524784E+09 | 0.245294E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.911716E+10 | 0.597474E+10 | 0.504269E+10 | 0.274051E+10 | 0.230217E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121367E+11 | 0.776667E+10 | 0.941897E+10 | 0.713585E+10 | 0.228312E+10 | 0.00 | 0.00 |
February | 0.103437E+11 | 0.637168E+10 | 0.789161E+10 | 0.556346E+10 | 0.232815E+10 | 0.00 | 0.00 |
March | 0.956458E+10 | 0.625438E+10 | 0.710074E+10 | 0.409427E+10 | 0.300647E+10 | 0.00 | 0.00 |
April | 0.717099E+10 | 0.380313E+10 | 0.465898E+10 | 0.173838E+10 | 0.292059E+10 | 0.00 | 0.00 |
May | 0.592500E+10 | 0.231898E+10 | 0.340220E+10 | 0.476196E+09 | 0.292600E+10 | 0.00 | 0.00 |
June | 0.623440E+10 | 0.110713E+10 | 0.284055E+10 | 0.180234E+09 | 0.266032E+10 | 0.00 | 0.00 |
July | 0.649999E+10 | 0.913784E+09 | 0.299215E+10 | 0.277378E+09 | 0.271477E+10 | 0.00 | 0.00 |
August | 0.771737E+10 | 0.132869E+10 | 0.381417E+10 | 0.100963E+10 | 0.280454E+10 | 0.00 | 0.00 |
September | 0.105831E+11 | 0.255866E+10 | 0.576144E+10 | 0.299327E+10 | 0.276817E+10 | 0.00 | 0.00 |
October | 0.125319E+11 | 0.419558E+10 | 0.808903E+10 | 0.546873E+10 | 0.262031E+10 | 0.00 | 0.00 |
November | 0.127787E+11 | 0.655101E+10 | 0.942040E+10 | 0.718190E+10 | 0.223850E+10 | 0.00 | 0.00 |
December | 0.120761E+11 | 0.849480E+10 | 0.964718E+10 | 0.724161E+10 | 0.240557E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113563E+12 | 0.516645E+11 | 0.750374E+11 | 0.433609E+11 | 0.316765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.592500E+10 | 0.913784E+09 | 0.284055E+10 | 0.180234E+09 | 0.223850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127787E+11 | 0.849480E+10 | 0.964718E+10 | 0.724161E+10 | 0.300647E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255656E+10 | 0.600909E+10 | 0.258612E+10 | 0.145643E+10 | 0.112969E+10 | 0.00 | 0.00 |
February | 0.278893E+10 | 0.503477E+10 | 0.263576E+10 | 0.140096E+10 | 0.123480E+10 | 0.00 | 0.00 |
March | 0.472995E+10 | 0.485425E+10 | 0.397662E+10 | 0.213133E+10 | 0.184529E+10 | 0.00 | 0.00 |
April | 0.629611E+10 | 0.297807E+10 | 0.442335E+10 | 0.238913E+10 | 0.203422E+10 | 0.00 | 0.00 |
May | 0.809614E+10 | 0.178569E+10 | 0.492318E+10 | 0.263413E+10 | 0.228906E+10 | 0.00 | 0.00 |
June | 0.863032E+10 | 0.952916E+09 | 0.463774E+10 | 0.249098E+10 | 0.214677E+10 | 0.00 | 0.00 |
July | 0.786773E+10 | 0.848244E+09 | 0.425286E+10 | 0.211333E+10 | 0.213953E+10 | 0.00 | 0.00 |
August | 0.723363E+10 | 0.122840E+10 | 0.411868E+10 | 0.209904E+10 | 0.201964E+10 | 0.00 | 0.00 |
September | 0.691210E+10 | 0.191577E+10 | 0.407612E+10 | 0.227081E+10 | 0.180531E+10 | 0.00 | 0.00 |
October | 0.517708E+10 | 0.323064E+10 | 0.362583E+10 | 0.211615E+10 | 0.150968E+10 | 0.00 | 0.00 |
November | 0.332667E+10 | 0.534345E+10 | 0.294518E+10 | 0.179330E+10 | 0.115188E+10 | 0.00 | 0.00 |
December | 0.219309E+10 | 0.714188E+10 | 0.245250E+10 | 0.133228E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.658083E+11 | 0.413232E+11 | 0.446539E+11 | 0.242279E+11 | 0.204261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219309E+10 | 0.848244E+09 | 0.245250E+10 | 0.133228E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.863032E+10 | 0.714188E+10 | 0.492318E+10 | 0.263413E+10 | 0.228906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214516E+09 | 0.796871E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.587223E+09 | 0.645642E+10 | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.00 | 0.00 |
March | 0.136417E+10 | 0.604543E+10 | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.00 | 0.00 |
April | 0.272535E+10 | 0.342498E+10 | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.00 | 0.00 |
May | 0.481039E+10 | 0.206222E+10 | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.00 | 0.00 |
June | 0.664408E+10 | 0.107831E+10 | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.00 | 0.00 |
July | 0.631204E+10 | 0.887985E+09 | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.00 | 0.00 |
August | 0.489600E+10 | 0.120927E+10 | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.00 | 0.00 |
September | 0.355877E+10 | 0.236359E+10 | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.00 | 0.00 |
October | 0.183664E+10 | 0.393093E+10 | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.00 | 0.00 |
November | 0.414693E+09 | 0.658856E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 0.141570E+09 | 0.885494E+10 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335054E+11 | 0.508713E+11 | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141570E+09 | 0.887985E+09 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Maximum of Months | 0.664408E+10 | 0.885494E+10 | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219256E+10 | 0.490584E+10 | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.313364E+10 | 0.398019E+10 | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.472786E+10 | 0.373936E+10 | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.00 | 0.00 |
April | 0.669774E+10 | 0.218056E+10 | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.00 | 0.00 |
May | 0.816636E+10 | 0.139412E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
June | 0.905306E+10 | 0.713532E+09 | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.00 | 0.00 |
July | 0.842634E+10 | 0.596976E+09 | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.00 | 0.00 |
August | 0.770051E+10 | 0.809078E+09 | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.00 | 0.00 |
September | 0.683400E+10 | 0.151012E+10 | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.00 | 0.00 |
October | 0.449190E+10 | 0.250704E+10 | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.00 | 0.00 |
November | 0.295503E+10 | 0.405182E+10 | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.206027E+10 | 0.541498E+10 | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.664393E+11 | 0.318036E+11 | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.206027E+10 | 0.596976E+09 | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.905306E+10 | 0.541498E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120243E+11 | 0.755488E+10 | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.00 | 0.00 |
February | 0.102523E+11 | 0.618873E+10 | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.00 | 0.00 |
March | 0.948768E+10 | 0.602132E+10 | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.00 | 0.00 |
April | 0.716534E+10 | 0.363693E+10 | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.00 | 0.00 |
May | 0.595134E+10 | 0.222987E+10 | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.00 | 0.00 |
June | 0.631707E+10 | 0.109896E+10 | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.00 | 0.00 |
July | 0.657385E+10 | 0.920851E+09 | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.00 | 0.00 |
August | 0.777678E+10 | 0.130453E+10 | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.00 | 0.00 |
September | 0.105257E+11 | 0.250967E+10 | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.00 | 0.00 |
October | 0.124403E+11 | 0.406830E+10 | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.00 | 0.00 |
November | 0.127049E+11 | 0.630832E+10 | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.00 | 0.00 |
December | 0.120468E+11 | 0.813698E+10 | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113266E+12 | 0.499793E+11 | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.595134E+10 | 0.920851E+09 | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127049E+11 | 0.813698E+10 | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266435E+10 | 0.531547E+10 | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.00 | 0.00 |
February | 0.291805E+10 | 0.437325E+10 | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.00 | 0.00 |
March | 0.488834E+10 | 0.417401E+10 | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.00 | 0.00 |
April | 0.645595E+10 | 0.253860E+10 | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.00 | 0.00 |
May | 0.811644E+10 | 0.163820E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
June | 0.871831E+10 | 0.864014E+09 | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.00 | 0.00 |
July | 0.801013E+10 | 0.731372E+09 | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.00 | 0.00 |
August | 0.742717E+10 | 0.972570E+09 | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.00 | 0.00 |
September | 0.695669E+10 | 0.175942E+10 | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.00 | 0.00 |
October | 0.529757E+10 | 0.281014E+10 | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.00 | 0.00 |
November | 0.348931E+10 | 0.446785E+10 | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.00 | 0.00 |
December | 0.238480E+10 | 0.584170E+10 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.673271E+11 | 0.354866E+11 | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238480E+10 | 0.731372E+09 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.871831E+10 | 0.584170E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315927E+09 | 0.723330E+10 | 0.137685E+10 | 0.00 | 0.137685E+10 | 0.00 | 0.00 |
February | 0.693571E+09 | 0.592921E+10 | 0.151857E+10 | 0.00 | 0.151857E+10 | 0.00 | 0.00 |
March | 0.147909E+10 | 0.561761E+10 | 0.220024E+10 | 0.00 | 0.220024E+10 | 0.00 | 0.00 |
April | 0.275300E+10 | 0.326199E+10 | 0.245848E+10 | 19369252.49 | 0.243911E+10 | 0.00 | 0.00 |
May | 0.477678E+10 | 0.202992E+10 | 0.301304E+10 | 0.217885E+09 | 0.279516E+10 | 0.00 | 0.00 |
June | 0.656061E+10 | 0.109385E+10 | 0.310050E+10 | 0.381708E+09 | 0.271879E+10 | 0.00 | 0.00 |
July | 0.620713E+10 | 0.915371E+09 | 0.296098E+10 | 0.288229E+09 | 0.267275E+10 | 0.00 | 0.00 |
August | 0.481946E+10 | 0.121261E+10 | 0.249675E+10 | 51052109.64 | 0.244570E+10 | 0.00 | 0.00 |
September | 0.352793E+10 | 0.232007E+10 | 0.210836E+10 | 841312.35 | 0.210752E+10 | 0.00 | 0.00 |
October | 0.190503E+10 | 0.366820E+10 | 0.180887E+10 | 0.00 | 0.180887E+10 | 0.00 | 0.00 |
November | 0.515331E+09 | 0.595133E+10 | 0.141319E+10 | 0.00 | 0.141319E+10 | 0.00 | 0.00 |
December | 0.230079E+09 | 0.805489E+10 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.337839E+11 | 0.472884E+11 | 0.258220E+11 | 0.959085E+09 | 0.248629E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230079E+09 | 0.915371E+09 | 0.136618E+10 | 0.00 | 0.136618E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656061E+10 | 0.805489E+10 | 0.310050E+10 | 0.381708E+09 | 0.279516E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231507E+10 | 0.447344E+10 | 0.245504E+10 | 0.133177E+10 | 0.112327E+10 | 0.00 | 0.00 |
February | 0.323855E+10 | 0.368757E+10 | 0.296674E+10 | 0.169102E+10 | 0.127572E+10 | 0.00 | 0.00 |
March | 0.480237E+10 | 0.353403E+10 | 0.405541E+10 | 0.223440E+10 | 0.182101E+10 | 0.00 | 0.00 |
April | 0.668719E+10 | 0.211856E+10 | 0.472893E+10 | 0.262350E+10 | 0.210543E+10 | 0.00 | 0.00 |
May | 0.811819E+10 | 0.138400E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
June | 0.898125E+10 | 0.726172E+09 | 0.488275E+10 | 0.271637E+10 | 0.216638E+10 | 0.00 | 0.00 |
July | 0.834146E+10 | 0.616549E+09 | 0.452472E+10 | 0.236545E+10 | 0.215927E+10 | 0.00 | 0.00 |
August | 0.763509E+10 | 0.816924E+09 | 0.430552E+10 | 0.220352E+10 | 0.210199E+10 | 0.00 | 0.00 |
September | 0.679779E+10 | 0.149996E+10 | 0.412800E+10 | 0.235532E+10 | 0.177267E+10 | 0.00 | 0.00 |
October | 0.451578E+10 | 0.238477E+10 | 0.328051E+10 | 0.177046E+10 | 0.151005E+10 | 0.00 | 0.00 |
November | 0.306116E+10 | 0.372251E+10 | 0.284583E+10 | 0.165675E+10 | 0.118908E+10 | 0.00 | 0.00 |
December | 0.219756E+10 | 0.494451E+10 | 0.245293E+10 | 0.129962E+10 | 0.115331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.666915E+11 | 0.299090E+11 | 0.456690E+11 | 0.249887E+11 | 0.206804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219756E+10 | 0.616549E+09 | 0.245293E+10 | 0.129962E+10 | 0.112327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898125E+10 | 0.494451E+10 | 0.504267E+10 | 0.274050E+10 | 0.230216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121791E+11 | 0.693629E+10 | 0.941893E+10 | 0.713583E+10 | 0.228311E+10 | 0.00 | 0.00 |
February | 0.103645E+11 | 0.574708E+10 | 0.789158E+10 | 0.556344E+10 | 0.232814E+10 | 0.00 | 0.00 |
March | 0.957237E+10 | 0.567421E+10 | 0.710072E+10 | 0.409425E+10 | 0.300646E+10 | 0.00 | 0.00 |
April | 0.715973E+10 | 0.349391E+10 | 0.465896E+10 | 0.173837E+10 | 0.292058E+10 | 0.00 | 0.00 |
May | 0.590291E+10 | 0.218730E+10 | 0.340218E+10 | 0.476194E+09 | 0.292599E+10 | 0.00 | 0.00 |
June | 0.623572E+10 | 0.111168E+10 | 0.284054E+10 | 0.180233E+09 | 0.266031E+10 | 0.00 | 0.00 |
July | 0.646773E+10 | 0.946846E+09 | 0.299214E+10 | 0.277377E+09 | 0.271476E+10 | 0.00 | 0.00 |
August | 0.769420E+10 | 0.130915E+10 | 0.381415E+10 | 0.100963E+10 | 0.280452E+10 | 0.00 | 0.00 |
September | 0.104704E+11 | 0.247872E+10 | 0.576142E+10 | 0.299326E+10 | 0.276816E+10 | 0.00 | 0.00 |
October | 0.124651E+11 | 0.387464E+10 | 0.808900E+10 | 0.546871E+10 | 0.262030E+10 | 0.00 | 0.00 |
November | 0.128427E+11 | 0.584072E+10 | 0.942036E+10 | 0.718187E+10 | 0.223849E+10 | 0.00 | 0.00 |
December | 0.122592E+11 | 0.748230E+10 | 0.964714E+10 | 0.724158E+10 | 0.240556E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113614E+12 | 0.470829E+11 | 0.750371E+11 | 0.433607E+11 | 0.316764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.590291E+10 | 0.946846E+09 | 0.284054E+10 | 0.180233E+09 | 0.223849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.128427E+11 | 0.748230E+10 | 0.964714E+10 | 0.724158E+10 | 0.300646E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271930E+10 | 0.492860E+10 | 0.258610E+10 | 0.145642E+10 | 0.112968E+10 | 0.00 | 0.00 |
February | 0.296165E+10 | 0.409279E+10 | 0.263575E+10 | 0.140096E+10 | 0.123479E+10 | 0.00 | 0.00 |
March | 0.492171E+10 | 0.394253E+10 | 0.397660E+10 | 0.213132E+10 | 0.184528E+10 | 0.00 | 0.00 |
April | 0.644528E+10 | 0.244819E+10 | 0.442333E+10 | 0.238912E+10 | 0.203421E+10 | 0.00 | 0.00 |
May | 0.807132E+10 | 0.161043E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
June | 0.865757E+10 | 0.870188E+09 | 0.463773E+10 | 0.249097E+10 | 0.214676E+10 | 0.00 | 0.00 |
July | 0.794136E+10 | 0.745240E+09 | 0.425284E+10 | 0.211332E+10 | 0.213952E+10 | 0.00 | 0.00 |
August | 0.737335E+10 | 0.972937E+09 | 0.411866E+10 | 0.209903E+10 | 0.201963E+10 | 0.00 | 0.00 |
September | 0.692399E+10 | 0.173625E+10 | 0.407610E+10 | 0.227080E+10 | 0.180530E+10 | 0.00 | 0.00 |
October | 0.531296E+10 | 0.267568E+10 | 0.362582E+10 | 0.211615E+10 | 0.150967E+10 | 0.00 | 0.00 |
November | 0.353861E+10 | 0.413949E+10 | 0.294517E+10 | 0.179329E+10 | 0.115187E+10 | 0.00 | 0.00 |
December | 0.244635E+10 | 0.541802E+10 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.673134E+11 | 0.335803E+11 | 0.446538E+11 | 0.242278E+11 | 0.204260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244635E+10 | 0.745240E+09 | 0.245249E+10 | 0.133227E+10 | 0.112022E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865757E+10 | 0.541802E+10 | 0.492316E+10 | 0.263412E+10 | 0.228905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.358849E+11 | -0.348616E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102325E+10 | 58.98 | 0.00 | 0.00 |
February | 0.325791E+11 | -0.316537E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925380364.4 | 58.98 | 0.00 | 0.00 |
March | 0.368884E+11 | -0.358606E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102781E+10 | 58.98 | 0.00 | 0.00 |
April | 0.313434E+11 | -0.303539E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989567506.2 | 58.98 | 0.00 | 0.00 |
May | 0.307864E+11 | -0.297635E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102292E+10 | 58.98 | 0.00 | 0.00 |
June | 0.281467E+11 | -0.271562E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990466855.2 | 58.97 | 0.00 | 0.00 |
July | 0.255666E+11 | -0.245491E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101745E+10 | 58.97 | 0.00 | 0.00 |
August | 0.279293E+11 | -0.269084E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102093E+10 | 58.98 | 0.00 | 0.00 |
September | 0.266908E+11 | -0.257060E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984858676.5 | 58.97 | 0.00 | 0.00 |
October | 0.297912E+11 | -0.287742E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101695E+10 | 58.97 | 0.00 | 0.00 |
November | 0.317419E+11 | -0.307569E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984990309.7 | 58.97 | 0.00 | 0.00 |
December | 0.337920E+11 | -0.327728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101922E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.371141E+12 | -0.359117E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120238E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.255666E+11 | -0.358606E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102781E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.368884E+11 | -0.245491E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925380364.4 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:20 | 8814.21 | 38.77 | 276.17 | 279.33 | 1869.39 | 27.23 | 182.17 | 263.00 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9489.66 | 37.14 | 262.00 | 269.50 | 1370.43 | 23.17 | 154.83 | 246.83 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:19 | 2008.79 | 20.00 | 68.83 | 322.83 | 1038.97 | 20.87 | 146.00 | 292.17 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:10 | 1281.35 | 19.36 | 28.00 | 337.50 | 784.75 | 20.69 | 135.50 | 297.33 |
May | 408.83 | 0.53 | 0.48 | 01-MAY-06:49 | 1058.08 | 19.03 | 0.17 | 363.00 | 645.83 | 20.38 | 112.00 | 325.00 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:49 | 952.48 | 18.94 | 0.00 | 355.83 | 596.88 | 20.39 | 59.50 | 316.83 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-06:49 | 1010.19 | 18.97 | 1.17 | 360.83 | 608.93 | 20.36 | 111.17 | 305.67 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:49 | 1188.30 | 19.32 | 15.83 | 349.17 | 713.47 | 20.65 | 145.00 | 300.33 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1500.09 | 19.75 | 51.00 | 319.67 | 881.84 | 20.64 | 131.33 | 283.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:10 | 3593.03 | 26.02 | 153.50 | 308.67 | 1213.81 | 21.43 | 139.33 | 285.83 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8983.49 | 37.67 | 288.50 | 288.00 | 1491.64 | 24.07 | 142.50 | 270.17 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 7981.01 | 38.04 | 284.33 | 276.33 | 1841.70 | 27.26 | 208.00 | 269.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3514.49 | 24.93 | 1429.50 | 3830.67 | 1028.45 | 21.97 | 1667.33 | 3455.83 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 952.48 | 18.94 | 0.00 | 269.50 | 596.88 | 20.36 | 59.50 | 246.83 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9489.66 | 38.77 | 288.50 | 363.00 | 1869.39 | 27.26 | 208.00 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:09 | 2434.38 | 24.31 | 94.67 | 250.33 | 1327.79 | 24.07 | 106.67 | 205.83 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2925.67 | 24.26 | 90.00 | 253.33 | 1087.00 | 22.57 | 92.17 | 214.67 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2665.02 | 23.42 | 103.17 | 313.33 | 1421.25 | 23.50 | 126.67 | 280.83 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 3404.56 | 24.21 | 119.67 | 340.67 | 1326.44 | 22.99 | 107.00 | 311.83 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2707.90 | 22.63 | 103.67 | 369.00 | 1481.50 | 23.11 | 96.83 | 339.17 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2761.52 | 22.75 | 100.00 | 361.33 | 1518.05 | 23.20 | 83.00 | 331.50 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 2451.32 | 22.69 | 100.67 | 368.17 | 1319.52 | 23.15 | 102.17 | 325.50 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 3074.22 | 23.89 | 120.67 | 352.17 | 1220.53 | 23.00 | 110.50 | 318.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2934.41 | 23.71 | 115.33 | 323.17 | 1141.33 | 22.50 | 109.00 | 289.67 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-06:40 | 2560.60 | 23.46 | 94.17 | 292.67 | 1388.54 | 23.58 | 103.00 | 257.67 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:50 | 2091.72 | 23.41 | 89.00 | 261.33 | 1112.73 | 23.39 | 90.17 | 218.83 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 1848.54 | 23.21 | 87.00 | 252.50 | 948.32 | 22.91 | 118.83 | 216.00 |
