Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:49
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:49:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26778.20 | 578.11 | 578.11 |
Net Site Energy | 26778.20 | 578.11 | 578.11 |
Total Source Energy | 80703.86 | 1742.30 | 1742.30 |
Net Source Energy | 80703.86 | 1742.30 | 1742.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 769.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1909.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2272.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 186.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 272.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.53 |
Humidification | 1127.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.60 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 794.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 24808.59 | 1969.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3578.29 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 769.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2272.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 186.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 272.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.53 |
Humidification | General | 1127.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.60 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 794.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 769.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1909.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2272.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 186.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 272.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.53 |
Humidification | Unassigned | 1127.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.60 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 794.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 99.94 | 42.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 358.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 535.59 | 42.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 99.94 | 42.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 358.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 535.59 | 42.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 24808.587 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24808.587 | 100.00 |
Total On-Site and Utility Electric Sources | 24808.587 | 100.00 |
Total Electricity End Uses | 24808.587 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3578.29 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3578.29 | 100.00 |
Total Water End Uses | 3578.29 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 15.33 |
Time Setpoint Not Met During Occupied Cooling | 124.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5938.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-AUG-15:39 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:10 |
Heating | 0.00 | 756869.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 323763.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82865.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 229929.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36555.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55701.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31442.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1787637.09 | 788311.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 756869.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 323763.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 229929.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 36555.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 55701.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 31442.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1273.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2437.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10250.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1130.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6047.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7195.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 591.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 864.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3572.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 861.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 78568.79 | 2135.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 77.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1696.20 | 46.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 18.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 77.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1696.20 | 46.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.59 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.511881 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.92 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.498186 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.56 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.84 | 0.325883 | 0.329000 | 1.92 | 0.869022 | 0.500000 | 0.001169 | 0.000167 | 1.92 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 54.75 | 0.347390 | 0.342000 | 18.73 | 0.926373 | 0.500000 | 0.001097 | 0.003300 | 18.73 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.20 | 0.365452 | 0.371000 | 1.93 | 0.974539 | 0.500000 | 0.001043 | 0.000612 | 2.10 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.845342 | 0.282514 | 0.285000 | 0.240922 | 0.753369 | 0.500000 | 0.001349 | 0.000065 | 0.240922 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.30 | 0.118405 | 0.200000 | 0.259964 | 0.315747 | 0.500000 | 0.003218 | 0.000056 | 0.259964 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.82 | 0.131032 | 0.200000 | 0.364529 | 0.349420 | 0.500000 | 0.002908 | 0.000092 | 0.364529 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.57 | 0.097826 | 0.200000 | 0.314650 | 0.300000 | 0.500000 | 0.003895 | 0.000046 | 0.314650 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.64 | 0.312462 | 0.308000 | 2.35 | 0.833233 | 0.500000 | 0.001219 | 0.001462 | 5.03 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.60 | 0.113140 | 0.200000 | 2.72 | 0.301707 | 0.500000 | 0.003368 | 0.000979 | 3.37 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.89 | 0.126420 | 0.200000 | 3.78 | 0.337119 | 0.500000 | 0.003014 | 0.001472 | 5.07 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.47 | 0.106373 | 0.200000 | 2.89 | 0.300000 | 0.500000 | 0.003582 | 0.000895 | 3.08 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.847971 | 0.281638 | 0.286000 | 0.242520 | 0.751034 | 0.500000 | 0.001353 | 0.000193 | 0.663418 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.34 | 0.114652 | 0.200000 | 0.268474 | 0.305738 | 0.500000 | 0.003323 | 0.000128 | 0.440246 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.97 | 0.121113 | 0.200000 | 0.394386 | 0.322967 | 0.500000 | 0.003146 | 0.000194 | 0.667124 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.51 | 0.102210 | 0.200000 | 0.301154 | 0.300000 | 0.500000 | 0.003728 | 0.000121 | 0.417438 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19129.03 | 0.000167 | 385.63 |
CORE_MID VAV BOX REHEAT COIL | 377221.47 | 0.003300 | 8463.40 |
CORE_TOP VAV BOX REHEAT COIL | 69925.83 | 0.000612 | 1847.12 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7439.43 | 0.000065 | 190.23 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6346.97 | 0.000056 | 149.62 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10519.80 | 0.000092 | 262.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5230.26 | 0.000046 | 112.89 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 167126.52 | 0.001462 | 4409.10 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 111903.88 | 0.000979 | 2952.09 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 168256.16 | 0.001472 | 4438.87 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 102276.55 | 0.000895 | 2698.39 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22008.43 | 0.000193 | 580.46 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14603.96 | 0.000128 | 385.16 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22131.13 | 0.000194 | 583.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13848.73 | 0.000121 | 365.26 |
VAV_BOT WITH REHEAT HEATING COIL | 53443.87 | 0.000468 | 881.44 |
VAV_MID WITH REHEAT HEATING COIL | 513020.25 | 0.004488 | 8426.70 |
VAV_TOP WITH REHEAT HEATING COIL | 48504.05 | 0.000424 | 808.00 |
CAV_BAS HEATING COIL | 273861.15 | 0.002396 | 6099.41 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.69 | 3.10 | 11.38 | 3.10 | 9.46 | 9.46 | 0.300000 | 0.327827 | 9.46 |
VAV_MID WITH REHEAT | 54.68 | 30.47 | 109.36 | 30.47 | 86.84 | 86.84 | 0.300000 | 0.350888 | 86.84 |
VAV_TOP WITH REHEAT | 5.44 | 3.14 | 10.87 | 4.29 | 9.63 | 9.63 | 0.300000 | 0.445168 | 9.63 |
CAV_BAS | 5.59 | 5.59 | 5.59 | 5.59 | 5.59 | 5.59 | 1.00 | 1.00 | 5.59 |
AIRLOOP DATACENTER BASEMENT | 21.56 | 21.56 | 21.56 | 21.56 | 21.56 | 21.56 | 1.00 | 0.999998 | 21.56 |
AIRLOOP DATACENTER BOT | 0.511881 | 0.511881 | 0.511881 | 0.511881 | 0.511881 | 0.511881 | 1.00 | 1.00 | 0.511881 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 1.00 | 1.00 | 4.92 |
AIRLOOP DATACENTER TOP | 0.498186 | 0.498186 | 0.498186 | 0.498186 | 0.498186 | 0.498186 | 1.00 | 1.00 | 0.498186 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.46 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.84 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.63 | |
CAV_BAS_OA_CONTROLLER | 5.59 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.56 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.511881 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.92 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.498186 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.64 | 6.67 | 11.02 | 0.008718 | 0.008500 | 162885.53 | 0.004659 | 9.46 |
VAV_MID WITH REHEAT COOLING COIL | 24.70 | 6.67 | 10.92 | 0.008728 | 0.008500 | 1515257.95 | 0.043336 | 86.84 |
VAV_TOP WITH REHEAT COOLING COIL | 24.63 | 6.67 | 11.02 | 0.008714 | 0.008500 | 165676.16 | 0.004738 | 9.63 |
CAV_BAS COOLING COIL | 24.29 | 6.67 | 11.41 | 0.008852 | 0.008500 | 93522.95 | 0.002675 | 5.59 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.46 |
VAV_MID WITH REHEAT FAN | 86.84 |
VAV_TOP WITH REHEAT FAN | 9.63 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004659 | 0.000102 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000468 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.043336 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004488 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004738 | 0.000100 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000424 | |
CAV_BAS_COOLC_CONTROLLER | 0.002675 | 0.000178 |
CAV_BAS_HEATC_CONTROLLER | 0.002396 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.59 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.56 | 426109.37 | 306957.01 | 0.010435 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.511881 | 9856.68 | 7195.21 | 0.000241 |
AIRLOOP DATACENTER MID COOLING COIL | 4.92 | 94706.14 | 69127.32 | 0.002319 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.498186 | 9594.10 | 7003.03 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.56 | 21.56 | 21.56 | 21.56 | 426109.37 | 426109.37 | 17946.39 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.511881 | 0.511881 | 0.511881 | 0.511881 | 9856.68 | 9856.68 | 829.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.92 | 4.92 | 4.92 | 4.92 | 94706.14 | 94706.14 | 8290.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.498186 | 0.498186 | 0.498186 | 0.498186 | 9594.10 | 9594.10 | 829.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.56 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.511881 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.92 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.498186 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.56 | 426109.37 | 0.010435 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.511881 | 9856.68 | 0.000241 |
AIRLOOP DATACENTER MID HEATING COIL | 4.92 | 94706.14 | 0.002319 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.498186 | 9594.10 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17946.39 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 829.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8290.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 829.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000145 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.055408 | 9046.39 | |
HEATSYS1 PUMP | 0.017556 | 5287.20 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.055408 | 6.65 |
HEATSYS1 | 0.017556 | 2.11 |
COOLSYS1_SUPPLY | 0.055408 | 6.65 |
SINGLE WATER PLANT LOOP | 0.013231 | 1.59 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.055408 | 0.055408 | 232574.14 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2006797.46 | 2006797.46 | 0.017556 |
CENTRAL BOILER | 545007.33 | 534198.67 | 0.013231 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.027704 | 3131.56 |
COOLSYS1 CHILLER2 PUMP | 0.027704 | 3131.56 |
PLANT CIRC PUMP | 0.013231 | 3374.59 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.055408 | 0.027922 | 977403.70 | 983352.08 | 0.049854 |
COOLSYS1 CHILLER2 | 0.055408 | 0.027922 | 977403.70 | 983352.08 | 0.049854 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013231 | 139666.47 | 59527.15 | 69833.23 | 7879.72 | 21439.95 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.099708 | 11.96 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.099708 | 24685.42 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.26 | 1168185.31 | 7.65 | 146023.16 |
TOWERWATERSYS COOLTOWER 2 | 38.26 | 1168185.31 | 7.65 | 146023.16 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.050545 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3898E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3921E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2832E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2851E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7314E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7328E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6362E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6370E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4422E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5954E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3276E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4622E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7686E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8783E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6580E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7133E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1739 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5660E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1994 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1111 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1138 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7203E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7658E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6576E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4505E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6395E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3368E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5110E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7754E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9047E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6585E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7149E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3896E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3922E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2829E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2852E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7312E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7329E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6361E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6369E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3745E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8230E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2094E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7320E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5490E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6955E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5073E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5455E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2602E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5545E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9850E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3320E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7803E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8361E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9620E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8561E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2226E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3390E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0081E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0935E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5030E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5364E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5074E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5461E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9049E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9072E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4600E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4619E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1482E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1496E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6363E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6371E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9566E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0887E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5031E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6100E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1835E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2626E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6585E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7150E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8121E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5437E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6999E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9330E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2914E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2759E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7658E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6571E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9544E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0883E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5000E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6051E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1781E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2456E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6580E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7133E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9070E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4599E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4617E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1480E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1493E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6362E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6370E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5553E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6765E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1484E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2364E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0389E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0695E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5075E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5462E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0966E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0724E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4945E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7124E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9229E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4845E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9620E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8561E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6677E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9813E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2982E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6447E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0814E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2120E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5072E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5454E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1746 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1296 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1946 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1487 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1274 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9449E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8359E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8866E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6143E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0933E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.3110E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8385E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0143E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1509E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9853E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9197E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.9302E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9451E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6732E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1125E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2285E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2893E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8359E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8862E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.2974E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4271E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6231E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9810E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0543E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6865E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9853E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9197E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1746 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1298 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1946 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1490 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1276 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9614E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8484E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8930E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6198E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1012E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.3172E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8463E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0263E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1598E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9978E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9261E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.9305E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9497E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6739E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1161E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2352E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2936E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8484E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8925E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3012E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4335E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6272E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9868E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0650E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6942E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9978E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9261E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76817.04316 | 76817.04316 | 5.58996 | 5.58996 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 80212.59556 | 80212.59556 | 5.83658 | 5.83658 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 752672.15518 | 752672.15518 | 54.75241 | 54.75241 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 190683.18425 | 190683.18425 | 8.07984 | 10.77825 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71558.26195 | 71558.26195 | 5.20463 | 5.20463 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48999.37549 | 48999.37549 | 2.10067 | 2.10067 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11511.38019 | 11511.38019 | 0.84534 | 0.84534 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5042.44473 | 5042.44473 | 0.21583 | 0.21583 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17700.36057 | 17700.36057 | 1.29982 | 1.29982 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3760.06998 | 3760.06998 | 0.16112 | 0.16112 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24819.97649 | 24819.97649 | 1.82265 | 1.82265 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6891.43606 | 6891.43606 | 0.29572 | 0.29572 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21423.90636 | 21423.90636 | 1.57325 | 1.57325 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2102.41857 | 2102.41857 | 8.94757E-002 | 8.94757E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 104080.56199 | 104080.56199 | 7.64318 | 7.64318 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 117002.15740 | 117002.15740 | 5.03468 | 5.03468 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 185240.59783 | 185240.59783 | 13.60303 | 13.60303 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 78337.54191 | 78337.54191 | 3.37143 | 3.37143 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 257256.21261 | 257256.21261 | 18.89149 | 18.89149 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 117791.69343 | 117791.69343 | 5.06880 | 5.06880 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 197024.90322 | 197024.90322 | 14.46841 | 14.46841 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 71608.47210 | 71608.47210 | 3.08071 | 3.08071 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11547.21540 | 11547.21540 | 0.84797 | 0.84797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15402.59238 | 15402.59238 | 0.66342 | 0.66342 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18279.86224 | 18279.86224 | 1.34237 | 1.34237 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10220.30188 | 10220.30188 | 0.44025 | 0.44025 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26852.92466 | 26852.92466 | 1.97193 | 1.97193 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15488.36591 | 15488.36591 | 0.66712 | 0.66712 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20505.01796 | 20505.01796 | 1.50577 | 1.50577 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9692.32194 | 9692.32194 | 0.41744 | 0.41744 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8837.55313 | 8837.55313 | 0.51188 | 0.51188 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84900.30300 | 84900.30300 | 4.91754 | 4.91754 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8601.08445 | 8601.08445 | 0.49819 | 0.49819 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372172.91540 | 372172.91540 | 21.55644 | 21.55644 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 133986.79 | 9.45712 | 9.45712 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 37666.77 | 1.83997 | 1.83997 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1232105.04 | 86.84256 | 86.84256 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 519125.01 | 27.33387 | 27.33387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 136422.09 | 9.63433 | 9.63433 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51958.86 | 4.28889 | 4.28889 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 |
7 | CAV_BAS | Cooling | Sensible | 69609.68 | 5.58996 | 5.58996 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63649.34 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365829.43 | 21.55648 | 21.55648 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17946.39 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8627.53 | 0.51188 | 0.51188 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82853.87 | 4.91754 | 4.91754 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8290.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8394.72 | 0.49819 | 0.49819 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.58996 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.83658 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32588 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.92023 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86902 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16913E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67349E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.92023 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19129.03053 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67349E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 385.62624 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.75241 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34739 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.72532 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92637 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09675E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30010E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.72532 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 377221.46562 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30010E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8463.39561 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.20463 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36545 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93092 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97454 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04254E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11742E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.10067 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 69925.83040 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11742E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1847.12434 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84534 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28251 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24092 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75337 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34861E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.50834E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24092 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7439.42903 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.50834E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.23043 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29982 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11841 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25996 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31575 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21777E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.55260E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25996 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6346.96516 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.55260E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.62010 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82265 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13103 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36453 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34942 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90768E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.20318E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36453 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10519.80274 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.20318E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 262.00137 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57325 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.78261E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31465 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.89467E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.57566E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31465 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5230.25675 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.57566E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 112.89365 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.64318 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31246 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35410 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83323 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21935E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46210E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.03468 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 167126.52137 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46210E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4409.10184 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.60303 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11314 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.72061 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30171 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36750E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.78984E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.37143 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 111903.87566 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.78984E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2952.09450 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.89149 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12642 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.77830 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33712 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01377E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47198E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.06880 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 168256.15924 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47198E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4438.86887 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.46841 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10637 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89368 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58173E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.94760E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.08071 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 102276.55421 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.94760E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2698.38666 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84797 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28164 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24252 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75103 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35280E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92539E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66342 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22008.43106 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92539E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 580.45623 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34237 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11465 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26847 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30574 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32311E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27762E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44025 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14603.95724 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27762E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 385.15786 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97193 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12111 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39439 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32297 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14583E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93613E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66712 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22131.12562 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93613E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 583.68921 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50577 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10221 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30115 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72762E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21155E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41744 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13848.73137 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21155E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.25621 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51188 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.91754 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49819 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.55644 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.68882 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.10030 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.37764 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.10030 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.45712 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.45712 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32783 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 54.67926 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.47201 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 109.35852 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.47201 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.84256 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.84256 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35089 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.43634 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13745 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.87267 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.28889 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.63433 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.63433 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.44517 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.58996 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.58996 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.58996 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.58996 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.58996 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.58996 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.55644 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.55644 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.55644 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.55644 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.55648 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.55648 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51188 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51188 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51188 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51188 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51188 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51188 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.91754 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.91754 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.91754 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.91754 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91754 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.91754 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49819 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49819 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49819 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49819 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49819 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49819 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.45712 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.84256 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.63433 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.58996 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.55648 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51188 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.91754 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49819 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.45712 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.64378 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02356 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71815E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 162885.52553 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.65851E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.45712 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53443.86795 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.67550E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 881.43616 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.45712 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.65851E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.02220E-004 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.67550E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.84256 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.70374 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92266 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72775E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1515257.95383 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.33362E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 86.84256 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 513020.25202 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.48812E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8426.70444 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.84256 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.33362E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09883E-005 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48812E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.63433 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.63162 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02354 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71407E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 165676.15737 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.73832E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.63433 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 48504.05025 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.24335E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 808.00200 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.63433 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.73832E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00498E-004 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.24335E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.58996 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.28756 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40640 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85193E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 93522.94607 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.67474E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.58996 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 273861.14886 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39586E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6099.41199 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.58996 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.67474E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.78032E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39586E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.55648 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.55648 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 426109.36923 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 306957.01049 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04354E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.55648 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.55648 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.55648 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.55648 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 426109.36923 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 426109.36923 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17946.39161 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.55648 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.55648 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 426109.36923 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04354E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17946.39161 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.44568E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51188 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51188 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9856.67587 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7195.20694 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41389E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51188 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51188 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51188 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51188 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9856.67587 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9856.67587 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51188 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51188 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9856.67587 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41389E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91754 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.91754 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94706.13644 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 69127.32103 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31935E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.91754 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.91754 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.91754 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.91754 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94706.13644 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94706.13644 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8290.48945 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.91754 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.91754 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94706.13644 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31935E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8290.48945 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49819 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49819 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9594.09688 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7003.03157 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34959E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49819 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49819 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49819 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49819 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9594.09688 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9594.09688 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49819 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49819 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9594.09688 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34959E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.54078E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9046.39293 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.54078E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.64893 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.54078E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.54078E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 232574.13959 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.75563E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.10676 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.75563E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5287.19850 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2006797.45509 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2006797.46000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.75563E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.54078E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.64893 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.77039E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3131.56145 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.77039E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3131.56145 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.54078E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.79224E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 977403.70332 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 983352.08000 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.98539E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.54078E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.79224E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 977403.70332 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 983352.08000 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.98539E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32311E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58773 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32311E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3374.58868 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32311E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59527.15080 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21439.94521 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 545007.32836 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 534198.67000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32311E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.97077E-002 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.96493 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.97077E-002 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24685.42233 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.26192 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1168185.30699 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.65238 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 146023.16337 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.26192 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1168185.30699 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.65238 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 146023.16337 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.05450E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.05450E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18138.18 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 357480.92 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 66271.04 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7045.28 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6013.11 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9963.55 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4957.42 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 158353.79 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 106028.97 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 159423.90 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 96908.87 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20852.06 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13836.56 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20968.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13121.13 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41310.41 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 393253.34 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 38261.98 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 217136.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 210839.10 | 156301.13 | 54537.98 | 0.74 | 36365.17 | 368.84 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1955578.71 | 1443702.27 | 511876.44 | 0.74 | 339268.26 | 3441.05 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 214622.39 | 159165.01 | 55457.37 | 0.74 | 37055.60 | 375.84 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 121387.36 | 90939.91 | 30447.45 | 0.75 | 20382.48 | 206.73 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.65 | 22.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.65 | 22.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3329047927 | 0.2316836071 | Pass | Pass | 0.5146590930 | 0.4669225459 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.9623123229E-003 | 7.0536787646E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9857192202E-003 | 7.0014132584E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.3987731287E-002 | 2.9092465176E-002 | Pass | Pass | 0.5289799191 | 0.5087638469 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8359679360E-002 | 1.5371409431E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.5116332646E-002 | 8.8470390289E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.5849850690E-002 | 0.1133273814 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.3007751680E-002 | 5.6438877083E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3717382940E-002 | 1.9636520861E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.9174169040E-002 | 8.3988222161E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.7098147030E-002 | 0.1150534527 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.8944218704E-002 | 5.5634664025E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2337019356 | 0.2171755448 | Pass | Pass | 15.1036906946 | 31.3368989799 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1676910560 | 0.1773289928 | Pass | Pass | 10.1839432830 | 23.3569269635 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1638110375 | 0.1621379359 | Pass | Pass | 6.7729700420 | 18.8791772922 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.7162029691E-002 | 0.1001473106 | Pass | Pass | 18.9561514752 | 96.3365869381 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8990782061E-003 | 6.4587294728E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4263370049E-003 | 9.1793449984E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7794318953E-002 | 5.8901058469E-002 | Pass | Pass | 0.4988622509 | 0.4798967877 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.9049478871E-006 | 3.6066022922E-006 | Pass | Pass | 4.2459649556E-003 | 4.6775879499E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.6206679749E-006 | 1.2720384271E-005 | Pass | Pass | 0.7805558820 | 6.8829771973 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5605806504E-002 | 2.3785269402E-002 | Pass | Pass | 3.5972705547E-003 | 4.2745232924E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2588157199E-006 | 1.1610694721E-006 | Pass | Pass | 6.3131773580E-005 | 1.0819627766E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5840.10 | 131.23 | 0.00 | 33437.04 | 5015.35 | 44423.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.52 | 0.0000 | Y | 14.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.02 | 0.0000 | Y | 9.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.77 | 0.0000 | Y | 14.19 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.19 | 0.0000 | Y | 9.28 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 145.37 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.97 | 0.0000 | Y | 92.10 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.74 | 0.0000 | Y | 141.73 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.12 | 0.0000 | Y | 92.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 14.53 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.97 | 0.0000 | Y | 9.21 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.74 | 0.0000 | Y | 14.17 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.12 | 0.0000 | Y | 9.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1018.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.50 | 42.50 | 105.87 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.54 | 63.02 | 11.70 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.54 | 47.95 | 239.37 | |
Exterior Lighting Total | 40855.88 | 356.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1931375.39 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2006797.46 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 983352.08 | 5.33 | 1007230.18 | 6.30 | 6.65 | 22.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 983352.08 | 5.33 | 1007230.18 | 6.30 | 6.65 | 22.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 534198.67 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1168185.31 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1168185.31 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 162885.53 | 210839.10 | 156301.13 | 54537.98 | 0.74 | - | 36365.17 | 368.84 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1515257.95 | 1955578.71 | 1443702.27 | 511876.44 | 0.74 | - | 339268.26 | 3441.05 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 165676.16 | 214622.39 | 159165.01 | 55457.37 | 0.74 | - | 37055.60 | 375.84 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 93522.95 | 121387.36 | 90939.91 | 30447.45 | 0.75 | - | 20382.48 | 206.73 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 426109.37 | 306957.01 | 119152.36 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9856.68 | 7195.21 | 2661.47 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94706.14 | 69127.32 | 25578.82 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9594.10 | 7003.03 | 2591.07 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19129.03 | 18138.18 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 377221.47 | 357480.92 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 69925.83 | 66271.04 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7439.43 | 7045.28 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6346.97 | 6013.11 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10519.80 | 9963.55 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5230.26 | 4957.42 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 167126.52 | 158353.79 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 111903.88 | 106028.97 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 168256.16 | 159423.90 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 102276.55 | 96908.87 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22008.43 | 20852.06 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14603.96 | 13836.56 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22131.13 | 20968.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13848.73 | 13121.13 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53443.87 | 41310.41 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 513020.25 | 393253.34 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 48504.05 | 38261.98 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 273861.15 | 217136.06 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 426109.37 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9856.68 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94706.14 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9594.10 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17946.39 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8290.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.46 | 20436.34 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 86.84 | 198324.77 | 2283.73 | 1.00 | 1.07 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.63 | 20819.27 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.59 | 9478.63 | 1695.65 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.56 | 35740.06 | 1657.97 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 573.36 | 1120.11 | 1.00 | 1.60 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.92 | 5508.18 | 1120.11 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 558.02 | 1120.11 | 1.00 | 1.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.055408 | 9046.39 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.017556 | 5287.20 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027704 | 3131.56 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027704 | 3131.56 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013231 | 3374.59 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.099708 | 24685.42 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76817.04 | 76817.04 | 27.64 | 5.590 | 5.590 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 80212.60 | 80212.60 | 32.13 | 5.837 | 5.837 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 752672.16 | 752672.16 | 301.54 | 54.752 | 54.752 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 71558.26 | 71558.26 | 28.67 | 5.205 | 5.205 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.67 | 0.00840 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11511.38 | 11511.38 | 36.73 | 0.845 | 0.845 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00883 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17700.36 | 17700.36 | 87.64 | 1.300 | 1.300 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00864 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24819.98 | 24819.98 | 79.19 | 1.823 | 1.823 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00865 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21423.91 | 21423.91 | 106.07 | 1.573 | 1.573 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 104080.56 | 104080.56 | 332.09 | 7.643 | 7.643 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00885 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 185240.60 | 185240.60 | 917.15 | 13.603 | 13.603 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00863 | 21.65 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 257256.21 | 257256.21 | 820.80 | 18.891 | 18.891 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00864 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 197024.90 | 197024.90 | 975.49 | 14.468 | 14.468 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11547.22 | 11547.22 | 36.84 | 0.848 | 0.848 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00881 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18279.86 | 18279.86 | 90.51 | 1.342 | 1.342 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00863 | 21.65 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26852.92 | 26852.92 | 85.68 | 1.972 | 1.972 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00864 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20505.02 | 20505.02 | 101.52 | 1.506 | 1.506 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8837.55 | 8837.55 | 244.11 | 0.512 | 0.512 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84900.30 | 84900.30 | 2345.13 | 4.918 | 4.918 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 23.08 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8601.08 | 8601.08 | 237.58 | 0.498 | 0.498 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372172.92 | 372172.92 | 474.90 | 21.556 | 21.556 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 24.43 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19.60 | 22.24 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 190683.18 | 190683.18 | 76.39 | 8.080 | 10.778 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 48999.38 | 48999.38 | 19.63 | 2.101 | 2.101 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5042.44 | 5042.44 | 16.09 | 0.216 | 0.216 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3760.07 | 3760.07 | 18.62 | 0.161 | 0.161 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6891.44 | 6891.44 | 21.99 | 0.296 | 0.296 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2102.42 | 2102.42 | 10.41 | 0.089 | 0.089 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00691 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 117002.16 | 117002.16 | 373.32 | 5.035 | 5.035 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 78337.54 | 78337.54 | 387.86 | 3.371 | 3.371 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 117791.69 | 117791.69 | 375.83 | 5.069 | 5.069 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 71608.47 | 71608.47 | 354.54 | 3.081 | 3.081 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15402.59 | 15402.59 | 49.14 | 0.663 | 0.663 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10220.30 | 10220.30 | 50.60 | 0.440 | 0.440 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15488.37 | 15488.37 | 49.42 | 0.667 | 0.667 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9692.32 | 9692.32 | 47.99 | 0.417 | 0.417 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18.00 | 26.79 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.57 | 0.00615 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.81 | 0.00298 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.46 | 9.46 | 1.84 | 1.84 | 9.4571 | 3.1003 | 9.4571 | 0.3278 | 0.3000 |
VAV_MID WITH REHEAT | 86.84 | 86.84 | 27.33 | 27.33 | 86.8426 | 30.4720 | 86.8426 | 0.3509 | 0.3000 |
VAV_TOP WITH REHEAT | 9.63 | 9.63 | 4.29 | 4.29 | 9.6343 | 4.2889 | 9.6343 | 0.4452 | 0.3000 |
CAV_BAS | 5.59 | 5.59 | 1.20 | 1.20 | 5.5900 | 5.5900 | 5.5900 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.56 | 21.56 | 0.34 | 0.34 | 21.5565 | 21.5564 | 21.5565 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5119 | 0.5119 | 0.5119 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 0.16 | 0.16 | 4.9175 | 4.9175 | 4.9175 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4982 | 0.4982 | 0.4982 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19129.031 | 19129.031 | 1.920235 | 0.00016735 | 385.626 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19129.03 | 19129.03 | 1.920235 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19199.56 | 19199.56 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 377221.466 | 377221.466 | 18.725325 | 0.00330010 | 8463.396 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 377221.47 | 377221.47 | 18.725325 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 190683.18 | 0.00 | 378512.46 | 378512.46 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69925.830 | 69925.830 | 2.100666 | 0.00061174 | 1847.124 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69925.83 | 69925.83 | 2.100666 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 48999.38 | 0.00 | 70176.76 | 70176.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7439.429 | 7439.429 | 0.240922 | 0.00006508 | 190.230 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7439.43 | 7439.43 | 0.240922 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00737858 | 47.2431 | 5042.44 | 0.00 | 7462.36 | 7462.36 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6346.965 | 6346.965 | 0.259964 | 0.00005553 | 149.620 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6346.97 | 6346.97 | 0.259964 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00747505 | 47.8533 | 3760.07 | 0.00 | 6367.73 | 6367.73 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10519.803 | 10519.803 | 0.364529 | 0.00009203 | 262.001 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10519.80 | 10519.80 | 0.364529 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00760652 | 48.6843 | 6891.44 | 0.00 | 10552.67 | 10552.67 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5230.257 | 5230.257 | 0.314650 | 0.00004576 | 112.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5230.26 | 5230.26 | 0.314650 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00691445 | 44.3042 | 2102.42 | 0.00 | 5248.52 | 5248.52 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 167126.521 | 167126.521 | 5.034678 | 0.00146210 | 4409.102 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 167126.52 | 167126.52 | 5.034678 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773339 | 49.4864 | 117002.16 | 0.00 | 167685.89 | 167685.89 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 111903.876 | 111903.876 | 3.371432 | 0.00097898 | 2952.095 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 111903.88 | 111903.88 | 3.371432 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00774703 | 49.5725 | 78337.54 | 0.00 | 112277.46 | 112277.46 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 168256.159 | 168256.159 | 5.068795 | 0.00147198 | 4438.869 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 168256.16 | 168256.16 | 5.068795 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773746 | 49.5121 | 117791.69 | 0.00 | 168819.06 | 168819.06 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 102276.554 | 102276.554 | 3.080714 | 0.00089476 | 2698.387 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 102276.55 | 102276.55 | 3.080714 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00768865 | 49.2040 | 71608.47 | 0.00 | 102619.92 | 102619.92 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22008.431 | 22008.431 | 0.663418 | 0.00019254 | 580.456 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22008.43 | 22008.43 | 0.663418 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780504 | 49.9389 | 15402.59 | 0.00 | 22080.90 | 22080.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14603.957 | 14603.957 | 0.440246 | 0.00012776 | 385.158 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14603.96 | 14603.96 | 0.440246 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780610 | 49.9456 | 10220.30 | 0.00 | 14651.96 | 14651.96 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22131.126 | 22131.126 | 0.667124 | 0.00019361 | 583.689 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22131.13 | 22131.13 | 0.667124 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780648 | 49.9479 | 15488.37 | 0.00 | 22203.97 | 22203.97 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13848.731 | 13848.731 | 0.417438 | 0.00012115 | 365.256 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13848.73 | 13848.73 | 0.417438 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00778989 | 49.8433 | 9692.32 | 0.00 | 13894.37 | 13894.37 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 162885.526 | -999.000 | 9.457122 | 0.00465851 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 162885.53 | 156437.63 | 9.457122 | 24.64 | 16.69 | 0.00871815 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 26.8389 | 24.00 | 0.00883239 | 47.0188 | 128680.34 | 0.00 | 164440.64 | 152013.64 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53443.868 | 53443.868 | 2.837137 | 0.00046755 | 881.436 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53443.87 | 53443.87 | 2.837137 | -2.93 | -3.13 | 0.00286601 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 89.4631 | 21.57 | 0.00529070 | 32.8207 | 17796.37 | 0.00 | 49979.92 | 49979.92 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1515257.954 | -999.000 | 86.842560 | 0.04333619 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1515257.95 | 1453014.30 | 86.842560 | 24.70 | 16.72 | 0.00872775 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 29.2275 | 24.00 | 0.00886101 | 47.1691 | 1177347.89 | 0.00 | 1529687.07 | 1407579.76 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 513020.252 | 513020.252 | 26.052768 | 0.00448812 | 8426.704 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 513020.25 | 513020.25 | 26.052768 | -3.65 | -3.68 | 0.00279190 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 97.4252 | 21.00 | 0.00785165 | 50.2322 | 498476.90 | 0.00 | 475761.04 | 475761.04 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 165676.157 | -999.000 | 9.634330 | 0.00473832 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 165676.16 | 159229.99 | 9.634330 | 24.63 | 16.68 | 0.00871407 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 26.3453 | 24.00 | 0.00882393 | 46.9744 | 131153.93 | 0.00 | 167260.62 | 154720.58 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 48504.050 | 48504.050 | 2.890299 | 0.00042433 | 808.002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48504.05 | 48504.05 | 2.890299 | -1.22 | -1.46 | 0.00329012 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 87.8176 | 21.00 | 0.00784971 | 50.2200 | 58592.22 | 0.00 | 46298.77 | 46298.77 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 93522.946 | -999.000 | 5.589957 | 0.00267474 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 93522.95 | 87542.23 | 5.589957 | 24.29 | 16.68 | 0.00885193 | 11.41 | 11.41 | 0.00850000 | 25.22 | 0.00840522 | 16.63 | 21.4699 | 24.00 | 0.00899077 | 47.8504 | 70247.53 | 0.00 | 94412.00 | 86199.18 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 273861.149 | 273861.149 | 5.589957 | 0.00239586 | 6099.412 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 273861.15 | 273861.15 | 5.589957 | -0.92 | -2.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.4699 | 24.48 | 0.00265759 | 13.8825 | 0.00 | 0.00 | 229427.86 | 229427.86 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426109.369 | 306957.010 | 21.556479 | 0.01043539 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 396592.32 | 394261.53 | -999.0 | 28.40 | 17.83 | 0.00854009 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | -999.0000 | 27.00 | 0.00854221 | 38.0734 | 371821.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9856.676 | 7195.207 | 0.511881 | 0.00024139 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 9133.58 | 9028.50 | -999.0 | 27.83 | 17.67 | 0.00857630 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858180 | 38.2449 | 8837.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94706.136 | 69127.321 | 4.917545 | 0.00231935 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 87760.26 | 86710.95 | -999.0 | 27.83 | 17.67 | 0.00857931 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858514 | 38.2597 | 84900.30 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9594.097 | 7003.032 | 0.498186 | 0.00023496 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 8890.41 | 8785.31 | -999.0 | 27.83 | 17.67 | 0.00857841 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858413 | 38.2552 | 8601.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426109.369 | 426109.369 | 21.556479 | 0.01043539 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426109.37 | 426109.37 | 21.556479 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5698 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9856.676 | 9856.676 | 0.511881 | 0.00024139 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9856.68 | 9856.68 | 0.511881 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0539 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94706.136 | 94706.136 | 4.917545 | 0.00231935 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94706.14 | 94706.14 | 4.917545 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1789 | 24.73 | 0.00615224 | 31.4762 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9594.097 | 9594.097 | 0.498186 | 0.00023496 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9594.10 | 9594.10 | 0.498186 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1379 | 23.63 | 0.00298298 | 16.3898 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17946.39 | 17946.39 | 21.556479 | -0.07 | -0.07 | 0.00840829 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5698 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.511881 | -0.13 | -0.13 | 0.00832158 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0539 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8290.49 | 8290.49 | 4.917545 | -0.14 | -0.14 | 0.00604115 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1789 | 24.73 | 0.00615224 | 31.4762 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.498186 | -0.13 | -1.35 | 0.00297277 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1379 | 23.63 | 0.00298298 | 16.3898 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19129.031 | 19129.031 | 1.920235 | 0.00016735 | 385.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.9344 | 0.953212 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 19129.03 | 19129.03 | 1.0000 | 2.28771410 | 1.920235 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.16733203 | 60.00 | 32.22 | 27.78 | 0.000 | 19129.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19199.56 | 19199.56 | 2.28771410 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 377221.466 | 377221.466 | 18.725325 | 0.00330010 | 8463.396 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 18.4263 | 18.797187 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 377221.47 | 377221.47 | 1.0000 | 22.30882809 | 18.725325 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 3.29976130 | 60.00 | 32.22 | 27.78 | 0.000 | 377221.47 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 190683.18 | 0.00 | 378512.46 | 378512.46 | 22.30882809 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.44 | 17.85 | 0.00800000 | 50026.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 69925.830 | 69925.830 | 2.100666 | 0.00061174 | 1847.124 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 3.4157 | 3.484449 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69925.83 | 69925.83 | 1.0000 | 2.50267497 | 2.100666 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.61167926 | 60.00 | 32.22 | 27.78 | 0.000 | 69925.83 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 48999.38 | 0.00 | 70176.76 | 70176.76 | 2.50267497 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61100.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7439.429 | 7439.429 | 0.240922 | 0.00006508 | 190.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.3634 | 0.370712 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7439.43 | 7439.43 | 1.0000 | 0.28702831 | 0.240922 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06507673 | 60.00 | 32.22 | 27.78 | 0.000 | 7439.43 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00737858 | 21.00 | 0.00737858 | 47.2431 | 5042.44 | 0.00 | 7462.36 | 7462.36 | 0.28702831 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.30 | 20.67 | 0.00800000 | 59058.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6346.965 | 6346.965 | 0.259964 | 0.00005553 | 149.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.3100 | 0.316273 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6346.97 | 6346.97 | 1.0000 | 0.30971337 | 0.259964 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05552036 | 60.00 | 32.22 | 27.78 | 0.000 | 6346.97 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00747505 | 21.00 | 0.00747505 | 47.8533 | 3760.07 | 0.00 | 6367.73 | 6367.73 | 0.30971337 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.96 | 19.01 | 0.00800000 | 53619.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10519.803 | 10519.803 | 0.364529 | 0.00009203 | 262.001 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.5139 | 0.524208 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10519.80 | 10519.80 | 1.0000 | 0.43429005 | 0.364529 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09202244 | 60.00 | 32.22 | 27.78 | 0.000 | 10519.80 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00760652 | 21.00 | 0.00760652 | 48.6843 | 6891.44 | 0.00 | 10552.67 | 10552.67 | 0.43429005 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.63 | 20.16 | 0.00800000 | 57358.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5230.257 | 5230.257 | 0.314650 | 0.00004576 | 112.894 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.2555 | 0.260627 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5230.26 | 5230.26 | 1.0000 | 0.37486561 | 0.314650 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04575190 | 60.00 | 32.22 | 27.78 | 0.000 | 5230.26 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00691445 | 21.00 | 0.00691445 | 44.3042 | 2102.42 | 0.00 | 5248.52 | 5248.52 | 0.37486561 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.53 | 16.85 | 0.00800000 | 47060.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 167126.521 | 167126.521 | 5.034678 | 0.00146210 | 4409.102 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 8.1637 | 8.328021 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 167126.52 | 167126.52 | 1.0000 | 5.99817460 | 5.034678 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.46194657 | 60.00 | 32.22 | 27.78 | 0.000 | 167126.52 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773339 | 21.00 | 0.00773339 | 49.4864 | 117002.16 | 0.00 | 167685.89 | 167685.89 | 5.99817460 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 111903.876 | 111903.876 | 3.371432 | 0.00097898 | 2952.095 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 5.4662 | 5.576242 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 111903.88 | 111903.88 | 1.0000 | 4.01662916 | 3.371432 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.97888405 | 60.00 | 32.22 | 27.78 | 0.000 | 111903.88 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00774703 | 21.00 | 0.00774703 | 49.5725 | 78337.54 | 0.00 | 112277.46 | 112277.46 | 4.01662916 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 168256.159 | 168256.159 | 5.068795 | 0.00147198 | 4438.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 8.2189 | 8.384312 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 168256.16 | 168256.16 | 1.0000 | 6.03882096 | 5.068795 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.47182812 | 60.00 | 32.22 | 27.78 | 0.000 | 168256.16 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773746 | 21.00 | 0.00773746 | 49.5121 | 117791.69 | 0.00 | 168819.06 | 168819.06 | 6.03882096 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102276.554 | 102276.554 | 3.080714 | 0.00089476 | 2698.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 4.9960 | 5.096506 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 102276.55 | 102276.55 | 1.0000 | 3.67027703 | 3.080714 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.89466864 | 60.00 | 32.22 | 27.78 | 0.000 | 102276.55 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00768865 | 21.00 | 0.00768865 | 49.2040 | 71608.47 | 0.00 | 102619.92 | 102619.92 | 3.67027703 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22008.431 | 22008.431 | 0.663418 | 0.00019254 | 580.456 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 1.0751 | 1.096694 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22008.43 | 22008.43 | 1.0000 | 0.79037755 | 0.663418 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19251971 | 60.00 | 32.22 | 27.78 | 0.000 | 22008.43 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00780504 | 21.00 | 0.00780504 | 49.9389 | 15402.59 | 0.00 | 22080.90 | 22080.90 | 0.79037755 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14603.957 | 14603.957 | 0.440246 | 0.00012776 | 385.158 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.7134 | 0.727725 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14603.96 | 14603.96 | 1.0000 | 0.52449663 | 0.440246 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12774876 | 60.00 | 32.22 | 27.78 | 0.000 | 14603.96 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00780610 | 21.00 | 0.00780610 | 49.9456 | 10220.30 | 0.00 | 14651.96 | 14651.96 | 0.52449663 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22131.126 | 22131.126 | 0.667124 | 0.00019361 | 583.689 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 1.0811 | 1.102808 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22131.13 | 22131.13 | 1.0000 | 0.79479277 | 0.667124 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19359299 | 60.00 | 32.22 | 27.78 | 0.000 | 22131.13 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00780648 | 21.00 | 0.00780648 | 49.9479 | 15488.37 | 0.00 | 22203.97 | 22203.97 | 0.79479277 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13848.731 | 13848.731 | 0.417438 | 0.00012115 | 365.256 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 0.6765 | 0.690091 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13848.73 | 13848.73 | 1.0000 | 0.49732433 | 0.417438 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12114238 | 60.00 | 32.22 | 27.78 | 0.000 | 13848.73 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778989 | 21.00 | 0.00778989 | 49.8433 | 9692.32 | 0.00 | 13894.37 | 13894.37 | 0.49732433 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 162885.526 | -999.000 | 9.457122 | 0.00465851 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0466 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.457122 | 11.26695090 | 4197.9300 | 999.8980 | 55.40210046 | 15.00 | 6.67 | 8.33 | 1937342.58 | 8.4077 | 8.407678 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | Sensible | 162885.53 | 156437.63 | 1.0000 | 11.26695090 | 9.457122 | 24.64 | 16.69 | 0.00871815 | 46966.0 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 4.65803020 | 6.67 | 15.00 | 8.33 | 20436.338 | 142449.19 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 26.8389 | 24.00 | 0.00883239 | 24.00 | 0.00883239 | 47.0188 | 128680.34 | 0.00 | 164440.64 | 152013.64 | 11.26695090 | 24.64 | 16.80 | 0.00871815 | 46966.0 | 11.43 | 11.30 | 0.00828085 | 32371.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53443.868 | 53443.868 | 2.837137 | 0.00046755 | 881.436 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.457122 | 11.26695090 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 2.6106 | 2.663142 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53443.87 | 53443.87 | 1.0000 | 3.38008527 | 2.837137 | -2.93 | -3.13 | 0.00286601 | 4202.9 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.46750258 | 60.00 | 32.22 | 27.78 | 0.000 | 53443.87 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 89.4631 | 8.65 | 0.00463561 | 21.57 | 0.00529070 | 32.8207 | 17796.37 | 0.00 | 49979.92 | 49979.92 | 3.38008527 | 2.80 | 0.33 | 0.00286601 | 9996.2 | 17.44 | 8.06 | 0.00286601 | 24782.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1515257.954 | -999.000 | 86.842560 | 0.04333619 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0644 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.842560 | 103.46179530 | 4197.9300 | 999.8980 | 55.40210046 | 15.00 | 6.67 | 8.33 | 1937342.58 | 78.2132 | 78.213217 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1515257.95 | 1453014.30 | 1.0000 | 103.46179530 | 86.842560 | 24.70 | 16.72 | 0.00872775 | 47051.7 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 43.33176493 | 6.67 | 15.00 | 8.33 | 198324.769 | 1316933.18 | 26.40 | 0.00840708 | 17.04 | 25.38195000 | 29.2275 | 24.00 | 0.00886101 | 24.00 | 0.00886101 | 47.1691 | 1177347.89 | 0.00 | 1529687.07 | 1407579.76 | 103.46179530 | 24.70 | 16.83 | 0.00872775 | 47051.7 | 11.38 | 11.26 | 0.00825980 | 32266.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 513020.252 | 513020.252 | 26.052768 | 0.00448812 | 8426.704 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.842560 | 103.46179530 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 25.0598 | 25.564127 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 513020.25 | 513020.25 | 1.0000 | 31.03853859 | 26.052768 | -3.65 | -3.68 | 0.00279190 | 3297.2 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 4.48766713 | 60.00 | 32.22 | 27.78 | 0.000 | 513020.25 | -4.30 | 0.00265759 | -4.30 | 25.38195000 | 97.4252 | 21.00 | 0.00787402 | 21.00 | 0.00785165 | 50.2322 | 498476.90 | 0.00 | 475761.04 | 475761.04 | 31.03853859 | 2.80 | 0.22 | 0.00279190 | 9810.5 | 17.98 | 8.23 | 0.00279190 | 25138.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 165676.157 | -999.000 | 9.634330 | 0.00473832 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0390 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.634330 | 11.47807071 | 4197.9300 | 999.8980 | 55.40210046 | 15.00 | 6.67 | 8.33 | 1937342.58 | 8.5517 | 8.551722 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 165676.16 | 159229.99 | 1.0000 | 11.47807071 | 9.634330 | 24.63 | 16.68 | 0.00871407 | 46943.2 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 4.73783377 | 6.67 | 15.00 | 8.33 | 20819.273 | 144856.88 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 26.3453 | 24.00 | 0.00882393 | 24.00 | 0.00882393 | 46.9744 | 131153.93 | 0.00 | 167260.62 | 154720.58 | 11.47807071 | 24.63 | 16.79 | 0.00871407 | 46943.2 | 11.43 | 11.30 | 0.00828091 | 32371.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 48504.050 | 48504.050 | 2.890299 | 0.00042433 | 808.002 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.634330 | 11.47807071 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 2.3693 | 2.416988 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48504.05 | 48504.05 | 1.0000 | 3.44342121 | 2.890299 | -1.22 | -1.46 | 0.00329012 | 6997.1 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.42429130 | 60.00 | 32.22 | 27.78 | 0.000 | 48504.05 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 87.8176 | 21.00 | 0.00784971 | 21.00 | 0.00784971 | 50.2200 | 58592.22 | 0.00 | 46298.77 | 46298.77 | 3.44342121 | 2.80 | 0.94 | 0.00329012 | 11059.1 | 16.10 | 7.93 | 0.00329012 | 24504.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 93522.946 | -999.000 | 5.589957 | 0.00267474 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2953 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.589957 | 6.65971806 | 4197.9300 | 999.8980 | 55.40210046 | 15.00 | 6.67 | 8.33 | 1937342.58 | 4.8274 | 4.827383 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 93522.95 | 87542.23 | 1.0000 | 6.65971806 | 5.589957 | 24.29 | 16.68 | 0.00885193 | 46942.9 | 11.41 | 11.41 | 0.00850000 | 32899.8 | 2.67447157 | 6.67 | 15.00 | 8.33 | 9478.635 | 84044.31 | 25.22 | 0.00840522 | 16.63 | 1.20015641 | 21.4699 | 24.00 | 0.00899077 | 24.00 | 0.00899077 | 47.8504 | 70247.53 | 0.00 | 94412.00 | 86199.18 | 6.65971806 | 24.29 | 16.79 | 0.00885193 | 46942.9 | 11.61 | 11.47 | 0.00836305 | 32766.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 273861.149 | 273861.149 | 5.589957 | 0.00239586 | 6099.412 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.589957 | 6.65971806 | 4197.9300 | 999.8980 | 17.55454865 | 54.44 | 82.22 | 27.78 | 2047185.05 | 13.3774 | 13.646676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 273861.15 | 273861.15 | 1.0000 | 6.65971806 | 5.589957 | -0.92 | -2.30 | 0.00265759 | 5714.2 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 2.39561240 | 60.00 | 32.22 | 27.78 | 0.000 | 273861.15 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 21.4699 | 0.00 | 0.00265759 | 24.48 | 0.00265759 | 13.8825 | 0.00 | 0.00 | 229427.86 | 229427.86 | 6.65971806 | 12.80 | 5.54 | 0.00265759 | 19571.7 | 46.92 | 19.28 | 0.00265759 | 54021.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 426109.369 | 306957.010 | 21.556479 | 0.01043539 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7156 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 396592.32 | 394261.53 | 0.9307 | -999.0 | -999.0 | 28.40 | 17.83 | 0.00854009 | 50349.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 396592.32 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | -999.0000 | 27.00 | 0.00854221 | 27.00 | 0.00854221 | 38.0734 | 371821.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9856.676 | 7195.207 | 0.511881 | 0.00024139 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7829 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 9133.58 | 9028.50 | 0.9266 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857630 | 49861.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9133.58 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858180 | 27.00 | 0.00858180 | 38.2449 | 8837.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94706.136 | 69127.321 | 4.917545 | 0.00231935 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7885 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 87760.26 | 86710.95 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857931 | 49864.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87760.26 | 23.08 | 0.00840189 | 15.87 | 0.15632344 | -999.0000 | 27.00 | 0.00858514 | 27.00 | 0.00858514 | 38.2597 | 84900.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9594.097 | 7003.032 | 0.498186 | 0.00023496 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7868 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 8890.41 | 8785.31 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857841 | 49863.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8890.41 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858413 | 27.00 | 0.00858413 | 38.2552 | 8601.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 426109.369 | 426109.369 | 21.556479 | 0.01043539 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 426109.37 | 426109.37 | 1.0000 | 25.68178621 | 21.556479 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 426109.37 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5698 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9856.676 | 9856.676 | 0.511881 | 0.00024139 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9856.68 | 9856.68 | 1.0000 | 0.60984105 | 0.511881 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9856.68 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0539 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94706.136 | 94706.136 | 4.917545 | 0.00231935 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94706.14 | 94706.14 | 1.0000 | 5.85862529 | 4.917545 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94706.14 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.1789 | 0.00 | 0.00615224 | 24.73 | 0.00615224 | 31.4762 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9594.097 | 9594.097 | 0.498186 | 0.00023496 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9594.10 | 9594.10 | 1.0000 | 0.59352479 | 0.498186 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9594.10 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1379 | 0.00 | 0.00298298 | 23.63 | 0.00298298 | 16.3898 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.556479 | 25.68178621 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17946.39 | 17946.39 | 1.0000 | 25.68178621 | 21.556479 | -0.07 | -0.07 | 0.00840829 | 20959.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17946.39 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5698 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.511881 | 0.60984105 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.60984105 | 0.511881 | -0.13 | -0.13 | 0.00832158 | 20677.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0539 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.917545 | 5.85862529 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8290.49 | 8290.49 | 1.0000 | 5.85862529 | 4.917545 | -0.14 | -0.14 | 0.00604115 | 14969.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8290.49 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.1789 | 0.00 | 0.00615224 | 24.73 | 0.00615224 | 31.4762 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.498186 | 0.59352479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.59352479 | 0.498186 | -0.13 | -1.35 | 0.00297277 | 7298.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1379 | 0.00 | 0.00298298 | 23.63 | 0.00298298 | 16.3898 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.46 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 86.84 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.63 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.59 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 21.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2474.50 | 193.83 | 0.00 |
CORE_BOTTOM | 2405.50 | 469.83 | 12.50 |
CORE_MID | 1031.00 | 2799.83 | 12.00 |
CORE_TOP | 1172.00 | 4200.67 | 401.83 |
PERIMETER_BOT_ZN_3 | 1202.00 | 3365.33 | 17.50 |
PERIMETER_BOT_ZN_2 | 1599.83 | 3580.83 | 109.33 |
PERIMETER_BOT_ZN_1 | 1908.83 | 3239.50 | 147.83 |
PERIMETER_BOT_ZN_4 | 2612.00 | 2031.50 | 110.67 |
PERIMETER_MID_ZN_3 | 1438.50 | 4597.50 | 854.67 |
PERIMETER_MID_ZN_2 | 1680.00 | 3637.33 | 780.00 |
PERIMETER_MID_ZN_1 | 1958.00 | 3832.33 | 536.67 |
PERIMETER_MID_ZN_4 | 1756.83 | 4274.67 | 636.00 |
PERIMETER_TOP_ZN_3 | 2300.83 | 4889.67 | 1774.17 |
PERIMETER_TOP_ZN_2 | 2764.17 | 4296.83 | 1622.83 |
PERIMETER_TOP_ZN_1 | 2531.17 | 4199.17 | 1302.00 |
PERIMETER_TOP_ZN_4 | 2356.50 | 4566.50 | 1370.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 747.00 | 747.00 |
DATACENTER_MID_ZN_6 | 5916.50 | 112.83 | 112.83 |
DATACENTER_TOP_ZN_6 | 5508.83 | 282.50 | 187.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5796.83 | 5796.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5938.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 32.33 | 0.00 | 4.17 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 19.83 | 0.00 | 19.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 27.67 | 0.00 | 27.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 45.00 | 0.00 | 23.33 |
PERIMETER_MID_ZN_3 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 3.17 | 18.33 | 0.00 | 18.33 |
PERIMETER_MID_ZN_1 | 1.33 | 24.17 | 0.00 | 23.83 |
PERIMETER_MID_ZN_4 | 1.50 | 22.67 | 0.00 | 12.17 |
PERIMETER_TOP_ZN_3 | 59.17 | 0.00 | 15.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 27.83 | 14.33 | 0.33 | 14.33 |
PERIMETER_TOP_ZN_1 | 19.83 | 18.83 | 0.00 | 18.67 |
PERIMETER_TOP_ZN_4 | 15.83 | 21.33 | 0.00 | 11.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 2.00 | 0.00 | 2.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 61.00 | 185.67 | 15.33 | 124.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 1.340 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 1.021 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.757 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.694 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.898 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.492 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 1.589 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 2.071 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.703 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.305 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 1.515 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.515 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.684 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.359 | 0.075 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 1.455 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.502 | 0.075 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 25.291 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.19 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.25 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1014.08 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 54309693.34 | 0.00 | 54309693.34 | 0.00 | 54309693.34 | 37848132.68 | 4002.66 | 115.61 | 4641.72 | 245.86 |
CORE_BOTTOM | 42242787.22 | 0.00 | 42242787.22 | 0.00 | 42242787.22 | 33990283.35 | 4276.08 | 72.25 | 4411.67 | 267.57 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 5484.53 | 75.09 | 3200.38 | 116.37 |
CORE_TOP | 28258621.76 | 0.00 | 28258621.76 | 0.00 | 28258621.76 | 33990283.35 | 6083.12 | 59.83 | 2617.05 | 218.01 |
PERIMETER_BOT_ZN_3 | 4672479.76 | 0.00 | 4672479.76 | 255127.48 | 4927607.24 | 4267819.30 | 5227.41 | 94.88 | 3437.71 | 267.57 |
PERIMETER_BOT_ZN_2 | 5008478.58 | 0.00 | 5008478.58 | 170084.87 | 5178563.45 | 2750345.05 | 3611.80 | 0.88 | 5147.33 | 267.57 |
PERIMETER_BOT_ZN_1 | 8227541.24 | 0.00 | 8227541.24 | 255127.48 | 8482668.72 | 4267912.63 | 3621.04 | 3.33 | 5135.62 | 267.57 |
PERIMETER_BOT_ZN_4 | 6950649.77 | 0.00 | 6950649.77 | 170084.87 | 7120734.64 | 2750345.05 | 3606.79 | 0.00 | 5153.21 | 267.57 |
PERIMETER_MID_ZN_3 | 35986046.58 | 0.00 | 35986046.58 | 598343.38 | 36584389.95 | 42678193.03 | 5817.00 | 88.77 | 2854.23 | 116.37 |
PERIMETER_MID_ZN_2 | 47206545.34 | 0.00 | 47206545.34 | 398895.31 | 47605440.65 | 27503450.52 | 3854.23 | 2.29 | 4903.48 | 1025.37 |
PERIMETER_MID_ZN_1 | 77154981.62 | 0.00 | 77154981.62 | 598343.38 | 77753324.99 | 42679126.28 | 3881.81 | 6.42 | 4871.77 | 116.37 |
PERIMETER_MID_ZN_4 | 50090905.36 | 0.00 | 50090905.36 | 398895.31 | 50489800.67 | 27503450.52 | 3843.93 | 5.18 | 4910.89 | 116.37 |
PERIMETER_TOP_ZN_3 | 3506068.36 | 0.00 | 3506068.36 | 742904.54 | 4248972.89 | 4267819.30 | 6019.60 | 66.57 | 2673.83 | 218.01 |
PERIMETER_TOP_ZN_2 | 4474175.59 | 0.00 | 4474175.59 | 495269.35 | 4969444.95 | 2750345.05 | 4000.71 | 4.76 | 4754.53 | 218.01 |
PERIMETER_TOP_ZN_1 | 7417610.35 | 0.00 | 7417610.35 | 742904.54 | 8160514.89 | 4267912.63 | 4023.43 | 7.30 | 4729.27 | 218.01 |
PERIMETER_TOP_ZN_4 | 4967573.42 | 0.00 | 4967573.42 | 495269.35 | 5462842.78 | 2750345.05 | 3975.56 | 6.53 | 4777.91 | 218.01 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.39E+09 | 0.00 | 0.39E+09 | 0.00 | 0.39E+09 | 10671554.30 | 2.50 | 7.17 | 8750.33 | 2815.50 |
Total Facility | 0.58E+10 | 0.00 | 0.58E+10 | 23271546.24 | 0.58E+10 | 0.50E+10 | 6365.17 | 4407.25 | 8757.50 | 3724.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4733 | 0.0000 | 2.4733 | 0.0000 | 2.4733 | 1.2002 | 1307.63 | 113.04 | 4522.34 |
CORE_BOTTOM | 1.9040 | 0.0000 | 1.9040 | 0.0000 | 1.9040 | 1.0778 | 1660.33 | 69.53 | 4213.14 |
CORE_MID | 14.1184 | 0.0000 | 14.1184 | 0.0000 | 14.1184 | 10.7782 | 2739.00 | 74.92 | 3129.08 |
CORE_TOP | 1.2975 | 0.0000 | 1.2975 | 0.0000 | 1.2975 | 1.0778 | 3309.09 | 59.83 | 2574.08 |
PERIMETER_BOT_ZN_3 | 0.2106 | 0.0000 | 0.2106 | 0.0059 | 0.2165 | 0.1353 | 2606.29 | 91.66 | 3245.04 |
PERIMETER_BOT_ZN_2 | 0.2256 | 0.0000 | 0.2256 | 0.0039 | 0.2296 | 0.0872 | 1062.37 | 0.88 | 4879.76 |
PERIMETER_BOT_ZN_1 | 0.3727 | 0.0000 | 0.3727 | 0.0059 | 0.3786 | 0.1353 | 1069.80 | 2.79 | 4870.41 |
PERIMETER_BOT_ZN_4 | 0.3128 | 0.0000 | 0.3128 | 0.0039 | 0.3167 | 0.0872 | 1057.36 | 0.00 | 4885.64 |
PERIMETER_MID_ZN_3 | 1.6507 | 0.0000 | 1.6507 | 0.0138 | 1.6646 | 1.3533 | 3072.56 | 88.53 | 2781.91 |
PERIMETER_MID_ZN_2 | 1.9757 | 0.0000 | 1.9757 | 0.0098 | 1.9855 | 0.8721 | 1140.09 | 1.58 | 3892.33 |
PERIMETER_MID_ZN_1 | 3.5563 | 0.0000 | 3.5563 | 0.0138 | 3.5702 | 1.3533 | 1158.48 | 4.93 | 4779.60 |
PERIMETER_MID_ZN_4 | 2.2936 | 0.0000 | 2.2936 | 0.0092 | 2.3028 | 0.8721 | 1133.43 | 3.28 | 4806.28 |
PERIMETER_TOP_ZN_3 | 0.1607 | 0.0000 | 0.1607 | 0.0172 | 0.1779 | 0.1353 | 3248.19 | 66.18 | 2628.62 |
PERIMETER_TOP_ZN_2 | 0.2058 | 0.0000 | 0.2058 | 0.0115 | 0.2172 | 0.0872 | 1262.25 | 2.17 | 4678.58 |
PERIMETER_TOP_ZN_1 | 0.3418 | 0.0000 | 0.3418 | 0.0172 | 0.3590 | 0.1353 | 1276.33 | 4.44 | 4662.23 |
PERIMETER_TOP_ZN_4 | 0.2276 | 0.0000 | 0.2276 | 0.0115 | 0.2390 | 0.0872 | 1241.83 | 4.67 | 4696.50 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.0319 | 0.0000 | 13.0319 | 0.0000 | 13.0319 | 0.3384 | 1.00 | 7.17 | 5934.83 |
Total Facility | 257.8764 | 0.0000 | 257.8764 | 0.5438 | 258.4202 | 158.4706 | 3548.17 | 4389.34 | 5942.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 95242296.94 | 0.00 | 95242296.94 | 48026705.38 | 3613.00 | 2.13 | 5144.86 | 267.57 |
VAV_MID WITH REHEAT | 0.74E+09 | 0.00 | 0.74E+09 | 0.48E+09 | 3875.65 | 6.51 | 4877.83 | 116.37 |
VAV_TOP WITH REHEAT | 69015383.98 | 0.00 | 69015383.98 | 48026705.38 | 4025.43 | 7.84 | 4726.73 | 218.01 |
CAV_BAS | 77085401.11 | 0.00 | 77085401.11 | 37848132.68 | 3942.43 | 2.37 | 4815.20 | 245.86 |
AIRLOOP DATACENTER BASEMENT | 0.56E+09 | 0.00 | 0.56E+09 | 10671554.30 | 2.50 | 0.00 | 8757.50 | 2815.50 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.2945 | 0.0000 | 4.2945 | 1.5229 | 1063.57 | 1.96 | 4877.47 |
VAV_MID WITH REHEAT | 33.7660 | 0.0000 | 33.7660 | 15.2292 | 1154.17 | 4.62 | 4784.21 |
VAV_TOP WITH REHEAT | 3.1700 | 0.0000 | 3.1700 | 1.5229 | 1276.49 | 4.38 | 4662.13 |
CAV_BAS | 3.5105 | 0.0000 | 3.5105 | 1.2002 | 1294.82 | 0.27 | 4647.91 |
AIRLOOP DATACENTER BASEMENT | 18.4971 | 0.0000 | 18.4971 | 0.3384 | 1.00 | 0.00 | 5942.00 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4541.48 | 0.00 | 0.00 | 0.00 | 611.72 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3831.71 | 0.00 | 0.00 | 0.00 | 1103.93 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3271.65 | 0.00 | 0.00 | 0.00 | 1751.78 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 110.97 | 4798.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 7.17 | 8750.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.6253 | 0.0000 | 0.0000 | 0.0000 | 2.4314 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 46.9616 | 0.0000 | 0.0000 | 0.0000 | 23.7613 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.8210 | 0.0000 | 0.0000 | 0.0000 | 2.3534 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7185 | 4.5417 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4917 | 18.5246 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1492 |
Defaulted Fields | 1182 |
Fields with Defaults | 3868 |
Autosized Fields | 332 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
Electricity:Building | 17912.96 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17912.96 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-08:10 |
InteriorLights:Electricity | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.94 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.66 | 397.62 | 16-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.23 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.23 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.56 | 617.01 | 02-APR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.19 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.19 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.72 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.28 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.28 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 509.02 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.37 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.37 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 326.45 | 3976.17 | 02-APR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.10 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.10 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 505.39 | 6170.07 | 02-APR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.73 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.73 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 326.95 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.60 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.60 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.90 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.53 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.53 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.64 | 397.62 | 02-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.21 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.21 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.54 | 617.01 | 02-APR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.17 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.17 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.69 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.26 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.26 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 650.29 | 3594.20 | 02-JAN-04:50 | 316473.81 | 13-JUN-16:00 |
HeatRejection:Electricity | 272.83 | 147.55 | 10-JAN-08:00 | 78014.96 | 22-MAY-14:10 |
General:HeatRejection:Electricity | 272.83 | 147.55 | 10-JAN-08:00 | 78014.96 | 22-MAY-14:10 |
Electricity:HVAC | 4033.78 | 46779.69 | 29-JAN-01:30 | 391479.42 | 14-AUG-16:50 |
ExteriorEquipment:Electricity | 1909.63 | 28161.90 | 01-JAN-00:10 | 116932.81 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.02 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-08:20 |
ElectricityPurchased:Facility | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
ElectricityPurchased:Plant | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
Cogeneration:ElectricityPurchased | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
ElectricityNet:Plant | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
Cogeneration:ElectricityNet | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
General:Cogeneration:ElectricityNet | 24808.59 | 309375.00 | 29-JAN-01:30 | 1787637.09 | 14-AUG-15:40 |
Fans:Electricity | 2272.15 | 42379.63 | 02-JAN-23:10 | 239749.81 | 28-APR-14:50 |
General:Fans:Electricity | 2272.15 | 42379.63 | 02-JAN-23:10 | 239749.81 | 28-APR-14:50 |
ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 769.50 | 1677.68 | 02-JAN-07:10 | 326043.42 | 14-AUG-16:00 |
General:Cooling:Electricity | 769.50 | 1677.68 | 02-JAN-07:10 | 326043.42 | 14-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1127.96 | 0.00 | 17-JAN-11:30 | 100000.00 | 03-MAR-22:10 |
General:Humidifier:Electricity | 1127.96 | 0.00 | 17-JAN-11:30 | 100000.00 | 03-MAR-22:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 186.61 | 3374.59 | 09-JAN-05:40 | 40043.65 | 12-JUN-14:20 |
General:Pumps:Electricity | 186.61 | 3374.59 | 09-JAN-05:40 | 40043.65 | 12-JUN-14:20 |
WIRED_LTG_ELECTRICITY | 90.95 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1969.62 | 7280.88 | 30-APR-13:10 | 788311.68 | 10-JAN-08:00 |
NaturalGas:Plant | 1969.62 | 7280.88 | 30-APR-13:10 | 788311.68 | 10-JAN-08:00 |
Heating:NaturalGas | 1174.66 | 0.00 | 01-JAN-00:40 | 774183.98 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 1174.66 | 0.00 | 01-JAN-00:40 | 774183.98 | 02-JAN-06:10 |
WaterSystems:NaturalGas | 794.96 | 7280.88 | 04-JAN-05:20 | 83767.11 | 09-FEB-12:50 |
Water Heater:WaterSystems:NaturalGas | 794.96 | 7280.88 | 04-JAN-05:20 | 83767.11 | 09-FEB-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4046.15 | 4567.81 | 02-JAN-07:10 | 1934814.65 | 14-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 4046.15 | 4567.81 | 02-JAN-07:10 | 1934814.65 | 14-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 4046.15 | 4567.81 | 02-JAN-07:10 | 1934814.65 | 14-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3578.29 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:10 |
Water:HVAC | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
Humidifier:Water | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
General:Humidifier:Water | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
MainsWater:Facility | 3578.29 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:10 |
MainsWater:HVAC | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
Humidifier:MainsWater | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
General:Humidifier:MainsWater | 419.60 | 0.00 | 17-JAN-11:30 | 0.00 | 08-MAR-05:10 |
Water:Plant | 3158.69 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3158.69 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 878.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
General:HeatRejection:Water | 878.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
HeatRejection:MainsWater | 878.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
General:HeatRejection:MainsWater | 878.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27224.63 | 96299.67 | 15-JAN-05:00 | 7653869.98 | 13-JUN-16:00 |
EnergyTransfer:Building | 17612.98 | 88221.65 | 15-JAN-03:10 | 1557509.63 | 14-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 660.68 | 0.00 | 01-JAN-00:10 | 70614.07 | 10-OCT-05:10 |
Heating:EnergyTransfer | 206.40 | 0.00 | 06-JAN-22:10 | 455944.47 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 1.88 | 0.00 | 01-JAN-00:10 | 14075.26 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 206.40 | 0.00 | 06-JAN-22:10 | 455944.47 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 1.88 | 0.00 | 01-JAN-00:10 | 14075.26 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 17406.58 | 87582.59 | 15-JAN-06:00 | 1557509.63 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 658.80 | 0.00 | 01-JAN-00:10 | 70614.07 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 17406.58 | 87582.59 | 15-JAN-06:00 | 1557509.63 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 658.80 | 0.00 | 01-JAN-00:10 | 70614.07 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 590.07 | 0.00 | 01-JAN-00:10 | 54053.44 | 28-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 590.07 | 0.00 | 01-JAN-00:10 | 54053.44 | 28-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 590.07 | 0.00 | 01-JAN-00:10 | 54053.44 | 28-AUG-14:00 |
EnergyTransfer:Zone:CORE_MID | 4095.12 | 0.00 | 01-JAN-00:10 | 419114.12 | 25-MAY-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.05 | 0.00 | 01-JAN-00:10 | 80726.26 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.05 | 0.00 | 01-JAN-00:10 | 80726.26 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4095.06 | 0.00 | 01-JAN-00:10 | 419114.12 | 25-MAY-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4095.06 | 0.00 | 01-JAN-00:10 | 419114.12 | 25-MAY-05:10 |
EnergyTransfer:Zone:CORE_TOP | 350.67 | 0.00 | 01-JAN-00:40 | 64592.14 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.51 | 0.00 | 01-JAN-00:10 | 64592.14 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.51 | 0.00 | 01-JAN-00:10 | 64592.14 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 345.15 | 0.00 | 01-JAN-00:40 | 47036.72 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 345.15 | 0.00 | 01-JAN-00:40 | 47036.72 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.91 | 0.00 | 01-JAN-00:10 | 8923.89 | 10-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1078.33 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1078.33 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.90 | 0.00 | 01-JAN-00:10 | 8923.89 | 10-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.90 | 0.00 | 01-JAN-00:10 | 8923.89 | 10-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.97 | 0.00 | 01-JAN-00:10 | 13989.81 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1389.21 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1389.21 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.96 | 0.00 | 01-JAN-00:10 | 13989.81 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.96 | 0.00 | 01-JAN-00:10 | 13989.81 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.37 | 0.00 | 01-JAN-00:10 | 21722.09 | 11-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 3338.11 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 3338.11 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.32 | 0.00 | 01-JAN-00:10 | 21722.09 | 11-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.32 | 0.00 | 01-JAN-00:10 | 21722.09 | 11-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 90.06 | 0.00 | 01-JAN-00:10 | 17866.74 | 28-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 8.27 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 8.27 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 90.06 | 0.00 | 01-JAN-00:10 | 17866.74 | 28-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 90.06 | 0.00 | 01-JAN-00:10 | 17866.74 | 28-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 400.97 | 0.00 | 01-JAN-00:10 | 98101.98 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.12 | 0.00 | 01-JAN-00:10 | 98101.98 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.12 | 0.00 | 01-JAN-00:10 | 98101.98 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 369.85 | 0.00 | 01-JAN-00:10 | 76500.42 | 13-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 369.85 | 0.00 | 01-JAN-00:10 | 76500.42 | 13-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 507.03 | 0.00 | 01-JAN-00:10 | 145690.25 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.29 | 0.00 | 01-JAN-00:10 | 74792.23 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.29 | 0.00 | 01-JAN-00:10 | 74792.23 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 486.73 | 0.00 | 01-JAN-00:10 | 145690.25 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 486.73 | 0.00 | 01-JAN-00:10 | 145690.25 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 891.22 | 0.00 | 01-JAN-00:10 | 234257.28 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.35 | 0.00 | 01-JAN-00:10 | 86971.42 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.35 | 0.00 | 01-JAN-00:10 | 86971.42 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 872.88 | 0.00 | 01-JAN-00:10 | 234257.28 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 872.88 | 0.00 | 01-JAN-00:10 | 234257.28 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 539.51 | 0.00 | 01-JAN-00:10 | 168563.59 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.39 | 0.00 | 01-JAN-00:10 | 57242.84 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.39 | 0.00 | 01-JAN-00:10 | 57242.84 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 528.12 | 0.00 | 01-JAN-00:10 | 168563.59 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 528.12 | 0.00 | 01-JAN-00:10 | 168563.59 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.87 | 0.00 | 01-JAN-00:40 | 11703.45 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.70 | 0.00 | 01-JAN-00:40 | 11703.45 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.70 | 0.00 | 01-JAN-00:40 | 11703.45 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.17 | 0.00 | 01-JAN-00:10 | 8530.25 | 13-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.17 | 0.00 | 01-JAN-00:10 | 8530.25 | 13-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.63 | 0.00 | 01-JAN-00:40 | 14511.36 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.57 | 0.00 | 01-JAN-00:40 | 12411.71 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.57 | 0.00 | 01-JAN-00:40 | 12411.71 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.07 | 0.00 | 01-JAN-00:10 | 14511.36 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.07 | 0.00 | 01-JAN-00:10 | 14511.36 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.83 | 0.00 | 01-JAN-00:40 | 23578.55 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.95 | 0.00 | 01-JAN-00:40 | 17665.61 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.95 | 0.00 | 01-JAN-00:40 | 17665.61 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 75.88 | 0.00 | 01-JAN-00:10 | 23578.55 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 75.88 | 0.00 | 01-JAN-00:10 | 23578.55 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.56 | 0.00 | 01-JAN-00:40 | 17496.83 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.64 | 0.00 | 01-JAN-00:40 | 10308.94 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.64 | 0.00 | 01-JAN-00:40 | 10308.94 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.92 | 0.00 | 01-JAN-00:10 | 17496.83 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.92 | 0.00 | 01-JAN-00:10 | 17496.83 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.75 | 0.00 | 01-JAN-00:10 | 8039.00 | 28-AUG-14:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.99 | 0.00 | 01-JAN-00:10 | 4259.24 | 17-DEC-13:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.99 | 0.00 | 01-JAN-00:10 | 4259.24 | 17-DEC-13:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.76 | 0.00 | 01-JAN-00:10 | 8039.00 | 28-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.76 | 0.00 | 01-JAN-00:10 | 8039.00 | 28-AUG-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 325.57 | 0.00 | 01-JAN-00:10 | 53764.36 | 24-JUL-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 45.97 | 0.00 | 01-JAN-00:10 | 47218.94 | 26-DEC-12:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 45.97 | 0.00 | 01-JAN-00:10 | 47218.94 | 26-DEC-12:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 279.60 | 0.00 | 01-JAN-00:10 | 53764.36 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 279.60 | 0.00 | 01-JAN-00:10 | 53764.36 | 24-JUL-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.82 | 0.00 | 01-JAN-00:40 | 19326.84 | 26-DEC-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.61 | 0.00 | 01-JAN-00:40 | 19326.84 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.61 | 0.00 | 01-JAN-00:40 | 19326.84 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.21 | 0.00 | 01-JAN-00:10 | 17038.62 | 13-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.21 | 0.00 | 01-JAN-00:10 | 17038.62 | 13-JUN-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.94 | 787.78 | 14-JAN-18:30 | 8372.82 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.94 | 787.78 | 14-JAN-18:30 | 8372.82 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.94 | 787.78 | 14-JAN-18:30 | 8372.82 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.34 | 6.53 | 01-JAN-17:00 | 79575.91 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.66 | 0.00 | 01-JAN-15:20 | 5559.28 | 02-JAN-04:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.66 | 0.00 | 01-JAN-15:20 | 5559.28 | 02-JAN-04:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1173.68 | 0.00 | 01-JAN-00:10 | 79575.91 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1173.68 | 0.00 | 01-JAN-00:10 | 79575.91 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.41 | 0.03 | 12-JAN-09:50 | 8064.92 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 02-JAN-13:50 | 595.96 | 08-JAN-18:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 02-JAN-13:50 | 595.96 | 08-JAN-18:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.75 | 0.00 | 01-JAN-00:10 | 8064.92 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.75 | 0.00 | 01-JAN-00:10 | 8064.92 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7168.69 | 86690.85 | 15-JAN-06:00 | 368588.02 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7168.69 | 86690.85 | 15-JAN-06:00 | 368588.02 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7168.69 | 86690.85 | 15-JAN-06:00 | 368588.02 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1304.61 | 0.00 | 01-JAN-00:40 | 650464.75 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 442.36 | 0.00 | 01-JAN-00:10 | 51547.08 | 15-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51547.08 | 15-FEB-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51547.08 | 15-FEB-13:00 |
EnergyTransfer:HVAC | 4329.74 | 2990.69 | 01-JAN-06:00 | 1782366.33 | 14-AUG-15:50 |
HeatingCoils:EnergyTransfer | 862.24 | 0.00 | 01-JAN-00:40 | 633498.93 | 10-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 862.24 | 0.00 | 01-JAN-00:40 | 633498.93 | 10-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 862.24 | 0.00 | 01-JAN-00:40 | 633498.93 | 10-JAN-08:00 |
CoolingCoils:EnergyTransfer | 3467.50 | 2890.13 | 02-JAN-07:10 | 1782366.33 | 14-AUG-15:50 |
EnergyTransfer:Plant | 5281.91 | 0.00 | 01-JAN-00:40 | 4588688.78 | 13-JUN-16:00 |
LoopToLoop:EnergyTransfer | 1257.92 | 0.00 | 01-JAN-00:10 | 1448995.48 | 13-JUN-16:00 |
WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51547.08 | 15-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51547.08 | 15-FEB-13:00 |
Boilers:EnergyTransfer | 857.78 | 0.00 | 01-JAN-00:40 | 638472.03 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 1266.49 | 0.00 | 01-JAN-00:10 | 1450607.29 | 13-JUN-16:00 |
HeatRejection:EnergyTransfer | 1457.34 | 0.00 | 01-JAN-00:10 | 1652355.64 | 13-JUN-16:00 |
General:HeatRejection:EnergyTransfer | 1457.34 | 0.00 | 01-JAN-00:10 | 1652355.64 | 13-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 1.884 | -658.795 | 0.000 | 0.000 | 92.733 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -76.390 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -590.072 | 0.000 | 0.000 | 83.435 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 22.887 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 0.053 | -4095.051 | 0.000 | 0.000 | 844.961 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1587.457 |
CORE_TOP | 0.000 | 0.000 | 5.512 | -345.152 | 0.000 | 0.000 | 88.253 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -232.362 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.004 | -58.904 | 0.000 | 0.000 | 10.765 | 14.573 | 36.365 | 22.453 | 0.000 | 0.002 | 49.298 | 0.000 | -70.270 | 0.000 | -4.284 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.011 | -60.956 | 0.000 | 0.000 | 7.071 | 9.227 | 23.435 | 52.539 | 0.000 | 0.001 | 15.072 | 0.000 | -43.593 | 0.000 | -2.806 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.046 | -101.322 | 0.000 | 0.000 | 10.896 | 14.192 | 36.366 | 106.019 | 0.000 | 0.002 | 4.260 | 0.000 | -66.205 | 0.000 | -4.254 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -90.055 | 0.000 | 0.000 | 6.863 | 9.281 | 23.435 | 50.091 | 0.000 | 0.001 | 54.029 | 0.000 | -50.525 | 0.000 | -3.120 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 31.119 | -369.850 | 0.000 | 0.000 | 113.875 | 145.369 | 363.654 | 237.721 | 0.000 | 0.036 | 191.775 | 0.000 | -624.485 | 0.000 | -89.214 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 20.294 | -486.738 | 0.000 | 0.000 | 54.070 | 92.100 | 234.352 | 529.334 | 0.000 | 0.026 | 18.911 | 0.000 | -401.669 | 0.000 | -60.681 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 18.346 | -872.873 | 0.000 | 0.000 | 111.854 | 141.729 | 363.660 | 1062.187 | 0.000 | 0.037 | 0.055 | 0.000 | -630.661 | 0.000 | -94.187 | -100.093 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 11.393 | -528.118 | 0.000 | 0.000 | 73.932 | 92.600 | 234.351 | 516.597 | 0.000 | 0.021 | 92.966 | 0.000 | -431.009 | 0.000 | -62.733 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 14.697 | -30.170 | 0.000 | 0.000 | 11.672 | 14.534 | 36.365 | 24.799 | 0.000 | 0.004 | 0.001 | 0.000 | -57.617 | 0.000 | -10.281 | -4.004 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.565 | -42.069 | 0.000 | 0.000 | 7.429 | 9.209 | 23.435 | 53.567 | 0.000 | 0.003 | 0.002 | 0.000 | -37.432 | 0.000 | -7.071 | -15.637 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 9.949 | -75.883 | 0.000 | 0.000 | 11.430 | 14.172 | 36.366 | 107.307 | 0.000 | 0.004 | 0.003 | 0.000 | -58.659 | 0.000 | -10.930 | -33.757 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.640 | -46.915 | 0.000 | 0.000 | 7.531 | 9.259 | 23.435 | 52.120 | 0.000 | 0.002 | 0.001 | 0.000 | -40.489 | 0.000 | -7.349 | -3.234 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.939 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.047 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.656 | -1173.681 | 0.000 | 0.000 | 9.502 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -426.833 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.667 | -104.748 | 0.000 | 0.000 | 0.952 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.906 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7168.689 | 0.000 | 0.000 | 20.564 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -409.385 |
GROUNDFLOOR_PLENUM | 0.989 | -52.765 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 60.895 | 0.000 | 0.000 | 0.000 | -9.122 | 0.000 |
MIDFLOOR_PLENUM | 45.967 | -279.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 388.364 | 0.000 | 0.000 | 0.000 | -154.778 | -0.004 |
TOPFLOOR_PLENUM | 30.611 | -36.211 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 21.929 | 0.000 | 0.000 | 0.000 | -16.333 | -0.003 |
Total Facility | 77.567 | -368.575 | 128.835 | -17037.979 | 0.000 | 0.000 | 1568.738 | 3236.569 | 14676.396 | 2814.734 | 0.000 | 0.193 | 920.447 | 0.000 | -2512.616 | 0.000 | -537.144 | -2967.120 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 07-AUG-04:11 | 0.00 | 0.00 | 0.00 | -115201.59 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 101145.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | -93792.66 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 87317.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-AUG-05:02 | 0.00 | 0.00 | 0.00 | -794051.39 | 0.00 | 0.00 | 8374.64 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 703829.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -73889.81 | 0.00 | 0.00 | 848.59 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 64856.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-JUN-05:03 | 0.00 | 0.00 | 0.00 | -9361.99 | 0.00 | 0.00 | 115.01 | 67.47 | 960.25 | 2715.84 | 0.00 | 0.00 | 5541.15 | 0.00 | -0.00 | 0.00 | -37.73 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-AUG-09:42 | 0.00 | 0.00 | 0.00 | -23649.27 | 0.00 | 0.00 | 22.26 | 37.27 | 464.11 | 14482.07 | 0.00 | 0.00 | 8814.78 | 0.00 | -0.00 | 0.00 | -171.22 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:51 | 0.00 | 0.00 | 0.00 | -34789.34 | 0.00 | 0.00 | 32.60 | 57.83 | 720.19 | 27359.89 | 0.00 | 0.00 | 6813.64 | 0.00 | -0.00 | 0.00 | -194.82 | 0.00 |
PERIMETER_BOT_ZN_4 | 20-AUG-16:21 | 0.00 | 0.00 | 0.00 | -29573.34 | 0.00 | 0.00 | 15.47 | 37.27 | 464.11 | 19112.40 | 0.00 | 0.00 | 10005.41 | 0.00 | -0.00 | 0.00 | -61.31 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -76501.52 | 0.00 | 0.00 | 11143.72 | 10409.61 | 21605.52 | 54469.92 | 0.00 | 396.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21523.92 |
PERIMETER_MID_ZN_2 | 16-JUL-09:01 | 0.00 | 0.00 | 0.00 | -259837.96 | 0.00 | 0.00 | 203.20 | 372.66 | 4641.14 | 174347.04 | 0.00 | 0.00 | 83776.16 | 0.00 | -0.00 | 0.00 | -3502.24 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-13:12 | 0.00 | 0.00 | 0.00 | -344490.80 | 0.00 | 0.00 | 348.95 | 578.28 | 7201.95 | 210361.62 | 0.00 | 0.00 | 130646.05 | 0.00 | -0.00 | 0.00 | -4646.06 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -290629.12 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 183018.42 | 0.00 | 0.00 | 104574.46 | 0.00 | -0.00 | 0.00 | -939.89 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-15:10 | 0.00 | 0.00 | 0.00 | -8531.19 | 0.00 | 0.00 | 1114.36 | 1040.96 | 2160.55 | 5280.34 | 0.00 | 46.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1112.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:32 | 0.00 | 0.00 | 0.00 | -24393.14 | 0.00 | 0.00 | 22.27 | 37.27 | 464.11 | 14991.12 | 0.00 | 0.00 | 8983.92 | 0.00 | -0.00 | 0.00 | -105.55 | 0.00 |
PERIMETER_TOP_ZN_1 | 20-AUG-13:52 | 0.00 | 0.00 | 0.00 | -35897.48 | 0.00 | 0.00 | 34.49 | 57.83 | 720.19 | 19119.17 | 0.00 | 0.00 | 16295.53 | 0.00 | -0.00 | 0.00 | -329.73 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-17:21 | 0.00 | 0.00 | 0.00 | -30716.34 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 20292.26 | 0.00 | 0.00 | 10408.63 | 0.00 | -0.00 | 0.00 | -382.16 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 | -8375.49 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 556.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-18:05 | 0.00 | 0.00 | 0.00 | -79575.91 | 0.00 | 0.00 | 0.00 | 250.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 1381.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 30-APR-17:51 | 0.00 | 0.00 | 0.00 | -8064.92 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 245.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | -368591.33 | 0.00 | 0.00 | 2180.39 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18692.14 |
GROUNDFLOOR_PLENUM | 21-AUG-05:13 | 0.00 | -9094.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9139.62 | 0.00 | -0.00 | 0.00 | -44.80 | 0.00 |
MIDFLOOR_PLENUM | 30-DEC-05:01 | 0.00 | -78868.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98521.06 | 0.00 | -0.00 | 0.00 | -19652.48 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:20 | 0.00 | -17038.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17053.08 | 0.00 | -0.00 | 0.00 | -14.40 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | 44521.00 | 0.00 | -1670544.44 | 0.00 | 0.00 | 16273.30 | 10917.52 | 616289.16 | 0.00 | 0.00 | 0.00 | 1104792.19 | 0.00 | -118031.34 | 0.00 | -4217.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 15390.50 | 0.00 | 0.00 | 0.00 | 520.13 | 1077.81 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30445.98 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:02 | 0.00 | 0.00 | 274276.59 | 0.00 | 0.00 | 0.00 | 11443.39 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -367567.20 |
CORE_TOP | 02-JAN-04:11 | 0.00 | 0.00 | 72825.29 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -79300.27 |
PERIMETER_BOT_ZN_3 | 11-JAN-06:01 | 0.00 | 0.00 | 5925.82 | 0.00 | 0.00 | 0.00 | 142.08 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5041.71 | 0.00 | -107.42 | -1946.49 |
PERIMETER_BOT_ZN_2 | 11-JAN-06:02 | 0.00 | 0.00 | 4001.05 | 0.00 | 0.00 | 0.00 | 92.64 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3396.22 | 0.00 | -71.94 | -1287.83 |
PERIMETER_BOT_ZN_1 | 10-JAN-06:02 | 0.00 | 0.00 | 8226.03 | 0.00 | 0.00 | 0.00 | 146.74 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5306.20 | 0.00 | -140.36 | -3953.94 |
PERIMETER_BOT_ZN_4 | 10-JAN-06:05 | 0.00 | 0.00 | 66.17 | 0.00 | 0.00 | 0.00 | 87.59 | 43.48 | 618.81 | 0.00 | 0.00 | 0.00 | 3052.39 | 0.00 | -3773.84 | 0.00 | -94.61 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-05:11 | 0.00 | 0.00 | 105993.97 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34410.30 | 0.00 | -11090.94 | -68623.05 |
PERIMETER_MID_ZN_2 | 26-DEC-05:11 | 0.00 | 0.00 | 136370.91 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23036.34 | 0.00 | -7566.98 | -111007.09 |
PERIMETER_MID_ZN_1 | 26-DEC-05:11 | 0.00 | 0.00 | 190042.62 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37377.84 | 0.00 | -11973.87 | -148821.35 |
PERIMETER_MID_ZN_4 | 26-DEC-05:11 | 0.00 | 0.00 | 123698.01 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24768.41 | 0.00 | -7942.22 | -96226.84 |
PERIMETER_TOP_ZN_3 | 26-DEC-03:43 | 0.00 | 0.00 | 12687.95 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3622.97 | 0.00 | -1788.08 | -8089.92 |
PERIMETER_TOP_ZN_2 | 18-DEC-04:11 | 0.00 | 0.00 | 17235.27 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2353.26 | 0.00 | -643.18 | -14762.78 |
PERIMETER_TOP_ZN_1 | 18-DEC-04:11 | 0.00 | 0.00 | 25544.93 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3637.86 | 0.00 | -975.19 | -21744.94 |
PERIMETER_TOP_ZN_4 | 02-JAN-04:11 | 0.00 | 0.00 | 17236.20 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1987.83 | 0.00 | -46.11 | -15726.21 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-04:33 | 0.00 | 0.00 | 5579.22 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25315.35 |
DATACENTER_TOP_ZN_6 | 08-JAN-18:10 | 0.00 | 0.00 | 595.96 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2569.58 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 11966.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1379.04 | -10587.91 |
MIDFLOOR_PLENUM | 10-SEP-15:21 | 122874.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3244.17 | -119629.97 |
TOPFLOOR_PLENUM | 04-DEC-06:12 | 22903.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -342.49 | -22560.80 |
Total Facility | 02-JAN-06:02 | -266515.16 | 285263.36 | 865246.12 | -285263.36 | 0.00 | 0.00 | 20437.57 | 10917.52 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151246.94 | 0.00 | 0.00 | -740254.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.3776 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4571 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 109.3585 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 86.8426 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.8727 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6343 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5900 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5900 | 0.2147 | 1.0000 | Not calculated | 1.2002 | 0.2147 | ||
AIRLOOP DATACENTER BASEMENT | 21.5564 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5565 | 0.0157 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.5119 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5119 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9175 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9175 | 0.0318 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4982 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4982 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.6888 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1003 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 54.6793 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.4720 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4363 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1375 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5900 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5900 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2147 | ||
AIRLOOP DATACENTER BASEMENT | 21.5564 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5564 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.5119 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5119 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9175 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9175 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4982 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4982 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5900 | 5.5900 | 5.5900 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8366 | 5.8366 | 1.9202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.7524 | 54.7524 | 18.7253 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2046 | 5.2046 | 1.9309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8453 | 0.8453 | 0.2409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2998 | 1.2998 | 0.2600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8226 | 1.8226 | 0.3645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5733 | 1.5733 | 0.3147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6432 | 7.6432 | 2.3541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.6030 | 13.6030 | 2.7206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.8915 | 18.8915 | 3.7783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4684 | 14.4684 | 2.8937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8480 | 0.8480 | 0.2425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3424 | 1.3424 | 0.2685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9719 | 1.9719 | 0.3944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5058 | 1.5058 | 0.3012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5119 | 0.5119 | 0.5119 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9175 | 4.9175 | 4.9175 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4982 | 0.4982 | 0.4982 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5564 | 21.5564 | 21.5564 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.3776 | 9.4571 | 11.3776 | 3.1003 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 109.3585 | 86.8426 | 109.3585 | 30.4720 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.8727 | 9.6343 | 10.8727 | 3.1375 | 0.0000 | 1.0000 |
CAV_BAS | 5.5900 | 5.5900 | 5.5900 | 5.5900 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5564 | 21.5565 | 21.5564 | 21.5564 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5119 | 0.5119 | 0.5119 | 0.5119 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9175 | 4.9175 | 4.9175 | 4.9175 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4982 | 0.4982 | 0.4982 | 0.4982 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5900 | 5.5900 | 5.5900 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9183 | 2.9183 | 1.9202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.3762 | 27.3762 | 18.7253 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6023 | 2.6023 | 1.9309 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4227 | 0.4227 | 0.2409 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6499 | 0.6499 | 0.2600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9113 | 0.9113 | 0.3645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7866 | 0.7866 | 0.3147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8216 | 3.8216 | 2.3541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8015 | 6.8015 | 2.7206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4457 | 9.4457 | 3.7783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2342 | 7.2342 | 2.8937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4240 | 0.4240 | 0.2425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6712 | 0.6712 | 0.2685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9860 | 0.9860 | 0.3944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7529 | 0.7529 | 0.3012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5119 | 0.5119 | 0.5119 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9175 | 4.9175 | 4.9175 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4982 | 0.4982 | 0.4982 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5564 | 21.5564 | 21.5564 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.6888 | 3.1003 | 3.1003 | 3.1003 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 54.6793 | 30.4720 | 30.4720 | 30.4720 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4363 | 3.1375 | 3.1375 | 3.1375 | 0.0000 | 1.0000 |
CAV_BAS | 5.5900 | 5.5900 | 5.5900 | 5.5900 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5564 | 21.5564 | 21.5564 | 21.5564 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5119 | 0.5119 | 0.5119 | 0.5119 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9175 | 4.9175 | 4.9175 | 4.9175 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4982 | 0.4982 | 0.4982 | 0.4982 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 15.33 |
Number of hours cooling loads not met | 124.33 |
Number of hours not met | 139.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1174.66 | 774183.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 769.50 | 326043.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3236.57 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.94 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.02 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2272.15 | 239749.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 186.61 | 40043.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 272.83 | 78014.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1127.96 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 794.96 | 83767.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 24808.59 |
Natural Gas | 0.00 | 1969.62 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26778.20 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.87 |
Space Heating | 0.00 |
Space Cooling | 16.61 |
Fans (All) | 49.05 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 535.59 |
Subtotal | 535.59 |
Natural Gas [MJ/m2] | |
Space Heating | 25.36 |
Service Water Heating | 17.16 |
Miscellaneous (All) | 42.52 |
Subtotal | 42.52 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.09 |
Space Heating | 4.39 |
Space Cooling | 2.87 |
Fans (All) | 8.49 |
Service Water Heating | 2.97 |
Receptacle Equipment | 54.81 |
Miscellaneous | 14.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8518.50 | 241.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8537.50 | 222.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8730.17 | 29.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7954.00 | 806.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7892.83 | 867.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7875.00 | 885.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7635.00 | 1125.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