Annual Sum or Average | 4125.67 | 0.52 | 2681.23 | 23.45 | 1218.00 | 3738.00 | 1289.05 | 23.15 | 1246.00 | 3310.00 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1848.54 | 22.63 | 87.00 | 250.33 | 948.32 | 22.50 | 83.00 | 205.83 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 3404.56 | 24.31 | 120.67 | 369.00 | 1518.05 | 24.07 | 126.67 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:09 | 536.13 | 16.46 | 0.00 | 232.17 | 354.43 | 18.28 | 0.00 | 148.83 |
February | 268.33 | 0.55 | 0.48 | 01-FEB-09:30 | 610.60 | 17.16 | 0.00 | 235.17 | 403.47 | 18.85 | 0.00 | 172.00 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:09 | 716.70 | 17.93 | 0.00 | 306.17 | 458.94 | 19.39 | 8.17 | 244.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 848.39 | 19.05 | 0.00 | 349.83 | 540.09 | 20.38 | 54.50 | 310.50 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:10 | 1037.66 | 19.79 | 41.17 | 385.17 | 600.77 | 20.97 | 147.33 | 359.17 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:10 | 1112.00 | 22.67 | 107.00 | 381.67 | 631.60 | 21.38 | 138.33 | 357.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 1052.44 | 21.12 | 63.33 | 391.17 | 632.26 | 22.40 | 165.17 | 352.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 896.11 | 19.33 | 1.67 | 360.67 | 559.99 | 20.64 | 92.50 | 323.50 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:09 | 714.46 | 18.29 | 0.00 | 312.67 | 465.13 | 19.72 | 19.67 | 250.17 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-07:49 | 641.45 | 17.46 | 0.00 | 282.00 | 420.72 | 19.05 | 1.83 | 216.83 |
November | 295.83 | 0.57 | 0.48 | 01-NOV-13:09 | 520.90 | 16.46 | 0.00 | 241.50 | 348.43 | 18.23 | 0.00 | 149.67 |
December | 289.50 | 0.57 | 0.48 | 01-DEC-08:00 | 534.95 | 16.42 | 0.00 | 231.50 | 347.17 | 18.20 | 0.00 | 154.67 |
Annual Sum or Average | 4125.67 | 0.53 | 795.74 | 18.75 | 213.17 | 3709.67 | 494.28 | 19.96 | 627.50 | 3039.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 520.90 | 16.42 | 0.00 | 231.50 | 347.17 | 18.20 | 0.00 | 148.83 | |
Maximum of Months | 408.83 | 0.57 | 0.48 | 1112.00 | 22.67 | 107.00 | 391.17 | 632.26 | 22.40 | 165.17 | 359.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:09 | 2051.44 | 24.76 | 99.00 | 264.83 | 1105.18 | 24.46 | 109.33 | 217.50 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:30 | 2353.13 | 24.43 | 89.83 | 255.00 | 1268.19 | 24.34 | 102.67 | 216.00 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:09 | 2968.35 | 23.80 | 113.00 | 323.17 | 1130.97 | 22.39 | 123.50 | 287.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-07:49 | 3351.58 | 23.34 | 111.83 | 346.50 | 1314.23 | 22.34 | 100.83 | 313.50 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2598.87 | 17.43 | 0.00 | 376.83 | 1441.74 | 19.93 | 51.17 | 350.83 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2697.36 | 17.55 | 0.00 | 372.67 | 1479.96 | 20.02 | 45.67 | 343.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:10 | 2416.36 | 17.80 | 3.67 | 382.17 | 1324.35 | 20.04 | 65.67 | 337.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:19 | 2467.40 | 20.34 | 57.17 | 354.17 | 1279.93 | 20.11 | 57.83 | 314.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-08:09 | 2925.30 | 23.57 | 112.83 | 322.00 | 1150.29 | 22.44 | 122.83 | 287.17 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:00 | 2528.94 | 24.41 | 100.17 | 303.33 | 1341.33 | 24.25 | 105.33 | 265.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1890.11 | 23.29 | 86.83 | 269.50 | 942.96 | 22.92 | 81.17 | 224.33 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-08:50 | 2074.17 | 24.94 | 107.00 | 257.50 | 844.75 | 23.39 | 111.67 | 224.50 |
Annual Sum or Average | 4125.67 | 0.51 | 2561.53 | 21.80 | 881.33 | 3827.67 | 1236.04 | 22.00 | 1077.67 | 3382.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1890.11 | 17.43 | 0.00 | 255.00 | 844.75 | 19.93 | 45.67 | 216.00 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3351.58 | 24.94 | 113.00 | 382.17 | 1479.96 | 24.46 | 123.50 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:20 | 8895.67 | 38.37 | 275.83 | 279.33 | 1989.70 | 22.96 | 97.17 | 263.83 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9563.82 | 36.67 | 261.50 | 269.83 | 1477.45 | 18.67 | 34.83 | 249.83 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 2058.73 | 13.62 | 10.67 | 323.67 | 1120.13 | 16.58 | 1.83 | 297.33 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:10 | 1315.44 | 13.48 | 0.00 | 338.00 | 842.59 | 17.02 | 0.00 | 302.83 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:40 | 1081.99 | 13.47 | 0.00 | 363.83 | 690.61 | 16.95 | 0.00 | 332.17 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:40 | 974.63 | 13.28 | 0.00 | 356.67 | 638.04 | 16.87 | 0.00 | 325.00 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-06:40 | 1031.00 | 13.34 | 0.00 | 361.83 | 650.33 | 16.86 | 0.00 | 314.50 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:40 | 1215.93 | 13.57 | 0.00 | 349.67 | 763.93 | 17.06 | 0.00 | 307.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1548.43 | 13.68 | 11.00 | 321.17 | 949.77 | 16.70 | 0.00 | 287.83 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:10 | 3683.72 | 21.50 | 131.00 | 312.17 | 1320.22 | 17.20 | 13.33 | 288.67 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 9056.93 | 37.16 | 288.33 | 288.17 | 1637.76 | 21.28 | 90.00 | 275.33 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 8050.80 | 37.59 | 284.00 | 276.33 | 1958.21 | 23.03 | 101.33 | 270.00 |
Annual Sum or Average | 4125.67 | 0.51 | 3562.64 | 20.67 | 1262.33 | 3840.67 | 1105.59 | 18.17 | 338.50 | 3515.00 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 974.63 | 13.28 | 0.00 | 269.83 | 638.04 | 16.58 | 0.00 | 249.83 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9563.82 | 38.37 | 288.33 | 363.83 | 1989.70 | 23.03 | 101.33 | 332.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:09 | 2471.59 | 21.81 | 92.50 | 251.00 | 1376.53 | 22.18 | 63.33 | 212.50 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2973.53 | 21.66 | 89.67 | 254.33 | 1142.41 | 20.21 | 41.00 | 219.17 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2722.02 | 20.40 | 101.33 | 314.33 | 1484.64 | 21.11 | 71.00 | 285.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3415.06 | 20.26 | 109.83 | 340.50 | 1397.19 | 20.30 | 60.67 | 315.33 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2745.35 | 19.39 | 103.67 | 370.17 | 1553.86 | 20.49 | 72.67 | 343.50 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2813.95 | 19.39 | 100.00 | 364.33 | 1588.39 | 20.54 | 70.00 | 336.00 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 2492.38 | 19.37 | 100.67 | 369.67 | 1383.30 | 20.52 | 70.33 | 330.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 3105.78 | 21.00 | 120.50 | 353.33 | 1284.95 | 20.36 | 63.33 | 322.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2985.10 | 20.75 | 114.50 | 323.83 | 1202.74 | 19.83 | 57.67 | 294.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-06:40 | 2612.15 | 20.60 | 92.50 | 293.50 | 1445.21 | 21.34 | 63.50 | 264.00 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 2132.59 | 20.63 | 87.83 | 262.50 | 1163.10 | 21.28 | 61.00 | 226.50 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 1882.31 | 20.57 | 81.33 | 253.33 | 993.46 | 20.92 | 50.33 | 220.67 |
Annual Sum or Average | 4125.67 | 0.52 | 2722.07 | 20.40 | 1194.33 | 3750.83 | 1350.39 | 20.71 | 744.83 | 3370.83 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1882.31 | 19.37 | 81.33 | 251.00 | 993.46 | 19.83 | 41.00 | 212.50 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 3415.06 | 21.81 | 120.50 | 370.17 | 1588.39 | 22.18 | 72.67 | 343.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:09 | 546.14 | 10.70 | 0.00 | 233.67 | 377.94 | 14.54 | 0.00 | 166.00 |
February | 268.33 | 0.54 | 0.48 | 01-FEB-09:20 | 623.19 | 11.67 | 0.00 | 236.67 | 430.59 | 15.38 | 0.00 | 181.50 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:09 | 732.93 | 12.49 | 0.00 | 307.83 | 490.10 | 16.07 | 0.00 | 254.83 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 868.44 | 13.79 | 0.00 | 350.33 | 576.76 | 17.36 | 0.00 | 316.00 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 1061.24 | 14.29 | 3.00 | 385.50 | 642.58 | 17.76 | 0.00 | 362.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1138.11 | 18.01 | 83.17 | 381.67 | 676.05 | 17.87 | 1.33 | 360.83 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 1076.41 | 15.89 | 37.33 | 391.50 | 673.66 | 19.31 | 37.50 | 356.00 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 925.04 | 13.95 | 0.00 | 362.00 | 597.62 | 17.51 | 0.00 | 327.67 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-07:49 | 731.28 | 13.04 | 0.00 | 315.00 | 496.97 | 16.62 | 0.00 | 263.00 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-07:40 | 655.33 | 12.07 | 0.00 | 283.83 | 449.16 | 15.72 | 0.00 | 230.50 |
November | 295.83 | 0.56 | 0.48 | 01-NOV-12:00 | 531.48 | 10.76 | 0.00 | 243.00 | 371.83 | 14.59 | 0.00 | 168.67 |
December | 289.50 | 0.56 | 0.48 | 01-DEC-08:39 | 543.86 | 10.71 | 0.00 | 232.67 | 369.87 | 14.47 | 0.00 | 172.83 |
Annual Sum or Average | 4125.67 | 0.52 | 814.21 | 13.37 | 123.50 | 3723.67 | 527.79 | 16.63 | 38.83 | 3160.33 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 531.48 | 10.70 | 0.00 | 232.67 | 369.87 | 14.47 | 0.00 | 166.00 | |
Maximum of Months | 408.83 | 0.56 | 0.48 | 1138.11 | 18.01 | 83.17 | 391.50 | 676.05 | 19.31 | 37.50 | 362.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:09 | 2036.94 | 20.72 | 81.83 | 264.67 | 1155.98 | 22.55 | 63.50 | 222.67 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-09:20 | 2397.20 | 21.79 | 88.33 | 256.00 | 1320.78 | 22.30 | 61.33 | 220.83 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-08:09 | 3022.72 | 20.93 | 111.33 | 323.67 | 1191.23 | 19.76 | 52.50 | 291.00 |
April | 373.83 | 0.51 | 0.48 | 01-APR-07:40 | 3396.14 | 20.29 | 111.83 | 347.50 | 1379.97 | 19.54 | 51.83 | 317.17 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2637.85 | 12.73 | 0.00 | 377.17 | 1510.32 | 16.45 | 0.00 | 355.00 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2746.18 | 12.83 | 0.00 | 372.83 | 1546.63 | 16.57 | 0.00 | 349.00 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-06:00 | 2455.02 | 13.21 | 3.67 | 383.00 | 1384.65 | 16.65 | 0.00 | 342.33 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:19 | 2500.91 | 16.55 | 57.17 | 354.83 | 1342.22 | 16.76 | 3.67 | 317.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:00 | 2975.60 | 20.58 | 112.67 | 323.00 | 1211.13 | 19.75 | 56.00 | 292.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:49 | 2719.78 | 21.94 | 104.00 | 303.83 | 1401.16 | 22.02 | 69.00 | 271.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2715.81 | 22.56 | 112.00 | 270.83 | 992.00 | 20.71 | 54.00 | 230.83 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-08:39 | 2106.95 | 22.63 | 105.67 | 257.83 | 887.94 | 21.42 | 52.00 | 229.83 |
Annual Sum or Average | 4125.67 | 0.51 | 2668.20 | 18.45 | 888.50 | 3835.17 | 1295.31 | 19.24 | 463.83 | 3440.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 2036.94 | 12.73 | 0.00 | 256.00 | 887.94 | 16.45 | 0.00 | 220.83 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3396.14 | 22.63 | 112.67 | 383.00 | 1546.63 | 22.55 | 69.00 | 355.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:20 | 8897.14 | 38.36 | 275.83 | 279.33 | 1991.39 | 22.95 | 97.17 | 263.83 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9565.83 | 36.66 | 261.50 | 269.83 | 1479.03 | 18.66 | 34.83 | 249.83 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 2060.79 | 13.59 | 10.67 | 323.67 | 1121.47 | 16.57 | 1.83 | 297.50 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:10 | 1316.92 | 13.45 | 0.00 | 338.00 | 843.60 | 17.00 | 0.00 | 303.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:40 | 1083.13 | 13.44 | 0.00 | 363.83 | 691.44 | 16.94 | 0.00 | 332.17 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:40 | 975.53 | 13.25 | 0.00 | 356.67 | 638.76 | 16.86 | 0.00 | 325.00 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-06:40 | 1032.13 | 13.31 | 0.00 | 361.83 | 651.13 | 16.85 | 0.00 | 314.67 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:40 | 1217.33 | 13.54 | 0.00 | 349.83 | 764.89 | 17.04 | 0.00 | 308.00 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1550.10 | 13.65 | 11.00 | 321.17 | 950.88 | 16.68 | 0.00 | 287.83 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:10 | 3685.62 | 21.47 | 131.00 | 312.17 | 1321.62 | 17.19 | 13.33 | 288.67 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 9058.19 | 37.15 | 288.33 | 288.33 | 1639.15 | 21.26 | 90.00 | 275.33 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 8051.98 | 37.58 | 284.00 | 276.33 | 1960.03 | 23.02 | 101.33 | 270.00 |
Annual Sum or Average | 4125.67 | 0.51 | 3564.08 | 20.65 | 1262.33 | 3841.00 | 1106.77 | 18.15 | 338.50 | 3516.00 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 975.53 | 13.25 | 0.00 | 269.83 | 638.76 | 16.57 | 0.00 | 249.83 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9565.83 | 38.36 | 288.33 | 363.83 | 1991.39 | 23.02 | 101.33 | 332.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:09 | 2472.23 | 21.78 | 92.50 | 251.00 | 1377.33 | 22.16 | 63.33 | 212.50 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2974.30 | 21.63 | 89.67 | 254.17 | 1143.35 | 20.20 | 41.00 | 219.17 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2723.02 | 20.37 | 101.33 | 314.33 | 1485.65 | 21.09 | 71.00 | 285.83 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3416.13 | 20.23 | 109.83 | 340.50 | 1398.32 | 20.28 | 60.67 | 315.33 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2746.40 | 19.36 | 103.67 | 370.17 | 1555.03 | 20.48 | 72.67 | 343.67 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2814.88 | 19.36 | 100.00 | 364.17 | 1589.50 | 20.52 | 70.00 | 336.00 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 2493.42 | 19.34 | 100.67 | 369.67 | 1384.42 | 20.50 | 70.33 | 330.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 3106.92 | 20.97 | 120.50 | 353.33 | 1286.13 | 20.35 | 63.33 | 322.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2986.02 | 20.73 | 114.50 | 323.83 | 1203.72 | 19.81 | 57.67 | 294.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-06:40 | 2598.35 | 20.27 | 89.83 | 293.00 | 1446.18 | 21.32 | 63.50 | 264.17 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 2108.90 | 19.49 | 80.50 | 261.67 | 1163.84 | 21.27 | 61.00 | 226.83 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 2394.14 | 22.32 | 106.83 | 253.33 | 994.31 | 20.91 | 50.33 | 220.67 |
Annual Sum or Average | 4125.67 | 0.52 | 2755.98 | 20.39 | 1209.83 | 3749.17 | 1351.41 | 20.70 | 744.83 | 3371.67 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 2108.90 | 19.34 | 80.50 | 251.00 | 994.31 | 19.81 | 41.00 | 212.50 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 3416.13 | 22.32 | 120.50 | 370.17 | 1589.50 | 22.16 | 72.67 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:09 | 546.41 | 10.66 | 0.00 | 233.67 | 378.32 | 14.52 | 0.00 | 166.17 |
February | 268.33 | 0.54 | 0.48 | 01-FEB-09:20 | 623.53 | 11.63 | 0.00 | 236.83 | 431.02 | 15.36 | 0.00 | 181.83 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:09 | 733.49 | 12.45 | 0.00 | 307.83 | 490.63 | 16.06 | 0.00 | 255.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 869.07 | 13.76 | 0.00 | 350.50 | 577.38 | 17.34 | 0.00 | 316.00 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 1062.07 | 14.26 | 3.00 | 385.50 | 643.32 | 17.74 | 0.00 | 362.83 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1138.94 | 17.98 | 83.17 | 381.67 | 676.81 | 17.86 | 1.33 | 361.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 1077.31 | 15.86 | 37.33 | 391.50 | 674.44 | 19.29 | 37.50 | 356.00 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 925.77 | 13.92 | 0.00 | 362.00 | 598.30 | 17.49 | 0.00 | 328.00 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-07:49 | 731.76 | 13.00 | 0.00 | 315.00 | 497.48 | 16.61 | 0.00 | 263.00 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-07:40 | 655.73 | 12.04 | 0.00 | 283.83 | 449.62 | 15.70 | 0.00 | 230.67 |
November | 295.83 | 0.56 | 0.48 | 01-NOV-12:00 | 531.73 | 10.72 | 0.00 | 243.00 | 372.19 | 14.57 | 0.00 | 169.00 |
December | 289.50 | 0.56 | 0.48 | 01-DEC-08:39 | 544.16 | 10.68 | 0.00 | 232.67 | 370.26 | 14.46 | 0.00 | 173.00 |
Annual Sum or Average | 4125.67 | 0.52 | 814.79 | 13.34 | 123.50 | 3724.00 | 528.36 | 16.61 | 38.83 | 3162.83 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 531.73 | 10.66 | 0.00 | 232.67 | 370.26 | 14.46 | 0.00 | 166.17 | |
Maximum of Months | 408.83 | 0.56 | 0.48 | 1138.94 | 17.98 | 83.17 | 391.50 | 676.81 | 19.29 | 37.50 | 362.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:09 | 2037.52 | 20.69 | 81.83 | 264.67 | 1156.76 | 22.54 | 63.50 | 223.00 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-09:20 | 2397.95 | 21.77 | 88.33 | 256.17 | 1321.67 | 22.28 | 61.33 | 221.00 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-08:09 | 3023.85 | 20.90 | 111.33 | 323.67 | 1192.27 | 19.75 | 52.50 | 291.00 |
April | 373.83 | 0.51 | 0.48 | 01-APR-07:40 | 3397.26 | 20.26 | 111.83 | 347.50 | 1381.04 | 19.53 | 51.83 | 317.17 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2638.93 | 12.69 | 0.00 | 377.17 | 1511.47 | 16.43 | 0.00 | 355.00 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:49 | 2747.25 | 12.79 | 0.00 | 372.83 | 1547.70 | 16.56 | 0.00 | 349.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-06:00 | 2456.20 | 13.17 | 3.67 | 383.17 | 1385.76 | 16.64 | 0.00 | 342.33 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:19 | 2502.06 | 16.52 | 57.17 | 355.17 | 1343.34 | 16.75 | 3.67 | 317.67 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:00 | 2976.56 | 20.55 | 112.67 | 323.00 | 1212.15 | 19.74 | 56.00 | 292.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:49 | 2720.51 | 21.91 | 104.00 | 303.83 | 1402.08 | 22.01 | 69.00 | 271.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2716.35 | 22.53 | 112.00 | 270.83 | 992.72 | 20.69 | 54.00 | 230.83 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-08:39 | 2107.61 | 22.61 | 105.67 | 258.00 | 888.73 | 21.40 | 52.00 | 229.83 |
Annual Sum or Average | 4125.67 | 0.51 | 2669.14 | 18.42 | 888.50 | 3836.00 | 1296.30 | 19.22 | 463.83 | 3440.83 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 2037.52 | 12.69 | 0.00 | 256.17 | 888.73 | 16.43 | 0.00 | 221.00 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3397.26 | 22.61 | 112.67 | 383.17 | 1547.70 | 22.54 | 69.00 | 355.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.822794E+09 | 19289.06 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530700E+09 | 20515.04 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238412E+09 | 13338.99 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61809487.48 | 8234.92 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.735556E+09 | 16887.35 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822794E+09 | 20515.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67406437.29 | 14279.07 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39660394.49 | 14289.00 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5708581.57 | 4436.22 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75828.81 | 73.12 | 28-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21587054.69 | 4893.10 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67406437.29 | 14289.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 83837991.38 | 11356.72 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47847907.42 | 11387.77 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14688024.24 | 11391.43 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6020489.71 | 6971.34 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95190027.89 | 11399.88 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95190027.89 | 11399.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 79313796.39 | 16507.82 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45839621.45 | 13653.15 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10130177.85 | 7244.80 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11682707.01 | 16296.86 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67214884.36 | 16557.55 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79313796.39 | 16557.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8548512.58 | 1332.43 | 28-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8548512.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8548512.58 | 1332.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176484E+11 | 211057.74 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118030E+11 | 222755.09 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645690E+10 | 164531.76 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292340E+09 | 54083.98 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 938610.00 | 1564.35 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.530488E+10 | 129479.76 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303966E+11 | 221618.62 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.719030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303966E+11 | 222755.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134826E+11 | 164454.76 | 13-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748874E+10 | 172247.33 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348259E+10 | 173133.21 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126999E+09 | 128441.67 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11573053.62 | 4412.32 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439301E+10 | 173252.05 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162597E+11 | 159431.47 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162597E+11 | 173252.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.836141E+10 | 155123.26 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392625E+10 | 154896.04 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204106E+10 | 154941.34 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91655479.65 | 78135.35 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45241076.42 | 14157.10 | 25-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278907E+10 | 159141.27 | 21-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.985374E+10 | 155145.13 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.985374E+10 | 159141.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465801E+10 | 176890.47 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273479E+10 | 176852.45 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122752E+10 | 176382.54 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89831995.25 | 90204.89 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129975E+10 | 176902.31 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.561127E+10 | 177655.71 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561127E+10 | 177655.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.760778E+10 | 155478.60 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430285E+10 | 155451.19 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155468E+10 | 155372.36 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76420511.49 | 51722.55 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240248E+10 | 155488.12 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.843990E+10 | 155528.22 | 05-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.843990E+10 | 155528.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342363E+10 | 27188.79 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227524E+10 | 28767.34 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140492E+10 | 22682.50 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113120E+09 | 9815.01 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20351415.33 | 4005.32 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127918E+10 | 18254.07 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508807E+10 | 28470.80 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508807E+10 | 28767.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133370E+10 | 85992.73 | 17-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279621E+09 | 85586.64 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29984287.42 | 11012.10 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623469E+09 | 85648.86 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175144E+10 | 85994.62 | 04-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175144E+10 | 85994.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394408E+10 | 18185.18 | 17-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246525E+10 | 18094.10 | 27-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136369E+10 | 17979.46 | 01-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146661E+09 | 17899.45 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93813.68 | 124.99 | 25-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118673E+09 | 16811.01 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195048E+10 | 18108.71 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473718E+10 | 18117.32 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473718E+10 | 18185.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201870E+10 | 17048.58 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110652E+10 | 16962.25 | 27-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657533E+09 | 16880.12 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58490552.85 | 16806.12 | 11-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 318474.19 | 335.99 | 25-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96227915.76 | 11894.66 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.989520E+09 | 16975.12 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241695E+10 | 17039.93 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241695E+10 | 17048.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171015E+10 | 19847.64 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109309E+10 | 19812.53 | 27-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768763E+09 | 19687.22 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120890E+09 | 19573.58 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 120723.04 | 131.45 | 02-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32745434.56 | 4325.95 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.871708E+09 | 19828.21 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200348E+10 | 19837.77 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200348E+10 | 19847.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200403E+10 | 18505.90 | 09-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128824E+10 | 18476.82 | 27-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673378E+09 | 18473.76 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76313784.68 | 13193.13 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43358519.85 | 1769.55 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.923406E+09 | 18488.40 | 28-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225186E+10 | 18494.71 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225186E+10 | 18505.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.313937E+10 | 0.313937E+10 | 51148.21 | 03-JAN-14:30 | 51148.21 | 0.00 |
February | 0.00 | 0.00 | 0.106476E+11 | 0.106476E+11 | 82745.02 | 21-FEB-15:00 | 82745.02 | 0.00 |
March | 0.00 | 0.00 | 0.266127E+11 | 0.266127E+11 | 100059.21 | 21-MAR-15:40 | 100059.21 | 0.00 |
April | 0.00 | 0.00 | 0.743385E+11 | 0.743385E+11 | 132281.06 | 21-APR-14:40 | 132281.06 | 0.07 |
May | 0.00 | 0.00 | 0.108249E+12 | 0.108119E+12 | 166933.71 | 30-MAY-05:02 | 166933.71 | 0.21 |
June | 0.00 | 0.00 | 0.148427E+12 | 0.147948E+12 | 168188.08 | 15-JUN-05:02 | 168188.08 | 0.46 |
July | 0.00 | 0.00 | 0.179061E+12 | 0.152596E+12 | 307151.84 | 21-JUL-04:11 | 97987.70 | 0.83 |
August | 0.00 | 0.00 | 0.169649E+12 | 0.158795E+12 | 263323.93 | 05-AUG-05:02 | 154371.56 | 0.84 |
September | 0.00 | 0.00 | 0.116011E+12 | 0.108614E+12 | 269341.04 | 22-SEP-04:12 | 98558.24 | 0.55 |
October | 0.00 | 0.00 | 0.656806E+11 | 0.636688E+11 | 152602.46 | 02-OCT-05:02 | 152602.46 | 0.26 |
November | 0.00 | 0.00 | 0.197779E+11 | 0.197779E+11 | 95134.22 | 03-NOV-16:00 | 95134.22 | 0.02 |
December | 0.00 | 0.00 | 0.149962E+10 | 0.149962E+10 | 29449.25 | 20-DEC-15:00 | 29449.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.923094E+12 | 0.875756E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.149962E+10 | 0.149962E+10 | 29449.25 | 29449.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179061E+12 | 0.158795E+12 | 307151.84 | 168188.08 | 0.84 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.240568E+11 | 0.240568E+11 | 386451.01 | 12-JAN-15:10 | 386451.01 | 0.00 |
February | 0.00 | 0.00 | 0.820405E+11 | 0.820405E+11 | 595718.39 | 21-FEB-16:00 | 595718.39 | 0.00 |
March | 0.00 | 0.00 | 0.198652E+12 | 0.198652E+12 | 785414.82 | 21-MAR-16:00 | 785414.82 | 0.00 |
April | 0.00 | 0.00 | 0.544898E+12 | 0.544898E+12 | 1151159.63 | 21-APR-14:40 | 1151159.63 | 0.06 |
May | 0.00 | 0.00 | 0.956922E+12 | 0.955881E+12 | 1421958.93 | 30-MAY-05:02 | 1421958.93 | 0.21 |
June | 0.00 | 0.00 | 0.127592E+13 | 0.127284E+13 | 1589350.87 | 08-JUN-05:03 | 1589350.87 | 0.40 |
July | 0.00 | 0.00 | 0.140363E+13 | 0.121636E+13 | 2601361.98 | 22-JUL-05:03 | 849866.49 | 0.67 |
August | 0.00 | 0.00 | 0.123496E+13 | 0.117112E+13 | 2388025.96 | 03-AUG-04:12 | 1100328.61 | 0.64 |
September | 0.00 | 0.00 | 0.100094E+13 | 0.938879E+12 | 2279057.40 | 22-SEP-04:12 | 833654.80 | 0.52 |
October | 0.00 | 0.00 | 0.527279E+12 | 0.510767E+12 | 1349520.18 | 05-OCT-05:03 | 1057974.14 | 0.25 |
November | 0.00 | 0.00 | 0.146898E+12 | 0.146898E+12 | 766119.75 | 03-NOV-16:00 | 766119.75 | 0.02 |
December | 0.00 | 0.00 | 0.986204E+10 | 0.986204E+10 | 187655.69 | 20-DEC-15:00 | 187655.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.740606E+13 | 0.707225E+13 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.986204E+10 | 0.986204E+10 | 187655.69 | 187655.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140363E+13 | 0.127284E+13 | 2601361.98 | 1589350.87 | 0.67 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.171071E+10 | 0.171071E+10 | 34247.32 | 12-JAN-15:00 | 34247.32 | 0.00 |
February | 0.00 | 0.00 | 0.700477E+10 | 0.700477E+10 | 58167.55 | 20-FEB-15:52 | 58167.55 | 0.00 |
March | 0.00 | 0.00 | 0.183589E+11 | 0.183589E+11 | 83212.67 | 21-MAR-16:00 | 83212.67 | 0.00 |
April | 0.00 | 0.00 | 0.579875E+11 | 0.579875E+11 | 133405.18 | 21-APR-14:40 | 133405.18 | 0.05 |
May | 0.00 | 0.00 | 0.105098E+12 | 0.104989E+12 | 150772.59 | 30-MAY-15:00 | 150772.59 | 0.21 |
June | 0.00 | 0.00 | 0.144505E+12 | 0.144208E+12 | 162786.81 | 15-JUN-14:40 | 162786.81 | 0.41 |
July | 0.00 | 0.00 | 0.157299E+12 | 0.138001E+12 | 281139.19 | 17-JUL-04:12 | 94696.70 | 0.68 |
August | 0.00 | 0.00 | 0.136363E+12 | 0.130098E+12 | 257758.16 | 03-AUG-05:03 | 119924.33 | 0.65 |
September | 0.00 | 0.00 | 0.107119E+12 | 0.101362E+12 | 251230.91 | 22-SEP-05:03 | 92009.31 | 0.52 |
October | 0.00 | 0.00 | 0.531269E+11 | 0.516958E+11 | 144849.96 | 03-OCT-14:00 | 130143.88 | 0.24 |
November | 0.00 | 0.00 | 0.121347E+11 | 0.121347E+11 | 77683.81 | 09-NOV-15:00 | 77683.81 | 0.02 |
December | 0.00 | 0.00 | 0.588364E+09 | 0.588364E+09 | 12790.80 | 23-DEC-15:00 | 12790.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.801296E+12 | 0.768138E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.588364E+09 | 0.588364E+09 | 12790.80 | 12790.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157299E+12 | 0.144208E+12 | 281139.19 | 162786.81 | 0.68 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.132977E+10 | 0.132977E+10 | 34443.83 | 03-JAN-15:00 | 34443.83 | 0.00 |
February | 0.00 | 0.00 | 0.473085E+10 | 0.473085E+10 | 57543.37 | 21-FEB-15:00 | 57543.37 | 0.00 |
March | 0.00 | 0.00 | 0.128680E+11 | 0.128680E+11 | 56880.91 | 21-MAR-16:00 | 56880.91 | 0.00 |
April | 0.00 | 0.00 | 0.382977E+11 | 0.382977E+11 | 84773.55 | 20-APR-05:03 | 84773.55 | 0.05 |
May | 0.00 | 0.00 | 0.663555E+11 | 0.663136E+11 | 152843.04 | 29-MAY-15:37 | 129453.12 | 0.18 |
June | 0.00 | 0.00 | 0.836771E+11 | 0.835703E+11 | 131407.12 | 19-JUN-04:12 | 99074.00 | 0.34 |
July | 0.00 | 0.00 | 0.972112E+11 | 0.861303E+11 | 217753.16 | 09-JUL-18:16 | 114784.49 | 0.56 |
August | 0.00 | 0.00 | 0.944098E+11 | 0.908657E+11 | 182355.28 | 02-AUG-05:03 | 73172.62 | 0.60 |
September | 0.00 | 0.00 | 0.763854E+11 | 0.738102E+11 | 189456.38 | 10-SEP-15:30 | 121650.56 | 0.48 |
October | 0.00 | 0.00 | 0.425616E+11 | 0.421428E+11 | 136050.02 | 05-OCT-04:12 | 86580.73 | 0.20 |
November | 0.00 | 0.00 | 0.111115E+11 | 0.111097E+11 | 68843.08 | 10-NOV-06:03 | 68843.08 | 0.02 |
December | 0.00 | 0.00 | 0.229426E+09 | 0.229426E+09 | 18332.84 | 11-DEC-05:11 | 18332.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.529168E+12 | 0.511398E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.229426E+09 | 0.229426E+09 | 18332.84 | 18332.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.972112E+11 | 0.908657E+11 | 217753.16 | 129453.12 | 0.60 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101543E+11 | 0.911856E+10 | 5414.64 | 13-JAN-11:50 | 4887.74 | 0.00 |
February | 0.00 | 0.00 | 0.256980E+11 | 0.250695E+11 | 128301.16 | 20-FEB-16:00 | 128301.16 | 0.00 |
March | 0.00 | 0.00 | 0.112760E+12 | 0.112448E+12 | 267878.53 | 21-MAR-16:00 | 267878.53 | 0.00 |
April | 0.00 | 0.00 | 0.539616E+12 | 0.522498E+12 | 410472.26 | 29-APR-17:10 | 393957.98 | 0.00 |
May | 0.00 | 0.00 | 0.180490E+12 | 0.172468E+12 | 195342.30 | 31-MAY-23:10 | 195342.30 | 0.00 |
June | 0.00 | 0.00 | 0.500169E+12 | 0.457419E+12 | 353265.71 | 03-JUN-17:43 | 219167.57 | 0.00 |
July | 0.00 | 0.00 | 0.100828E+13 | 0.714642E+12 | 493319.77 | 20-JUL-15:00 | 152782.97 | 0.00 |
August | 0.00 | 0.00 | 0.111355E+13 | 0.831517E+12 | 467863.14 | 01-AUG-21:12 | 182794.02 | 0.00 |
September | 0.00 | 0.00 | 0.175296E+12 | 0.149452E+12 | 239126.63 | 01-SEP-10:30 | 140026.30 | 0.00 |
October | 0.00 | 0.00 | 0.173641E+12 | 0.145069E+12 | 325605.05 | 04-OCT-11:30 | 218205.98 | 0.00 |
November | 0.00 | 0.00 | 0.767010E+11 | 0.720714E+11 | 254750.03 | 03-NOV-16:00 | 240101.14 | 0.00 |
December | 0.00 | 0.00 | 0.548677E+11 | 0.530672E+11 | 182371.19 | 23-DEC-15:00 | 182371.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.397122E+13 | 0.326484E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101543E+11 | 0.911856E+10 | 5414.64 | 4887.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111355E+13 | 0.831517E+12 | 493319.77 | 393957.98 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.493147E+10 | 0.491787E+10 | 2703.51 | 02-JAN-17:00 | 2624.40 | 0.00 |
February | 0.00 | 0.00 | 0.937033E+10 | 0.935466E+10 | 4741.73 | 20-FEB-17:17 | 4741.73 | 0.00 |
March | 0.00 | 0.00 | 0.158150E+11 | 0.158115E+11 | 7738.93 | 31-MAR-24:00 | 7738.93 | 0.00 |
April | 0.00 | 0.00 | 0.205816E+11 | 0.205644E+11 | 8533.49 | 22-APR-17:55 | 8533.49 | 0.00 |
May | 0.00 | 0.00 | 0.645726E+10 | 0.639522E+10 | 4146.67 | 31-MAY-24:00 | 4137.31 | 0.00 |
June | 0.00 | 0.00 | 0.113381E+11 | 0.112266E+11 | 5983.39 | 30-JUN-23:55 | 5983.39 | 0.00 |
July | 0.00 | 0.00 | 0.169686E+11 | 0.166445E+11 | 7907.73 | 31-JUL-24:00 | 7901.87 | 0.00 |
August | 0.00 | 0.00 | 0.219816E+11 | 0.217116E+11 | 8723.41 | 08-AUG-17:00 | 8301.71 | 0.00 |
September | 0.00 | 0.00 | 0.647558E+10 | 0.625878E+10 | 4100.80 | 30-SEP-24:00 | 4100.80 | 0.00 |
October | 0.00 | 0.00 | 0.113754E+11 | 0.112119E+11 | 5906.74 | 31-OCT-24:00 | 5906.74 | 0.00 |
November | 0.00 | 0.00 | 0.153572E+11 | 0.153169E+11 | 6845.62 | 09-NOV-16:50 | 6737.90 | 0.00 |
December | 0.00 | 0.00 | 0.205152E+11 | 0.205091E+11 | 8348.47 | 17-DEC-16:47 | 8348.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161168E+12 | 0.159923E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.493147E+10 | 0.491787E+10 | 2703.51 | 2624.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219816E+11 | 0.217116E+11 | 8723.41 | 8533.49 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.326242E+11 | 0.324971E+11 | 23756.19 | 12-JAN-16:50 | 22850.95 | 0.00 |
February | 0.00 | 0.00 | 0.787327E+11 | 0.785782E+11 | 43343.64 | 21-FEB-17:00 | 43343.64 | 0.00 |
March | 0.00 | 0.00 | 0.142371E+12 | 0.142336E+12 | 71752.19 | 31-MAR-23:40 | 71752.19 | 0.00 |
April | 0.00 | 0.00 | 0.193166E+12 | 0.192993E+12 | 80802.46 | 28-APR-16:00 | 80369.92 | 0.00 |
May | 0.00 | 0.00 | 0.594215E+11 | 0.588093E+11 | 40120.61 | 31-MAY-24:00 | 40052.32 | 0.00 |
June | 0.00 | 0.00 | 0.107878E+12 | 0.106771E+12 | 58177.32 | 30-JUN-23:55 | 58177.32 | 0.00 |
July | 0.00 | 0.00 | 0.161515E+12 | 0.158282E+12 | 76071.92 | 31-JUL-24:00 | 76009.74 | 0.00 |
August | 0.00 | 0.00 | 0.207371E+12 | 0.204668E+12 | 82829.70 | 08-AUG-17:00 | 78640.40 | 0.00 |
September | 0.00 | 0.00 | 0.590833E+11 | 0.569499E+11 | 38209.92 | 30-SEP-23:50 | 38209.92 | 0.00 |
October | 0.00 | 0.00 | 0.102798E+12 | 0.101188E+12 | 53991.54 | 31-OCT-24:00 | 53991.54 | 0.00 |
November | 0.00 | 0.00 | 0.135228E+12 | 0.134827E+12 | 64551.65 | 09-NOV-16:50 | 63476.81 | 0.00 |
December | 0.00 | 0.00 | 0.179164E+12 | 0.179101E+12 | 77950.28 | 15-DEC-16:50 | 77950.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145935E+13 | 0.144700E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.326242E+11 | 0.324971E+11 | 23756.19 | 22850.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207371E+12 | 0.204668E+12 | 82829.70 | 80369.92 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.179570E+10 | 0.178466E+10 | 2393.90 | 12-JAN-16:50 | 2303.63 | 0.00 |