Min | 7635.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1125.00 | 0.00 | 0.00 | 0.00 |
Average | 8568.33 | 191.67 | 0.00 | 0.00 | 0.00 |
Sum | 197071.50 | 4408.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368084.00 | 532.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1682.83 | 585.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1647.50 | 620.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1629.50 | 638.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87359.33 | 16035.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368084.00 | 16035.67 | 0.00 | 0.00 | 0.00 |
Average | 79531.18 | 803.73 | 0.00 | 0.00 | 0.00 |
Sum | 1829217.17 | 18485.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8459.17 | 300.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8621.33 | 128.50 | 10.17 | 0.00 | 0.00 |
CORE_MID | 8711.50 | 48.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8567.33 | 192.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8723.67 | 36.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8617.00 | 143.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8601.67 | 158.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8597.00 | 163.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8139.50 | 620.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Min | 8139.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 620.50 | 10.17 | 0.00 | 0.00 |
Average | 8670.44 | 89.12 | 0.44 | 0.00 | 0.00 |
Sum | 199420.17 | 2049.67 | 10.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367854.17 | 761.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330624.50 | 136.50 | 52.00 | 0.00 | 0.00 |
CORE_MID | 330716.00 | 97.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2152.50 | 115.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2141.83 | 126.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2139.17 | 128.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 94298.50 | 9096.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367854.17 | 9096.50 | 52.00 | 0.00 | 0.00 |
Average | 79877.38 | 455.28 | 2.26 | 0.00 | 0.00 |
Sum | 1837179.67 | 10471.33 | 52.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:49:12
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486008E+11 | 110177.77 | 17-JAN-05:11 | 6.00 | 6.00 | 0.566004E+10 | 7499.17 | 13-JAN-10:20 | 6.00 | 6.00 |
February | 0.447216E+11 | 111700.77 | 21-FEB-05:11 | 5.37 | 4.72 | 0.513482E+10 | 7499.14 | 17-FEB-10:09 | 5.37 | 4.72 |
March | 0.547621E+11 | 110153.71 | 13-MAR-04:11 | 2.17 | 1.63 | 0.613011E+10 | 7499.14 | 07-MAR-10:20 | 2.17 | 1.63 |
April | 0.556626E+11 | 111568.24 | 17-APR-04:12 | 4.67 | 3.76 | 0.544932E+10 | 7499.30 | 25-APR-13:20 | 13.33 | 9.08 |
May | 0.557456E+11 | 114570.18 | 01-MAY-04:11 | 4.67 | 3.91 | 0.589904E+10 | 7499.12 | 04-MAY-09:09 | 9.00 | 8.02 |
June | 0.581888E+11 | 110627.61 | 19-JUN-04:12 | 11.00 | 10.27 | 0.588012E+10 | 7499.34 | 08-JUN-13:20 | 11.00 | 10.27 |
July | 0.590721E+11 | 109516.72 | 03-JUL-04:12 | 9.00 | 7.77 | 0.547182E+10 | 7499.09 | 18-JUL-13:20 | 19.00 | 15.69 |
August | 0.654299E+11 | 115206.97 | 07-AUG-04:11 | 10.67 | 9.54 | 0.613645E+10 | 7584.10 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.559857E+11 | 111463.21 | 25-SEP-04:12 | 11.00 | 9.41 | 0.544965E+10 | 7499.39 | 06-SEP-09:09 | 11.00 | 9.41 |
October | 0.558639E+11 | 111746.46 | 10-OCT-04:12 | 10.33 | 10.33 | 0.566684E+10 | 7499.31 | 17-OCT-09:20 | 11.67 | 11.31 |
November | 0.535391E+11 | 111288.95 | 06-NOV-05:11 | 8.00 | 7.45 | 0.561092E+10 | 7499.15 | 10-NOV-10:09 | 11.00 | 9.41 |
December | 0.512236E+11 | 113111.53 | 26-DEC-05:11 | 1.97 | 0.30 | 0.546518E+10 | 7499.25 | 20-DEC-10:20 | 1.97 | 0.30 |
Annual Sum or Average | 0.658796E+12 | 0.679543E+11 | ||||||||
Minimum of Months | 0.447216E+11 | 109516.72 | 1.97 | 0.30 | 0.513482E+10 | 7499.09 | 1.97 | 0.30 | ||
Maximum of Months | 0.654299E+11 | 115206.97 | 11.00 | 10.33 | 0.613645E+10 | 7584.10 | 23.00 | 15.69 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377203E+11 | 84887.33 | 02-JAN-06:02 | 1.17 | 0.75 | 0.505769E+10 | 6734.77 | 10-JAN-10:00 | -2.0 | -2.0 |
February | 0.371969E+11 | 86011.43 | 21-FEB-05:11 | 5.37 | 4.72 | 0.459657E+10 | 6734.81 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.480203E+11 | 88692.01 | 20-MAR-04:11 | 5.33 | 4.89 | 0.549973E+10 | 6734.78 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.546823E+11 | 93629.95 | 24-APR-04:12 | 7.00 | 5.73 | 0.488430E+10 | 6735.05 | 14-APR-13:00 | 7.00 | 5.73 |
May | 0.499534E+11 | 92610.21 | 01-MAY-04:12 | 4.67 | 3.91 | 0.528402E+10 | 6734.75 | 04-MAY-09:09 | 9.00 | 8.02 |
June | 0.552162E+11 | 90466.72 | 05-JUN-04:12 | 12.00 | 11.82 | 0.527012E+10 | 6734.98 | 08-JUN-13:09 | 13.50 | 10.04 |
July | 0.590217E+11 | 93542.32 | 05-JUL-04:12 | 7.67 | 6.81 | 0.489691E+10 | 6734.84 | 03-JUL-09:09 | 7.67 | 6.81 |
August | 0.659571E+11 | 92696.58 | 07-AUG-04:12 | 10.67 | 9.54 | 0.549876E+10 | 6832.00 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.493360E+11 | 90346.11 | 05-SEP-04:12 | 6.67 | 6.14 | 0.487825E+10 | 6734.92 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.460144E+11 | 93793.34 | 10-OCT-04:12 | 10.33 | 10.33 | 0.507928E+10 | 6734.95 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.442899E+11 | 93209.20 | 13-NOV-05:11 | 3.33 | 3.18 | 0.502940E+10 | 6734.76 | 10-NOV-10:09 | 3.33 | 3.18 |
December | 0.426639E+11 | 89430.89 | 26-DEC-05:11 | 1.97 | 0.30 | 0.489825E+10 | 6734.82 | 20-DEC-10:20 | 1.97 | 0.30 |
Annual Sum or Average | 0.590072E+12 | 0.608733E+11 | ||||||||
Minimum of Months | 0.371969E+11 | 84887.33 | 1.17 | 0.30 | 0.459657E+10 | 6734.75 | -2.0 | -2.0 | ||
Maximum of Months | 0.659571E+11 | 93793.34 | 12.00 | 11.82 | 0.549973E+10 | 6832.00 | 23.00 | 15.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259789E+11 | 51673.74 | 26-JAN-06:02 | 5.00 | 4.51 | 0.484916E+10 | 6734.76 | 20-JAN-10:09 | 5.00 | 4.51 |
February | 0.248581E+11 | 32951.22 | 10-FEB-06:03 | 5.00 | 4.51 | 0.446493E+10 | 6734.76 | 24-FEB-10:09 | 5.17 | 3.81 |
March | 0.308030E+11 | 70893.34 | 24-MAR-05:02 | 4.00 | 3.12 | 0.539517E+10 | 6734.72 | 29-MAR-09:09 | 7.17 | 6.35 |
April | 0.359086E+11 | 78728.11 | 29-APR-05:02 | 6.17 | 5.65 | 0.484968E+10 | 6734.97 | 14-APR-13:00 | 6.17 | 5.65 |
May | 0.389231E+11 | 79319.15 | 25-MAY-05:02 | 7.17 | 7.17 | 0.525176E+10 | 6734.74 | 04-MAY-09:09 | 7.17 | 7.17 |
June | 0.423081E+11 | 78870.25 | 30-JUN-05:02 | 11.00 | 10.57 | 0.525380E+10 | 6734.93 | 08-JUN-13:09 | 11.00 | 10.57 |
July | 0.422835E+11 | 79128.10 | 25-JUL-04:12 | 13.00 | 12.63 | 0.487996E+10 | 6734.78 | 18-JUL-13:09 | 13.00 | 12.63 |
August | 0.460069E+11 | 79410.99 | 26-AUG-05:02 | 14.00 | 12.84 | 0.548306E+10 | 6734.86 | 08-AUG-09:00 | 14.00 | 12.84 |
September | 0.391365E+11 | 79093.00 | 02-SEP-05:02 | 13.00 | 11.97 | 0.485484E+10 | 6734.88 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.318104E+11 | 75214.34 | 05-OCT-05:02 | 4.00 | 4.00 | 0.501171E+10 | 6734.86 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.270303E+11 | 54427.45 | 01-NOV-05:02 | 5.00 | 4.51 | 0.489396E+10 | 6734.75 | 10-NOV-10:09 | 11.00 | 9.41 |
December | 0.244589E+11 | 26519.42 | 22-DEC-17:00 | 5.00 | 4.08 | 0.462435E+10 | 6734.57 | 15-DEC-14:09 | 5.00 | 4.08 |
Annual Sum or Average | 0.409506E+12 | 0.598124E+11 | ||||||||
Minimum of Months | 0.244589E+11 | 26519.42 | 4.00 | 3.12 | 0.446493E+10 | 6734.57 | 5.00 | 3.81 | ||
Maximum of Months | 0.460069E+11 | 79410.99 | 14.00 | 12.84 | 0.548306E+10 | 6734.97 | 14.00 | 12.84 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189406E+11 | 20816.44 | 20-JAN-17:00 | 5.00 | 4.51 | 0.422972E+10 | 6635.63 | 20-JAN-14:00 | 5.00 | 4.51 |
February | 0.185244E+11 | 20411.13 | 24-FEB-17:00 | 6.00 | 4.60 | 0.392977E+10 | 6562.35 | 24-FEB-14:00 | 6.00 | 4.60 |
March | 0.237925E+11 | 25473.37 | 31-MAR-16:00 | 9.00 | 4.96 | 0.486057E+10 | 6733.89 | 10-MAR-14:00 | 9.00 | 4.96 |
April | 0.303784E+11 | 48119.00 | 21-APR-05:02 | 8.00 | 6.97 | 0.468464E+10 | 6734.94 | 14-APR-13:00 | 8.00 | 6.97 |
May | 0.340158E+11 | 52113.10 | 23-MAY-05:03 | 9.67 | 9.01 | 0.512234E+10 | 6734.75 | 12-MAY-09:09 | 9.67 | 9.01 |
June | 0.398377E+11 | 73379.02 | 27-JUN-05:03 | 14.17 | 14.17 | 0.520753E+10 | 6734.88 | 09-JUN-13:00 | 14.17 | 14.17 |
July | 0.406399E+11 | 73899.35 | 24-JUL-05:03 | 13.00 | 13.00 | 0.484256E+10 | 6734.74 | 18-JUL-13:09 | 13.00 | 13.00 |
August | 0.429731E+11 | 71199.62 | 15-AUG-05:03 | 14.50 | 11.07 | 0.544317E+10 | 6734.80 | 08-AUG-09:00 | 14.50 | 11.07 |
September | 0.338294E+11 | 67668.78 | 13-SEP-05:03 | 9.33 | 9.25 | 0.476159E+10 | 6734.84 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.242432E+11 | 33122.94 | 06-OCT-16:00 | 17.00 | 9.21 | 0.461640E+10 | 6734.56 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.202197E+11 | 24536.66 | 10-NOV-16:50 | 7.67 | 6.84 | 0.432472E+10 | 6734.32 | 10-NOV-14:30 | 7.67 | 6.84 |
December | 0.177595E+11 | 18840.94 | 21-DEC-17:00 | 6.00 | 5.49 | 0.403262E+10 | 6415.34 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.345154E+12 | 0.560556E+11 | ||||||||
Minimum of Months | 0.177595E+11 | 18840.94 | 5.00 | 4.51 | 0.392977E+10 | 6415.34 | 5.00 | 4.51 | ||
Maximum of Months | 0.429731E+11 | 73899.35 | 17.00 | 14.17 | 0.544317E+10 | 6734.94 | 16.00 | 14.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269432E+10 | 2840.31 | 24-JAN-06:03 | 6.00 | 5.49 | 0.563487E+09 | 843.49 | 17-JAN-14:09 | 6.00 | 5.49 |
February | 0.272935E+10 | 3073.64 | 21-FEB-14:10 | 9.00 | 7.84 | 0.530883E+09 | 845.62 | 27-FEB-14:30 | 8.50 | 7.45 |
March | 0.376554E+10 | 4949.29 | 20-MAR-12:30 | 10.10 | 6.57 | 0.662244E+09 | 845.63 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.553917E+10 | 7250.02 | 28-APR-14:00 | 20.00 | 12.76 | 0.605832E+09 | 845.66 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.551912E+10 | 7222.53 | 22-MAY-15:00 | 24.00 | 16.08 | 0.656000E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.731092E+10 | 9361.80 | 13-JUN-05:03 | 14.50 | 12.20 | 0.660051E+09 | 845.66 | 08-JUN-13:09 | 14.50 | 12.20 |
July | 0.803321E+10 | 8923.89 | 10-JUL-15:00 | 23.00 | 16.69 | 0.614143E+09 | 846.20 | 10-JUL-13:20 | 23.00 | 16.69 |
August | 0.823533E+10 | 8245.39 | 14-AUG-15:30 | 25.50 | 15.95 | 0.688935E+09 | 858.69 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.525640E+10 | 6619.72 | 13-SEP-14:20 | 23.00 | 16.22 | 0.604810E+09 | 845.64 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.379571E+10 | 5474.25 | 10-OCT-13:10 | 13.00 | 11.87 | 0.616761E+09 | 845.63 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.315020E+10 | 3597.33 | 08-NOV-14:30 | 12.00 | 11.73 | 0.594897E+09 | 845.62 | 24-NOV-14:09 | 12.83 | 11.81 |
December | 0.287523E+10 | 2760.19 | 05-DEC-06:02 | 6.00 | 5.49 | 0.556711E+09 | 835.79 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.589045E+11 | 0.735475E+10 | ||||||||
Minimum of Months | 0.269432E+10 | 2760.19 | 6.00 | 5.49 | 0.530883E+09 | 835.79 | 6.00 | 5.49 | ||
Maximum of Months | 0.823533E+10 | 9361.80 | 25.50 | 16.69 | 0.688935E+09 | 858.69 | 24.00 | 16.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258876E+10 | 4350.09 | 20-JAN-10:05 | 4.33 | 3.91 | 0.348328E+09 | 544.95 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.270461E+10 | 5703.86 | 17-FEB-09:45 | 2.67 | 1.90 | 0.326207E+09 | 544.95 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.339025E+10 | 5077.58 | 25-MAR-09:30 | 10.00 | 7.02 | 0.402047E+09 | 544.95 | 08-MAR-10:00 | 10.00 | 7.02 |
April | 0.641984E+10 | 22334.32 | 30-APR-08:32 | 17.80 | 12.19 | 0.388470E+09 | 544.98 | 14-APR-13:00 | 17.80 | 12.19 |
May | 0.654300E+10 | 22750.78 | 07-MAY-08:32 | 10.67 | 8.56 | 0.421004E+09 | 545.58 | 23-MAY-09:09 | 19.17 | 14.75 |
June | 0.730316E+10 | 16679.34 | 18-JUN-09:53 | 13.90 | 11.33 | 0.423667E+09 | 545.83 | 13-JUN-09:20 | 13.90 | 11.33 |
July | 0.789781E+10 | 22963.38 | 23-JUL-08:42 | 19.83 | 15.59 | 0.394801E+09 | 545.79 | 10-JUL-09:39 | 19.83 | 15.59 |
August | 0.832589E+10 | 23648.92 | 20-AUG-09:42 | 16.17 | 13.12 | 0.442055E+09 | 554.29 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.645399E+10 | 18818.90 | 04-SEP-08:52 | 14.00 | 10.69 | 0.390123E+09 | 544.97 | 07-SEP-09:39 | 13.33 | 10.64 |
October | 0.391234E+10 | 14260.17 | 01-OCT-09:13 | 12.33 | 8.70 | 0.381692E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.292439E+10 | 4902.83 | 13-NOV-09:25 | 8.00 | 7.22 | 0.355833E+09 | 544.95 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.249200E+10 | 3038.15 | 06-DEC-09:55 | 4.00 | 3.12 | 0.331331E+09 | 544.95 | 08-DEC-10:20 | 4.67 | 3.49 |
Annual Sum or Average | 0.609560E+11 | 0.460556E+10 | ||||||||
Minimum of Months | 0.249200E+10 | 3038.15 | 2.67 | 1.90 | 0.326207E+09 | 544.95 | 4.67 | 3.49 | ||
Maximum of Months | 0.832589E+10 | 23648.92 | 19.83 | 15.59 | 0.442055E+09 | 554.29 | 23.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499908E+10 | 30009.86 | 15-JAN-13:13 | 9.67 | 6.81 | 0.562861E+09 | 845.64 | 20-JAN-10:00 | 6.00 | 5.49 |
February | 0.565599E+10 | 20729.01 | 19-FEB-13:32 | 6.00 | 4.14 | 0.524704E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 4.14 |
March | 0.547973E+10 | 12350.26 | 28-MAR-12:10 | 11.67 | 7.18 | 0.632765E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.107919E+11 | 32570.84 | 30-APR-12:32 | 22.00 | 13.38 | 0.598713E+09 | 847.06 | 28-APR-13:39 | 22.00 | 13.38 |
May | 0.888367E+10 | 16777.04 | 22-MAY-13:10 | 22.17 | 14.96 | 0.644317E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.981425E+10 | 17198.29 | 18-JUN-12:53 | 15.40 | 11.94 | 0.653981E+09 | 845.70 | 08-JUN-13:09 | 15.40 | 11.94 |
July | 0.114597E+11 | 31717.46 | 30-JUL-12:22 | 16.50 | 12.23 | 0.610962E+09 | 845.66 | 18-JUL-13:09 | 16.50 | 12.23 |
August | 0.138973E+11 | 33224.51 | 20-AUG-13:02 | 23.00 | 14.82 | 0.686798E+09 | 872.53 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.122823E+11 | 34788.85 | 10-SEP-12:51 | 21.00 | 15.44 | 0.603616E+09 | 847.19 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.814561E+10 | 31582.12 | 01-OCT-11:52 | 14.00 | 9.83 | 0.597795E+09 | 846.82 | 04-OCT-13:50 | 14.00 | 10.28 |
November | 0.548484E+10 | 32100.04 | 11-NOV-12:32 | 9.00 | 7.29 | 0.570701E+09 | 845.64 | 08-NOV-14:00 | 9.00 | 7.29 |
December | 0.442778E+10 | 15913.58 | 18-DEC-13:30 | 8.00 | 5.46 | 0.536895E+09 | 845.65 | 20-DEC-10:20 | 8.33 | 7.62 |
Annual Sum or Average | 0.101322E+12 | 0.722411E+10 | ||||||||
Minimum of Months | 0.442778E+10 | 12350.26 | 6.00 | 4.14 | 0.524704E+09 | 845.64 | 6.00 | 4.14 | ||
Maximum of Months | 0.138973E+11 | 34788.85 | 23.00 | 15.44 | 0.686798E+09 | 872.53 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371573E+10 | 7788.28 | 30-JAN-16:25 | 7.55 | 6.78 | 0.363750E+09 | 544.95 | 17-JAN-14:00 | 7.55 | 6.78 |
February | 0.439346E+10 | 10423.45 | 27-FEB-16:20 | 8.00 | 6.64 | 0.351604E+09 | 544.95 | 21-FEB-14:09 | 8.00 | 6.64 |
March | 0.574577E+10 | 11204.94 | 23-MAR-16:00 | 10.00 | 6.65 | 0.437570E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.992480E+10 | 28972.48 | 30-APR-15:51 | 24.00 | 13.13 | 0.395630E+09 | 544.99 | 14-APR-13:00 | 24.00 | 13.13 |
May | 0.807844E+10 | 27640.43 | 21-MAY-16:52 | 20.00 | 12.79 | 0.422401E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.104783E+11 | 28141.78 | 11-JUN-16:52 | 14.00 | 12.24 | 0.426708E+09 | 544.99 | 08-JUN-13:09 | 14.00 | 12.24 |
July | 0.122689E+11 | 29448.05 | 09-JUL-17:01 | 21.00 | 15.03 | 0.397449E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.131738E+11 | 29571.59 | 20-AUG-16:21 | 23.00 | 14.81 | 0.446062E+09 | 560.05 | 28-AUG-13:00 | 23.00 | 15.30 |
September | 0.746501E+10 | 27564.04 | 10-SEP-14:52 | 22.00 | 16.43 | 0.390299E+09 | 544.97 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.557529E+10 | 21790.86 | 01-OCT-15:12 | 12.67 | 9.64 | 0.401423E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.476127E+10 | 10440.11 | 06-NOV-05:11 | 8.00 | 7.45 | 0.396233E+09 | 544.96 | 07-NOV-14:09 | 11.00 | 10.91 |
December | 0.447434E+10 | 7602.61 | 18-DEC-14:30 | 8.00 | 5.66 | 0.384822E+09 | 544.96 | 04-DEC-14:00 | 8.00 | 5.66 |
Annual Sum or Average | 0.900550E+11 | 0.481395E+10 | ||||||||
Minimum of Months | 0.371573E+10 | 7602.61 | 7.55 | 5.66 | 0.351604E+09 | 544.95 | 7.55 | 5.66 | ||
Maximum of Months | 0.131738E+11 | 29571.59 | 24.00 | 16.43 | 0.446062E+09 | 560.05 | 24.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114422E+10 | 2023.24 | 19-JAN-15:40 | 8.33 | 7.46 | 0.488254E+09 | 744.16 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.130496E+10 | 1960.51 | 22-FEB-15:00 | 9.00 | 6.99 | 0.450111E+09 | 728.36 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.219418E+10 | 2292.04 | 30-MAR-14:00 | 13.00 | 7.37 | 0.570042E+09 | 817.07 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.329433E+10 | 5530.99 | 28-APR-14:00 | 20.00 | 12.76 | 0.570344E+09 | 845.65 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.392373E+10 | 5900.47 | 22-MAY-15:00 | 24.00 | 16.08 | 0.629428E+09 | 845.62 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.531661E+10 | 7650.04 | 13-JUN-15:00 | 26.00 | 17.83 | 0.651743E+09 | 845.65 | 08-JUN-13:09 | 26.00 | 17.83 |
July | 0.564615E+10 | 7426.76 | 10-JUL-15:00 | 23.00 | 16.69 | 0.607009E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.548832E+10 | 6486.70 | 10-AUG-15:00 | 21.00 | 15.45 | 0.678269E+09 | 845.63 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.384786E+10 | 5726.25 | 13-SEP-15:30 | 23.00 | 16.22 | 0.584076E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.240885E+10 | 2990.05 | 06-OCT-15:30 | 17.00 | 9.21 | 0.548390E+09 | 845.60 | 11-OCT-13:50 | 16.00 | 10.29 |
November | 0.158747E+10 | 2125.16 | 10-NOV-15:10 | 11.83 | 8.42 | 0.497420E+09 | 770.52 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.828330E+09 | 1793.13 | 21-DEC-14:40 | 8.00 | 6.98 | 0.456734E+09 | 686.37 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.369850E+11 | 0.673182E+10 | ||||||||
Minimum of Months | 0.828330E+09 | 1793.13 | 8.00 | 6.98 | 0.450111E+09 | 686.37 | 8.00 | 6.98 | ||
Maximum of Months | 0.564615E+10 | 7650.04 | 26.00 | 17.83 | 0.678269E+09 | 845.65 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121565E+10 | 2656.67 | 20-JAN-10:00 | 4.00 | 3.60 | 0.227754E+09 | 499.21 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.144783E+10 | 3796.77 | 17-FEB-09:55 | 3.00 | 2.16 | 0.213304E+09 | 521.19 | 17-FEB-09:00 | 3.00 | 2.16 |
March | 0.220181E+10 | 3237.44 | 25-MAR-09:30 | 10.00 | 7.02 | 0.260086E+09 | 515.45 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.545752E+10 | 23313.76 | 30-APR-09:12 | 18.67 | 12.24 | 0.278603E+09 | 521.33 | 28-APR-07:00 | 18.67 | 12.24 |
May | 0.586837E+10 | 24837.96 | 21-MAY-09:22 | 13.00 | 9.81 | 0.299779E+09 | 521.55 | 23-MAY-08:50 | 18.67 | 14.65 |
June | 0.673749E+10 | 24882.72 | 25-JUN-09:22 | 17.00 | 12.48 | 0.306082E+09 | 521.52 | 13-JUN-08:00 | 17.00 | 12.48 |
July | 0.715270E+10 | 25983.78 | 16-JUL-09:01 | 16.00 | 13.59 | 0.288291E+09 | 521.47 | 10-JUL-08:50 | 16.00 | 13.59 |
August | 0.754110E+10 | 23636.10 | 13-AUG-09:12 | 15.33 | 13.33 | 0.319847E+09 | 521.25 | 14-AUG-07:10 | 17.50 | 14.66 |
September | 0.586628E+10 | 23702.43 | 10-SEP-09:22 | 17.50 | 14.17 | 0.281534E+09 | 521.24 | 21-SEP-08:09 | 13.00 | 11.30 |
October | 0.287044E+10 | 7142.44 | 04-OCT-09:00 | 12.00 | 9.31 | 0.255949E+09 | 521.20 | 02-OCT-10:30 | 12.00 | 9.31 |
November | 0.153647E+10 | 2773.91 | 11-NOV-12:02 | 9.00 | 7.08 | 0.228483E+09 | 493.37 | 03-NOV-10:30 | 9.00 | 7.08 |
December | 0.777614E+09 | 2271.55 | 06-DEC-10:00 | 4.00 | 3.12 | 0.214974E+09 | 447.89 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.486733E+11 | 0.317469E+10 | ||||||||
Minimum of Months | 0.777614E+09 | 2271.55 | 3.00 | 2.16 | 0.213304E+09 | 447.89 | 3.00 | 2.16 | ||
Maximum of Months | 0.754110E+10 | 25983.78 | 18.67 | 14.17 | 0.319847E+09 | 521.55 | 18.67 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393110E+10 | 28564.93 | 15-JAN-13:43 | 9.17 | 6.97 | 0.535110E+09 | 845.65 | 17-JAN-14:39 | 10.67 | 7.88 |
February | 0.467731E+10 | 27798.12 | 19-FEB-15:13 | 5.67 | 4.13 | 0.499518E+09 | 845.86 | 17-FEB-14:20 | 5.67 | 4.13 |
March | 0.409048E+10 | 10957.68 | 28-MAR-12:10 | 11.67 | 7.18 | 0.589767E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.940863E+10 | 34207.37 | 30-APR-13:12 | 22.33 | 12.98 | 0.581480E+09 | 846.72 | 28-APR-13:39 | 22.33 | 12.98 |
May | 0.812260E+10 | 27217.52 | 21-MAY-13:23 | 17.00 | 10.30 | 0.623780E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.868909E+10 | 21308.73 | 11-JUN-12:43 | 17.83 | 14.32 | 0.639773E+09 | 845.69 | 08-JUN-13:09 | 17.83 | 14.32 |
July | 0.992271E+10 | 32852.96 | 30-JUL-13:32 | 17.00 | 12.42 | 0.601070E+09 | 845.66 | 18-JUL-13:09 | 17.00 | 12.42 |
August | 0.122972E+11 | 34448.38 | 13-AUG-13:12 | 21.00 | 15.45 | 0.675600E+09 | 846.63 | 29-AUG-13:00 | 18.00 | 13.90 |
September | 0.122516E+11 | 34322.34 | 24-SEP-11:42 | 19.00 | 14.78 | 0.594853E+09 | 846.84 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.742111E+10 | 30170.78 | 01-OCT-13:22 | 12.50 | 9.55 | 0.568970E+09 | 846.58 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.405112E+10 | 29541.90 | 11-NOV-12:02 | 9.00 | 7.08 | 0.529899E+09 | 845.64 | 17-NOV-10:09 | 6.17 | 3.87 |
December | 0.242463E+10 | 14500.07 | 18-DEC-13:30 | 8.00 | 5.46 | 0.494504E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.872876E+11 | 0.693432E+10 | ||||||||
Minimum of Months | 0.242463E+10 | 10957.68 | 5.67 | 4.13 | 0.494504E+09 | 845.64 | 5.67 | 3.37 | ||
Maximum of Months | 0.122972E+11 | 34448.38 | 22.33 | 15.45 | 0.675600E+09 | 846.84 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155875E+10 | 4084.91 | 19-JAN-15:50 | 8.17 | 7.46 | 0.315826E+09 | 538.93 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.205052E+10 | 7240.73 | 27-FEB-16:30 | 8.00 | 6.72 | 0.296657E+09 | 544.94 | 27-FEB-14:00 | 8.00 | 6.72 |
March | 0.272972E+10 | 7480.59 | 23-MAR-16:40 | 10.00 | 6.65 | 0.359391E+09 | 544.84 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.539451E+10 | 25953.66 | 30-APR-17:11 | 24.00 | 12.77 | 0.360937E+09 | 544.98 | 14-APR-13:00 | 24.00 | 12.77 |
May | 0.611464E+10 | 28243.92 | 21-MAY-17:21 | 20.00 | 13.00 | 0.393998E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.746636E+10 | 29113.06 | 25-JUN-17:21 | 21.50 | 17.05 | 0.412285E+09 | 544.97 | 08-JUN-13:09 | 21.50 | 17.05 |
July | 0.805062E+10 | 28961.89 | 09-JUL-18:11 | 21.00 | 15.03 | 0.387769E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.764238E+10 | 26446.30 | 13-AUG-17:11 | 18.67 | 14.49 | 0.432966E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.559112E+10 | 24402.18 | 10-SEP-16:01 | 20.67 | 16.45 | 0.368364E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.322884E+10 | 9842.09 | 03-OCT-15:40 | 14.00 | 8.96 | 0.343472E+09 | 544.93 | 06-OCT-13:00 | 16.00 | 9.11 |
November | 0.196378E+10 | 4223.25 | 10-NOV-15:30 | 11.50 | 8.42 | 0.317024E+09 | 544.93 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.102094E+10 | 2617.52 | 21-DEC-14:40 | 8.00 | 6.98 | 0.294928E+09 | 498.03 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.528122E+11 | 0.428362E+10 | ||||||||
Minimum of Months | 0.102094E+10 | 2617.52 | 8.00 | 6.65 | 0.294928E+09 | 498.03 | 8.00 | 6.65 | ||
Maximum of Months | 0.805062E+10 | 29113.06 | 24.00 | 17.05 | 0.432966E+09 | 544.98 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479406E+09 | 1895.80 | 19-JAN-15:50 | 8.17 | 7.46 | 0.469144E+09 | 693.24 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.622786E+09 | 1808.23 | 09-FEB-15:50 | 8.00 | 5.73 | 0.427272E+09 | 673.52 | 03-FEB-14:00 | 8.00 | 5.73 |
March | 0.133757E+10 | 2171.84 | 30-MAR-15:30 | 12.00 | 6.19 | 0.530397E+09 | 760.61 | 30-MAR-13:00 | 12.00 | 6.19 |
April | 0.277078E+10 | 5776.78 | 28-APR-15:30 | 20.05 | 13.01 | 0.540181E+09 | 845.64 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.344432E+10 | 6493.35 | 22-MAY-15:20 | 23.67 | 15.81 | 0.598147E+09 | 845.63 | 22-MAY-13:00 | 23.67 | 15.81 |
June | 0.501378E+10 | 8530.25 | 13-JUN-15:10 | 26.08 | 17.81 | 0.637070E+09 | 845.64 | 09-JUN-13:00 | 26.08 | 17.81 |
July | 0.541995E+10 | 8158.78 | 10-JUL-15:00 | 23.00 | 16.69 | 0.597703E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.515174E+10 | 6976.13 | 14-AUG-16:00 | 26.00 | 15.86 | 0.664353E+09 | 845.63 | 15-AUG-13:00 | 19.00 | 15.28 |
September | 0.331768E+10 | 5935.68 | 13-SEP-15:30 | 23.00 | 16.22 | 0.560765E+09 | 845.63 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.163822E+10 | 2470.31 | 01-OCT-14:22 | 13.00 | 9.54 | 0.504684E+09 | 805.19 | 06-OCT-13:00 | 16.00 | 9.11 |
November | 0.732302E+09 | 2016.24 | 10-NOV-15:40 | 11.33 | 8.41 | 0.469572E+09 | 725.70 | 10-NOV-14:00 | 11.33 | 8.41 |
December | 0.241977E+09 | 1651.81 | 21-DEC-16:10 | 6.83 | 6.31 | 0.448116E+09 | 637.81 | 21-DEC-14:00 | 6.83 | 6.31 |
Annual Sum or Average | 0.301705E+11 | 0.644740E+10 | ||||||||
Minimum of Months | 0.241977E+09 | 1651.81 | 6.83 | 5.73 | 0.427272E+09 | 637.81 | 6.83 | 5.73 | ||
Maximum of Months | 0.541995E+10 | 8530.25 | 26.08 | 17.81 | 0.664353E+09 | 845.64 | 26.08 | 17.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622728E+09 | 2359.25 | 20-JAN-10:40 | 5.33 | 4.86 | 0.302614E+09 | 489.20 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.842311E+09 | 2556.49 | 24-FEB-10:40 | 5.67 | 4.28 | 0.280867E+09 | 519.03 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.145058E+10 | 2485.49 | 25-MAR-10:00 | 11.00 | 7.91 | 0.340788E+09 | 493.59 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.478863E+10 | 21084.99 | 30-APR-09:32 | 19.33 | 12.50 | 0.375209E+09 | 544.98 | 14-APR-13:00 | 19.33 | 12.50 |
May | 0.528262E+10 | 19574.62 | 21-MAY-09:12 | 13.00 | 9.64 | 0.401933E+09 | 545.47 | 23-MAY-09:20 | 19.33 | 14.73 |
June | 0.648608E+10 | 24392.11 | 25-JUN-09:32 | 17.33 | 12.62 | 0.413991E+09 | 545.78 | 13-JUN-09:00 | 17.33 | 12.62 |
July | 0.691605E+10 | 24074.98 | 23-JUL-09:22 | 20.50 | 15.83 | 0.390250E+09 | 545.55 | 10-JUL-09:50 | 20.50 | 15.83 |
August | 0.724575E+10 | 24092.10 | 20-AUG-09:52 | 16.00 | 13.05 | 0.433967E+09 | 544.98 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.524602E+10 | 18171.58 | 04-SEP-10:02 | 14.58 | 11.21 | 0.380200E+09 | 544.97 | 07-SEP-09:50 | 13.17 | 10.73 |
October | 0.206811E+10 | 5990.04 | 04-OCT-10:00 | 13.00 | 9.81 | 0.336306E+09 | 544.95 | 03-OCT-09:09 | 13.00 | 9.81 |
November | 0.788640E+09 | 2261.55 | 03-NOV-10:00 | 7.00 | 5.17 | 0.301844E+09 | 474.39 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.330960E+09 | 1975.67 | 06-DEC-10:10 | 4.50 | 3.47 | 0.289346E+09 | 433.85 | 06-DEC-10:20 | 5.00 | 3.82 |
Annual Sum or Average | 0.420685E+11 | 0.424731E+10 | ||||||||
Minimum of Months | 0.330960E+09 | 1975.67 | 4.50 | 3.47 | 0.280867E+09 | 433.85 | 5.00 | 3.82 | ||
Maximum of Months | 0.724575E+10 | 24392.11 | 20.50 | 15.83 | 0.433967E+09 | 545.78 | 20.50 | 15.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262144E+10 | 13526.47 | 11-JAN-13:40 | -1.3 | -2.8 | 0.510541E+09 | 845.64 | 17-JAN-14:39 | 10.67 | 7.88 |
February | 0.331712E+10 | 17559.11 | 17-FEB-13:40 | 6.00 | 3.25 | 0.477060E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 3.25 |
March | 0.287573E+10 | 8735.92 | 28-MAR-12:20 | 11.33 | 7.17 | 0.555820E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.842553E+10 | 35531.36 | 30-APR-13:32 | 22.67 | 12.88 | 0.563590E+09 | 846.77 | 28-APR-13:39 | 22.67 | 12.88 |
May | 0.738238E+10 | 23998.18 | 21-MAY-14:32 | 18.33 | 10.42 | 0.600889E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.836914E+10 | 22274.43 | 11-JUN-14:32 | 17.33 | 14.10 | 0.624464E+09 | 845.69 | 08-JUN-13:09 | 17.33 | 14.10 |
July | 0.966190E+10 | 27771.39 | 30-JUL-13:53 | 17.00 | 12.42 | 0.591011E+09 | 845.67 | 21-JUL-13:09 | 17.00 | 12.42 |
August | 0.118984E+11 | 35895.66 | 20-AUG-13:52 | 23.00 | 14.82 | 0.663343E+09 | 846.22 | 30-AUG-13:09 | 20.50 | 15.21 |
September | 0.113114E+11 | 35391.43 | 24-SEP-15:02 | 22.00 | 15.41 | 0.581541E+09 | 846.73 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.592813E+10 | 34221.14 | 01-OCT-13:42 | 12.83 | 9.38 | 0.542305E+09 | 846.17 | 05-OCT-13:50 | 15.67 | 8.60 |
November | 0.260635E+10 | 17735.96 | 11-NOV-13:42 | 9.00 | 7.08 | 0.503671E+09 | 845.63 | 03-NOV-13:00 | 9.00 | 7.08 |
December | 0.148547E+10 | 11638.49 | 18-DEC-13:30 | 8.00 | 5.46 | 0.475930E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.758830E+11 | 0.669017E+10 | ||||||||
Minimum of Months | 0.148547E+10 | 8735.92 | -1.3 | -2.8 | 0.475930E+09 | 845.63 | 6.00 | 3.25 | ||
Maximum of Months | 0.118984E+11 | 35895.66 | 23.00 | 15.41 | 0.663343E+09 | 846.77 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.893848E+09 | 3423.66 | 19-JAN-15:40 | 8.33 | 7.46 | 0.307330E+09 | 521.18 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.133743E+10 | 6346.06 | 27-FEB-16:30 | 8.00 | 6.72 | 0.287970E+09 | 541.83 | 09-FEB-14:00 | 8.00 | 6.72 |
March | 0.197419E+10 | 6770.28 | 23-MAR-16:50 | 10.00 | 6.65 | 0.343534E+09 | 529.88 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.495419E+10 | 26773.52 | 30-APR-16:52 | 24.00 | 12.58 | 0.345546E+09 | 544.98 | 14-APR-13:00 | 24.00 | 12.58 |
May | 0.570648E+10 | 29276.84 | 21-MAY-17:11 | 20.00 | 12.93 | 0.378235E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.730516E+10 | 30542.35 | 25-JUN-17:31 | 21.67 | 18.03 | 0.401605E+09 | 544.97 | 09-JUN-13:00 | 21.67 | 18.03 |
July | 0.791550E+10 | 30716.06 | 09-JUL-17:21 | 21.00 | 15.03 | 0.380527E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.745708E+10 | 29121.36 | 13-AUG-17:01 | 18.83 | 14.64 | 0.422656E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.520563E+10 | 23305.71 | 24-SEP-16:21 | 21.50 | 15.22 | 0.354801E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.248511E+10 | 9412.41 | 03-OCT-15:40 | 14.00 | 8.96 | 0.326512E+09 | 544.92 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.117889E+10 | 3553.91 | 10-NOV-15:30 | 11.50 | 8.42 | 0.306472E+09 | 537.48 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.502022E+09 | 2530.91 | 21-DEC-14:40 | 8.00 | 6.98 | 0.290803E+09 | 472.94 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.469155E+11 | 0.414599E+10 | ||||||||
Minimum of Months | 0.502022E+09 | 2530.91 | 8.00 | 6.65 | 0.287970E+09 | 472.94 | 7.67 | 6.65 | ||
Maximum of Months | 0.791550E+10 | 30716.06 | 24.00 | 18.03 | 0.422656E+09 | 544.98 | 24.00 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192508E+10 | 5411.44 | 02-JAN-06:08 | 1.17 | 0.75 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | 0.75 |
February | 0.186987E+10 | 4568.61 | 25-FEB-06:10 | 1.00 | 1.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1.00 | 1.00 |
March | 0.298406E+10 | 4715.14 | 31-MAR-05:08 | 3.17 | 2.32 | 0.00 | 0.00 | 01-MAR-00:10 | 3.17 | 2.32 |
April | 0.553465E+10 | 7436.77 | 24-APR-05:15 | 7.00 | 5.00 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 5.00 |
May | 0.469791E+10 | 7918.69 | 01-MAY-05:15 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.635840E+10 | 7706.42 | 26-JUN-05:15 | 14.67 | 12.18 | 0.00 | 0.00 | 01-JUN-00:10 | 14.67 | 12.18 |
July | 0.734674E+10 | 8386.93 | 24-JUL-05:15 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.827692E+10 | 9095.02 | 21-AUG-05:13 | 11.00 | 9.86 | 0.00 | 0.00 | 01-AUG-00:10 | 11.00 | 9.86 |
September | 0.546114E+10 | 7064.23 | 11-SEP-05:15 | 9.33 | 9.33 | 0.00 | 0.00 | 01-SEP-00:10 | 9.33 | 9.33 |
October | 0.370024E+10 | 7334.24 | 10-OCT-05:15 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.266331E+10 | 5536.47 | 13-NOV-06:15 | 4.33 | 3.86 | 0.00 | 0.00 | 01-NOV-00:10 | 4.33 | 3.86 |
December | 0.194640E+10 | 4140.01 | 26-DEC-06:10 | 1.92 | 0.28 | 0.00 | 0.00 | 01-DEC-00:10 | 1.92 | 0.28 |
Annual Sum or Average | 0.527647E+11 | 0.00 | ||||||||
Minimum of Months | 0.186987E+10 | 4140.01 | 1.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.28 | ||
Maximum of Months | 0.827692E+10 | 9095.02 | 14.67 | 13.00 | 0.00 | 0.00 | 14.67 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.683597E+09 | 7155.36 | 09-JAN-05:01 | -2.1 | -2.8 | 0.00 | 0.00 | 01-JAN-00:10 | -2.1 | -2.8 |
February | 0.783263E+09 | 6237.94 | 18-FEB-06:01 | -1.2 | -1.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -1.5 |
March | 0.122459E+10 | 6163.97 | 04-MAR-06:02 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.257599E+10 | 5694.17 | 29-APR-05:10 | 6.17 | 5.65 | 0.00 | 0.00 | 01-APR-00:10 | 6.17 | 5.65 |
May | 0.268256E+10 | 5432.70 | 25-MAY-05:10 | 7.17 | 7.17 | 0.00 | 0.00 | 01-MAY-00:10 | 7.17 | 7.17 |
June | 0.396091E+10 | 5262.98 | 24-JUN-05:10 | 12.00 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 12.00 | 10.35 |
July | 0.446573E+10 | 5376.44 | 24-JUL-15:50 | 19.83 | 16.14 | 0.00 | 0.00 | 01-JUL-00:10 | 19.83 | 16.14 |
August | 0.483797E+10 | 5210.89 | 26-AUG-05:10 | 14.00 | 12.84 | 0.00 | 0.00 | 01-AUG-00:10 | 14.00 | 12.84 |
September | 0.360143E+10 | 5449.52 | 27-SEP-05:10 | 8.83 | 8.36 | 0.00 | 0.00 | 01-SEP-00:10 | 8.83 | 8.36 |
October | 0.179803E+10 | 4540.99 | 07-OCT-05:10 | 3.83 | 3.44 | 0.00 | 0.00 | 01-OCT-00:10 | 3.83 | 3.44 |
November | 0.896008E+09 | 7149.26 | 17-NOV-05:11 | 3.00 | 1.77 | 0.00 | 0.00 | 01-NOV-00:10 | 3.00 | 1.77 |
December | 0.450076E+09 | 7886.87 | 30-DEC-05:01 | -1.8 | -3.4 | 0.00 | 0.00 | 01-DEC-00:10 | -1.8 | -3.4 |
Annual Sum or Average | 0.279602E+11 | 0.00 | ||||||||
Minimum of Months | 0.450076E+09 | 4540.99 | -2.1 | -3.4 | 0.00 | 0.00 | -2.1 | -3.4 | ||
Maximum of Months | 0.483797E+10 | 7886.87 | 19.83 | 16.14 | 0.00 | 0.00 | 19.83 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7837072.63 | 776.78 | 15-JAN-13:48 | 9.17 | 6.97 | 0.00 | 0.00 | 01-JAN-00:10 | 9.17 | 6.97 |
February | 24969614.40 | 1172.78 | 22-FEB-12:40 | 9.33 | 7.76 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 7.76 |
March | 0.259526E+09 | 3182.07 | 25-MAR-12:30 | 13.00 | 10.05 | 0.00 | 0.00 | 01-MAR-00:10 | 13.00 | 10.05 |
April | 0.385602E+10 | 14215.81 | 28-APR-14:40 | 20.07 | 13.39 | 0.00 | 0.00 | 01-APR-00:10 | 20.07 | 13.39 |
May | 0.446683E+10 | 14721.48 | 22-MAY-14:40 | 23.67 | 15.97 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 15.97 |
June | 0.680954E+10 | 17038.62 | 13-JUN-14:20 | 25.40 | 17.58 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 17.58 |
July | 0.789077E+10 | 16697.15 | 21-JUL-14:40 | 27.00 | 15.95 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.95 |
August | 0.751854E+10 | 14676.91 | 14-AUG-14:50 | 24.83 | 16.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 16.12 |
September | 0.450176E+10 | 12600.99 | 12-SEP-15:00 | 22.00 | 15.41 | 0.00 | 0.00 | 01-SEP-00:10 | 22.00 | 15.41 |
October | 0.854422E+09 | 5478.94 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 21144943.37 | 1063.28 | 11-NOV-13:50 | 9.00 | 7.08 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.362113E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.789077E+10 | 17038.62 | 27.00 | 17.58 | 0.00 | 0.00 | 27.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320026E+10 | 2052.51 | 19-JAN-16:20 | 7.33 | 6.98 | 95230132.64 | 126.83 | 18-JAN-14:00 | 7.33 | 6.98 |
February | 0.780770E+10 | 4272.03 | 27-FEB-17:00 | 8.00 | 6.97 | 86396550.56 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.140655E+11 | 7023.10 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.30 | 1.71 |
April | 0.189797E+11 | 8375.49 | 30-APR-18:02 | 24.00 | 13.14 | 91605080.82 | 126.82 | 28-APR-09:30 | 24.00 | 13.14 |
May | 0.428608E+10 | 3366.02 | 31-MAY-24:00 | 9.40 | 7.45 | 99235070.98 | 126.84 | 23-MAY-13:30 | 9.40 | 7.45 |
June | 0.932908E+10 | 5204.20 | 30-JUN-24:00 | 11.00 | 9.86 | 98963578.12 | 126.84 | 27-JUN-09:20 | 11.00 | 9.86 |
July | 0.147911E+11 | 7263.26 | 31-JUL-24:00 | 11.40 | 9.79 | 91885311.11 | 126.83 | 25-JUL-09:09 | 11.40 | 9.79 |
August | 0.198052E+11 | 8236.01 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.418284E+10 | 3225.08 | 30-SEP-24:00 | 7.60 | 5.71 | 91610234.05 | 126.84 | 12-SEP-13:50 | 7.60 | 5.71 |
October | 0.909371E+10 | 5076.03 | 31-OCT-24:00 | 6.60 | 4.32 | 95232124.87 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.135503E+11 | 5839.82 | 03-NOV-16:00 | 8.00 | 4.84 | 94301232.43 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.188472E+11 | 7538.18 | 18-DEC-15:20 | 7.20 | 5.18 | 91880824.79 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.137939E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.320026E+10 | 2052.51 | 4.30 | 1.71 | 86396550.56 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.198052E+11 | 8375.49 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125312E+10 | 1799.87 | 19-JAN-16:30 | 7.00 | 6.74 | 95218248.17 | 126.82 | 18-JAN-14:00 | 7.00 | 6.74 |
February | 0.587194E+10 | 3863.98 | 27-FEB-17:00 | 8.00 | 6.97 | 86396562.19 | 126.82 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.118049E+11 | 6248.32 | 31-MAR-23:40 | 4.43 | 1.73 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.43 | 1.73 |
April | 0.173320E+11 | 7957.59 | 30-APR-18:05 | 24.00 | 13.14 | 91605092.61 | 126.82 | 28-APR-09:20 | 24.00 | 13.14 |
May | 0.332943E+10 | 3039.87 | 31-MAY-23:40 | 9.70 | 8.23 | 99234962.24 | 126.84 | 23-MAY-13:00 | 9.70 | 8.23 |
June | 0.841057E+10 | 4685.93 | 30-JUN-23:40 | 11.00 | 10.07 | 98963179.23 | 126.84 | 27-JUN-09:09 | 11.00 | 10.07 |
July | 0.136533E+11 | 6794.89 | 31-JUL-23:50 | 11.38 | 9.85 | 91885585.66 | 126.84 | 24-JUL-13:39 | 11.38 | 9.85 |
August | 0.184816E+11 | 7661.85 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.330029E+10 | 2810.79 | 30-SEP-23:30 | 7.65 | 5.76 | 91609850.95 | 126.84 | 12-SEP-13:00 | 7.65 | 5.76 |
October | 0.731814E+10 | 4302.71 | 31-OCT-24:00 | 6.60 | 4.32 | 95231955.25 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.110734E+11 | 5398.47 | 03-NOV-16:00 | 8.00 | 4.84 | 94301132.05 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.155396E+11 | 6864.66 | 21-DEC-15:20 | 7.67 | 6.81 | 91880845.20 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.117368E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.125312E+10 | 1799.87 | 4.43 | 1.73 | 86396562.19 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.184816E+11 | 7957.59 | 24.00 | 13.92 | 0.103239E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404228E+09 | 1698.28 | 19-JAN-16:40 | 6.67 | 6.49 | 93736474.62 | 127.50 | 03-JAN-10:00 | 6.67 | 6.49 |
February | 0.417030E+10 | 3682.76 | 17-FEB-17:00 | 5.00 | 2.86 | 86396563.12 | 126.82 | 08-FEB-14:00 | 5.00 | 2.86 |
March | 0.102672E+11 | 5782.98 | 31-MAR-23:20 | 4.57 | 1.75 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.57 | 1.75 |
April | 0.164912E+11 | 8064.92 | 30-APR-17:53 | 24.00 | 13.13 | 91605095.38 | 126.82 | 28-APR-09:30 | 24.00 | 13.13 |
May | 0.257132E+10 | 2886.83 | 31-MAY-23:20 | 10.00 | 9.01 | 99235587.78 | 126.84 | 23-MAY-13:00 | 10.00 | 9.01 |
June | 0.801167E+10 | 4432.96 | 30-JUN-23:20 | 11.00 | 10.27 | 98963206.10 | 126.84 | 27-JUN-09:09 | 11.00 | 10.27 |
July | 0.133160E+11 | 6634.88 | 31-JUL-23:20 | 11.33 | 10.03 | 91885643.89 | 126.84 | 24-JUL-13:39 | 11.33 | 10.03 |
August | 0.181310E+11 | 7734.93 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.260917E+10 | 2257.29 | 30-SEP-23:10 | 7.68 | 5.79 | 91609936.54 | 126.84 | 12-SEP-13:00 | 7.68 | 5.79 |
October | 0.585073E+10 | 3899.74 | 03-OCT-16:50 | 13.17 | 8.54 | 95231886.69 | 126.83 | 13-OCT-13:00 | 11.00 | 11.00 |
November | 0.934512E+10 | 5307.51 | 10-NOV-16:20 | 9.67 | 7.83 | 94301142.03 | 126.83 | 08-NOV-14:00 | 9.67 | 7.83 |
December | 0.135799E+11 | 6645.37 | 21-DEC-15:20 | 7.67 | 6.81 | 91880850.85 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.104748E+12 | 0.114132E+10 | ||||||||
Minimum of Months | 0.404228E+09 | 1698.28 | 4.57 | 1.75 | 86396563.12 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.181310E+11 | 8064.92 | 24.00 | 13.92 | 0.103239E+09 | 127.50 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237418E+12 | 91808.43 | 19-JAN-17:00 | 6.00 | 6.00 | 0.206144E+10 | 2745.70 | 25-JAN-14:39 | 11.00 | 9.22 |
February | 0.435377E+12 | 183340.99 | 09-FEB-17:00 | 6.00 | 4.60 | 0.187025E+10 | 2746.01 | 08-FEB-14:30 | 6.00 | 4.60 |
March | 0.728796E+12 | 358782.01 | 31-MAR-24:00 | 4.30 | 1.71 | 0.223479E+10 | 2745.37 | 31-MAR-09:39 | 4.30 | 1.71 |
April | 0.944183E+12 | 368215.02 | 28-APR-16:00 | 20.00 | 12.32 | 0.198317E+10 | 2749.21 | 28-APR-09:09 | 20.00 | 12.32 |
May | 0.240900E+12 | 176060.12 | 31-MAY-24:00 | 9.40 | 7.45 | 0.214807E+10 | 2745.85 | 04-MAY-09:39 | 9.40 | 7.45 |
June | 0.470550E+12 | 267408.23 | 30-JUN-24:00 | 11.00 | 9.86 | 0.214226E+10 | 2748.76 | 12-JUN-13:00 | 11.00 | 9.86 |
July | 0.732416E+12 | 360204.63 | 31-JUL-24:00 | 11.40 | 9.79 | 0.199016E+10 | 2750.79 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.977941E+12 | 368588.02 | 28-AUG-16:00 | 24.00 | 15.59 | 0.223773E+10 | 2750.73 | 25-AUG-09:00 | 24.00 | 15.59 |
September | 0.234625E+12 | 175562.09 | 30-SEP-24:00 | 7.60 | 5.71 | 0.198292E+10 | 2745.68 | 13-SEP-13:00 | 7.60 | 5.71 |
October | 0.485404E+12 | 267526.75 | 31-OCT-24:00 | 6.60 | 4.32 | 0.206140E+10 | 2746.10 | 30-OCT-13:30 | 6.60 | 4.32 |
November | 0.706585E+12 | 275983.47 | 15-NOV-17:00 | 8.00 | 6.97 | 0.204131E+10 | 2746.62 | 06-NOV-10:50 | 8.00 | 6.97 |
December | 0.974500E+12 | 367427.84 | 26-DEC-17:00 | 1.00 | 0.17 | 0.198901E+10 | 2745.46 | 08-DEC-10:39 | 1.00 | 0.17 |
Annual Sum or Average | 0.716869E+13 | 0.247425E+11 | ||||||||
Minimum of Months | 0.234625E+12 | 91808.43 | 1.00 | 0.17 | 0.187025E+10 | 2745.37 | 1.00 | 0.17 | ||
Maximum of Months | 0.977941E+12 | 368588.02 | 24.00 | 15.59 | 0.223773E+10 | 2750.79 | 24.00 | 15.59 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347987E+09 | 11644.89 | 02-JAN-04:07 | 1.17 |
February | 68354178.23 | 11532.05 | 08-FEB-05:15 | 6.00 |
March | 0.108775E+09 | 11686.72 | 27-MAR-03:05 | 1.65 |
April | 0.125025E+09 | 11549.63 | 06-APR-04:15 | 4.00 |
May | 0.208803E+09 | 11573.26 | 24-MAY-04:15 | 8.77 |
June | 86473596.26 | 11580.04 | 29-JUN-04:15 | 11.00 |
July | 0.276687E+09 | 15390.56 | 22-JUL-16:01 | 29.00 |
August | 0.172600E+09 | 11122.92 | 15-AUG-04:14 | 13.33 |
September | 95177840.05 | 11663.77 | 07-SEP-04:17 | 9.00 |
October | 0.126661E+09 | 11567.93 | 18-OCT-04:15 | 9.33 |
November | 0.160214E+09 | 11560.41 | 15-NOV-05:15 | 11.00 |
December | 0.107700E+09 | 12502.27 | 25-DEC-22:23 | 3.00 |
Annual Sum or Average | 0.188446E+10 | |||
Minimum of Months | 68354178.23 | 11122.92 | 1.17 | |
Maximum of Months | 0.347987E+09 | 15390.56 | 29.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5317649.38 | 27428.57 | 02-JAN-06:02 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 5317649.38 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 5317649.38 | 27428.57 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176243E+10 | 72825.31 | 02-JAN-04:11 | 1.13 |
February | 0.831678E+09 | 66283.37 | 21-FEB-05:11 | 5.37 |
March | 0.332151E+09 | 64995.03 | 06-MAR-05:11 | 3.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 96300483.06 | 60709.48 | 23-OCT-05:02 | 3.17 |
November | 0.781323E+09 | 67469.34 | 27-NOV-05:11 | 4.00 |
December | 0.170786E+10 | 71163.27 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.551174E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.176243E+10 | 72825.31 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3981187.71 | 5925.78 | 11-JAN-06:01 | -2.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 3981187.71 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 3981187.71 | 5925.78 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9077533.94 | 4000.91 | 11-JAN-06:02 | -2.9 |
February | 445465.28 | 2586.06 | 17-FEB-06:01 | -3.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 1136017.34 | 3291.46 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 10659016.55 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 9077533.94 | 4000.91 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30768140.39 | 8225.98 | 10-JAN-06:02 | -4.0 |
February | 2637712.17 | 7103.92 | 13-FEB-06:01 | -1.0 |
March | 41162.17 | 343.02 | 06-MAR-06:04 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 2260484.41 | 6340.51 | 27-NOV-06:03 | 4.00 |
December | 10620836.72 | 7184.63 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 46328335.85 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 30768140.39 | 8225.98 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4962.82 | 66.17 | 10-JAN-06:05 | -4.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 4962.82 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 4962.82 | 66.17 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.838957E+09 | 10195.52 | 02-JAN-05:01 | 1.00 |
February | 0.450373E+09 | 9840.92 | 13-FEB-05:01 | -1.0 |
March | 0.170537E+09 | 9360.41 | 06-MAR-05:11 | 3.87 |
April | 1844030.70 | 4581.47 | 01-APR-05:03 | 2.17 |
May | 2200100.46 | 8802.94 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 42166301.17 | 9038.92 | 23-OCT-05:02 | 3.17 |
November | 0.393600E+09 | 10077.97 | 20-NOV-05:01 | 0.67 |
December | 0.121217E+10 | 10599.33 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.311185E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.121217E+10 | 10599.33 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513630E+09 | 12850.21 | 09-JAN-05:01 | -2.1 |
February | 0.274291E+09 | 12075.57 | 17-FEB-05:01 | -2.1 |
March | 0.119825E+09 | 11524.55 | 06-MAR-05:11 | 3.87 |
April | 2115834.08 | 3494.61 | 01-APR-05:03 | 2.17 |
May | 1325384.02 | 7097.93 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 33460319.46 | 10684.07 | 28-OCT-05:02 | 7.00 |
November | 0.259937E+09 | 12676.34 | 20-NOV-05:01 | 0.67 |
December | 0.824808E+09 | 13636.84 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.202939E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.824808E+09 | 13636.84 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416250E+09 | 17912.52 | 09-JAN-05:01 | -2.1 |
February | 0.215008E+09 | 17360.54 | 27-FEB-05:11 | 6.00 |
March | 0.112891E+09 | 16044.93 | 27-MAR-05:02 | 0.83 |
April | 46032.97 | 281.43 | 01-APR-05:05 | 2.17 |
May | 4334862.01 | 12922.57 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 18650710.67 | 14378.32 | 28-OCT-05:02 | 7.00 |
November | 0.228863E+09 | 18132.65 | 27-NOV-05:11 | 4.00 |
December | 0.838577E+09 | 19003.95 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.183462E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.838577E+09 | 19003.95 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306888E+09 | 11689.88 | 02-JAN-05:01 | 1.00 |
February | 0.140954E+09 | 11036.93 | 13-FEB-05:01 | -1.0 |
March | 43922943.47 | 9958.01 | 04-MAR-06:02 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 1496566.31 | 6762.39 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 8618140.68 | 7320.49 | 28-OCT-05:02 | 7.00 |
November | 0.151148E+09 | 11433.83 | 27-NOV-05:11 | 4.00 |
December | 0.486281E+09 | 12369.56 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.113931E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.486281E+09 | 12369.56 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339449E+10 | 12536.14 | 02-JAN-04:11 | 1.13 |
February | 0.234871E+10 | 12583.48 | 27-FEB-05:11 | 6.00 |
March | 0.144075E+10 | 12131.65 | 06-MAR-05:11 | 3.87 |
April | 0.267630E+09 | 10453.46 | 11-APR-04:12 | 6.00 |
May | 0.126472E+09 | 10879.59 | 05-MAY-04:12 | 5.33 |
June | 2983076.21 | 8382.58 | 07-JUN-05:03 | 6.33 |
July | 1958220.94 | 9764.73 | 31-JUL-05:03 | 7.50 |
August | 12510.95 | 83.41 | 28-AUG-05:05 | 9.17 |
September | 47539544.58 | 9930.19 | 18-SEP-05:03 | 12.00 |
October | 0.826695E+09 | 11608.44 | 23-OCT-04:11 | 3.00 |
November | 0.209916E+10 | 12489.42 | 27-NOV-05:11 | 4.00 |
December | 0.414083E+10 | 12687.98 | 26-DEC-03:43 | 2.00 |
Annual Sum or Average | 0.146972E+11 | |||
Minimum of Months | 12510.95 | 83.41 | 1.13 | |
Maximum of Months | 0.414083E+10 | 12687.98 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192891E+10 | 17134.20 | 02-JAN-04:11 | 1.13 |
February | 0.131295E+10 | 17069.64 | 27-FEB-05:11 | 6.00 |
March | 0.872726E+09 | 16694.46 | 06-MAR-05:11 | 3.87 |
April | 98025031.64 | 13123.34 | 17-APR-05:02 | 3.83 |
May | 58557096.57 | 14598.38 | 05-MAY-04:12 | 5.33 |
June | 1449101.52 | 5419.16 | 07-JUN-05:03 | 6.33 |
July | 447933.22 | 2639.87 | 31-JUL-05:03 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 13445721.55 | 8259.22 | 18-SEP-05:03 | 12.00 |
October | 0.481886E+09 | 15580.12 | 23-OCT-04:11 | 3.00 |
November | 0.123801E+10 | 17108.82 | 27-NOV-05:11 | 4.00 |
December | 0.255870E+10 | 17235.11 | 18-DEC-04:11 | -0.3 |
Annual Sum or Average | 0.856510E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.3 | |
Maximum of Months | 0.255870E+10 | 17235.11 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205182E+10 | 25400.56 | 02-JAN-04:11 | 1.13 |
February | 0.141357E+10 | 25349.09 | 27-FEB-05:11 | 6.00 |
March | 0.113813E+10 | 24782.84 | 06-MAR-05:11 | 3.87 |
April | 0.160547E+09 | 16580.02 | 25-APR-05:02 | 5.17 |
May | 0.157453E+09 | 21773.82 | 05-MAY-04:12 | 5.33 |
June | 7898750.99 | 15277.30 | 08-JUN-05:03 | 6.17 |
July | 413203.45 | 2754.69 | 01-JUL-05:03 | 10.17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 7323949.40 | 8246.97 | 07-SEP-05:03 | 8.83 |
October | 0.542810E+09 | 22221.01 | 23-OCT-04:11 | 3.00 |
November | 0.137962E+10 | 25516.25 | 27-NOV-05:11 | 4.00 |
December | 0.308932E+10 | 25544.72 | 18-DEC-04:11 | -0.3 |
Annual Sum or Average | 0.994890E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.3 | |
Maximum of Months | 0.308932E+10 | 25544.72 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138642E+10 | 17236.18 | 02-JAN-04:11 | 1.13 |
February | 0.816803E+09 | 16354.39 | 27-FEB-05:11 | 6.00 |
March | 0.523251E+09 | 15638.97 | 06-MAR-05:11 | 3.87 |
April | 49907670.44 | 9025.13 | 01-APR-05:03 | 2.17 |
May | 49977725.50 | 14166.95 | 05-MAY-04:12 | 5.33 |
June | 364194.81 | 2298.20 | 08-JUN-05:03 | 6.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 4502190.39 | 7147.76 | 07-SEP-05:03 | 8.83 |
October | 0.280031E+09 | 14534.84 | 30-OCT-04:11 | 7.00 |
November | 0.808015E+09 | 16913.21 | 27-NOV-05:11 | 4.00 |
December | 0.172088E+10 | 17168.23 | 18-DEC-04:11 | -0.3 |
Annual Sum or Average | 0.564015E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.3 | |
Maximum of Months | 0.172088E+10 | 17236.18 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86610597.62 | 9295.32 | 15-JAN-13:13 | 9.67 |
February | 64811072.50 | 9688.95 | 21-FEB-05:11 | 5.37 |
March | 47170445.55 | 9513.74 | 06-MAR-05:11 | 3.87 |
April | 0.114929E+09 | 11492.44 | 30-APR-14:32 | 23.67 |
May | 87595150.05 | 8115.84 | 01-MAY-04:11 | 4.67 |
June | 83000506.94 | 8272.34 | 19-JUN-04:12 | 11.00 |
July | 0.121110E+09 | 9242.33 | 30-JUL-15:02 | 16.83 |
August | 0.109997E+09 | 10846.83 | 20-AUG-15:41 | 23.83 |
September | 85235367.29 | 11072.81 | 10-SEP-14:52 | 22.00 |
October | 58726605.05 | 9509.82 | 01-OCT-15:12 | 12.67 |
November | 71645289.93 | 10339.47 | 27-NOV-05:11 | 4.00 |
December | 58418194.28 | 11963.98 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.989249E+09 | |||
Minimum of Months | 47170445.55 | 8115.84 | 1.97 | |
Maximum of Months | 0.121110E+09 | 11963.98 | 23.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108346E+10 | 11335.19 | 15-JAN-13:43 | 9.17 |
February | 0.778509E+09 | 10747.75 | 19-FEB-15:13 | 5.67 |
March | 0.449879E+09 | 5061.95 | 23-MAR-05:02 | 6.67 |
April | 51549000.74 | 12020.99 | 30-APR-15:12 | 24.00 |
May | 65978552.76 | 8939.07 | 21-MAY-15:21 | 18.50 |
June | 53052016.08 | 7156.63 | 25-JUN-15:22 | 24.50 |
July | 72514818.40 | 11376.82 | 30-JUL-15:31 | 16.33 |
August | 61767426.32 | 11760.87 | 13-AUG-15:51 | 21.00 |
September | 72061247.62 | 12287.16 | 10-SEP-15:21 | 21.50 |
October | 0.177237E+09 | 8202.38 | 01-OCT-14:02 | 13.00 |
November | 0.544397E+09 | 8697.19 | 11-NOV-12:02 | 9.00 |
December | 0.118613E+10 | 4721.89 | 26-DEC-12:00 | 6.00 |
Annual Sum or Average | 0.459654E+10 | |||
Minimum of Months | 51549000.74 | 4721.89 | 5.67 | |
Maximum of Months | 0.118613E+10 | 12287.16 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.595849E+10 | 22044.55 | 09-JAN-05:12 | -2.1 |
February | 0.418418E+10 | 17763.25 | 13-FEB-06:13 | -1.0 |
March | 0.324979E+10 | 14098.35 | 06-MAR-05:22 | 3.90 |
April | 0.113921E+10 | 11716.29 | 21-APR-05:02 | 8.00 |
May | 0.846537E+09 | 14612.73 | 23-MAY-05:03 | 9.67 |
June | 0.280455E+09 | 14268.16 | 21-JUN-05:03 | 11.17 |
July | 0.221654E+09 | 13567.03 | 21-JUL-05:03 | 11.83 |
August | 0.333645E+09 | 13288.82 | 01-AUG-05:02 | 13.00 |
September | 0.714830E+09 | 13422.06 | 12-SEP-05:03 | 11.83 |
October | 0.231222E+10 | 12238.01 | 23-OCT-05:02 | 3.17 |
November | 0.420963E+10 | 18899.83 | 20-NOV-05:12 | 0.33 |
December | 0.716038E+10 | 22903.38 | 04-DEC-06:12 | 3.00 |
Annual Sum or Average | 0.306110E+11 | |||
Minimum of Months | 0.221654E+09 | 11716.29 | -2.1 | |
Maximum of Months | 0.716038E+10 | 22903.38 | 13.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65563637.48 | 557.92 | 02-JAN-04:33 | 1.07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 65563637.48 | |||
Minimum of Months | 0.00 | 0.00 | 1.07 | |
Maximum of Months | 65563637.48 | 557.92 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656979E+09 | 595.96 | 08-JAN-18:10 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 5661270.62 | 410.65 | 16-MAY-04:30 | 6.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 3934731.28 | 379.63 | 03-SEP-06:45 | 9.83 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.666575E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.656979E+09 | 595.96 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144953E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116782E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126764E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105057E+10 | 1906.53 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109596E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107745E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100996E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115954E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108377E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126678E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142946E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.151446E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145729E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100996E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.151446E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.894154E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.731184E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.807826E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675897E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.709636E+09 | 735.93 | 15-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.698313E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.654416E+09 | 735.93 | 07-JUL-15:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.747294E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.691184E+09 | 982.28 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.798250E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.889475E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.929324E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.922695E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.654416E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.929324E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135364E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111581E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124560E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105195E+10 | 1625.29 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110129E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108278E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101639E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116427E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107634E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122594E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134902E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140872E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141917E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101639E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140872E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903657E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.736325E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.812405E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677932E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.707523E+09 | 801.02 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.695067E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.652291E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.750537E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698137E+09 | 1228.64 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.806158E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.894933E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.945893E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.928086E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.652291E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.945893E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144343E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116358E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126264E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104932E+10 | 1805.53 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109506E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107699E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100942E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115834E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108223E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126254E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142419E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.150915E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145369E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100942E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.150915E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.892090E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.729096E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806389E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675339E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.708947E+09 | 735.93 | 15-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.697880E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.653904E+09 | 735.93 | 07-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746618E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690518E+09 | 801.02 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.796496E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.886488E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.926203E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.920997E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.653904E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.926203E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135214E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111275E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124336E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105098E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110039E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108208E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101565E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116323E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107544E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122336E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134714E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140634E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141729E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101565E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140634E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900918E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.734384E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810824E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677109E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.706974E+09 | 735.93 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.694493E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.651886E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.749839E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697334E+09 | 1228.64 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.803323E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.890505E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.942450E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.926004E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.651886E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.942450E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144302E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116357E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126236E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104911E+10 | 1524.25 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109504E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107697E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100938E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115830E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108211E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126224E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142367E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.150869E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145345E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100938E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.150869E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.892090E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.729018E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806335E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675324E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.708938E+09 | 735.93 | 15-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.697838E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.653858E+09 | 735.93 | 07-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746562E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690476E+09 | 801.02 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.796329E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.886404E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.925889E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.920906E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.653858E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.925889E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135214E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111275E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124326E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105096E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110038E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108201E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101563E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116315E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107542E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122329E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134696E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140627E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141722E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101563E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140627E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900625E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.734159E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810647E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677109E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.706961E+09 | 735.93 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.694493E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.651838E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.749761E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697278E+09 | 1163.55 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.803276E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.890318E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.942324E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.925879E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.651838E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.942324E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144953E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222581E+09 |
February | 0.136985E+10 | 0.116782E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313195E+09 |
March | 0.163685E+10 | 0.126764E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186802E+09 |
April | 0.145243E+10 | 0.105057E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233190E+09 |
May | 0.157338E+10 | 0.109596E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.552605E+09 |
June | 0.156900E+10 | 0.107745E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249724.16 | 0.426579E+09 |
July | 0.145680E+10 | 0.100996E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171829.81 | 0.412910E+09 |
August | 0.163685E+10 | 0.115954E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161918.61 | 0.298699E+09 |
September | 0.145243E+10 | 0.108377E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310168E+09 |
October | 0.150991E+10 | 0.126678E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338033E+09 |
November | 0.149516E+10 | 0.142946E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417695E+09 |
December | 0.145680E+10 | 0.151446E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571961E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145729E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1583476.10 | 0.428442E+10 |
Minimum of Months | 0.136985E+10 | 0.100996E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186802E+09 |
Maximum of Months | 0.163685E+10 | 0.151446E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171829.81 | 0.571961E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.894154E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147513E+09 |
February | 0.882782E+09 | 0.731184E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205230E+09 |
March | 0.105485E+10 | 0.807826E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121145E+09 |
April | 0.936002E+09 | 0.675897E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153346E+09 |
May | 0.101394E+10 | 0.709636E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 0.367799E+09 |
June | 0.101113E+10 | 0.698313E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166480.50 | 0.280262E+09 |
July | 0.938820E+09 | 0.654416E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 880180.29 | 0.269772E+09 |
August | 0.105485E+10 | 0.747294E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107942.91 | 0.193709E+09 |
September | 0.936002E+09 | 0.691184E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209519E+09 |
October | 0.973041E+09 | 0.798250E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220904E+09 |
November | 0.963541E+09 | 0.889475E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269749E+09 |
December | 0.938820E+09 | 0.929324E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367119E+09 |
Annual Sum or Average | 0.116768E+11 | 0.922695E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1154606.02 | 0.280607E+10 |
Minimum of Months | 0.882782E+09 | 0.654416E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121145E+09 |
Maximum of Months | 0.105485E+10 | 0.929324E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 880180.29 | 0.367799E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135364E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222665E+09 |
February | 0.136988E+10 | 0.111581E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311565E+09 |
March | 0.163688E+10 | 0.124560E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181573E+09 |
April | 0.145246E+10 | 0.105195E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234383E+09 |
May | 0.157341E+10 | 0.110129E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 0.549511E+09 |
June | 0.156904E+10 | 0.108278E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249717.03 | 0.422295E+09 |
July | 0.145684E+10 | 0.101639E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1228842.62 | 0.410545E+09 |
August | 0.163688E+10 | 0.116427E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161895.64 | 0.302665E+09 |
September | 0.145246E+10 | 0.107634E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320219E+09 |
October | 0.150994E+10 | 0.122594E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337982E+09 |
November | 0.149520E+10 | 0.134902E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409627E+09 |
December | 0.145684E+10 | 0.140872E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551018E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141917E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1640458.70 | 0.425405E+10 |
Minimum of Months | 0.136988E+10 | 0.101639E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181573E+09 |
Maximum of Months | 0.163688E+10 | 0.140872E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1228842.62 | 0.551018E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.903657E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154607E+09 |
February | 0.882782E+09 | 0.736325E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223378E+09 |
March | 0.105485E+10 | 0.812405E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133356E+09 |
April | 0.936002E+09 | 0.677932E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172112E+09 |
May | 0.101394E+10 | 0.707523E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.393174E+09 |
June | 0.101113E+10 | 0.695067E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166456.08 | 0.311651E+09 |
July | 0.938820E+09 | 0.652291E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662262.02 | 0.310518E+09 |
August | 0.105485E+10 | 0.750537E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107878.38 | 0.229380E+09 |
September | 0.936002E+09 | 0.698137E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223276E+09 |
October | 0.973041E+09 | 0.806158E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243957E+09 |
November | 0.963541E+09 | 0.894933E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303664E+09 |
December | 0.938820E+09 | 0.945893E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420478E+09 |
Annual Sum or Average | 0.116768E+11 | 0.928086E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 936598.82 | 0.311955E+10 |
Minimum of Months | 0.882782E+09 | 0.652291E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133356E+09 |
Maximum of Months | 0.105485E+10 | 0.945893E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662262.02 | 0.420478E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144343E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451093E+09 |
February | 0.136985E+10 | 0.116358E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642371E+09 |
March | 0.163685E+10 | 0.126264E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386002E+09 |
April | 0.145243E+10 | 0.104932E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493884E+09 |
May | 0.157338E+10 | 0.109506E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119526E+10 |
June | 0.156900E+10 | 0.107699E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546223.75 | 0.934055E+09 |
July | 0.145680E+10 | 0.100942E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2731482.94 | 0.886274E+09 |
August | 0.163685E+10 | 0.115834E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356973.78 | 0.637174E+09 |
September | 0.145243E+10 | 0.108223E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658728E+09 |
October | 0.150991E+10 | 0.126254E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689419E+09 |
November | 0.149516E+10 | 0.142419E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828394E+09 |
December | 0.145680E+10 | 0.150915E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111879E+10 |