February | 0.00 | 0.00 | 0.672875E+10 | 0.671366E+10 | 4342.18 | 21-FEB-17:00 | 4342.18 | 0.00 |
March | 0.00 | 0.00 | 0.133783E+11 | 0.133749E+11 | 6896.93 | 31-MAR-23:20 | 6896.93 | 0.00 |
April | 0.00 | 0.00 | 0.190763E+11 | 0.190591E+11 | 8207.61 | 28-APR-16:00 | 8163.32 | 0.00 |
May | 0.00 | 0.00 | 0.592297E+10 | 0.586170E+10 | 4051.74 | 31-MAY-24:00 | 4043.55 | 0.00 |
June | 0.00 | 0.00 | 0.109120E+11 | 0.108011E+11 | 5802.67 | 30-JUN-23:55 | 5802.67 | 0.00 |
July | 0.00 | 0.00 | 0.163163E+11 | 0.159929E+11 | 7628.00 | 31-JUL-24:00 | 7621.65 | 0.00 |
August | 0.00 | 0.00 | 0.208498E+11 | 0.205789E+11 | 8439.08 | 08-AUG-17:00 | 8015.56 | 0.00 |
September | 0.00 | 0.00 | 0.587118E+10 | 0.565761E+10 | 3667.65 | 30-SEP-23:20 | 3667.65 | 0.00 |
October | 0.00 | 0.00 | 0.982794E+10 | 0.966752E+10 | 5087.59 | 31-OCT-23:20 | 5087.59 | 0.00 |
November | 0.00 | 0.00 | 0.122928E+11 | 0.122530E+11 | 6502.09 | 09-NOV-16:50 | 6394.54 | 0.00 |
December | 0.00 | 0.00 | 0.161471E+11 | 0.161409E+11 | 7738.19 | 15-DEC-16:50 | 7738.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139119E+12 | 0.137886E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.179570E+10 | 0.178466E+10 | 2393.90 | 2303.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208498E+11 | 0.205789E+11 | 8439.08 | 8163.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 24786.86 | 1344044.31 | 09-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16149.78 | 1150083.89 | 09-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7378.13 | 1145992.18 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 453.27 | 626068.80 | 11-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.04 | 115.37 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.14 | 325.98 | 25-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 132.88 | 66463.86 | 25-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 8763.58 | 1394787.39 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33201.03 | 1238762.04 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 7559.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 33201.03 | 1394787.39 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12066.46 | 493421.22 | 03-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44331.96 | 788419.90 | 21-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 97828.62 | 1075673.51 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 286591.23 | 1669657.98 | 27-APR-12:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 481172.35 | 1660886.58 | 12-MAY-15:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 659028.30 | 1814610.83 | 17-JUN-16:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 709913.23 | 4791389.81 | 20-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 631654.85 | 2132411.76 | 02-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 521044.67 | 2106637.36 | 14-SEP-09:50 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 266929.16 | 1613677.31 | 03-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75027.54 | 1033484.95 | 09-NOV-15:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 5254.80 | 225251.17 | 20-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 317373.84 | 0.00 | ||||
Minimum of Months | 5254.80 | 225251.17 | 0.00 | 0.00 | ||
Maximum of Months | 709913.23 | 4791389.81 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11258.50 | 489206.85 | 03-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 43063.44 | 785193.08 | 21-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 96038.17 | 1072553.98 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 281285.17 | 1524485.52 | 28-APR-12:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 473455.43 | 2213989.76 | 30-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 650852.28 | 3496995.83 | 17-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 701231.60 | 5200279.47 | 22-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 623603.26 | 4928878.26 | 03-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 514279.04 | 3753290.05 | 22-SEP-04:12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 262822.70 | 1827486.68 | 05-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 73573.75 | 1029934.90 | 09-NOV-15:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 4534.08 | 226359.84 | 20-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312785.59 | 0.00 | ||||
Minimum of Months | 4534.08 | 226359.84 | 0.00 | 0.00 | ||
Maximum of Months | 701231.60 | 5200279.47 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28981.69 | 190082.05 | 03-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 89197.78 | 642385.53 | 20-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 208050.25 | 1103208.96 | 21-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 761296.07 | 1827396.92 | 21-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 523056.06 | 1299433.45 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1050017.81 | 1799617.36 | 02-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1463096.12 | 2037461.77 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1517760.37 | 2174903.95 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 499612.42 | 1238986.41 | 19-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 334802.13 | 1430797.89 | 03-OCT-14:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 158199.31 | 997169.96 | 03-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 134889.84 | 545545.05 | 10-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 567400.10 | 0.00 | ||||
Minimum of Months | 28981.69 | 190082.05 | 0.00 | 0.00 | ||
Maximum of Months | 1517760.37 | 2174903.95 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14431.24 | 48127.00 | 30-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14495.98 | 48122.29 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14799.38 | 47281.96 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13125.00 | 44549.77 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12531.09 | 41449.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 11895.32 | 38062.44 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 10589.55 | 35567.73 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11468.06 | 35707.87 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 11340.46 | 38016.93 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12162.56 | 41505.93 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13283.89 | 44798.50 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13653.15 | 47153.78 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12805.24 | ||||
Minimum of Months | 0.00 | 0.00 | 10589.55 | 35567.73 | ||
Maximum of Months | 0.00 | 0.00 | 14799.38 | 48127.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12261.20 | 580801.43 | 03-JAN-14:30 | 3597.46 | 142350.40 | 02-JAN-06:30 |
February | 48522.56 | 908171.08 | 21-FEB-16:10 | 2968.77 | 142597.65 | 02-FEB-14:00 |
March | 111007.09 | 1230654.92 | 21-MAR-16:00 | 2145.66 | 135845.71 | 17-MAR-05:30 |
April | 338193.02 | 2542393.50 | 21-APR-15:20 | 2120.47 | 120745.57 | 11-APR-05:04 |
May | 599395.08 | 2587908.00 | 22-MAY-15:20 | 427.14 | 113270.32 | 08-MAY-06:20 |
June | 885247.85 | 2809545.25 | 20-JUN-15:00 | 182.71 | 63628.68 | 13-JUN-05:50 |
July | 1253184.84 | 6474669.08 | 20-JUL-15:20 | 2.17 | 4668.84 | 16-JUL-04:10 |
August | 942517.66 | 4683375.36 | 02-AUG-08:20 | 242.74 | 44130.44 | 26-AUG-04:00 |
September | 755032.20 | 4418217.30 | 14-SEP-09:50 | 62.32 | 45397.93 | 12-SEP-06:25 |
October | 341445.11 | 3155508.85 | 03-OCT-14:00 | 592.66 | 103163.92 | 31-OCT-18:30 |
November | 85145.10 | 1183434.82 | 09-NOV-15:30 | 1985.86 | 138035.85 | 17-NOV-06:40 |
December | 3470.11 | 291496.71 | 20-DEC-15:10 | 3945.88 | 153171.52 | 18-DEC-10:20 |
Annual Sum or Average | 450490.11 | 1515.70 | ||||
Minimum of Months | 3470.11 | 291496.71 | 2.17 | 4668.84 | ||
Maximum of Months | 1253184.84 | 6474669.08 | 3945.88 | 153171.52 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176386E+11 | 0.91 | 11549.65 | 01-JAN-00:20 | 1.59 |
February | 0.155193E+11 | 0.89 | 11549.65 | 01-FEB-04:10 | 1.60 |
March | 0.180660E+11 | 0.93 | 11549.65 | 01-MAR-05:01 | 1.60 |
April | 0.164929E+11 | 0.88 | 11549.65 | 01-APR-04:12 | 1.60 |
May | 0.178828E+11 | 0.92 | 11549.65 | 01-MAY-04:11 | 1.60 |
June | 0.177345E+11 | 0.94 | 11549.65 | 01-JUN-04:12 | 1.59 |
July | 0.182384E+11 | 0.93 | 11549.65 | 01-JUL-03:02 | 1.59 |
August | 0.199966E+11 | 1.02 | 11549.65 | 01-AUG-03:02 | 1.58 |
September | 0.189406E+11 | 1.00 | 11549.65 | 01-SEP-04:12 | 1.58 |
October | 0.192295E+11 | 0.98 | 11549.65 | 01-OCT-11:57 | 1.59 |
November | 0.182076E+11 | 0.97 | 11549.65 | 01-NOV-04:12 | 1.58 |
December | 0.179586E+11 | 0.93 | 11549.65 | 01-DEC-05:12 | 1.59 |
Annual Sum or Average | 0.215905E+12 | 0.94 | |||
Minimum of Months | 0.155193E+11 | 0.88 | 11549.65 | 1.58 | |
Maximum of Months | 0.199966E+11 | 1.02 | 11549.65 | 1.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.566236E+10 | 0.39 | 14446.21 | 28-JAN-06:01 | 1.46 |
February | 0.603817E+10 | 0.43 | 13623.57 | 21-FEB-16:20 | 1.41 |
March | 0.897321E+10 | 0.51 | 14540.66 | 16-MAR-15:30 | 1.46 |
April | 0.117911E+11 | 0.63 | 20618.26 | 03-APR-05:02 | 1.82 |
May | 0.118017E+11 | 0.60 | 24643.90 | 30-MAY-05:02 | 2.03 |
June | 0.144388E+11 | 0.73 | 24643.90 | 10-JUN-05:02 | 2.03 |
July | 0.149182E+11 | 0.75 | 24643.90 | 12-JUL-05:02 | 2.01 |
August | 0.174156E+11 | 0.83 | 24643.90 | 05-AUG-05:02 | 2.01 |
September | 0.114718E+11 | 0.59 | 24643.90 | 13-SEP-04:12 | 2.01 |
October | 0.977251E+10 | 0.52 | 24643.90 | 02-OCT-05:02 | 2.01 |
November | 0.776400E+10 | 0.47 | 14641.55 | 24-NOV-15:50 | 1.47 |
December | 0.702181E+10 | 0.43 | 12953.21 | 27-DEC-06:01 | 1.36 |
Annual Sum or Average | 0.127069E+12 | 0.57 | |||
Minimum of Months | 0.566236E+10 | 0.39 | 12953.21 | 1.36 | |
Maximum of Months | 0.174156E+11 | 0.83 | 24643.90 | 2.03 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386685E+11 | 0.35 | 122935.79 | 25-JAN-06:02 | 1.37 |
February | 0.400055E+11 | 0.37 | 119725.32 | 15-FEB-06:02 | 1.35 |
March | 0.552544E+11 | 0.42 | 121753.85 | 18-MAR-05:02 | 1.37 |
April | 0.725190E+11 | 0.48 | 148067.50 | 21-APR-14:40 | 1.53 |
May | 0.989900E+11 | 0.56 | 230766.54 | 09-MAY-05:02 | 2.03 |
June | 0.119366E+12 | 0.64 | 230766.54 | 05-JUN-04:12 | 2.02 |
July | 0.110404E+12 | 0.60 | 230766.54 | 06-JUL-04:12 | 2.01 |
August | 0.114446E+12 | 0.61 | 230766.54 | 03-AUG-05:03 | 2.01 |
September | 0.907732E+11 | 0.53 | 230766.54 | 13-SEP-04:12 | 2.01 |
October | 0.656568E+11 | 0.44 | 214843.07 | 05-OCT-05:03 | 1.92 |
November | 0.455914E+11 | 0.37 | 127980.56 | 30-NOV-06:02 | 1.40 |
December | 0.379060E+11 | 0.34 | 122370.34 | 02-DEC-06:02 | 1.37 |
Annual Sum or Average | 0.889581E+12 | 0.48 | |||
Minimum of Months | 0.379060E+11 | 0.34 | 119725.32 | 1.35 | |
Maximum of Months | 0.119366E+12 | 0.64 | 230766.54 | 2.03 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332220E+10 | 0.33 | 5529.76 | 12-JAN-15:50 | 0.81 |
February | 0.328604E+10 | 0.35 | 6092.55 | 07-FEB-14:50 | 0.86 |
March | 0.450415E+10 | 0.38 | 10774.77 | 16-MAR-15:30 | 1.19 |
April | 0.664794E+10 | 0.44 | 15968.46 | 21-APR-15:00 | 1.50 |
May | 0.991141E+10 | 0.53 | 19321.29 | 30-MAY-15:00 | 1.69 |
June | 0.129070E+11 | 0.64 | 25581.82 | 19-JUN-04:12 | 2.01 |
July | 0.119566E+11 | 0.59 | 25581.82 | 24-JUL-04:11 | 2.01 |
August | 0.119336E+11 | 0.59 | 25581.82 | 05-AUG-05:02 | 2.01 |
September | 0.907998E+10 | 0.50 | 22409.24 | 13-SEP-05:03 | 1.85 |
October | 0.591052E+10 | 0.40 | 14388.67 | 05-OCT-05:03 | 1.40 |
November | 0.382941E+10 | 0.35 | 9487.12 | 09-NOV-16:10 | 1.09 |
December | 0.331415E+10 | 0.33 | 5108.36 | 04-DEC-05:01 | 0.78 |
Annual Sum or Average | 0.866030E+11 | 0.45 | |||
Minimum of Months | 0.328604E+10 | 0.33 | 5108.36 | 0.78 | |
Maximum of Months | 0.129070E+11 | 0.64 | 25581.82 | 2.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109094E+12 | 1.55 | 40731.05 | 01-JAN-00:05 | 1.55 |
February | 0.985366E+11 | 1.56 | 40731.05 | 01-FEB-00:10 | 1.55 |
March | 0.109094E+12 | 1.56 | 40731.05 | 01-MAR-00:10 | 1.56 |
April | 0.105575E+12 | 1.56 | 40731.05 | 01-APR-00:10 | 1.57 |
May | 0.109094E+12 | 1.55 | 40731.05 | 01-MAY-00:10 | 1.56 |
June | 0.105575E+12 | 1.55 | 40731.05 | 01-JUN-00:03 | 1.56 |
July | 0.109094E+12 | 1.54 | 40731.05 | 01-JUL-00:03 | 1.55 |
August | 0.109094E+12 | 1.54 | 40731.05 | 01-AUG-00:05 | 1.54 |
September | 0.105575E+12 | 1.54 | 40731.05 | 01-SEP-00:05 | 1.54 |
October | 0.109094E+12 | 1.55 | 40731.05 | 01-OCT-00:10 | 1.56 |
November | 0.105575E+12 | 1.56 | 40731.05 | 01-NOV-00:10 | 1.56 |
December | 0.109094E+12 | 1.56 | 40731.05 | 01-DEC-00:40 | 1.56 |
Annual Sum or Average | 0.128449E+13 | 1.55 | |||
Minimum of Months | 0.985366E+11 | 1.54 | 40731.05 | 1.54 | |
Maximum of Months | 0.109094E+12 | 1.56 | 40731.05 | 1.57 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164643E+10 | 1.06 | 614.71 | 01-JAN-00:05 | 1.06 |
February | 0.148710E+10 | 1.06 | 614.71 | 01-FEB-00:10 | 1.06 |
March | 0.164643E+10 | 1.06 | 614.71 | 01-MAR-00:10 | 1.06 |
April | 0.159332E+10 | 1.06 | 614.71 | 01-APR-00:10 | 1.06 |
May | 0.164643E+10 | 1.06 | 614.71 | 01-MAY-00:10 | 1.05 |
June | 0.159332E+10 | 1.05 | 614.71 | 01-JUN-00:03 | 1.05 |
July | 0.164643E+10 | 1.05 | 614.71 | 01-JUL-00:03 | 1.05 |
August | 0.164643E+10 | 1.05 | 614.71 | 01-AUG-00:10 | 1.05 |
September | 0.159332E+10 | 1.05 | 614.71 | 01-SEP-00:05 | 1.05 |
October | 0.164643E+10 | 1.05 | 614.71 | 01-OCT-00:10 | 1.06 |
November | 0.159332E+10 | 1.06 | 614.71 | 01-NOV-00:10 | 1.06 |
December | 0.164643E+10 | 1.06 | 614.71 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.193854E+11 | 1.06 | |||
Minimum of Months | 0.148710E+10 | 1.05 | 614.71 | 1.05 | |
Maximum of Months | 0.164643E+10 | 1.06 | 614.71 | 1.06 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156699E+11 | 1.06 | 5850.47 | 01-JAN-00:05 | 1.06 |
February | 0.141535E+11 | 1.06 | 5850.47 | 01-FEB-00:10 | 1.06 |
March | 0.156699E+11 | 1.06 | 5850.47 | 01-MAR-00:10 | 1.06 |
April | 0.151644E+11 | 1.06 | 5850.47 | 01-APR-00:10 | 1.06 |
May | 0.156699E+11 | 1.06 | 5850.47 | 01-MAY-00:10 | 1.05 |
June | 0.151644E+11 | 1.05 | 5850.47 | 01-JUN-00:03 | 1.05 |
July | 0.156699E+11 | 1.05 | 5850.47 | 01-JUL-00:03 | 1.05 |
August | 0.156699E+11 | 1.05 | 5850.47 | 01-AUG-00:10 | 1.05 |
September | 0.151644E+11 | 1.05 | 5850.47 | 01-SEP-00:05 | 1.05 |
October | 0.156699E+11 | 1.05 | 5850.47 | 01-OCT-00:20 | 1.06 |
November | 0.151644E+11 | 1.06 | 5850.47 | 01-NOV-00:10 | 1.06 |
December | 0.156699E+11 | 1.06 | 5850.47 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.184500E+12 | 1.06 | |||
Minimum of Months | 0.141535E+11 | 1.05 | 5850.47 | 1.05 | |
Maximum of Months | 0.156699E+11 | 1.06 | 5850.47 | 1.06 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.160137E+10 | 1.06 | 597.88 | 01-JAN-00:05 | 1.06 |
February | 0.144640E+10 | 1.06 | 597.88 | 01-FEB-00:10 | 1.06 |
March | 0.160137E+10 | 1.06 | 597.88 | 01-MAR-00:10 | 1.06 |
April | 0.154971E+10 | 1.06 | 597.88 | 01-APR-00:10 | 1.06 |
May | 0.160137E+10 | 1.06 | 597.88 | 01-MAY-00:10 | 1.05 |
June | 0.154971E+10 | 1.05 | 597.88 | 01-JUN-00:03 | 1.05 |
July | 0.160137E+10 | 1.05 | 597.88 | 01-JUL-00:03 | 1.05 |
August | 0.160137E+10 | 1.05 | 597.88 | 01-AUG-00:10 | 1.05 |
September | 0.154971E+10 | 1.05 | 597.88 | 01-SEP-00:05 | 1.05 |
October | 0.160137E+10 | 1.05 | 597.88 | 01-OCT-00:20 | 1.06 |
November | 0.154971E+10 | 1.06 | 597.88 | 01-NOV-00:10 | 1.06 |
December | 0.160137E+10 | 1.06 | 597.88 | 01-DEC-00:10 | 1.06 |
Annual Sum or Average | 0.188548E+11 | 1.06 | |||
Minimum of Months | 0.144640E+10 | 1.05 | 597.88 | 1.05 | |
Maximum of Months | 0.160137E+10 | 1.06 | 597.88 | 1.06 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.284438E+09 | 0.255994E+09 | 3723.65 | 28-JAN-06:01 | 3351.29 | 3351.29 | 42.62 | 6.44 |
February | 0.167318E+09 | 0.150587E+09 | 3568.12 | 02-FEB-06:01 | 3211.31 | 3211.31 | 41.18 | 5.89 |
March | 82918844.59 | 74626960.13 | 3492.71 | 02-MAR-06:01 | 3143.44 | 3143.44 | 39.81 | 5.65 |
April | 4826723.94 | 4344051.55 | 2261.35 | 11-APR-05:02 | 2035.22 | 2035.22 | 30.57 | 2.91 |
May | 426.41 | 383.77 | 0.46 | 02-MAY-06:00 | 0.42 | 0.42 | 23.73 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 23.73 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 23.73 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 23.73 | 0.00 |
September | 1468.07 | 1321.27 | 1.31 | 25-SEP-05:50 | 1.18 | 1.18 | 23.72 | 0.00 |
October | 1395507.74 | 1255956.97 | 254.77 | 25-OCT-05:03 | 229.30 | 229.30 | 22.07 | 0.27 |
November | 96725025.47 | 87052522.92 | 3699.60 | 28-NOV-06:01 | 3329.64 | 3329.64 | 41.91 | 6.35 |
December | 0.383288E+09 | 0.344959E+09 | 3702.30 | 27-DEC-06:01 | 3332.07 | 3332.07 | 41.55 | 6.36 |
Annual Sum or Average | 0.102091E+10 | 0.918820E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 | |
Maximum of Months | 0.383288E+09 | 0.344959E+09 | 3723.65 | 3351.29 | 3351.29 | 42.62 | 6.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4956934.26 | 4461240.83 | 117.94 | 12-JAN-15:00 | 106.14 | 106.14 | 6.70 | 10.71 |
February | 17200629.27 | 15480566.34 | 177.72 | 22-FEB-13:50 | 159.95 | 159.95 | 6.70 | 13.41 |
March | 45329871.06 | 40796883.95 | 276.25 | 21-MAR-16:00 | 248.63 | 248.63 | 6.70 | 16.92 |
April | 0.215596E+09 | 0.194037E+09 | 2277.09 | 28-APR-13:00 | 2049.38 | 2049.38 | 6.71 | 45.92 |
May | 0.517513E+09 | 0.465762E+09 | 2331.15 | 30-MAY-14:00 | 2098.03 | 2098.03 | 6.71 | 46.40 |
June | 0.927974E+09 | 0.835176E+09 | 7060.91 | 17-JUN-05:02 | 6354.82 | 6354.82 | 8.15 | 74.13 |
July | 0.100179E+10 | 0.901610E+09 | 17523.18 | 18-JUL-05:03 | 15770.87 | 15770.87 | 10.20 | 106.69 |
August | 0.908113E+09 | 0.817301E+09 | 17523.18 | 03-AUG-05:03 | 15770.87 | 15770.87 | 10.25 | 106.69 |
September | 0.764688E+09 | 0.688219E+09 | 11542.71 | 23-SEP-05:03 | 10388.43 | 10388.43 | 9.11 | 90.43 |
October | 0.298924E+09 | 0.269031E+09 | 3040.99 | 02-OCT-05:02 | 2736.89 | 2736.89 | 6.71 | 52.06 |
November | 54832541.64 | 49349287.48 | 1577.49 | 03-NOV-15:20 | 1419.74 | 1419.74 | 6.71 | 39.03 |
December | 1625921.30 | 1463329.17 | 39.80 | 07-DEC-14:30 | 35.82 | 35.82 | 6.70 | 5.59 |
Annual Sum or Average | 0.475854E+10 | 0.428269E+10 | ||||||
Minimum of Months | 1625921.30 | 1463329.17 | 39.80 | 35.82 | 35.82 | 6.70 | 5.59 | |
Maximum of Months | 0.100179E+10 | 0.901610E+09 | 17523.18 | 15770.87 | 15770.87 | 10.25 | 106.69 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.241727E+10 | 0.217555E+10 | 6030.37 | 01-JAN-01:43 | 5427.33 | 5427.33 | 6.74 | 53.34 |
February | 0.348149E+10 | 0.313334E+10 | 6030.37 | 01-FEB-10:20 | 5427.33 | 5427.33 | 6.72 | 53.34 |
March | 0.555140E+10 | 0.499626E+10 | 6030.37 | 01-MAR-05:09 | 5427.33 | 5427.33 | 6.72 | 53.34 |
April | 0.971660E+10 | 0.874494E+10 | 6030.37 | 01-APR-04:12 | 5427.33 | 5427.33 | 6.76 | 53.34 |
May | 0.109644E+11 | 0.986793E+10 | 6030.37 | 01-MAY-00:10 | 5427.33 | 5427.33 | 6.82 | 53.34 |
June | 0.127952E+11 | 0.115157E+11 | 6030.37 | 01-JUN-04:12 | 5427.33 | 5427.33 | 9.20 | 53.34 |
July | 0.140955E+11 | 0.126859E+11 | 6030.37 | 01-JUL-00:03 | 5427.33 | 5427.33 | 7.05 | 53.34 |
August | 0.146575E+11 | 0.131918E+11 | 6030.37 | 01-AUG-00:05 | 5427.33 | 5427.33 | 6.88 | 53.34 |
September | 0.102496E+11 | 0.922467E+10 | 6030.37 | 01-SEP-00:05 | 5427.33 | 5427.33 | 6.83 | 53.34 |
October | 0.840382E+10 | 0.756343E+10 | 6030.37 | 01-OCT-07:23 | 5427.33 | 5427.33 | 7.69 | 53.34 |
November | 0.434217E+10 | 0.390795E+10 | 6030.37 | 01-NOV-04:12 | 5427.33 | 5427.33 | 6.92 | 53.34 |
December | 0.215852E+10 | 0.194267E+10 | 6030.37 | 01-DEC-06:40 | 5427.33 | 5427.33 | 6.72 | 53.34 |
Annual Sum or Average | 0.988335E+11 | 0.889502E+11 | ||||||
Minimum of Months | 0.215852E+10 | 0.194267E+10 | 6030.37 | 5427.33 | 5427.33 | 6.72 | 53.34 | |
Maximum of Months | 0.146575E+11 | 0.131918E+11 | 6030.37 | 5427.33 | 5427.33 | 9.20 | 53.34 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.76 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.991392E+09 | 0.892253E+09 | 6030.37 | 03-APR-12:10 | 5427.33 | 5427.33 | 11.71 | 26.67 |
May | 0.261959E+10 | 0.235763E+10 | 6030.37 | 02-MAY-15:20 | 5427.33 | 5427.33 | 11.80 | 26.67 |
June | 0.423050E+10 | 0.380745E+10 | 6030.37 | 01-JUN-08:70 | 5427.33 | 5427.33 | 12.72 | 26.67 |
July | 0.484910E+10 | 0.436419E+10 | 6030.37 | 01-JUL-13:50 | 5427.33 | 5427.33 | 11.94 | 26.67 |
August | 0.380703E+10 | 0.342633E+10 | 6030.37 | 01-AUG-07:40 | 5427.33 | 5427.33 | 12.71 | 26.67 |
September | 0.308634E+10 | 0.277771E+10 | 6030.37 | 01-SEP-07:20 | 5427.33 | 5427.33 | 12.04 | 26.67 |
October | 0.947974E+09 | 0.853176E+09 | 6030.37 | 02-OCT-09:40 | 5427.33 | 5427.33 | 12.07 | 26.67 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.81 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.205319E+11 | 0.184787E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.484910E+10 | 0.436419E+10 | 6030.37 | 5427.33 | 5427.33 | 12.72 | 26.67 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-JAN-00:05 | 3297.67 | 3297.67 | 18.77 | 15.30 |
February | 0.886412E+10 | 0.797771E+10 | 3664.07 | 01-FEB-00:10 | 3297.67 | 3297.67 | 19.37 | 15.30 |
March | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-MAR-00:10 | 3297.67 | 3297.67 | 19.89 | 15.30 |
April | 0.949728E+10 | 0.854755E+10 | 3664.07 | 01-APR-00:10 | 3297.67 | 3297.67 | 20.58 | 15.30 |
May | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-MAY-00:10 | 3297.67 | 3297.67 | 21.82 | 15.30 |
June | 0.949728E+10 | 0.854755E+10 | 3664.07 | 01-JUN-00:03 | 3297.67 | 3297.67 | 33.97 | 15.30 |
July | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-JUL-00:03 | 3297.67 | 3297.67 | 43.20 | 15.30 |
August | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-AUG-00:05 | 3297.67 | 3297.67 | 47.84 | 15.30 |
September | 0.949728E+10 | 0.854755E+10 | 3664.07 | 01-SEP-00:05 | 3297.67 | 3297.67 | 25.99 | 15.30 |
October | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-OCT-00:10 | 3297.67 | 3297.67 | 19.63 | 15.30 |
November | 0.949728E+10 | 0.854755E+10 | 3664.07 | 01-NOV-00:10 | 3297.67 | 3297.67 | 20.08 | 15.30 |
December | 0.981385E+10 | 0.883247E+10 | 3664.07 | 01-DEC-00:10 | 3297.67 | 3297.67 | 20.45 | 15.30 |
Annual Sum or Average | 0.115550E+12 | 0.103995E+12 | ||||||
Minimum of Months | 0.886412E+10 | 0.797771E+10 | 3664.07 | 3297.67 | 3297.67 | 18.77 | 15.30 | |
Maximum of Months | 0.981385E+10 | 0.883247E+10 | 3664.07 | 3297.67 | 3297.67 | 47.84 | 15.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.50 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.08 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.21 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.40 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.70 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.88 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.45 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.06 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.86 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.44 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.23 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.02 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.50 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.45 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.624063E+10 | 0.561657E+10 | 15590.72 | 03-JAN-14:30 | 14031.64 | 14031.64 | 23.30 | 63.08 |
February | 0.899136E+10 | 0.809222E+10 | 15604.65 | 21-FEB-16:10 | 14044.19 | 14044.19 | 24.54 | 63.08 |
March | 0.143421E+11 | 0.129079E+11 | 15619.83 | 21-MAR-16:00 | 14057.85 | 14057.85 | 25.77 | 63.08 |
April | 0.265942E+11 | 0.239348E+11 | 31243.76 | 21-APR-15:20 | 28119.38 | 28119.38 | 25.92 | 126.17 |
May | 0.328073E+11 | 0.295266E+11 | 31246.02 | 22-MAY-15:20 | 28121.42 | 28121.42 | 26.01 | 126.17 |
June | 0.423100E+11 | 0.380790E+11 | 31257.03 | 20-JUN-15:00 | 28131.33 | 28131.33 | 26.43 | 126.17 |
July | 0.472456E+11 | 0.425210E+11 | 31319.53 | 17-JUL-07:20 | 28187.58 | 28187.58 | 29.27 | 126.17 |
August | 0.463137E+11 | 0.416824E+11 | 31319.53 | 02-AUG-07:50 | 28187.58 | 28187.58 | 29.13 | 126.17 |
September | 0.332560E+11 | 0.299304E+11 | 31319.53 | 14-SEP-09:50 | 28187.58 | 28187.58 | 29.48 | 126.17 |
October | 0.234597E+11 | 0.211138E+11 | 31274.24 | 03-OCT-14:00 | 28146.82 | 28146.82 | 27.08 | 126.17 |
November | 0.112175E+11 | 0.100957E+11 | 15617.48 | 09-NOV-15:30 | 14055.74 | 14055.74 | 25.59 | 63.08 |
December | 0.557168E+10 | 0.501451E+10 | 15578.42 | 20-DEC-15:10 | 14020.57 | 14020.57 | 22.21 | 63.08 |
Annual Sum or Average | 0.298350E+12 | 0.268515E+12 | ||||||
Minimum of Months | 0.557168E+10 | 0.501451E+10 | 15578.42 | 14020.57 | 14020.57 | 22.21 | 63.08 | |
Maximum of Months | 0.472456E+11 | 0.425210E+11 | 31319.53 | 28187.58 | 28187.58 | 29.48 | 126.17 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 24786.86 | 1344044.31 | 09-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.80 | 24.80 | 16149.78 | 1150083.89 | 09-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23.46 | 23.46 | 7378.13 | 1145992.18 | 01-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.29 | 25.29 | 453.27 | 626068.80 | 11-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.73 | 23.73 | 0.04 | 115.37 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 23.73 | 23.73 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 23.73 | 23.73 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.73 | 23.73 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.73 | 23.73 | 0.14 | 325.98 | 25-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.72 | 23.72 | 132.88 | 66463.86 | 25-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.57 | 21.57 | 8763.58 | 1394787.39 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.25 | 24.25 | 33201.03 | 1238762.04 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 7559.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.57 | 21.57 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 33201.03 | 1394787.39 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12066.46 | 493421.22 | 03-JAN-14:30 | 8.91 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44331.96 | 788419.90 | 21-FEB-16:00 | 10.23 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 97828.62 | 1075673.51 | 21-MAR-16:00 | 11.51 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 286591.23 | 1669657.98 | 27-APR-12:50 | 10.43 | 8.11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 481172.35 | 1660886.58 | 12-MAY-15:10 | 10.42 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 659028.30 | 1814610.83 | 17-JUN-16:02 | 10.76 | 6.70 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 709913.23 | 4791389.81 | 20-JUL-15:10 | 17.44 | 11.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 631654.85 | 2132411.76 | 02-AUG-08:20 | 11.47 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 521044.67 | 2106637.36 | 14-SEP-09:50 | 11.41 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 266929.16 | 1613677.31 | 03-OCT-14:00 | 10.31 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75027.54 | 1033484.95 | 09-NOV-15:30 | 11.32 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 5254.80 | 225251.17 | 20-DEC-15:00 | 7.71 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 317373.84 | 0.00 | ||||||
Minimum of Months | 5254.80 | 225251.17 | 7.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 709913.23 | 4791389.81 | 17.44 | 11.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 11258.50 | 489206.85 | 03-JAN-14:30 | 18.75 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 43063.44 | 785193.08 | 21-FEB-16:00 | 21.12 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 96038.17 | 1072553.98 | 21-MAR-16:00 | 21.87 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 281285.17 | 1524485.52 | 28-APR-12:20 | 16.11 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 473455.43 | 2213989.76 | 30-MAY-05:02 | 22.04 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 650852.28 | 3496995.83 | 17-JUN-05:02 | 17.98 | 9.84 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 701231.60 | 5200279.47 | 22-JUL-05:03 | 18.35 | 12.51 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 623603.26 | 4928878.26 | 03-AUG-05:03 | 17.75 | 12.21 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 514279.04 | 3753290.05 | 22-SEP-04:12 | 16.82 | 10.71 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 262822.70 | 1827486.68 | 05-OCT-05:03 | 16.06 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 73573.75 | 1029934.90 | 09-NOV-15:30 | 19.34 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 4534.08 | 226359.84 | 20-DEC-15:00 | 16.87 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312785.59 | 0.00 | ||||||
Minimum of Months | 4534.08 | 226359.84 | 16.06 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 701231.60 | 5200279.47 | 22.04 | 12.51 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28981.69 | 190082.05 | 03-JAN-17:00 | 21.91 | 21.06 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 89197.78 | 642385.53 | 20-FEB-16:00 | 30.31 | 25.78 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 208050.25 | 1103208.96 | 21-MAR-16:00 | 38.75 | 29.91 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 761296.07 | 1827396.92 | 21-APR-15:00 | 51.74 | 39.27 | 0.00 | 0.00 | 01-APR-00:10 |
May | 523056.06 | 1299433.45 | 19-MAY-16:00 | 42.30 | 37.62 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1050017.81 | 1799617.36 | 02-JUN-16:00 | 51.24 | 43.36 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1463096.12 | 2037461.77 | 03-JUL-16:00 | 55.45 | 44.52 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1517760.37 | 2174903.95 | 07-AUG-16:10 | 57.87 | 44.66 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 499612.42 | 1238986.41 | 19-SEP-16:00 | 41.21 | 36.52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 334802.13 | 1430797.89 | 03-OCT-14:10 | 44.66 | 36.94 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 158199.31 | 997169.96 | 03-NOV-16:00 | 36.82 | 28.50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 134889.84 | 545545.05 | 10-DEC-15:00 | 28.52 | 21.91 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 567400.10 | 0.00 | ||||||
Minimum of Months | 28981.69 | 190082.05 | 21.91 | 21.06 | 0.00 | 0.00 | ||
Maximum of Months | 1517760.37 | 2174903.95 | 57.87 | 44.66 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.62 | 56.62 | 14431.24 | 48127.00 | 30-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.69 | 56.69 | 14495.98 | 48122.29 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.81 | 56.81 | 14799.38 | 47281.96 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.90 | 56.90 | 13125.00 | 44549.77 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.69 | 57.69 | 12531.09 | 41449.57 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.30 | 57.30 | 11895.32 | 38062.44 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.82 | 57.82 | 10589.55 | 35567.73 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.17 | 58.17 | 11468.06 | 35707.87 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.26 | 57.26 | 11340.46 | 38016.93 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.25 | 57.25 | 12162.56 | 41505.93 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.89 | 56.89 | 13283.89 | 44798.50 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 13653.15 | 47153.78 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12805.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.62 | 56.62 | 10589.55 | 35567.73 | ||
Maximum of Months | 0.00 | 0.00 | 58.17 | 58.17 | 14799.38 | 48127.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12261.20 | 580801.43 | 03-JAN-14:30 | 23.30 | 21.10 | 3597.46 | 142350.40 | 02-JAN-06:30 |
February | 48522.56 | 908171.08 | 21-FEB-16:10 | 24.54 | 21.10 | 2968.77 | 142597.65 | 02-FEB-14:00 |
March | 111007.09 | 1230654.92 | 21-MAR-16:00 | 25.77 | 21.10 | 2145.66 | 135845.71 | 17-MAR-05:30 |
April | 338193.02 | 2542393.50 | 21-APR-15:20 | 25.92 | 21.32 | 2120.47 | 120745.57 | 11-APR-05:04 |
May | 599395.08 | 2587908.00 | 22-MAY-15:20 | 26.01 | 22.10 | 427.14 | 113270.32 | 08-MAY-06:20 |
June | 885247.85 | 2809545.25 | 20-JUN-15:00 | 26.43 | 22.91 | 182.71 | 63628.68 | 13-JUN-05:50 |
July | 1253184.84 | 6474669.08 | 20-JUL-15:20 | 33.38 | 27.79 | 2.17 | 4668.84 | 16-JUL-04:10 |
August | 942517.66 | 4683375.36 | 02-AUG-08:20 | 29.98 | 25.33 | 242.74 | 44130.44 | 26-AUG-04:00 |
September | 755032.20 | 4418217.30 | 14-SEP-09:50 | 29.48 | 24.99 | 62.32 | 45397.93 | 12-SEP-06:25 |
October | 341445.11 | 3155508.85 | 03-OCT-14:00 | 27.08 | 23.56 | 592.66 | 103163.92 | 31-OCT-18:30 |
November | 85145.10 | 1183434.82 | 09-NOV-15:30 | 25.59 | 21.10 | 1985.86 | 138035.85 | 17-NOV-06:40 |
December | 3470.11 | 291496.71 | 20-DEC-15:10 | 22.21 | 21.10 | 3945.88 | 153171.52 | 18-DEC-10:20 |
Annual Sum or Average | 450490.11 | 1515.70 | ||||||
Minimum of Months | 3470.11 | 291496.71 | 22.21 | 21.10 | 2.17 | 4668.84 | ||
Maximum of Months | 1253184.84 | 6474669.08 | 33.38 | 27.79 | 3945.88 | 153171.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.106190E+10 | 0.00 | 0.313937E+10 | 0.566236E+10 | 0.00 | 0.00 |
February | 0.664048E+09 | 0.00 | 0.106476E+11 | 0.603817E+10 | 0.00 | 0.00 |
March | 0.268938E+09 | 0.00 | 0.266127E+11 | 0.897321E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.743385E+11 | 0.117911E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.108249E+12 | 0.118017E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.148427E+12 | 0.144388E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.179061E+12 | 0.149182E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.169649E+12 | 0.174156E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.116011E+12 | 0.114718E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.656806E+11 | 0.977251E+10 | 0.00 | 0.00 |
November | 79588513.02 | 0.00 | 0.197779E+11 | 0.776400E+10 | 0.00 | 0.00 |
December | 0.919548E+09 | 0.00 | 0.149962E+10 | 0.702181E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.299402E+10 | 0.00 | 0.923094E+12 | 0.127069E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.149962E+10 | 0.566236E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106190E+10 | 0.00 | 0.179061E+12 | 0.174156E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.517582E+11 | 0.00 | 0.240568E+11 | 0.386685E+11 | 0.00 | 0.00 |
February | 0.302556E+11 | 0.00 | 0.820405E+11 | 0.400055E+11 | 0.00 | 0.00 |
March | 0.147628E+11 | 0.00 | 0.198652E+12 | 0.552544E+11 | 0.00 | 0.00 |
April | 0.677247E+09 | 0.00 | 0.544898E+12 | 0.725190E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.956922E+12 | 0.989900E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127592E+13 | 0.119366E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.140363E+13 | 0.110404E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.123496E+13 | 0.114446E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.100094E+13 | 0.907732E+11 | 0.00 | 0.00 |
October | 57752740.03 | 0.00 | 0.527279E+12 | 0.656568E+11 | 0.00 | 0.00 |
November | 0.161892E+11 | 0.00 | 0.146898E+12 | 0.455914E+11 | 0.00 | 0.00 |
December | 0.705612E+11 | 0.00 | 0.986204E+10 | 0.379060E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.184262E+12 | 0.00 | 0.740606E+13 | 0.889581E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.986204E+10 | 0.379060E+11 | 0.00 | 0.00 |
Maximum of Months | 0.705612E+11 | 0.00 | 0.140363E+13 | 0.119366E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.144343E+11 | 0.00 | 0.171071E+10 | 0.332220E+10 | 0.00 | 0.00 |
February | 0.850797E+10 | 0.00 | 0.700477E+10 | 0.328604E+10 | 0.00 | 0.00 |
March | 0.489826E+10 | 0.00 | 0.183589E+11 | 0.450415E+10 | 0.00 | 0.00 |
April | 0.515476E+09 | 0.00 | 0.579875E+11 | 0.664794E+10 | 0.00 | 0.00 |
May | 120723.04 | 0.00 | 0.105098E+12 | 0.991141E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144505E+12 | 0.129070E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.157299E+12 | 0.119566E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.136363E+12 | 0.119336E+11 | 0.00 | 0.00 |
September | 412287.86 | 0.00 | 0.107119E+12 | 0.907998E+10 | 0.00 | 0.00 |
October | 0.311357E+09 | 0.00 | 0.531269E+11 | 0.591052E+10 | 0.00 | 0.00 |
November | 0.663777E+10 | 0.00 | 0.121347E+11 | 0.382941E+10 | 0.00 | 0.00 |
December | 0.182490E+11 | 0.00 | 0.588364E+09 | 0.331415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.535546E+11 | 0.00 | 0.801296E+12 | 0.866030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.588364E+09 | 0.328604E+10 | 0.00 | 0.00 |
Maximum of Months | 0.182490E+11 | 0.00 | 0.157299E+12 | 0.129070E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.132977E+10 | 0.176386E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.473085E+10 | 0.155193E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.128680E+11 | 0.180660E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.382977E+11 | 0.164929E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.663555E+11 | 0.178828E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.836771E+11 | 0.177345E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.972112E+11 | 0.182384E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.944098E+11 | 0.199966E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.763854E+11 | 0.189406E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.425616E+11 | 0.192295E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.111115E+11 | 0.182076E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.229426E+09 | 0.179586E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.529168E+12 | 0.215905E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.229426E+09 | 0.155193E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.972112E+11 | 0.199966E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.156311E+11 | 0.301334E+12 | 0.00 | 69.48 |
February | 0.00 | 0.00 | 0.369084E+11 | 0.334822E+12 | 0.00 | 83.73 |
March | 0.00 | 0.00 | 0.154904E+12 | 0.411921E+12 | 0.00 | 96.97 |
April | 0.00 | 0.00 | 0.736796E+12 | 0.550165E+12 | 0.00 | 92.04 |
May | 0.00 | 0.00 | 0.250663E+12 | 0.315328E+12 | 0.00 | 50.61 |
June | 0.00 | 0.00 | 0.692024E+12 | 0.338857E+12 | 0.00 | 15.41 |
July | 0.00 | 0.00 | 0.135486E+13 | 0.461309E+12 | 0.00 | 2.09 |
August | 0.00 | 0.00 | 0.148967E+13 | 0.528542E+12 | 0.00 | 16.12 |
September | 0.00 | 0.00 | 0.240806E+12 | 0.201845E+12 | 0.00 | 11.44 |
October | 0.00 | 0.00 | 0.234686E+12 | 0.276643E+12 | 0.00 | 39.62 |
November | 0.00 | 0.00 | 0.104398E+12 | 0.368298E+12 | 0.00 | 87.43 |
December | 0.00 | 0.00 | 0.755531E+11 | 0.397336E+12 | 0.00 | 99.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.538691E+13 | 0.448640E+13 | 0.00 | 664.47 |