Annual Sum or Average | 0.181194E+11 | 0.145369E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3634680.47 | 0.892145E+10 |
Minimum of Months | 0.136985E+10 | 0.100942E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386002E+09 |
Maximum of Months | 0.163685E+10 | 0.150915E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2731482.94 | 0.119526E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.892090E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305023E+09 |
February | 0.649041E+09 | 0.729096E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434161E+09 |
March | 0.773965E+09 | 0.806389E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258278E+09 |
April | 0.688021E+09 | 0.675339E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343007E+09 |
May | 0.744847E+09 | 0.708947E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815931E+09 |
June | 0.742030E+09 | 0.697880E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364126.14 | 0.629756E+09 |
July | 0.690839E+09 | 0.653904E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1993790.61 | 0.608853E+09 |
August | 0.773965E+09 | 0.746618E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238088.62 | 0.439282E+09 |
September | 0.688021E+09 | 0.690518E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464108E+09 |
October | 0.715730E+09 | 0.796496E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467302E+09 |
November | 0.708685E+09 | 0.886488E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554997E+09 |
December | 0.690839E+09 | 0.926203E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747428E+09 |
Annual Sum or Average | 0.858171E+10 | 0.920997E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2596005.36 | 0.606813E+10 |
Minimum of Months | 0.649041E+09 | 0.653904E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258278E+09 |
Maximum of Months | 0.773965E+09 | 0.926203E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1993790.61 | 0.815931E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135214E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492511E+09 |
February | 0.136988E+10 | 0.111275E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693453E+09 |
March | 0.163688E+10 | 0.124336E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400121E+09 |
April | 0.145246E+10 | 0.105098E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529343E+09 |
May | 0.157341E+10 | 0.110039E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123412E+10 |
June | 0.156904E+10 | 0.108208E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546205.30 | 0.944687E+09 |
July | 0.145684E+10 | 0.101565E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2834515.26 | 0.916746E+09 |
August | 0.163688E+10 | 0.116323E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356971.78 | 0.680269E+09 |
September | 0.145246E+10 | 0.107544E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726628E+09 |
October | 0.150994E+10 | 0.122336E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748994E+09 |
November | 0.149520E+10 | 0.134714E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883413E+09 |
December | 0.145684E+10 | 0.140634E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116842E+10 |
Annual Sum or Average | 0.181198E+11 | 0.141729E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3737692.34 | 0.941871E+10 |
Minimum of Months | 0.136988E+10 | 0.101565E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400121E+09 |
Maximum of Months | 0.163688E+10 | 0.140634E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2834515.26 | 0.123412E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900918E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311888E+09 |
February | 0.882782E+09 | 0.734384E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447229E+09 |
March | 0.105485E+10 | 0.810824E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261855E+09 |
April | 0.936002E+09 | 0.677109E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348709E+09 |
May | 0.101394E+10 | 0.706974E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845613E+09 |
June | 0.101113E+10 | 0.694493E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364075.69 | 0.662423E+09 |
July | 0.938820E+09 | 0.651886E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1487367.86 | 0.644049E+09 |
August | 0.105485E+10 | 0.749839E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238000.80 | 0.465419E+09 |
September | 0.936002E+09 | 0.697334E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468687E+09 |
October | 0.973041E+09 | 0.803323E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480756E+09 |
November | 0.963541E+09 | 0.890505E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569117E+09 |
December | 0.938820E+09 | 0.942450E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767569E+09 |
Annual Sum or Average | 0.116768E+11 | 0.926004E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2089444.35 | 0.627331E+10 |
Minimum of Months | 0.882782E+09 | 0.651886E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261855E+09 |
Maximum of Months | 0.105485E+10 | 0.942450E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1487367.86 | 0.845613E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144302E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508434E+09 |
February | 0.136985E+10 | 0.116357E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721330E+09 |
March | 0.163685E+10 | 0.126236E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440620E+09 |
April | 0.145243E+10 | 0.104911E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571039E+09 |
May | 0.157338E+10 | 0.109504E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139550E+10 |
June | 0.156900E+10 | 0.107697E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630063.23 | 0.111426E+10 |
July | 0.145680E+10 | 0.100938E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3077407.40 | 0.105736E+10 |
August | 0.163685E+10 | 0.115830E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415509.90 | 0.759375E+09 |
September | 0.145243E+10 | 0.108211E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754401E+09 |
October | 0.150991E+10 | 0.126224E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767159E+09 |
November | 0.149516E+10 | 0.142367E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923414E+09 |
December | 0.145680E+10 | 0.150869E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126776E+10 |
Annual Sum or Average | 0.181194E+11 | 0.145345E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4122980.53 | 0.102806E+11 |
Minimum of Months | 0.136985E+10 | 0.100938E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440620E+09 |
Maximum of Months | 0.163685E+10 | 0.150869E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3077407.40 | 0.139550E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.892090E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342625E+09 |
February | 0.882782E+09 | 0.729018E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490030E+09 |
March | 0.105485E+10 | 0.806335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297793E+09 |
April | 0.936002E+09 | 0.675324E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403791E+09 |
May | 0.101394E+10 | 0.708938E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966861E+09 |
June | 0.101113E+10 | 0.697838E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420034.17 | 0.758799E+09 |
July | 0.938820E+09 | 0.653858E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2240719.67 | 0.736650E+09 |
August | 0.105485E+10 | 0.746562E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277006.03 | 0.531518E+09 |
September | 0.936002E+09 | 0.690476E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544695E+09 |
October | 0.973041E+09 | 0.796329E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528012E+09 |
November | 0.963541E+09 | 0.886404E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622461E+09 |
December | 0.938820E+09 | 0.925889E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847920E+09 |
Annual Sum or Average | 0.116768E+11 | 0.920906E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2937759.86 | 0.707116E+10 |
Minimum of Months | 0.882782E+09 | 0.653858E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297793E+09 |
Maximum of Months | 0.105485E+10 | 0.925889E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2240719.67 | 0.966861E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135214E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549259E+09 |
February | 0.136988E+10 | 0.111275E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785163E+09 |
March | 0.163688E+10 | 0.124326E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460039E+09 |
April | 0.145246E+10 | 0.105096E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622666E+09 |
May | 0.157341E+10 | 0.110038E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145527E+10 |
June | 0.156904E+10 | 0.108201E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630043.20 | 0.113072E+10 |
July | 0.145684E+10 | 0.101563E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3247544.40 | 0.109916E+10 |
August | 0.163688E+10 | 0.116315E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415513.30 | 0.817748E+09 |
September | 0.145246E+10 | 0.107542E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852567E+09 |
October | 0.150994E+10 | 0.122329E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852776E+09 |
November | 0.149520E+10 | 0.134696E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991028E+09 |
December | 0.145684E+10 | 0.140627E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131332E+10 |
Annual Sum or Average | 0.181198E+11 | 0.141722E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4293100.89 | 0.109297E+11 |
Minimum of Months | 0.136988E+10 | 0.101563E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460039E+09 |
Maximum of Months | 0.163688E+10 | 0.140627E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3247544.40 | 0.145527E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900625E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354086E+09 |
February | 0.882782E+09 | 0.734159E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514355E+09 |
March | 0.105485E+10 | 0.810647E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305517E+09 |
April | 0.936002E+09 | 0.677109E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410906E+09 |
May | 0.101394E+10 | 0.706961E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100374E+10 |
June | 0.101113E+10 | 0.694493E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420006.53 | 0.796903E+09 |
July | 0.938820E+09 | 0.651838E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1771269.40 | 0.776128E+09 |
August | 0.105485E+10 | 0.749761E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277026.71 | 0.559803E+09 |
September | 0.936002E+09 | 0.697278E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549195E+09 |
October | 0.973041E+09 | 0.803276E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551776E+09 |
November | 0.963541E+09 | 0.890318E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649416E+09 |
December | 0.938820E+09 | 0.942324E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877332E+09 |
Annual Sum or Average | 0.116768E+11 | 0.925879E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2468302.64 | 0.734915E+10 |
Minimum of Months | 0.882782E+09 | 0.651838E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305517E+09 |
Maximum of Months | 0.105485E+10 | 0.942324E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1771269.40 | 0.100374E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479218E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672598E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391622E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490742E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116858E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292080.15 | 0.893755E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014285.55 | 0.865394E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197783.50 | 0.636982E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669827E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723854E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900910E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122869E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2504149.20 | 0.912216E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391622E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014285.55 | 0.122869E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791876E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113517E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660787E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842332E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203171E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556890.34 | 0.155678E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3824960.50 | 0.148782E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395413.48 | 0.109637E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115982E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122746E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149253E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199518E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4777264.32 | 0.154778E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660787E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3824960.50 | 0.203171E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787452E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113736E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693396E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927900E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222534E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178492.90 | 0.175728E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2552382.03 | 0.168370E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213043.43 | 0.122543E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123342E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123753E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146156E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196252E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2943918.36 | 0.163329E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693396E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2552382.03 | 0.222534E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 735.38 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 665.26 | 08-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 690.62 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1906.53 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 750.79 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1084.72 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 751.95 | 05-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 22-JUL-17:10 | 737.12 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 515.17 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 672.74 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 849.46 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 896.69 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1316.90 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.17 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 1316.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 485.27 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 424.16 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 442.70 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 482.72 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 704.75 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 559.91 | 18-JUN-09:50 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-15:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 22-JUL-19:10 | 470.65 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 14-AUG-16:50 | 319.92 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 446.96 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 539.73 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 571.19 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 831.29 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.92 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 831.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 722.63 | 01-JAN-14:55 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 705.40 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 657.79 | 27-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1625.29 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 717.49 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1055.64 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 807.76 | 18-JUN-12:10 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 | 22-JUL-19:10 | 745.70 | 30-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 517.77 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 661.13 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 830.52 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 836.52 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1271.01 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.77 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 | 1271.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 514.14 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 470.24 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 497.67 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 564.38 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 760.38 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 636.78 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.14 | 22-JUL-19:06 | 642.29 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 14-AUG-16:50 | 395.89 | 18-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 477.11 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 618.28 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 663.09 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 959.60 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.89 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 31.14 | 959.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1449.37 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1445.02 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1441.43 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1805.53 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1476.46 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2287.19 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1643.25 | 05-JUN-21:13 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.29 | 22-JUL-17:01 | 1448.11 | 30-JUL-18:50 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1093.93 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1367.12 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1701.01 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1672.85 | 25-NOV-05:14 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2669.44 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.93 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 135.29 | 2669.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 970.81 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 961.64 | 08-FEB-22:03 |
March | 1239.33 | 01-MAR-08:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 959.06 | 27-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 987.37 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 15-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1485.33 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1329.08 | 18-JUN-10:10 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 07-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.74 | 22-JUL-19:10 | 989.82 | 30-JUL-18:50 |
August | 1239.33 | 01-AUG-07:10 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 14-AUG-16:50 | 698.34 | 22-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 801.02 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 926.87 | 06-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1110.10 | 20-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1126.12 | 25-NOV-05:12 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1747.79 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.34 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 119.74 | 1747.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1597.87 | 01-JAN-14:55 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1623.03 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1440.75 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1573.51 | 16-APR-12:20 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2258.72 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1793.71 | 18-JUN-15:32 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.45 | 22-JUL-19:10 | 1637.25 | 30-JUL-18:50 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1126.88 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1405.85 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1791.50 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1699.00 | 25-NOV-05:12 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2704.36 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.88 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 158.45 | 2704.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 998.25 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 968.73 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 962.81 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1009.69 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1532.89 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1366.71 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.71 | 22-JUL-19:06 | 1410.07 | 30-JUL-18:50 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.66 | 14-AUG-16:50 | 803.47 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 936.60 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1168.87 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1123.99 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1792.26 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.47 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 71.71 | 1792.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1638.75 | 10-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1787.23 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1778.03 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1587.41 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2604.37 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 1974.99 | 05-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.26 | 22-JUL-17:01 | 1690.15 | 11-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1309.91 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1511.01 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1941.11 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2095.21 | 25-NOV-05:20 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3123.86 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1309.91 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 149.26 | 3123.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1105.62 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1190.49 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1184.49 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1081.32 | 16-APR-11:55 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1709.44 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1586.21 | 18-JUN-10:55 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 | 22-JUL-19:10 | 1188.61 | 30-JUL-18:30 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 841.80 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1034.77 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1279.42 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1396.77 | 25-NOV-05:20 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2053.28 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.80 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 | 2053.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1662.70 | 10-JAN-05:52 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1793.71 | 08-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1778.35 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1993.56 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2590.31 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 2214.97 | 18-JUN-15:23 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.22 | 22-JUL-19:10 | 1989.63 | 30-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1355.12 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1567.75 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2008.71 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2095.19 | 25-NOV-05:20 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3163.84 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.12 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 178.22 | 3163.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1109.23 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1198.73 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1190.07 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1216.36 | 15-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1768.73 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1692.50 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.60 | 22-JUL-19:06 | 1726.69 | 30-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 969.28 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1163.55 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1053.60 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1359.20 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1413.69 | 25-NOV-05:14 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2123.28 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.28 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 84.60 | 2123.28 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1623.03 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1450.46 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1462.73 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1593.40 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 2360.00 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.37 | 13-JUN-16:00 | 1581.52 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.95 | 22-JUL-18:51 | 1467.17 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 14-AUG-17:00 | 1086.14 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1470.77 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1812.30 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1952.91 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2893.48 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.95 | 2893.48 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2717.42 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2477.57 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2447.16 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2674.79 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 4105.76 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 | 13-JUN-16:00 | 2750.68 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.22 | 22-JUL-18:51 | 2424.89 | 30-JUL-18:54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 14-AUG-17:00 | 1892.11 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2503.90 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3059.84 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3138.81 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4762.07 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1892.11 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.22 | 4762.07 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2415.49 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2675.61 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2623.98 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2590.74 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 4231.29 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 13-JUN-17:00 | 3271.70 | 18-JUN-15:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.26 | 22-JUL-18:51 | 2901.71 | 30-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 14-AUG-18:00 | 2066.98 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2429.74 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3104.85 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2928.46 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5109.02 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2066.98 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.26 | 5109.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 110177.77 | 17-JAN-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111700.77 | 21-FEB-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110153.71 | 13-MAR-04:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 111568.24 | 17-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114570.18 | 01-MAY-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 110627.61 | 19-JUN-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 109516.72 | 03-JUL-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115206.97 | 07-AUG-04:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 111463.21 | 25-SEP-04:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111746.46 | 10-OCT-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 111288.95 | 06-NOV-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113111.53 | 26-DEC-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 109516.72 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115206.97 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84887.33 | 02-JAN-06:02 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86011.43 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88692.01 | 20-MAR-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93629.95 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92610.21 | 01-MAY-04:12 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90466.72 | 05-JUN-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93542.32 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 92696.58 | 07-AUG-04:12 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90346.11 | 05-SEP-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93793.34 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93209.20 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89430.89 | 26-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 84887.33 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93793.34 | 8061.19 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 51673.74 | 26-JAN-06:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 32951.22 | 10-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70893.34 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78728.11 | 29-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79319.15 | 25-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78870.25 | 30-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79128.10 | 25-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79410.99 | 26-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79093.00 | 02-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75214.34 | 05-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54427.45 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26519.42 | 22-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26519.42 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79410.99 | 15316.26 | 17424.44 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20816.44 | 20-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20411.13 | 24-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25473.37 | 31-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48119.00 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52113.10 | 23-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73379.02 | 27-JUN-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73899.35 | 24-JUL-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71199.62 | 15-AUG-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67668.78 | 13-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33122.94 | 06-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24536.66 | 10-NOV-16:50 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18840.94 | 21-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18840.94 | 6448.95 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73899.35 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2840.31 | 24-JAN-06:03 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3073.64 | 21-FEB-14:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
March | 4949.29 | 20-MAR-12:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 |
April | 7250.02 | 28-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
May | 7222.53 | 22-MAY-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 9361.80 | 13-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
July | 8923.89 | 10-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
August | 8245.39 | 14-AUG-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 0.00 |
September | 6619.72 | 13-SEP-14:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
October | 5474.25 | 10-OCT-13:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 |
November | 3597.33 | 08-NOV-14:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
December | 2760.19 | 05-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2760.19 | 809.73 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9361.80 | 2010.79 | 1040.96 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 80.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4350.09 | 20-JAN-10:05 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5703.86 | 17-FEB-09:45 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5077.58 | 25-MAR-09:30 | 818.42 | 447.22 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22334.32 | 30-APR-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.57 |
May | 22750.78 | 07-MAY-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.23 |
June | 16679.34 | 18-JUN-09:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.29 |
July | 22963.38 | 23-JUL-08:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.26 |
August | 23648.92 | 20-AUG-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.22 |
September | 18818.90 | 04-SEP-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.43 |
October | 14260.17 | 01-OCT-09:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.14 |
November | 4902.83 | 13-NOV-09:25 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 |
December | 3038.15 | 06-DEC-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3038.15 | 260.91 | 149.06 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23648.92 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30009.86 | 15-JAN-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 |
February | 20729.01 | 19-FEB-13:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 |
March | 12350.26 | 28-MAR-12:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
April | 32570.84 | 30-APR-12:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.45 |
May | 16777.04 | 22-MAY-13:10 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 17198.29 | 18-JUN-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.09 |
July | 31717.46 | 30-JUL-12:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.07 |
August | 33224.51 | 20-AUG-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.22 |
September | 34788.85 | 10-SEP-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.82 |
October | 31582.12 | 01-OCT-11:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.12 |
November | 32100.04 | 11-NOV-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.13 |
December | 15913.58 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12350.26 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 | |
Maximum of Months | 34788.85 | 2010.83 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7788.28 | 30-JAN-16:25 | 4957.30 | 2943.70 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10423.45 | 27-FEB-16:20 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11204.94 | 23-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 |
April | 28972.48 | 30-APR-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27640.43 | 21-MAY-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.15 |
June | 28141.78 | 11-JUN-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.49 |
July | 29448.05 | 09-JUL-17:01 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.08 |
August | 29571.59 | 20-AUG-16:21 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.31 |
September | 27564.04 | 10-SEP-14:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.01 |
October | 21790.86 | 01-OCT-15:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.86 |
November | 10440.11 | 06-NOV-05:11 | 0.00 | 347.85 | 3843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7602.61 | 18-DEC-14:30 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7602.61 | 0.00 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29571.59 | 4957.30 | 2943.70 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2023.24 | 19-JAN-15:40 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1960.51 | 22-FEB-15:00 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 |
March | 2292.04 | 30-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.26 |
April | 5530.99 | 28-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 |
May | 5900.47 | 22-MAY-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 7650.04 | 13-JUN-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 0.00 |
July | 7426.76 | 10-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
August | 6486.70 | 10-AUG-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.63 |
September | 5726.25 | 13-SEP-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
October | 2990.05 | 06-OCT-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 |
November | 2125.16 | 10-NOV-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.31 |
December | 1793.13 | 21-DEC-14:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1793.13 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7650.04 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 150.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2656.67 | 20-JAN-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3796.77 | 17-FEB-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3237.44 | 25-MAR-09:30 | 0.00 | 447.22 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23313.76 | 30-APR-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.07 |
May | 24837.96 | 21-MAY-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.37 |
June | 24882.72 | 25-JUN-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.76 |
July | 25983.78 | 16-JUL-09:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.22 |
August | 23636.10 | 13-AUG-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.44 |
September | 23702.43 | 10-SEP-09:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.86 |
October | 7142.44 | 04-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.84 |
November | 2773.91 | 11-NOV-12:02 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.91 |
December | 2271.55 | 06-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2271.55 | 0.00 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25983.78 | 2478.65 | 1341.67 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28564.93 | 15-JAN-13:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.05 |
February | 27798.12 | 19-FEB-15:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.07 |
March | 10957.68 | 28-MAR-12:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.32 |
April | 34207.37 | 30-APR-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.07 |
May | 27217.52 | 21-MAY-13:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.28 |
June | 21308.73 | 11-JUN-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.86 |
July | 32852.96 | 30-JUL-13:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.57 |
August | 34448.38 | 13-AUG-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.61 |
September | 34322.34 | 24-SEP-11:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.72 |
October | 30170.78 | 01-OCT-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.72 |
November | 29541.90 | 11-NOV-12:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 821.91 |
December | 14500.07 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10957.68 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 | |
Maximum of Months | 34448.38 | 1923.15 | 1040.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4084.91 | 19-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7240.73 | 27-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7480.59 | 23-MAR-16:40 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.77 |
April | 25953.66 | 30-APR-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.58 |
May | 28243.92 | 21-MAY-17:21 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.80 |
June | 29113.06 | 25-JUN-17:21 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.99 |
July | 28961.89 | 09-JUL-18:11 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.54 |
August | 26446.30 | 13-AUG-17:11 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.44 |
September | 24402.18 | 10-SEP-16:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.46 |
October | 9842.09 | 03-OCT-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.43 |
November | 4223.25 | 10-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.93 |
December | 2617.52 | 21-DEC-14:40 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2617.52 | 0.00 | 260.86 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29113.06 | 1295.83 | 670.83 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1895.80 | 19-JAN-15:50 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1808.23 | 09-FEB-15:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.11 |
March | 2171.84 | 30-MAR-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.67 |
April | 5776.78 | 28-APR-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 |
May | 6493.35 | 22-MAY-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
June | 8530.25 | 13-JUN-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.98 | 0.00 |
July | 8158.78 | 10-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 |
August | 6976.13 | 14-AUG-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
September | 5935.68 | 13-SEP-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
October | 2470.31 | 01-OCT-14:22 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.78 |
November | 2016.24 | 10-NOV-15:40 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.10 |
December | 1651.81 | 21-DEC-16:10 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1651.81 | 506.08 | 289.13 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8530.25 | 1923.11 | 2187.81 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 46.98 | 703.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2359.25 | 20-JAN-10:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2556.49 | 24-FEB-10:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
March | 2485.49 | 25-MAR-10:00 | 409.21 | 223.61 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21084.99 | 30-APR-09:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.78 |
May | 19574.62 | 21-MAY-09:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.52 |
June | 24392.11 | 25-JUN-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.55 |
July | 24074.98 | 23-JUL-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.62 |
August | 24092.10 | 20-AUG-09:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.68 |
September | 18171.58 | 04-SEP-10:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.21 |
October | 5990.04 | 04-OCT-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2261.55 | 03-NOV-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.81 |
December | 1975.67 | 06-DEC-10:10 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1975.67 | 326.14 | 186.33 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24392.11 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13526.47 | 11-JAN-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.38 |
February | 17559.11 | 17-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.76 |
March | 8735.92 | 28-MAR-12:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.12 |
April | 35531.36 | 30-APR-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.36 |
May | 23998.18 | 21-MAY-14:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.86 |
June | 22274.43 | 11-JUN-14:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.07 |
July | 27771.39 | 30-JUL-13:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.29 |
August | 35895.66 | 20-AUG-13:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.73 |
September | 35391.43 | 24-SEP-15:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.09 |
October | 34221.14 | 01-OCT-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.03 |
November | 17735.96 | 11-NOV-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.21 |
December | 11638.49 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8735.92 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.72 | |
Maximum of Months | 35895.66 | 1923.15 | 1040.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3423.66 | 19-JAN-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6346.06 | 27-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6770.28 | 23-MAR-16:50 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 |
April | 26773.52 | 30-APR-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.09 |
May | 29276.84 | 21-MAY-17:11 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.39 |
June | 30542.35 | 25-JUN-17:31 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.53 |
July | 30716.06 | 09-JUL-17:21 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.16 |
August | 29121.36 | 13-AUG-17:01 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.54 |
September | 23305.71 | 24-SEP-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.43 |
October | 9412.41 | 03-OCT-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.21 |
November | 3553.91 | 10-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.60 |
December | 2530.91 | 21-DEC-14:40 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2530.91 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30716.06 | 1295.83 | 670.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5411.44 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4568.61 | 25-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 |
March | 4715.14 | 31-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.86 |
April | 7436.77 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.80 |
May | 7918.69 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.71 |
June | 7706.42 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.27 |
July | 8386.93 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.69 |
August | 9095.02 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 |
September | 7064.23 | 11-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7334.24 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5536.47 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.43 |
December | 4140.01 | 26-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4140.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9095.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7155.36 | 09-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6237.94 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.55 |
March | 6163.97 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.51 |
April | 5694.17 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5432.70 | 25-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.37 |
June | 5262.98 | 24-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 |
July | 5376.44 | 24-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.98 |
August | 5210.89 | 26-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 |
September | 5449.52 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.78 |
October | 4540.99 | 07-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.56 |
November | 7149.26 | 17-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.83 |
December | 7886.87 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4540.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7886.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 776.78 | 15-JAN-13:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.18 |
February | 1172.78 | 22-FEB-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.99 |
March | 3182.07 | 25-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 |
April | 14215.81 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 |
May | 14721.48 | 22-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.35 |
June | 17038.62 | 13-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
July | 16697.15 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 0.00 |
August | 14676.91 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 |
September | 12600.99 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.95 |
October | 5478.94 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.97 |
November | 1063.28 | 11-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1122.97 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17038.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 1122.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2052.51 | 19-JAN-16:20 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4272.03 | 27-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7023.10 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8375.49 | 30-APR-18:02 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3366.02 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5204.20 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7263.26 | 31-JUL-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8236.01 | 13-AUG-18:10 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3225.08 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5076.03 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5839.82 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7538.18 | 18-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2052.51 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8375.49 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1799.87 | 19-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3863.98 | 27-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6248.32 | 31-MAR-23:40 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7957.59 | 30-APR-18:05 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3039.87 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4685.93 | 30-JUN-23:40 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6794.89 | 31-JUL-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7661.85 | 13-AUG-18:10 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2810.79 | 30-SEP-23:30 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4302.71 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5398.47 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6864.66 | 21-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1799.87 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7957.59 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1698.28 | 19-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3682.76 | 17-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5782.98 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8064.92 | 30-APR-17:53 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2886.83 | 31-MAY-23:20 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4432.96 | 30-JUN-23:20 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6634.88 | 31-JUL-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7734.93 | 13-AUG-18:10 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2257.29 | 30-SEP-23:10 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3899.74 | 03-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5307.51 | 10-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6645.37 | 21-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1698.28 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8064.92 | 222.14 | 450.11 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91808.43 | 19-JAN-17:00 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183340.99 | 09-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358782.01 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368215.02 | 28-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176060.12 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267408.23 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360204.63 | 31-JUL-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368588.02 | 28-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175562.09 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267526.75 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275983.47 | 15-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367427.84 | 26-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91808.43 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368588.02 | 9617.36 | 10941.12 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.151485E+13 | 1031635.70 | 03-JAN-08:09 | 0.360605E+12 | 788311.68 | 10-JAN-07:00 |
February | 0.171250E+13 | 1135015.96 | 14-FEB-08:09 | 0.257871E+12 | 672124.08 | 17-FEB-07:10 |
March | 0.232697E+13 | 1274273.02 | 27-MAR-07:10 | 0.210610E+12 | 480636.56 | 27-MAR-06:10 |
April | 0.261922E+13 | 1663848.03 | 28-APR-15:00 | 0.839258E+11 | 345686.79 | 08-APR-06:10 |
May | 0.152018E+13 | 1271505.89 | 22-MAY-15:09 | 0.760706E+11 | 325346.89 | 05-MAY-05:10 |
June | 0.184842E+13 | 1539634.87 | 13-JUN-15:30 | 0.662271E+11 | 81429.43 | 01-JUN-11:00 |
July | 0.227627E+13 | 1663177.90 | 21-JUL-15:20 | 0.635615E+11 | 80388.76 | 06-JUL-11:39 |
August | 0.280339E+13 | 1787637.09 | 14-AUG-15:39 | 0.672103E+11 | 79973.86 | 01-AUG-11:39 |
September | 0.149828E+13 | 1288667.86 | 27-SEP-15:50 | 0.642311E+11 | 147143.52 | 21-SEP-06:10 |
October | 0.183967E+13 | 1267482.37 | 06-OCT-15:20 | 0.108639E+12 | 358763.06 | 28-OCT-05:10 |
November | 0.218297E+13 | 1303913.76 | 16-NOV-16:00 | 0.215975E+12 | 601265.59 | 29-NOV-07:10 |
December | 0.266588E+13 | 1464749.74 | 29-DEC-08:09 | 0.394692E+12 | 738469.96 | 26-DEC-05:19 |
Annual Sum or Average | 0.248086E+14 | 0.196962E+13 | ||||
Minimum of Months | 0.149828E+13 | 1031635.70 | 0.635615E+11 | 79973.86 | ||
Maximum of Months | 0.280339E+13 | 1787637.09 | 0.394692E+12 | 788311.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.277740E+12 | 0.444933E+11 | 0.766053E+12 | 0.162152E+12 | 0.167251E+12 | 0.916953E+10 | 0.00 | 0.105196E+11 | 0.165770E+10 | 0.758135E+11 | 0.00 | 0.00 | 0.00 |
February | 0.246896E+12 | 0.345613E+11 | 0.978954E+12 | 0.146465E+12 | 0.153342E+12 | 0.827474E+10 | 0.00 | 0.237850E+11 | 0.369605E+10 | 0.116523E+12 | 0.00 | 0.00 | 0.00 |
March | 0.290107E+12 | 0.308164E+11 | 0.141687E+13 | 0.162322E+12 | 0.172495E+12 | 0.962173E+10 | 0.00 | 0.415311E+11 | 0.723340E+10 | 0.195968E+12 | 0.00 | 0.00 | 0.00 |
April | 0.255772E+12 | 0.230363E+11 | 0.165903E+13 | 0.156902E+12 | 0.195448E+12 | 0.127873E+11 | 0.00 | 0.775282E+11 | 0.223386E+11 | 0.216383E+12 | 0.00 | 0.00 | 0.00 |
May | 0.274981E+12 | 0.191640E+11 | 0.774844E+12 | 0.162234E+12 | 0.199786E+12 | 0.134437E+11 | 0.00 | 0.258560E+11 | 0.101783E+11 | 0.396943E+11 | 0.00 | 0.00 | 0.00 |
June | 0.273356E+12 | 0.165920E+11 | 0.106252E+13 | 0.157063E+12 | 0.211459E+12 | 0.200010E+11 | 0.00 | 0.662000E+11 | 0.281049E+11 | 0.131246E+11 | 0.00 | 0.00 | 0.00 |
July | 0.255213E+12 | 0.178410E+11 | 0.139340E+13 | 0.162072E+12 | 0.222128E+12 | 0.283121E+11 | 0.00 | 0.128613E+12 | 0.585917E+11 | 0.100935E+11 | 0.00 | 0.00 | 0.00 |
August | 0.286435E+12 | 0.214285E+11 | 0.173200E+13 | 0.162321E+12 | 0.235006E+12 | 0.319662E+11 | 0.00 | 0.226030E+12 | 0.935326E+11 | 0.146702E+11 | 0.00 | 0.00 | 0.00 |
September | 0.256885E+12 | 0.266429E+11 | 0.740713E+12 | 0.156901E+12 | 0.205787E+12 | 0.227069E+11 | 0.00 | 0.491964E+11 | 0.247814E+11 | 0.146615E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271708E+12 | 0.350556E+11 | 0.108340E+13 | 0.162150E+12 | 0.180099E+12 | 0.110061E+11 | 0.00 | 0.295887E+11 | 0.767833E+10 | 0.589820E+11 | 0.00 | 0.00 | 0.00 |
November | 0.274809E+12 | 0.409293E+11 | 0.135889E+13 | 0.156971E+12 | 0.163745E+12 | 0.939714E+10 | 0.00 | 0.383124E+11 | 0.719027E+10 | 0.132721E+12 | 0.00 | 0.00 | 0.00 |
December | 0.272667E+12 | 0.463809E+11 | 0.170972E+13 | 0.162078E+12 | 0.165606E+12 | 0.992430E+10 | 0.00 | 0.523388E+11 | 0.784751E+10 | 0.239321E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323657E+13 | 0.356942E+12 | 0.146764E+14 | 0.190963E+13 | 0.227215E+13 | 0.186611E+12 | 0.00 | 0.769500E+12 | 0.272831E+12 | 0.112796E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.246896E+12 | 0.165920E+11 | 0.740713E+12 | 0.146465E+12 | 0.153342E+12 | 0.827474E+10 | 0.00 | 0.105196E+11 | 0.165770E+10 | 0.100935E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.290107E+12 | 0.463809E+11 | 0.173200E+13 | 0.162322E+12 | 0.235006E+12 | 0.319662E+11 | 0.00 | 0.226030E+12 | 0.935326E+11 | 0.239321E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.291682E+12 | 0.00 | 0.689227E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.195052E+12 | 0.00 | 0.628184E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.138354E+12 | 0.00 | 0.722559E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.180368E+11 | 0.00 | 0.658890E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.770050E+10 | 0.00 | 0.683701E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.227409E+09 | 0.00 | 0.659997E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 76479801.55 | 0.00 | 0.634850E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 31603278.86 | 0.00 | 0.671787E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.171839E+10 | 0.00 | 0.625127E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.431715E+11 | 0.00 | 0.654679E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150785E+12 | 0.00 | 0.651895E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.327822E+12 | 0.00 | 0.668699E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117466E+13 | 0.00 | 0.794960E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 31603278.86 | 0.00 | 0.625127E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.327822E+12 | 0.00 | 0.722559E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 116932.81 | 02-JAN-08:20 | 111602.45 | 20-JAN-11:00 | 3705.47 | 02-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 116932.81 | 01-FEB-08:20 | 118210.01 | 17-FEB-14:00 | 3517.94 | 16-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 314611.94 | 15-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 116926.86 | 15-MAR-07:19 | 113582.92 | 23-MAR-15:00 | 18879.27 | 27-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 305776.82 | 10-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 116922.13 | 10-APR-07:19 | 239749.81 | 28-APR-14:50 | 21726.69 | 28-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 283720.93 | 04-MAY-07:10 | 27558.46 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 116910.36 | 04-MAY-07:19 | 203816.31 | 23-MAY-15:20 | 36493.02 | 22-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 281231.72 | 14-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 116909.03 | 14-JUN-07:19 | 238587.20 | 13-JUN-15:20 | 40043.65 | 12-JUN-14:20 | 0.00 | 01-JUN-00:10 |
July | 283655.84 | 07-JUL-07:10 | 27558.46 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 116910.32 | 07-JUL-07:19 | 238383.51 | 21-JUL-15:20 | 37843.22 | 22-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 297349.23 | 22-AUG-07:30 | 40855.88 | 14-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 116917.63 | 22-AUG-07:40 | 232898.50 | 14-AUG-15:09 | 37524.50 | 28-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 297530.49 | 08-SEP-07:30 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 116917.73 | 08-SEP-07:40 | 236832.67 | 12-SEP-15:09 | 39680.12 | 12-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 16-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 116932.81 | 16-OCT-07:19 | 172950.90 | 03-OCT-14:00 | 18895.52 | 06-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 116932.81 | 01-NOV-07:19 | 115453.42 | 03-NOV-13:09 | 18919.76 | 20-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-08:09 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 116932.81 | 01-DEC-08:20 | 97220.76 | 21-DEC-14:09 | 18965.46 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 281231.72 | 27558.46 | 423497.50 | 116909.03 | 97220.76 | 3517.94 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 116932.81 | 239749.81 | 40043.65 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 6860.76 | 19-JAN-16:30 | 1777.06 | 29-JAN-05:00 | 60391.93 | 10-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 13314.11 | 17-FEB-16:00 | 2840.42 | 07-FEB-14:00 | 100000.00 | 20-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 21292.60 | 31-MAR-23:30 | 5740.22 | 25-MAR-12:00 | 100000.00 | 03-MAR-22:10 | 0.00 | 0.00 | 0.00 |
April | 205317.59 | 30-APR-15:39 | 51372.18 | 28-APR-14:00 | 100000.00 | 01-APR-04:30 | 0.00 | 0.00 | 0.00 |
May | 192236.56 | 22-MAY-14:20 | 78014.96 | 22-MAY-14:09 | 94025.09 | 21-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 290227.34 | 13-JUN-15:00 | 78014.96 | 12-JUN-12:50 | 100000.00 | 08-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 314070.01 | 21-JUL-15:39 | 78014.96 | 10-JUL-09:09 | 100000.00 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 326043.42 | 14-AUG-15:00 | 78014.96 | 14-AUG-10:30 | 100000.00 | 14-AUG-16:49 | 0.00 | 0.00 | 0.00 |
September | 171334.48 | 13-SEP-13:30 | 78014.96 | 11-SEP-14:09 | 68644.88 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 56592.17 | 07-OCT-14:00 | 49419.16 | 07-OCT-14:00 | 100000.00 | 07-OCT-16:19 | 0.00 | 0.00 | 0.00 |
November | 32849.93 | 24-NOV-11:00 | 25304.36 | 24-NOV-11:00 | 100000.00 | 19-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 30441.38 | 23-DEC-10:00 | 8638.49 | 23-DEC-10:00 | 100000.00 | 03-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6860.76 | 1777.06 | 60391.93 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 326043.42 | 78014.96 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1031635.70 | 03-JAN-08:09 | 325713.14 | 423497.50 | 40855.88 | 116818.00 | 77405.19 | 3456.85 | 0.00 | 2394.04 | 266.76 |
February | 1135015.96 | 14-FEB-08:09 | 325713.14 | 541788.89 | 0.00 | 116818.00 | 77435.55 | 3441.70 | 0.00 | 9202.35 | 1242.34 |
March | 1274273.02 | 27-MAR-07:10 | 298743.35 | 660080.29 | 0.00 | 116813.90 | 78631.09 | 3442.90 | 0.00 | 14613.82 | 1947.68 |
April | 1663848.03 | 28-APR-15:00 | 280450.63 | 778371.69 | 0.00 | 82865.22 | 209952.17 | 19248.07 | 0.00 | 182841.95 | 50644.82 |
May | 1271505.89 | 22-MAY-15:09 | 280450.63 | 423497.50 | 0.00 | 82865.22 | 199013.41 | 36109.92 | 0.00 | 171554.24 | 78014.96 |
June | 1539634.87 | 13-JUN-15:30 | 280450.63 | 541788.89 | 0.00 | 82865.22 | 238272.79 | 36375.36 | 0.00 | 281867.02 | 78014.96 |
July | 1663177.90 | 21-JUL-15:20 | 280450.63 | 660080.29 | 0.00 | 82865.22 | 238383.51 | 36968.14 | 0.00 | 312331.97 | 52098.14 |
August | 1787637.09 | 14-AUG-15:39 | 280450.63 | 778371.69 | 0.00 | 82865.22 | 229929.40 | 36555.01 | 0.00 | 323763.24 | 55701.90 |
September | 1288667.86 | 27-SEP-15:50 | 280450.63 | 423497.50 | 0.00 | 82865.22 | 193095.17 | 34902.75 | 0.00 | 161674.56 | 52435.43 |
October | 1267482.37 | 06-OCT-15:20 | 280450.63 | 541788.89 | 0.00 | 82865.22 | 163174.43 | 18895.52 | 0.00 | 53236.40 | 27071.28 |
November | 1303913.76 | 16-NOV-16:00 | 325713.14 | 660080.29 | 40855.88 | 82889.42 | 91239.58 | 18810.60 | 0.00 | 16822.24 | 3002.88 |
December | 1464749.74 | 29-DEC-08:09 | 325713.14 | 778371.69 | 40855.88 | 116818.00 | 77702.90 | 3453.79 | 0.00 | 19388.20 | 2446.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1031635.70 | 280450.63 | 423497.50 | 0.00 | 82865.22 | 77405.19 | 3441.70 | 0.00 | 2394.04 | 266.76 | |
Maximum of Months | 1787637.09 | 325713.14 | 778371.69 | 40855.88 | 116818.00 | 238383.51 | 36968.14 | 0.00 | 323763.24 | 78014.96 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 774183.98 | 02-JAN-06:10 | 0.00 | 83685.02 | 30-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 640984.47 | 17-FEB-07:10 | 0.00 | 83767.11 | 09-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 449518.55 | 27-MAR-06:10 | 0.00 | 83719.08 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 316342.23 | 08-APR-06:10 | 0.00 | 83174.64 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 318066.01 | 05-MAY-05:10 | 0.00 | 82417.91 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 34299.63 | 08-JUN-05:10 | 0.00 | 81429.43 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 15672.41 | 31-JUL-05:10 | 0.00 | 80388.76 | 06-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 3049.57 | 23-AUG-05:19 | 0.00 | 79973.86 | 01-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 116515.21 | 21-SEP-06:10 | 0.00 | 80484.84 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 330364.01 | 28-OCT-05:10 | 0.00 | 81259.48 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 572662.16 | 27-NOV-05:19 | 0.00 | 82378.34 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 731189.08 | 26-DEC-05:19 | 0.00 | 83217.47 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 3049.57 | 0.00 | 79973.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 774183.98 | 0.00 | 83767.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.96 | 2.67 | 27.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.76 | 0.00 | 25.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.84 | 0.00 | 25.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.62 | 0.00 | 26.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.91 | 0.00 | 26.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.07 | 0.00 | 27.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.58 | 0.00 | 26.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.08 | 0.17 | 26.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.61 | 0.17 | 26.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.70 | 1.17 | 26.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.24 | 0.00 | 26.24 |
Annual Sum or Average | 0.00 | 0.00 | 32.33 | 26.68 | 4.17 | 26.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.07 | 2.67 | 27.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
February | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
December | 1.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Annual Sum or Average | 2.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.32 | 1.33 | 28.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.98 | 2.17 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.06 | 3.00 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.03 | 5.33 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.00 | 3.83 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.85 | 4.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.17 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.83 | 28.00 | 19.83 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.32 | 5.33 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.83 | 27.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.81 | 0.83 | 27.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.23 | 2.50 | 28.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.58 | 1.33 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.56 | 2.33 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 4.67 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.09 | 5.83 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.07 | 6.17 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.99 | 1.50 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.83 | 1.33 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 27.67 | 27.95 | 27.50 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.23 | 6.17 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.29 | 2.50 | 28.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.18 | 3.00 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.44 | 3.00 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.14 | 5.00 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.76 | 5.17 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.08 | 3.33 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.87 | 0.50 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 45.00 | 28.07 | 23.33 | 28.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.44 | 5.17 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 2.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Annual Sum or Average | 4.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.40 | 1.33 | 28.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.00 | 1.83 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.99 | 3.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.17 | 4.67 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.02 | 3.67 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.70 | 3.67 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
December | 1.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 3.17 | 19.22 | 0.00 | 19.22 | 18.33 | 26.72 | 18.33 | 27.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.43 | 0.00 | 19.43 | 4.67 | 28.40 | 4.67 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.29 | 0.00 | 19.29 | 0.67 | 26.14 | 0.67 | 26.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.95 | 0.83 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.55 | 1.67 | 28.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.69 | 0.83 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.47 | 1.67 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.84 | 3.83 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.07 | 5.67 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.25 | 6.17 | 28.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.16 | 1.50 | 28.16 |
November | 0.17 | 19.41 | 0.00 | 19.41 | 1.00 | 26.72 | 1.00 | 27.29 |
December | 1.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 1.33 | 19.31 | 0.00 | 19.31 | 24.17 | 27.60 | 23.83 | 27.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.41 | 0.00 | 19.41 | 6.17 | 28.55 | 6.17 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.67 | 1.00 | 28.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.16 | 2.00 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.45 | 1.50 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.50 | 3.00 | 28.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.36 | 2.50 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.82 | 2.17 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 1.50 | 19.31 | 0.00 | 19.31 | 22.67 | 27.79 | 12.17 | 27.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.35 | 0.00 | 19.35 | 6.50 | 28.67 | 3.00 | 28.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.83 | 18.82 | 4.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 9.33 | 18.94 | 2.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 3.50 | 19.17 | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 9.17 | 18.97 | 2.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 21.67 | 18.15 | 6.17 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
Annual Sum or Average | 59.17 | 18.65 | 15.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.67 | 19.36 | 6.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
February | 5.00 | 18.67 | 0.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
March | 2.33 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.18 | 1.33 | 28.18 |
May | 0.17 | 19.21 | 0.00 | 19.21 | 1.17 | 26.71 | 1.17 | 27.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 3.33 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.13 | 4.17 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.88 | 2.83 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.49 | 1.50 | 27.49 |
October | 0.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
November | 3.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