Minimum of Months | 0.00 | 0.00 | 0.156311E+11 | 0.201845E+12 | 0.00 | 2.09 |
Maximum of Months | 0.00 | 0.00 | 0.148967E+13 | 0.550165E+12 | 0.00 | 99.53 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.626031E+10 | 0.297527E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.118029E+11 | 0.391963E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198326E+11 | 0.566407E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.265353E+11 | 0.754703E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.858093E+10 | 0.377011E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154867E+11 | 0.574191E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.231873E+11 | 0.786514E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.296550E+11 | 0.931984E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.854180E+10 | 0.365955E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144998E+11 | 0.477085E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.191248E+11 | 0.536092E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.253648E+11 | 0.649597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208872E+12 | 0.670903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.626031E+10 | 0.297527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.296550E+11 | 0.931984E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.416769E+11 | 0.247226E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.994249E+11 | 0.348456E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.178830E+12 | 0.521291E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249263E+12 | 0.712610E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.790829E+11 | 0.353314E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.147366E+12 | 0.546520E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220693E+12 | 0.748476E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279921E+12 | 0.882201E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.780477E+11 | 0.341288E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131252E+12 | 0.441238E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.168734E+12 | 0.486706E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.222015E+12 | 0.585207E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189631E+13 | 0.621453E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.416769E+11 | 0.247226E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279921E+12 | 0.882201E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.230805E+10 | 0.211371E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.852429E+10 | 0.324194E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.168425E+11 | 0.506553E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.246600E+11 | 0.713339E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.789766E+10 | 0.357605E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149178E+11 | 0.555550E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223089E+11 | 0.759398E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.281732E+11 | 0.892472E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.776983E+10 | 0.344836E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125775E+11 | 0.435096E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153799E+11 | 0.463676E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.200664E+11 | 0.552069E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181426E+12 | 0.611616E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.230805E+10 | 0.211371E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.281732E+11 | 0.892472E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.566236E+10 | 0.313937E+10 | 0.106190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603817E+10 | 0.106476E+11 | 0.664048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897321E+10 | 0.266127E+11 | 0.268938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117911E+11 | 0.743385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118017E+11 | 0.108249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144388E+11 | 0.148427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149182E+11 | 0.179061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174156E+11 | 0.169649E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114718E+11 | 0.116011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977251E+10 | 0.656806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776400E+10 | 0.197779E+11 | 79588513.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702181E+10 | 0.149962E+10 | 0.919548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127069E+12 | 0.923094E+12 | 0.299402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566236E+10 | 0.149962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174156E+11 | 0.179061E+12 | 0.106190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386685E+11 | 0.240568E+11 | 0.517582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400055E+11 | 0.820405E+11 | 0.302556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552544E+11 | 0.198652E+12 | 0.147628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725190E+11 | 0.544898E+12 | 0.677247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989900E+11 | 0.956922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119366E+12 | 0.127592E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110404E+12 | 0.140363E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114446E+12 | 0.123496E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907732E+11 | 0.100094E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.656568E+11 | 0.527279E+12 | 57752740.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455914E+11 | 0.146898E+12 | 0.161892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379060E+11 | 0.986204E+10 | 0.705612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889581E+12 | 0.740606E+13 | 0.184262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.379060E+11 | 0.986204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119366E+12 | 0.140363E+13 | 0.705612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.332220E+10 | 0.171071E+10 | 0.144343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328604E+10 | 0.700477E+10 | 0.850797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450415E+10 | 0.183589E+11 | 0.489826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664794E+10 | 0.579875E+11 | 0.515476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.991141E+10 | 0.105098E+12 | 120723.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129070E+11 | 0.144505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119566E+11 | 0.157299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119336E+11 | 0.136363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907998E+10 | 0.107119E+12 | 412287.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591052E+10 | 0.531269E+11 | 0.311357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382941E+10 | 0.121347E+11 | 0.663777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331415E+10 | 0.588364E+09 | 0.182490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866030E+11 | 0.801296E+12 | 0.535546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328604E+10 | 0.588364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129070E+11 | 0.157299E+12 | 0.182490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176386E+11 | 0.132977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155193E+11 | 0.473085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180660E+11 | 0.128680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164929E+11 | 0.382977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178828E+11 | 0.663555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177345E+11 | 0.836771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182384E+11 | 0.972112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199966E+11 | 0.944098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189406E+11 | 0.763854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192295E+11 | 0.425616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182076E+11 | 0.111115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179586E+11 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215905E+12 | 0.529168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155193E+11 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199966E+11 | 0.972112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109094E+12 | 0.101543E+11 | 0.00 | 0.00 | 0.00 | 0.185926E+12 | 0.00 | 0.00 |
February | 0.985366E+11 | 0.256980E+11 | 0.00 | 0.00 | 0.00 | 0.224066E+12 | 0.00 | 0.00 |
March | 0.109094E+12 | 0.112760E+12 | 0.00 | 0.00 | 0.00 | 0.259514E+12 | 0.00 | 0.00 |
April | 0.105575E+12 | 0.539616E+12 | 0.00 | 0.00 | 0.00 | 0.246302E+12 | 0.00 | 0.00 |
May | 0.109094E+12 | 0.180490E+12 | 0.00 | 0.00 | 0.00 | 0.135451E+12 | 0.00 | 0.00 |
June | 0.105575E+12 | 0.500169E+12 | 0.00 | 0.00 | 0.00 | 0.412421E+11 | 0.00 | 0.00 |
July | 0.109094E+12 | 0.100828E+13 | 0.00 | 0.00 | 0.00 | 0.560344E+10 | 0.00 | 0.00 |
August | 0.109094E+12 | 0.111355E+13 | 0.00 | 0.00 | 0.00 | 0.431330E+11 | 0.00 | 0.00 |
September | 0.105575E+12 | 0.175296E+12 | 0.00 | 0.00 | 0.00 | 0.306222E+11 | 0.00 | 0.00 |
October | 0.109094E+12 | 0.173641E+12 | 0.00 | 0.00 | 0.00 | 0.106027E+12 | 0.00 | 0.00 |
November | 0.105575E+12 | 0.767010E+11 | 0.00 | 0.00 | 0.00 | 0.233973E+12 | 0.00 | 0.00 |
December | 0.109094E+12 | 0.548677E+11 | 0.00 | 0.00 | 0.00 | 0.266358E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.128449E+13 | 0.397122E+13 | 0.00 | 0.00 | 0.00 | 0.177822E+13 | 0.00 | 0.00 |
Minimum of Months | 0.985366E+11 | 0.101543E+11 | 0.00 | 0.00 | 0.00 | 0.560344E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109094E+12 | 0.111355E+13 | 0.00 | 0.00 | 0.00 | 0.266358E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164643E+10 | 0.493147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148710E+10 | 0.937033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164643E+10 | 0.158150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159332E+10 | 0.205816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164643E+10 | 0.645726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159332E+10 | 0.113381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164643E+10 | 0.169686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164643E+10 | 0.219816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159332E+10 | 0.647558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164643E+10 | 0.113754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159332E+10 | 0.153572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164643E+10 | 0.205152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193854E+11 | 0.161168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148710E+10 | 0.493147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164643E+10 | 0.219816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156699E+11 | 0.326242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141535E+11 | 0.787327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156699E+11 | 0.142371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151644E+11 | 0.193166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156699E+11 | 0.594215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151644E+11 | 0.107878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156699E+11 | 0.161515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156699E+11 | 0.207371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151644E+11 | 0.590833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156699E+11 | 0.102798E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151644E+11 | 0.135228E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156699E+11 | 0.179164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184500E+12 | 0.145935E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141535E+11 | 0.326242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156699E+11 | 0.207371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.160137E+10 | 0.179570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144640E+10 | 0.672875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160137E+10 | 0.133783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154971E+10 | 0.190763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160137E+10 | 0.592297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154971E+10 | 0.109120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160137E+10 | 0.163163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160137E+10 | 0.208498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154971E+10 | 0.587118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160137E+10 | 0.982794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154971E+10 | 0.122928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160137E+10 | 0.161471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188548E+11 | 0.139119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144640E+10 | 0.179570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160137E+10 | 0.208498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.566236E+10 | 0.106190E+10 | 0.313937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603817E+10 | 0.664048E+09 | 0.106476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897321E+10 | 0.268938E+09 | 0.266127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117911E+11 | 0.00 | 0.743385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118017E+11 | 0.00 | 0.108249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144388E+11 | 0.00 | 0.148427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149182E+11 | 0.00 | 0.179061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174156E+11 | 0.00 | 0.169649E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114718E+11 | 0.00 | 0.116011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977251E+10 | 0.00 | 0.656806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776400E+10 | 79588513.02 | 0.197779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702181E+10 | 0.919548E+09 | 0.149962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127069E+12 | 0.299402E+10 | 0.923094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566236E+10 | 0.00 | 0.149962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174156E+11 | 0.106190E+10 | 0.179061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.386685E+11 | 0.517582E+11 | 0.240568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400055E+11 | 0.302556E+11 | 0.820405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552544E+11 | 0.147628E+11 | 0.198652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725190E+11 | 0.677247E+09 | 0.544898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.989900E+11 | 0.00 | 0.956922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119366E+12 | 0.00 | 0.127592E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110404E+12 | 0.00 | 0.140363E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114446E+12 | 0.00 | 0.123496E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907732E+11 | 0.00 | 0.100094E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.656568E+11 | 57752740.03 | 0.527279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455914E+11 | 0.161892E+11 | 0.146898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379060E+11 | 0.705612E+11 | 0.986204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889581E+12 | 0.184262E+12 | 0.740606E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.379060E+11 | 0.00 | 0.986204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119366E+12 | 0.705612E+11 | 0.140363E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.332220E+10 | 0.144343E+11 | 0.171071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328604E+10 | 0.850797E+10 | 0.700477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450415E+10 | 0.489826E+10 | 0.183589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664794E+10 | 0.515476E+09 | 0.579875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.991141E+10 | 120723.04 | 0.105098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129070E+11 | 0.00 | 0.144505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119566E+11 | 0.00 | 0.157299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119336E+11 | 0.00 | 0.136363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907998E+10 | 412287.86 | 0.107119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591052E+10 | 0.311357E+09 | 0.531269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382941E+10 | 0.663777E+10 | 0.121347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331415E+10 | 0.182490E+11 | 0.588364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866030E+11 | 0.535546E+11 | 0.801296E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328604E+10 | 0.00 | 0.588364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129070E+11 | 0.182490E+11 | 0.157299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176386E+11 | 0.00 | 0.132977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155193E+11 | 0.00 | 0.473085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180660E+11 | 0.00 | 0.128680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164929E+11 | 0.00 | 0.382977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178828E+11 | 0.00 | 0.663555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.177345E+11 | 0.00 | 0.836771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182384E+11 | 0.00 | 0.972112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199966E+11 | 0.00 | 0.944098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189406E+11 | 0.00 | 0.763854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192295E+11 | 0.00 | 0.425616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182076E+11 | 0.00 | 0.111115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179586E+11 | 0.00 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215905E+12 | 0.00 | 0.529168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155193E+11 | 0.00 | 0.229426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199966E+11 | 0.00 | 0.972112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109094E+12 | 0.00 | 0.156311E+11 | 0.00 | 0.547675E+10 | 0.00 | 0.00 | 0.00 | 0.186763E+12 | 0.00 | 0.00 | 0.00 |
February | 0.985366E+11 | 0.00 | 0.369084E+11 | 0.00 | 0.112104E+11 | 0.00 | 0.00 | 0.00 | 0.225075E+12 | 0.00 | 0.00 | 0.00 |
March | 0.109094E+12 | 0.00 | 0.154904E+12 | 0.00 | 0.421446E+11 | 0.00 | 0.00 | 0.00 | 0.260682E+12 | 0.00 | 0.00 | 0.00 |
April | 0.105575E+12 | 0.00 | 0.736796E+12 | 0.00 | 0.197180E+12 | 0.00 | 0.00 | 0.00 | 0.247410E+12 | 0.00 | 0.00 | 0.00 |
May | 0.109094E+12 | 0.00 | 0.250663E+12 | 0.00 | 0.701734E+11 | 0.00 | 0.00 | 0.00 | 0.136060E+12 | 0.00 | 0.00 | 0.00 |
June | 0.105575E+12 | 0.00 | 0.692024E+12 | 0.00 | 0.191855E+12 | 0.00 | 0.00 | 0.00 | 0.414278E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109094E+12 | 0.00 | 0.135486E+13 | 0.00 | 0.346586E+12 | 0.00 | 0.00 | 0.00 | 0.562866E+10 | 0.00 | 0.00 | 0.00 |
August | 0.109094E+12 | 0.00 | 0.148967E+13 | 0.00 | 0.376121E+12 | 0.00 | 0.00 | 0.00 | 0.433272E+11 | 0.00 | 0.00 | 0.00 |