December | 10.17 | 17.07 | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Annual Sum or Average | 27.83 | 18.00 | 0.33 | 17.97 | 14.33 | 21.32 | 14.33 | 22.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 0.00 | 17.04 |
Maximum of Months | 10.17 | 19.21 | 0.17 | 19.21 | 4.17 | 28.18 | 4.17 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
February | 3.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
March | 1.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.66 | 1.67 | 28.71 |
May | 0.17 | 19.26 | 0.00 | 19.26 | 0.50 | 25.45 | 0.50 | 26.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.80 | 3.50 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.07 | 5.00 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.15 | 5.00 | 28.15 |
October | 0.67 | 19.39 | 0.00 | 19.39 | 1.17 | 24.76 | 1.17 | 25.95 |
November | 2.67 | 18.81 | 0.00 | 18.81 | 0.33 | 19.80 | 0.33 | 20.58 |
December | 6.50 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
Annual Sum or Average | 19.83 | 18.61 | 0.00 | 18.61 | 18.83 | 23.19 | 18.67 | 24.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 0.00 | 18.30 |
Maximum of Months | 6.50 | 19.39 | 0.00 | 19.39 | 5.00 | 28.66 | 5.00 | 28.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
February | 2.83 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.83 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.60 | 1.17 | 28.63 |
May | 0.17 | 19.37 | 0.00 | 19.37 | 3.17 | 27.74 | 1.67 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.47 | 1.50 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.47 | 3.17 | 28.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.34 | 2.67 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.95 | 1.50 | 27.95 |
October | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
November | 2.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 5.33 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 15.83 | 18.61 | 0.00 | 18.61 | 21.33 | 24.22 | 11.67 | 25.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 0.00 | 18.25 |
Maximum of Months | 5.33 | 19.43 | 0.00 | 19.43 | 6.67 | 28.60 | 3.17 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.50 | 2.00 | 28.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 28.50 | 2.00 | 28.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.50 | 2.00 | 28.50 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.67 | 23.96 | 99.83 | 25.07 | 0.00 | 25.07 |
February | 42.67 | 23.99 | 86.33 | 25.35 | 0.00 | 25.35 |
March | 30.50 | 24.01 | 85.83 | 25.47 | 0.00 | 25.47 |
April | 0.67 | 24.00 | 102.83 | 26.28 | 0.00 | 26.28 |
May | 1.50 | 24.00 | 174.33 | 25.29 | 0.00 | 25.29 |
June | 0.00 | 0.00 | 310.67 | 24.69 | 0.00 | 24.69 |
July | 0.00 | 0.00 | 419.83 | 24.69 | 0.00 | 24.69 |
August | 0.00 | 0.00 | 430.67 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 308.17 | 24.79 | 0.00 | 24.79 |
October | 0.83 | 24.00 | 190.67 | 25.37 | 0.00 | 25.37 |
November | 6.67 | 24.00 | 161.50 | 25.51 | 0.00 | 25.51 |
December | 27.33 | 24.00 | 103.83 | 25.70 | 0.00 | 25.70 |
Annual Sum or Average | 193.83 | 23.98 | 2474.50 | 25.02 | 0.00 | 25.02 |
Minimum of Months | 0.00 | 0.00 | 85.83 | 24.55 | 0.00 | 24.55 |
Maximum of Months | 83.67 | 24.01 | 430.67 | 26.28 | 0.00 | 26.28 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 185.33 | 23.91 | 53.00 | 24.26 | 12.50 | 24.36 |
February | 101.33 | 23.82 | 50.83 | 24.38 | 0.00 | 24.38 |
March | 40.17 | 23.90 | 77.83 | 25.13 | 0.00 | 25.13 |
April | 3.50 | 23.94 | 98.17 | 25.56 | 0.00 | 25.56 |
May | 14.50 | 23.78 | 156.67 | 24.68 | 0.00 | 24.68 |
June | 0.00 | 0.00 | 344.83 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 429.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 457.67 | 24.31 | 0.00 | 24.31 |
September | 0.67 | 23.77 | 298.83 | 24.39 | 0.00 | 24.39 |
October | 15.50 | 23.77 | 200.67 | 24.85 | 0.00 | 24.85 |
November | 35.00 | 23.89 | 151.17 | 24.92 | 0.00 | 24.92 |
December | 73.83 | 23.87 | 86.83 | 24.85 | 0.00 | 24.85 |
Annual Sum or Average | 469.83 | 23.87 | 2405.50 | 24.54 | 12.50 | 24.55 |
Minimum of Months | 0.00 | 0.00 | 50.83 | 24.26 | 0.00 | 24.31 |
Maximum of Months | 185.33 | 23.94 | 457.67 | 25.56 | 12.50 | 25.56 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 433.67 | 23.09 | 12.00 | 23.05 | 12.00 | 23.02 |
February | 377.83 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
March | 390.17 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
April | 190.50 | 23.66 | 19.17 | 23.80 | 0.00 | 23.80 |
May | 159.67 | 23.50 | 63.67 | 23.79 | 0.00 | 23.79 |
June | 45.17 | 23.54 | 212.17 | 24.21 | 0.00 | 24.21 |
July | 38.67 | 23.45 | 264.50 | 24.19 | 0.00 | 24.19 |
August | 12.00 | 23.51 | 275.83 | 24.22 | 0.00 | 24.22 |
September | 83.50 | 23.50 | 155.83 | 24.06 | 0.00 | 24.06 |
October | 232.17 | 23.43 | 25.33 | 23.52 | 0.00 | 23.52 |
November | 359.00 | 23.33 | 2.50 | 23.34 | 0.00 | 23.34 |
December | 477.50 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
Annual Sum or Average | 2799.83 | 23.29 | 1031.00 | 23.57 | 12.00 | 23.56 |
Minimum of Months | 12.00 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 477.50 | 23.66 | 275.83 | 24.22 | 12.00 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.00 | 21.50 | 112.67 | 21.22 | 112.67 | 21.02 |
February | 454.00 | 21.76 | 74.67 | 21.50 | 74.67 | 21.31 |
March | 511.67 | 22.27 | 26.17 | 22.18 | 26.17 | 22.10 |
April | 350.50 | 23.09 | 1.17 | 23.09 | 0.00 | 23.09 |
May | 305.00 | 23.07 | 46.17 | 23.21 | 0.00 | 23.21 |
June | 146.50 | 23.24 | 174.33 | 23.74 | 0.00 | 23.74 |
July | 135.83 | 23.19 | 234.67 | 23.84 | 0.00 | 23.84 |
August | 126.83 | 23.29 | 222.50 | 23.84 | 0.00 | 23.84 |
September | 240.83 | 23.00 | 91.33 | 23.30 | 0.00 | 23.30 |
October | 451.17 | 22.45 | 2.50 | 22.44 | 2.50 | 22.43 |
November | 480.33 | 21.91 | 61.00 | 21.73 | 61.00 | 21.59 |
December | 497.00 | 21.34 | 124.83 | 21.03 | 124.83 | 20.82 |
Annual Sum or Average | 4200.67 | 22.25 | 1172.00 | 22.36 | 401.83 | 22.19 |
Minimum of Months | 126.83 | 21.34 | 1.17 | 21.03 | 0.00 | 20.82 |
Maximum of Months | 511.67 | 23.29 | 234.67 | 23.84 | 124.83 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 22.35 | 17.50 | 22.31 | 17.50 | 22.26 |
February | 441.83 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
March | 452.50 | 23.15 | 4.50 | 23.17 | 0.00 | 23.17 |
April | 225.00 | 23.52 | 16.67 | 23.62 | 0.00 | 23.62 |
May | 211.33 | 23.42 | 61.67 | 23.62 | 0.00 | 23.62 |
June | 47.50 | 23.64 | 260.83 | 24.15 | 0.00 | 24.15 |
July | 8.33 | 23.67 | 358.83 | 24.30 | 0.00 | 24.30 |
August | 23.50 | 23.61 | 344.17 | 24.18 | 0.00 | 24.18 |
September | 176.83 | 23.34 | 119.00 | 23.69 | 0.00 | 23.69 |
October | 349.67 | 23.13 | 18.83 | 23.21 | 0.00 | 23.21 |
November | 434.00 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
December | 497.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
Annual Sum or Average | 3365.33 | 22.91 | 1202.00 | 23.26 | 17.50 | 23.25 |
Minimum of Months | 8.33 | 22.35 | 0.00 | 22.31 | 0.00 | 22.26 |
Maximum of Months | 497.83 | 23.67 | 358.83 | 24.30 | 17.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.17 | 21.95 | 24.00 | 21.94 | 20.33 | 21.90 |
February | 427.50 | 22.10 | 5.17 | 22.13 | 1.00 | 22.12 |
March | 470.67 | 22.45 | 2.33 | 22.46 | 0.00 | 22.46 |
April | 205.50 | 23.10 | 107.17 | 23.58 | 4.83 | 23.63 |
May | 189.33 | 23.12 | 175.17 | 23.79 | 6.33 | 23.85 |
June | 112.67 | 23.61 | 299.17 | 24.12 | 12.33 | 24.20 |
July | 79.00 | 24.23 | 345.83 | 24.39 | 22.00 | 24.52 |
August | 98.50 | 23.71 | 335.50 | 24.16 | 15.50 | 24.25 |
September | 177.67 | 23.31 | 239.83 | 23.95 | 14.50 | 24.05 |
October | 365.67 | 22.57 | 51.67 | 22.81 | 0.33 | 22.81 |
November | 472.83 | 22.28 | 1.83 | 22.29 | 0.00 | 22.29 |
December | 494.33 | 21.78 | 12.17 | 21.76 | 12.17 | 21.74 |
Annual Sum or Average | 3580.83 | 22.46 | 1599.83 | 23.04 | 109.33 | 23.08 |
Minimum of Months | 79.00 | 21.78 | 1.83 | 21.76 | 0.00 | 21.74 |
Maximum of Months | 494.33 | 24.23 | 345.83 | 24.39 | 22.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.83 | 21.93 | 73.67 | 22.19 | 24.00 | 22.16 |
February | 346.50 | 22.13 | 64.33 | 22.47 | 6.67 | 22.47 |
March | 420.50 | 22.44 | 10.33 | 22.49 | 0.00 | 22.49 |
April | 203.33 | 23.22 | 156.17 | 23.74 | 7.50 | 23.81 |
May | 230.17 | 22.92 | 152.17 | 23.52 | 2.67 | 23.55 |
June | 127.50 | 23.41 | 268.67 | 23.99 | 8.67 | 24.05 |
July | 91.50 | 24.02 | 330.50 | 24.31 | 20.17 | 24.43 |
August | 89.50 | 24.23 | 367.17 | 24.33 | 24.83 | 24.47 |
September | 162.50 | 23.57 | 266.00 | 24.12 | 24.00 | 24.28 |
October | 319.33 | 22.69 | 123.50 | 23.17 | 5.50 | 23.21 |
November | 396.83 | 22.36 | 48.00 | 22.62 | 3.67 | 22.66 |
December | 441.00 | 21.83 | 48.33 | 21.95 | 20.17 | 21.90 |
Annual Sum or Average | 3239.50 | 22.54 | 1908.83 | 23.21 | 147.83 | 23.26 |
Minimum of Months | 89.50 | 21.83 | 10.33 | 21.95 | 0.00 | 21.90 |
Maximum of Months | 441.00 | 24.23 | 367.17 | 24.33 | 24.83 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.00 | 22.44 | 15.17 | 22.50 | 1.50 | 22.50 |
February | 327.17 | 22.97 | 45.50 | 23.17 | 0.33 | 23.17 |
March | 206.67 | 23.29 | 64.17 | 23.78 | 0.00 | 23.78 |
April | 26.33 | 24.81 | 289.33 | 24.84 | 9.33 | 24.91 |
May | 122.00 | 23.51 | 220.50 | 24.17 | 12.33 | 24.27 |
June | 24.33 | 25.96 | 432.33 | 24.54 | 18.83 | 24.62 |
July | 28.00 | 26.80 | 481.50 | 24.70 | 27.00 | 24.81 |
August | 24.17 | 27.12 | 505.83 | 24.62 | 24.17 | 24.73 |
September | 101.17 | 23.67 | 284.00 | 24.22 | 14.83 | 24.32 |
October | 188.50 | 23.17 | 151.67 | 23.89 | 2.33 | 23.91 |
November | 229.17 | 23.20 | 95.00 | 23.69 | 0.00 | 23.69 |
December | 304.00 | 23.24 | 27.00 | 23.43 | 0.00 | 23.43 |
Annual Sum or Average | 2031.50 | 23.20 | 2612.00 | 23.99 | 110.67 | 24.05 |
Minimum of Months | 24.17 | 22.44 | 15.17 | 22.50 | 0.00 | 22.50 |
Maximum of Months | 450.00 | 27.12 | 505.83 | 24.84 | 27.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.88 | 230.67 | 20.70 | 230.67 | 20.61 |
February | 454.00 | 21.00 | 154.67 | 20.81 | 154.67 | 20.70 |
March | 514.00 | 21.64 | 62.33 | 21.53 | 62.33 | 21.45 |
April | 415.50 | 22.68 | 6.50 | 22.65 | 5.83 | 22.62 |
May | 387.17 | 22.81 | 27.33 | 22.89 | 0.00 | 22.89 |
June | 171.50 | 23.15 | 136.33 | 23.59 | 0.00 | 23.59 |
July | 152.50 | 23.23 | 205.50 | 23.75 | 0.00 | 23.75 |
August | 186.17 | 23.15 | 163.33 | 23.55 | 0.00 | 23.55 |
September | 332.50 | 22.76 | 50.67 | 22.92 | 0.00 | 22.92 |
October | 496.17 | 21.96 | 16.33 | 21.91 | 16.33 | 21.86 |
November | 489.00 | 21.16 | 113.83 | 20.99 | 113.83 | 20.88 |
December | 497.00 | 20.58 | 271.00 | 20.43 | 271.00 | 20.35 |
Annual Sum or Average | 4597.50 | 21.81 | 1438.50 | 21.81 | 854.67 | 21.62 |
Minimum of Months | 152.50 | 20.58 | 6.50 | 20.43 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.23 | 271.00 | 23.75 | 271.00 | 23.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.87 | 182.33 | 20.73 | 182.33 | 20.66 |
February | 383.17 | 21.08 | 117.33 | 20.93 | 117.33 | 20.84 |
March | 431.17 | 21.41 | 58.00 | 21.33 | 58.00 | 21.26 |
April | 246.00 | 22.55 | 64.33 | 22.96 | 6.83 | 23.01 |
May | 244.00 | 22.57 | 110.83 | 23.20 | 6.17 | 23.27 |
June | 169.33 | 23.07 | 183.67 | 23.79 | 11.67 | 23.89 |
July | 140.83 | 23.51 | 236.00 | 24.21 | 20.33 | 24.35 |
August | 162.33 | 23.28 | 217.50 | 23.92 | 15.50 | 24.04 |
September | 213.83 | 22.75 | 147.00 | 23.51 | 12.33 | 23.62 |
October | 381.50 | 21.69 | 25.17 | 21.75 | 11.67 | 21.71 |
November | 416.17 | 21.03 | 92.17 | 20.91 | 92.17 | 20.83 |
December | 422.00 | 20.53 | 245.67 | 20.39 | 245.67 | 20.33 |
Annual Sum or Average | 3637.33 | 21.67 | 1680.00 | 22.02 | 780.00 | 21.88 |
Minimum of Months | 140.83 | 20.53 | 25.17 | 20.39 | 6.17 | 20.33 |
Maximum of Months | 431.17 | 23.51 | 245.67 | 24.21 | 245.67 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.17 | 21.43 | 152.50 | 21.49 | 113.50 | 21.36 |
February | 367.17 | 21.57 | 107.67 | 21.79 | 58.17 | 21.68 |
March | 469.17 | 21.77 | 42.50 | 21.71 | 37.83 | 21.64 |
April | 257.67 | 22.60 | 139.50 | 23.27 | 6.83 | 23.33 |
May | 301.67 | 22.49 | 128.67 | 23.06 | 2.50 | 23.09 |
June | 208.83 | 22.86 | 215.67 | 23.57 | 5.00 | 23.61 |
July | 177.50 | 23.22 | 254.00 | 23.92 | 18.17 | 24.03 |
August | 163.83 | 23.44 | 284.33 | 23.99 | 22.67 | 24.14 |
September | 208.50 | 23.14 | 242.50 | 23.86 | 24.67 | 24.03 |
October | 355.83 | 22.03 | 106.50 | 22.53 | 9.67 | 22.57 |
November | 422.50 | 21.52 | 82.67 | 21.67 | 49.67 | 21.61 |
December | 467.50 | 21.05 | 201.50 | 20.91 | 188.00 | 20.78 |
Annual Sum or Average | 3832.33 | 22.01 | 1958.00 | 22.52 | 536.67 | 22.44 |
Minimum of Months | 163.83 | 21.05 | 42.50 | 20.91 | 2.50 | 20.78 |
Maximum of Months | 469.17 | 23.44 | 284.33 | 23.99 | 188.00 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 21.07 | 160.33 | 20.93 | 160.33 | 20.85 |
February | 426.00 | 21.23 | 87.67 | 21.13 | 83.00 | 21.04 |
March | 499.17 | 21.58 | 32.33 | 21.54 | 29.17 | 21.50 |
April | 334.17 | 22.65 | 76.33 | 22.97 | 6.17 | 23.03 |
May | 328.67 | 22.64 | 122.50 | 23.11 | 8.00 | 23.18 |
June | 179.00 | 23.07 | 237.83 | 23.78 | 10.00 | 23.85 |
July | 145.17 | 23.26 | 301.00 | 24.02 | 15.67 | 24.12 |
August | 148.33 | 23.23 | 272.33 | 23.90 | 14.00 | 24.00 |
September | 286.83 | 22.65 | 139.83 | 23.22 | 9.00 | 23.29 |
October | 449.67 | 21.82 | 32.17 | 21.92 | 6.17 | 21.90 |
November | 482.17 | 21.22 | 71.00 | 21.12 | 71.00 | 21.03 |
December | 497.00 | 20.74 | 223.50 | 20.61 | 223.50 | 20.54 |
Annual Sum or Average | 4274.67 | 21.79 | 1756.83 | 22.16 | 636.00 | 22.05 |
Minimum of Months | 145.17 | 20.74 | 32.17 | 20.61 | 6.17 | 20.54 |
Maximum of Months | 499.17 | 23.26 | 301.00 | 24.02 | 223.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.24 | 361.17 | 20.09 | 361.17 | 20.03 |
February | 454.00 | 20.31 | 283.67 | 20.13 | 283.67 | 20.04 |
March | 514.00 | 20.92 | 227.00 | 20.74 | 227.00 | 20.65 |
April | 440.17 | 22.08 | 64.00 | 21.89 | 61.83 | 21.74 |
May | 421.50 | 22.19 | 48.83 | 22.22 | 20.33 | 22.15 |
June | 236.67 | 22.72 | 120.50 | 23.18 | 0.00 | 23.18 |
July | 212.00 | 22.80 | 189.83 | 23.43 | 0.17 | 23.43 |
August | 244.67 | 22.76 | 148.17 | 23.23 | 0.00 | 23.23 |
September | 376.67 | 22.22 | 49.00 | 22.31 | 11.33 | 22.25 |
October | 502.00 | 21.12 | 134.00 | 20.88 | 134.00 | 20.72 |
November | 489.00 | 20.44 | 269.67 | 20.23 | 269.67 | 20.13 |
December | 497.00 | 20.03 | 405.00 | 19.93 | 405.00 | 19.89 |
Annual Sum or Average | 4889.67 | 21.25 | 2300.83 | 21.13 | 1774.17 | 20.90 |
Minimum of Months | 212.00 | 20.03 | 48.83 | 19.93 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 22.80 | 405.00 | 23.43 | 405.00 | 23.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 337.67 | 20.20 | 337.67 | 20.13 |
February | 454.00 | 20.55 | 250.00 | 20.35 | 250.00 | 20.25 |
March | 514.00 | 20.96 | 209.33 | 20.80 | 209.33 | 20.72 |
April | 295.83 | 22.23 | 92.67 | 22.52 | 28.00 | 22.45 |
May | 301.83 | 22.27 | 129.33 | 22.80 | 10.83 | 22.79 |
June | 203.67 | 22.74 | 227.00 | 23.57 | 10.50 | 23.65 |
July | 163.17 | 23.13 | 300.17 | 23.99 | 18.50 | 24.11 |
August | 187.67 | 22.96 | 282.83 | 23.75 | 12.00 | 23.83 |
September | 235.83 | 22.24 | 191.00 | 23.15 | 8.00 | 23.16 |
October | 452.83 | 21.16 | 118.00 | 20.99 | 111.83 | 20.85 |
November | 489.00 | 20.52 | 239.83 | 20.32 | 239.83 | 20.22 |
December | 497.00 | 20.10 | 386.33 | 19.98 | 386.33 | 19.93 |
Annual Sum or Average | 4296.83 | 21.22 | 2764.17 | 21.48 | 1622.83 | 21.25 |
Minimum of Months | 163.17 | 20.10 | 92.67 | 19.98 | 8.00 | 19.93 |
Maximum of Months | 514.00 | 23.13 | 386.33 | 23.99 | 386.33 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.17 | 20.79 | 264.67 | 20.65 | 249.17 | 20.52 |
February | 392.33 | 20.96 | 203.17 | 20.90 | 170.83 | 20.72 |
March | 492.67 | 21.19 | 178.17 | 20.99 | 178.17 | 20.87 |
April | 293.50 | 22.15 | 154.00 | 22.61 | 42.50 | 22.52 |
May | 333.67 | 21.97 | 138.17 | 22.49 | 22.50 | 22.41 |
June | 244.83 | 22.42 | 194.17 | 23.22 | 5.67 | 23.26 |
July | 208.67 | 22.74 | 239.00 | 23.62 | 16.67 | 23.73 |
August | 208.67 | 22.98 | 259.33 | 23.71 | 21.33 | 23.86 |
September | 240.33 | 22.55 | 230.33 | 23.42 | 26.00 | 23.53 |
October | 396.67 | 21.45 | 149.50 | 21.71 | 72.50 | 21.58 |
November | 449.67 | 20.93 | 198.00 | 20.81 | 177.67 | 20.66 |
December | 481.00 | 20.47 | 322.67 | 20.29 | 319.00 | 20.19 |
Annual Sum or Average | 4199.17 | 21.49 | 2531.17 | 21.80 | 1302.00 | 21.59 |
Minimum of Months | 208.67 | 20.47 | 138.17 | 20.29 | 5.67 | 20.19 |
Maximum of Months | 492.67 | 22.98 | 322.67 | 23.71 | 319.00 | 23.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 20.54 | 294.33 | 20.36 | 294.33 | 20.28 |
February | 437.50 | 20.77 | 199.67 | 20.56 | 197.67 | 20.44 |
March | 504.17 | 21.09 | 159.33 | 20.96 | 157.00 | 20.87 |
April | 366.50 | 22.16 | 94.67 | 22.41 | 31.17 | 22.37 |
May | 357.17 | 22.13 | 122.83 | 22.64 | 15.83 | 22.66 |
June | 231.17 | 22.67 | 215.33 | 23.45 | 11.00 | 23.53 |
July | 181.33 | 22.79 | 269.50 | 23.73 | 15.00 | 23.83 |
August | 217.50 | 22.88 | 234.00 | 23.59 | 14.50 | 23.70 |
September | 324.67 | 22.18 | 124.33 | 22.73 | 12.67 | 22.76 |
October | 463.83 | 21.26 | 89.83 | 21.24 | 68.83 | 21.12 |
November | 485.17 | 20.73 | 195.50 | 20.54 | 195.50 | 20.43 |
December | 497.00 | 20.28 | 357.17 | 20.16 | 357.17 | 20.10 |
Annual Sum or Average | 4566.50 | 21.37 | 2356.50 | 21.58 | 1370.67 | 21.38 |
Minimum of Months | 181.33 | 20.28 | 89.83 | 20.16 | 11.00 | 20.10 |
Maximum of Months | 504.17 | 22.88 | 357.17 | 23.73 | 357.17 | 23.83 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 7.83 | 27.00 | 454.00 | 27.00 | 7.83 | 27.00 |
March | 3.83 | 27.00 | 514.00 | 27.00 | 3.83 | 27.00 |
April | 86.67 | 27.00 | 485.00 | 27.00 | 86.67 | 27.00 |
May | 13.67 | 27.00 | 508.00 | 27.00 | 13.67 | 27.00 |
June | 73.17 | 27.00 | 496.00 | 27.00 | 73.17 | 27.00 |
July | 188.33 | 27.00 | 497.00 | 27.00 | 188.33 | 27.00 |
August | 329.33 | 27.00 | 514.00 | 27.00 | 329.33 | 27.00 |
September | 24.17 | 27.00 | 485.00 | 27.00 | 24.17 | 27.00 |
October | 13.67 | 27.00 | 502.00 | 27.00 | 13.67 | 27.00 |
November | 5.67 | 27.00 | 489.00 | 27.00 | 5.67 | 27.00 |
December | 0.67 | 27.00 | 497.00 | 27.00 | 0.67 | 27.00 |
Annual Sum or Average | 747.00 | 27.00 | 5943.00 | 27.00 | 747.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 329.33 | 27.00 | 514.00 | 27.00 | 329.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 485.67 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 13.33 | 27.00 | 485.00 | 27.00 | 13.33 | 27.00 |
May | 5.17 | 27.00 | 508.00 | 27.00 | 5.17 | 27.00 |
June | 14.83 | 27.00 | 496.00 | 27.00 | 14.83 | 27.00 |
July | 28.67 | 27.00 | 497.00 | 27.00 | 28.67 | 27.00 |
August | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
September | 6.33 | 27.00 | 485.00 | 27.00 | 6.33 | 27.00 |
October | 1.00 | 27.00 | 502.00 | 27.00 | 1.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 486.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 112.83 | 27.00 | 5916.50 | 27.00 | 112.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.33 | 25.18 | 330.67 | 26.62 | 0.00 | 26.62 |
February | 3.67 | 27.00 | 378.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 483.67 | 27.00 | 0.00 | 27.00 |
April | 17.67 | 27.00 | 485.00 | 27.00 | 17.67 | 27.00 |
May | 9.83 | 27.00 | 508.00 | 27.00 | 9.83 | 27.00 |
June | 31.17 | 27.00 | 496.00 | 27.00 | 31.17 | 27.00 |
July | 57.67 | 27.00 | 497.00 | 27.00 | 57.67 | 27.00 |
August | 62.17 | 27.00 | 514.00 | 27.00 | 62.17 | 27.00 |
September | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
October | 0.67 | 27.00 | 496.33 | 27.00 | 0.67 | 27.00 |
November | 0.00 | 0.00 | 446.33 | 27.00 | 0.00 | 27.00 |
December | 6.17 | 27.00 | 388.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 282.50 | 26.45 | 5508.83 | 26.97 | 187.33 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 330.67 | 26.62 | 0.00 | 26.62 |
Maximum of Months | 85.33 | 27.00 | 514.00 | 27.00 | 62.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.83 | 27.00 | 502.00 | 27.00 | 355.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5796.83 | 27.00 | 5943.00 | 27.00 | 5796.83 | 27.00 |
Minimum of Months | 355.83 | 27.00 | 454.00 | 27.00 | 355.83 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 27.66946 | 0.79427 | 18.41952 |
February | 454.00000 | 27.00000 | 27.94590 | 0.85111 | 20.38054 |
March | 514.00000 | 27.00000 | 27.83269 | 0.89697 | 22.05184 |
April | 485.00000 | 27.00000 | 28.44393 | 0.97986 | 25.34601 |
May | 508.00000 | 27.00015 | 32.80532 | 0.23879 | 6.32534 |
June | 496.00000 | 27.00047 | 35.86404 | 0.34108 | 7.50939 |
July | 497.00000 | 27.00035 | 36.14287 | 0.39946 | 8.40306 |
August | 514.00000 | 27.00016 | 36.33177 | 0.43985 | 9.10624 |
September | 485.00000 | 27.00046 | 36.11310 | 0.26837 | 6.61674 |
October | 502.00000 | 27.00015 | 32.73792 | 0.91783 | 22.84780 |
November | 489.00000 | 27.00007 | 30.58169 | 0.91376 | 22.70495 |
December | 497.00000 | 27.00000 | 26.77487 | 0.89281 | 21.89661 |
Annual Sum or Average | 5943.00000 | 27.00015 | 31.63064 | 0.65926 | 15.91549 |
Minimum of Months | 454.00000 | 27.00000 | 26.77487 | 0.23879 | 6.32534 |
Maximum of Months | 514.00000 | 27.00047 | 36.33177 | 0.97986 | 25.34601 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99855 | 27.69513 | 0.68243 | 14.93537 |
February | 454.00000 | 27.00001 | 27.93073 | 0.72105 | 16.09423 |
March | 514.00000 | 27.00000 | 27.82187 | 0.75032 | 16.95645 |
April | 485.00000 | 27.00000 | 28.43507 | 0.84942 | 20.37317 |
May | 508.00000 | 27.00014 | 32.80889 | 0.14152 | 5.64868 |
June | 496.00000 | 27.00045 | 35.88677 | 0.23432 | 6.30040 |
July | 497.00000 | 27.00037 | 36.15168 | 0.26613 | 6.63958 |
August | 514.00000 | 27.00019 | 36.33408 | 0.28616 | 6.84671 |
September | 485.00000 | 27.00043 | 36.20488 | 0.17521 | 5.82714 |
October | 502.00000 | 27.00014 | 32.74418 | 0.80147 | 18.64675 |
November | 489.00000 | 27.00006 | 30.56400 | 0.75225 | 17.03365 |
December | 497.00000 | 27.00000 | 26.75766 | 0.69182 | 15.17430 |
Annual Sum or Average | 5943.00000 | 27.00003 | 31.63825 | 0.52735 | 12.49747 |
Minimum of Months | 454.00000 | 26.99855 | 26.75766 | 0.14152 | 5.64868 |
Maximum of Months | 514.00000 | 27.00045 | 36.33408 | 0.84942 | 20.37317 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.63620 | 28.45228 | 0.53373 | 11.97131 |
February | 454.00000 | 27.00001 | 27.93911 | 0.64032 | 13.88163 |
March | 514.00000 | 27.00000 | 27.82633 | 0.67858 | 14.85301 |
April | 485.00000 | 27.00000 | 28.43801 | 0.80659 | 19.00981 |
May | 508.00000 | 27.00041 | 32.82260 | 0.09254 | 5.62764 |
June | 496.00000 | 27.00045 | 35.90246 | 0.20930 | 6.23096 |
July | 497.00000 | 27.00037 | 36.16317 | 0.24683 | 6.60382 |
August | 514.00000 | 27.00020 | 36.34462 | 0.26231 | 6.71294 |
September | 485.00000 | 27.00064 | 36.27801 | 0.12775 | 5.70704 |
October | 502.00000 | 27.00013 | 32.78256 | 0.73219 | 16.48356 |
November | 489.00000 | 27.00006 | 30.58490 | 0.67228 | 14.69521 |
December | 497.00000 | 27.00000 | 26.76343 | 0.61052 | 13.02575 |
Annual Sum or Average | 5943.00000 | 26.96946 | 31.71924 | 0.46587 | 11.19812 |
Minimum of Months | 454.00000 | 26.63620 | 26.76343 | 0.09254 | 5.62764 |
Maximum of Months | 514.00000 | 27.00064 | 36.34462 | 0.80659 | 19.00981 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 30.07474 | 1.03982 | 27.83706 |
February | 454.00000 | 27.00041 | 30.01312 | 1.20464 | 35.48191 |
March | 514.00000 | 27.00022 | 29.86685 | 1.35553 | 43.16103 |
April | 485.00000 | 27.00103 | 28.55006 | 1.49723 | 50.75184 |
May | 508.00000 | 26.99998 | 30.98072 | 0.49389 | 10.16591 |
June | 496.00000 | 27.00063 | 35.12502 | 0.76068 | 17.23735 |
July | 497.00000 | 27.00552 | 36.01601 | 0.97970 | 25.31810 |
August | 514.00000 | 27.01950 | 33.88501 | 1.16072 | 33.36841 |
September | 485.00000 | 26.99986 | 34.71646 | 0.55102 | 11.45287 |
October | 502.00000 | 27.00012 | 31.39075 | 1.24418 | 37.44853 |
November | 489.00000 | 27.00016 | 30.49416 | 1.37346 | 44.10815 |
December | 497.00000 | 27.00042 | 28.69005 | 1.47960 | 49.79637 |
Annual Sum or Average | 5943.00000 | 27.00238 | 31.66164 | 1.09411 | 32.13905 |
Minimum of Months | 454.00000 | 26.99986 | 28.55006 | 0.49389 | 10.16591 |
Maximum of Months | 514.00000 | 27.01950 | 36.01601 | 1.49723 | 50.75184 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43779 | 27.86407 | 0.37570 | 8.38460 |
February | 454.00000 | 24.42922 | 28.65712 | 0.38196 | 8.36770 |
March | 514.00000 | 24.36718 | 27.94111 | 0.37211 | 8.22136 |
April | 485.00000 | 24.50211 | 28.02961 | 0.41370 | 9.06638 |
May | 508.00000 | 24.45895 | 34.25256 | -0.4151 | 9.41976 |
June | 496.00000 | 24.43222 | 42.09589 | -0.3549 | 8.42466 |
July | 497.00000 | 24.58184 | 43.64863 | -0.2938 | 7.84154 |
August | 514.00000 | 24.46203 | 44.52781 | -0.3137 | 8.01604 |
September | 485.00000 | 24.50676 | 41.33620 | -0.3379 | 8.48055 |
October | 502.00000 | 24.53233 | 34.92143 | 0.46534 | 10.04252 |
November | 489.00000 | 24.53259 | 31.61166 | 0.43878 | 9.53703 |
December | 497.00000 | 24.48310 | 27.00694 | 0.38780 | 8.58872 |
Annual Sum or Average | 5943.00000 | 24.47697 | 34.37218 | 0.09032 | 8.69913 |
Minimum of Months | 454.00000 | 24.36718 | 27.00694 | -0.4151 | 7.84154 |
Maximum of Months | 514.00000 | 24.58184 | 44.52781 | 0.46534 | 10.04252 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16984 | 32.31430 | 0.34016 | 8.12396 |
February | 454.00000 | 24.21810 | 30.66832 | 0.34745 | 7.68793 |
March | 514.00000 | 24.29550 | 29.73627 | 0.37273 | 8.17798 |
April | 485.00000 | 24.34732 | 29.12393 | 0.40719 | 8.74692 |
May | 508.00000 | 24.24344 | 35.48971 | -0.4612 | 9.82675 |
June | 496.00000 | 24.25766 | 43.15381 | -0.3791 | 8.36188 |
July | 497.00000 | 24.30391 | 45.02438 | -0.3397 | 7.78507 |
August | 514.00000 | 24.27453 | 45.37831 | -0.3345 | 7.70919 |
September | 485.00000 | 24.23833 | 42.51394 | -0.4027 | 8.72639 |
October | 502.00000 | 24.37905 | 36.51323 | 0.44041 | 9.38526 |
November | 489.00000 | 24.38027 | 33.53488 | 0.41599 | 8.94132 |
December | 497.00000 | 24.33704 | 29.11137 | 0.36748 | 8.11027 |
Annual Sum or Average | 5943.00000 | 24.28732 | 36.09375 | 0.06164 | 8.46917 |
Minimum of Months | 454.00000 | 24.16984 | 29.11137 | -0.4612 | 7.68793 |
Maximum of Months | 514.00000 | 24.38027 | 45.37831 | 0.44041 | 9.82675 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.21202 | 34.71259 | 0.08175 | 5.77526 |
February | 454.00000 | 23.39591 | 33.42873 | 0.12532 | 5.81143 |
March | 514.00000 | 23.61612 | 32.59645 | 0.18157 | 6.02613 |
April | 485.00000 | 24.00378 | 30.87137 | 0.28993 | 6.95022 |
May | 508.00000 | 23.96583 | 36.73497 | -0.5864 | 12.67721 |
June | 496.00000 | 24.08263 | 44.17054 | -0.4772 | 10.06413 |
July | 497.00000 | 24.09248 | 46.17806 | -0.4595 | 9.73637 |
August | 514.00000 | 24.07845 | 46.58298 | -0.4531 | 9.54151 |
September | 485.00000 | 23.99803 | 43.67317 | -0.5152 | 10.89105 |
October | 502.00000 | 23.82831 | 38.72303 | 0.28308 | 6.97481 |
November | 489.00000 | 23.51669 | 36.73585 | 0.17763 | 6.16531 |
December | 497.00000 | 23.00388 | 33.04262 | 0.01606 | 5.66777 |
Annual Sum or Average | 5943.00000 | 23.73516 | 38.16256 | -0.1139 | 8.04244 |
Minimum of Months | 454.00000 | 23.00388 | 30.87137 | -0.5864 | 5.66777 |
Maximum of Months | 514.00000 | 24.09248 | 46.58298 | 0.28993 | 12.67721 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50905 | 36.20580 | -0.3545 | 9.77987 |
February | 454.00000 | 21.75823 | 36.66522 | -0.2827 | 8.55158 |
March | 514.00000 | 22.27936 | 35.64273 | -0.1529 | 6.72429 |
April | 485.00000 | 23.35706 | 32.62733 | 0.12652 | 6.25373 |
May | 508.00000 | 23.45965 | 38.34640 | -0.7690 | 18.94541 |
June | 496.00000 | 23.84477 | 45.03038 | -0.5610 | 12.30706 |
July | 497.00000 | 23.87633 | 46.96537 | -0.5316 | 11.74587 |
August | 514.00000 | 23.87356 | 47.33252 | -0.5274 | 11.35166 |
September | 485.00000 | 23.52497 | 45.56658 | -0.6870 | 16.13597 |
October | 502.00000 | 22.60320 | 42.30743 | -0.0235 | 6.23389 |
November | 489.00000 | 21.94697 | 40.50238 | -0.2131 | 7.49953 |
December | 497.00000 | 21.33650 | 35.42119 | -0.4060 | 10.43616 |
Annual Sum or Average | 5943.00000 | 22.78821 | 40.24900 | -0.3666 | 10.51517 |
Minimum of Months | 454.00000 | 21.33650 | 32.62733 | -0.7690 | 6.23389 |
Maximum of Months | 514.00000 | 23.87633 | 47.33252 | 0.12652 | 18.94541 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36747 | 32.67860 | -0.1345 | 6.35321 |
February | 454.00000 | 22.64677 | 32.75819 | -0.0612 | 5.87556 |
March | 514.00000 | 23.27109 | 31.15364 | 0.08611 | 5.82614 |
April | 485.00000 | 23.86045 | 29.41105 | 0.25432 | 6.76545 |
May | 508.00000 | 23.81746 | 35.61218 | -0.6354 | 14.24439 |
June | 496.00000 | 24.10587 | 42.66967 | -0.4425 | 9.55903 |
July | 497.00000 | 24.22755 | 44.40779 | -0.3751 | 8.35185 |
August | 514.00000 | 24.13713 | 45.03819 | -0.4089 | 8.84916 |
September | 485.00000 | 23.79940 | 42.77628 | -0.5932 | 13.17208 |
October | 502.00000 | 23.43151 | 38.05073 | 0.17555 | 6.23838 |
November | 489.00000 | 23.05485 | 35.41506 | 0.05606 | 5.82339 |
December | 497.00000 | 22.56014 | 31.11753 | -0.0956 | 5.79549 |
Annual Sum or Average | 5943.00000 | 23.44585 | 36.79303 | -0.1828 | 8.08642 |
Minimum of Months | 454.00000 | 22.36747 | 29.41105 | -0.6354 | 5.79549 |
Maximum of Months | 514.00000 | 24.22755 | 45.03819 | 0.25432 | 14.24439 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03176 | 32.36671 | -0.1935 | 6.94435 |
February | 454.00000 | 22.22611 | 32.59141 | -0.1339 | 6.55707 |
March | 514.00000 | 22.60101 | 31.53164 | -0.0449 | 6.12653 |
April | 485.00000 | 23.71111 | 29.11764 | 0.28937 | 8.04561 |
May | 508.00000 | 23.80651 | 35.11658 | -0.5415 | 13.78537 |
June | 496.00000 | 23.99616 | 42.65251 | -0.3949 | 10.26218 |
July | 497.00000 | 24.17661 | 44.34356 | -0.3051 | 9.08600 |
August | 514.00000 | 24.02894 | 45.05258 | -0.3504 | 9.59047 |
September | 485.00000 | 23.84618 | 42.10005 | -0.4709 | 12.48379 |
October | 502.00000 | 23.01439 | 38.29132 | 0.11535 | 6.53417 |
November | 489.00000 | 22.34814 | 35.98193 | -0.0848 | 6.04742 |
December | 497.00000 | 21.79673 | 31.53247 | -0.2557 | 7.10510 |
Annual Sum or Average | 5943.00000 | 23.13809 | 36.76125 | -0.1990 | 8.56059 |
Minimum of Months | 454.00000 | 21.79673 | 29.11764 | -0.5415 | 6.04742 |
Maximum of Months | 514.00000 | 24.17661 | 45.05258 | 0.28937 | 13.78537 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38076 | 31.79860 | -0.1000 | 7.82431 |
February | 454.00000 | 22.65251 | 31.72807 | -0.0152 | 7.52359 |
March | 514.00000 | 22.73847 | 31.30509 | -0.0132 | 6.35448 |
April | 485.00000 | 23.78338 | 28.93998 | 0.31435 | 8.64464 |
May | 508.00000 | 23.62570 | 35.53951 | -0.6271 | 16.16871 |
June | 496.00000 | 23.93079 | 42.85451 | -0.4480 | 10.93904 |
July | 497.00000 | 24.12241 | 44.43891 | -0.3415 | 9.40601 |
August | 514.00000 | 24.13930 | 44.65244 | -0.2996 | 9.02779 |
September | 485.00000 | 23.95132 | 41.70401 | -0.3938 | 11.88542 |
October | 502.00000 | 23.24088 | 37.68299 | 0.19330 | 7.75259 |
November | 489.00000 | 22.73245 | 35.25206 | 0.01527 | 6.96781 |
December | 497.00000 | 22.13363 | 31.00234 | -0.1741 | 7.70120 |
Annual Sum or Average | 5943.00000 | 23.28954 | 36.45150 | -0.1597 | 9.19534 |
Minimum of Months | 454.00000 | 22.13363 | 28.93998 | -0.6271 | 6.35448 |
Maximum of Months | 514.00000 | 24.13930 | 44.65244 | 0.31435 | 16.16871 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.63154 | 30.95719 | -0.0324 | 6.18188 |
February | 454.00000 | 23.33500 | 30.23743 | 0.15728 | 6.52517 |
March | 514.00000 | 23.93587 | 28.72683 | 0.30423 | 7.64215 |
April | 485.00000 | 24.48602 | 27.56281 | 0.53013 | 11.78326 |
May | 508.00000 | 24.04782 | 34.46786 | -0.4247 | 10.99923 |
June | 496.00000 | 24.37148 | 41.49187 | -0.1883 | 7.39774 |
July | 497.00000 | 24.55538 | 43.15085 | -0.0722 | 7.06108 |
August | 514.00000 | 24.49067 | 43.57551 | -0.0809 | 6.97893 |
September | 485.00000 | 24.04898 | 41.45660 | -0.3796 | 10.12766 |
October | 502.00000 | 23.91819 | 36.03587 | 0.35353 | 8.48171 |
November | 489.00000 | 23.83376 | 32.71512 | 0.29066 | 7.54352 |
December | 497.00000 | 23.70580 | 28.03969 | 0.21691 | 6.58760 |
Annual Sum or Average | 5943.00000 | 23.95050 | 34.90916 | 0.05474 | 8.10948 |
Minimum of Months | 454.00000 | 22.63154 | 27.56281 | -0.4247 | 6.18188 |
Maximum of Months | 514.00000 | 24.55538 | 43.57551 | 0.53013 | 11.78326 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87950 | 35.31325 | -0.5248 | 12.00981 |
February | 454.00000 | 21.00281 | 35.88948 | -0.4754 | 10.71513 |
March | 514.00000 | 21.63873 | 34.73173 | -0.3129 | 7.92707 |
April | 485.00000 | 22.87082 | 31.99642 | 0.00072 | 6.27622 |
May | 508.00000 | 23.09455 | 37.57546 | -0.8946 | 23.71206 |
June | 496.00000 | 23.73479 | 43.95248 | -0.5989 | 13.55083 |
July | 497.00000 | 23.81147 | 45.73096 | -0.5534 | 12.33175 |
August | 514.00000 | 23.67973 | 46.67487 | -0.6048 | 13.58697 |
September | 485.00000 | 23.14090 | 44.64994 | -0.8349 | 21.42216 |
October | 502.00000 | 21.98634 | 41.87184 | -0.1739 | 6.74910 |
November | 489.00000 | 21.15943 | 39.50925 | -0.4116 | 9.60341 |
December | 497.00000 | 20.58424 | 34.64980 | -0.6095 | 13.84060 |
Annual Sum or Average | 5943.00000 | 22.30850 | 39.41027 | -0.5003 | 12.66099 |
Minimum of Months | 454.00000 | 20.58424 | 31.99642 | -0.8946 | 6.27622 |
Maximum of Months | 514.00000 | 23.81147 | 46.67487 | 0.00072 | 23.71206 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.86852 | 33.75570 | -0.5229 | 11.64203 |
February | 385.00000 | 21.09421 | 34.07314 | -0.4464 | 10.10279 |
March | 433.00000 | 21.42305 | 33.58139 | -0.3526 | 8.39834 |
April | 410.00000 | 23.20598 | 30.15795 | 0.14518 | 7.73571 |
May | 430.00000 | 23.29305 | 35.94171 | -0.7353 | 20.65072 |
June | 418.00000 | 23.70409 | 43.13535 | -0.5155 | 13.96632 |
July | 422.00000 | 24.01382 | 44.53452 | -0.3931 | 11.81257 |
August | 433.00000 | 23.79229 | 45.39866 | -0.4623 | 12.68349 |
September | 410.00000 | 23.45748 | 42.73654 | -0.6299 | 17.76432 |
October | 427.00000 | 21.95110 | 40.50211 | -0.1591 | 7.17928 |
November | 417.00000 | 21.03973 | 38.29579 | -0.4337 | 9.67756 |
December | 422.00000 | 20.53434 | 33.34003 | -0.6210 | 14.01078 |
Annual Sum or Average | 5034.00000 | 22.37043 | 37.98754 | -0.4281 | 12.14947 |
Minimum of Months | 385.00000 | 20.53434 | 30.15795 | -0.7353 | 7.17928 |
Maximum of Months | 433.00000 | 24.01382 | 45.39866 | 0.14518 | 20.65072 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.83854 | 32.63243 | -0.2504 | 9.46159 |
February | 454.00000 | 22.10570 | 32.89798 | -0.1589 | 9.01406 |
March | 514.00000 | 21.97027 | 33.17627 | -0.2056 | 7.62245 |
April | 485.00000 | 23.35986 | 29.99675 | 0.20571 | 8.57764 |
May | 508.00000 | 23.19406 | 36.55343 | -0.7721 | 21.81242 |
June | 496.00000 | 23.57671 | 43.82624 | -0.5766 | 14.83095 |
July | 497.00000 | 23.80244 | 45.34509 | -0.4658 | 12.80308 |
August | 514.00000 | 23.84199 | 45.53299 | -0.4140 | 11.94248 |
September | 485.00000 | 23.70291 | 42.23012 | -0.4716 | 14.99488 |
October | 502.00000 | 22.65882 | 39.33445 | 0.05504 | 8.08243 |
November | 489.00000 | 21.90991 | 37.24387 | -0.1943 | 8.55574 |
December | 497.00000 | 21.24254 | 32.68995 | -0.4238 | 11.25700 |
Annual Sum or Average | 5943.00000 | 22.77041 | 37.66654 | -0.3084 | 11.60474 |
Minimum of Months | 454.00000 | 21.24254 | 29.99675 | -0.7721 | 7.62245 |
Maximum of Months | 514.00000 | 23.84199 | 45.53299 | 0.20571 | 21.81242 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08666 | 33.81514 | -0.4508 | 10.32322 |
February | 454.00000 | 21.40375 | 34.07521 | -0.3456 | 9.12790 |
March | 514.00000 | 21.64616 | 33.51753 | -0.2790 | 7.62609 |
April | 485.00000 | 23.10028 | 30.54504 | 0.12945 | 7.51492 |
May | 508.00000 | 23.15894 | 36.57639 | -0.7608 | 21.58272 |
June | 496.00000 | 23.73444 | 43.38409 | -0.4737 | 12.87408 |
July | 497.00000 | 23.89030 | 45.10829 | -0.3947 | 11.58199 |
August | 514.00000 | 23.79300 | 45.78823 | -0.4416 | 11.81142 |
September | 485.00000 | 23.22842 | 43.61720 | -0.6982 | 19.29181 |
October | 502.00000 | 22.05337 | 40.69906 | -0.1178 | 6.83182 |
November | 489.00000 | 21.26189 | 38.31478 | -0.3612 | 8.70360 |
December | 497.00000 | 20.74139 | 33.39163 | -0.5536 | 12.12363 |
Annual Sum or Average | 5943.00000 | 22.43224 | 38.27323 | -0.3968 | 11.63307 |
Minimum of Months | 454.00000 | 20.74139 | 30.54504 | -0.7608 | 6.83182 |
Maximum of Months | 514.00000 | 23.89030 | 45.78823 | 0.12945 | 21.58272 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23766 | 36.62872 | -0.7318 | 18.68652 |
February | 454.00000 | 20.31423 | 37.38027 | -0.6888 | 17.28472 |
March | 514.00000 | 20.91853 | 36.23103 | -0.5218 | 11.96247 |
April | 485.00000 | 22.26033 | 33.26405 | -0.1562 | 7.73972 |
May | 508.00000 | 22.49969 | 38.97923 | -1.1015 | 33.14440 |
June | 496.00000 | 23.40212 | 44.89000 | -0.7115 | 17.82901 |
July | 497.00000 | 23.53058 | 46.49427 | -0.6467 | 15.91313 |
August | 514.00000 | 23.39207 | 47.50238 | -0.7041 | 17.35233 |
September | 485.00000 | 22.60624 | 46.12308 | -1.0246 | 29.79988 |
October | 502.00000 | 21.11506 | 44.17732 | -0.4080 | 10.09511 |
November | 489.00000 | 20.43708 | 41.20748 | -0.6302 | 15.43787 |
December | 497.00000 | 20.02759 | 35.85605 | -0.7981 | 21.06630 |
Annual Sum or Average | 5943.00000 | 21.73937 | 40.75761 | -0.6775 | 18.03443 |
Minimum of Months | 454.00000 | 20.02759 | 33.26405 | -1.1015 | 7.73972 |
Maximum of Months | 514.00000 | 23.53058 | 47.50238 | -0.1562 | 33.14440 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34533 | 35.47998 | -0.6924 | 17.14470 |
February | 454.00000 | 20.55275 | 36.05602 | -0.6148 | 14.89588 |
March | 514.00000 | 20.96248 | 35.19342 | -0.4960 | 11.28379 |
April | 485.00000 | 22.95008 | 30.97194 | 0.07963 | 8.15838 |
May | 508.00000 | 23.02061 | 37.05856 | -0.8284 | 24.18365 |
June | 496.00000 | 23.53500 | 43.92224 | -0.5604 | 15.57974 |
July | 497.00000 | 23.86115 | 45.18598 | -0.4273 | 12.72870 |
August | 514.00000 | 23.68060 | 45.99292 | -0.4835 | 13.45091 |
September | 485.00000 | 23.23746 | 43.64837 | -0.7059 | 20.30107 |
October | 502.00000 | 21.44096 | 42.62926 | -0.3053 | 9.31440 |
November | 489.00000 | 20.52327 | 40.19439 | -0.5993 | 14.24420 |
December | 497.00000 | 20.09554 | 34.93928 | -0.7748 | 20.12034 |
Annual Sum or Average | 5943.00000 | 22.02681 | 39.30496 | -0.5345 | 15.12130 |
Minimum of Months | 454.00000 | 20.09554 | 30.97194 | -0.8284 | 8.15838 |
Maximum of Months | 514.00000 | 23.86115 | 45.99292 | 0.07963 | 24.18365 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.10013 | 34.03401 | -0.4747 | 13.64946 |
February | 454.00000 | 21.40145 | 34.37844 | -0.3726 | 12.29821 |
March | 514.00000 | 21.30995 | 34.59580 | -0.4013 | 10.49847 |
April | 485.00000 | 22.93522 | 30.94194 | 0.08761 | 9.02451 |
May | 508.00000 | 22.74314 | 37.67963 | -0.9382 | 29.00295 |
June | 496.00000 | 23.26214 | 44.68175 | -0.6829 | 19.05850 |
July | 497.00000 | 23.54214 | 46.04422 | -0.5521 | 16.16615 |
August | 514.00000 | 23.59751 | 46.19975 | -0.4988 | 14.96808 |
September | 485.00000 | 23.34224 | 43.22195 | -0.6099 | 20.03007 |
October | 502.00000 | 22.00211 | 41.18682 | -0.1342 | 9.39254 |
November | 489.00000 | 21.20837 | 38.84434 | -0.4068 | 11.96513 |
December | 497.00000 | 20.58488 | 34.02819 | -0.6313 | 16.70378 |
Annual Sum or Average | 5943.00000 | 22.25713 | 38.86275 | -0.4700 | 15.26259 |
Minimum of Months | 454.00000 | 20.58488 | 30.94194 | -0.9382 | 9.02451 |
Maximum of Months | 514.00000 | 23.59751 | 46.19975 | 0.08761 | 29.00295 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54944 | 34.88702 | -0.6261 | 15.33686 |
February | 454.00000 | 20.88376 | 35.22831 | -0.5112 | 13.06654 |
March | 514.00000 | 21.14125 | 34.64477 | -0.4337 | 10.21471 |
April | 485.00000 | 22.62432 | 31.52733 | 0.00584 | 8.18943 |
May | 508.00000 | 22.71800 | 37.66514 | -0.9183 | 28.58725 |
June | 496.00000 | 23.42603 | 44.19352 | -0.5763 | 16.68119 |
July | 497.00000 | 23.63906 | 45.75665 | -0.4767 | 14.60107 |
August | 514.00000 | 23.51990 | 46.51177 | -0.5332 | 14.98205 |
September | 485.00000 | 22.80028 | 44.75858 | -0.8511 | 25.63632 |
October | 502.00000 | 21.46946 | 42.34781 | -0.2845 | 8.64857 |
November | 489.00000 | 20.75535 | 39.51502 | -0.5244 | 12.41702 |
December | 497.00000 | 20.28237 | 34.38927 | -0.7104 | 17.57443 |
Annual Sum or Average | 5943.00000 | 21.99223 | 39.32154 | -0.5376 | 15.51218 |
Minimum of Months | 454.00000 | 20.28237 | 31.52733 | -0.9183 | 8.18943 |
Maximum of Months | 514.00000 | 23.63906 | 46.51177 | 0.00584 | 28.58725 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 17676205.48 | 592.24 | 20-MAR-05:05 | 8.40 | 84973530.84 | 0.00 | 0.102650E+09 | 0.05 | 4.90 | 25-MAR-05:50 | 0.00 | 0.00 |
April | 0.749085E+10 | 104499.92 | 28-APR-15:00 | 70.32 | 0.479574E+11 | 0.00 | 0.554483E+11 | 0.55 | 7.58 | 28-APR-15:50 | 0.00 | 0.00 |
May | 0.882956E+10 | 127973.21 | 22-MAY-13:40 | 74.55 | 0.576488E+11 | 0.00 | 0.664784E+11 | 0.57 | 7.59 | 22-MAY-12:10 | 0.00 | 0.00 |
June | 0.256860E+11 | 142209.29 | 12-JUN-17:20 | 182.78 | 0.171586E+12 | 0.00 | 0.197272E+12 | 1.48 | 7.59 | 20-JUN-14:10 | 0.00 | 0.00 |
July | 0.441516E+11 | 143643.51 | 22-JUL-10:00 | 323.26 | 0.292280E+12 | 0.00 | 0.336432E+12 | 2.54 | 7.59 | 22-JUL-18:22 | 0.00 | 0.00 |
August | 0.580787E+11 | 137450.77 | 28-AUG-13:30 | 395.00 | 0.384462E+12 | 0.00 | 0.442541E+12 | 3.17 | 7.59 | 07-AUG-16:00 | 0.00 | 0.00 |
September | 0.307699E+11 | 139081.37 | 13-SEP-16:20 | 236.85 | 0.201502E+12 | 0.00 | 0.232272E+12 | 1.89 | 7.59 | 11-SEP-12:40 | 0.00 | 0.00 |
October | 0.212441E+10 | 41015.54 | 07-OCT-15:00 | 33.42 | 0.108716E+11 | 0.00 | 0.129960E+11 | 0.22 | 6.49 | 07-OCT-15:00 | 0.00 | 0.00 |
November | 40029465.39 | 10175.49 | 24-NOV-12:00 | 9.64 | 0.192329E+09 | 0.00 | 0.232358E+09 | 0.06 | 4.91 | 17-NOV-06:40 | 0.00 | 0.00 |
December | 28737800.13 | 590.40 | 08-DEC-05:55 | 13.62 | 0.138196E+09 | 0.00 | 0.166934E+09 | 0.09 | 4.89 | 04-DEC-10:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.177218E+12 | 1347.84 | 0.116672E+13 | 0.00 | 0.134394E+13 | 0.89 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.580787E+11 | 143643.51 | 395.00 | 0.384462E+12 | 0.00 | 0.442541E+12 | 3.17 | 7.59 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.486911E+09 | 86139.63 | 22-MAY-14:20 | 1.83 | 0.363713E+10 | 0.00 | 0.412404E+10 | 0.02 | 7.58 | 22-MAY-14:10 | 0.00 | 0.00 |
June | 0.388135E+10 | 100874.18 | 13-JUN-16:00 | 14.33 | 0.282812E+11 | 0.00 | 0.321625E+11 | 0.14 | 7.52 | 12-JUN-16:00 | 0.00 | 0.00 |
July | 0.439658E+10 | 106903.91 | 22-JUL-16:02 | 16.06 | 0.322022E+11 | 0.00 | 0.365988E+11 | 0.16 | 7.59 | 21-JUL-13:40 | 0.00 | 0.00 |
August | 0.273137E+10 | 88908.20 | 28-AUG-14:10 | 10.33 | 0.201935E+11 | 0.00 | 0.229249E+11 | 0.10 | 7.59 | 14-AUG-14:50 | 0.00 | 0.00 |
September | 0.213565E+10 | 79382.41 | 13-SEP-13:30 | 8.50 | 0.154558E+11 | 0.00 | 0.175915E+11 | 0.08 | 7.55 | 27-SEP-15:50 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136319E+11 | 51.06 | 0.997699E+11 | 0.00 | 0.113402E+12 | 0.04 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.439658E+10 | 106903.91 | 16.06 | 0.322022E+11 | 0.00 | 0.365988E+11 | 0.16 | 7.59 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.165770E+10 | 744.00 | 1777.06 | 29-JAN-06:00 | 34150.35 | 19-JAN-16:30 | 18.70 | 18.33 | 14.09 |
February | 0.369605E+10 | 672.00 | 2840.42 | 07-FEB-15:00 | 67702.30 | 17-FEB-17:00 | 19.33 | 18.33 | 14.09 |
March | 0.723340E+10 | 744.00 | 5740.22 | 25-MAR-13:00 | 112083.30 | 31-MAR-23:40 | 19.97 | 18.33 | 14.09 |
April | 0.222816E+11 | 720.00 | 49248.27 | 20-APR-16:00 | 586155.14 | 30-APR-19:02 | 21.43 | 18.58 | 14.09 |
May | 0.990120E+10 | 744.00 | 49248.27 | 11-MAY-16:00 | 109876.95 | 22-MAY-15:00 | 19.00 | 18.39 | 14.09 |
June | 0.261084E+11 | 720.00 | 49248.27 | 09-JUN-11:00 | 370224.71 | 13-JUN-17:00 | 20.20 | 18.78 | 14.09 |
July | 0.566956E+11 | 744.00 | 49248.27 | 02-JUL-13:00 | 541673.64 | 22-JUL-19:02 | 22.40 | 19.41 | 14.09 |
August | 0.918179E+11 | 744.00 | 49248.27 | 01-AUG-07:00 | 634154.63 | 14-AUG-16:00 | 26.36 | 20.17 | 14.09 |
September | 0.238121E+11 | 720.00 | 49248.27 | 01-SEP-15:10 | 80673.49 | 13-SEP-16:00 | 19.22 | 18.60 | 14.09 |
October | 0.767405E+10 | 744.00 | 49248.27 | 07-OCT-14:30 | 83099.06 | 31-OCT-23:30 | 19.40 | 18.33 | 14.09 |
November | 0.719027E+10 | 720.00 | 25304.36 | 24-NOV-12:00 | 114809.14 | 24-NOV-12:00 | 19.90 | 18.33 | 14.09 |
December | 0.784751E+10 | 744.00 | 8638.49 | 23-DEC-11:00 | 147420.96 | 23-DEC-11:00 | 20.43 | 18.33 | 14.09 |
Annual Sum or Average | 0.265916E+12 | 8760.00 | 20.54 | 18.66 | 14.09 | ||||
Minimum of Months | 0.165770E+10 | 672.00 | 1777.06 | 34150.35 | 18.70 | 18.33 | 14.09 | ||
Maximum of Months | 0.918179E+11 | 744.00 | 49248.27 | 634154.63 | 26.36 | 20.17 | 14.09 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.10 | 21.10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.10 | 21.10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 185943.85 | 27-MAR-05:07 | 21.01 | 21.01 | 0.06 |
April | 57055797.46 | 36.99 | 2123.91 | 28-APR-15:00 | 893663.64 | 28-APR-15:00 | 21.06 | 20.95 | 3.82 |
May | 0.205396E+09 | 46.82 | 14383.35 | 22-MAY-13:30 | 1028727.89 | 22-MAY-13:40 | 21.16 | 21.03 | 4.11 |
June | 0.144020E+10 | 126.74 | 14383.35 | 12-JUN-12:20 | 1048800.95 | 21-JUN-13:10 | 21.46 | 21.07 | 11.05 |
July | 0.148158E+10 | 243.70 | 14383.35 | 10-JUL-08:30 | 1045297.49 | 10-JUL-08:50 | 21.74 | 21.10 | 19.43 |
August | 0.152193E+10 | 328.13 | 14383.35 | 14-AUG-09:50 | 1083516.35 | 28-AUG-13:30 | 21.94 | 21.10 | 24.69 |
September | 0.839480E+09 | 164.96 | 14383.35 | 11-SEP-13:30 | 1076106.38 | 25-SEP-12:50 | 21.52 | 21.07 | 14.18 |
October | 4287200.64 | 14.83 | 186.49 | 11-OCT-15:00 | 314793.06 | 07-OCT-15:10 | 21.08 | 21.06 | 1.51 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 193210.40 | 20-NOV-05:50 | 20.93 | 20.93 | 0.05 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 193328.83 | 15-DEC-05:55 | 20.97 | 20.97 | 0.08 |
Annual Sum or Average | 0.554993E+10 | 962.19 | 21.26 | 21.04 | 6.63 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 20.93 | 0.00 | ||
Maximum of Months | 0.152193E+10 | 328.13 | 14383.35 | 1083516.35 | 21.94 | 21.10 | 24.69 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.10 | 21.10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.10 | 21.10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.01 | 21.01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.06 | 21.06 | 0.00 |
May | 71701296.43 | 1.67 | 14383.35 | 22-MAY-14:10 | 930493.26 | 22-MAY-14:10 | 21.16 | 21.15 | 0.11 |
June | 0.556327E+09 | 11.17 | 14383.35 | 12-JUN-12:50 | 889924.96 | 21-JUN-15:00 | 21.46 | 21.40 | 0.75 |
July | 0.414509E+09 | 11.90 | 14383.35 | 10-JUL-09:10 | 895708.05 | 10-JUL-10:10 | 21.74 | 21.68 | 0.79 |
August | 0.192823E+09 | 7.83 | 14383.35 | 14-AUG-10:30 | 955689.95 | 21-AUG-12:40 | 21.94 | 21.89 | 0.52 |
September | 0.129847E+09 | 3.83 | 14383.35 | 11-SEP-14:10 | 948251.21 | 25-SEP-15:40 | 21.52 | 21.50 | 0.26 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.08 | 21.08 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.93 | 20.93 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.97 | 20.97 | 0.00 |
Annual Sum or Average | 0.136521E+10 | 36.40 | 21.26 | 21.24 | 0.20 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 20.93 | 0.00 | ||
Maximum of Months | 0.556327E+09 | 11.90 | 14383.35 | 955689.95 | 21.94 | 21.89 | 0.79 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.219838E+12 | 0.00 | 421.47 | 1358254.01 | 02-JAN-06:02 | 0.00 | 27.23 | 57.99 | 0.39 | 0.00 | 0.04 | 0.68 | 02-JAN-06:02 |
February | 0.141173E+12 | 0.00 | 361.54 | 1151549.10 | 27-FEB-05:11 | 0.00 | 26.29 | 56.30 | 0.26 | 0.00 | 0.03 | 0.57 | 27-FEB-05:11 |
March | 0.965690E+11 | 0.00 | 358.94 | 1051173.15 | 27-MAR-05:02 | 0.00 | 24.49 | 52.03 | 0.16 | 0.00 | 0.02 | 0.52 | 27-MAR-05:02 |
April | 0.118993E+11 | 0.00 | 114.18 | 250343.88 | 01-APR-05:03 | 0.00 | 24.06 | 33.21 | 0.02 | 0.00 | 0.00 | 0.12 | 01-APR-05:03 |
May | 0.500128E+10 | 0.00 | 86.29 | 902749.92 | 05-MAY-05:03 | 0.00 | 22.43 | 29.25 | 0.01 | 0.00 | 0.00 | 0.45 | 05-MAY-05:03 |
June | 0.145702E+09 | 0.00 | 19.63 | 58444.88 | 08-JUN-05:03 | 0.00 | 22.19 | 23.82 | 0.00 | 0.00 | 0.00 | 0.03 | 08-JUN-05:03 |
July | 49000785.97 | 0.00 | 10.55 | 27727.25 | 31-JUL-05:03 | 0.00 | 21.72 | 22.58 | 0.00 | 0.00 | 0.00 | 0.01 | 31-JUL-05:03 |
August | 20248293.95 | 0.00 | 7.47 | 2874.12 | 23-AUG-05:20 | 0.00 | 21.82 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23-AUG-05:20 |
September | 0.110097E+10 | 0.00 | 45.68 | 74651.56 | 21-SEP-06:10 | 0.00 | 21.91 | 25.70 | 0.00 | 0.00 | 0.00 | 0.04 | 21-SEP-06:10 |
October | 0.288504E+11 | 0.00 | 247.39 | 988057.00 | 28-OCT-05:02 | 0.00 | 22.85 | 42.44 | 0.05 | 0.00 | 0.01 | 0.49 | 28-OCT-05:02 |
November | 0.107785E+12 | 0.00 | 365.74 | 1218267.58 | 27-NOV-05:11 | 0.00 | 23.71 | 52.99 | 0.18 | 0.00 | 0.02 | 0.61 | 27-NOV-05:11 |
December | 0.245350E+12 | 0.00 | 443.51 | 1138643.64 | 11-DEC-05:11 | 0.00 | 27.19 | 59.89 | 0.42 | 0.00 | 0.05 | 0.57 | 11-DEC-05:11 |
Annual Sum or Average | 0.857782E+12 | 0.00 | 2482.40 | 0.00 | 23.81 | 39.82 | 0.12 | 0.00 | 0.01 | ||||
Minimum of Months | 20248293.95 | 0.00 | 7.47 | 2874.12 | 0.00 | 21.72 | 22.43 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.245350E+12 | 0.00 | 443.51 | 1358254.01 | 0.00 | 27.23 | 59.89 | 0.42 | 0.00 | 0.05 | 0.68 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.70 | 18.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.33 | 19.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.97 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.43 | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 19.00 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.20 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 22.40 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 26.36 | 26.36 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 19.22 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.40 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.90 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.43 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 18.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 26.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.463960E+10 | 0.00 | 54.29 | 0.463439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83220.98 | 30-APR-15:12 | 83220.98 | 30-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.561799E+10 | 0.00 | 65.69 | 0.561799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99233.01 | 22-MAY-15:00 | 99233.01 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.182839E+11 | 0.00 | 169.27 | 0.180132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124972.57 | 13-JUN-16:00 | 117110.72 | 13-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.311273E+11 | 0.00 | 302.03 | 0.310805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120577.11 | 21-JUL-15:20 | 120577.11 | 21-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.412213E+11 | 0.00 | 374.24 | 0.410759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125866.71 | 14-AUG-15:10 | 125866.71 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.192813E+11 | 0.00 | 211.37 | 0.192503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89815.27 | 13-SEP-14:20 | 89815.27 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.103818E+10 | 0.00 | 24.43 | 0.103818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24890.33 | 11-OCT-15:00 | 24890.33 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 12987169.27 | 0.00 | 0.83 | 12987169.27 | 0.00 | 0.00 | 0.00 | 0.00 | 8023.87 | 24-NOV-12:00 | 8023.87 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121223E+12 | 0.00 | 1202.15 | 0.120723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.412213E+11 | 0.00 | 374.24 | 0.410759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125866.71 | 125866.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47151.58 | 0.00 | 13.39 | 47151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 02-JAN-04:30 | 3.32 | 02-JAN-04:30 | 0.00 | 0.00 | 0.00 |
February | 40396.28 | 0.00 | 17.61 | 40396.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 17-FEB-06:01 | 1.36 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 78365.53 | 0.00 | 22.53 | 78365.53 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 27-MAR-05:40 | 3.29 | 27-MAR-05:40 | 0.00 | 0.00 | 0.00 |
April | 0.384183E+11 | 0.00 | 65.87 | 0.383991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 823260.19 | 30-APR-15:12 | 823260.19 | 30-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.480701E+11 | 0.00 | 72.03 | 0.480701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 856154.24 | 22-MAY-15:00 | 856154.24 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.151882E+12 | 0.00 | 171.10 | 0.149702E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1131958.52 | 13-JUN-16:00 | 1049494.06 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.246517E+12 | 0.00 | 296.06 | 0.246250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1073360.03 | 21-JUL-15:30 | 1073360.03 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.310642E+12 | 0.00 | 373.01 | 0.309945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1011503.12 | 14-AUG-15:40 | 1011503.12 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.169679E+12 | 0.00 | 223.14 | 0.168691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 845817.44 | 13-SEP-14:40 | 845817.44 | 13-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.869778E+10 | 0.00 | 32.37 | 0.869778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227160.15 | 07-OCT-15:00 | 227160.15 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 50104132.06 | 0.00 | 9.08 | 50104132.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37231.99 | 24-NOV-12:00 | 37231.99 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 39711.52 | 0.00 | 13.62 | 39711.52 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 16-DEC-05:15 | 3.61 | 16-DEC-05:15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973956E+12 | 0.00 | 1309.81 | 0.969804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 39711.52 | 0.00 | 9.08 | 39711.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 1.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.310642E+12 | 0.00 | 373.01 | 0.309945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1131958.52 | 1073360.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 77901.77 | 0.00 | 0.08 | 77901.77 | 0.00 | 0.00 | 0.00 | 0.00 | 366.61 | 02-JAN-04:30 | 366.61 | 02-JAN-04:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.370326E+10 | 0.00 | 51.95 | 0.370326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84578.02 | 30-APR-15:32 | 84578.02 | 30-APR-15:32 | 0.00 | 0.00 | 0.00 |
May | 0.484941E+10 | 0.00 | 63.61 | 0.484941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93629.63 | 22-MAY-15:00 | 93629.63 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.157259E+11 | 0.00 | 156.71 | 0.155135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131962.62 | 13-JUN-16:00 | 125921.91 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.251205E+11 | 0.00 | 278.50 | 0.250988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125074.34 | 21-JUL-15:40 | 125074.34 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.297960E+11 | 0.00 | 361.33 | 0.297619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115879.85 | 14-AUG-15:40 | 115879.85 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.152895E+11 | 0.00 | 199.75 | 0.152650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86292.81 | 13-SEP-15:00 | 86292.81 | 13-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.623258E+09 | 0.00 | 22.23 | 0.623258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21582.06 | 07-OCT-15:00 | 21582.06 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 4559993.44 | 0.00 | 0.67 | 4559993.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3485.91 | 24-NOV-12:00 | 3485.91 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.951125E+11 | 0.00 | 1134.83 | 0.948197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.297960E+11 | 0.00 | 361.33 | 0.297619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131962.62 | 125921.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 1667287.05 | 0.00 | 0.10 | 811174.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5948.13 | 18-MAR-05:02 | 2700.71 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.751880E+09 | 0.00 | 18.57 | 0.751880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28478.73 | 28-APR-15:00 | 28478.73 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.227142E+10 | 0.00 | 32.74 | 0.227142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57514.92 | 22-MAY-15:00 | 57514.92 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.824059E+10 | 0.00 | 87.58 | 0.817182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65108.16 | 27-JUN-05:03 | 60343.92 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.135545E+11 | 0.00 | 181.25 | 0.134261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66040.79 | 10-JUL-11:00 | 66040.79 | 10-JUL-11:00 | 0.00 | 0.00 | 0.00 |
August | 0.178470E+11 | 0.00 | 259.44 | 0.177709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65567.08 | 14-AUG-16:00 | 65567.08 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.851000E+10 | 0.00 | 120.21 | 0.846358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58553.86 | 16-SEP-05:02 | 49189.78 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.162845E+09 | 0.00 | 9.28 | 0.144688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36665.91 | 20-OCT-05:02 | 16244.39 | 13-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 21877835.12 | 0.00 | 0.89 | 18968296.88 | 0.00 | 0.00 | 0.00 | 0.00 | 16264.68 | 15-NOV-05:12 | 16264.68 | 15-NOV-05:12 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513617E+11 | 0.00 | 710.06 | 0.510202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178470E+11 | 0.00 | 259.44 | 0.177709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66040.79 | 66040.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.369871E+10 | 0.345760E+10 | 718.42 | 0.369851E+10 | 198279.16 | 0.00 | 0.02 | 10-JAN-17:05 | 0.01 | 29-JAN-05:10 | 2947.41 | 10-JAN-17:05 | 2947.41 | 10-JAN-17:05 | 56.33 | 29-JAN-05:50 | 1722.43 | 10-JAN-17:05 | 0.00 |
February | 0.607995E+10 | 0.392502E+10 | 660.58 | 0.596901E+10 | 0.110939E+09 | 0.00 | 0.03 | 20-FEB-16:00 | 0.01 | 07-FEB-14:15 | 5124.22 | 20-FEB-15:50 | 5124.22 | 20-FEB-15:50 | 94.89 | 06-FEB-19:10 | 2390.55 | 20-FEB-16:00 | 0.00 |
March | 0.110236E+11 | 0.572918E+10 | 704.50 | 0.105064E+11 | 0.517144E+09 | 0.00 | 0.03 | 31-MAR-23:30 | 0.01 | 18-MAR-04:40 | 5613.14 | 31-MAR-23:10 | 5613.14 | 31-MAR-23:10 | 330.63 | 01-MAR-18:30 | 2744.67 | 31-MAR-23:30 | 0.00 |
April | 0.608287E+11 | 0.205765E+11 | 718.75 | 0.571462E+11 | 0.368252E+10 | 0.00 | 0.95 | 30-APR-17:00 | 0.01 | 23-APR-14:00 | 327015.39 | 30-APR-17:41 | 327015.39 | 30-APR-17:41 | 120022.50 | 28-APR-08:00 | 110974.92 | 30-APR-17:00 | 0.00 |
May | 0.227118E+10 | 0.314113E+10 | 566.43 | 0.224194E+10 | 29242838.40 | 0.00 | 0.16 | 22-MAY-15:00 | 0.01 | 24-MAY-05:03 | 53375.05 | 22-MAY-15:00 | 49331.05 | 22-MAY-15:00 | 4044.00 | 22-MAY-15:00 | 17698.78 | 22-MAY-15:00 | 0.00 |
June | 0.220522E+11 | 0.944180E+10 | 307.28 | 0.186313E+11 | 0.342094E+10 | 0.00 | 0.60 | 13-JUN-17:00 | 0.01 | 16-JUN-05:20 | 221370.72 | 13-JUN-17:00 | 218697.39 | 13-JUN-17:00 | 93221.94 | 25-JUN-17:51 | 72951.44 | 13-JUN-17:00 | 0.00 |
July | 0.123580E+12 | 0.385555E+11 | 473.71 | 0.979977E+11 | 0.255827E+11 | 0.00 | 0.86 | 21-JUL-17:00 | 0.01 | 30-JUL-16:32 | 312732.90 | 21-JUL-16:00 | 312732.90 | 21-JUL-16:00 | 66525.83 | 23-JUL-16:31 | 111505.59 | 22-JUL-18:00 | 0.00 |
August | 0.397848E+12 | 0.110925E+12 | 711.08 | 0.288100E+12 | 0.109748E+12 | 0.00 | 1.00 | 14-AUG-16:00 | 0.01 | 07-AUG-04:42 | 386006.10 | 14-AUG-13:00 | 375827.54 | 14-AUG-16:00 | 168246.75 | 08-AUG-13:00 | 126149.60 | 14-AUG-17:10 | 0.00 |
September | 0.120084E+10 | 0.279196E+10 | 351.15 | 0.113463E+10 | 66212671.70 | 0.00 | 0.09 | 27-SEP-16:00 | 0.01 | 04-SEP-13:55 | 28413.33 | 13-SEP-16:00 | 27237.11 | 27-SEP-16:00 | 4389.21 | 13-SEP-16:00 | 9853.81 | 27-SEP-16:00 | 0.00 |
October | 0.313532E+10 | 0.336989E+10 | 531.31 | 0.302402E+10 | 0.111298E+09 | 0.00 | 0.05 | 07-OCT-15:00 | 0.01 | 18-OCT-07:05 | 12799.05 | 07-OCT-15:00 | 12799.05 | 07-OCT-15:00 | 150.96 | 31-OCT-24:00 | 4912.45 | 07-OCT-15:00 | 0.00 |
November | 0.762256E+10 | 0.473290E+10 | 605.74 | 0.713840E+10 | 0.484159E+09 | 0.00 | 0.10 | 24-NOV-12:00 | 0.01 | 07-NOV-20:10 | 29223.15 | 24-NOV-12:00 | 23023.48 | 24-NOV-12:00 | 6199.67 | 24-NOV-12:00 | 9069.38 | 24-NOV-12:00 | 0.00 |
December | 0.146441E+11 | 0.705710E+10 | 744.00 | 0.134742E+11 | 0.116990E+10 | 0.00 | 0.15 | 23-DEC-11:00 | 0.02 | 02-DEC-17:00 | 39688.50 | 23-DEC-11:00 | 39688.50 | 23-DEC-11:00 | 720.55 | 21-DEC-20:00 | 13304.81 | 23-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.653986E+12 | 0.213704E+12 | 7092.96 | 0.509063E+12 | 0.144923E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.120084E+10 | 0.279196E+10 | 307.28 | 0.113463E+10 | 198279.16 | 0.00 | 0.02 | 0.01 | 2947.41 | 2947.41 | 56.33 | 1722.43 | 0.00 | ||||||
Maximum of Months | 0.397848E+12 | 0.110925E+12 | 744.00 | 0.288100E+12 | 0.109748E+12 | 0.00 | 1.00 | 0.02 | 386006.10 | 375827.54 | 168246.75 | 126149.60 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.419350E+10 | 0.108059E+10 | 744.00 | 0.419200E+10 | 1498327.08 | 0.00 | 0.28 | 16-JAN-16:25 | 0.11 | 10-JAN-08:00 | 2324.99 | 01-JAN-16:10 | 2319.22 | 01-JAN-16:05 | 52.72 | 18-JAN-16:20 | 562.21 | 16-JAN-16:25 | 0.00 |
February | 0.871238E+10 | 0.209791E+10 | 672.00 | 0.871110E+10 | 1283654.96 | 0.00 | 0.54 | 19-FEB-16:53 | 0.36 | 17-FEB-07:40 | 4539.20 | 19-FEB-16:57 | 4539.20 | 19-FEB-16:57 | 56.81 | 07-FEB-16:00 | 1090.63 | 19-FEB-16:53 | 0.00 |
March | 0.150690E+11 | 0.345871E+10 | 744.00 | 0.150687E+11 | 312060.42 | 0.00 | 0.84 | 31-MAR-24:00 | 0.58 | 01-MAR-07:10 | 7596.46 | 31-MAR-24:00 | 7596.46 | 31-MAR-24:00 | 65.07 | 20-MAR-06:10 | 1703.45 | 31-MAR-24:00 | 0.00 |
April | 0.200713E+11 | 0.445689E+10 | 720.00 | 0.200708E+11 | 538492.00 | 0.00 | 1.00 | 30-APR-17:32 | 0.30 | 30-APR-23:53 | 8945.29 | 30-APR-18:10 | 8945.29 | 30-APR-18:10 | 69.10 | 28-APR-11:00 | 2631.47 | 30-APR-18:10 | 0.00 |
May | 0.544479E+10 | 0.134883E+10 | 744.00 | 0.542491E+10 | 19886841.45 | 0.00 | 0.44 | 31-MAY-24:00 | 0.16 | 05-MAY-06:05 | 3939.38 | 31-MAY-24:00 | 3939.38 | 31-MAY-24:00 | 138.26 | 23-MAY-16:00 | 905.45 | 31-MAY-24:00 | 0.00 |
June | 0.105880E+11 | 0.246954E+10 | 720.00 | 0.105024E+11 | 85641001.73 | 0.00 | 0.62 | 30-JUN-24:00 | 0.40 | 01-JUN-06:10 | 5777.56 | 30-JUN-24:00 | 5777.56 | 30-JUN-24:00 | 226.46 | 26-JUN-17:50 | 1489.99 | 13-JUN-16:00 | 0.00 |
July | 0.161970E+11 | 0.370009E+10 | 744.00 | 0.160798E+11 | 0.117245E+09 | 0.00 | 0.82 | 31-JUL-24:00 | 0.59 | 01-JUL-06:30 | 7836.62 | 31-JUL-24:00 | 7836.62 | 31-JUL-24:00 | 252.74 | 18-JUL-16:00 | 2332.75 | 22-JUL-18:35 | 0.00 |
August | 0.212244E+11 | 0.479928E+10 | 744.00 | 0.210896E+11 | 0.134845E+09 | 0.00 | 0.95 | 14-AUG-18:00 | 0.30 | 31-AUG-24:00 | 8831.79 | 13-AUG-18:14 | 8809.39 | 13-AUG-18:05 | 270.90 | 08-AUG-13:30 | 2679.04 | 14-AUG-18:00 | 0.00 |
September | 0.545002E+10 | 0.133728E+10 | 720.00 | 0.538528E+10 | 64740576.02 | 0.00 | 0.44 | 30-SEP-24:00 | 0.18 | 21-SEP-06:10 | 3798.44 | 30-SEP-24:00 | 3798.44 | 30-SEP-24:00 | 155.28 | 19-SEP-16:00 | 905.73 | 30-SEP-24:00 | 0.00 |
October | 0.102552E+11 | 0.240290E+10 | 744.00 | 0.102288E+11 | 26435145.81 | 0.00 | 0.63 | 31-OCT-24:00 | 0.37 | 28-OCT-07:00 | 5649.39 | 31-OCT-24:00 | 5649.39 | 31-OCT-24:00 | 128.30 | 17-OCT-15:30 | 1291.05 | 31-OCT-24:00 | 0.00 |
November | 0.145890E+11 | 0.331083E+10 | 720.00 | 0.145732E+11 | 15774946.13 | 0.00 | 0.69 | 19-NOV-16:05 | 0.57 | 25-NOV-08:00 | 6194.55 | 19-NOV-16:05 | 6194.55 | 19-NOV-16:05 | 143.00 | 08-NOV-15:10 | 1407.81 | 19-NOV-16:05 | 0.00 |
December | 0.198491E+11 | 0.442887E+10 | 744.00 | 0.198490E+11 | 118732.25 | 0.00 | 0.89 | 31-DEC-15:15 | 0.76 | 02-DEC-18:00 | 7962.87 | 25-DEC-15:15 | 7962.87 | 25-DEC-15:15 | 38.70 | 20-DEC-17:10 | 1803.71 | 31-DEC-15:15 | 0.00 |
Annual Sum or Average | 0.151644E+12 | 0.348917E+11 | 8760.00 | 0.151176E+12 | 0.468320E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.419350E+10 | 0.108059E+10 | 672.00 | 0.419200E+10 | 118732.25 | 0.00 | 0.28 | 0.11 | 2324.99 | 2319.22 | 38.70 | 562.21 | 0.00 | ||||||
Maximum of Months | 0.212244E+11 | 0.479928E+10 | 744.00 | 0.210896E+11 | 0.134845E+09 | 0.00 | 1.00 | 0.76 | 8945.29 | 8945.29 | 270.90 | 2679.04 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.212053E+11 | 0.577807E+10 | 737.17 | 0.211911E+11 | 14241843.18 | 0.00 | 0.25 | 19-JAN-16:20 | 0.00 | 02-JAN-04:03 | 19731.30 | 19-JAN-16:20 | 19731.30 | 19-JAN-16:20 | 499.54 | 18-JAN-16:30 | 4838.46 | 19-JAN-16:20 | 0.00 |
February | 0.672217E+11 | 0.164991E+11 | 672.00 | 0.672085E+11 | 13183498.54 | 0.00 | 0.48 | 17-FEB-17:00 | 0.25 | 13-FEB-07:10 | 40549.58 | 27-FEB-17:00 | 40549.58 | 27-FEB-17:00 | 555.05 | 07-FEB-16:00 | 9401.62 | 17-FEB-17:00 | 0.00 |
March | 0.127481E+12 | 0.296757E+11 | 744.00 | 0.127478E+12 | 3146338.42 | 0.00 | 0.79 | 31-MAR-23:40 | 0.49 | 27-MAR-06:10 | 67991.42 | 31-MAR-23:40 | 67991.42 | 31-MAR-23:40 | 541.83 | 20-MAR-06:10 | 15397.86 | 31-MAR-23:40 | 0.00 |
April | 0.183652E+12 | 0.410530E+11 | 720.00 | 0.183646E+12 | 5671091.77 | 0.00 | 0.99 | 30-APR-18:10 | 0.27 | 30-APR-23:55 | 85084.09 | 30-APR-18:05 | 85084.09 | 30-APR-18:05 | 675.69 | 28-APR-11:00 | 25120.54 | 30-APR-18:10 | 0.00 |
May | 0.442748E+11 | 0.111122E+11 | 744.00 | 0.440789E+11 | 0.195830E+09 | 0.00 | 0.42 | 31-MAY-23:40 | 0.10 | 05-MAY-06:05 | 35906.91 | 31-MAY-23:40 | 35906.91 | 31-MAY-23:40 | 1375.65 | 23-MAY-16:00 | 8293.72 | 31-MAY-23:40 | 0.00 |
June | 0.961034E+11 | 0.225445E+11 | 720.00 | 0.952545E+11 | 0.848918E+09 | 0.00 | 0.59 | 30-JUN-23:40 | 0.36 | 08-JUN-06:05 | 52367.51 | 30-JUN-23:40 | 52367.51 | 30-JUN-23:40 | 2233.10 | 26-JUN-17:50 | 14139.49 | 13-JUN-16:00 | 0.00 |
July | 0.149975E+12 | 0.344245E+11 | 744.00 | 0.148816E+12 | 0.115941E+10 | 0.00 | 0.80 | 31-JUL-23:50 | 0.55 | 01-JUL-06:40 | 73457.10 | 31-JUL-23:50 | 73457.10 | 31-JUL-23:50 | 2493.73 | 18-JUL-16:00 | 22187.99 | 22-JUL-18:35 | 0.00 |
August | 0.198391E+12 | 0.450458E+11 | 744.00 | 0.197057E+12 | 0.133460E+10 | 0.00 | 0.94 | 14-AUG-18:00 | 0.24 | 31-AUG-24:00 | 82336.99 | 13-AUG-18:03 | 82126.87 | 13-AUG-18:05 | 2686.56 | 08-AUG-13:30 | 25555.13 | 14-AUG-18:00 | 0.00 |
September | 0.450731E+11 | 0.111968E+11 | 720.00 | 0.444431E+11 | 0.629994E+09 | 0.00 | 0.41 | 30-SEP-23:30 | 0.13 | 07-SEP-06:05 | 33616.10 | 30-SEP-23:30 | 33616.10 | 30-SEP-23:30 | 1561.25 | 19-SEP-16:00 | 8079.83 | 30-SEP-23:30 | 0.00 |
October | 0.841901E+11 | 0.200087E+11 | 744.00 | 0.839289E+11 | 0.261143E+09 | 0.00 | 0.57 | 31-OCT-24:00 | 0.29 | 30-OCT-06:10 | 48535.29 | 31-OCT-24:00 | 48535.29 | 31-OCT-24:00 | 1268.56 | 17-OCT-15:30 | 11237.96 | 31-OCT-24:00 | 0.00 |
November | 0.120536E+12 | 0.278054E+11 | 720.00 | 0.120379E+12 | 0.157386E+09 | 0.00 | 0.65 | 03-NOV-16:00 | 0.46 | 27-NOV-07:10 | 56374.47 | 10-NOV-16:10 | 56164.93 | 10-NOV-16:00 | 1421.73 | 08-NOV-15:10 | 12672.76 | 03-NOV-16:00 | 0.00 |
December | 0.164812E+12 | 0.374673E+11 | 744.00 | 0.164811E+12 | 1472180.32 | 0.00 | 0.80 | 29-DEC-15:50 | 0.63 | 26-DEC-07:10 | 70491.68 | 21-DEC-15:20 | 70491.68 | 21-DEC-15:20 | 391.96 | 20-DEC-17:10 | 15705.04 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.130292E+13 | 0.302611E+12 | 8753.17 | 0.129829E+13 | 0.462500E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.212053E+11 | 0.577807E+10 | 672.00 | 0.211911E+11 | 1472180.32 | 0.00 | 0.25 | 0.00 | 19731.30 | 19731.30 | 391.96 | 4838.46 | 0.00 | ||||||
Maximum of Months | 0.198391E+12 | 0.450458E+11 | 744.00 | 0.197057E+12 | 0.133460E+10 | 0.00 | 0.99 | 0.63 | 85084.09 | 85084.09 | 2686.56 | 25555.13 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.703887E+09 | 0.203359E+09 | 412.85 | 0.702965E+09 | 922226.31 | 0.00 | 0.23 | 19-JAN-16:30 | 0.00 | 01-JAN-00:03 | 1876.94 | 19-JAN-16:30 | 1876.94 | 19-JAN-16:30 | 45.81 | 18-JAN-16:40 | 462.47 | 19-JAN-16:30 | 0.00 |
February | 0.503794E+10 | 0.126292E+10 | 672.00 | 0.503669E+10 | 1246495.80 | 0.00 | 0.46 | 17-FEB-17:00 | 0.09 | 20-FEB-08:10 | 3842.15 | 27-FEB-17:00 | 3842.15 | 27-FEB-17:00 | 52.83 | 07-FEB-16:30 | 916.25 | 17-FEB-17:00 | 0.00 |
March | 0.112298E+11 | 0.264990E+10 | 744.00 | 0.112295E+11 | 299924.34 | 0.00 | 0.73 | 31-MAR-23:20 | 0.36 | 06-MAR-05:12 | 6341.00 | 31-MAR-23:20 | 6341.00 | 31-MAR-23:20 | 43.30 | 20-MAR-06:10 | 1451.10 | 31-MAR-23:20 | 0.00 |
April | 0.175431E+11 | 0.395091E+10 | 720.00 | 0.175426E+11 | 553795.46 | 0.00 | 0.99 | 30-APR-18:00 | 0.25 | 30-APR-23:53 | 8622.94 | 30-APR-17:56 | 8622.94 | 30-APR-17:53 | 67.40 | 28-APR-11:00 | 2545.41 | 30-APR-18:00 | 0.00 |
May | 0.368298E+10 | 0.937269E+09 | 743.14 | 0.366356E+10 | 19414943.66 | 0.00 | 0.40 | 31-MAY-23:20 | 0.00 | 05-MAY-01:45 | 3444.85 | 31-MAY-23:20 | 3444.85 | 31-MAY-23:20 | 138.42 | 23-MAY-16:00 | 799.71 | 31-MAY-23:20 | 0.00 |
June | 0.922992E+10 | 0.217672E+10 | 720.00 | 0.914523E+10 | 84689964.95 | 0.00 | 0.56 | 30-JUN-23:20 | 0.29 | 08-JUN-06:05 | 4990.98 | 30-JUN-23:20 | 4990.98 | 30-JUN-23:20 | 224.29 | 26-JUN-17:50 | 1448.60 | 13-JUN-16:00 | 0.00 |
July | 0.146794E+11 | 0.338505E+10 | 744.00 | 0.145636E+11 | 0.115776E+09 | 0.00 | 0.81 | 22-JUL-18:50 | 0.50 | 31-JUL-06:20 | 7192.90 | 31-JUL-23:20 | 7192.90 | 31-JUL-23:20 | 249.75 | 18-JUL-16:00 | 2276.37 | 22-JUL-18:35 | 0.00 |
August | 0.195075E+11 | 0.444978E+10 | 744.00 | 0.193744E+11 | 0.133152E+09 | 0.00 | 0.94 | 14-AUG-18:00 | 0.21 | 31-AUG-24:00 | 8314.10 | 13-AUG-18:03 | 8292.97 | 13-AUG-18:05 | 268.09 | 08-AUG-13:30 | 2582.16 | 14-AUG-18:00 | 0.00 |
September | 0.382994E+10 | 0.964751E+09 | 719.75 | 0.376794E+10 | 62005489.78 | 0.00 | 0.35 | 30-SEP-23:10 | 0.00 | 03-SEP-05:45 | 2815.32 | 30-SEP-23:10 | 2815.32 | 30-SEP-23:10 | 157.28 | 19-SEP-16:00 | 743.06 | 13-SEP-17:00 | 0.00 |
October | 0.697031E+10 | 0.168284E+10 | 744.00 | 0.694482E+10 | 25487281.14 | 0.00 | 0.51 | 31-OCT-23:20 | 0.18 | 23-OCT-06:10 | 4338.94 | 31-OCT-23:20 | 4338.94 | 31-OCT-23:20 | 126.79 | 17-OCT-15:40 | 1017.88 | 31-OCT-23:20 | 0.00 |
November | 0.103439E+11 | 0.242321E+10 | 720.00 | 0.103284E+11 | 15496370.27 | 0.00 | 0.63 | 03-NOV-16:00 | 0.31 | 27-NOV-05:17 | 5567.60 | 10-NOV-16:10 | 5546.04 | 10-NOV-16:10 | 141.41 | 08-NOV-15:10 | 1247.74 | 03-NOV-16:00 | 0.00 |
December | 0.145409E+11 | 0.335678E+10 | 744.00 | 0.145407E+11 | 133966.49 | 0.00 | 0.76 | 29-DEC-15:50 | 0.46 | 26-DEC-04:50 | 6837.12 | 21-DEC-15:20 | 6837.12 | 21-DEC-15:20 | 37.94 | 20-DEC-17:10 | 1511.14 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.117300E+12 | 0.274435E+11 | 8427.74 | 0.116840E+12 | 0.459179E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.703887E+09 | 0.203359E+09 | 412.85 | 0.702965E+09 | 133966.49 | 0.00 | 0.23 | 0.00 | 1876.94 | 1876.94 | 37.94 | 462.47 | 0.00 | ||||||
Maximum of Months | 0.195075E+11 | 0.444978E+10 | 744.00 | 0.193744E+11 | 0.133152E+09 | 0.00 | 0.99 | 0.50 | 8622.94 | 8622.94 | 268.09 | 2582.16 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.38 | 653.05 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.51 | 611.54 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.54 | 513.24 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.53 | 404.01 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 239.66 | 312.67 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 355.24 | 245.54 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 358.93 | 228.14 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 274.11 | 257.94 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 176.16 | 340.28 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.65 | 474.17 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.98 | 596.76 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 720.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 142.39 | 445.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 228.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 358.93 | 720.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.38 | 653.05 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.51 | 611.54 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.54 | 513.24 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.53 | 404.01 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 239.66 | 312.67 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 355.24 | 245.54 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 358.93 | 228.14 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 274.11 | 257.94 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 176.16 | 340.28 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.65 | 474.17 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.98 | 596.76 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 720.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 142.39 | 445.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 228.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 358.93 | 720.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.38 | 653.05 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.51 | 611.54 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.54 | 513.24 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.53 | 404.01 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 239.66 | 312.67 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 355.24 | 245.54 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 358.93 | 228.14 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 274.11 | 257.94 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 176.16 | 340.28 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.65 | 474.17 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.98 | 596.76 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 720.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 142.39 | 445.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 228.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 358.93 | 720.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.38 | 653.05 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.51 | 611.54 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.54 | 513.24 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.53 | 404.01 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 239.66 | 312.67 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 355.24 | 245.54 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 358.93 | 228.14 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 274.11 | 257.94 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 176.16 | 340.28 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.65 | 474.17 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.98 | 596.76 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 720.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 142.39 | 445.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 228.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 358.93 | 720.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.95 | 0.00 | 91.95 | 2.38 | 653.02 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.51 | 611.51 | 0.00 | 0.00 | 0.00 |
March | 198.70 | 0.00 | 198.70 | 45.54 | 513.22 | 0.00 | 0.00 | 0.00 |
April | 323.52 | 1.45 | 322.07 | 183.52 | 403.99 | 0.00 | 0.00 | 0.00 |
May | 404.48 | 19.51 | 384.96 | 239.65 | 312.66 | 0.00 | 0.00 | 0.00 |
June | 447.12 | 28.04 | 419.09 | 355.23 | 245.53 | 0.00 | 0.00 | 0.00 |
July | 424.12 | 24.18 | 399.94 | 358.92 | 228.13 | 0.00 | 0.00 | 0.00 |
August | 333.38 | 5.22 | 328.16 | 274.10 | 257.93 | 0.00 | 0.00 | 0.00 |
September | 253.75 | 0.06 | 253.69 | 176.15 | 340.26 | 0.00 | 0.00 | 0.00 |
October | 162.60 | 0.00 | 162.60 | 51.64 | 474.15 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.98 | 596.74 | 0.00 | 0.00 | 0.00 |
December | 66.53 | 0.00 | 66.53 | 0.00 | 720.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.08 | 6.58 | 239.49 | 142.39 | 445.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.53 | 0.00 | 66.53 | 0.00 | 228.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.12 | 28.04 | 419.09 | 358.92 | 720.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.84 | 83.89 | 124.95 | 109.25 | 665.40 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.38 | 184.63 | 623.39 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.93 | 518.77 | 0.00 | 0.00 | 0.00 |
April | 873.82 | 410.61 | 463.21 | 889.71 | 411.08 | 0.00 | 0.00 | 0.00 |
May | 918.79 | 400.67 | 518.12 | 912.87 | 350.22 | 0.00 | 0.00 | 0.00 |
June | 909.44 | 363.22 | 546.22 | 968.46 | 272.76 | 0.00 | 0.00 | 0.00 |
July | 928.36 | 394.55 | 533.80 | 1033.94 | 251.84 | 0.00 | 0.00 | 0.00 |
August | 879.41 | 420.18 | 459.24 | 1009.40 | 272.97 | 0.00 | 0.00 | 0.00 |
September | 791.94 | 421.12 | 370.82 | 875.60 | 352.32 | 0.00 | 0.00 | 0.00 |
October | 382.28 | 158.43 | 223.85 | 320.45 | 490.13 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 103.05 | 603.52 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.71 | 726.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.89 | 246.54 | 327.35 | 555.33 | 460.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.71 | 251.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.36 | 421.12 | 546.22 | 1033.94 | 726.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.84 | 83.89 | 124.95 | 109.25 | 665.40 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.38 | 184.63 | 623.39 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.93 | 518.77 | 0.00 | 0.00 | 0.00 |
April | 873.82 | 410.61 | 463.21 | 889.71 | 411.08 | 0.00 | 0.00 | 0.00 |
May | 918.79 | 400.67 | 518.12 | 912.87 | 350.22 | 0.00 | 0.00 | 0.00 |
June | 909.44 | 363.22 | 546.22 | 968.46 | 272.76 | 0.00 | 0.00 | 0.00 |
July | 928.36 | 394.55 | 533.80 | 1033.94 | 251.84 | 0.00 | 0.00 | 0.00 |
August | 879.41 | 420.18 | 459.24 | 1009.40 | 272.97 | 0.00 | 0.00 | 0.00 |
September | 791.94 | 421.12 | 370.82 | 875.60 | 352.32 | 0.00 | 0.00 | 0.00 |
October | 382.28 | 158.43 | 223.85 | 320.45 | 490.13 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 103.05 | 603.52 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.71 | 726.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.89 | 246.54 | 327.35 | 555.33 | 460.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.71 | 251.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.36 | 421.12 | 546.22 | 1033.94 | 726.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.83 | 83.89 | 124.95 | 109.25 | 665.39 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.37 | 184.63 | 623.38 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.92 | 518.76 | 0.00 | 0.00 | 0.00 |
April | 873.80 | 410.61 | 463.20 | 889.69 | 411.08 | 0.00 | 0.00 | 0.00 |
May | 918.78 | 400.66 | 518.11 | 912.85 | 350.21 | 0.00 | 0.00 | 0.00 |
June | 909.42 | 363.21 | 546.21 | 968.44 | 272.75 | 0.00 | 0.00 | 0.00 |
July | 928.34 | 394.54 | 533.79 | 1033.92 | 251.84 | 0.00 | 0.00 | 0.00 |
August | 879.40 | 420.17 | 459.23 | 1009.38 | 272.97 | 0.00 | 0.00 | 0.00 |
September | 791.93 | 421.11 | 370.82 | 875.58 | 352.32 | 0.00 | 0.00 | 0.00 |
October | 382.27 | 158.42 | 223.85 | 320.45 | 490.12 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 103.04 | 603.51 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.71 | 726.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.88 | 246.53 | 327.34 | 555.32 | 460.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.71 | 251.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.34 | 421.11 | 546.21 | 1033.92 | 726.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 500.35 | 556.23 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.75 | 545.76 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.44 | 300.33 | 467.51 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.78 | 404.29 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 697.57 | 342.26 | 0.00 | 0.00 | 0.00 |
June | 623.73 | 150.98 | 472.75 | 669.46 | 266.22 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 783.00 | 248.91 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.64 | 272.24 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1144.08 | 339.71 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.77 | 267.17 | 694.56 | 442.16 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 439.39 | 528.26 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.83 | 632.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 672.37 | 419.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 300.33 | 248.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1144.08 | 632.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 500.35 | 556.23 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.75 | 545.76 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.43 | 300.33 | 467.51 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.78 | 404.29 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 697.57 | 342.26 | 0.00 | 0.00 | 0.00 |
June | 623.72 | 150.98 | 472.75 | 669.46 | 266.22 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 783.00 | 248.91 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.64 | 272.24 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1144.07 | 339.71 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.76 | 267.17 | 694.56 | 442.16 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 439.39 | 528.26 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.83 | 632.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 672.37 | 419.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 300.33 | 248.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1144.07 | 632.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 500.35 | 556.23 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.75 | 545.76 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.44 | 300.33 | 467.51 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.78 | 404.29 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 697.57 | 342.26 | 0.00 | 0.00 | 0.00 |
June | 623.73 | 150.98 | 472.75 | 669.46 | 266.22 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 783.00 | 248.91 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.64 | 272.24 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1144.08 | 339.71 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.77 | 267.17 | 694.56 | 442.16 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 439.39 | 528.26 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.83 | 632.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 672.37 | 419.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 300.33 | 248.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1144.08 | 632.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 500.35 | 556.23 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.75 | 545.76 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.43 | 300.33 | 467.51 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.78 | 404.29 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 697.57 | 342.26 | 0.00 | 0.00 | 0.00 |
June | 623.72 | 150.98 | 472.75 | 669.46 | 266.22 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 783.00 | 248.91 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.64 | 272.24 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1144.07 | 339.71 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.76 | 267.17 | 694.56 | 442.16 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 439.39 | 528.26 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.83 | 632.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 672.37 | 419.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 300.33 | 248.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1144.07 | 632.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.05 | 337.94 | 184.10 | 500.33 | 556.21 | 0.00 | 0.00 | 0.00 |
February | 637.58 | 389.06 | 248.52 | 629.73 | 545.73 | 0.00 | 0.00 | 0.00 |
March | 394.20 | 114.77 | 279.42 | 300.31 | 467.49 | 0.00 | 0.00 | 0.00 |
April | 818.58 | 369.99 | 448.59 | 912.75 | 404.27 | 0.00 | 0.00 | 0.00 |
May | 677.04 | 220.42 | 456.62 | 697.54 | 342.24 | 0.00 | 0.00 | 0.00 |
June | 623.70 | 150.97 | 472.73 | 669.43 | 266.21 | 0.00 | 0.00 | 0.00 |
July | 675.77 | 211.62 | 464.14 | 782.97 | 248.90 | 0.00 | 0.00 | 0.00 |
August | 791.85 | 356.20 | 435.65 | 974.60 | 272.23 | 0.00 | 0.00 | 0.00 |
September | 935.76 | 548.18 | 387.58 | 1144.03 | 339.70 | 0.00 | 0.00 | 0.00 |
October | 642.91 | 375.75 | 267.16 | 694.53 | 442.15 | 0.00 | 0.00 | 0.00 |
November | 455.82 | 277.29 | 178.53 | 439.37 | 528.24 | 0.00 | 0.00 | 0.00 |
December | 361.28 | 231.47 | 129.81 | 333.82 | 632.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.08 | 297.48 | 329.60 | 672.35 | 419.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.28 | 114.77 | 129.81 | 300.31 | 248.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.76 | 548.18 | 472.73 | 1144.03 | 632.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.09 | 67.10 | 135.99 | 105.98 | 714.99 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.43 | 701.15 | 0.00 | 0.00 | 0.00 |
March | 325.13 | 62.20 | 262.93 | 159.29 | 599.52 | 0.00 | 0.00 | 0.00 |
April | 767.16 | 304.72 | 462.44 | 739.53 | 497.94 | 0.00 | 0.00 | 0.00 |
May | 900.05 | 365.99 | 534.06 | 884.08 | 395.26 | 0.00 | 0.00 | 0.00 |
June | 971.96 | 400.12 | 571.84 | 1036.78 | 321.85 | 0.00 | 0.00 | 0.00 |
July | 989.90 | 436.45 | 553.45 | 1099.79 | 308.40 | 0.00 | 0.00 | 0.00 |
August | 831.45 | 359.99 | 471.45 | 928.67 | 342.75 | 0.00 | 0.00 | 0.00 |
September | 667.04 | 299.12 | 367.93 | 719.46 | 403.11 | 0.00 | 0.00 | 0.00 |
October | 355.84 | 127.96 | 227.88 | 283.58 | 559.23 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.36 | 98.37 | 705.69 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.65 | 868.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.65 | 221.31 | 335.34 | 529.46 | 534.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.65 | 308.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.90 | 436.45 | 571.84 | 1099.79 | 868.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.09 | 67.10 | 135.99 | 105.98 | 714.99 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.43 | 701.15 | 0.00 | 0.00 | 0.00 |
March | 325.13 | 62.20 | 262.93 | 159.29 | 599.52 | 0.00 | 0.00 | 0.00 |
April | 767.16 | 304.72 | 462.44 | 739.53 | 497.94 | 0.00 | 0.00 | 0.00 |
May | 900.05 | 365.99 | 534.06 | 884.08 | 395.26 | 0.00 | 0.00 | 0.00 |
June | 971.96 | 400.12 | 571.84 | 1036.78 | 321.85 | 0.00 | 0.00 | 0.00 |
July | 989.90 | 436.45 | 553.45 | 1099.79 | 308.40 | 0.00 | 0.00 | 0.00 |
August | 831.45 | 359.99 | 471.45 | 928.67 | 342.75 | 0.00 | 0.00 | 0.00 |
September | 667.04 | 299.12 | 367.93 | 719.46 | 403.11 | 0.00 | 0.00 | 0.00 |
October | 355.84 | 127.96 | 227.88 | 283.58 | 559.23 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.36 | 98.37 | 705.69 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.65 | 868.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.65 | 221.31 | 335.34 | 529.46 | 534.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.65 | 308.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.90 | 436.45 | 571.84 | 1099.79 | 868.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.08 | 67.10 | 135.98 | 105.98 | 714.97 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.42 | 701.14 | 0.00 | 0.00 | 0.00 |
March | 325.12 | 62.20 | 262.93 | 159.28 | 599.51 | 0.00 | 0.00 | 0.00 |
April | 767.14 | 304.72 | 462.43 | 739.51 | 497.93 | 0.00 | 0.00 | 0.00 |
May | 900.04 | 365.99 | 534.05 | 884.06 | 395.26 | 0.00 | 0.00 | 0.00 |
June | 971.94 | 400.11 | 571.83 | 1036.77 | 321.84 | 0.00 | 0.00 | 0.00 |
July | 989.88 | 436.44 | 553.44 | 1099.77 | 308.39 | 0.00 | 0.00 | 0.00 |
August | 831.43 | 359.99 | 471.45 | 928.66 | 342.74 | 0.00 | 0.00 | 0.00 |
September | 667.03 | 299.11 | 367.92 | 719.45 | 403.11 | 0.00 | 0.00 | 0.00 |
October | 355.83 | 127.96 | 227.88 | 283.58 | 559.22 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.35 | 98.37 | 705.68 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.64 | 868.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.64 | 221.31 | 335.33 | 529.45 | 534.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.64 | 308.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.88 | 436.44 | 571.83 | 1099.77 | 868.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.78 | 0.00 | 459.78 | 26.58 | 2880.26 | 0.00 | 0.00 | 0.00 |
February | 717.96 | 0.00 | 717.96 | 90.88 | 2693.68 | 0.00 | 0.00 | 0.00 |
March | 993.53 | 0.00 | 993.53 | 298.74 | 2253.89 | 0.00 | 0.00 | 0.00 |
April | 1617.62 | 7.24 | 1610.38 | 981.12 | 1835.48 | 0.00 | 0.00 | 0.00 |
May | 2022.44 | 97.57 | 1924.87 | 1253.62 | 1458.60 | 0.00 | 0.00 | 0.00 |
June | 2235.68 | 140.19 | 2095.49 | 1805.24 | 1157.90 | 0.00 | 0.00 | 0.00 |
July | 2120.67 | 120.91 | 1999.76 | 1843.00 | 1063.84 | 0.00 | 0.00 | 0.00 |
August | 1666.95 | 26.12 | 1640.83 | 1417.32 | 1189.13 | 0.00 | 0.00 | 0.00 |
September | 1268.78 | 0.28 | 1268.50 | 925.24 | 1579.77 | 0.00 | 0.00 | 0.00 |
October | 813.02 | 0.00 | 813.02 | 317.55 | 2091.58 | 0.00 | 0.00 | 0.00 |
November | 488.51 | 0.00 | 488.51 | 44.74 | 2541.87 | 0.00 | 0.00 | 0.00 |
December | 332.67 | 0.00 | 332.67 | 1.42 | 3059.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1230.42 | 32.92 | 1197.50 | 753.81 | 1980.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.67 | 0.00 | 332.67 | 1.42 | 1063.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.68 | 140.19 | 2095.49 | 1843.00 | 3059.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.51 | 251.67 | 374.84 | 353.56 | 1805.72 | 0.00 | 0.00 | 0.00 |
February | 934.23 | 345.11 | 589.12 | 585.91 | 1707.89 | 0.00 | 0.00 | 0.00 |
March | 976.29 | 192.39 | 783.90 | 569.95 | 1418.70 | 0.00 | 0.00 | 0.00 |
April | 2621.43 | 1231.83 | 1389.60 | 2671.52 | 1173.95 | 0.00 | 0.00 | 0.00 |
May | 2756.35 | 1202.00 | 1554.35 | 2738.02 | 998.51 | 0.00 | 0.00 | 0.00 |
June | 2728.28 | 1089.65 | 1638.63 | 2897.60 | 785.79 | 0.00 | 0.00 | 0.00 |
July | 2785.04 | 1183.64 | 1601.40 | 3092.14 | 727.30 | 0.00 | 0.00 | 0.00 |
August | 2638.22 | 1260.51 | 1377.70 | 3020.96 | 791.21 | 0.00 | 0.00 | 0.00 |
September | 2375.80 | 1263.34 | 1112.46 | 2624.54 | 1009.12 | 0.00 | 0.00 | 0.00 |
October | 1146.83 | 475.28 | 671.55 | 987.46 | 1340.55 | 0.00 | 0.00 | 0.00 |
November | 597.88 | 203.77 | 394.11 | 334.31 | 1608.85 | 0.00 | 0.00 | 0.00 |
December | 443.10 | 164.74 | 278.36 | 218.91 | 1941.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.65 | 739.61 | 982.04 | 1678.51 | 1273.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 443.10 | 164.74 | 278.36 | 218.91 | 727.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2785.04 | 1263.34 | 1638.63 | 3092.14 | 1941.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2610.30 | 1689.76 | 920.55 | 2516.03 | 2664.71 | 0.00 | 0.00 | 0.00 |
February | 3188.01 | 1945.37 | 1242.64 | 3157.48 | 2623.11 | 0.00 | 0.00 | 0.00 |
March | 1971.04 | 573.88 | 1397.16 | 1534.19 | 2198.22 | 0.00 | 0.00 | 0.00 |
April | 4093.02 | 1850.00 | 2243.02 | 4560.44 | 1941.89 | 0.00 | 0.00 | 0.00 |
May | 3385.31 | 1102.15 | 2283.16 | 3484.28 | 1655.04 | 0.00 | 0.00 | 0.00 |
June | 3118.59 | 754.88 | 2363.71 | 3349.57 | 1279.71 | 0.00 | 0.00 | 0.00 |
July | 3378.93 | 1058.15 | 2320.78 | 3919.49 | 1190.80 | 0.00 | 0.00 | 0.00 |
August | 3959.37 | 1781.07 | 2178.30 | 4869.26 | 1306.86 | 0.00 | 0.00 | 0.00 |
September | 4678.94 | 2741.00 | 1937.94 | 5695.37 | 1663.39 | 0.00 | 0.00 | 0.00 |
October | 3214.62 | 1878.80 | 1335.82 | 3475.55 | 2109.20 | 0.00 | 0.00 | 0.00 |
November | 2279.17 | 1386.48 | 892.69 | 2213.87 | 2467.87 | 0.00 | 0.00 | 0.00 |
December | 1806.45 | 1157.40 | 649.05 | 1697.84 | 2936.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3135.51 | 1487.45 | 1648.07 | 3368.17 | 1999.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1806.45 | 573.88 | 649.05 | 1534.19 | 1190.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4678.94 | 2741.00 | 2363.71 | 5695.37 | 2936.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.25 | 201.30 | 407.95 | 349.91 | 1880.31 | 0.00 | 0.00 | 0.00 |
February | 1078.71 | 455.46 | 623.24 | 824.38 | 1807.04 | 0.00 | 0.00 | 0.00 |
March | 975.38 | 186.59 | 788.79 | 560.18 | 1480.44 | 0.00 | 0.00 | 0.00 |
April | 2301.45 | 914.15 | 1387.29 | 2300.71 | 1284.64 | 0.00 | 0.00 | 0.00 |
May | 2700.13 | 1097.97 | 1602.16 | 2691.25 | 1094.10 | 0.00 | 0.00 | 0.00 |
June | 2915.85 | 1200.34 | 1715.50 | 3144.90 | 873.80 | 0.00 | 0.00 | 0.00 |
July | 2969.66 | 1309.33 | 1660.33 | 3351.92 | 817.56 | 0.00 | 0.00 | 0.00 |
August | 2494.32 | 1079.97 | 1414.35 | 2844.17 | 889.86 | 0.00 | 0.00 | 0.00 |
September | 2001.11 | 897.34 | 1103.77 | 2196.23 | 1106.14 | 0.00 | 0.00 | 0.00 |
October | 1067.51 | 383.87 | 683.64 | 910.53 | 1420.23 | 0.00 | 0.00 | 0.00 |
November | 577.70 | 168.64 | 409.06 | 337.94 | 1703.97 | 0.00 | 0.00 | 0.00 |
December | 327.00 | 69.00 | 257.99 | 112.60 | 2069.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.94 | 663.94 | 1006.00 | 1638.12 | 1366.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.00 | 69.00 | 257.99 | 112.60 | 817.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2969.66 | 1309.33 | 1715.50 | 3351.92 | 2069.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.78 | 0.00 | 459.78 | 43.55 | 2627.40 | 0.00 | 0.00 | 0.00 |
February | 717.96 | 0.00 | 717.96 | 130.14 | 2453.99 | 0.00 | 0.00 | 0.00 |
March | 993.53 | 0.00 | 993.53 | 351.18 | 2061.43 | 0.00 | 0.00 | 0.00 |
April | 1617.62 | 7.24 | 1610.38 | 1027.29 | 1716.15 | 0.00 | 0.00 | 0.00 |
May | 2022.44 | 97.57 | 1924.87 | 1310.49 | 1368.89 | 0.00 | 0.00 | 0.00 |
June | 2235.68 | 140.19 | 2095.49 | 1828.48 | 1110.35 | 0.00 | 0.00 | 0.00 |
July | 2120.67 | 120.91 | 1999.76 | 1860.89 | 1024.62 | 0.00 | 0.00 | 0.00 |
August | 1666.95 | 26.12 | 1640.83 | 1434.15 | 1141.31 | 0.00 | 0.00 | 0.00 |
September | 1268.78 | 0.28 | 1268.50 | 963.95 | 1480.47 | 0.00 | 0.00 | 0.00 |
October | 813.02 | 0.00 | 813.02 | 370.78 | 1880.99 | 0.00 | 0.00 | 0.00 |
November | 488.51 | 0.00 | 488.51 | 67.55 | 2288.82 | 0.00 | 0.00 | 0.00 |
December | 332.67 | 0.00 | 332.67 | 8.37 | 2807.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1230.42 | 32.92 | 1197.50 | 786.37 | 1827.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.67 | 0.00 | 332.67 | 8.37 | 1024.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.68 | 140.19 | 2095.49 | 1860.89 | 2807.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.51 | 251.67 | 374.84 | 377.15 | 1653.94 | 0.00 | 0.00 | 0.00 |
February | 934.23 | 345.11 | 589.12 | 622.39 | 1566.58 | 0.00 | 0.00 | 0.00 |
March | 976.29 | 192.39 | 783.90 | 607.22 | 1310.24 | 0.00 | 0.00 | 0.00 |
April | 2621.43 | 1231.83 | 1389.60 | 2693.72 | 1113.47 | 0.00 | 0.00 | 0.00 |
May | 2756.35 | 1202.00 | 1554.35 | 2760.18 | 949.62 | 0.00 | 0.00 | 0.00 |
June | 2728.28 | 1089.65 | 1638.63 | 2904.20 | 759.97 | 0.00 | 0.00 | 0.00 |
July | 2785.04 | 1183.64 | 1601.40 | 3093.84 | 707.03 | 0.00 | 0.00 | 0.00 |
August | 2638.22 | 1260.51 | 1377.70 | 3023.00 | 768.31 | 0.00 | 0.00 | 0.00 |
September | 2375.80 | 1263.34 | 1112.46 | 2640.58 | 961.19 | 0.00 | 0.00 | 0.00 |
October | 1146.83 | 475.28 | 671.55 | 1021.42 | 1223.56 | 0.00 | 0.00 | 0.00 |
November | 597.88 | 203.77 | 394.11 | 358.12 | 1462.60 | 0.00 | 0.00 | 0.00 |
December | 443.10 | 164.74 | 278.36 | 235.23 | 1789.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.65 | 739.61 | 982.04 | 1698.59 | 1186.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 443.10 | 164.74 | 278.36 | 235.23 | 707.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2785.04 | 1263.34 | 1638.63 | 3093.84 | 1789.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2610.30 | 1689.76 | 920.55 | 2573.21 | 2436.47 | 0.00 | 0.00 | 0.00 |
February | 3188.01 | 1945.37 | 1242.64 | 3218.83 | 2410.33 | 0.00 | 0.00 | 0.00 |
March | 1971.04 | 573.88 | 1397.16 | 1593.13 | 2023.30 | 0.00 | 0.00 | 0.00 |
April | 4093.02 | 1850.00 | 2243.02 | 4589.27 | 1837.17 | 0.00 | 0.00 | 0.00 |
May | 3385.31 | 1102.15 | 2283.16 | 3516.19 | 1563.10 | 0.00 | 0.00 | 0.00 |
June | 3118.59 | 754.88 | 2363.71 | 3363.88 | 1228.65 | 0.00 | 0.00 | 0.00 |
July | 3378.93 | 1058.15 | 2320.78 | 3927.54 | 1148.59 | 0.00 | 0.00 | 0.00 |
August | 3959.37 | 1781.07 | 2178.30 | 4873.85 | 1260.58 | 0.00 | 0.00 | 0.00 |
September | 4678.94 | 2741.00 | 1937.94 | 5714.97 | 1580.06 | 0.00 | 0.00 | 0.00 |
October | 3214.62 | 1878.80 | 1335.82 | 3521.73 | 1927.02 | 0.00 | 0.00 | 0.00 |
November | 2279.17 | 1386.48 | 892.69 | 2259.21 | 2242.33 | 0.00 | 0.00 | 0.00 |
December | 1806.45 | 1157.40 | 649.05 | 1737.45 | 2698.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3135.51 | 1487.45 | 1648.07 | 3402.69 | 1860.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1806.45 | 573.88 | 649.05 | 1593.13 | 1148.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4678.94 | 2741.00 | 2363.71 | 5714.97 | 2698.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.25 | 201.30 | 407.95 | 366.92 | 1741.40 | 0.00 | 0.00 | 0.00 |
February | 1078.71 | 455.46 | 623.24 | 847.18 | 1683.42 | 0.00 | 0.00 | 0.00 |
March | 975.38 | 186.59 | 788.79 | 586.86 | 1382.14 | 0.00 | 0.00 | 0.00 |
April | 2301.45 | 914.15 | 1387.29 | 2320.71 | 1220.36 | 0.00 | 0.00 | 0.00 |
May | 2700.13 | 1097.97 | 1602.16 | 2709.09 | 1040.64 | 0.00 | 0.00 | 0.00 |
June | 2915.85 | 1200.34 | 1715.50 | 3149.33 | 842.30 | 0.00 | 0.00 | 0.00 |
July | 2969.66 | 1309.33 | 1660.33 | 3352.59 | 791.31 | 0.00 | 0.00 | 0.00 |
August | 2494.32 | 1079.97 | 1414.35 | 2847.10 | 859.98 | 0.00 | 0.00 | 0.00 |
September | 2001.11 | 897.34 | 1103.77 | 2212.27 | 1052.09 | 0.00 | 0.00 | 0.00 |
October | 1067.51 | 383.87 | 683.64 | 935.76 | 1313.83 | 0.00 | 0.00 | 0.00 |
November | 577.70 | 168.64 | 409.06 | 352.20 | 1574.15 | 0.00 | 0.00 | 0.00 |
December | 327.00 | 69.00 | 257.99 | 120.37 | 1929.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.94 | 663.94 | 1006.00 | 1652.70 | 1283.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.00 | 69.00 | 257.99 | 120.37 | 791.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2969.66 | 1309.33 | 1715.50 | 3352.59 | 1929.36 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246297E+09 | 0.00 | 0.246297E+09 | 6371454.71 | 0.174912E+10 |
February | 0.347383E+09 | 0.00 | 0.347383E+09 | 23008896.37 | 0.147943E+10 |
March | 0.532222E+09 | 0.00 | 0.532222E+09 | 0.121980E+09 | 0.137465E+10 |
April | 0.838586E+09 | 3753159.90 | 0.834833E+09 | 0.475713E+09 | 0.104719E+10 |
May | 0.108339E+10 | 52268564.87 | 0.103113E+10 | 0.641895E+09 | 0.837468E+09 |
June | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.920791E+09 | 0.636433E+09 |
July | 0.113601E+10 | 64770054.73 | 0.107124E+10 | 0.961371E+09 | 0.611046E+09 |
August | 0.892964E+09 | 13990527.09 | 0.878973E+09 | 0.734186E+09 | 0.690863E+09 |
September | 0.657743E+09 | 145545.35 | 0.657598E+09 | 0.456605E+09 | 0.882002E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.138330E+09 | 0.127003E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10311818.01 | 0.154681E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.192917E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755297E+10 | 0.449056E+10 | 0.140542E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.611046E+09 |
Maximum of Months | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.961371E+09 | 0.192917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246296E+09 | 0.00 | 0.246296E+09 | 6371412.89 | 0.174912E+10 |
February | 0.347382E+09 | 0.00 | 0.347382E+09 | 23008771.06 | 0.147943E+10 |
March | 0.532221E+09 | 0.00 | 0.532221E+09 | 0.121979E+09 | 0.137465E+10 |
April | 0.838585E+09 | 3753155.39 | 0.834832E+09 | 0.475712E+09 | 0.104719E+10 |
May | 0.108339E+10 | 52268502.15 | 0.103113E+10 | 0.641894E+09 | 0.837468E+09 |
June | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.920790E+09 | 0.636433E+09 |
July | 0.113601E+10 | 64769977.01 | 0.107124E+10 | 0.961370E+09 | 0.611046E+09 |
August | 0.892963E+09 | 13990510.31 | 0.878972E+09 | 0.734185E+09 | 0.690863E+09 |
September | 0.657743E+09 | 145545.18 | 0.657597E+09 | 0.456604E+09 | 0.882002E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.138329E+09 | 0.127003E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10311755.72 | 0.154681E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.192917E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755296E+10 | 0.449056E+10 | 0.140542E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.611046E+09 |
Maximum of Months | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.961370E+09 | 0.192917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246297E+09 | 0.00 | 0.246297E+09 | 6371454.71 | 0.174912E+10 |
February | 0.347383E+09 | 0.00 | 0.347383E+09 | 23008896.37 | 0.147943E+10 |
March | 0.532222E+09 | 0.00 | 0.532222E+09 | 0.121980E+09 | 0.137465E+10 |
April | 0.838586E+09 | 3753159.90 | 0.834833E+09 | 0.475713E+09 | 0.104719E+10 |
May | 0.108339E+10 | 52268564.87 | 0.103113E+10 | 0.641895E+09 | 0.837468E+09 |
June | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.920791E+09 | 0.636433E+09 |
July | 0.113601E+10 | 64770054.73 | 0.107124E+10 | 0.961371E+09 | 0.611046E+09 |
August | 0.892964E+09 | 13990527.09 | 0.878973E+09 | 0.734186E+09 | 0.690863E+09 |
September | 0.657743E+09 | 145545.35 | 0.657598E+09 | 0.456605E+09 | 0.882002E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.138330E+09 | 0.127003E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10311818.01 | 0.154681E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.192917E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755297E+10 | 0.449056E+10 | 0.140542E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.611046E+09 |
Maximum of Months | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.961371E+09 | 0.192917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246296E+09 | 0.00 | 0.246296E+09 | 6371412.89 | 0.174912E+10 |
February | 0.347382E+09 | 0.00 | 0.347382E+09 | 23008771.06 | 0.147943E+10 |
March | 0.532221E+09 | 0.00 | 0.532221E+09 | 0.121979E+09 | 0.137465E+10 |
April | 0.838585E+09 | 3753155.39 | 0.834832E+09 | 0.475712E+09 | 0.104719E+10 |
May | 0.108339E+10 | 52268502.15 | 0.103113E+10 | 0.641894E+09 | 0.837468E+09 |
June | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.920790E+09 | 0.636433E+09 |
July | 0.113601E+10 | 64769977.01 | 0.107124E+10 | 0.961370E+09 | 0.611046E+09 |
August | 0.892963E+09 | 13990510.31 | 0.878972E+09 | 0.734185E+09 | 0.690863E+09 |
September | 0.657743E+09 | 145545.18 | 0.657597E+09 | 0.456604E+09 | 0.882002E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.138329E+09 | 0.127003E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10311755.72 | 0.154681E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.192917E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755296E+10 | 0.449056E+10 | 0.140542E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.611046E+09 |
Maximum of Months | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.961370E+09 | 0.192917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246287E+09 | 0.00 | 0.246287E+09 | 6371197.91 | 0.174905E+10 |
February | 0.347369E+09 | 0.00 | 0.347369E+09 | 23007969.01 | 0.147937E+10 |
March | 0.532200E+09 | 0.00 | 0.532200E+09 | 0.121975E+09 | 0.137460E+10 |
April | 0.838552E+09 | 3753008.63 | 0.834799E+09 | 0.475694E+09 | 0.104715E+10 |
May | 0.108335E+10 | 52266458.21 | 0.103108E+10 | 0.641869E+09 | 0.837435E+09 |
June | 0.115894E+10 | 72673345.31 | 0.108627E+10 | 0.920754E+09 | 0.636407E+09 |
July | 0.113597E+10 | 64767444.21 | 0.107120E+10 | 0.961332E+09 | 0.611021E+09 |
August | 0.892928E+09 | 13989963.21 | 0.878938E+09 | 0.734156E+09 | 0.690835E+09 |
September | 0.657717E+09 | 145539.49 | 0.657571E+09 | 0.456587E+09 | 0.881966E+09 |
October | 0.435509E+09 | 0.00 | 0.435509E+09 | 0.138324E+09 | 0.126998E+10 |
November | 0.253235E+09 | 0.00 | 0.253235E+09 | 10311402.40 | 0.154674E+10 |
December | 0.178201E+09 | 0.00 | 0.178201E+09 | 0.00 | 0.192909E+10 |
Annual Sum or Average | 0.776026E+10 | 0.207596E+09 | 0.755266E+10 | 0.449038E+10 | 0.140536E+11 |
Minimum of Months | 0.178201E+09 | 0.00 | 0.178201E+09 | 0.00 | 0.611021E+09 |
Maximum of Months | 0.115894E+10 | 72673345.31 | 0.108627E+10 | 0.961332E+09 | 0.192909E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559353E+09 | 0.224693E+09 | 0.334660E+09 | 0.292611E+09 | 0.178221E+10 |
February | 0.753373E+09 | 0.278302E+09 | 0.475072E+09 | 0.446666E+09 | 0.150810E+10 |
March | 0.871644E+09 | 0.171769E+09 | 0.699875E+09 | 0.468521E+09 | 0.138946E+10 |
April | 0.226494E+10 | 0.106431E+10 | 0.120063E+10 | 0.230613E+10 | 0.106553E+10 |
May | 0.246090E+10 | 0.107315E+10 | 0.138774E+10 | 0.244503E+10 | 0.938023E+09 |
June | 0.235726E+10 | 0.941467E+09 | 0.141579E+10 | 0.251025E+10 | 0.706987E+09 |
July | 0.248651E+10 | 0.105677E+10 | 0.142974E+10 | 0.276930E+10 | 0.674529E+09 |
August | 0.235542E+10 | 0.112540E+10 | 0.123002E+10 | 0.270358E+10 | 0.731125E+09 |
September | 0.205271E+10 | 0.109154E+10 | 0.961175E+09 | 0.226955E+10 | 0.913222E+09 |
October | 0.102390E+10 | 0.424331E+09 | 0.599570E+09 | 0.858298E+09 | 0.131277E+10 |
November | 0.516571E+09 | 0.176055E+09 | 0.340516E+09 | 0.267094E+09 | 0.156432E+10 |
December | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175992E+09 | 0.194494E+10 |
Annual Sum or Average | 0.180982E+11 | 0.777486E+10 | 0.103233E+11 | 0.175130E+11 | 0.145312E+11 |
Minimum of Months | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175992E+09 | 0.674529E+09 |
Maximum of Months | 0.248651E+10 | 0.112540E+10 | 0.142974E+10 | 0.276930E+10 | 0.194494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559353E+09 | 0.224693E+09 | 0.334660E+09 | 0.292611E+09 | 0.178221E+10 |
February | 0.753373E+09 | 0.278302E+09 | 0.475072E+09 | 0.446666E+09 | 0.150810E+10 |
March | 0.871644E+09 | 0.171769E+09 | 0.699875E+09 | 0.468521E+09 | 0.138946E+10 |
April | 0.226494E+10 | 0.106431E+10 | 0.120063E+10 | 0.230613E+10 | 0.106553E+10 |
May | 0.246090E+10 | 0.107315E+10 | 0.138774E+10 | 0.244503E+10 | 0.938023E+09 |
June | 0.235726E+10 | 0.941467E+09 | 0.141579E+10 | 0.251025E+10 | 0.706987E+09 |
July | 0.248651E+10 | 0.105677E+10 | 0.142974E+10 | 0.276930E+10 | 0.674529E+09 |
August | 0.235542E+10 | 0.112540E+10 | 0.123002E+10 | 0.270358E+10 | 0.731125E+09 |
September | 0.205271E+10 | 0.109154E+10 | 0.961175E+09 | 0.226955E+10 | 0.913222E+09 |
October | 0.102390E+10 | 0.424331E+09 | 0.599570E+09 | 0.858298E+09 | 0.131277E+10 |
November | 0.516571E+09 | 0.176055E+09 | 0.340516E+09 | 0.267094E+09 | 0.156432E+10 |
December | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175992E+09 | 0.194494E+10 |
Annual Sum or Average | 0.180982E+11 | 0.777486E+10 | 0.103233E+11 | 0.175130E+11 | 0.145312E+11 |
Minimum of Months | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175992E+09 | 0.674529E+09 |
Maximum of Months | 0.248651E+10 | 0.112540E+10 | 0.142974E+10 | 0.276930E+10 | 0.194494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559342E+09 | 0.224689E+09 | 0.334654E+09 | 0.292605E+09 | 0.178217E+10 |
February | 0.753360E+09 | 0.278297E+09 | 0.475063E+09 | 0.446658E+09 | 0.150808E+10 |
March | 0.871628E+09 | 0.171766E+09 | 0.699862E+09 | 0.468513E+09 | 0.138944E+10 |
April | 0.226490E+10 | 0.106429E+10 | 0.120061E+10 | 0.230609E+10 | 0.106551E+10 |
May | 0.246085E+10 | 0.107313E+10 | 0.138772E+10 | 0.244499E+10 | 0.938006E+09 |
June | 0.235722E+10 | 0.941450E+09 | 0.141577E+10 | 0.251021E+10 | 0.706974E+09 |
July | 0.248646E+10 | 0.105675E+10 | 0.142972E+10 | 0.276925E+10 | 0.674516E+09 |
August | 0.235538E+10 | 0.112538E+10 | 0.123000E+10 | 0.270353E+10 | 0.731112E+09 |
September | 0.205268E+10 | 0.109152E+10 | 0.961157E+09 | 0.226951E+10 | 0.913205E+09 |
October | 0.102388E+10 | 0.424323E+09 | 0.599559E+09 | 0.858283E+09 | 0.131275E+10 |
November | 0.516562E+09 | 0.176052E+09 | 0.340510E+09 | 0.267090E+09 | 0.156429E+10 |
December | 0.395596E+09 | 0.147077E+09 | 0.248519E+09 | 0.175989E+09 | 0.194490E+10 |
Annual Sum or Average | 0.180979E+11 | 0.777472E+10 | 0.103231E+11 | 0.175127E+11 | 0.145310E+11 |
Minimum of Months | 0.395596E+09 | 0.147077E+09 | 0.248519E+09 | 0.175989E+09 | 0.674516E+09 |
Maximum of Months | 0.248646E+10 | 0.112538E+10 | 0.142972E+10 | 0.276925E+10 | 0.194490E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905180E+09 | 0.493125E+09 | 0.134013E+10 | 0.148981E+10 |
February | 0.154250E+10 | 0.941257E+09 | 0.601247E+09 | 0.152350E+10 | 0.132029E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748439E+09 | 0.804394E+09 | 0.125219E+10 |
April | 0.212185E+10 | 0.959049E+09 | 0.116280E+10 | 0.236593E+10 | 0.104791E+10 |
May | 0.181346E+10 | 0.590404E+09 | 0.122306E+10 | 0.186836E+10 | 0.916704E+09 |
June | 0.161670E+10 | 0.391335E+09 | 0.122536E+10 | 0.173524E+10 | 0.690050E+09 |
July | 0.181005E+10 | 0.566837E+09 | 0.124321E+10 | 0.209719E+10 | 0.666693E+09 |
August | 0.212098E+10 | 0.954095E+09 | 0.116688E+10 | 0.261048E+10 | 0.729164E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296544E+10 | 0.880536E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.186030E+10 | 0.118429E+10 |
November | 0.118153E+10 | 0.718758E+09 | 0.462777E+09 | 0.113890E+10 | 0.136925E+10 |
December | 0.967691E+09 | 0.620004E+09 | 0.347687E+09 | 0.894136E+09 | 0.169425E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938174E+10 | 0.103948E+11 | 0.212040E+11 | 0.132411E+11 |
Minimum of Months | 0.967691E+09 | 0.307418E+09 | 0.347687E+09 | 0.804394E+09 | 0.666693E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296544E+10 | 0.169425E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905179E+09 | 0.493124E+09 | 0.134013E+10 | 0.148981E+10 |
February | 0.154250E+10 | 0.941256E+09 | 0.601246E+09 | 0.152349E+10 | 0.132029E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748438E+09 | 0.804393E+09 | 0.125219E+10 |
April | 0.212184E+10 | 0.959048E+09 | 0.116280E+10 | 0.236593E+10 | 0.104791E+10 |
May | 0.181346E+10 | 0.590403E+09 | 0.122306E+10 | 0.186836E+10 | 0.916704E+09 |
June | 0.161669E+10 | 0.391334E+09 | 0.122536E+10 | 0.173524E+10 | 0.690050E+09 |
July | 0.181005E+10 | 0.566836E+09 | 0.124321E+10 | 0.209719E+10 | 0.666693E+09 |
August | 0.212098E+10 | 0.954094E+09 | 0.116688E+10 | 0.261048E+10 | 0.729164E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296544E+10 | 0.880536E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.186030E+10 | 0.118429E+10 |
November | 0.118153E+10 | 0.718757E+09 | 0.462777E+09 | 0.113890E+10 | 0.136925E+10 |
December | 0.967689E+09 | 0.620003E+09 | 0.347686E+09 | 0.894135E+09 | 0.169425E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938173E+10 | 0.103948E+11 | 0.212040E+11 | 0.132411E+11 |
Minimum of Months | 0.967689E+09 | 0.307418E+09 | 0.347686E+09 | 0.804393E+09 | 0.666693E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296544E+10 | 0.169425E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905180E+09 | 0.493125E+09 | 0.134013E+10 | 0.148981E+10 |
February | 0.154250E+10 | 0.941257E+09 | 0.601247E+09 | 0.152350E+10 | 0.132029E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748439E+09 | 0.804394E+09 | 0.125219E+10 |
April | 0.212185E+10 | 0.959049E+09 | 0.116280E+10 | 0.236593E+10 | 0.104791E+10 |
May | 0.181346E+10 | 0.590404E+09 | 0.122306E+10 | 0.186836E+10 | 0.916704E+09 |
June | 0.161670E+10 | 0.391335E+09 | 0.122536E+10 | 0.173524E+10 | 0.690050E+09 |
July | 0.181005E+10 | 0.566837E+09 | 0.124321E+10 | 0.209719E+10 | 0.666693E+09 |
August | 0.212098E+10 | 0.954095E+09 | 0.116688E+10 | 0.261048E+10 | 0.729164E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296544E+10 | 0.880536E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.186030E+10 | 0.118429E+10 |
November | 0.118153E+10 | 0.718758E+09 | 0.462777E+09 | 0.113890E+10 | 0.136925E+10 |
December | 0.967691E+09 | 0.620004E+09 | 0.347687E+09 | 0.894136E+09 | 0.169425E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938174E+10 | 0.103948E+11 | 0.212040E+11 | 0.132411E+11 |
Minimum of Months | 0.967691E+09 | 0.307418E+09 | 0.347687E+09 | 0.804394E+09 | 0.666693E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296544E+10 | 0.169425E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905179E+09 | 0.493124E+09 | 0.134013E+10 | 0.148981E+10 |
February | 0.154250E+10 | 0.941256E+09 | 0.601246E+09 | 0.152349E+10 | 0.132029E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748438E+09 | 0.804393E+09 | 0.125219E+10 |
April | 0.212184E+10 | 0.959048E+09 | 0.116280E+10 | 0.236593E+10 | 0.104791E+10 |
May | 0.181346E+10 | 0.590403E+09 | 0.122306E+10 | 0.186836E+10 | 0.916704E+09 |
June | 0.161669E+10 | 0.391334E+09 | 0.122536E+10 | 0.173524E+10 | 0.690050E+09 |
July | 0.181005E+10 | 0.566836E+09 | 0.124321E+10 | 0.209719E+10 | 0.666693E+09 |
August | 0.212098E+10 | 0.954094E+09 | 0.116688E+10 | 0.261048E+10 | 0.729164E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296544E+10 | 0.880536E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.186030E+10 | 0.118429E+10 |
November | 0.118153E+10 | 0.718757E+09 | 0.462777E+09 | 0.113890E+10 | 0.136925E+10 |
December | 0.967689E+09 | 0.620003E+09 | 0.347686E+09 | 0.894135E+09 | 0.169425E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938173E+10 | 0.103948E+11 | 0.212040E+11 | 0.132411E+11 |
Minimum of Months | 0.967689E+09 | 0.307418E+09 | 0.347686E+09 | 0.804393E+09 | 0.666693E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296544E+10 | 0.169425E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139825E+10 | 0.905144E+09 | 0.493105E+09 | 0.134008E+10 | 0.148975E+10 |
February | 0.154244E+10 | 0.941219E+09 | 0.601223E+09 | 0.152343E+10 | 0.132024E+10 |
March | 0.105581E+10 | 0.307406E+09 | 0.748409E+09 | 0.804362E+09 | 0.125214E+10 |
April | 0.212176E+10 | 0.959011E+09 | 0.116275E+10 | 0.236584E+10 | 0.104787E+10 |
May | 0.181339E+10 | 0.590380E+09 | 0.122301E+10 | 0.186829E+10 | 0.916667E+09 |
June | 0.161663E+10 | 0.391319E+09 | 0.122531E+10 | 0.173517E+10 | 0.690022E+09 |
July | 0.180998E+10 | 0.566814E+09 | 0.124316E+10 | 0.209710E+10 | 0.666666E+09 |
August | 0.212089E+10 | 0.954057E+09 | 0.116684E+10 | 0.261038E+10 | 0.729135E+09 |
September | 0.242549E+10 | 0.142089E+10 | 0.100460E+10 | 0.296532E+10 | 0.880501E+09 |
October | 0.172196E+10 | 0.100641E+10 | 0.715552E+09 | 0.186023E+10 | 0.118424E+10 |
November | 0.118149E+10 | 0.718729E+09 | 0.462758E+09 | 0.113886E+10 | 0.136919E+10 |
December | 0.967652E+09 | 0.619979E+09 | 0.347673E+09 | 0.894100E+09 | 0.169418E+10 |
Annual Sum or Average | 0.197757E+11 | 0.938136E+10 | 0.103944E+11 | 0.212032E+11 | 0.132406E+11 |
Minimum of Months | 0.967652E+09 | 0.307406E+09 | 0.347673E+09 | 0.804362E+09 | 0.666666E+09 |
Maximum of Months | 0.242549E+10 | 0.142089E+10 | 0.124316E+10 | 0.296532E+10 | 0.169418E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543943E+09 | 0.179721E+09 | 0.364222E+09 | 0.283862E+09 | 0.191502E+10 |
February | 0.869877E+09 | 0.367290E+09 | 0.502587E+09 | 0.622770E+09 | 0.169623E+10 |
March | 0.870829E+09 | 0.166590E+09 | 0.704240E+09 | 0.426633E+09 | 0.160577E+10 |
April | 0.198847E+10 | 0.789837E+09 | 0.119863E+10 | 0.191685E+10 | 0.129066E+10 |
May | 0.241070E+10 | 0.980273E+09 | 0.143043E+10 | 0.236791E+10 | 0.105867E+10 |
June | 0.251932E+10 | 0.103711E+10 | 0.148221E+10 | 0.268735E+10 | 0.834224E+09 |
July | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294567E+10 | 0.826016E+09 |
August | 0.222695E+10 | 0.964207E+09 | 0.126274E+10 | 0.248736E+10 | 0.918012E+09 |
September | 0.172897E+10 | 0.775311E+09 | 0.953663E+09 | 0.186485E+10 | 0.104487E+10 |
October | 0.953085E+09 | 0.342725E+09 | 0.610360E+09 | 0.759545E+09 | 0.149784E+10 |
November | 0.499139E+09 | 0.145705E+09 | 0.353434E+09 | 0.254973E+09 | 0.182915E+10 |
December | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79401561.89 | 0.232545E+10 |
Annual Sum or Average | 0.175546E+11 | 0.697936E+10 | 0.105752E+11 | 0.166972E+11 | 0.168419E+11 |
Minimum of Months | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79401561.89 | 0.826016E+09 |
Maximum of Months | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294567E+10 | 0.232545E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543943E+09 | 0.179721E+09 | 0.364222E+09 | 0.283862E+09 | 0.191502E+10 |
February | 0.869877E+09 | 0.367290E+09 | 0.502587E+09 | 0.622770E+09 | 0.169623E+10 |
March | 0.870829E+09 | 0.166590E+09 | 0.704240E+09 | 0.426633E+09 | 0.160577E+10 |
April | 0.198847E+10 | 0.789837E+09 | 0.119863E+10 | 0.191685E+10 | 0.129066E+10 |
May | 0.241070E+10 | 0.980273E+09 | 0.143043E+10 | 0.236791E+10 | 0.105867E+10 |
June | 0.251932E+10 | 0.103711E+10 | 0.148221E+10 | 0.268735E+10 | 0.834224E+09 |
July | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294567E+10 | 0.826016E+09 |
August | 0.222695E+10 | 0.964207E+09 | 0.126274E+10 | 0.248736E+10 | 0.918012E+09 |
September | 0.172897E+10 | 0.775311E+09 | 0.953663E+09 | 0.186485E+10 | 0.104487E+10 |
October | 0.953085E+09 | 0.342725E+09 | 0.610360E+09 | 0.759545E+09 | 0.149784E+10 |
November | 0.499139E+09 | 0.145705E+09 | 0.353434E+09 | 0.254973E+09 | 0.182915E+10 |
December | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79401561.89 | 0.232545E+10 |
Annual Sum or Average | 0.175546E+11 | 0.697936E+10 | 0.105752E+11 | 0.166972E+11 | 0.168419E+11 |
Minimum of Months | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79401561.89 | 0.826016E+09 |
Maximum of Months | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294567E+10 | 0.232545E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543933E+09 | 0.179718E+09 | 0.364216E+09 | 0.283856E+09 | 0.191498E+10 |
February | 0.869861E+09 | 0.367283E+09 | 0.502578E+09 | 0.622759E+09 | 0.169619E+10 |
March | 0.870813E+09 | 0.166587E+09 | 0.704227E+09 | 0.426625E+09 | 0.160574E+10 |
April | 0.198843E+10 | 0.789823E+09 | 0.119861E+10 | 0.191682E+10 | 0.129063E+10 |
May | 0.241065E+10 | 0.980255E+09 | 0.143040E+10 | 0.236787E+10 | 0.105865E+10 |
June | 0.251927E+10 | 0.103709E+10 | 0.148218E+10 | 0.268730E+10 | 0.834208E+09 |
July | 0.265129E+10 | 0.116896E+10 | 0.148233E+10 | 0.294562E+10 | 0.826000E+09 |
August | 0.222691E+10 | 0.964190E+09 | 0.126272E+10 | 0.248731E+10 | 0.917996E+09 |
September | 0.172894E+10 | 0.775297E+09 | 0.953645E+09 | 0.186482E+10 | 0.104485E+10 |
October | 0.953068E+09 | 0.342719E+09 | 0.610349E+09 | 0.759531E+09 | 0.149781E+10 |
November | 0.499130E+09 | 0.145702E+09 | 0.353427E+09 | 0.254968E+09 | 0.182912E+10 |
December | 0.291940E+09 | 61605613.80 | 0.230334E+09 | 79400111.05 | 0.232541E+10 |
Annual Sum or Average | 0.175542E+11 | 0.697923E+10 | 0.105750E+11 | 0.166969E+11 | 0.168416E+11 |
Minimum of Months | 0.291940E+09 | 61605613.80 | 0.230334E+09 | 79400111.05 | 0.826000E+09 |
Maximum of Months | 0.265129E+10 | 0.116896E+10 | 0.148233E+10 | 0.294562E+10 | 0.232541E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123147E+10 | 0.00 | 0.123147E+10 | 71203259.93 | 0.771449E+10 |
February | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.219867E+09 | 0.651654E+10 |
March | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.800151E+09 | 0.603681E+10 |
April | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.254306E+10 | 0.475755E+10 |
May | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.335770E+10 | 0.390673E+10 |
June | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.467919E+10 | 0.300129E+10 |
July | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.493630E+10 | 0.284939E+10 |
August | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.379616E+10 | 0.318497E+10 |
September | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.239821E+10 | 0.409475E+10 |
October | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.850526E+09 | 0.560209E+10 |
November | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.115969E+09 | 0.658853E+10 |
December | 0.891029E+09 | 0.00 | 0.891029E+09 | 3808954.46 | 0.819535E+10 |
Annual Sum or Average | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.237721E+11 | 0.624485E+11 |
Minimum of Months | 0.891029E+09 | 0.00 | 0.891029E+09 | 3808954.46 | 0.284939E+10 |
Maximum of Months | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.493630E+10 | 0.819535E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.946962E+09 | 0.483643E+10 |
February | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.141744E+10 | 0.413174E+10 |
March | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.152655E+10 | 0.379984E+10 |
April | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.692458E+10 | 0.304288E+10 |
May | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.733351E+10 | 0.267441E+10 |
June | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.751058E+10 | 0.203677E+10 |
July | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.828198E+10 | 0.194800E+10 |
August | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.809134E+10 | 0.211916E+10 |
September | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.680281E+10 | 0.261563E+10 |
October | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.264481E+10 | 0.359053E+10 |
November | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.866544E+09 | 0.417015E+10 |
December | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.586321E+09 | 0.520137E+10 |
Annual Sum or Average | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.529334E+11 | 0.401669E+11 |
Minimum of Months | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.586321E+09 | 0.194800E+10 |
Maximum of Months | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.828198E+10 | 0.520137E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.673894E+10 | 0.713717E+10 |
February | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.763858E+10 | 0.634583E+10 |
March | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.410917E+10 | 0.588772E+10 |
April | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.118207E+11 | 0.503338E+10 |
May | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.933229E+10 | 0.443287E+10 |
June | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.868209E+10 | 0.331700E+10 |
July | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.104980E+11 | 0.318943E+10 |
August | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.130418E+11 | 0.350029E+10 |
September | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.147624E+11 | 0.431150E+10 |
October | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.930890E+10 | 0.564929E+10 |
November | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.573835E+10 | 0.639672E+10 |
December | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.454750E+10 | 0.786488E+10 |
Annual Sum or Average | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.106219E+12 | 0.630661E+11 |
Minimum of Months | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.410917E+10 | 0.318943E+10 |
Maximum of Months | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.147624E+11 | 0.786488E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.937197E+09 | 0.503623E+10 |
February | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.199434E+10 | 0.437159E+10 |
March | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.150038E+10 | 0.396520E+10 |
April | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.596345E+10 | 0.332977E+10 |
May | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.720825E+10 | 0.293044E+10 |
June | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.815158E+10 | 0.226490E+10 |
July | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.897778E+10 | 0.218975E+10 |
August | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.761782E+10 | 0.238339E+10 |
September | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.569264E+10 | 0.286710E+10 |
October | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.243876E+10 | 0.380395E+10 |
November | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.875933E+09 | 0.441669E+10 |
December | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.301597E+09 | 0.554194E+10 |
Annual Sum or Average | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.516597E+11 | 0.431009E+11 |
Minimum of Months | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.301597E+09 | 0.218975E+10 |
Maximum of Months | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.897778E+10 | 0.554194E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.116656E+09 | 0.703723E+10 |
February | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.314844E+09 | 0.593669E+10 |
March | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.940597E+09 | 0.552133E+10 |
April | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.266274E+10 | 0.444825E+10 |
May | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.351003E+10 | 0.366642E+10 |
June | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.473942E+10 | 0.287802E+10 |
July | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.498421E+10 | 0.274433E+10 |
August | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.384123E+10 | 0.305688E+10 |
September | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.249856E+10 | 0.383738E+10 |
October | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.993085E+09 | 0.503804E+10 |
November | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.175079E+09 | 0.593263E+10 |
December | 0.891029E+09 | 0.00 | 0.891029E+09 | 22413353.46 | 0.752022E+10 |
Annual Sum or Average | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.247989E+11 | 0.576174E+11 |
Minimum of Months | 0.891029E+09 | 0.00 | 0.891029E+09 | 22413353.46 | 0.274433E+10 |
Maximum of Months | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.498421E+10 | 0.752022E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.101015E+10 | 0.442993E+10 |
February | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.150570E+10 | 0.378986E+10 |
March | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.162638E+10 | 0.350935E+10 |
April | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.698212E+10 | 0.288613E+10 |
May | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.739288E+10 | 0.254347E+10 |
June | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.752768E+10 | 0.196986E+10 |
July | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.828655E+10 | 0.189370E+10 |
August | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.809679E+10 | 0.205784E+10 |
September | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.684438E+10 | 0.249142E+10 |
October | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.273578E+10 | 0.327718E+10 |
November | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.928257E+09 | 0.379105E+10 |
December | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.630033E+09 | 0.479187E+10 |
Annual Sum or Average | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.535667E+11 | 0.374317E+11 |
Minimum of Months | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.630033E+09 | 0.189370E+10 |
Maximum of Months | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.828655E+10 | 0.479187E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.689209E+10 | 0.652585E+10 |
February | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.778701E+10 | 0.583108E+10 |
March | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.426703E+10 | 0.541920E+10 |
April | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.118954E+11 | 0.476195E+10 |
May | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.941776E+10 | 0.418661E+10 |
June | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.871917E+10 | 0.318467E+10 |
July | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.105195E+11 | 0.307639E+10 |
August | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.130541E+11 | 0.337635E+10 |
September | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.148132E+11 | 0.409552E+10 |
October | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.943261E+10 | 0.516133E+10 |
November | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.585587E+10 | 0.581211E+10 |
December | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.465359E+10 | 0.722814E+10 |
Annual Sum or Average | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.107307E+12 | 0.586592E+11 |
Minimum of Months | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.426703E+10 | 0.307639E+10 |
Maximum of Months | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.148132E+11 | 0.722814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.982762E+09 | 0.466418E+10 |
February | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.204950E+10 | 0.407253E+10 |
March | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.157185E+10 | 0.370194E+10 |
April | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.601529E+10 | 0.316317E+10 |
May | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.725602E+10 | 0.278726E+10 |
June | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.816307E+10 | 0.218324E+10 |
July | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.897958E+10 | 0.211946E+10 |
August | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.762568E+10 | 0.230337E+10 |
September | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.573421E+10 | 0.272701E+10 |
October | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.250634E+10 | 0.351896E+10 |
November | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.912908E+09 | 0.408020E+10 |
December | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.322398E+09 | 0.516761E+10 |
Annual Sum or Average | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.521196E+11 | 0.404889E+11 |
Minimum of Months | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.322398E+09 | 0.211946E+10 |
Maximum of Months | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.897958E+10 | 0.516761E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.89 | 3265.20 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 47.55 | 3057.66 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 227.71 | 2566.16 | 993.54 | 0.00 | 993.54 | 0.00 | 0.00 |
April | 917.65 | 2020.02 | 1617.63 | 7.24 | 1610.39 | 0.00 | 0.00 |
May | 1198.27 | 1563.36 | 2022.45 | 97.57 | 1924.88 | 0.00 | 0.00 |
June | 1776.20 | 1227.68 | 2235.69 | 140.19 | 2095.50 | 0.00 | 0.00 |
July | 1794.66 | 1140.68 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1370.56 | 1289.68 | 1666.96 | 26.12 | 1640.84 | 0.00 | 0.00 |
September | 880.79 | 1701.38 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 258.23 | 2370.85 | 813.03 | 0.00 | 813.03 | 0.00 | 0.00 |
November | 19.89 | 2983.78 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 0.00 | 3601.32 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 711.97 | 2228.26 | 1230.42 | 32.92 | 1197.51 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1140.68 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1794.66 | 3601.32 | 2235.69 | 140.19 | 2095.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 327.74 | 1996.19 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 553.90 | 1870.16 | 934.24 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 524.77 | 1556.29 | 976.30 | 192.39 | 783.91 | 0.00 | 0.00 |
April | 2669.11 | 1233.24 | 2621.44 | 1231.83 | 1389.61 | 0.00 | 0.00 |
May | 2738.60 | 1050.65 | 2756.36 | 1202.00 | 1554.36 | 0.00 | 0.00 |
June | 2905.37 | 818.27 | 2728.29 | 1089.65 | 1638.64 | 0.00 | 0.00 |
July | 3101.80 | 755.52 | 2785.05 | 1183.65 | 1601.40 | 0.00 | 0.00 |
August | 3028.19 | 818.91 | 2638.23 | 1260.52 | 1377.71 | 0.00 | 0.00 |
September | 2626.78 | 1056.96 | 2375.81 | 1263.35 | 1112.46 | 0.00 | 0.00 |
October | 961.35 | 1470.39 | 1146.84 | 475.28 | 671.56 | 0.00 | 0.00 |
November | 309.14 | 1810.55 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 197.12 | 2178.46 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1665.99 | 1382.34 | 1721.66 | 739.61 | 982.05 | 0.00 | 0.00 |
Minimum of Months | 197.12 | 755.52 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3101.80 | 2178.46 | 2785.05 | 1263.35 | 1638.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2501.72 | 2781.14 | 2610.31 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3148.73 | 2728.76 | 3188.02 | 1945.37 | 1242.65 | 0.00 | 0.00 |
March | 1501.62 | 2337.55 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4563.88 | 2021.42 | 4093.03 | 1850.00 | 2243.03 | 0.00 | 0.00 |
May | 3487.81 | 1711.28 | 3385.32 | 1102.15 | 2283.17 | 0.00 | 0.00 |
June | 3347.27 | 1331.10 | 3118.60 | 754.88 | 2363.72 | 0.00 | 0.00 |
July | 3914.97 | 1244.56 | 3378.94 | 1058.15 | 2320.79 | 0.00 | 0.00 |
August | 4873.17 | 1361.18 | 3959.38 | 1781.08 | 2178.30 | 0.00 | 0.00 |
September | 5720.33 | 1698.55 | 4678.96 | 2741.01 | 1937.95 | 0.00 | 0.00 |
October | 3472.76 | 2210.80 | 3214.64 | 1878.81 | 1335.83 | 0.00 | 0.00 |
November | 2196.94 | 2641.28 | 2279.18 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1669.15 | 3162.78 | 1806.46 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3361.85 | 2099.35 | 3135.52 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1501.62 | 1244.56 | 1806.46 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5720.33 | 3162.78 | 4678.96 | 2741.01 | 2363.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 317.94 | 2144.94 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 772.28 | 2103.44 | 1078.71 | 455.47 | 623.24 | 0.00 | 0.00 |
March | 477.86 | 1798.56 | 975.39 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2218.57 | 1493.80 | 2301.45 | 914.16 | 1387.30 | 0.00 | 0.00 |
May | 2652.22 | 1185.78 | 2700.14 | 1097.97 | 1602.17 | 0.00 | 0.00 |
June | 3110.33 | 965.53 | 2915.86 | 1200.35 | 1715.51 | 0.00 | 0.00 |
July | 3299.34 | 925.19 | 2969.67 | 1309.34 | 1660.34 | 0.00 | 0.00 |
August | 2786.00 | 1028.23 | 2494.33 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2158.38 | 1209.33 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 850.74 | 1677.68 | 1067.52 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 295.11 | 2117.06 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 88.93 | 2604.66 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1588.38 | 1602.15 | 1669.95 | 663.94 | 1006.01 | 0.00 | 0.00 |
Minimum of Months | 88.93 | 925.19 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3299.34 | 2604.66 | 2969.67 | 1309.34 | 1715.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.58 | 2880.26 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 90.88 | 2693.68 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 298.74 | 2253.89 | 993.53 | 0.00 | 993.53 | 0.00 | 0.00 |
April | 981.12 | 1835.48 | 1617.62 | 7.24 | 1610.38 | 0.00 | 0.00 |
May | 1253.62 | 1458.60 | 2022.44 | 97.57 | 1924.87 | 0.00 | 0.00 |
June | 1805.24 | 1157.90 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
July | 1843.00 | 1063.84 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1417.32 | 1189.13 | 1666.95 | 26.12 | 1640.83 | 0.00 | 0.00 |
September | 925.24 | 1579.77 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 317.55 | 2091.58 | 813.02 | 0.00 | 813.02 | 0.00 | 0.00 |
November | 44.74 | 2541.87 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 1.42 | 3059.79 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 753.81 | 1980.23 | 1230.42 | 32.92 | 1197.50 | 0.00 | 0.00 |
Minimum of Months | 1.42 | 1063.84 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1843.00 | 3059.79 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 353.56 | 1805.72 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 585.91 | 1707.89 | 934.23 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 569.95 | 1418.70 | 976.29 | 192.39 | 783.90 | 0.00 | 0.00 |
April | 2671.52 | 1173.95 | 2621.43 | 1231.83 | 1389.60 | 0.00 | 0.00 |
May | 2738.02 | 998.51 | 2756.35 | 1202.00 | 1554.35 | 0.00 | 0.00 |
June | 2897.60 | 785.79 | 2728.28 | 1089.65 | 1638.63 | 0.00 | 0.00 |
July | 3092.14 | 727.30 | 2785.04 | 1183.64 | 1601.40 | 0.00 | 0.00 |
August | 3020.96 | 791.21 | 2638.22 | 1260.51 | 1377.70 | 0.00 | 0.00 |
September | 2624.54 | 1009.12 | 2375.80 | 1263.34 | 1112.46 | 0.00 | 0.00 |
October | 987.46 | 1340.55 | 1146.83 | 475.28 | 671.55 | 0.00 | 0.00 |
November | 334.31 | 1608.85 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 218.91 | 1941.97 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1678.51 | 1273.68 | 1721.65 | 739.61 | 982.04 | 0.00 | 0.00 |
Minimum of Months | 218.91 | 727.30 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3092.14 | 1941.97 | 2785.04 | 1263.34 | 1638.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2516.03 | 2664.71 | 2610.30 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3157.48 | 2623.11 | 3188.01 | 1945.37 | 1242.64 | 0.00 | 0.00 |
March | 1534.19 | 2198.22 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4560.44 | 1941.89 | 4093.02 | 1850.00 | 2243.02 | 0.00 | 0.00 |
May | 3484.28 | 1655.04 | 3385.31 | 1102.15 | 2283.16 | 0.00 | 0.00 |
June | 3349.57 | 1279.71 | 3118.59 | 754.88 | 2363.71 | 0.00 | 0.00 |
July | 3919.49 | 1190.80 | 3378.93 | 1058.15 | 2320.78 | 0.00 | 0.00 |
August | 4869.26 | 1306.86 | 3959.37 | 1781.07 | 2178.30 | 0.00 | 0.00 |
September | 5695.37 | 1663.39 | 4678.94 | 2741.00 | 1937.94 | 0.00 | 0.00 |
October | 3475.55 | 2109.20 | 3214.62 | 1878.80 | 1335.82 | 0.00 | 0.00 |
November | 2213.87 | 2467.87 | 2279.17 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1697.84 | 2936.41 | 1806.45 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3368.17 | 1999.81 | 3135.51 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1534.19 | 1190.80 | 1806.45 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5695.37 | 2936.41 | 4678.94 | 2741.00 | 2363.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 349.91 | 1880.31 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 824.38 | 1807.04 | 1078.71 | 455.46 | 623.24 | 0.00 | 0.00 |
March | 560.18 | 1480.44 | 975.38 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2300.71 | 1284.64 | 2301.45 | 914.15 | 1387.29 | 0.00 | 0.00 |
May | 2691.25 | 1094.10 | 2700.13 | 1097.97 | 1602.16 | 0.00 | 0.00 |
June | 3144.90 | 873.80 | 2915.85 | 1200.34 | 1715.50 | 0.00 | 0.00 |
July | 3351.92 | 817.56 | 2969.66 | 1309.33 | 1660.33 | 0.00 | 0.00 |
August | 2844.17 | 889.86 | 2494.32 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2196.23 | 1106.14 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 910.53 | 1420.23 | 1067.51 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 337.94 | 1703.97 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 112.60 | 2069.12 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1638.12 | 1366.72 | 1669.94 | 663.94 | 1006.00 | 0.00 | 0.00 |
Minimum of Months | 112.60 | 817.56 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3351.92 | 2069.12 | 2969.66 | 1309.33 | 1715.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.55 | 2627.40 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 130.14 | 2453.99 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 351.18 | 2061.43 | 993.53 | 0.00 | 993.53 | 0.00 | 0.00 |
April | 1027.29 | 1716.15 | 1617.62 | 7.24 | 1610.38 | 0.00 | 0.00 |
May | 1310.49 | 1368.89 | 2022.44 | 97.57 | 1924.87 | 0.00 | 0.00 |
June | 1828.48 | 1110.35 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
July | 1860.89 | 1024.62 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1434.15 | 1141.31 | 1666.95 | 26.12 | 1640.83 | 0.00 | 0.00 |
September | 963.95 | 1480.47 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 370.78 | 1880.99 | 813.02 | 0.00 | 813.02 | 0.00 | 0.00 |
November | 67.55 | 2288.82 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 8.37 | 2807.73 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 786.37 | 1827.04 | 1230.42 | 32.92 | 1197.50 | 0.00 | 0.00 |
Minimum of Months | 8.37 | 1024.62 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1860.89 | 2807.73 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 377.15 | 1653.94 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 622.39 | 1566.58 | 934.23 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 607.22 | 1310.24 | 976.29 | 192.39 | 783.90 | 0.00 | 0.00 |
April | 2693.72 | 1113.47 | 2621.43 | 1231.83 | 1389.60 | 0.00 | 0.00 |
May | 2760.18 | 949.62 | 2756.35 | 1202.00 | 1554.35 | 0.00 | 0.00 |
June | 2904.20 | 759.97 | 2728.28 | 1089.65 | 1638.63 | 0.00 | 0.00 |
July | 3093.84 | 707.03 | 2785.04 | 1183.64 | 1601.40 | 0.00 | 0.00 |
August | 3023.00 | 768.31 | 2638.22 | 1260.51 | 1377.70 | 0.00 | 0.00 |
September | 2640.58 | 961.19 | 2375.80 | 1263.34 | 1112.46 | 0.00 | 0.00 |
October | 1021.42 | 1223.56 | 1146.83 | 475.28 | 671.55 | 0.00 | 0.00 |
November | 358.12 | 1462.60 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 235.23 | 1789.08 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1698.59 | 1186.95 | 1721.65 | 739.61 | 982.04 | 0.00 | 0.00 |
Minimum of Months | 235.23 | 707.03 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3093.84 | 1789.08 | 2785.04 | 1263.34 | 1638.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2573.21 | 2436.47 | 2610.30 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3218.83 | 2410.33 | 3188.01 | 1945.37 | 1242.64 | 0.00 | 0.00 |
March | 1593.13 | 2023.30 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4589.27 | 1837.17 | 4093.02 | 1850.00 | 2243.02 | 0.00 | 0.00 |
May | 3516.19 | 1563.10 | 3385.31 | 1102.15 | 2283.16 | 0.00 | 0.00 |
June | 3363.88 | 1228.65 | 3118.59 | 754.88 | 2363.71 | 0.00 | 0.00 |
July | 3927.54 | 1148.59 | 3378.93 | 1058.15 | 2320.78 | 0.00 | 0.00 |
August | 4873.85 | 1260.58 | 3959.37 | 1781.07 | 2178.30 | 0.00 | 0.00 |
September | 5714.97 | 1580.06 | 4678.94 | 2741.00 | 1937.94 | 0.00 | 0.00 |
October | 3521.73 | 1927.02 | 3214.62 | 1878.80 | 1335.82 | 0.00 | 0.00 |
November | 2259.21 | 2242.33 | 2279.17 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1737.45 | 2698.68 | 1806.45 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3402.69 | 1860.07 | 3135.51 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1593.13 | 1148.59 | 1806.45 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5714.97 | 2698.68 | 4678.94 | 2741.00 | 2363.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.92 | 1741.40 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 847.18 | 1683.42 | 1078.71 | 455.46 | 623.24 | 0.00 | 0.00 |
March | 586.86 | 1382.14 | 975.38 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2320.71 | 1220.36 | 2301.45 | 914.15 | 1387.29 | 0.00 | 0.00 |
May | 2709.09 | 1040.64 | 2700.13 | 1097.97 | 1602.16 | 0.00 | 0.00 |
June | 3149.33 | 842.30 | 2915.85 | 1200.34 | 1715.50 | 0.00 | 0.00 |
July | 3352.59 | 791.31 | 2969.66 | 1309.33 | 1660.33 | 0.00 | 0.00 |
August | 2847.10 | 859.98 | 2494.32 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2212.27 | 1052.09 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 935.76 | 1313.83 | 1067.51 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 352.20 | 1574.15 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 120.37 | 1929.36 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1652.70 | 1283.90 | 1669.94 | 663.94 | 1006.00 | 0.00 | 0.00 |
Minimum of Months | 120.37 | 791.31 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3352.59 | 1929.36 | 2969.66 | 1309.33 | 1715.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 31856933.12 | 0.874552E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.115043E+09 | 0.739710E+10 | 0.173690E+10 | 0.00 | 0.173690E+10 | 0.00 | 0.00 |
March | 0.609893E+09 | 0.687321E+10 | 0.266109E+10 | 0.00 | 0.266109E+10 | 0.00 | 0.00 |
April | 0.237854E+10 | 0.523590E+10 | 0.419289E+10 | 18765639.20 | 0.417413E+10 | 0.00 | 0.00 |
May | 0.320945E+10 | 0.418731E+10 | 0.541693E+10 | 0.261341E+09 | 0.515559E+10 | 0.00 | 0.00 |
June | 0.460392E+10 | 0.318214E+10 | 0.579491E+10 | 0.363378E+09 | 0.543153E+10 | 0.00 | 0.00 |
July | 0.480681E+10 | 0.305521E+10 | 0.568001E+10 | 0.323848E+09 | 0.535616E+10 | 0.00 | 0.00 |
August | 0.367090E+10 | 0.345429E+10 | 0.446478E+10 | 69952038.01 | 0.439483E+10 | 0.00 | 0.00 |
September | 0.228301E+10 | 0.440997E+10 | 0.328869E+10 | 727720.56 | 0.328796E+10 | 0.00 | 0.00 |
October | 0.691643E+09 | 0.635008E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 51558549.85 | 0.773397E+10 | 0.126622E+10 | 0.00 | 0.126622E+10 | 0.00 | 0.00 |
December | 0.00 | 0.964577E+10 | 0.891033E+09 | 0.00 | 0.891033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224526E+11 | 0.702705E+11 | 0.388025E+11 | 0.103801E+10 | 0.377645E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.305521E+10 | 0.891033E+09 | 0.00 | 0.891033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480681E+10 | 0.964577E+10 | 0.579491E+10 | 0.363378E+09 | 0.543153E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.877827E+09 | 0.534659E+10 | 0.167805E+10 | 0.674074E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.133999E+10 | 0.452429E+10 | 0.226011E+10 | 0.834900E+09 | 0.142521E+10 | 0.00 | 0.00 |