September | 0.105575E+12 | 0.00 | 0.240806E+12 | 0.00 | 0.655103E+11 | 0.00 | 0.00 | 0.00 | 0.307600E+11 | 0.00 | 0.00 | 0.00 |
October | 0.109094E+12 | 0.00 | 0.234686E+12 | 0.00 | 0.610449E+11 | 0.00 | 0.00 | 0.00 | 0.106505E+12 | 0.00 | 0.00 | 0.00 |
November | 0.105575E+12 | 0.00 | 0.104398E+12 | 0.00 | 0.276972E+11 | 0.00 | 0.00 | 0.00 | 0.235026E+12 | 0.00 | 0.00 | 0.00 |
December | 0.109094E+12 | 0.00 | 0.755531E+11 | 0.00 | 0.206855E+11 | 0.00 | 0.00 | 0.00 | 0.267557E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128449E+13 | 0.00 | 0.538691E+13 | 0.00 | 0.141568E+13 | 0.00 | 0.00 | 0.00 | 0.178622E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985366E+11 | 0.00 | 0.156311E+11 | 0.00 | 0.547675E+10 | 0.00 | 0.00 | 0.00 | 0.562866E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109094E+12 | 0.00 | 0.148967E+13 | 0.00 | 0.376121E+12 | 0.00 | 0.00 | 0.00 | 0.267557E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164643E+10 | 0.00 | 0.626031E+10 | 0.00 | 0.132884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148710E+10 | 0.00 | 0.118029E+11 | 0.00 | 0.243253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164643E+10 | 0.00 | 0.198326E+11 | 0.00 | 0.401764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159332E+10 | 0.00 | 0.265353E+11 | 0.00 | 0.595370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164643E+10 | 0.00 | 0.858093E+10 | 0.00 | 0.212368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159332E+10 | 0.00 | 0.154867E+11 | 0.00 | 0.414859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164643E+10 | 0.00 | 0.231873E+11 | 0.00 | 0.621870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164643E+10 | 0.00 | 0.296550E+11 | 0.00 | 0.767341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159332E+10 | 0.00 | 0.854180E+10 | 0.00 | 0.206622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164643E+10 | 0.00 | 0.144998E+11 | 0.00 | 0.312441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159332E+10 | 0.00 | 0.191248E+11 | 0.00 | 0.376760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164643E+10 | 0.00 | 0.253648E+11 | 0.00 | 0.484953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193854E+11 | 0.00 | 0.208872E+12 | 0.00 | 0.477049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148710E+10 | 0.00 | 0.626031E+10 | 0.00 | 0.132884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164643E+10 | 0.00 | 0.296550E+11 | 0.00 | 0.767341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156699E+11 | 0.00 | 0.416769E+11 | 0.00 | 0.905275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141535E+11 | 0.00 | 0.994249E+11 | 0.00 | 0.206921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156699E+11 | 0.00 | 0.178830E+12 | 0.00 | 0.364592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151644E+11 | 0.00 | 0.249263E+12 | 0.00 | 0.560965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156699E+11 | 0.00 | 0.790829E+11 | 0.00 | 0.196614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151644E+11 | 0.00 | 0.147366E+12 | 0.00 | 0.394876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156699E+11 | 0.00 | 0.220693E+12 | 0.00 | 0.591777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156699E+11 | 0.00 | 0.279921E+12 | 0.00 | 0.725502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151644E+11 | 0.00 | 0.780477E+11 | 0.00 | 0.189644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156699E+11 | 0.00 | 0.131252E+12 | 0.00 | 0.284539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151644E+11 | 0.00 | 0.168734E+12 | 0.00 | 0.335062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156699E+11 | 0.00 | 0.222015E+12 | 0.00 | 0.428508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184500E+12 | 0.00 | 0.189631E+13 | 0.00 | 0.436953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141535E+11 | 0.00 | 0.416769E+11 | 0.00 | 0.905275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156699E+11 | 0.00 | 0.279921E+12 | 0.00 | 0.725502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.160137E+10 | 0.00 | 0.230805E+10 | 0.00 | 0.512343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144640E+10 | 0.00 | 0.852429E+10 | 0.00 | 0.179554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160137E+10 | 0.00 | 0.168425E+11 | 0.00 | 0.346416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154971E+10 | 0.00 | 0.246600E+11 | 0.00 | 0.558368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160137E+10 | 0.00 | 0.789766E+10 | 0.00 | 0.197469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154971E+10 | 0.00 | 0.149178E+11 | 0.00 | 0.400579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160137E+10 | 0.00 | 0.223089E+11 | 0.00 | 0.599261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160137E+10 | 0.00 | 0.281732E+11 | 0.00 | 0.732335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154971E+10 | 0.00 | 0.776983E+10 | 0.00 | 0.189865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160137E+10 | 0.00 | 0.125775E+11 | 0.00 | 0.274959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154971E+10 | 0.00 | 0.153799E+11 | 0.00 | 0.308705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160137E+10 | 0.00 | 0.200664E+11 | 0.00 | 0.391932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188548E+11 | 0.00 | 0.181426E+12 | 0.00 | 0.423068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144640E+10 | 0.00 | 0.230805E+10 | 0.00 | 0.512343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160137E+10 | 0.00 | 0.281732E+11 | 0.00 | 0.732335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462753E+09 | 0.00 | 0.00 | 0.127403E+09 | 0.00 | 0.00 | 0.766015E+11 | 0.00 | 1.03 |
February | 0.218833E+09 | 0.00 | 0.00 | 0.103795E+09 | 0.00 | 0.00 | 0.636775E+11 | 0.00 | 1.16 |
March | 0.155666E+09 | 0.00 | 0.00 | 0.116736E+09 | 0.00 | 0.00 | 0.677372E+11 | 0.00 | 1.45 |
April | 38508755.55 | 0.528860E+09 | 0.00 | 0.101976E+09 | 28143253.29 | 0.00 | 0.391031E+11 | 0.00 | 1.23 |
May | 57826869.07 | 0.185601E+10 | 0.00 | 74687449.88 | 84574054.30 | 0.00 | 0.188109E+11 | 0.00 | 0.98 |
June | 80802391.83 | 0.627743E+10 | 0.00 | 47962003.52 | 0.115912E+09 | 0.00 | 0.696266E+10 | 0.00 | 0.75 |
July | 19564761.30 | 0.124563E+11 | 0.00 | 22824147.52 | 0.108180E+09 | 0.00 | 0.213510E+10 | 0.00 | 0.75 |
August | 16122683.55 | 0.465849E+10 | 0.00 | 72592221.07 | 79917769.30 | 0.00 | 0.103489E+11 | 0.00 | 0.98 |
September | 0.193769E+09 | 0.227226E+10 | 0.00 | 92506539.95 | 35876364.88 | 0.00 | 0.175240E+11 | 0.00 | 1.05 |
October | 0.257337E+09 | 0.354641E+09 | 0.00 | 0.135516E+09 | 3278609.49 | 0.00 | 0.514474E+11 | 0.00 | 1.61 |
November | 0.384424E+09 | 0.00 | 0.00 | 0.143876E+09 | 0.00 | 0.00 | 0.767722E+11 | 0.00 | 1.46 |
December | 0.480210E+09 | 0.00 | 0.00 | 0.141116E+09 | 0.00 | 0.00 | 0.831130E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.236582E+10 | 0.284040E+11 | 0.00 | 0.118099E+10 | 0.455882E+09 | 0.00 | 0.514233E+12 | 0.00 | 1.12 |
Minimum of Months | 16122683.55 | 0.00 | 0.00 | 22824147.52 | 0.00 | 0.00 | 0.213510E+10 | 0.00 | 0.75 |
Maximum of Months | 0.480210E+09 | 0.124563E+11 | 0.00 | 0.143876E+09 | 0.115912E+09 | 0.00 | 0.831130E+11 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236992E+10 | 0.00 | 0.00 | 86016969.04 | 0.00 | 0.00 | 0.504888E+11 | 0.00 | 0.68 |
February | 0.233128E+10 | 0.00 | 0.00 | 83567023.36 | 0.00 | 0.00 | 0.462864E+11 | 0.00 | 0.83 |
March | 0.265461E+10 | 0.00 | 0.00 | 0.106762E+09 | 0.00 | 0.00 | 0.528581E+11 | 0.00 | 1.06 |
April | 0.440346E+10 | 0.280300E+09 | 0.00 | 96864183.07 | 95065030.38 | 0.00 | 0.319521E+11 | 0.00 | 1.04 |
May | 0.161477E+10 | 0.978921E+09 | 0.00 | 70107492.33 | 0.189864E+09 | 0.00 | 0.138748E+11 | 0.00 | 0.70 |
June | 0.155099E+10 | 0.346590E+10 | 0.00 | 43730670.25 | 0.295193E+09 | 0.00 | 0.500759E+10 | 0.00 | 0.57 |
July | 0.582697E+09 | 0.116310E+11 | 0.00 | 11798845.26 | 0.218591E+10 | 0.00 | 0.678342E+09 | 0.00 | 0.59 |
August | 0.247340E+10 | 0.398819E+10 | 0.00 | 53714404.92 | 0.794305E+09 | 0.00 | 0.708332E+10 | 0.00 | 0.84 |
September | 0.142993E+10 | 0.212753E+10 | 0.00 | 64629278.79 | 0.206665E+09 | 0.00 | 0.992673E+10 | 0.00 | 0.69 |
October | 0.221814E+10 | 0.553690E+09 | 0.00 | 96688661.42 | 21274536.39 | 0.00 | 0.350584E+11 | 0.00 | 1.04 |
November | 0.325207E+10 | 0.00 | 0.00 | 0.105701E+09 | 0.00 | 0.00 | 0.524536E+11 | 0.00 | 0.98 |
December | 0.272274E+10 | 0.00 | 0.00 | 0.105232E+09 | 0.00 | 0.00 | 0.598869E+11 | 0.00 | 0.74 |
Annual Sum or Average | 0.276040E+11 | 0.230256E+11 | 0.00 | 0.924812E+09 | 0.378828E+10 | 0.00 | 0.365555E+12 | 0.00 | 0.81 |
Minimum of Months | 0.582697E+09 | 0.00 | 0.00 | 11798845.26 | 0.00 | 0.00 | 0.678342E+09 | 0.00 | 0.57 |
Maximum of Months | 0.440346E+10 | 0.116310E+11 | 0.00 | 0.106762E+09 | 0.218591E+10 | 0.00 | 0.598869E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102385E+12 | 0.00 | 0.00 | 0.391501E+09 | 0.00 | 0.00 | 0.270522E+12 | 0.00 | 0.49 |
February | 0.688387E+11 | 0.00 | 0.00 | 0.425208E+09 | 0.00 | 0.00 | 0.278047E+12 | 0.00 | 0.61 |
March | 0.434165E+11 | 0.00 | 0.00 | 0.633072E+09 | 0.00 | 0.00 | 0.345455E+12 | 0.00 | 0.78 |
April | 0.161446E+11 | 0.283329E+10 | 0.00 | 0.677241E+09 | 0.556150E+09 | 0.00 | 0.226460E+12 | 0.00 | 0.71 |
May | 0.120735E+11 | 0.101796E+11 | 0.00 | 0.575732E+09 | 0.116566E+10 | 0.00 | 0.113540E+12 | 0.00 | 0.60 |
June | 0.565238E+10 | 0.357333E+11 | 0.00 | 0.368185E+09 | 0.190553E+10 | 0.00 | 0.428458E+11 | 0.00 | 0.47 |
July | 0.154148E+10 | 0.102537E+12 | 0.00 | 91040498.45 | 0.471675E+10 | 0.00 | 0.529239E+10 | 0.00 | 0.44 |
August | 0.343229E+10 | 0.335396E+11 | 0.00 | 0.434361E+09 | 0.256344E+10 | 0.00 | 0.579760E+11 | 0.00 | 0.57 |
September | 0.984272E+10 | 0.204213E+11 | 0.00 | 0.510375E+09 | 0.121906E+10 | 0.00 | 0.766163E+11 | 0.00 | 0.57 |
October | 0.213016E+11 | 0.495709E+10 | 0.00 | 0.661458E+09 | 0.424298E+09 | 0.00 | 0.249298E+12 | 0.00 | 0.79 |
November | 0.553422E+11 | 0.00 | 0.00 | 0.543676E+09 | 0.00 | 0.00 | 0.304515E+12 | 0.00 | 0.67 |
December | 0.114330E+12 | 0.00 | 0.00 | 0.369375E+09 | 0.00 | 0.00 | 0.266356E+12 | 0.00 | 0.47 |
Annual Sum or Average | 0.454301E+12 | 0.210201E+12 | 0.00 | 0.568123E+10 | 0.125509E+11 | 0.00 | 0.223692E+13 | 0.00 | 0.60 |
Minimum of Months | 0.154148E+10 | 0.00 | 0.00 | 91040498.45 | 0.00 | 0.00 | 0.529239E+10 | 0.00 | 0.44 |
Maximum of Months | 0.114330E+12 | 0.102537E+12 | 0.00 | 0.677241E+09 | 0.471675E+10 | 0.00 | 0.345455E+12 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175044E+11 | 0.00 | 0.00 | 11320841.71 | 0.00 | 0.563904E+09 | 0.103130E+11 | 0.00 | 0.39 |
February | 0.129638E+11 | 0.00 | 0.00 | 17462734.41 | 0.00 | 12699956.29 | 0.136541E+11 | 0.00 | 0.50 |
March | 0.999743E+10 | 0.00 | 0.00 | 35699757.82 | 0.00 | 0.00 | 0.215377E+11 | 0.00 | 0.67 |
April | 0.321352E+10 | 0.155324E+09 | 0.00 | 55471044.07 | 56881459.62 | 0.00 | 0.174558E+11 | 0.00 | 0.68 |
May | 0.157117E+10 | 0.670132E+09 | 0.00 | 56973119.80 | 0.119156E+09 | 0.00 | 0.927104E+10 | 0.00 | 0.59 |
June | 0.592073E+09 | 0.299557E+10 | 0.00 | 42639194.67 | 0.184589E+09 | 0.00 | 0.398029E+10 | 0.00 | 0.47 |
July | 0.159886E+09 | 0.982657E+10 | 0.00 | 11391366.93 | 0.516358E+09 | 0.00 | 0.477459E+09 | 0.00 | 0.44 |
August | 0.333138E+09 | 0.287278E+10 | 0.00 | 47536691.24 | 0.241558E+09 | 0.00 | 0.550041E+10 | 0.00 | 0.56 |
September | 0.132979E+10 | 0.160971E+10 | 0.00 | 50472890.77 | 0.126462E+09 | 0.00 | 0.579265E+10 | 0.00 | 0.55 |
October | 0.463416E+10 | 0.366577E+09 | 0.00 | 48432360.83 | 56429600.30 | 0.00 | 0.176524E+11 | 0.00 | 0.72 |
November | 0.125132E+11 | 0.00 | 0.00 | 24903046.81 | 0.00 | 0.216906E+09 | 0.151189E+11 | 0.00 | 0.55 |
December | 0.192413E+11 | 0.00 | 0.00 | 8649820.91 | 0.00 | 0.520703E+09 | 0.856832E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.840538E+11 | 0.184967E+11 | 0.00 | 0.410953E+09 | 0.130143E+10 | 0.131421E+10 | 0.129322E+12 | 0.00 | 0.54 |
Minimum of Months | 0.159886E+09 | 0.00 | 0.00 | 8649820.91 | 0.00 | 0.00 | 0.477459E+09 | 0.00 | 0.37 |
Maximum of Months | 0.192413E+11 | 0.982657E+10 | 0.00 | 56973119.80 | 0.516358E+09 | 0.563904E+09 | 0.215377E+11 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311269E+10 | 0.00 | 0.00 | 929759.47 | 0.00 | 56524947.01 | 0.966613E+09 | 0.00 | 0.42 |
February | 0.236485E+10 | 0.00 | 0.00 | 2149316.34 | 0.00 | 35471849.55 | 0.144339E+10 | 0.00 | 0.54 |
March | 0.188673E+10 | 0.00 | 0.00 | 5076589.07 | 0.00 | 526324.01 | 0.273984E+10 | 0.00 | 0.77 |
April | 0.101363E+10 | 50291780.72 | 0.00 | 8417173.68 | 12083882.03 | 0.00 | 0.253141E+10 | 0.00 | 0.91 |
May | 0.341474E+09 | 0.200273E+09 | 0.00 | 8381791.80 | 24442410.04 | 0.00 | 0.143719E+10 | 0.00 | 0.75 |
June | 0.228559E+09 | 0.775574E+09 | 0.00 | 6488262.67 | 34843339.56 | 0.00 | 0.674057E+09 | 0.00 | 0.76 |
July | 75693901.50 | 0.202061E+10 | 0.00 | 1792556.67 | 0.281717E+09 | 0.00 | 96798677.02 | 0.00 | 0.76 |
August | 0.332192E+09 | 0.676826E+09 | 0.00 | 7269267.07 | 0.100123E+09 | 0.00 | 0.855884E+09 | 0.00 | 0.94 |
September | 0.305364E+09 | 0.331119E+09 | 0.00 | 6612027.98 | 27800644.73 | 0.00 | 0.850799E+09 | 0.00 | 0.67 |
October | 0.947604E+09 | 84502116.70 | 0.00 | 7029325.96 | 2519974.14 | 0.00 | 0.244269E+10 | 0.00 | 0.84 |
November | 0.214206E+10 | 0.00 | 0.00 | 3790611.06 | 0.00 | 0.00 | 0.213598E+10 | 0.00 | 0.62 |
December | 0.323881E+10 | 0.00 | 0.00 | 1182701.89 | 0.00 | 843410.31 | 0.113718E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.159897E+11 | 0.413920E+10 | 0.00 | 59119383.66 | 0.483530E+09 | 93366530.88 | 0.173118E+11 | 0.00 | 0.70 |
Minimum of Months | 75693901.50 | 0.00 | 0.00 | 929759.47 | 0.00 | 0.00 | 96798677.02 | 0.00 | 0.42 |
Maximum of Months | 0.323881E+10 | 0.202061E+10 | 0.00 | 8417173.68 | 0.281717E+09 | 56524947.01 | 0.273984E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240249E+10 | 0.00 | 0.00 | 2410789.71 | 0.00 | 46841770.05 | 0.181984E+10 | 0.00 | 0.66 |
February | 0.180028E+10 | 0.00 | 0.00 | 3813342.17 | 0.00 | 37392798.17 | 0.235793E+10 | 0.00 | 0.88 |
March | 0.162428E+10 | 0.00 | 0.00 | 6967240.88 | 0.00 | 5370708.85 | 0.379997E+10 | 0.00 | 1.27 |
April | 0.938710E+09 | 37292879.81 | 0.00 | 10650056.84 | 11525035.41 | 0.00 | 0.341511E+10 | 0.00 | 1.57 |
May | 0.291161E+09 | 0.168410E+09 | 0.00 | 10731669.83 | 23076368.26 | 0.00 | 0.206576E+10 | 0.00 | 1.37 |
June | 0.215771E+09 | 0.589103E+09 | 0.00 | 6691807.66 | 35419506.04 | 0.00 | 0.693103E+09 | 0.00 | 1.13 |
July | 75663309.17 | 0.162532E+10 | 0.00 | 1608711.64 | 0.277462E+09 | 0.00 | 86043048.53 | 0.00 | 1.04 |
August | 0.374783E+09 | 0.561030E+09 | 0.00 | 5938146.54 | 0.104749E+09 | 0.00 | 0.705149E+09 | 0.00 | 1.29 |
September | 0.282837E+09 | 0.343993E+09 | 0.00 | 8012770.35 | 24765494.07 | 0.00 | 0.119395E+10 | 0.00 | 1.22 |
October | 0.106979E+10 | 59891276.22 | 0.00 | 7665481.35 | 3402736.96 | 0.00 | 0.268614E+10 | 0.00 | 1.32 |
November | 0.198067E+10 | 0.00 | 0.00 | 4779206.46 | 0.00 | 2701934.22 | 0.253767E+10 | 0.00 | 0.97 |
December | 0.264301E+10 | 0.00 | 0.00 | 2016175.80 | 0.00 | 66646231.91 | 0.161065E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.136995E+11 | 0.338504E+10 | 0.00 | 71285399.24 | 0.480400E+09 | 0.158953E+09 | 0.229713E+11 | 0.00 | 1.11 |
Minimum of Months | 75663309.17 | 0.00 | 0.00 | 1608711.64 | 0.00 | 0.00 | 86043048.53 | 0.00 | 0.63 |
Maximum of Months | 0.264301E+10 | 0.162532E+10 | 0.00 | 10731669.83 | 0.277462E+09 | 66646231.91 | 0.379997E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173969E+10 | 0.00 | 0.00 | 13329663.11 | 0.00 | 49004810.71 | 0.848386E+10 | 0.00 | 1.11 |
February | 0.146413E+10 | 0.00 | 0.00 | 13411260.28 | 0.00 | 40159182.71 | 0.706593E+10 | 0.00 | 1.26 |
March | 0.148443E+10 | 0.00 | 0.00 | 13848814.07 | 0.00 | 3606306.97 | 0.695552E+10 | 0.00 | 1.46 |
April | 0.118066E+10 | 80985645.05 | 0.00 | 11706230.41 | 13483385.12 | 0.00 | 0.340420E+10 | 0.00 | 1.21 |
May | 0.506518E+09 | 0.231472E+09 | 0.00 | 8385118.23 | 27318721.95 | 0.00 | 0.132995E+10 | 0.00 | 0.79 |
June | 0.259917E+09 | 0.772058E+09 | 0.00 | 5998602.75 | 41250954.60 | 0.00 | 0.592588E+09 | 0.00 | 0.72 |
July | 86593716.00 | 0.199677E+10 | 0.00 | 1669276.43 | 0.317219E+09 | 0.00 | 82748043.93 | 0.00 | 0.75 |
August | 0.373426E+09 | 0.791234E+09 | 0.00 | 7995764.91 | 0.111434E+09 | 0.00 | 0.897037E+09 | 0.00 | 1.04 |
September | 0.284079E+09 | 0.534955E+09 | 0.00 | 10532926.65 | 29281937.96 | 0.00 | 0.126880E+10 | 0.00 | 0.97 |
October | 0.786366E+09 | 0.159323E+09 | 0.00 | 20059748.67 | 565850.61 | 0.00 | 0.539777E+10 | 0.00 | 1.66 |
November | 0.125521E+10 | 0.00 | 0.00 | 20498521.21 | 0.00 | 10505671.02 | 0.880707E+10 | 0.00 | 1.60 |
December | 0.182089E+10 | 0.00 | 0.00 | 13939074.72 | 0.00 | 36035970.11 | 0.919085E+10 | 0.00 | 1.12 |
Annual Sum or Average | 0.112419E+11 | 0.456680E+10 | 0.00 | 0.141375E+09 | 0.540554E+09 | 0.139312E+09 | 0.534763E+11 | 0.00 | 1.14 |
Minimum of Months | 86593716.00 | 0.00 | 0.00 | 1669276.43 | 0.00 | 0.00 | 82748043.93 | 0.00 | 0.72 |
Maximum of Months | 0.182089E+10 | 0.199677E+10 | 0.00 | 20498521.21 | 0.317219E+09 | 49004810.71 | 0.919085E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298187E+10 | 0.00 | 0.00 | 3723016.90 | 0.00 | 0.00 | 0.304814E+10 | 0.00 | 0.98 |
February | 0.173266E+10 | 0.00 | 0.00 | 6705425.18 | 0.00 | 0.00 | 0.398902E+10 | 0.00 | 1.29 |
March | 0.911639E+09 | 0.00 | 0.00 | 14081069.30 | 0.00 | 0.00 | 0.668767E+10 | 0.00 | 2.05 |
April | 0.556192E+09 | 95542672.53 | 0.00 | 18550559.71 | 8470825.29 | 0.00 | 0.511897E+10 | 0.00 | 2.23 |
May | 0.311242E+09 | 0.271386E+09 | 0.00 | 9956511.46 | 17012039.20 | 0.00 | 0.167884E+10 | 0.00 | 1.32 |
June | 0.212533E+09 | 0.958556E+09 | 0.00 | 7864192.34 | 27579626.43 | 0.00 | 0.782629E+09 | 0.00 | 1.29 |
July | 66615344.56 | 0.248183E+10 | 0.00 | 2725911.88 | 0.246440E+09 | 0.00 | 0.134932E+09 | 0.00 | 1.37 |
August | 0.230001E+09 | 0.104652E+10 | 0.00 | 12306984.78 | 19290931.00 | 0.00 | 0.134654E+10 | 0.00 | 1.95 |
September | 0.232033E+09 | 0.383798E+09 | 0.00 | 9333909.04 | 26746984.47 | 0.00 | 0.117126E+10 | 0.00 | 1.24 |
October | 0.395945E+09 | 0.111312E+09 | 0.00 | 13370929.76 | 955160.00 | 0.00 | 0.429110E+10 | 0.00 | 1.87 |
November | 0.957030E+09 | 0.00 | 0.00 | 11592124.45 | 0.00 | 0.00 | 0.598050E+10 | 0.00 | 1.66 |
December | 0.130780E+10 | 0.00 | 0.00 | 8446026.34 | 0.00 | 0.00 | 0.620827E+10 | 0.00 | 1.18 |
Annual Sum or Average | 0.989557E+10 | 0.534895E+10 | 0.00 | 0.118657E+09 | 0.346495E+09 | 0.00 | 0.404379E+11 | 0.00 | 1.54 |
Minimum of Months | 66615344.56 | 0.00 | 0.00 | 2725911.88 | 0.00 | 0.00 | 0.134932E+09 | 0.00 | 0.98 |
Maximum of Months | 0.298187E+10 | 0.248183E+10 | 0.00 | 18550559.71 | 0.246440E+09 | 0.00 | 0.668767E+10 | 0.00 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292716E+11 | 0.00 | 0.00 | 11988.14 | 0.00 | 0.853799E+10 | 0.137226E+09 | 0.00 | 0.39 |
February | 0.261127E+11 | 0.00 | 0.00 | 2528960.81 | 0.00 | 0.503354E+10 | 0.135356E+10 | 0.00 | 0.45 |
March | 0.255984E+11 | 0.00 | 0.00 | 15416426.59 | 0.00 | 0.281711E+10 | 0.665786E+10 | 0.00 | 0.56 |
April | 0.118634E+11 | 0.492217E+09 | 0.00 | 46189725.28 | 62435898.98 | 44884079.77 | 0.108205E+11 | 0.00 | 0.59 |
May | 0.420026E+10 | 0.220487E+10 | 0.00 | 63717614.66 | 0.147440E+09 | 0.00 | 0.954550E+10 | 0.00 | 0.64 |