March | 0.140556E+10 | 0.416836E+10 | 0.261492E+10 | 0.515305E+09 | 0.209961E+10 | 0.00 | 0.00 |
April | 0.691834E+10 | 0.319657E+10 | 0.679477E+10 | 0.319291E+10 | 0.360186E+10 | 0.00 | 0.00 |
May | 0.733506E+10 | 0.281405E+10 | 0.738264E+10 | 0.321944E+10 | 0.416320E+10 | 0.00 | 0.00 |
June | 0.753071E+10 | 0.212095E+10 | 0.707174E+10 | 0.282438E+10 | 0.424736E+10 | 0.00 | 0.00 |
July | 0.830786E+10 | 0.202357E+10 | 0.745948E+10 | 0.317028E+10 | 0.428920E+10 | 0.00 | 0.00 |
August | 0.811070E+10 | 0.219336E+10 | 0.706622E+10 | 0.337618E+10 | 0.369005E+10 | 0.00 | 0.00 |
September | 0.680860E+10 | 0.273965E+10 | 0.615811E+10 | 0.327460E+10 | 0.288351E+10 | 0.00 | 0.00 |
October | 0.257488E+10 | 0.393829E+10 | 0.307168E+10 | 0.127299E+10 | 0.179870E+10 | 0.00 | 0.00 |
November | 0.801279E+09 | 0.469294E+10 | 0.154970E+10 | 0.528162E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.527974E+09 | 0.583478E+10 | 0.118680E+10 | 0.441237E+09 | 0.745567E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525388E+11 | 0.435934E+11 | 0.542942E+11 | 0.233244E+11 | 0.309698E+11 | 0.00 | 0.00 |
Minimum of Months | 0.527974E+09 | 0.202357E+10 | 0.118680E+10 | 0.441237E+09 | 0.745567E+09 | 0.00 | 0.00 |
Maximum of Months | 0.830786E+10 | 0.583478E+10 | 0.745948E+10 | 0.337618E+10 | 0.428920E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.670060E+10 | 0.744901E+10 | 0.699146E+10 | 0.452586E+10 | 0.246560E+10 | 0.00 | 0.00 |
February | 0.761741E+10 | 0.660141E+10 | 0.771245E+10 | 0.470625E+10 | 0.300621E+10 | 0.00 | 0.00 |
March | 0.402194E+10 | 0.626089E+10 | 0.527924E+10 | 0.153708E+10 | 0.374216E+10 | 0.00 | 0.00 |
April | 0.118296E+11 | 0.523952E+10 | 0.106091E+11 | 0.479521E+10 | 0.581393E+10 | 0.00 | 0.00 |
May | 0.934174E+10 | 0.458348E+10 | 0.906723E+10 | 0.295200E+10 | 0.611524E+10 | 0.00 | 0.00 |
June | 0.867612E+10 | 0.345022E+10 | 0.808341E+10 | 0.195666E+10 | 0.612676E+10 | 0.00 | 0.00 |
July | 0.104859E+11 | 0.333344E+10 | 0.905017E+10 | 0.283416E+10 | 0.621601E+10 | 0.00 | 0.00 |
August | 0.130523E+11 | 0.364579E+10 | 0.106048E+11 | 0.477044E+10 | 0.583437E+10 | 0.00 | 0.00 |
September | 0.148271E+11 | 0.440265E+10 | 0.121279E+11 | 0.710470E+10 | 0.502315E+10 | 0.00 | 0.00 |
October | 0.930143E+10 | 0.592140E+10 | 0.861008E+10 | 0.503220E+10 | 0.357788E+10 | 0.00 | 0.00 |
November | 0.569446E+10 | 0.684619E+10 | 0.590762E+10 | 0.359376E+10 | 0.231387E+10 | 0.00 | 0.00 |
December | 0.447064E+10 | 0.847118E+10 | 0.483841E+10 | 0.309999E+10 | 0.173842E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106019E+12 | 0.662052E+11 | 0.988819E+11 | 0.469083E+11 | 0.519736E+11 | 0.00 | 0.00 |
Minimum of Months | 0.402194E+10 | 0.333344E+10 | 0.483841E+10 | 0.153708E+10 | 0.173842E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148271E+11 | 0.847118E+10 | 0.121279E+11 | 0.710470E+10 | 0.621601E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851579E+09 | 0.574501E+10 | 0.163182E+10 | 0.539160E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.186830E+10 | 0.508865E+10 | 0.260962E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.127989E+10 | 0.481727E+10 | 0.261247E+10 | 0.499766E+09 | 0.211271E+10 | 0.00 | 0.00 |
April | 0.575052E+10 | 0.387194E+10 | 0.596537E+10 | 0.236950E+10 | 0.359587E+10 | 0.00 | 0.00 |
May | 0.710370E+10 | 0.317599E+10 | 0.723205E+10 | 0.294080E+10 | 0.429125E+10 | 0.00 | 0.00 |
June | 0.806199E+10 | 0.250266E+10 | 0.755791E+10 | 0.311130E+10 | 0.444660E+10 | 0.00 | 0.00 |
July | 0.883695E+10 | 0.247803E+10 | 0.795398E+10 | 0.350693E+10 | 0.444705E+10 | 0.00 | 0.00 |
August | 0.746202E+10 | 0.275402E+10 | 0.668081E+10 | 0.289260E+10 | 0.378821E+10 | 0.00 | 0.00 |
September | 0.559452E+10 | 0.313458E+10 | 0.518689E+10 | 0.232592E+10 | 0.286097E+10 | 0.00 | 0.00 |
October | 0.227862E+10 | 0.449349E+10 | 0.285924E+10 | 0.102817E+10 | 0.183107E+10 | 0.00 | 0.00 |
November | 0.764914E+09 | 0.548742E+10 | 0.149741E+10 | 0.437112E+09 | 0.106030E+10 | 0.00 | 0.00 |
December | 0.238203E+09 | 0.697632E+10 | 0.875829E+09 | 0.184819E+09 | 0.691010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.500912E+11 | 0.505254E+11 | 0.526634E+11 | 0.209379E+11 | 0.317254E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238203E+09 | 0.247803E+10 | 0.875829E+09 | 0.184819E+09 | 0.691010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.883695E+10 | 0.697632E+10 | 0.795398E+10 | 0.350693E+10 | 0.444705E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71203259.93 | 0.771449E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.219867E+09 | 0.651654E+10 | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.00 | 0.00 |
March | 0.800151E+09 | 0.603681E+10 | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.00 | 0.00 |
April | 0.254306E+10 | 0.475755E+10 | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.00 | 0.00 |
May | 0.335770E+10 | 0.390673E+10 | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.00 | 0.00 |
June | 0.467919E+10 | 0.300129E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
July | 0.493630E+10 | 0.284939E+10 | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.00 | 0.00 |
August | 0.379616E+10 | 0.318497E+10 | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.00 | 0.00 |
September | 0.239821E+10 | 0.409475E+10 | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.00 | 0.00 |
October | 0.850526E+09 | 0.560209E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 0.115969E+09 | 0.658853E+10 | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.00 | 0.00 |
December | 3808954.46 | 0.819535E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237721E+11 | 0.624485E+11 | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.00 | 0.00 |
Minimum of Months | 3808954.46 | 0.284939E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493630E+10 | 0.819535E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.946962E+09 | 0.483643E+10 | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.141744E+10 | 0.413174E+10 | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.00 | 0.00 |
March | 0.152655E+10 | 0.379984E+10 | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.00 | 0.00 |
April | 0.692458E+10 | 0.304288E+10 | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.00 | 0.00 |
May | 0.733351E+10 | 0.267441E+10 | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.00 | 0.00 |
June | 0.751058E+10 | 0.203677E+10 | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.00 | 0.00 |
July | 0.828198E+10 | 0.194800E+10 | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.00 | 0.00 |
August | 0.809134E+10 | 0.211916E+10 | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.00 | 0.00 |
September | 0.680281E+10 | 0.261563E+10 | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.00 | 0.00 |
October | 0.264481E+10 | 0.359053E+10 | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.00 | 0.00 |
November | 0.866544E+09 | 0.417015E+10 | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.586321E+09 | 0.520137E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.529334E+11 | 0.401669E+11 | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.586321E+09 | 0.194800E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.828198E+10 | 0.520137E+10 | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.673894E+10 | 0.713717E+10 | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.00 | 0.00 |
February | 0.763858E+10 | 0.634583E+10 | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.00 | 0.00 |
March | 0.410917E+10 | 0.588772E+10 | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.00 | 0.00 |
April | 0.118207E+11 | 0.503338E+10 | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.00 | 0.00 |
May | 0.933229E+10 | 0.443287E+10 | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.00 | 0.00 |
June | 0.868209E+10 | 0.331700E+10 | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.00 | 0.00 |
July | 0.104980E+11 | 0.318943E+10 | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.00 | 0.00 |
August | 0.130418E+11 | 0.350029E+10 | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.00 | 0.00 |
September | 0.147624E+11 | 0.431150E+10 | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.00 | 0.00 |
October | 0.930890E+10 | 0.564929E+10 | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.00 | 0.00 |
November | 0.573835E+10 | 0.639672E+10 | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.00 | 0.00 |
December | 0.454750E+10 | 0.786488E+10 | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106219E+12 | 0.630661E+11 | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.410917E+10 | 0.318943E+10 | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147624E+11 | 0.786488E+10 | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.937197E+09 | 0.503623E+10 | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.199434E+10 | 0.437159E+10 | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.150038E+10 | 0.396520E+10 | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.00 | 0.00 |
April | 0.596345E+10 | 0.332977E+10 | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.00 | 0.00 |
May | 0.720825E+10 | 0.293044E+10 | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.00 | 0.00 |
June | 0.815158E+10 | 0.226490E+10 | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.00 | 0.00 |
July | 0.897778E+10 | 0.218975E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
August | 0.761782E+10 | 0.238339E+10 | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.00 | 0.00 |
September | 0.569264E+10 | 0.286710E+10 | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.00 | 0.00 |
October | 0.243876E+10 | 0.380395E+10 | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.00 | 0.00 |
November | 0.875933E+09 | 0.441669E+10 | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.00 | 0.00 |
December | 0.301597E+09 | 0.554194E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.516597E+11 | 0.431009E+11 | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.301597E+09 | 0.218975E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.897778E+10 | 0.554194E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116656E+09 | 0.703723E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.314844E+09 | 0.593669E+10 | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.00 | 0.00 |
March | 0.940597E+09 | 0.552133E+10 | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.00 | 0.00 |
April | 0.266274E+10 | 0.444825E+10 | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.00 | 0.00 |
May | 0.351003E+10 | 0.366642E+10 | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.00 | 0.00 |
June | 0.473942E+10 | 0.287802E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
July | 0.498421E+10 | 0.274433E+10 | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.00 | 0.00 |
August | 0.384123E+10 | 0.305688E+10 | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.00 | 0.00 |
September | 0.249856E+10 | 0.383738E+10 | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.00 | 0.00 |
October | 0.993085E+09 | 0.503804E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 0.175079E+09 | 0.593263E+10 | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.00 | 0.00 |
December | 22413353.46 | 0.752022E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.247989E+11 | 0.576174E+11 | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.00 | 0.00 |
Minimum of Months | 22413353.46 | 0.274433E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Maximum of Months | 0.498421E+10 | 0.752022E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101015E+10 | 0.442993E+10 | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.150570E+10 | 0.378986E+10 | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.00 | 0.00 |
March | 0.162638E+10 | 0.350935E+10 | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.00 | 0.00 |
April | 0.698212E+10 | 0.288613E+10 | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.00 | 0.00 |
May | 0.739288E+10 | 0.254347E+10 | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.00 | 0.00 |
June | 0.752768E+10 | 0.196986E+10 | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.00 | 0.00 |
July | 0.828655E+10 | 0.189370E+10 | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.00 | 0.00 |
August | 0.809679E+10 | 0.205784E+10 | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.00 | 0.00 |
September | 0.684438E+10 | 0.249142E+10 | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.00 | 0.00 |
October | 0.273578E+10 | 0.327718E+10 | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.00 | 0.00 |
November | 0.928257E+09 | 0.379105E+10 | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.630033E+09 | 0.479187E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.535667E+11 | 0.374317E+11 | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.630033E+09 | 0.189370E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.828655E+10 | 0.479187E+10 | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.689209E+10 | 0.652585E+10 | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.00 | 0.00 |
February | 0.778701E+10 | 0.583108E+10 | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.00 | 0.00 |
March | 0.426703E+10 | 0.541920E+10 | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.00 | 0.00 |
April | 0.118954E+11 | 0.476195E+10 | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.00 | 0.00 |
May | 0.941776E+10 | 0.418661E+10 | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.00 | 0.00 |
June | 0.871917E+10 | 0.318467E+10 | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.00 | 0.00 |
July | 0.105195E+11 | 0.307639E+10 | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.00 | 0.00 |
August | 0.130541E+11 | 0.337635E+10 | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.00 | 0.00 |
September | 0.148132E+11 | 0.409552E+10 | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.00 | 0.00 |
October | 0.943261E+10 | 0.516133E+10 | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.00 | 0.00 |
November | 0.585587E+10 | 0.581211E+10 | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.00 | 0.00 |
December | 0.465359E+10 | 0.722814E+10 | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107307E+12 | 0.586592E+11 | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426703E+10 | 0.307639E+10 | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148132E+11 | 0.722814E+10 | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.982762E+09 | 0.466418E+10 | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.204950E+10 | 0.407253E+10 | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.157185E+10 | 0.370194E+10 | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.00 | 0.00 |
April | 0.601529E+10 | 0.316317E+10 | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.00 | 0.00 |
May | 0.725602E+10 | 0.278726E+10 | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.00 | 0.00 |
June | 0.816307E+10 | 0.218324E+10 | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.00 | 0.00 |
July | 0.897958E+10 | 0.211946E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
August | 0.762568E+10 | 0.230337E+10 | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.00 | 0.00 |
September | 0.573421E+10 | 0.272701E+10 | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.00 | 0.00 |
October | 0.250634E+10 | 0.351896E+10 | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.00 | 0.00 |
November | 0.912908E+09 | 0.408020E+10 | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.00 | 0.00 |
December | 0.322398E+09 | 0.516761E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.521196E+11 | 0.404889E+11 | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322398E+09 | 0.211946E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.897958E+10 | 0.516761E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.397401E+11 | -0.387131E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102705E+10 | 58.98 | 0.00 | 0.00 |
February | 0.363411E+11 | -0.354136E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -927526730.1 | 58.98 | 0.00 | 0.00 |
March | 0.424104E+11 | -0.413821E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102831E+10 | 58.97 | 0.00 | 0.00 |
April | 0.377973E+11 | -0.368082E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989050766.9 | 58.98 | 0.00 | 0.00 |
May | 0.392810E+11 | -0.382564E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102465E+10 | 58.98 | 0.00 | 0.00 |
June | 0.378885E+11 | -0.368969E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991660445.9 | 58.98 | 0.00 | 0.00 |
July | 0.353619E+11 | -0.343429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101907E+10 | 58.98 | 0.00 | 0.00 |
August | 0.383313E+11 | -0.373083E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102297E+10 | 58.97 | 0.00 | 0.00 |
September | 0.350855E+11 | -0.340969E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988646250.1 | 58.97 | 0.00 | 0.00 |
October | 0.369476E+11 | -0.359261E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102153E+10 | 58.97 | 0.00 | 0.00 |
November | 0.372377E+11 | -0.362484E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989327169.6 | 58.98 | 0.00 | 0.00 |
December | 0.380847E+11 | -0.370603E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102443E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.454507E+12 | -0.442453E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120542E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.350855E+11 | -0.413821E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102831E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.424104E+11 | -0.340969E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -927526730.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4009.58 | 36.45 | 191.17 | 222.17 | 3328.65 | 37.57 | 193.67 | 194.67 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 5750.32 | 36.15 | 213.67 | 246.17 | 2653.30 | 30.40 | 199.83 | 218.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4254.16 | 31.42 | 190.83 | 310.67 | 1200.82 | 22.35 | 211.67 | 266.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2695.08 | 21.24 | 219.50 | 355.50 | 1501.20 | 22.65 | 292.83 | 329.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2153.32 | 20.83 | 198.67 | 410.67 | 1195.05 | 22.24 | 313.50 | 374.17 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:00 | 2099.28 | 21.10 | 204.00 | 413.17 | 1153.66 | 22.51 | 319.67 | 372.33 |
July | 429.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2092.00 | 20.88 | 200.33 | 421.50 | 1177.61 | 22.29 | 328.17 | 383.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2413.32 | 20.88 | 194.33 | 382.50 | 1372.68 | 22.31 | 309.83 | 349.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3543.99 | 22.83 | 185.67 | 331.17 | 1652.51 | 22.88 | 271.67 | 304.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:00 | 7274.45 | 35.37 | 217.17 | 280.00 | 2130.42 | 25.35 | 206.50 | 239.33 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4623.14 | 36.29 | 167.17 | 216.67 | 3816.53 | 37.47 | 170.83 | 173.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3889.58 | 37.35 | 128.67 | 183.33 | 3230.06 | 38.54 | 128.67 | 132.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3338.18 | 25.91 | 2311.17 | 3773.50 | 1758.71 | 25.31 | 2946.83 | 3338.17 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2092.00 | 20.83 | 128.67 | 183.33 | 1153.66 | 22.24 | 128.67 | 132.67 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7274.45 | 37.35 | 219.50 | 421.50 | 3816.53 | 38.54 | 328.17 | 383.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1480.02 | 24.87 | 88.17 | 210.67 | 871.33 | 24.86 | 102.00 | 146.33 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1804.35 | 25.06 | 94.00 | 239.33 | 994.67 | 25.18 | 126.00 | 195.00 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2036.81 | 25.11 | 98.83 | 304.83 | 1071.00 | 25.34 | 167.50 | 252.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3789.21 | 26.21 | 167.50 | 364.67 | 2180.12 | 26.45 | 259.67 | 339.67 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3885.28 | 25.10 | 152.67 | 423.00 | 1738.11 | 24.49 | 254.83 | 382.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3918.46 | 25.62 | 151.17 | 420.83 | 1780.79 | 25.20 | 271.17 | 389.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3831.56 | 25.78 | 168.17 | 432.17 | 1733.57 | 25.25 | 276.00 | 401.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3685.82 | 25.46 | 147.50 | 390.83 | 1619.48 | 24.72 | 268.83 | 361.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3489.17 | 25.87 | 152.67 | 338.50 | 1910.44 | 25.90 | 237.33 | 308.33 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2759.36 | 26.32 | 118.50 | 273.83 | 1240.19 | 25.13 | 158.17 | 216.00 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1516.18 | 24.80 | 82.50 | 205.17 | 859.44 | 24.87 | 97.33 | 137.17 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1280.34 | 25.47 | 65.67 | 166.00 | 880.40 | 26.79 | 79.50 | 99.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3148.67 | 25.54 | 1487.33 | 3769.83 | 1547.83 | 25.29 | 2298.33 | 3230.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1280.34 | 24.80 | 65.67 | 166.00 | 859.44 | 24.49 | 79.50 | 99.67 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3918.46 | 26.32 | 168.17 | 432.17 | 2180.12 | 26.79 | 276.00 | 401.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.59 | 0.48 | 01-JAN-10:30 | 547.26 | 16.20 | 0.00 | 188.83 | 315.11 | 17.76 | 0.00 | 77.33 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 726.39 | 17.91 | 0.00 | 224.50 | 421.64 | 19.38 | 16.67 | 143.50 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 891.03 | 18.63 | 0.17 | 300.67 | 481.28 | 19.89 | 41.17 | 220.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1191.74 | 20.25 | 28.00 | 360.83 | 706.01 | 21.59 | 248.67 | 329.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 1407.18 | 22.04 | 135.00 | 425.50 | 803.58 | 23.27 | 322.50 | 398.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1598.82 | 23.11 | 162.33 | 428.17 | 881.59 | 23.51 | 340.33 | 401.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1486.54 | 22.88 | 171.17 | 438.83 | 868.86 | 24.16 | 358.67 | 416.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1197.74 | 20.30 | 58.00 | 390.00 | 728.39 | 21.69 | 288.17 | 360.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 979.81 | 19.65 | 0.83 | 326.33 | 608.54 | 21.13 | 165.50 | 284.17 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:49 | 825.30 | 18.54 | 0.00 | 263.83 | 490.19 | 20.02 | 43.67 | 178.67 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:20 | 607.31 | 16.97 | 0.00 | 182.33 | 351.96 | 18.49 | 0.00 | 79.67 |
December | 131.67 | 0.59 | 0.48 | 02-DEC-10:00 | 514.04 | 16.45 | 0.00 | 135.00 | 299.58 | 18.07 | 0.00 | 42.00 |
Annual Sum or Average | 3515.67 | 0.52 | 1119.87 | 20.18 | 555.50 | 3664.83 | 651.21 | 21.45 | 1825.33 | 2931.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 514.04 | 16.20 | 0.00 | 135.00 | 299.58 | 17.76 | 0.00 | 42.00 | |
Maximum of Months | 429.00 | 0.59 | 0.48 | 1598.82 | 23.11 | 171.17 | 438.83 | 881.59 | 24.16 | 358.67 | 416.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:20 | 1337.70 | 24.12 | 85.33 | 203.83 | 760.18 | 24.14 | 99.50 | 147.00 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2088.04 | 24.32 | 91.50 | 234.00 | 1116.96 | 24.27 | 125.17 | 183.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1921.36 | 24.01 | 98.50 | 304.17 | 1031.86 | 24.26 | 158.00 | 252.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3626.14 | 24.08 | 139.17 | 355.33 | 1633.79 | 23.67 | 234.50 | 328.17 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-07:19 | 3286.11 | 22.30 | 95.00 | 413.50 | 1811.40 | 23.15 | 249.50 | 383.50 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3798.79 | 21.57 | 72.50 | 419.00 | 1691.52 | 21.85 | 248.50 | 381.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3773.36 | 21.47 | 65.33 | 428.00 | 1719.82 | 21.78 | 242.83 | 395.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3366.59 | 22.99 | 116.83 | 383.33 | 1866.10 | 23.61 | 239.00 | 351.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:20 | 3265.43 | 24.62 | 129.17 | 326.00 | 1777.71 | 24.98 | 205.33 | 298.50 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2596.89 | 25.54 | 113.50 | 269.17 | 1159.15 | 24.52 | 149.00 | 211.50 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1469.61 | 23.97 | 77.17 | 197.67 | 782.68 | 23.93 | 91.33 | 132.83 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:20 | 1060.12 | 22.34 | 46.33 | 161.17 | 549.15 | 22.11 | 54.00 | 83.00 |
Annual Sum or Average | 3515.67 | 0.52 | 2963.51 | 23.23 | 1130.33 | 3695.17 | 1481.01 | 23.39 | 2096.67 | 3147.67 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1060.12 | 21.47 | 46.33 | 161.17 | 549.15 | 21.78 | 54.00 | 83.00 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 3798.79 | 25.54 | 139.17 | 428.00 | 1866.10 | 24.98 | 249.50 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4034.20 | 36.02 | 190.67 | 222.17 | 3419.26 | 37.20 | 189.83 | 196.67 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5788.22 | 35.72 | 213.33 | 246.17 | 2817.48 | 29.99 | 141.83 | 224.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4267.23 | 30.13 | 181.17 | 310.67 | 1273.86 | 17.60 | 4.67 | 272.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2740.76 | 15.03 | 0.00 | 356.00 | 1605.88 | 18.51 | 17.17 | 333.33 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2187.87 | 14.74 | 0.00 | 410.83 | 1276.27 | 18.18 | 0.00 | 379.00 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:49 | 2129.77 | 15.07 | 0.00 | 413.50 | 1230.20 | 18.48 | 0.00 | 376.83 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 2127.70 | 14.87 | 0.00 | 421.83 | 1258.14 | 18.31 | 2.67 | 387.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2595.47 | 15.05 | 5.50 | 382.67 | 1469.83 | 18.20 | 8.67 | 352.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 4626.64 | 19.98 | 76.17 | 331.50 | 1772.83 | 18.54 | 12.33 | 307.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7310.13 | 34.61 | 216.17 | 280.17 | 2249.12 | 21.06 | 33.67 | 244.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4641.62 | 35.84 | 166.83 | 216.67 | 3915.40 | 37.12 | 167.17 | 176.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3899.47 | 36.85 | 128.50 | 183.67 | 3322.53 | 38.16 | 128.67 | 135.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3487.55 | 21.96 | 1178.33 | 3775.83 | 1856.16 | 21.92 | 706.67 | 3387.00 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2127.70 | 14.74 | 0.00 | 183.67 | 1230.20 | 17.60 | 0.00 | 135.67 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7310.13 | 36.85 | 216.17 | 421.83 | 3915.40 | 38.16 | 189.83 | 387.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1501.80 | 22.79 | 82.50 | 211.17 | 903.88 | 23.31 | 73.50 | 150.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1835.65 | 22.66 | 75.33 | 239.67 | 1038.65 | 23.33 | 70.17 | 201.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2061.78 | 21.21 | 71.33 | 305.67 | 1116.38 | 23.38 | 65.17 | 257.33 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3807.79 | 22.15 | 107.17 | 364.33 | 2266.30 | 24.35 | 92.83 | 345.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3942.40 | 22.24 | 134.00 | 423.17 | 1818.13 | 21.95 | 72.17 | 389.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3969.56 | 22.82 | 139.17 | 421.17 | 1862.80 | 22.77 | 81.50 | 392.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3876.24 | 22.35 | 139.67 | 433.00 | 1816.65 | 22.83 | 87.17 | 404.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3747.33 | 22.70 | 127.83 | 391.83 | 1700.53 | 22.29 | 72.00 | 365.17 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3546.39 | 23.02 | 109.33 | 338.83 | 1988.73 | 23.79 | 85.33 | 311.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2768.48 | 22.90 | 85.00 | 274.50 | 1298.39 | 23.14 | 69.00 | 221.00 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1540.59 | 22.56 | 64.83 | 206.17 | 895.00 | 23.22 | 69.00 | 140.83 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1301.83 | 23.34 | 52.67 | 167.50 | 911.94 | 25.49 | 65.67 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3188.48 | 22.53 | 1188.83 | 3777.00 | 1616.62 | 23.14 | 903.50 | 3281.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1301.83 | 21.21 | 52.67 | 167.50 | 895.00 | 21.95 | 65.17 | 102.50 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3969.56 | 23.34 | 139.67 | 433.00 | 2266.30 | 25.49 | 92.83 | 404.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:20 | 552.50 | 10.31 | 0.00 | 189.50 | 334.29 | 13.82 | 0.00 | 89.33 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-11:00 | 735.03 | 12.19 | 0.00 | 224.83 | 447.83 | 15.67 | 0.00 | 153.33 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 902.91 | 12.69 | 0.00 | 300.67 | 510.92 | 16.01 | 0.00 | 232.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1212.63 | 15.04 | 0.00 | 360.83 | 751.98 | 18.46 | 5.83 | 334.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1431.05 | 16.95 | 38.00 | 425.83 | 855.98 | 20.21 | 54.17 | 402.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1625.97 | 18.21 | 58.17 | 428.17 | 969.03 | 21.32 | 80.83 | 405.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1515.83 | 18.08 | 58.83 | 439.17 | 924.02 | 21.23 | 80.33 | 419.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1235.13 | 14.95 | 0.00 | 391.83 | 776.00 | 18.45 | 6.83 | 363.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 996.23 | 14.55 | 0.00 | 326.50 | 648.19 | 18.03 | 0.00 | 289.00 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:40 | 836.23 | 13.07 | 0.00 | 264.17 | 521.04 | 16.52 | 0.00 | 186.17 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:09 | 613.53 | 11.06 | 0.00 | 182.83 | 373.52 | 14.59 | 0.00 | 88.33 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-10:50 | 518.64 | 10.26 | 0.00 | 135.67 | 317.74 | 13.96 | 0.00 | 50.17 |
Annual Sum or Average | 3515.67 | 0.51 | 1140.14 | 14.86 | 155.00 | 3670.00 | 696.53 | 18.23 | 228.00 | 3015.00 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 518.64 | 10.26 | 0.00 | 135.67 | 317.74 | 13.82 | 0.00 | 50.17 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1625.97 | 18.21 | 58.83 | 439.17 | 969.03 | 21.32 | 80.83 | 419.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:09 | 1357.81 | 22.02 | 78.00 | 205.00 | 791.52 | 22.56 | 68.83 | 154.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2085.44 | 20.35 | 58.33 | 234.33 | 1166.66 | 22.25 | 61.50 | 188.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1954.16 | 21.18 | 72.33 | 305.33 | 1076.36 | 22.15 | 54.17 | 255.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:00 | 3683.53 | 21.13 | 101.83 | 355.83 | 1710.82 | 21.10 | 50.00 | 332.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3336.51 | 18.73 | 73.83 | 414.00 | 1889.47 | 20.35 | 45.50 | 386.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:00 | 3850.23 | 17.73 | 50.33 | 420.33 | 1775.89 | 18.63 | 0.00 | 384.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3822.28 | 17.63 | 53.17 | 428.83 | 1804.95 | 18.59 | 3.67 | 399.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3410.33 | 19.72 | 86.83 | 383.17 | 1945.99 | 21.02 | 57.33 | 354.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 3302.10 | 21.52 | 96.83 | 325.33 | 1848.48 | 22.78 | 76.50 | 302.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2613.30 | 22.27 | 81.67 | 270.83 | 1213.99 | 22.49 | 64.83 | 216.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:50 | 1492.92 | 21.61 | 59.50 | 199.67 | 817.33 | 22.19 | 65.00 | 136.83 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:09 | 1077.29 | 19.80 | 37.67 | 161.83 | 575.37 | 20.30 | 37.00 | 89.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3001.64 | 19.95 | 850.33 | 3704.50 | 1548.06 | 20.90 | 584.33 | 3201.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1077.29 | 17.63 | 37.67 | 161.83 | 575.37 | 18.59 | 0.00 | 89.00 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3850.23 | 22.27 | 101.83 | 428.83 | 1945.99 | 22.78 | 76.50 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4035.07 | 36.02 | 190.67 | 222.17 | 3421.02 | 37.19 | 189.83 | 196.83 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5790.02 | 35.71 | 213.33 | 246.17 | 2820.02 | 29.98 | 141.83 | 224.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4270.56 | 30.12 | 181.17 | 310.83 | 1276.39 | 17.59 | 4.67 | 272.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2744.66 | 15.00 | 0.00 | 356.00 | 1608.37 | 18.50 | 16.83 | 333.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2191.06 | 14.71 | 0.00 | 410.83 | 1278.23 | 18.17 | 0.00 | 379.17 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 2132.94 | 15.04 | 0.00 | 413.67 | 1232.12 | 18.46 | 0.00 | 376.83 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 2130.68 | 14.84 | 0.00 | 421.83 | 1260.00 | 18.30 | 2.50 | 387.50 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2598.81 | 15.02 | 5.50 | 382.67 | 1471.97 | 18.19 | 8.17 | 352.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 4629.94 | 19.96 | 76.17 | 331.50 | 1775.35 | 18.53 | 12.00 | 307.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7312.44 | 34.60 | 216.17 | 280.17 | 2251.99 | 21.05 | 33.67 | 244.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4642.61 | 35.83 | 166.83 | 216.67 | 3917.68 | 37.12 | 167.17 | 176.67 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3900.25 | 36.84 | 128.50 | 183.67 | 3324.20 | 38.16 | 128.67 | 136.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3490.35 | 21.94 | 1178.33 | 3776.17 | 1858.36 | 21.91 | 705.33 | 3388.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2130.68 | 14.71 | 0.00 | 183.67 | 1232.12 | 17.59 | 0.00 | 136.00 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7312.44 | 36.84 | 216.17 | 421.83 | 3917.68 | 38.16 | 189.83 | 387.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1502.63 | 22.77 | 82.50 | 211.17 | 904.76 | 23.30 | 73.33 | 150.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1836.79 | 22.63 | 75.33 | 239.67 | 1039.84 | 23.32 | 69.83 | 201.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2063.84 | 21.19 | 71.33 | 305.67 | 1117.94 | 23.37 | 65.00 | 257.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3809.81 | 22.13 | 107.17 | 364.33 | 2268.26 | 24.34 | 92.83 | 345.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3944.80 | 22.22 | 134.00 | 423.17 | 1820.09 | 21.94 | 72.17 | 389.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3972.15 | 22.79 | 139.17 | 421.17 | 1864.85 | 22.76 | 81.50 | 392.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3878.56 | 22.32 | 139.67 | 433.00 | 1818.61 | 22.82 | 87.17 | 404.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3749.14 | 22.68 | 127.83 | 391.83 | 1702.34 | 22.27 | 72.00 | 365.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3547.68 | 22.99 | 109.33 | 339.00 | 1990.38 | 23.77 | 85.00 | 311.83 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2769.76 | 22.88 | 85.00 | 274.83 | 1299.80 | 23.12 | 68.67 | 221.17 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1541.54 | 22.53 | 64.83 | 206.33 | 896.01 | 23.21 | 68.33 | 140.83 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1302.56 | 23.31 | 52.67 | 167.67 | 912.82 | 25.48 | 65.33 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3190.28 | 22.51 | 1188.83 | 3777.83 | 1618.28 | 23.12 | 901.17 | 3283.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1302.56 | 21.19 | 52.67 | 167.67 | 896.01 | 21.94 | 65.00 | 102.50 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3972.15 | 23.31 | 139.67 | 433.00 | 2268.26 | 25.48 | 92.83 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:20 | 553.06 | 10.28 | 0.00 | 189.67 | 334.78 | 13.80 | 0.00 | 90.00 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-11:00 | 735.78 | 12.16 | 0.00 | 224.83 | 448.47 | 15.65 | 0.00 | 153.33 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 904.19 | 12.66 | 0.00 | 301.00 | 511.80 | 15.99 | 0.00 | 233.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1213.77 | 15.01 | 0.00 | 361.00 | 752.99 | 18.44 | 5.17 | 335.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1432.53 | 16.93 | 38.00 | 426.00 | 857.16 | 20.20 | 53.50 | 402.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1627.69 | 18.19 | 58.17 | 428.17 | 970.36 | 21.31 | 79.50 | 405.83 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1517.28 | 18.05 | 58.83 | 439.17 | 925.23 | 21.21 | 79.50 | 420.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1236.19 | 14.92 | 0.00 | 391.83 | 776.98 | 18.44 | 6.67 | 363.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 996.96 | 14.52 | 0.00 | 326.50 | 648.96 | 18.02 | 0.00 | 289.33 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:40 | 837.00 | 13.03 | 0.00 | 264.17 | 521.75 | 16.50 | 0.00 | 186.33 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:09 | 614.14 | 11.03 | 0.00 | 183.17 | 374.06 | 14.57 | 0.00 | 88.67 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-10:50 | 519.11 | 10.23 | 0.00 | 136.00 | 318.20 | 13.94 | 0.00 | 50.17 |
Annual Sum or Average | 3515.67 | 0.51 | 1141.25 | 14.83 | 155.00 | 3671.50 | 697.47 | 18.22 | 224.33 | 3017.83 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 519.11 | 10.23 | 0.00 | 136.00 | 318.20 | 13.80 | 0.00 | 50.17 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1627.69 | 18.19 | 58.83 | 439.17 | 970.36 | 21.31 | 79.50 | 420.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:09 | 1358.66 | 21.99 | 78.00 | 205.33 | 792.43 | 22.55 | 68.83 | 154.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2086.58 | 20.32 | 58.33 | 234.50 | 1167.93 | 22.24 | 60.83 | 189.17 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1956.21 | 21.15 | 72.33 | 305.50 | 1077.95 | 22.14 | 54.00 | 256.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:00 | 3685.56 | 21.10 | 101.83 | 355.83 | 1712.73 | 21.08 | 50.00 | 332.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3338.79 | 18.70 | 73.83 | 414.00 | 1891.42 | 20.34 | 45.50 | 386.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:00 | 3852.82 | 17.70 | 50.33 | 420.33 | 1778.02 | 18.61 | 0.00 | 384.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3824.49 | 17.60 | 53.17 | 428.83 | 1806.93 | 18.57 | 3.67 | 399.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3412.36 | 19.69 | 86.83 | 383.17 | 1947.92 | 21.00 | 57.00 | 354.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 3303.63 | 21.49 | 96.83 | 325.33 | 1850.13 | 22.77 | 76.17 | 302.83 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2614.65 | 22.24 | 81.67 | 270.83 | 1215.43 | 22.47 | 64.67 | 217.17 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:50 | 1493.92 | 21.58 | 59.50 | 199.83 | 818.35 | 22.18 | 65.00 | 137.00 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:09 | 1078.07 | 19.78 | 37.67 | 162.17 | 576.18 | 20.29 | 36.83 | 89.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3003.47 | 19.92 | 850.33 | 3705.67 | 1549.75 | 20.89 | 582.50 | 3203.00 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1078.07 | 17.60 | 37.67 | 162.17 | 576.18 | 18.57 | 0.00 | 89.00 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3852.82 | 22.24 | 101.83 | 428.83 | 1947.92 | 22.77 | 76.17 | 399.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.625860E+10 | 27897.15 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367170E+10 | 23311.79 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176614E+10 | 15890.11 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132298E+09 | 11991.73 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43050393.41 | 7826.83 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2144.86 | 0.90 | 02-JUN-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3265.85 | 1.02 | 05-JUL-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2543.98 | 1.01 | 22-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4882626.12 | 2839.00 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204470E+09 | 8057.77 | 07-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151259E+10 | 17697.72 | 29-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406180E+10 | 21219.79 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2144.86 | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625860E+10 | 27897.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 75033804.20 | 9618.16 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3198866.87 | 842.66 | 17-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 378489.69 | 105.01 | 30-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78611160.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75033804.20 | 9618.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214084E+09 | 9150.07 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83809011.49 | 5054.45 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14669528.54 | 1847.62 | 04-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 978529.57 | 338.95 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49716621.16 | 2114.90 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235571E+09 | 9181.84 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.598829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235571E+09 | 9181.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344125E+09 | 15413.77 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139307E+09 | 15426.27 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41052624.31 | 2782.25 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 192327.85 | 739.14 | 05-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3299871.86 | 807.60 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84517338.96 | 9821.54 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320256E+09 | 15446.56 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344125E+09 | 15446.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19988542.37 | 2111.50 | 10-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19988542.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19988542.37 | 2111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108736E+12 | 310216.52 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.687558E+11 | 259736.38 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486011E+11 | 188164.73 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647908E+10 | 153538.73 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170009E+10 | 96200.94 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13311208.21 | 12417.01 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.270370E+09 | 52095.95 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735580E+10 | 100792.14 | 12-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420293E+11 | 210327.71 | 29-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102812E+12 | 242925.64 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108736E+12 | 310216.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.459210E+09 | 430317.92 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7764549.74 | 7841.29 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.459210E+09 | 430317.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197914E+11 | 114547.41 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127338E+11 | 113568.00 | 27-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.617368E+10 | 121746.98 | 31-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.445024E+09 | 59499.97 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53206234.72 | 122603.75 | 06-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 652937.96 | 1088.23 | 21-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265451E+10 | 112992.71 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109203E+11 | 113515.32 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259415E+11 | 113538.75 | 12-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.259415E+11 | 122603.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189953E+11 | 149958.73 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129786E+11 | 149681.58 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.846318E+10 | 151503.43 | 31-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500727E+09 | 50738.14 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229983E+09 | 98773.53 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412329.12 | 2748.86 | 07-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50262062.06 | 10658.61 | 21-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428065E+10 | 148906.74 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127910E+11 | 149959.38 | 28-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258272E+11 | 149995.41 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.841172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258272E+11 | 151503.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156422E+11 | 218449.60 | 04-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.994542E+10 | 217883.42 | 16-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.778336E+10 | 217840.95 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.658407E+09 | 34390.12 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719350E+09 | 184250.19 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11701345.52 | 14564.75 | 08-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2592235.30 | 2181.26 | 07-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314520E+10 | 184747.56 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101345E+11 | 218254.55 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262590E+11 | 218486.57 | 06-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.743017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.262590E+11 | 218486.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156598E+11 | 144762.18 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.934546E+10 | 144297.09 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580577E+10 | 144382.50 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372527E+09 | 17216.24 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.351767E+09 | 94082.20 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61257598.17 | 14775.44 | 07-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317403E+10 | 93196.40 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.976566E+10 | 144523.68 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217324E+11 | 144591.35 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217324E+11 | 144762.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138339E+11 | 35236.87 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.966856E+10 | 31165.76 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752160E+10 | 23492.30 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145469E+10 | 20099.13 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511802E+09 | 13901.43 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10827232.73 | 4272.00 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 281.63 | 0.47 | 05-JUL-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 290938.16 | 501.79 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98645112.82 | 9032.78 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172448E+10 | 14818.06 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.660253E+10 | 25433.78 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133876E+11 | 27907.98 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 281.63 | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138339E+11 | 35236.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428015E+10 | 75672.71 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247005E+10 | 75665.26 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123601E+10 | 75634.93 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17032482.25 | 5097.58 | 03-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.514997E+09 | 75370.20 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215305E+10 | 75625.01 | 20-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528336E+10 | 75634.94 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.528336E+10 | 75672.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.528916E+10 | 12648.90 | 30-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388667E+10 | 12647.63 | 27-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270535E+10 | 12619.24 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591159E+09 | 12516.94 | 05-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337045E+09 | 12561.74 | 05-MAY-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8539667.68 | 10758.01 | 07-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6423625.76 | 12518.00 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4073832.40 | 1672.98 | 28-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200839E+09 | 12522.65 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168150E+10 | 12650.18 | 16-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365641E+10 | 12649.57 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.622773E+10 | 12649.69 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4073832.40 | 1672.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.622773E+10 | 12650.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.387677E+10 | 17450.24 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286123E+10 | 17433.29 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227192E+10 | 17420.48 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323547E+09 | 17386.13 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213683E+09 | 17377.61 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9605199.25 | 7165.04 | 07-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2859396.57 | 4387.85 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5184014.19 | 1527.40 | 23-AUG-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114853E+09 | 10573.11 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140043E+10 | 17428.02 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294020E+10 | 17438.58 | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.474507E+10 | 17422.06 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2859396.57 | 1527.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.474507E+10 | 17450.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414115E+10 | 26050.10 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303359E+10 | 26048.74 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285769E+10 | 26020.31 | 07-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.626566E+09 | 21201.34 | 25-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571489E+09 | 25984.73 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72572778.96 | 19568.59 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29607391.72 | 5331.85 | 01-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11091465.92 | 1189.47 | 12-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161451E+09 | 10813.92 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162151E+10 | 26020.50 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322288E+10 | 26056.77 | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571361E+10 | 26031.71 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11091465.92 | 1189.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571361E+10 | 26056.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340442E+10 | 17746.25 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231893E+10 | 17734.43 | 27-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183912E+10 | 17727.47 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.364315E+09 | 11542.30 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301228E+09 | 17700.96 | 05-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18377417.39 | 4255.32 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11141315.27 | 1782.28 | 01-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1102435.17 | 458.86 | 24-AUG-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141806E+09 | 9163.43 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123674E+10 | 17714.92 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246018E+10 | 17733.98 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404530E+10 | 17742.34 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1102435.17 | 458.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404530E+10 | 17746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 231.53 | 1.00 | 18-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 274.68 | 0.81 | 19-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104.56 | 0.70 | 09-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 180.36 | 0.99 | 29-AUG-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 108.55 | 0.90 | 11-SEP-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 148.25 | 0.99 | 07-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1047.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 274.68 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.463960E+10 | 0.463439E+10 | 83220.98 | 30-APR-15:12 | 83220.98 | 0.03 |
May | 0.00 | 0.00 | 0.561799E+10 | 0.561799E+10 | 99233.01 | 22-MAY-15:00 | 99233.01 | 0.07 |
June | 0.00 | 0.00 | 0.182839E+11 | 0.180132E+11 | 124972.57 | 13-JUN-16:00 | 113911.00 | 0.23 |
July | 0.00 | 0.00 | 0.311273E+11 | 0.310805E+11 | 120577.11 | 21-JUL-15:20 | 120577.11 | 0.40 |
August | 0.00 | 0.00 | 0.412213E+11 | 0.410759E+11 | 125866.71 | 14-AUG-15:10 | 125866.71 | 0.48 |
September | 0.00 | 0.00 | 0.192813E+11 | 0.192503E+11 | 89815.27 | 13-SEP-14:20 | 89815.27 | 0.27 |
October | 0.00 | 0.00 | 0.103818E+10 | 0.103818E+10 | 24890.33 | 11-OCT-15:00 | 24890.33 | 0.00 |
November | 0.00 | 0.00 | 12987169.27 | 12987169.27 | 8023.87 | 24-NOV-12:00 | 8023.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121223E+12 | 0.120723E+12 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.412213E+11 | 0.410759E+11 | 125866.71 | 125866.71 | 0.48 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47151.58 | 47151.58 | 3.32 | 02-JAN-04:30 | 3.32 | 0.00 |
February | 0.00 | 0.00 | 40396.28 | 40396.28 | 1.36 | 17-FEB-06:01 | 1.36 | 0.01 |
March | 0.00 | 0.00 | 78365.53 | 78365.53 | 3.29 | 27-MAR-05:40 | 3.29 | 0.00 |
April | 0.00 | 0.00 | 0.384183E+11 | 0.383991E+11 | 823260.19 | 30-APR-15:12 | 823260.19 | 0.03 |
May | 0.00 | 0.00 | 0.480701E+11 | 0.480701E+11 | 856154.24 | 22-MAY-15:00 | 856154.24 | 0.07 |
June | 0.00 | 0.00 | 0.151882E+12 | 0.149702E+12 | 1131958.52 | 13-JUN-16:00 | 1020636.39 | 0.23 |
July | 0.00 | 0.00 | 0.246517E+12 | 0.246250E+12 | 1073360.03 | 21-JUL-15:30 | 1073360.03 | 0.39 |
August | 0.00 | 0.00 | 0.310642E+12 | 0.309945E+12 | 1011503.12 | 14-AUG-15:40 | 1011503.12 | 0.48 |
September | 0.00 | 0.00 | 0.169679E+12 | 0.168691E+12 | 845817.44 | 13-SEP-14:40 | 845817.44 | 0.28 |
October | 0.00 | 0.00 | 0.869778E+10 | 0.869778E+10 | 227160.15 | 07-OCT-15:00 | 227160.15 | 0.01 |
November | 0.00 | 0.00 | 50104132.06 | 50104132.06 | 37231.99 | 24-NOV-12:00 | 37231.99 | 0.01 |
December | 0.00 | 0.00 | 39711.52 | 39711.52 | 3.61 | 16-DEC-05:15 | 3.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.973956E+12 | 0.969804E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 39711.52 | 39711.52 | 1.36 | 1.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.310642E+12 | 0.309945E+12 | 1131958.52 | 1073360.03 | 0.48 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 77901.77 | 77901.77 | 366.61 | 02-JAN-04:30 | 366.61 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.370326E+10 | 0.370326E+10 | 84578.02 | 30-APR-15:32 | 84578.02 | 0.03 |
May | 0.00 | 0.00 | 0.484941E+10 | 0.484941E+10 | 93629.63 | 22-MAY-15:00 | 93629.63 | 0.07 |
June | 0.00 | 0.00 | 0.157259E+11 | 0.155135E+11 | 131962.62 | 13-JUN-16:00 | 121549.21 | 0.21 |
July | 0.00 | 0.00 | 0.251205E+11 | 0.250988E+11 | 125074.34 | 21-JUL-15:40 | 125074.34 | 0.37 |
August | 0.00 | 0.00 | 0.297960E+11 | 0.297619E+11 | 115879.85 | 14-AUG-15:40 | 115879.85 | 0.46 |
September | 0.00 | 0.00 | 0.152895E+11 | 0.152650E+11 | 86292.81 | 13-SEP-15:00 | 86292.81 | 0.26 |
October | 0.00 | 0.00 | 0.623258E+09 | 0.623258E+09 | 21582.06 | 07-OCT-15:00 | 21582.06 | 0.00 |
November | 0.00 | 0.00 | 4559993.44 | 4559993.44 | 3485.91 | 24-NOV-12:00 | 3485.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.951125E+11 | 0.948197E+11 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.297960E+11 | 0.297619E+11 | 131962.62 | 125074.34 | 0.46 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1667287.05 | 811174.26 | 5948.13 | 18-MAR-05:02 | 2700.71 | 0.00 |
April | 0.00 | 0.00 | 0.751880E+09 | 0.751880E+09 | 28478.73 | 28-APR-15:00 | 28478.73 | 0.01 |
May | 0.00 | 0.00 | 0.227142E+10 | 0.227142E+10 | 57514.92 | 22-MAY-15:00 | 57514.92 | 0.04 |
June | 0.00 | 0.00 | 0.824059E+10 | 0.817182E+10 | 65108.16 | 27-JUN-05:03 | 26344.34 | 0.12 |
July | 0.00 | 0.00 | 0.135545E+11 | 0.134261E+11 | 66040.79 | 10-JUL-11:00 | 66040.79 | 0.24 |
August | 0.00 | 0.00 | 0.178470E+11 | 0.177709E+11 | 65567.08 | 14-AUG-16:00 | 65567.08 | 0.33 |
September | 0.00 | 0.00 | 0.851000E+10 | 0.846358E+10 | 58553.86 | 16-SEP-05:02 | 27989.39 | 0.16 |
October | 0.00 | 0.00 | 0.162845E+09 | 0.144688E+09 | 36665.91 | 20-OCT-05:02 | 15987.16 | 0.00 |
November | 0.00 | 0.00 | 21877835.12 | 18968296.88 | 16264.68 | 15-NOV-05:12 | 16264.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513617E+11 | 0.510202E+11 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178470E+11 | 0.177709E+11 | 66040.79 | 66040.79 | 0.33 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.369871E+10 | 0.369851E+10 | 2947.41 | 10-JAN-17:05 | 2947.41 | 0.00 |
February | 0.00 | 0.00 | 0.607995E+10 | 0.596901E+10 | 5124.22 | 20-FEB-15:50 | 5124.22 | 0.00 |
March | 0.00 | 0.00 | 0.110236E+11 | 0.105064E+11 | 5613.14 | 31-MAR-23:10 | 5613.14 | 0.00 |
April | 0.00 | 0.00 | 0.608287E+11 | 0.571462E+11 | 327015.39 | 30-APR-17:41 | 327015.39 | 0.00 |
May | 0.00 | 0.00 | 0.227118E+10 | 0.224194E+10 | 53375.05 | 22-MAY-15:00 | 49331.05 | 0.00 |
June | 0.00 | 0.00 | 0.220522E+11 | 0.186313E+11 | 221370.72 | 13-JUN-17:00 | 218697.39 | 0.00 |
July | 0.00 | 0.00 | 0.123580E+12 | 0.979977E+11 | 312732.90 | 21-JUL-16:00 | 312732.90 | 0.00 |
August | 0.00 | 0.00 | 0.397848E+12 | 0.288100E+12 | 386006.10 | 14-AUG-13:00 | 325500.27 | 0.00 |
September | 0.00 | 0.00 | 0.120084E+10 | 0.113463E+10 | 28413.33 | 13-SEP-16:00 | 24024.12 | 0.00 |
October | 0.00 | 0.00 | 0.313532E+10 | 0.302402E+10 | 12799.05 | 07-OCT-15:00 | 12799.05 | 0.00 |
November | 0.00 | 0.00 | 0.762256E+10 | 0.713840E+10 | 29223.15 | 24-NOV-12:00 | 23023.48 | 0.00 |
December | 0.00 | 0.00 | 0.146441E+11 | 0.134742E+11 | 39688.50 | 23-DEC-11:00 | 39688.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.653986E+12 | 0.509063E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.120084E+10 | 0.113463E+10 | 2947.41 | 2947.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.397848E+12 | 0.288100E+12 | 386006.10 | 327015.39 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.419350E+10 | 0.419200E+10 | 2324.99 | 01-JAN-16:10 | 2319.22 | 0.00 |
February | 0.00 | 0.00 | 0.871238E+10 | 0.871110E+10 | 4539.20 | 19-FEB-16:57 | 4539.20 | 0.00 |
March | 0.00 | 0.00 | 0.150690E+11 | 0.150687E+11 | 7596.46 | 31-MAR-24:00 | 7596.46 | 0.00 |
April | 0.00 | 0.00 | 0.200713E+11 | 0.200708E+11 | 8945.29 | 30-APR-18:10 | 8945.29 | 0.00 |
May | 0.00 | 0.00 | 0.544479E+10 | 0.542491E+10 | 3939.38 | 31-MAY-24:00 | 3939.38 | 0.00 |
June | 0.00 | 0.00 | 0.105880E+11 | 0.105024E+11 | 5777.56 | 30-JUN-24:00 | 5777.56 | 0.00 |
July | 0.00 | 0.00 | 0.161970E+11 | 0.160798E+11 | 7836.62 | 31-JUL-24:00 | 7836.62 | 0.00 |
August | 0.00 | 0.00 | 0.212244E+11 | 0.210896E+11 | 8831.79 | 13-AUG-18:14 | 8808.97 | 0.00 |
September | 0.00 | 0.00 | 0.545002E+10 | 0.538528E+10 | 3798.44 | 30-SEP-24:00 | 3798.44 | 0.00 |
October | 0.00 | 0.00 | 0.102552E+11 | 0.102288E+11 | 5649.39 | 31-OCT-24:00 | 5649.39 | 0.00 |
November | 0.00 | 0.00 | 0.145890E+11 | 0.145732E+11 | 6194.55 | 19-NOV-16:05 | 6194.55 | 0.00 |
December | 0.00 | 0.00 | 0.198491E+11 | 0.198490E+11 | 7962.87 | 25-DEC-15:15 | 7962.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151644E+12 | 0.151176E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.419350E+10 | 0.419200E+10 | 2324.99 | 2319.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212244E+11 | 0.210896E+11 | 8945.29 | 8945.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.212053E+11 | 0.211911E+11 | 19731.30 | 19-JAN-16:20 | 19731.30 | 0.00 |
February | 0.00 | 0.00 | 0.672217E+11 | 0.672085E+11 | 40549.58 | 27-FEB-17:00 | 40549.58 | 0.00 |
March | 0.00 | 0.00 | 0.127481E+12 | 0.127478E+12 | 67991.42 | 31-MAR-23:40 | 67991.42 | 0.00 |
April | 0.00 | 0.00 | 0.183652E+12 | 0.183646E+12 | 85084.09 | 30-APR-18:05 | 85084.09 | 0.00 |
May | 0.00 | 0.00 | 0.442748E+11 | 0.440789E+11 | 35906.91 | 31-MAY-23:40 | 35906.91 | 0.00 |
June | 0.00 | 0.00 | 0.961034E+11 | 0.952545E+11 | 52367.51 | 30-JUN-23:40 | 52367.51 | 0.00 |
July | 0.00 | 0.00 | 0.149975E+12 | 0.148816E+12 | 73457.10 | 31-JUL-23:50 | 73457.10 | 0.00 |
August | 0.00 | 0.00 | 0.198391E+12 | 0.197057E+12 | 82336.99 | 13-AUG-18:03 | 82126.86 | 0.00 |
September | 0.00 | 0.00 | 0.450731E+11 | 0.444431E+11 | 33616.10 | 30-SEP-23:30 | 33616.10 | 0.00 |
October | 0.00 | 0.00 | 0.841901E+11 | 0.839289E+11 | 48535.29 | 31-OCT-24:00 | 48535.29 | 0.00 |
November | 0.00 | 0.00 | 0.120536E+12 | 0.120379E+12 | 56374.47 | 10-NOV-16:10 | 56156.78 | 0.00 |
December | 0.00 | 0.00 | 0.164812E+12 | 0.164811E+12 | 70491.68 | 21-DEC-15:20 | 70491.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130292E+13 | 0.129829E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.212053E+11 | 0.211911E+11 | 19731.30 | 19731.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198391E+12 | 0.197057E+12 | 85084.09 | 85084.09 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.703887E+09 | 0.702965E+09 | 1876.94 | 19-JAN-16:30 | 1876.94 | 0.00 |
February | 0.00 | 0.00 | 0.503794E+10 | 0.503669E+10 | 3842.15 | 27-FEB-17:00 | 3842.15 | 0.00 |
March | 0.00 | 0.00 | 0.112298E+11 | 0.112295E+11 | 6341.00 | 31-MAR-23:20 | 6341.00 | 0.00 |
April | 0.00 | 0.00 | 0.175431E+11 | 0.175426E+11 | 8622.94 | 30-APR-17:56 | 8622.94 | 0.00 |
May | 0.00 | 0.00 | 0.368298E+10 | 0.366356E+10 | 3444.85 | 31-MAY-23:20 | 3444.85 | 0.00 |
June | 0.00 | 0.00 | 0.922992E+10 | 0.914523E+10 | 4990.98 | 30-JUN-23:20 | 4990.98 | 0.00 |
July | 0.00 | 0.00 | 0.146794E+11 | 0.145636E+11 | 7192.90 | 31-JUL-23:20 | 7192.90 | 0.00 |
August | 0.00 | 0.00 | 0.195075E+11 | 0.193744E+11 | 8314.10 | 13-AUG-18:03 | 8292.96 | 0.00 |
September | 0.00 | 0.00 | 0.382994E+10 | 0.376794E+10 | 2815.32 | 30-SEP-23:10 | 2815.32 | 0.00 |
October | 0.00 | 0.00 | 0.697031E+10 | 0.694482E+10 | 4338.94 | 31-OCT-23:20 | 4338.94 | 0.00 |
November | 0.00 | 0.00 | 0.103439E+11 | 0.103284E+11 | 5567.60 | 10-NOV-16:10 | 5546.04 | 0.00 |
December | 0.00 | 0.00 | 0.145409E+11 | 0.145407E+11 | 6837.12 | 21-DEC-15:20 | 6837.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117300E+12 | 0.116840E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.703887E+09 | 0.702965E+09 | 1876.94 | 1876.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195075E+11 | 0.193744E+11 | 8622.94 | 8622.94 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 82078.13 | 1358254.01 | 02-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58355.17 | 1151549.10 | 27-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 36054.73 | 1051173.15 | 27-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4590.79 | 250343.88 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1867.26 | 902749.92 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.21 | 58444.88 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.30 | 27727.25 | 31-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 7.56 | 2874.12 | 23-AUG-05:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 424.76 | 74651.56 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10771.51 | 988057.00 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 41583.85 | 1218267.58 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 91603.13 | 1138643.64 | 11-DEC-05:11 |
Annual Sum or Average | 0.00 | 27200.09 | ||||
Minimum of Months | 0.00 | 0.00 | 7.56 | 2874.12 | ||
Maximum of Months | 0.00 | 0.00 | 91603.13 | 1358254.01 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.30 | 31-JAN-07:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.01 | 0.56 | 28-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31.74 | 2853.51 | 20-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18502.09 | 784779.56 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23052.42 | 1305261.71 | 22-MAY-14:20 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 77752.10 | 1450607.29 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121770.91 | 1597585.22 | 22-JUL-16:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 151816.87 | 1348072.63 | 28-AUG-14:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 84872.39 | 1161528.78 | 12-SEP-15:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4059.00 | 266194.15 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 74.20 | 48722.73 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 51.60 | 2820.01 | 16-DEC-05:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 40439.13 | 0.00 | ||||
Minimum of Months | 0.00 | 0.30 | 0.00 | 0.00 | ||
Maximum of Months | 151816.87 | 1597585.22 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.14 | 02-JAN-04:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.02 | 288.03 | 18-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18474.32 | 1129266.07 | 30-APR-15:51 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23079.71 | 1468219.33 | 22-MAY-14:10 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 77835.05 | 1778768.43 | 12-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121486.59 | 1376680.46 | 21-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 151174.34 | 1672175.19 | 28-AUG-13:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 85157.45 | 1895243.62 | 12-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 3934.18 | 267869.61 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36.45 | 49532.89 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.01 | 2.22 | 16-DEC-05:15 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 40369.91 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 151174.34 | 1895243.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18053.64 | 34150.35 | 19-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 48878.19 | 67702.30 | 17-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80126.56 | 112083.30 | 31-MAR-23:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 151902.38 | 1113158.30 | 30-APR-18:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 32860.46 | 435701.41 | 22-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 91855.28 | 961396.98 | 13-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 200581.19 | 1345343.83 | 22-JUL-18:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 395991.67 | 1322833.80 | 14-AUG-17:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43595.43 | 344335.08 | 13-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 52109.44 | 130944.06 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76756.14 | 114809.14 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102613.28 | 147420.96 | 23-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 108614.49 | 0.00 | ||||
Minimum of Months | 18053.64 | 34150.35 | 0.00 | 0.00 | ||
Maximum of Months | 395991.67 | 1345343.83 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15864.80 | 53217.99 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16048.09 | 53334.20 | 17-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16856.83 | 53238.95 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15607.76 | 52439.20 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15691.22 | 51296.46 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15641.59 | 49879.80 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14234.37 | 48611.57 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15334.99 | 47965.39 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14565.26 | 48617.36 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14827.62 | 49876.78 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15398.91 | 51265.60 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15249.86 | 52466.64 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 15440.01 | ||||
Minimum of Months | 0.00 | 0.00 | 14234.37 | 47965.39 | ||
Maximum of Months | 0.00 | 0.00 | 16856.83 | 53334.20 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4.03 | 6097.26 | 21-MAR-14:50 | 369.25 | 109320.29 | 21-MAR-05:50 |
April | 21320.01 | 893663.64 | 28-APR-15:00 | 662.28 | 113561.61 | 08-APR-05:55 |
May | 27345.54 | 1984519.55 | 22-MAY-14:10 | 333.70 | 68004.06 | 11-MAY-19:10 |
June | 98206.61 | 2197719.10 | 13-JUN-16:00 | 489.42 | 55053.62 | 08-JUN-05:15 |
July | 148018.73 | 2001563.58 | 22-JUL-10:20 | 662.31 | 59229.30 | 31-JUL-08:30 |
August | 182144.56 | 2033175.14 | 14-AUG-14:30 | 471.41 | 55510.16 | 31-AUG-18:30 |
September | 101124.08 | 1957785.53 | 12-SEP-15:40 | 803.46 | 84377.23 | 20-SEP-06:00 |
October | 4388.87 | 314793.06 | 07-OCT-15:10 | 380.24 | 87343.03 | 12-OCT-06:00 |
November | 15.90 | 55313.91 | 24-NOV-12:00 | 411.53 | 98963.66 | 16-NOV-06:50 |
December | 4.94 | 7404.90 | 08-DEC-06:50 | 474.39 | 110096.00 | 18-DEC-06:30 |
Annual Sum or Average | 48874.26 | 423.10 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 182144.56 | 2197719.10 | 803.46 | 113561.61 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143094E+11 | 0.79 | 9478.63 | 01-JAN-00:25 | 1.41 |
February | 0.125597E+11 | 0.77 | 9478.63 | 01-FEB-05:12 | 1.40 |
March | 0.148454E+11 | 0.82 | 9478.63 | 01-MAR-05:12 | 1.40 |
April | 0.136777E+11 | 0.78 | 9478.63 | 01-APR-04:12 | 1.41 |
May | 0.144864E+11 | 0.80 | 9478.63 | 01-MAY-00:50 | 1.40 |
June | 0.142407E+11 | 0.81 | 9478.63 | 01-JUN-04:12 | 1.40 |
July | 0.139317E+11 | 0.77 | 9478.63 | 01-JUL-04:12 | 1.40 |
August | 0.154004E+11 | 0.85 | 9478.63 | 01-AUG-04:12 | 1.40 |
September | 0.138968E+11 | 0.79 | 9478.63 | 01-SEP-04:12 | 1.40 |
October | 0.141980E+11 | 0.78 | 9478.63 | 02-OCT-04:12 | 1.40 |
November | 0.137289E+11 | 0.78 | 9478.63 | 01-NOV-04:12 | 1.40 |
December | 0.137065E+11 | 0.76 | 9478.63 | 01-DEC-05:11 | 1.40 |
Annual Sum or Average | 0.168982E+12 | 0.79 | |||
Minimum of Months | 0.125597E+11 | 0.76 | 9478.63 | 1.40 | |
Maximum of Months | 0.154004E+11 | 0.85 | 9478.63 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.409346E+10 | 0.31 | 13554.32 | 10-JAN-06:01 | 1.38 |
February | 0.431308E+10 | 0.34 | 11184.66 | 13-FEB-06:01 | 1.23 |
March | 0.551458E+10 | 0.37 | 10183.17 | 18-MAR-05:02 | 1.15 |
April | 0.965910E+10 | 0.51 | 19305.76 | 28-APR-14:40 | 1.72 |
May | 0.754058E+10 | 0.44 | 14367.47 | 22-MAY-14:50 | 1.42 |
June | 0.962733E+10 | 0.52 | 16992.65 | 26-JUN-15:20 | 1.58 |
July | 0.112564E+11 | 0.55 | 17363.48 | 10-JUL-13:30 | 1.60 |
August | 0.132747E+11 | 0.62 | 20428.16 | 14-AUG-14:40 | 1.78 |
September | 0.834217E+10 | 0.47 | 15904.41 | 11-SEP-14:40 | 1.51 |
October | 0.615803E+10 | 0.38 | 13315.17 | 03-OCT-14:40 | 1.36 |
November | 0.507666E+10 | 0.35 | 10720.32 | 06-NOV-05:11 | 1.19 |
December | 0.473755E+10 | 0.33 | 12763.94 | 30-DEC-06:01 | 1.33 |
Annual Sum or Average | 0.895937E+11 | 0.43 | |||
Minimum of Months | 0.409346E+10 | 0.31 | 10183.17 | 1.15 | |
Maximum of Months | 0.132747E+11 | 0.62 | 20428.16 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321806E+11 | 0.31 | 97013.31 | 26-JAN-06:02 | 1.21 |
February | 0.311329E+11 | 0.32 | 55246.64 | 17-FEB-15:30 | 0.87 |
March | 0.355148E+11 | 0.33 | 120343.79 | 31-MAR-05:02 | 1.38 |
April | 0.579123E+11 | 0.40 | 154811.32 | 28-APR-14:50 | 1.61 |
May | 0.595080E+11 | 0.41 | 125812.85 | 23-MAY-15:20 | 1.41 |
June | 0.717422E+11 | 0.47 | 153418.92 | 13-JUN-15:30 | 1.59 |
July | 0.768427E+11 | 0.47 | 153732.10 | 21-JUL-15:30 | 1.60 |
August | 0.858606E+11 | 0.51 | 147894.73 | 14-AUG-15:20 | 1.56 |