June | 0.978188E+09 | 0.875558E+10 | 0.00 | 53030236.48 | 0.221427E+09 | 0.00 | 0.567161E+10 | 0.00 | 0.67 |
July | 0.230715E+09 | 0.190073E+11 | 0.00 | 13846262.57 | 0.642622E+09 | 0.00 | 0.741347E+09 | 0.00 | 0.61 |
August | 0.868368E+09 | 0.608541E+10 | 0.00 | 54386121.90 | 0.326921E+09 | 0.00 | 0.631481E+10 | 0.00 | 0.65 |
September | 0.352738E+10 | 0.318929E+10 | 0.00 | 45700716.73 | 0.180776E+09 | 0.00 | 0.511078E+10 | 0.00 | 0.55 |
October | 0.144617E+11 | 0.764305E+09 | 0.00 | 33701893.39 | 51070697.21 | 0.00 | 0.102264E+11 | 0.00 | 0.61 |
November | 0.277357E+11 | 0.00 | 0.00 | 5254305.37 | 0.00 | 0.337442E+10 | 0.277553E+10 | 0.00 | 0.48 |
December | 0.275527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114158E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.172401E+12 | 0.404990E+11 | 0.00 | 0.333784E+09 | 0.163269E+10 | 0.312238E+11 | 0.593551E+11 | 0.00 | 0.55 |
Minimum of Months | 0.230715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.292716E+11 | 0.190073E+11 | 0.00 | 63717614.66 | 0.642622E+09 | 0.114158E+11 | 0.108205E+11 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295944E+11 | 0.00 | 0.00 | 3572824.30 | 0.00 | 0.569467E+10 | 0.388685E+10 | 0.00 | 0.62 |
February | 0.211400E+11 | 0.00 | 0.00 | 16935944.59 | 0.00 | 0.265197E+10 | 0.119405E+11 | 0.00 | 0.77 |
March | 0.182259E+11 | 0.00 | 0.00 | 46210997.99 | 0.00 | 0.154924E+10 | 0.256324E+11 | 0.00 | 1.09 |
April | 0.682027E+10 | 0.496461E+09 | 0.00 | 95756688.31 | 48439552.89 | 43327565.62 | 0.288090E+11 | 0.00 | 1.34 |
May | 0.293885E+10 | 0.205274E+10 | 0.00 | 96196075.73 | 0.141465E+09 | 0.00 | 0.185727E+11 | 0.00 | 1.34 |
June | 0.981202E+09 | 0.733635E+10 | 0.00 | 64555870.06 | 0.207400E+09 | 0.00 | 0.677596E+10 | 0.00 | 1.11 |
July | 0.222487E+09 | 0.177389E+11 | 0.00 | 15866359.70 | 0.649726E+09 | 0.00 | 0.894896E+09 | 0.00 | 0.95 |
August | 0.131651E+10 | 0.620319E+10 | 0.00 | 58347145.44 | 0.327556E+09 | 0.00 | 0.679423E+10 | 0.00 | 1.11 |
September | 0.264930E+10 | 0.374237E+10 | 0.00 | 70300126.03 | 0.139839E+09 | 0.00 | 0.102698E+11 | 0.00 | 1.15 |
October | 0.123800E+11 | 0.623471E+09 | 0.00 | 55987435.99 | 49515238.14 | 0.00 | 0.196371E+11 | 0.00 | 1.16 |
November | 0.235430E+11 | 0.00 | 0.00 | 22075014.71 | 0.00 | 0.180643E+10 | 0.125661E+11 | 0.00 | 0.85 |
December | 0.303664E+11 | 0.00 | 0.00 | 1688635.59 | 0.00 | 0.771585E+10 | 0.188380E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.150178E+12 | 0.381935E+11 | 0.00 | 0.547493E+09 | 0.156394E+10 | 0.194615E+11 | 0.147663E+12 | 0.00 | 1.01 |
Minimum of Months | 0.222487E+09 | 0.00 | 0.00 | 1688635.59 | 0.00 | 0.00 | 0.894896E+09 | 0.00 | 0.59 |
Maximum of Months | 0.303664E+11 | 0.177389E+11 | 0.00 | 96196075.73 | 0.649726E+09 | 0.771585E+10 | 0.288090E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147604E+11 | 0.00 | 0.00 | 0.120983E+09 | 0.00 | 0.393938E+10 | 0.740917E+11 | 0.00 | 1.03 |
February | 0.141843E+11 | 0.00 | 0.00 | 0.124522E+09 | 0.00 | 0.197639E+10 | 0.592549E+11 | 0.00 | 1.15 |
March | 0.157003E+11 | 0.00 | 0.00 | 0.111414E+09 | 0.00 | 0.859024E+09 | 0.531612E+11 | 0.00 | 1.24 |
April | 0.100722E+11 | 0.100771E+10 | 0.00 | 88105476.48 | 52040242.89 | 34588671.38 | 0.231668E+11 | 0.00 | 0.92 |
May | 0.500113E+10 | 0.262503E+10 | 0.00 | 68106385.49 | 0.162953E+09 | 0.00 | 0.100910E+11 | 0.00 | 0.71 |
June | 0.125653E+10 | 0.871778E+10 | 0.00 | 48710374.35 | 0.256622E+09 | 0.00 | 0.496113E+10 | 0.00 | 0.64 |
July | 0.257585E+09 | 0.190468E+11 | 0.00 | 13301674.92 | 0.754321E+09 | 0.00 | 0.648233E+09 | 0.00 | 0.60 |
August | 0.815563E+09 | 0.764820E+10 | 0.00 | 65777444.25 | 0.360528E+09 | 0.00 | 0.738523E+10 | 0.00 | 0.78 |
September | 0.243209E+10 | 0.583537E+10 | 0.00 | 91596278.76 | 0.180440E+09 | 0.00 | 0.103990E+11 | 0.00 | 0.90 |
October | 0.905370E+10 | 0.172819E+10 | 0.00 | 0.177899E+09 | 10029632.24 | 0.00 | 0.440717E+11 | 0.00 | 1.49 |
November | 0.131819E+11 | 0.00 | 0.00 | 0.182704E+09 | 0.00 | 0.749146E+09 | 0.725316E+11 | 0.00 | 1.44 |
December | 0.158965E+11 | 0.00 | 0.00 | 0.112417E+09 | 0.00 | 0.444451E+10 | 0.732600E+11 | 0.00 | 0.97 |
Annual Sum or Average | 0.102612E+12 | 0.466091E+11 | 0.00 | 0.120554E+10 | 0.177693E+10 | 0.120030E+11 | 0.433023E+12 | 0.00 | 0.99 |
Minimum of Months | 0.257585E+09 | 0.00 | 0.00 | 13301674.92 | 0.00 | 0.00 | 0.648233E+09 | 0.00 | 0.60 |
Maximum of Months | 0.158965E+11 | 0.190468E+11 | 0.00 | 0.182704E+09 | 0.754321E+09 | 0.444451E+10 | 0.740917E+11 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297969E+11 | 0.00 | 0.00 | 13204842.22 | 0.00 | 0.584942E+10 | 0.954500E+10 | 0.00 | 0.73 |
February | 0.263664E+11 | 0.00 | 0.00 | 18946304.49 | 0.00 | 0.330811E+10 | 0.998352E+10 | 0.00 | 0.88 |
March | 0.245320E+11 | 0.00 | 0.00 | 48523048.60 | 0.00 | 0.853297E+09 | 0.214535E+11 | 0.00 | 1.24 |
April | 0.108566E+11 | 0.821578E+09 | 0.00 | 78145274.58 | 20710814.59 | 7387482.51 | 0.184646E+11 | 0.00 | 1.21 |
May | 0.449048E+10 | 0.281220E+10 | 0.00 | 66286689.19 | 66878307.09 | 0.00 | 0.953244E+10 | 0.00 | 1.06 |
June | 0.975290E+09 | 0.972249E+10 | 0.00 | 47485066.56 | 0.132169E+09 | 0.00 | 0.486563E+10 | 0.00 | 0.98 |
July | 0.233304E+09 | 0.183347E+11 | 0.00 | 12347532.53 | 0.537955E+09 | 0.00 | 0.606823E+09 | 0.00 | 0.88 |
August | 0.953726E+09 | 0.659631E+10 | 0.00 | 55774935.32 | 0.228662E+09 | 0.00 | 0.580267E+10 | 0.00 | 1.02 |
September | 0.318058E+10 | 0.347684E+10 | 0.00 | 60627805.31 | 0.160279E+09 | 0.00 | 0.666289E+10 | 0.00 | 0.95 |
October | 0.136701E+11 | 0.942682E+09 | 0.00 | 59276785.65 | 47181364.54 | 0.00 | 0.172143E+11 | 0.00 | 1.26 |
November | 0.272307E+11 | 0.00 | 0.00 | 28814638.81 | 0.00 | 0.134208E+10 | 0.148289E+11 | 0.00 | 1.03 |
December | 0.302507E+11 | 0.00 | 0.00 | 10835284.85 | 0.00 | 0.669988E+10 | 0.874594E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.172537E+12 | 0.427068E+11 | 0.00 | 0.500268E+09 | 0.119384E+10 | 0.180602E+11 | 0.127706E+12 | 0.00 | 0.99 |
Minimum of Months | 0.233304E+09 | 0.00 | 0.00 | 10835284.85 | 0.00 | 0.00 | 0.606823E+09 | 0.00 | 0.68 |
Maximum of Months | 0.302507E+11 | 0.183347E+11 | 0.00 | 78145274.58 | 0.537955E+09 | 0.669988E+10 | 0.214535E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172181E+10 | 0.00 | 0.00 | 0.41 |
February | 0.220796E+10 | 0.00 | 0.00 | 136627.32 | 0.00 | 0.102720E+10 | 80649407.34 | 0.00 | 0.48 |
March | 0.256607E+10 | 0.00 | 0.00 | 1026367.36 | 0.00 | 0.581286E+09 | 0.474141E+09 | 0.00 | 0.59 |
April | 0.125786E+10 | 27838468.51 | 0.00 | 4700893.50 | 6720142.11 | 77883042.36 | 0.904038E+09 | 0.00 | 0.62 |
May | 0.464616E+09 | 0.138868E+09 | 0.00 | 7099497.27 | 17189168.76 | 0.00 | 0.837798E+09 | 0.00 | 0.65 |
June | 0.129396E+09 | 0.691015E+09 | 0.00 | 6407649.05 | 22202716.11 | 0.00 | 0.525942E+09 | 0.00 | 0.66 |
July | 25587955.54 | 0.172411E+10 | 0.00 | 1803299.98 | 83377949.35 | 0.00 | 66246244.37 | 0.00 | 0.60 |
August | 0.151900E+09 | 0.488278E+09 | 0.00 | 6176914.76 | 35186211.42 | 0.00 | 0.582411E+09 | 0.00 | 0.65 |
September | 0.427568E+09 | 0.227527E+09 | 0.00 | 5390580.92 | 26838781.53 | 0.00 | 0.409898E+09 | 0.00 | 0.56 |
October | 0.156517E+10 | 55717717.26 | 0.00 | 2779983.97 | 7244793.87 | 40082180.40 | 0.775309E+09 | 0.00 | 0.63 |
November | 0.244362E+10 | 0.00 | 0.00 | 276696.85 | 0.00 | 0.789641E+09 | 0.157151E+09 | 0.00 | 0.52 |
December | 0.180273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208577E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.151419E+11 | 0.335336E+10 | 0.00 | 35798510.98 | 0.198760E+09 | 0.632367E+10 | 0.481358E+10 | 0.00 | 0.56 |
Minimum of Months | 25587955.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.256607E+10 | 0.172411E+10 | 0.00 | 7099497.27 | 83377949.35 | 0.208577E+10 | 0.904038E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254834E+10 | 0.00 | 0.00 | 63512.84 | 0.00 | 0.854476E+09 | 93946594.86 | 0.00 | 0.59 |
February | 0.211039E+10 | 0.00 | 0.00 | 852031.79 | 0.00 | 0.428412E+09 | 0.612563E+09 | 0.00 | 0.72 |
March | 0.166261E+10 | 0.00 | 0.00 | 3636637.94 | 0.00 | 0.315611E+09 | 0.205519E+10 | 0.00 | 1.03 |
April | 0.586240E+09 | 30242438.25 | 0.00 | 9275214.91 | 3200692.69 | 25502460.22 | 0.257462E+10 | 0.00 | 1.32 |
May | 0.255140E+09 | 0.132240E+09 | 0.00 | 10543150.63 | 15012490.12 | 0.00 | 0.172928E+10 | 0.00 | 1.35 |
June | 0.111783E+09 | 0.585635E+09 | 0.00 | 7643563.68 | 19288504.97 | 0.00 | 0.651961E+09 | 0.00 | 1.09 |
July | 21962775.72 | 0.163893E+10 | 0.00 | 2077151.86 | 84137427.02 | 0.00 | 80173019.06 | 0.00 | 0.94 |
August | 0.138486E+09 | 0.514551E+09 | 0.00 | 7003988.27 | 32467193.03 | 0.00 | 0.667355E+09 | 0.00 | 1.11 |
September | 0.259150E+09 | 0.303075E+09 | 0.00 | 8125487.46 | 16976039.15 | 0.00 | 0.893056E+09 | 0.00 | 1.15 |
October | 0.105525E+10 | 46587231.19 | 0.00 | 5002723.13 | 5692323.83 | 20438761.21 | 0.176028E+10 | 0.00 | 1.13 |
November | 0.209579E+10 | 0.00 | 0.00 | 1405730.66 | 0.00 | 0.425553E+09 | 0.775369E+09 | 0.00 | 0.80 |
December | 0.244896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109476E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.132941E+11 | 0.325126E+10 | 0.00 | 55629193.20 | 0.176775E+09 | 0.316476E+10 | 0.118938E+11 | 0.00 | 0.98 |
Minimum of Months | 21962775.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.254834E+10 | 0.163893E+10 | 0.00 | 10543150.63 | 84137427.02 | 0.109476E+10 | 0.257462E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145602E+10 | 0.00 | 0.00 | 8312000.02 | 0.00 | 0.629122E+09 | 0.576119E+10 | 0.00 | 0.90 |
February | 0.135162E+10 | 0.00 | 0.00 | 9152717.39 | 0.00 | 0.393682E+09 | 0.485959E+10 | 0.00 | 1.03 |
March | 0.151169E+10 | 0.00 | 0.00 | 8931315.65 | 0.00 | 0.378178E+09 | 0.474318E+10 | 0.00 | 1.18 |
April | 0.992321E+09 | 58075266.47 | 0.00 | 9295739.72 | 3733643.43 | 63136476.66 | 0.219199E+10 | 0.00 | 0.94 |
May | 0.534319E+09 | 0.163791E+09 | 0.00 | 7780494.31 | 18294584.79 | 0.00 | 0.931295E+09 | 0.00 | 0.72 |
June | 0.177423E+09 | 0.679287E+09 | 0.00 | 6011100.02 | 27271409.37 | 0.00 | 0.461578E+09 | 0.00 | 0.63 |
July | 29757001.68 | 0.170403E+10 | 0.00 | 1793469.28 | 0.106972E+09 | 0.00 | 61552334.74 | 0.00 | 0.60 |
August | 0.168710E+09 | 0.593635E+09 | 0.00 | 7698777.20 | 37751641.73 | 0.00 | 0.689116E+09 | 0.00 | 0.77 |
September | 0.297625E+09 | 0.406002E+09 | 0.00 | 11142981.75 | 20508007.04 | 0.00 | 0.966875E+09 | 0.00 | 0.90 |
October | 0.904636E+09 | 0.122306E+09 | 0.00 | 16270966.04 | 3521911.31 | 9659739.63 | 0.423793E+10 | 0.00 | 1.50 |
November | 0.129476E+10 | 0.00 | 0.00 | 13798463.00 | 0.00 | 0.361177E+09 | 0.627648E+10 | 0.00 | 1.36 |
December | 0.152704E+10 | 0.00 | 0.00 | 7689853.50 | 0.00 | 0.697992E+09 | 0.539834E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.102459E+11 | 0.372712E+10 | 0.00 | 0.107878E+09 | 0.218053E+09 | 0.253295E+10 | 0.365791E+11 | 0.00 | 0.94 |
Minimum of Months | 29757001.68 | 0.00 | 0.00 | 1793469.28 | 0.00 | 0.00 | 61552334.74 | 0.00 | 0.60 |
Maximum of Months | 0.152704E+10 | 0.170403E+10 | 0.00 | 16270966.04 | 0.106972E+09 | 0.697992E+09 | 0.627648E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236409E+10 | 0.00 | 0.00 | 991130.40 | 0.00 | 0.101096E+10 | 0.807742E+09 | 0.00 | 0.71 |
February | 0.234038E+10 | 0.00 | 0.00 | 1405903.94 | 0.00 | 0.577067E+09 | 0.859293E+09 | 0.00 | 0.87 |
March | 0.230722E+10 | 0.00 | 0.00 | 4084999.24 | 0.00 | 0.382412E+09 | 0.196134E+10 | 0.00 | 1.26 |
April | 0.110457E+10 | 46014608.71 | 0.00 | 8367998.41 | 1926422.50 | 29300207.70 | 0.175541E+10 | 0.00 | 1.25 |
May | 0.514193E+09 | 0.172612E+09 | 0.00 | 7552498.39 | 9692467.53 | 0.00 | 0.841249E+09 | 0.00 | 1.08 |
June | 0.129017E+09 | 0.729165E+09 | 0.00 | 5913678.44 | 15674236.92 | 0.00 | 0.461875E+09 | 0.00 | 0.94 |
July | 25535580.83 | 0.159872E+10 | 0.00 | 1739618.70 | 76073132.42 | 0.00 | 58550344.25 | 0.00 | 0.85 |
August | 0.157715E+09 | 0.504637E+09 | 0.00 | 6519842.20 | 28047666.92 | 0.00 | 0.545669E+09 | 0.00 | 1.01 |
September | 0.368309E+09 | 0.241029E+09 | 0.00 | 7329603.20 | 20900183.40 | 0.00 | 0.589596E+09 | 0.00 | 0.96 |
October | 0.145616E+10 | 68350539.56 | 0.00 | 5464162.21 | 6642433.47 | 296770.23 | 0.151473E+10 | 0.00 | 1.28 |
November | 0.238382E+10 | 0.00 | 0.00 | 2418981.32 | 0.00 | 0.441959E+09 | 0.130490E+10 | 0.00 | 1.03 |
December | 0.229972E+10 | 0.00 | 0.00 | 729897.90 | 0.00 | 0.117207E+10 | 0.681843E+09 | 0.00 | 0.66 |
Annual Sum or Average | 0.154507E+11 | 0.336053E+10 | 0.00 | 52518314.35 | 0.158957E+09 | 0.361406E+10 | 0.113822E+11 | 0.00 | 0.99 |
Minimum of Months | 25535580.83 | 0.00 | 0.00 | 729897.90 | 0.00 | 0.00 | 58550344.25 | 0.00 | 0.66 |
Maximum of Months | 0.238382E+10 | 0.159872E+10 | 0.00 | 8367998.41 | 76073132.42 | 0.117207E+10 | 0.196134E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3740842.50 | 0.00 | 0.00 | 0.447912E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7919630.08 | 0.00 | 0.00 | 0.359648E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14245476.63 | 0.00 | 0.00 | 0.372366E+09 | 0.00 | 0.31 |
April | 0.00 | 777485.07 | 0.00 | 16611354.87 | 0.00 | 0.00 | 0.185040E+09 | 0.00 | 0.29 |
May | 0.00 | 29779676.00 | 0.00 | 2869669.94 | 0.00 | 0.00 | 96069588.43 | 0.00 | 0.29 |
June | 0.00 | 87687665.17 | 0.00 | 1183587.43 | 0.00 | 0.00 | 11877321.35 | 0.00 | 0.30 |
July | 0.00 | 0.284289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.179561E+09 | 0.00 | 489976.32 | 0.00 | 0.00 | 930187.76 | 0.00 | 0.31 |
September | 0.00 | 0.117062E+09 | 0.00 | 1148165.91 | 0.00 | 0.00 | 26396488.82 | 0.00 | 0.29 |
October | 0.00 | 38814143.92 | 0.00 | 6289355.97 | 0.00 | 0.00 | 0.139773E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12841286.13 | 0.00 | 0.00 | 0.321961E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18226145.88 | 0.00 | 0.00 | 0.456270E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.737972E+09 | 0.00 | 85565491.66 | 0.00 | 0.00 | 0.241825E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.284289E+09 | 0.00 | 18226145.88 | 0.00 | 0.00 | 0.456270E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 25944160.03 | 0.00 | 0.00 | 0.449646E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 67942894.09 | 0.00 | 0.00 | 0.360857E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.129808E+09 | 0.00 | 0.00 | 0.373491E+10 | 0.00 | 0.31 |
April | 0.00 | 8006176.15 | 0.00 | 0.155947E+09 | 0.00 | 0.00 | 0.185706E+10 | 0.00 | 0.29 |
May | 0.00 | 0.293394E+09 | 0.00 | 26374682.42 | 0.00 | 0.00 | 0.962361E+09 | 0.00 | 0.29 |
June | 0.00 | 0.872660E+09 | 0.00 | 11227658.31 | 0.00 | 0.00 | 0.118603E+09 | 0.00 | 0.30 |
July | 0.00 | 0.283526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.181312E+10 | 0.00 | 4445070.47 | 0.00 | 0.00 | 9224498.62 | 0.00 | 0.30 |
September | 0.00 | 0.115135E+10 | 0.00 | 10377343.03 | 0.00 | 0.00 | 0.267329E+09 | 0.00 | 0.29 |
October | 0.00 | 0.383576E+09 | 0.00 | 56928103.21 | 0.00 | 0.00 | 0.140741E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.115224E+09 | 0.00 | 0.00 | 0.323325E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.162922E+09 | 0.00 | 0.00 | 0.457945E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.735737E+10 | 0.00 | 0.767141E+09 | 0.00 | 0.00 | 0.242746E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.283526E+10 | 0.00 | 0.162922E+09 | 0.00 | 0.00 | 0.457945E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 77156577.98 | 0.00 | 0.00 | 1672420.53 | 0.00 | 0.00 | 0.373821E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5993463.62 | 0.00 | 0.00 | 0.361939E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12340375.98 | 0.00 | 0.00 | 0.374229E+09 | 0.00 | 0.31 |
April | 0.00 | 905844.71 | 0.00 | 15299449.91 | 0.00 | 0.00 | 0.185278E+09 | 0.00 | 0.29 |
May | 0.00 | 29447725.92 | 0.00 | 2604773.69 | 0.00 | 0.00 | 96300865.95 | 0.00 | 0.29 |
June | 0.00 | 87463087.83 | 0.00 | 1118669.04 | 0.00 | 0.00 | 11886866.81 | 0.00 | 0.30 |
July | 0.00 | 0.283734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.184161E+09 | 0.00 | 404485.52 | 0.00 | 0.00 | 896082.77 | 0.00 | 0.30 |
September | 0.00 | 0.115413E+09 | 0.00 | 990720.12 | 0.00 | 0.00 | 26862539.73 | 0.00 | 0.29 |
October | 0.00 | 38310120.15 | 0.00 | 5411311.53 | 0.00 | 0.00 | 0.141437E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10768801.42 | 0.00 | 0.00 | 0.324225E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15187937.07 | 0.00 | 0.00 | 0.459162E+09 | 0.00 | 0.28 |
Annual Sum or Average | 77156577.98 | 0.739435E+09 | 0.00 | 71792408.42 | 0.00 | 0.00 | 0.235604E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 77156577.98 | 0.283734E+09 | 0.00 | 15299449.91 | 0.00 | 0.00 | 0.459162E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.538716E+09 | 0.00 | 0.00 | 0.525372E+12 | 0.00 | 13.56 |
February | 0.00 | 0.00 | 0.00 | 0.100030E+10 | 0.00 | 0.00 | 0.732614E+12 | 0.00 | 26.98 |
March | 0.00 | 0.00 | 0.00 | 0.161836E+10 | 0.00 | 0.00 | 0.983365E+12 | 0.00 | 38.46 |
April | 0.00 | 0.00 | 0.00 | 0.297061E+10 | 0.00 | 0.00 | 0.750477E+12 | 0.00 | 46.77 |
May | 0.00 | 0.135954E+10 | 0.00 | 0.464358E+09 | 0.00 | 0.00 | 0.308129E+12 | 0.00 | 26.09 |
June | 0.00 | 0.740598E+10 | 0.00 | 0.700858E+09 | 0.00 | 0.00 | 0.125634E+12 | 0.00 | 22.28 |
July | 0.00 | 0.161796E+12 | 0.00 | 59485597.10 | 0.00 | 0.00 | 0.248421E+10 | 0.00 | 26.12 |
August | 0.00 | 0.465312E+11 | 0.00 | 0.127520E+10 | 0.00 | 0.00 | 0.542344E+11 | 0.00 | 40.62 |
September | 0.00 | 0.795244E+10 | 0.00 | 0.422115E+09 | 0.00 | 0.00 | 0.209902E+12 | 0.00 | 27.51 |
October | 0.00 | 0.436031E+10 | 0.00 | 0.110731E+10 | 0.00 | 0.00 | 0.536995E+12 | 0.00 | 37.30 |
November | 0.00 | 0.00 | 0.00 | 0.168893E+10 | 0.00 | 0.00 | 0.972913E+12 | 0.00 | 36.62 |
December | 0.00 | 0.00 | 0.00 | 0.227056E+10 | 0.00 | 0.00 | 0.129711E+13 | 0.00 | 37.24 |
Annual Sum or Average | 0.00 | 0.229406E+12 | 0.00 | 0.141168E+11 | 0.00 | 0.00 | 0.649923E+13 | 0.00 | 31.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 59485597.10 | 0.00 | 0.00 | 0.248421E+10 | 0.00 | 13.56 |
Maximum of Months | 0.00 | 0.161796E+12 | 0.00 | 0.297061E+10 | 0.00 | 0.00 | 0.129711E+13 | 0.00 | 46.77 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:43:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.371281E+12 | 0.154551E+11 | 0.00 | 0.255695E+13 | 0.151800E+12 |
February | 0.384801E+12 | 0.126966E+11 | 0.00 | 0.247440E+13 | 0.339744E+12 |
March | 0.562094E+12 | 0.139464E+11 | 0.00 | 0.299132E+13 | 0.757955E+12 |
April | 0.589391E+12 | 0.756818E+10 | 0.00 | 0.216056E+13 | 0.204001E+13 |
May | 0.622194E+12 | 0.412620E+10 | 0.00 | 0.129216E+13 | 0.199297E+13 |
June | 0.611861E+12 | -488606634.5 | 0.00 | 0.384991E+12 | 0.310915E+13 |
July | 0.606037E+12 | -0.289144E+10 | 0.00 | -0.537450E+12 | 0.396841E+13 |
August | 0.565293E+12 | -316007969.3 | 0.00 | 0.180017E+12 | 0.395279E+13 |
September | 0.511675E+12 | 0.162952E+10 | 0.00 | 0.743339E+12 | 0.205564E+13 |
October | 0.467984E+12 | 0.659526E+10 | 0.00 | 0.215882E+13 | 0.132072E+13 |
November | 0.374304E+12 | 0.128097E+11 | 0.00 | 0.305043E+13 | 0.602272E+12 |
December | 0.315549E+12 | 0.133275E+11 | 0.00 | 0.331384E+13 | 0.431095E+12 |
Annual Sum or Average | 0.598246E+13 | 0.844586E+11 | 0.00 | 0.207694E+14 | 0.207226E+14 |
Minimum of Months | 0.315549E+12 | -0.289144E+10 | 0.00 | -0.537450E+12 | 0.151800E+12 |
Maximum of Months | 0.622194E+12 | 0.154551E+11 | 0.00 | 0.331384E+13 | 0.396841E+13 |