September | 0.685423E+11 | 0.45 | 155339.84 | 12-SEP-15:10 | 1.61 |
October | 0.429782E+11 | 0.34 | 101583.81 | 03-OCT-15:00 | 1.24 |
November | 0.321916E+11 | 0.31 | 97013.31 | 01-NOV-05:02 | 1.21 |
December | 0.304073E+11 | 0.30 | 41147.34 | 04-DEC-05:11 | 0.74 |
Annual Sum or Average | 0.624813E+12 | 0.38 | |||
Minimum of Months | 0.304073E+11 | 0.30 | 41147.34 | 0.74 | |
Maximum of Months | 0.858606E+11 | 0.51 | 155339.84 | 1.61 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.315809E+10 | 0.30 | 4929.81 | 02-JAN-04:11 | 0.75 |
February | 0.281165E+10 | 0.30 | 4929.81 | 06-FEB-05:11 | 0.75 |
March | 0.311026E+10 | 0.30 | 4929.81 | 06-MAR-05:11 | 0.75 |
April | 0.435070E+10 | 0.33 | 14498.96 | 28-APR-15:20 | 1.42 |
May | 0.474142E+10 | 0.35 | 13059.68 | 23-MAY-15:20 | 1.32 |
June | 0.600056E+10 | 0.39 | 16713.96 | 13-JUN-15:30 | 1.54 |
July | 0.658795E+10 | 0.39 | 15787.31 | 21-JUL-15:30 | 1.49 |
August | 0.696037E+10 | 0.42 | 14572.74 | 14-AUG-15:40 | 1.42 |
September | 0.515803E+10 | 0.36 | 14158.15 | 12-SEP-15:10 | 1.39 |
October | 0.325489E+10 | 0.29 | 6667.44 | 03-OCT-15:00 | 0.89 |
November | 0.290002E+10 | 0.29 | 4929.81 | 13-NOV-05:11 | 0.75 |
December | 0.324535E+10 | 0.31 | 4929.81 | 04-DEC-05:21 | 0.75 |
Annual Sum or Average | 0.522793E+11 | 0.34 | |||
Minimum of Months | 0.281165E+10 | 0.29 | 4929.81 | 0.75 | |
Maximum of Months | 0.696037E+10 | 0.42 | 16713.96 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.957262E+11 | 1.37 | 35740.06 | 01-JAN-00:03 | 1.37 |
February | 0.864624E+11 | 1.37 | 35740.06 | 01-FEB-00:10 | 1.37 |
March | 0.957262E+11 | 1.37 | 35740.06 | 01-MAR-00:10 | 1.37 |
April | 0.926382E+11 | 1.37 | 35740.06 | 01-APR-00:10 | 1.37 |
May | 0.957262E+11 | 1.37 | 35740.06 | 01-MAY-00:03 | 1.37 |
June | 0.926382E+11 | 1.37 | 35740.06 | 01-JUN-00:10 | 1.37 |
July | 0.957262E+11 | 1.36 | 35740.06 | 01-JUL-00:10 | 1.37 |
August | 0.957262E+11 | 1.36 | 35740.06 | 01-AUG-00:10 | 1.37 |
September | 0.926382E+11 | 1.37 | 35740.06 | 01-SEP-00:10 | 1.37 |
October | 0.957262E+11 | 1.37 | 35740.06 | 01-OCT-00:10 | 1.37 |
November | 0.926382E+11 | 1.37 | 35740.06 | 01-NOV-00:10 | 1.37 |
December | 0.957262E+11 | 1.37 | 35740.06 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112710E+13 | 1.37 | |||
Minimum of Months | 0.864624E+11 | 1.36 | 35740.06 | 1.37 | |
Maximum of Months | 0.957262E+11 | 1.37 | 35740.06 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153569E+10 | 0.93 | 573.36 | 01-JAN-00:03 | 0.92 |
February | 0.138708E+10 | 0.93 | 573.36 | 01-FEB-00:10 | 0.93 |
March | 0.153569E+10 | 0.93 | 573.36 | 01-MAR-00:10 | 0.92 |
April | 0.148616E+10 | 0.93 | 573.36 | 01-APR-00:10 | 0.93 |
May | 0.153569E+10 | 0.92 | 573.36 | 01-MAY-00:03 | 0.92 |
June | 0.148616E+10 | 0.92 | 573.36 | 01-JUN-00:10 | 0.92 |
July | 0.153569E+10 | 0.92 | 573.36 | 01-JUL-00:10 | 0.92 |
August | 0.153569E+10 | 0.92 | 573.36 | 01-AUG-00:10 | 0.92 |
September | 0.148616E+10 | 0.92 | 573.36 | 01-SEP-00:10 | 0.92 |
October | 0.153569E+10 | 0.92 | 573.36 | 01-OCT-00:10 | 0.93 |
November | 0.148616E+10 | 0.92 | 573.36 | 01-NOV-00:10 | 0.93 |
December | 0.153569E+10 | 0.93 | 573.36 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.180816E+11 | 0.92 | |||
Minimum of Months | 0.138708E+10 | 0.92 | 573.36 | 0.92 | |
Maximum of Months | 0.153569E+10 | 0.93 | 573.36 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147531E+11 | 0.93 | 5508.18 | 01-JAN-00:03 | 0.92 |
February | 0.133254E+11 | 0.93 | 5508.18 | 01-FEB-00:10 | 0.93 |
March | 0.147531E+11 | 0.93 | 5508.18 | 01-MAR-00:10 | 0.92 |
April | 0.142772E+11 | 0.93 | 5508.18 | 01-APR-00:10 | 0.93 |
May | 0.147531E+11 | 0.92 | 5508.18 | 01-MAY-00:03 | 0.92 |
June | 0.142772E+11 | 0.92 | 5508.18 | 01-JUN-00:10 | 0.92 |
July | 0.147531E+11 | 0.92 | 5508.18 | 01-JUL-00:10 | 0.92 |
August | 0.147531E+11 | 0.92 | 5508.18 | 01-AUG-00:10 | 0.92 |
September | 0.142772E+11 | 0.92 | 5508.18 | 01-SEP-00:10 | 0.92 |
October | 0.147531E+11 | 0.92 | 5508.18 | 01-OCT-00:20 | 0.93 |
November | 0.142772E+11 | 0.92 | 5508.18 | 01-NOV-00:10 | 0.93 |
December | 0.147531E+11 | 0.93 | 5508.18 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173706E+12 | 0.92 | |||
Minimum of Months | 0.133254E+11 | 0.92 | 5508.18 | 0.92 | |
Maximum of Months | 0.147531E+11 | 0.93 | 5508.18 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149461E+10 | 0.93 | 558.02 | 01-JAN-00:03 | 0.92 |
February | 0.134997E+10 | 0.93 | 558.02 | 01-FEB-00:10 | 0.93 |
March | 0.149461E+10 | 0.93 | 558.02 | 01-MAR-00:10 | 0.92 |
April | 0.144639E+10 | 0.93 | 558.02 | 01-APR-00:10 | 0.93 |
May | 0.149461E+10 | 0.92 | 558.02 | 01-MAY-00:03 | 0.92 |
June | 0.144639E+10 | 0.92 | 558.02 | 01-JUN-00:10 | 0.92 |
July | 0.149461E+10 | 0.92 | 558.02 | 01-JUL-00:10 | 0.92 |
August | 0.149461E+10 | 0.92 | 558.02 | 01-AUG-00:10 | 0.92 |
September | 0.144639E+10 | 0.92 | 558.02 | 01-SEP-00:10 | 0.92 |
October | 0.149461E+10 | 0.92 | 558.02 | 01-OCT-00:10 | 0.93 |
November | 0.144639E+10 | 0.92 | 558.02 | 01-NOV-00:20 | 0.93 |
December | 0.149461E+10 | 0.93 | 558.02 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.175978E+11 | 0.92 | |||
Minimum of Months | 0.134997E+10 | 0.92 | 558.02 | 0.92 | |
Maximum of Months | 0.149461E+10 | 0.93 | 558.02 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 18127653.95 | 16314888.56 | 961.29 | 02-JAN-06:02 | 865.16 | 865.16 | 44.37 | 8.64 |
February | 8951375.11 | 8056237.60 | 335.10 | 17-FEB-06:01 | 301.59 | 301.59 | 37.09 | 5.42 |
March | 5023410.98 | 4521069.89 | 320.79 | 27-MAR-05:02 | 288.71 | 288.71 | 34.74 | 5.32 |
April | 441059.16 | 396953.24 | 15.47 | 01-APR-05:03 | 13.93 | 13.93 | 26.11 | 1.07 |
May | 191819.90 | 172637.91 | 222.37 | 05-MAY-05:03 | 200.14 | 200.14 | 33.83 | 4.48 |
June | 3790.02 | 3411.02 | 1.85 | 08-JUN-05:03 | 1.66 | 1.66 | 22.34 | 0.23 |
July | 1231.95 | 1108.75 | 0.77 | 31-JUL-05:03 | 0.69 | 0.69 | 21.86 | 0.11 |
August | 500.38 | 450.34 | 0.07 | 23-AUG-05:20 | 0.06 | 0.06 | 21.83 | 0.01 |
September | 30447.07 | 27402.36 | 2.52 | 21-SEP-06:10 | 2.27 | 2.27 | 22.67 | 0.30 |
October | 1192305.34 | 1073074.80 | 228.98 | 28-OCT-05:02 | 206.08 | 206.08 | 30.07 | 4.55 |
November | 6839377.54 | 6155439.78 | 331.48 | 27-NOV-06:03 | 298.33 | 298.33 | 41.59 | 5.39 |
December | 18794196.49 | 16914776.85 | 339.76 | 30-DEC-06:01 | 305.78 | 305.78 | 41.06 | 5.45 |
Annual Sum or Average | 59597167.88 | 53637451.09 | ||||||
Minimum of Months | 500.38 | 450.34 | 0.07 | 0.06 | 0.06 | 21.83 | 0.01 | |
Maximum of Months | 18794196.49 | 16914776.85 | 961.29 | 865.16 | 865.16 | 44.37 | 8.64 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12.31 | 11.08 | 0.03 | 02-JAN-04:30 | 0.03 | 0.03 | 6.70 | 0.01 |
February | 4.82 | 4.34 | 0.00 | 17-FEB-06:01 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 725.24 | 652.71 | 2.56 | 18-MAR-05:03 | 2.31 | 2.31 | 6.70 | 0.62 |
April | 33859920.45 | 30473928.41 | 2878.12 | 28-APR-14:30 | 2590.31 | 2590.31 | 7.92 | 34.84 |
May | 55270908.72 | 49743817.85 | 4495.81 | 22-MAY-14:00 | 4046.23 | 4046.23 | 11.15 | 41.82 |
June | 0.201290E+09 | 0.181161E+09 | 5766.15 | 12-JUN-14:20 | 5189.53 | 5189.53 | 10.93 | 46.23 |
July | 0.304568E+09 | 0.274111E+09 | 3585.78 | 22-JUL-14:00 | 3227.20 | 3227.20 | 10.52 | 38.14 |
August | 0.328457E+09 | 0.295611E+09 | 8166.67 | 28-AUG-13:50 | 7350.01 | 7350.01 | 10.27 | 53.08 |
September | 0.223975E+09 | 0.201578E+09 | 5424.57 | 12-SEP-15:30 | 4882.11 | 4882.11 | 12.01 | 45.11 |
October | 2259087.70 | 2033178.93 | 68.62 | 06-OCT-15:20 | 61.75 | 61.75 | 6.70 | 5.92 |
November | 24201.88 | 21781.69 | 15.08 | 24-NOV-12:00 | 13.57 | 13.57 | 6.70 | 2.36 |
December | 3.80 | 3.42 | 0.00 | 16-DEC-05:15 | 0.00 | 0.00 | 6.70 | 0.00 |
Annual Sum or Average | 0.114970E+10 | 0.103473E+10 | ||||||
Minimum of Months | 3.80 | 3.42 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.328457E+09 | 0.295611E+09 | 8166.67 | 7350.01 | 7350.01 | 12.01 | 53.08 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 94729733.91 | 85256760.52 | 3131.56 | 18-MAR-04:12 | 2818.41 | 2818.41 | 6.71 | 27.70 |
April | 0.792813E+09 | 0.713532E+09 | 3131.56 | 01-APR-12:10 | 2818.41 | 2818.41 | 6.72 | 27.70 |
May | 0.840422E+09 | 0.756379E+09 | 3131.56 | 03-MAY-05:03 | 2818.41 | 2818.41 | 6.73 | 27.70 |
June | 0.206055E+10 | 0.185449E+10 | 3131.56 | 01-JUN-05:03 | 2818.41 | 2818.41 | 6.73 | 27.70 |
July | 0.364426E+10 | 0.327983E+10 | 3131.56 | 01-JUL-04:12 | 2818.41 | 2818.41 | 6.96 | 27.70 |
August | 0.445303E+10 | 0.400772E+10 | 3131.56 | 01-AUG-04:12 | 2818.41 | 2818.41 | 7.02 | 27.70 |
September | 0.267019E+10 | 0.240317E+10 | 3131.56 | 01-SEP-04:12 | 2818.41 | 2818.41 | 7.00 | 27.70 |
October | 0.376758E+09 | 0.339082E+09 | 3131.56 | 01-OCT-11:52 | 2818.41 | 2818.41 | 6.76 | 27.70 |
November | 0.108732E+09 | 97859058.53 | 3131.56 | 06-NOV-16:00 | 2818.41 | 2818.41 | 6.72 | 27.70 |
December | 0.153524E+09 | 0.138172E+09 | 3131.56 | 04-DEC-04:09 | 2818.41 | 2818.41 | 6.72 | 27.70 |
Annual Sum or Average | 0.151950E+11 | 0.136755E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.445303E+10 | 0.400772E+10 | 3131.56 | 2818.41 | 2818.41 | 7.02 | 27.70 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.70 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 24426179.32 | 21983561.39 | 3131.56 | 22-MAY-13:50 | 2818.41 | 2818.41 | 14.96 | 13.85 |
June | 0.170983E+09 | 0.153885E+09 | 3131.56 | 12-JUN-12:50 | 2818.41 | 2818.41 | 16.07 | 13.85 |
July | 0.192356E+09 | 0.173121E+09 | 3131.56 | 10-JUL-09:00 | 2818.41 | 2818.41 | 15.50 | 13.85 |
August | 0.127768E+09 | 0.114991E+09 | 3131.56 | 14-AUG-10:20 | 2818.41 | 2818.41 | 15.49 | 13.85 |
September | 0.116494E+09 | 0.104845E+09 | 3131.56 | 11-SEP-14:00 | 2818.41 | 2818.41 | 15.35 | 13.85 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.632027E+09 | 0.568825E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.192356E+09 | 0.173121E+09 | 3131.56 | 2818.41 | 2818.41 | 16.07 | 13.85 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-JAN-00:03 | 3037.13 | 3037.13 | 18.52 | 14.09 |
February | 0.816380E+10 | 0.734742E+10 | 3374.59 | 01-FEB-00:10 | 3037.13 | 3037.13 | 19.24 | 14.09 |
March | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-MAR-00:10 | 3037.13 | 3037.13 | 19.88 | 14.09 |
April | 0.874693E+10 | 0.787224E+10 | 3374.59 | 01-APR-00:10 | 3037.13 | 3037.13 | 20.62 | 14.09 |
May | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-MAY-00:03 | 3037.13 | 3037.13 | 19.09 | 14.09 |
June | 0.874693E+10 | 0.787224E+10 | 3374.59 | 01-JUN-00:10 | 3037.13 | 3037.13 | 19.55 | 14.09 |
July | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-JUL-00:10 | 3037.13 | 3037.13 | 19.97 | 14.09 |
August | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-AUG-00:10 | 3037.13 | 3037.13 | 20.59 | 14.09 |
September | 0.874693E+10 | 0.787224E+10 | 3374.59 | 01-SEP-00:10 | 3037.13 | 3037.13 | 18.99 | 14.09 |
October | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-OCT-00:10 | 3037.13 | 3037.13 | 19.49 | 14.09 |
November | 0.874693E+10 | 0.787224E+10 | 3374.59 | 01-NOV-00:10 | 3037.13 | 3037.13 | 20.03 | 14.09 |
December | 0.903850E+10 | 0.813465E+10 | 3374.59 | 01-DEC-00:10 | 3037.13 | 3037.13 | 20.43 | 14.09 |
Annual Sum or Average | 0.106421E+12 | 0.957789E+11 | ||||||
Minimum of Months | 0.816380E+10 | 0.734742E+10 | 3374.59 | 3037.13 | 3037.13 | 18.52 | 14.09 | |
Maximum of Months | 0.903850E+10 | 0.813465E+10 | 3374.59 | 3037.13 | 3037.13 | 20.62 | 14.09 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.49 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 55.39 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 55.54 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 55.90 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.25 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 55.60 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 55.57 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.76 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.51 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 55.72 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 55.59 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.60 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.39 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.76 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 21.10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 21.10 | 0.00 |
March | 0.370571E+09 | 0.333514E+09 | 12251.92 | 21-MAR-14:50 | 11026.73 | 11026.73 | 21.13 | 49.65 |
April | 0.310401E+10 | 0.279361E+10 | 12290.27 | 28-APR-15:00 | 11061.25 | 11061.25 | 25.41 | 49.65 |
May | 0.337195E+10 | 0.303475E+10 | 24590.41 | 22-MAY-14:10 | 22131.36 | 22131.36 | 25.88 | 99.30 |
June | 0.871195E+10 | 0.784076E+10 | 24601.00 | 13-JUN-16:00 | 22140.90 | 22140.90 | 26.40 | 99.30 |
July | 0.150196E+11 | 0.135176E+11 | 24591.25 | 22-JUL-10:20 | 22132.13 | 22132.13 | 25.92 | 99.30 |
August | 0.179055E+11 | 0.161150E+11 | 24592.82 | 14-AUG-14:30 | 22133.54 | 22133.54 | 26.00 | 99.30 |
September | 0.108400E+11 | 0.975600E+10 | 24589.08 | 12-SEP-15:40 | 22130.17 | 22130.17 | 25.82 | 99.30 |
October | 0.147445E+10 | 0.132701E+10 | 12265.03 | 07-OCT-15:10 | 11038.53 | 11038.53 | 22.62 | 49.65 |
November | 0.425352E+09 | 0.382817E+09 | 12254.01 | 24-NOV-12:00 | 11028.61 | 11028.61 | 21.37 | 49.65 |
December | 0.600581E+09 | 0.540523E+09 | 12251.98 | 08-DEC-06:50 | 11026.78 | 11026.78 | 21.14 | 49.65 |
Annual Sum or Average | 0.618240E+11 | 0.556416E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 | |
Maximum of Months | 0.179055E+11 | 0.161150E+11 | 24601.00 | 22140.90 | 22140.90 | 26.40 | 99.30 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 32.56 | 32.56 | 82078.13 | 1358254.01 | 02-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.05 | 23.05 | 58355.17 | 1151549.10 | 27-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.68 | 25.68 | 36054.73 | 1051173.15 | 27-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.93 | 23.93 | 4590.79 | 250343.88 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 23.13 | 23.13 | 1867.26 | 902749.92 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.85 | 21.85 | 56.21 | 58444.88 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.10 | 22.10 | 18.30 | 27727.25 | 31-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21.92 | 21.92 | 7.56 | 2874.12 | 23-AUG-05:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.61 | 21.61 | 424.76 | 74651.56 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.37 | 21.37 | 10771.51 | 988057.00 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.64 | 21.64 | 41583.85 | 1218267.58 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.33 | 26.33 | 91603.13 | 1138643.64 | 11-DEC-05:11 |
Annual Sum or Average | 0.00 | 27200.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.37 | 21.37 | 7.56 | 2874.12 | ||
Maximum of Months | 0.00 | 0.00 | 32.56 | 32.56 | 91603.13 | 1358254.01 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.30 | 31-JAN-07:00 | 6.70 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.01 | 0.56 | 28-FEB-16:00 | 6.70 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31.74 | 2853.51 | 20-MAR-05:03 | 6.72 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18502.09 | 784779.56 | 28-APR-15:00 | 13.47 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23052.42 | 1305261.71 | 22-MAY-14:20 | 12.33 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 77752.10 | 1450607.29 | 13-JUN-16:00 | 12.95 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121770.91 | 1597585.22 | 22-JUL-16:02 | 13.59 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 151816.87 | 1348072.63 | 28-AUG-14:10 | 12.51 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 84872.39 | 1161528.78 | 12-SEP-15:40 | 11.70 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4059.00 | 266194.15 | 07-OCT-15:00 | 8.99 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 74.20 | 48722.73 | 24-NOV-12:00 | 7.12 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 51.60 | 2820.01 | 16-DEC-05:15 | 6.72 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 40439.13 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.30 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 151816.87 | 1597585.22 | 13.59 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.14 | 02-JAN-04:30 | 6.70 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.71 | 6.71 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.02 | 288.03 | 18-MAR-05:03 | 6.81 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18474.32 | 1129266.07 | 30-APR-15:51 | 21.00 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23079.71 | 1468219.33 | 22-MAY-14:10 | 17.96 | 10.32 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 77835.05 | 1778768.43 | 12-JUN-14:20 | 15.90 | 10.77 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 121486.59 | 1376680.46 | 21-JUL-15:30 | 16.35 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 151174.34 | 1672175.19 | 28-AUG-13:50 | 14.23 | 10.29 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 85157.45 | 1895243.62 | 12-SEP-15:30 | 16.74 | 12.33 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 3934.18 | 267869.61 | 07-OCT-15:00 | 18.26 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36.45 | 49532.89 | 24-NOV-12:00 | 11.70 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.01 | 2.22 | 16-DEC-05:15 | 11.85 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 40369.91 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 151174.34 | 1895243.62 | 21.00 | 12.33 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 18053.64 | 34150.35 | 19-JAN-16:30 | 19.03 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 48878.19 | 67702.30 | 17-FEB-17:00 | 19.72 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80126.56 | 112083.30 | 31-MAR-23:40 | 20.62 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 151902.38 | 1113158.30 | 30-APR-18:10 | 40.66 | 29.05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 32860.46 | 435701.41 | 22-MAY-15:00 | 27.18 | 24.95 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 91855.28 | 961396.98 | 13-JUN-17:00 | 37.67 | 30.22 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 200581.19 | 1345343.83 | 22-JUL-18:00 | 45.20 | 34.63 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 395991.67 | 1322833.80 | 14-AUG-17:10 | 44.76 | 32.41 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43595.43 | 344335.08 | 13-SEP-16:00 | 25.34 | 23.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 52109.44 | 130944.06 | 07-OCT-15:00 | 21.01 | 19.59 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76756.14 | 114809.14 | 24-NOV-12:00 | 20.68 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 102613.28 | 147420.96 | 23-DEC-11:00 | 21.34 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 108614.49 | 0.00 | ||||||
Minimum of Months | 18053.64 | 34150.35 | 19.03 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 395991.67 | 1345343.83 | 45.20 | 34.63 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.33 | 57.33 | 15864.80 | 53217.99 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.08 | 56.08 | 16048.09 | 53334.20 | 17-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.08 | 56.08 | 16856.83 | 53238.95 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.58 | 56.58 | 15607.76 | 52439.20 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.13 | 57.13 | 15691.22 | 51296.46 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.23 | 56.23 | 15641.59 | 49879.80 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.24 | 56.24 | 14234.37 | 48611.57 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.10 | 57.10 | 15334.99 | 47965.39 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.15 | 57.15 | 14565.26 | 48617.36 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.84 | 56.84 | 14827.62 | 49876.78 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.15 | 56.15 | 15398.91 | 51265.60 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.14 | 57.14 | 15249.86 | 52466.64 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 15440.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.08 | 56.08 | 14234.37 | 47965.39 | ||
Maximum of Months | 0.00 | 0.00 | 57.33 | 57.33 | 16856.83 | 53334.20 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 21.10 | 21.10 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 21.10 | 21.10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4.03 | 6097.26 | 21-MAR-14:50 | 21.13 | 20.41 | 369.25 | 109320.29 | 21-MAR-05:50 |
April | 21320.01 | 893663.64 | 28-APR-15:00 | 25.41 | 21.10 | 662.28 | 113561.61 | 08-APR-05:55 |
May | 27345.54 | 1984519.55 | 22-MAY-14:10 | 25.88 | 21.40 | 333.70 | 68004.06 | 11-MAY-19:10 |
June | 98206.61 | 2197719.10 | 13-JUN-16:00 | 26.40 | 22.37 | 489.42 | 55053.62 | 08-JUN-05:15 |
July | 148018.73 | 2001563.58 | 22-JUL-10:20 | 25.92 | 21.96 | 662.31 | 59229.30 | 31-JUL-08:30 |
August | 182144.56 | 2033175.14 | 14-AUG-14:30 | 26.00 | 21.64 | 471.41 | 55510.16 | 31-AUG-18:30 |
September | 101124.08 | 1957785.53 | 12-SEP-15:40 | 25.82 | 21.37 | 803.46 | 84377.23 | 20-SEP-06:00 |
October | 4388.87 | 314793.06 | 07-OCT-15:10 | 22.62 | 21.10 | 380.24 | 87343.03 | 12-OCT-06:00 |
November | 15.90 | 55313.91 | 24-NOV-12:00 | 21.37 | 20.90 | 411.53 | 98963.66 | 16-NOV-06:50 |
December | 4.94 | 7404.90 | 08-DEC-06:50 | 21.14 | 20.26 | 474.39 | 110096.00 | 18-DEC-06:30 |
Annual Sum or Average | 48874.26 | 423.10 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.10 | 20.26 | 0.00 | 0.00 | ||
Maximum of Months | 182144.56 | 2197719.10 | 26.40 | 22.37 | 803.46 | 113561.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.691183E+10 | 0.00 | 0.00 | 0.409346E+10 | 0.00 | 0.00 |
February | 0.389802E+10 | 0.00 | 0.00 | 0.431308E+10 | 0.00 | 0.00 |
March | 0.182186E+10 | 0.00 | 0.00 | 0.551458E+10 | 0.00 | 0.00 |
April | 0.132298E+09 | 0.00 | 0.463960E+10 | 0.965910E+10 | 0.00 | 0.00 |
May | 43242721.26 | 0.00 | 0.561799E+10 | 0.754058E+10 | 0.00 | 0.00 |
June | 2144.86 | 0.00 | 0.182839E+11 | 0.962733E+10 | 0.00 | 0.00 |
July | 3265.85 | 0.00 | 0.311273E+11 | 0.112564E+11 | 0.00 | 0.00 |
August | 2543.98 | 0.00 | 0.412213E+11 | 0.132747E+11 | 0.00 | 0.00 |
September | 4882626.12 | 0.00 | 0.192813E+11 | 0.834217E+10 | 0.00 | 0.00 |
October | 0.208748E+09 | 0.00 | 0.103818E+10 | 0.615803E+10 | 0.00 | 0.00 |
November | 0.164683E+10 | 0.00 | 12987169.27 | 0.507666E+10 | 0.00 | 0.00 |
December | 0.461801E+10 | 0.00 | 0.00 | 0.473755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.192857E+11 | 0.00 | 0.121223E+12 | 0.895937E+11 | 0.00 | 0.00 |
Minimum of Months | 2144.86 | 0.00 | 0.00 | 0.409346E+10 | 0.00 | 0.00 |
Maximum of Months | 0.691183E+10 | 0.00 | 0.412213E+11 | 0.132747E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.179284E+12 | 0.00 | 47151.58 | 0.321806E+11 | 0.00 | 0.00 |
February | 0.113759E+12 | 0.00 | 40396.28 | 0.311329E+11 | 0.00 | 0.00 |
March | 0.768271E+11 | 0.00 | 78365.53 | 0.355148E+11 | 0.00 | 0.00 |
April | 0.845576E+10 | 0.00 | 0.384183E+11 | 0.579123E+11 | 0.00 | 0.00 |
May | 0.305439E+10 | 0.00 | 0.480701E+11 | 0.595080E+11 | 0.00 | 0.00 |
June | 25424882.86 | 0.00 | 0.151882E+12 | 0.717422E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.246517E+12 | 0.768427E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.310642E+12 | 0.858606E+11 | 0.00 | 0.00 |
September | 0.385135E+09 | 0.00 | 0.169679E+12 | 0.685423E+11 | 0.00 | 0.00 |
October | 0.206102E+11 | 0.00 | 0.869778E+10 | 0.429782E+11 | 0.00 | 0.00 |
November | 0.856407E+11 | 0.00 | 50104132.06 | 0.321916E+11 | 0.00 | 0.00 |
December | 0.202580E+12 | 0.00 | 39711.52 | 0.304073E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.690621E+12 | 0.00 | 0.973956E+12 | 0.624813E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 39711.52 | 0.304073E+11 | 0.00 | 0.00 |
Maximum of Months | 0.202580E+12 | 0.00 | 0.310642E+12 | 0.858606E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.348256E+11 | 0.00 | 77901.77 | 0.315809E+10 | 0.00 | 0.00 |
February | 0.242390E+11 | 0.00 | 0.00 | 0.281165E+10 | 0.00 | 0.00 |
March | 0.184317E+11 | 0.00 | 0.00 | 0.311026E+10 | 0.00 | 0.00 |
April | 0.337731E+10 | 0.00 | 0.370326E+10 | 0.435070E+10 | 0.00 | 0.00 |
May | 0.193525E+10 | 0.00 | 0.484941E+10 | 0.474142E+10 | 0.00 | 0.00 |
June | 0.119922E+09 | 0.00 | 0.157259E+11 | 0.600056E+10 | 0.00 | 0.00 |
July | 50032010.95 | 0.00 | 0.251205E+11 | 0.658795E+10 | 0.00 | 0.00 |
August | 21742685.84 | 0.00 | 0.297960E+11 | 0.696037E+10 | 0.00 | 0.00 |
September | 0.717594E+09 | 0.00 | 0.152895E+11 | 0.515803E+10 | 0.00 | 0.00 |
October | 0.817966E+10 | 0.00 | 0.623258E+09 | 0.325489E+10 | 0.00 | 0.00 |
November | 0.210353E+11 | 0.00 | 4559993.44 | 0.290002E+10 | 0.00 | 0.00 |
December | 0.394026E+11 | 0.00 | 0.00 | 0.324535E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.152336E+12 | 0.00 | 0.951125E+11 | 0.522793E+11 | 0.00 | 0.00 |
Minimum of Months | 21742685.84 | 0.00 | 0.00 | 0.281165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.394026E+11 | 0.00 | 0.297960E+11 | 0.696037E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143094E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.125597E+11 | 0.00 | 0.00 |
March | 231.53 | 0.00 | 1667287.05 | 0.148454E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.751880E+09 | 0.136777E+11 | 0.00 | 0.00 |
May | 274.68 | 0.00 | 0.227142E+10 | 0.144864E+11 | 0.00 | 0.00 |
June | 104.56 | 0.00 | 0.824059E+10 | 0.142407E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.135545E+11 | 0.139317E+11 | 0.00 | 0.00 |
August | 180.36 | 0.00 | 0.178470E+11 | 0.154004E+11 | 0.00 | 0.00 |
September | 108.55 | 0.00 | 0.851000E+10 | 0.138968E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.162845E+09 | 0.141980E+11 | 0.00 | 0.00 |
November | 148.25 | 0.00 | 21877835.12 | 0.137289E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.137065E+11 | 0.00 | 0.00 |
Annual Sum or Average | 1047.93 | 0.00 | 0.513617E+11 | 0.168982E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125597E+11 | 0.00 | 0.00 |
Maximum of Months | 274.68 | 0.00 | 0.178470E+11 | 0.154004E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.715631E+10 | 0.174997E+12 | 0.00 | 28.20 |
February | 0.00 | 0.00 | 0.100050E+11 | 0.206911E+12 | 0.00 | 43.35 |
March | 0.00 | 0.00 | 0.167528E+11 | 0.297423E+12 | 0.00 | 72.90 |
April | 0.00 | 0.00 | 0.814052E+11 | 0.329598E+12 | 0.00 | 80.49 |
May | 0.00 | 0.00 | 0.541231E+10 | 0.138562E+12 | 0.00 | 14.77 |
June | 0.00 | 0.00 | 0.314940E+11 | 0.115205E+12 | 0.00 | 4.88 |
July | 0.00 | 0.00 | 0.162136E+12 | 0.144375E+12 | 0.00 | 3.75 |
August | 0.00 | 0.00 | 0.508773E+12 | 0.221322E+12 | 0.00 | 5.46 |
September | 0.00 | 0.00 | 0.399281E+10 | 0.110092E+12 | 0.00 | 5.45 |
October | 0.00 | 0.00 | 0.650521E+10 | 0.158078E+12 | 0.00 | 21.94 |
November | 0.00 | 0.00 | 0.123555E+11 | 0.230092E+12 | 0.00 | 49.37 |
December | 0.00 | 0.00 | 0.217012E+11 | 0.342104E+12 | 0.00 | 89.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.867690E+12 | 0.246876E+13 | 0.00 | 419.60 |
Minimum of Months | 0.00 | 0.00 | 0.399281E+10 | 0.110092E+12 | 0.00 | 3.75 |
Maximum of Months | 0.00 | 0.00 | 0.508773E+12 | 0.342104E+12 | 0.00 | 89.03 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.527408E+10 | 0.261628E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108103E+11 | 0.348499E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185277E+11 | 0.499440E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245282E+11 | 0.594304E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.679363E+10 | 0.288453E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130576E+11 | 0.395569E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198971E+11 | 0.523579E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260237E+11 | 0.633497E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.678731E+10 | 0.282344E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126581E+11 | 0.393859E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178998E+11 | 0.479699E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242780E+11 | 0.596456E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186536E+12 | 0.529733E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.527408E+10 | 0.261628E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260237E+11 | 0.633497E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.269834E+11 | 0.205312E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.837208E+11 | 0.298245E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157157E+12 | 0.444288E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224705E+12 | 0.553302E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.553870E+11 | 0.258654E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118648E+12 | 0.368217E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184400E+12 | 0.491776E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243437E+12 | 0.597989E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.562699E+11 | 0.254740E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104199E+12 | 0.347618E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148342E+12 | 0.420826E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.202280E+12 | 0.522204E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160553E+13 | 0.476317E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.269834E+11 | 0.205312E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243437E+12 | 0.597989E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.907246E+09 | 0.169796E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.630086E+10 | 0.261289E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.138797E+11 | 0.414451E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.214940E+11 | 0.539730E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.462025E+10 | 0.243188E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.114066E+11 | 0.362311E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.180644E+11 | 0.487966E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239573E+11 | 0.594439E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.479470E+10 | 0.241114E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.865315E+10 | 0.317744E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127671E+11 | 0.386960E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.178977E+11 | 0.485139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144743E+12 | 0.450413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.907246E+09 | 0.169796E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239573E+11 | 0.594439E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.409346E+10 | 0.00 | 0.691183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431308E+10 | 0.00 | 0.389802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551458E+10 | 0.00 | 0.182186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.965910E+10 | 0.463960E+10 | 0.132298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754058E+10 | 0.561799E+10 | 43242721.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.962733E+10 | 0.182839E+11 | 2144.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112564E+11 | 0.311273E+11 | 3265.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132747E+11 | 0.412213E+11 | 2543.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.834217E+10 | 0.192813E+11 | 4882626.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615803E+10 | 0.103818E+10 | 0.208748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507666E+10 | 12987169.27 | 0.164683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473755E+10 | 0.00 | 0.461801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895937E+11 | 0.121223E+12 | 0.192857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.409346E+10 | 0.00 | 2144.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132747E+11 | 0.412213E+11 | 0.691183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321806E+11 | 47151.58 | 0.179284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311329E+11 | 40396.28 | 0.113759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355148E+11 | 78365.53 | 0.768271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579123E+11 | 0.384183E+11 | 0.845576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.595080E+11 | 0.480701E+11 | 0.305439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717422E+11 | 0.151882E+12 | 25424882.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768427E+11 | 0.246517E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.858606E+11 | 0.310642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.685423E+11 | 0.169679E+12 | 0.385135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.429782E+11 | 0.869778E+10 | 0.206102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321916E+11 | 50104132.06 | 0.856407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304073E+11 | 39711.52 | 0.202580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624813E+12 | 0.973956E+12 | 0.690621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304073E+11 | 39711.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.858606E+11 | 0.310642E+12 | 0.202580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.315809E+10 | 77901.77 | 0.348256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281165E+10 | 0.00 | 0.242390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311026E+10 | 0.00 | 0.184317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435070E+10 | 0.370326E+10 | 0.337731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.474142E+10 | 0.484941E+10 | 0.193525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600056E+10 | 0.157259E+11 | 0.119922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658795E+10 | 0.251205E+11 | 50032010.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.696037E+10 | 0.297960E+11 | 21742685.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.515803E+10 | 0.152895E+11 | 0.717594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325489E+10 | 0.623258E+09 | 0.817966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290002E+10 | 4559993.44 | 0.210353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324535E+10 | 0.00 | 0.394026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522793E+11 | 0.951125E+11 | 0.152336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281165E+10 | 0.00 | 21742685.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.696037E+10 | 0.297960E+11 | 0.394026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148454E+11 | 1667287.05 | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136777E+11 | 0.751880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144864E+11 | 0.227142E+10 | 274.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142407E+11 | 0.824059E+10 | 104.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139317E+11 | 0.135545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154004E+11 | 0.178470E+11 | 180.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138968E+11 | 0.851000E+10 | 108.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141980E+11 | 0.162845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137289E+11 | 21877835.12 | 148.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168982E+12 | 0.513617E+11 | 1047.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154004E+11 | 0.178470E+11 | 274.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.957262E+11 | 0.369871E+10 | 0.00 | 0.00 | 0.00 | 0.754738E+11 | 0.00 | 0.00 |
February | 0.864624E+11 | 0.607995E+10 | 0.00 | 0.00 | 0.00 | 0.116001E+12 | 0.00 | 0.00 |
March | 0.957262E+11 | 0.110236E+11 | 0.00 | 0.00 | 0.00 | 0.195090E+12 | 0.00 | 0.00 |
April | 0.926382E+11 | 0.608287E+11 | 0.00 | 0.00 | 0.00 | 0.215414E+12 | 0.00 | 0.00 |
May | 0.957262E+11 | 0.227118E+10 | 0.00 | 0.00 | 0.00 | 0.395164E+11 | 0.00 | 0.00 |
June | 0.926382E+11 | 0.220522E+11 | 0.00 | 0.00 | 0.00 | 0.130658E+11 | 0.00 | 0.00 |
July | 0.957262E+11 | 0.123580E+12 | 0.00 | 0.00 | 0.00 | 0.100483E+11 | 0.00 | 0.00 |
August | 0.957262E+11 | 0.397848E+12 | 0.00 | 0.00 | 0.00 | 0.146045E+11 | 0.00 | 0.00 |
September | 0.926382E+11 | 0.120084E+10 | 0.00 | 0.00 | 0.00 | 0.145958E+11 | 0.00 | 0.00 |
October | 0.957262E+11 | 0.313532E+10 | 0.00 | 0.00 | 0.00 | 0.587177E+11 | 0.00 | 0.00 |
November | 0.926382E+11 | 0.762256E+10 | 0.00 | 0.00 | 0.00 | 0.132126E+12 | 0.00 | 0.00 |
December | 0.957262E+11 | 0.146441E+11 | 0.00 | 0.00 | 0.00 | 0.238249E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.112710E+13 | 0.653986E+12 | 0.00 | 0.00 | 0.00 | 0.112290E+13 | 0.00 | 0.00 |
Minimum of Months | 0.864624E+11 | 0.120084E+10 | 0.00 | 0.00 | 0.00 | 0.100483E+11 | 0.00 | 0.00 |
Maximum of Months | 0.957262E+11 | 0.397848E+12 | 0.00 | 0.00 | 0.00 | 0.238249E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153569E+10 | 0.419350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138708E+10 | 0.871238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153569E+10 | 0.150690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148616E+10 | 0.200713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153569E+10 | 0.544479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148616E+10 | 0.105880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153569E+10 | 0.161970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153569E+10 | 0.212244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148616E+10 | 0.545002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153569E+10 | 0.102552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148616E+10 | 0.145890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153569E+10 | 0.198491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180816E+11 | 0.151644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138708E+10 | 0.419350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153569E+10 | 0.212244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147531E+11 | 0.212053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133254E+11 | 0.672217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147531E+11 | 0.127481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142772E+11 | 0.183652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147531E+11 | 0.442748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142772E+11 | 0.961034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147531E+11 | 0.149975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147531E+11 | 0.198391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142772E+11 | 0.450731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147531E+11 | 0.841901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142772E+11 | 0.120536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147531E+11 | 0.164812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173706E+12 | 0.130292E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133254E+11 | 0.212053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147531E+11 | 0.198391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149461E+10 | 0.703887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134997E+10 | 0.503794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149461E+10 | 0.112298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144639E+10 | 0.175431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149461E+10 | 0.368298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144639E+10 | 0.922992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149461E+10 | 0.146794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149461E+10 | 0.195075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144639E+10 | 0.382994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149461E+10 | 0.697031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144639E+10 | 0.103439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149461E+10 | 0.145409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175978E+11 | 0.117300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134997E+10 | 0.703887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149461E+10 | 0.195075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.409346E+10 | 0.691183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431308E+10 | 0.389802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551458E+10 | 0.182186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.965910E+10 | 0.132298E+09 | 0.463960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.754058E+10 | 43242721.26 | 0.561799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.962733E+10 | 2144.86 | 0.182839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112564E+11 | 3265.85 | 0.311273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132747E+11 | 2543.98 | 0.412213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.834217E+10 | 4882626.12 | 0.192813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615803E+10 | 0.208748E+09 | 0.103818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507666E+10 | 0.164683E+10 | 12987169.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473755E+10 | 0.461801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895937E+11 | 0.192857E+11 | 0.121223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.409346E+10 | 2144.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132747E+11 | 0.691183E+10 | 0.412213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321806E+11 | 0.179284E+12 | 47151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311329E+11 | 0.113759E+12 | 40396.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355148E+11 | 0.768271E+11 | 78365.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.579123E+11 | 0.845576E+10 | 0.384183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.595080E+11 | 0.305439E+10 | 0.480701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.717422E+11 | 25424882.86 | 0.151882E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768427E+11 | 0.00 | 0.246517E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.858606E+11 | 0.00 | 0.310642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.685423E+11 | 0.385135E+09 | 0.169679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.429782E+11 | 0.206102E+11 | 0.869778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321916E+11 | 0.856407E+11 | 50104132.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304073E+11 | 0.202580E+12 | 39711.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624813E+12 | 0.690621E+12 | 0.973956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304073E+11 | 0.00 | 39711.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.858606E+11 | 0.202580E+12 | 0.310642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.315809E+10 | 0.348256E+11 | 77901.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281165E+10 | 0.242390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311026E+10 | 0.184317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435070E+10 | 0.337731E+10 | 0.370326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.474142E+10 | 0.193525E+10 | 0.484941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600056E+10 | 0.119922E+09 | 0.157259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658795E+10 | 50032010.95 | 0.251205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.696037E+10 | 21742685.84 | 0.297960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.515803E+10 | 0.717594E+09 | 0.152895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325489E+10 | 0.817966E+10 | 0.623258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290002E+10 | 0.210353E+11 | 4559993.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324535E+10 | 0.394026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.522793E+11 | 0.152336E+12 | 0.951125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.281165E+10 | 21742685.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.696037E+10 | 0.394026E+11 | 0.297960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148454E+11 | 231.53 | 1667287.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136777E+11 | 0.00 | 0.751880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144864E+11 | 274.68 | 0.227142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142407E+11 | 104.56 | 0.824059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139317E+11 | 0.00 | 0.135545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154004E+11 | 180.36 | 0.178470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138968E+11 | 108.55 | 0.851000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141980E+11 | 0.00 | 0.162845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137289E+11 | 148.25 | 21877835.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168982E+12 | 1047.93 | 0.513617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154004E+11 | 274.68 | 0.178470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.957262E+11 | 0.00 | 0.715631E+10 | 0.00 | 0.345760E+10 | 0.00 | 0.00 | 0.00 | 0.758135E+11 | 0.00 | 0.00 | 0.00 |
February | 0.864624E+11 | 0.00 | 0.100050E+11 | 0.00 | 0.392502E+10 | 0.00 | 0.00 | 0.00 | 0.116523E+12 | 0.00 | 0.00 | 0.00 |
March | 0.957262E+11 | 0.00 | 0.167528E+11 | 0.00 | 0.572918E+10 | 0.00 | 0.00 | 0.00 | 0.195968E+12 | 0.00 | 0.00 | 0.00 |
April | 0.926382E+11 | 0.00 | 0.814052E+11 | 0.00 | 0.205765E+11 | 0.00 | 0.00 | 0.00 | 0.216383E+12 | 0.00 | 0.00 | 0.00 |
May | 0.957262E+11 | 0.00 | 0.541231E+10 | 0.00 | 0.314113E+10 | 0.00 | 0.00 | 0.00 | 0.396943E+11 | 0.00 | 0.00 | 0.00 |
June | 0.926382E+11 | 0.00 | 0.314940E+11 | 0.00 | 0.944180E+10 | 0.00 | 0.00 | 0.00 | 0.131246E+11 | 0.00 | 0.00 | 0.00 |
July | 0.957262E+11 | 0.00 | 0.162136E+12 | 0.00 | 0.385555E+11 | 0.00 | 0.00 | 0.00 | 0.100935E+11 | 0.00 | 0.00 | 0.00 |
August | 0.957262E+11 | 0.00 | 0.508773E+12 | 0.00 | 0.110925E+12 | 0.00 | 0.00 | 0.00 | 0.146702E+11 | 0.00 | 0.00 | 0.00 |
September | 0.926382E+11 | 0.00 | 0.399281E+10 | 0.00 | 0.279196E+10 | 0.00 | 0.00 | 0.00 | 0.146615E+11 | 0.00 | 0.00 | 0.00 |
October | 0.957262E+11 | 0.00 | 0.650521E+10 | 0.00 | 0.336989E+10 | 0.00 | 0.00 | 0.00 | 0.589820E+11 | 0.00 | 0.00 | 0.00 |
November | 0.926382E+11 | 0.00 | 0.123555E+11 | 0.00 | 0.473290E+10 | 0.00 | 0.00 | 0.00 | 0.132721E+12 | 0.00 | 0.00 | 0.00 |
December | 0.957262E+11 | 0.00 | 0.217012E+11 | 0.00 | 0.705710E+10 | 0.00 | 0.00 | 0.00 | 0.239321E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112710E+13 | 0.00 | 0.867690E+12 | 0.00 | 0.213704E+12 | 0.00 | 0.00 | 0.00 | 0.112796E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.864624E+11 | 0.00 | 0.399281E+10 | 0.00 | 0.279196E+10 | 0.00 | 0.00 | 0.00 | 0.100935E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.957262E+11 | 0.00 | 0.508773E+12 | 0.00 | 0.110925E+12 | 0.00 | 0.00 | 0.00 | 0.239321E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153569E+10 | 0.00 | 0.527408E+10 | 0.00 | 0.108059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138708E+10 | 0.00 | 0.108103E+11 | 0.00 | 0.209791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153569E+10 | 0.00 | 0.185277E+11 | 0.00 | 0.345871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148616E+10 | 0.00 | 0.245282E+11 | 0.00 | 0.445689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153569E+10 | 0.00 | 0.679363E+10 | 0.00 | 0.134883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148616E+10 | 0.00 | 0.130576E+11 | 0.00 | 0.246954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153569E+10 | 0.00 | 0.198971E+11 | 0.00 | 0.370009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153569E+10 | 0.00 | 0.260237E+11 | 0.00 | 0.479928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148616E+10 | 0.00 | 0.678731E+10 | 0.00 | 0.133728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153569E+10 | 0.00 | 0.126581E+11 | 0.00 | 0.240290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148616E+10 | 0.00 | 0.178998E+11 | 0.00 | 0.331083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153569E+10 | 0.00 | 0.242780E+11 | 0.00 | 0.442887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180816E+11 | 0.00 | 0.186536E+12 | 0.00 | 0.348917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138708E+10 | 0.00 | 0.527408E+10 | 0.00 | 0.108059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153569E+10 | 0.00 | 0.260237E+11 | 0.00 | 0.479928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147531E+11 | 0.00 | 0.269834E+11 | 0.00 | 0.577807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133254E+11 | 0.00 | 0.837208E+11 | 0.00 | 0.164991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147531E+11 | 0.00 | 0.157157E+12 | 0.00 | 0.296757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142772E+11 | 0.00 | 0.224705E+12 | 0.00 | 0.410530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147531E+11 | 0.00 | 0.553870E+11 | 0.00 | 0.111122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142772E+11 | 0.00 | 0.118648E+12 | 0.00 | 0.225445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147531E+11 | 0.00 | 0.184400E+12 | 0.00 | 0.344245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147531E+11 | 0.00 | 0.243437E+12 | 0.00 | 0.450458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142772E+11 | 0.00 | 0.562699E+11 | 0.00 | 0.111968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147531E+11 | 0.00 | 0.104199E+12 | 0.00 | 0.200087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142772E+11 | 0.00 | 0.148342E+12 | 0.00 | 0.278054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147531E+11 | 0.00 | 0.202280E+12 | 0.00 | 0.374673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173706E+12 | 0.00 | 0.160553E+13 | 0.00 | 0.302611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133254E+11 | 0.00 | 0.269834E+11 | 0.00 | 0.577807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147531E+11 | 0.00 | 0.243437E+12 | 0.00 | 0.450458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149461E+10 | 0.00 | 0.907246E+09 | 0.00 | 0.203359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134997E+10 | 0.00 | 0.630086E+10 | 0.00 | 0.126292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149461E+10 | 0.00 | 0.138797E+11 | 0.00 | 0.264990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144639E+10 | 0.00 | 0.214940E+11 | 0.00 | 0.395091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149461E+10 | 0.00 | 0.462025E+10 | 0.00 | 0.937269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144639E+10 | 0.00 | 0.114066E+11 | 0.00 | 0.217672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149461E+10 | 0.00 | 0.180644E+11 | 0.00 | 0.338505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149461E+10 | 0.00 | 0.239573E+11 | 0.00 | 0.444978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144639E+10 | 0.00 | 0.479470E+10 | 0.00 | 0.964751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149461E+10 | 0.00 | 0.865315E+10 | 0.00 | 0.168284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144639E+10 | 0.00 | 0.127671E+11 | 0.00 | 0.242321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149461E+10 | 0.00 | 0.178977E+11 | 0.00 | 0.335678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175978E+11 | 0.00 | 0.144743E+12 | 0.00 | 0.274435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134997E+10 | 0.00 | 0.907246E+09 | 0.00 | 0.203359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149461E+10 | 0.00 | 0.239573E+11 | 0.00 | 0.444978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558436E+09 | 0.00 | 0.00 | 0.106025E+09 | 0.00 | 0.00 | 0.677426E+11 | 0.00 | 0.56 |
February | 0.409667E+09 | 0.00 | 0.00 | 0.100970E+09 | 0.00 | 0.00 | 0.619800E+11 | 0.00 | 0.58 |
March | 0.361503E+09 | 0.00 | 0.00 | 0.113685E+09 | 0.00 | 0.00 | 0.754013E+11 | 0.00 | 0.68 |
April | 0.303678E+09 | 0.00 | 0.00 | 0.116885E+09 | 0.00 | 0.00 | 0.735857E+11 | 0.00 | 0.92 |
May | 0.280594E+09 | 0.00 | 0.00 | 0.113241E+09 | 0.00 | 0.00 | 0.733616E+11 | 0.00 | 0.94 |
June | 0.184909E+09 | 1764972.24 | 0.00 | 0.115190E+09 | 0.00 | 0.00 | 0.698587E+11 | 0.00 | 1.22 |
July | 0.289732E+09 | 54114676.56 | 0.00 | 0.118602E+09 | 6621284.36 | 0.00 | 0.644845E+11 | 0.00 | 1.30 |
August | 0.277569E+09 | 0.00 | 0.00 | 0.135976E+09 | 0.00 | 0.00 | 0.687431E+11 | 0.00 | 1.55 |
September | 0.281844E+09 | 0.00 | 0.00 | 0.116726E+09 | 0.00 | 0.00 | 0.666347E+11 | 0.00 | 1.26 |
October | 0.339310E+09 | 0.00 | 0.00 | 0.118530E+09 | 0.00 | 0.00 | 0.752898E+11 | 0.00 | 0.89 |
November | 0.398806E+09 | 0.00 | 0.00 | 0.115432E+09 | 0.00 | 0.00 | 0.723595E+11 | 0.00 | 0.71 |
December | 0.559305E+09 | 0.00 | 0.00 | 0.114426E+09 | 0.00 | 0.00 | 0.698566E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.424535E+10 | 55879648.79 | 0.00 | 0.138569E+10 | 6621284.36 | 0.00 | 0.839298E+12 | 0.00 | 0.93 |
Minimum of Months | 0.184909E+09 | 0.00 | 0.00 | 0.100970E+09 | 0.00 | 0.00 | 0.619800E+11 | 0.00 | 0.56 |
Maximum of Months | 0.559305E+09 | 54114676.56 | 0.00 | 0.135976E+09 | 6621284.36 | 0.00 | 0.754013E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315013E+10 | 0.00 | 0.00 | 62620753.04 | 0.00 | 0.00 | 0.466754E+11 | 0.00 | 0.39 |
February | 0.198925E+10 | 0.00 | 0.00 | 69934446.60 | 0.00 | 0.00 | 0.453177E+11 | 0.00 | 0.43 |
March | 0.151458E+10 | 0.00 | 0.00 | 89720544.97 | 0.00 | 0.00 | 0.588835E+11 | 0.00 | 0.52 |
April | 0.416360E+10 | 0.00 | 0.00 | 0.102950E+09 | 0.00 | 0.00 | 0.625422E+11 | 0.00 | 0.79 |
May | 0.432282E+10 | 0.00 | 0.00 | 86808416.77 | 0.00 | 0.00 | 0.553969E+11 | 0.00 | 0.72 |
June | 0.399690E+10 | 4466996.89 | 0.00 | 97880338.27 | 59581393.08 | 0.00 | 0.564887E+11 | 0.00 | 0.97 |
July | 0.684890E+10 | 21392044.83 | 0.00 | 99884820.12 | 8695431.89 | 0.00 | 0.512930E+11 | 0.00 | 1.06 |
August | 0.701000E+10 | 0.00 | 0.00 | 0.116688E+09 | 0.00 | 0.00 | 0.540157E+11 | 0.00 | 1.22 |
September | 0.424940E+10 | 0.00 | 0.00 | 88456638.91 | 0.00 | 0.00 | 0.476026E+11 | 0.00 | 0.90 |
October | 0.204260E+10 | 0.00 | 0.00 | 87424256.48 | 0.00 | 0.00 | 0.549471E+11 | 0.00 | 0.65 |
November | 0.186995E+10 | 0.00 | 0.00 | 84652303.31 | 0.00 | 0.00 | 0.532050E+11 | 0.00 | 0.52 |
December | 0.162033E+10 | 0.00 | 0.00 | 82162427.24 | 0.00 | 0.00 | 0.521144E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.427785E+11 | 25859041.72 | 0.00 | 0.106918E+10 | 68276824.97 | 0.00 | 0.638482E+12 | 0.00 | 0.72 |
Minimum of Months | 0.151458E+10 | 0.00 | 0.00 | 62620753.04 | 0.00 | 0.00 | 0.453177E+11 | 0.00 | 0.39 |
Maximum of Months | 0.701000E+10 | 21392044.83 | 0.00 | 0.116688E+09 | 59581393.08 | 0.00 | 0.625422E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214300E+12 | 0.00 | 0.00 | 0.177668E+09 | 0.00 | 0.141841E+09 | 0.158716E+12 | 0.00 | 0.30 |
February | 0.164945E+12 | 0.00 | 0.00 | 0.218304E+09 | 0.00 | 0.00 | 0.170108E+12 | 0.00 | 0.31 |
March | 0.149479E+12 | 0.00 | 0.00 | 0.320975E+09 | 0.00 | 0.00 | 0.250296E+12 | 0.00 | 0.35 |
April | 0.582447E+11 | 0.00 | 0.00 | 0.511853E+09 | 0.00 | 0.00 | 0.375475E+12 | 0.00 | 0.53 |
May | 0.724479E+11 | 0.00 | 0.00 | 0.535426E+09 | 0.00 | 0.00 | 0.388676E+12 | 0.00 | 0.57 |
June | 0.370503E+11 | 42419595.63 | 0.00 | 0.657962E+09 | 0.677462E+09 | 0.00 | 0.421344E+12 | 0.00 | 0.75 |
July | 0.491895E+11 | 0.250974E+09 | 0.00 | 0.635205E+09 | 0.135148E+09 | 0.00 | 0.358598E+12 | 0.00 | 0.77 |
August | 0.397525E+11 | 0.00 | 0.00 | 0.732199E+09 | 0.00 | 0.00 | 0.376150E+12 | 0.00 | 0.87 |
September | 0.559448E+11 | 0.00 | 0.00 | 0.581408E+09 | 0.00 | 0.00 | 0.347643E+12 | 0.00 | 0.73 |
October | 0.100814E+12 | 0.00 | 0.00 | 0.400891E+09 | 0.00 | 0.00 | 0.287524E+12 | 0.00 | 0.45 |
November | 0.150322E+12 | 0.00 | 0.00 | 0.247936E+09 | 0.00 | 0.00 | 0.194238E+12 | 0.00 | 0.33 |
December | 0.221579E+12 | 0.00 | 0.00 | 0.118615E+09 | 0.00 | 0.00 | 0.123824E+12 | 0.00 | 0.28 |
Annual Sum or Average | 0.131407E+13 | 0.293394E+09 | 0.00 | 0.513844E+10 | 0.812609E+09 | 0.141841E+09 | 0.345259E+13 | 0.00 | 0.52 |
Minimum of Months | 0.370503E+11 | 0.00 | 0.00 | 0.118615E+09 | 0.00 | 0.00 | 0.123824E+12 | 0.00 | 0.28 |
Maximum of Months | 0.221579E+12 | 0.250974E+09 | 0.00 | 0.732199E+09 | 0.677462E+09 | 0.141841E+09 | 0.421344E+12 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289967E+11 | 0.00 | 0.00 | 907883.50 | 0.00 | 0.137826E+10 | 0.142597E+10 | 0.00 | 0.28 |
February | 0.257154E+11 | 0.00 | 0.00 | 1266074.62 | 0.00 | 0.540993E+09 | 0.221566E+10 | 0.00 | 0.28 |
March | 0.271196E+11 | 0.00 | 0.00 | 4102008.95 | 0.00 | 0.438957E+09 | 0.561240E+10 | 0.00 | 0.31 |
April | 0.128371E+11 | 3103866.36 | 0.00 | 27898875.60 | 0.00 | 0.00 | 0.244541E+11 | 0.00 | 0.46 |
May | 0.125438E+11 | 0.00 | 0.00 | 34318397.54 | 0.00 | 0.00 | 0.282482E+11 | 0.00 | 0.51 |
June | 0.825521E+10 | 934018.96 | 0.00 | 51469822.21 | 55171039.57 | 0.00 | 0.352630E+11 | 0.00 | 0.72 |
July | 0.819223E+10 | 12815748.79 | 0.00 | 52866521.35 | 9757635.06 | 0.00 | 0.316890E+11 | 0.00 | 0.76 |
August | 0.775923E+10 | 0.00 | 0.00 | 56322352.68 | 0.00 | 0.00 | 0.317551E+11 | 0.00 | 0.83 |
September | 0.109849E+11 | 0.00 | 0.00 | 36269021.04 | 0.00 | 0.00 | 0.239370E+11 | 0.00 | 0.65 |
October | 0.194747E+11 | 0.00 | 0.00 | 9524727.71 | 0.00 | 0.218374E+09 | 0.102146E+11 | 0.00 | 0.37 |
November | 0.245523E+11 | 0.00 | 0.00 | 2070879.58 | 0.00 | 0.637433E+09 | 0.290444E+10 | 0.00 | 0.29 |
December | 0.286916E+11 | 0.00 | 0.00 | 70715.81 | 0.00 | 0.120040E+10 | 0.290171E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.215123E+12 | 16853634.11 | 0.00 | 0.277087E+09 | 64928674.63 | 0.441442E+10 | 0.198010E+12 | 0.00 | 0.48 |
Minimum of Months | 0.775923E+10 | 0.00 | 0.00 | 70715.81 | 0.00 | 0.00 | 0.290171E+09 | 0.00 | 0.27 |
Maximum of Months | 0.289967E+11 | 12815748.79 | 0.00 | 56322352.68 | 55171039.57 | 0.137826E+10 | 0.352630E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.402349E+10 | 0.00 | 0.00 | 292244.47 | 0.00 | 36936717.64 | 0.466355E+09 | 0.00 | 0.28 |
February | 0.343178E+10 | 0.00 | 0.00 | 626602.57 | 0.00 | 0.00 | 0.715226E+09 | 0.00 | 0.29 |
March | 0.279227E+10 | 0.00 | 0.00 | 2752799.79 | 0.00 | 0.00 | 0.239968E+10 | 0.00 | 0.36 |
April | 0.167643E+10 | 0.00 | 0.00 | 6825362.53 | 0.00 | 0.00 | 0.521022E+10 | 0.00 | 0.68 |
May | 0.156838E+10 | 0.00 | 0.00 | 6920593.15 | 0.00 | 0.00 | 0.509868E+10 | 0.00 | 0.67 |
June | 0.831373E+09 | 988535.67 | 0.00 | 10995235.05 | 7475386.30 | 0.00 | 0.693195E+10 | 0.00 | 1.05 |
July | 0.103863E+10 | 4797086.54 | 0.00 | 11709326.20 | 1090973.36 | 0.00 | 0.655949E+10 | 0.00 | 1.15 |
August | 0.117476E+10 | 0.00 | 0.00 | 12095774.00 | 0.00 | 0.00 | 0.621844E+10 | 0.00 | 1.24 |
September | 0.172570E+10 | 0.00 | 0.00 | 6164875.35 | 0.00 | 0.00 | 0.381781E+10 | 0.00 | 0.80 |
October | 0.233661E+10 | 0.00 | 0.00 | 3152448.54 | 0.00 | 0.00 | 0.270038E+10 | 0.00 | 0.46 |
November | 0.297406E+10 | 0.00 | 0.00 | 1430696.72 | 0.00 | 0.00 | 0.145225E+10 | 0.00 | 0.33 |
December | 0.404163E+10 | 0.00 | 0.00 | 137452.23 | 0.00 | 0.00 | 0.362096E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.276151E+11 | 5785622.22 | 0.00 | 63103410.61 | 8566359.66 | 36936717.64 | 0.419326E+11 | 0.00 | 0.63 |
Minimum of Months | 0.831373E+09 | 0.00 | 0.00 | 137452.23 | 0.00 | 0.00 | 0.362096E+09 | 0.00 | 0.28 |
Maximum of Months | 0.404163E+10 | 4797086.54 | 0.00 | 12095774.00 | 7475386.30 | 36936717.64 | 0.693195E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451029E+10 | 0.00 | 0.00 | 273646.17 | 0.00 | 79495131.96 | 0.309783E+09 | 0.00 | 0.47 |
February | 0.399738E+10 | 0.00 | 0.00 | 772274.54 | 0.00 | 10285982.66 | 0.550451E+09 | 0.00 | 0.50 |
March | 0.390955E+10 | 0.00 | 0.00 | 1057715.26 | 0.00 | 0.00 | 0.129949E+10 | 0.00 | 0.55 |
April | 0.194056E+10 | 0.00 | 0.00 | 9477737.94 | 0.00 | 0.00 | 0.613229E+10 | 0.00 | 1.22 |
May | 0.172673E+10 | 0.00 | 0.00 | 9594058.63 | 0.00 | 0.00 | 0.618855E+10 | 0.00 | 1.22 |
June | 0.128830E+10 | 602354.26 | 0.00 | 11486599.18 | 8066197.73 | 0.00 | 0.655707E+10 | 0.00 | 1.63 |
July | 0.143238E+10 | 6088943.18 | 0.00 | 12014729.29 | 1177197.60 | 0.00 | 0.616426E+10 | 0.00 | 1.75 |
August | 0.171637E+10 | 0.00 | 0.00 | 12814704.85 | 0.00 | 0.00 | 0.611512E+10 | 0.00 | 1.96 |
September | 0.183965E+10 | 0.00 | 0.00 | 9675256.99 | 0.00 | 0.00 | 0.505740E+10 | 0.00 | 1.51 |
October | 0.303499E+10 | 0.00 | 0.00 | 3283927.25 | 0.00 | 0.00 | 0.244309E+10 | 0.00 | 0.77 |
November | 0.423133E+10 | 0.00 | 0.00 | 408622.83 | 0.00 | 0.00 | 0.464326E+09 | 0.00 | 0.54 |
December | 0.459186E+10 | 0.00 | 0.00 | 192212.33 | 0.00 | 7466618.02 | 0.155487E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.342194E+11 | 6691297.44 | 0.00 | 71051485.27 | 9243395.34 | 97247732.65 | 0.414373E+11 | 0.00 | 1.05 |
Minimum of Months | 0.128830E+10 | 0.00 | 0.00 | 192212.33 | 0.00 | 0.00 | 0.155487E+09 | 0.00 | 0.46 |
Maximum of Months | 0.459186E+10 | 6088943.18 | 0.00 | 12814704.85 | 8066197.73 | 79495131.96 | 0.655707E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.505226E+10 | 0.00 | 0.00 | 4399647.68 | 0.00 | 0.174921E+09 | 0.309777E+10 | 0.00 | 0.52 |
February | 0.437757E+10 | 0.00 | 0.00 | 6341175.19 | 0.00 | 22682968.93 | 0.402542E+10 | 0.00 | 0.60 |
March | 0.485724E+10 | 0.00 | 0.00 | 3794032.17 | 0.00 | 508168.18 | 0.324675E+10 | 0.00 | 0.56 |
April | 0.259474E+10 | 0.00 | 0.00 | 16664568.78 | 0.00 | 0.00 | 0.107020E+11 | 0.00 | 1.37 |
May | 0.286877E+10 | 0.00 | 0.00 | 10935954.51 | 0.00 | 0.00 | 0.799069E+10 | 0.00 | 1.11 |
June | 0.213308E+10 | 1021612.09 | 0.00 | 13358003.09 | 11310681.87 | 0.00 | 0.824185E+10 | 0.00 | 1.43 |
July | 0.218409E+10 | 7100247.98 | 0.00 | 16225614.20 | 1650704.34 | 0.00 | 0.843101E+10 | 0.00 | 1.64 |
August | 0.223098E+10 | 0.00 | 0.00 | 23012678.82 | 0.00 | 0.00 | 0.982708E+10 | 0.00 | 2.09 |
September | 0.225889E+10 | 0.00 | 0.00 | 20578495.31 | 0.00 | 0.00 | 0.988434E+10 | 0.00 | 1.87 |
October | 0.367748E+10 | 0.00 | 0.00 | 10322256.38 | 0.00 | 0.00 | 0.718084E+10 | 0.00 | 1.05 |
November | 0.477760E+10 | 0.00 | 0.00 | 4811278.45 | 0.00 | 9295544.35 | 0.324985E+10 | 0.00 | 0.60 |
December | 0.549827E+10 | 0.00 | 0.00 | 2674943.94 | 0.00 | 60383207.00 | 0.200049E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.425110E+11 | 8121860.07 | 0.00 | 0.133119E+09 | 12961386.21 | 0.267791E+09 | 0.778781E+11 | 0.00 | 1.11 |
Minimum of Months | 0.213308E+10 | 0.00 | 0.00 | 2674943.94 | 0.00 | 0.00 | 0.200049E+10 | 0.00 | 0.47 |
Maximum of Months | 0.549827E+10 | 7100247.98 | 0.00 | 23012678.82 | 11310681.87 | 0.174921E+09 | 0.107020E+11 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489262E+10 | 0.00 | 0.00 | 1033844.14 | 0.00 | 253467.85 | 0.115372E+10 | 0.00 | 0.58 |
February | 0.312074E+10 | 0.00 | 0.00 | 3609756.85 | 0.00 | 0.00 | 0.306427E+10 | 0.00 | 0.68 |
March | 0.170678E+10 | 0.00 | 0.00 | 6936488.18 | 0.00 | 0.00 | 0.582011E+10 | 0.00 | 0.81 |
April | 0.615539E+09 | 0.00 | 0.00 | 19170769.43 | 0.00 | 0.00 | 0.110957E+11 | 0.00 | 1.85 |
May | 0.140000E+10 | 0.00 | 0.00 | 13122962.73 | 0.00 | 0.00 | 0.809084E+10 | 0.00 | 1.51 |
June | 0.589845E+09 | 23616546.86 | 0.00 | 19137705.59 | 442611.25 | 0.00 | 0.101062E+11 | 0.00 | 2.29 |
July | 0.815549E+09 | 10335338.38 | 0.00 | 24708112.25 | 121698.76 | 0.00 | 0.103179E+11 | 0.00 | 2.67 |
August | 0.807228E+09 | 0.00 | 0.00 | 27639772.34 | 0.00 | 0.00 | 0.106975E+11 | 0.00 | 2.99 |
September | 0.144574E+10 | 0.00 | 0.00 | 10945559.80 | 0.00 | 0.00 | 0.609678E+10 | 0.00 | 1.74 |
October | 0.189524E+10 | 0.00 | 0.00 | 6293126.45 | 0.00 | 0.00 | 0.527648E+10 | 0.00 | 1.03 |
November | 0.206129E+10 | 0.00 | 0.00 | 4658183.23 | 0.00 | 0.00 | 0.420949E+10 | 0.00 | 0.73 |
December | 0.263449E+10 | 0.00 | 0.00 | 3677393.53 | 0.00 | 0.00 | 0.345425E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.219851E+11 | 33951885.24 | 0.00 | 0.140934E+09 | 564310.01 | 253467.85 | 0.793832E+11 | 0.00 | 1.46 |
Minimum of Months | 0.589845E+09 | 0.00 | 0.00 | 1033844.14 | 0.00 | 0.00 | 0.115372E+10 | 0.00 | 0.58 |
Maximum of Months | 0.489262E+10 | 23616546.86 | 0.00 | 27639772.34 | 442611.25 | 253467.85 | 0.110957E+11 | 0.00 | 2.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167693E+11 | 0.00 | 0.00 | 0.28 |
February | 0.292416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101902E+11 | 0.00 | 0.00 | 0.28 |
March | 0.390693E+11 | 0.00 | 0.00 | 56406.57 | 0.00 | 0.496306E+10 | 0.336051E+09 | 0.00 | 0.31 |
April | 0.249160E+11 | 0.00 | 0.00 | 22099130.21 | 0.00 | 0.109614E+09 | 0.189440E+11 | 0.00 | 0.44 |
May | 0.246430E+11 | 0.00 | 0.00 | 30835912.14 | 0.00 | 14842155.02 | 0.242641E+11 | 0.00 | 0.50 |
June | 0.122640E+11 | 11053635.52 | 0.00 | 67515512.64 | 85168719.54 | 0.00 | 0.433595E+11 | 0.00 | 0.77 |
July | 0.131542E+11 | 61070571.24 | 0.00 | 69089480.67 | 16990427.57 | 0.00 | 0.392281E+11 | 0.00 | 0.83 |
August | 0.150929E+11 | 0.00 | 0.00 | 66689751.34 | 0.00 | 0.00 | 0.343783E+11 | 0.00 | 0.85 |
September | 0.236372E+11 | 0.00 | 0.00 | 30849835.27 | 0.00 | 0.00 | 0.185092E+11 | 0.00 | 0.61 |
October | 0.348834E+11 | 0.00 | 0.00 | 3116016.53 | 0.00 | 0.138411E+10 | 0.332446E+10 | 0.00 | 0.36 |
November | 0.315096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802517E+10 | 0.00 | 0.00 | 0.30 |
December | 0.215261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212588E+11 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.297902E+12 | 72124206.76 | 0.00 | 0.290252E+09 | 0.102159E+09 | 0.627151E+11 | 0.182344E+12 | 0.00 | 0.49 |
Minimum of Months | 0.122640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.390693E+11 | 61070571.24 | 0.00 | 69089480.67 | 85168719.54 | 0.212588E+11 | 0.433595E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345666E+11 | 0.00 | 0.00 | 98375.70 | 0.00 | 0.168620E+11 | 0.216759E+09 | 0.00 | 0.51 |
February | 0.342526E+11 | 0.00 | 0.00 | 1410906.99 | 0.00 | 0.103093E+11 | 0.107041E+10 | 0.00 | 0.51 |
March | 0.446491E+11 | 0.00 | 0.00 | 662444.46 | 0.00 | 0.581940E+10 | 0.816904E+09 | 0.00 | 0.55 |
April | 0.182908E+11 | 0.00 | 0.00 | 78392867.52 | 0.00 | 0.127091E+09 | 0.501706E+11 | 0.00 | 1.06 |
May | 0.224865E+11 | 0.00 | 0.00 | 76465385.51 | 0.00 | 16781004.29 | 0.485963E+11 | 0.00 | 1.13 |
June | 0.153061E+11 | 8792540.43 | 0.00 | 99473531.74 | 97309010.97 | 0.00 | 0.557846E+11 | 0.00 | 1.53 |
July | 0.140660E+11 | 91189298.18 | 0.00 | 0.108310E+09 | 19635648.12 | 0.00 | 0.522631E+11 | 0.00 | 1.60 |
August | 0.154936E+11 | 0.00 | 0.00 | 0.113256E+09 | 0.00 | 0.00 | 0.535520E+11 | 0.00 | 1.80 |
September | 0.208864E+11 | 0.00 | 0.00 | 80576526.09 | 0.00 | 0.00 | 0.411955E+11 | 0.00 | 1.41 |
October | 0.344514E+11 | 0.00 | 0.00 | 17684489.62 | 0.00 | 0.190543E+10 | 0.124599E+11 | 0.00 | 0.70 |
November | 0.365844E+11 | 0.00 | 0.00 | 17415.64 | 0.00 | 0.899786E+10 | 0.102128E+09 | 0.00 | 0.54 |
December | 0.254849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238882E+11 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.316519E+12 | 99981838.61 | 0.00 | 0.576348E+09 | 0.116945E+09 | 0.679260E+11 | 0.316228E+12 | 0.00 | 0.99 |
Minimum of Months | 0.140660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.446491E+11 | 91189298.18 | 0.00 | 0.113256E+09 | 97309010.97 | 0.238882E+11 | 0.557846E+11 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.472810E+11 | 0.00 | 0.00 | 34711289.30 | 0.00 | 0.120090E+11 | 0.249206E+11 | 0.00 | 0.54 |
February | 0.409014E+11 | 0.00 | 0.00 | 53500095.34 | 0.00 | 0.775925E+10 | 0.326547E+11 | 0.00 | 0.60 |
March | 0.519418E+11 | 0.00 | 0.00 | 19723016.01 | 0.00 | 0.574125E+10 | 0.176138E+11 | 0.00 | 0.53 |
April | 0.270005E+11 | 0.00 | 0.00 | 0.147067E+09 | 0.00 | 21849576.36 | 0.886160E+11 | 0.00 | 1.22 |
May | 0.348910E+11 | 0.00 | 0.00 | 90288468.23 | 0.00 | 0.155078E+09 | 0.650313E+11 | 0.00 | 1.05 |
June | 0.266038E+11 | 14468002.18 | 0.00 | 0.105125E+09 | 0.135140E+09 | 0.00 | 0.645673E+11 | 0.00 | 1.29 |
July | 0.233111E+11 | 0.113330E+09 | 0.00 | 0.132916E+09 | 33730190.93 | 0.00 | 0.665592E+11 | 0.00 | 1.45 |
August | 0.209892E+11 | 0.00 | 0.00 | 0.202915E+09 | 0.00 | 0.00 | 0.830082E+11 | 0.00 | 1.89 |
September | 0.247614E+11 | 0.00 | 0.00 | 0.209126E+09 | 0.00 | 0.00 | 0.922593E+11 | 0.00 | 1.87 |
October | 0.388791E+11 | 0.00 | 0.00 | 93183997.35 | 0.00 | 0.132754E+10 | 0.619429E+11 | 0.00 | 1.01 |
November | 0.455419E+11 | 0.00 | 0.00 | 32918169.33 | 0.00 | 0.681373E+10 | 0.208370E+11 | 0.00 | 0.56 |
December | 0.406933E+11 | 0.00 | 0.00 | 14199231.40 | 0.00 | 0.221928E+11 | 0.102714E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.422796E+12 | 0.127798E+09 | 0.00 | 0.113567E+10 | 0.168870E+09 | 0.560204E+11 | 0.628282E+12 | 0.00 | 1.04 |
Minimum of Months | 0.209892E+11 | 0.00 | 0.00 | 14199231.40 | 0.00 | 0.00 | 0.102714E+11 | 0.00 | 0.48 |
Maximum of Months | 0.519418E+11 | 0.113330E+09 | 0.00 | 0.209126E+09 | 0.135140E+09 | 0.221928E+11 | 0.922593E+11 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409281E+11 | 0.00 | 0.00 | 957001.13 | 0.00 | 0.130559E+11 | 0.956513E+09 | 0.00 | 0.54 |
February | 0.380673E+11 | 0.00 | 0.00 | 7492663.84 | 0.00 | 0.626884E+10 | 0.566192E+10 | 0.00 | 0.56 |
March | 0.483058E+11 | 0.00 | 0.00 | 4681159.00 | 0.00 | 0.302874E+10 | 0.419738E+10 | 0.00 | 0.60 |
April | 0.270352E+11 | 0.00 | 0.00 | 68476081.29 | 0.00 | 0.00 | 0.409249E+11 | 0.00 | 1.10 |
May | 0.288238E+11 | 0.00 | 0.00 | 81052699.20 | 0.00 | 43723907.63 | 0.453299E+11 | 0.00 | 1.22 |
June | 0.167504E+11 | 0.271501E+09 | 0.00 | 0.113079E+09 | 7146981.89 | 0.00 | 0.585522E+11 | 0.00 | 1.68 |
July | 0.149167E+11 | 0.122442E+09 | 0.00 | 0.141531E+09 | 7798717.56 | 0.00 | 0.567475E+11 | 0.00 | 1.81 |
August | 0.154280E+11 | 0.00 | 0.00 | 0.128689E+09 | 0.00 | 0.00 | 0.511346E+11 | 0.00 | 1.81 |
September | 0.261548E+11 | 0.00 | 0.00 | 60552958.03 | 0.00 | 0.00 | 0.321316E+11 | 0.00 | 1.38 |
October | 0.404499E+11 | 0.00 | 0.00 | 14063310.50 | 0.00 | 0.102183E+10 | 0.116016E+11 | 0.00 | 0.77 |
November | 0.409473E+11 | 0.00 | 0.00 | 1568154.79 | 0.00 | 0.622117E+10 | 0.154550E+10 | 0.00 | 0.57 |
December | 0.334638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189905E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.371271E+12 | 0.393944E+09 | 0.00 | 0.622143E+09 | 14945699.45 | 0.486306E+11 | 0.308784E+12 | 0.00 | 1.05 |
Minimum of Months | 0.149167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.483058E+11 | 0.271501E+09 | 0.00 | 0.141531E+09 | 7798717.56 | 0.189905E+11 | 0.585522E+11 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295634E+10 | 0.00 | 0.00 | 0.29 |
February | 0.148228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215518E+10 | 0.00 | 0.00 | 0.29 |
March | 0.275076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143208E+10 | 0.00 | 0.00 | 0.31 |
April | 0.249606E+10 | 0.00 | 0.00 | 1392681.83 | 365331.14 | 0.361376E+09 | 0.131897E+10 | 0.00 | 0.42 |
May | 0.277279E+10 | 0.00 | 0.00 | 2192336.58 | 0.00 | 0.195100E+09 | 0.174114E+10 | 0.00 | 0.48 |
June | 0.159922E+10 | 229856.68 | 0.00 | 5716892.39 | 6929378.54 | 2920036.01 | 0.377003E+10 | 0.00 | 0.75 |
July | 0.140307E+10 | 2805575.06 | 0.00 | 6455860.14 | 842812.55 | 2301385.87 | 0.377998E+10 | 0.00 | 0.81 |
August | 0.162005E+10 | 0.00 | 0.00 | 5719963.88 | 0.00 | 387389.93 | 0.319769E+10 | 0.00 | 0.82 |
September | 0.231551E+10 | 0.00 | 0.00 | 2241301.39 | 0.00 | 0.112129E+09 | 0.145114E+10 | 0.00 | 0.57 |
October | 0.273886E+10 | 0.00 | 0.00 | 28555.05 | 0.00 | 0.816410E+09 | 78956202.93 | 0.00 | 0.35 |
November | 0.166971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191002E+10 | 0.00 | 0.00 | 0.30 |
December | 0.824798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308075E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.228099E+11 | 3035431.74 | 0.00 | 23747591.25 | 8137522.22 | 0.130250E+11 | 0.153379E+11 | 0.00 | 0.47 |
Minimum of Months | 0.824798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 387389.93 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.277279E+10 | 2805575.06 | 0.00 | 6455860.14 | 6929378.54 | 0.308075E+10 | 0.377998E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269006E+10 | 0.00 | 0.00 | 0.48 |
February | 0.198928E+10 | 0.00 | 0.00 | 5514.96 | 0.00 | 0.196616E+10 | 17249513.08 | 0.00 | 0.48 |
March | 0.326637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134112E+10 | 0.00 | 0.00 | 0.53 |
April | 0.162973E+10 | 1408644.52 | 0.00 | 6530900.61 | 0.00 | 0.167471E+09 | 0.432992E+10 | 0.00 | 0.97 |
May | 0.216103E+10 | 0.00 | 0.00 | 6270957.98 | 0.00 | 0.103337E+09 | 0.428203E+10 | 0.00 | 1.05 |
June | 0.158587E+10 | 391782.97 | 0.00 | 9150664.60 | 7541108.96 | 3040055.77 | 0.531684E+10 | 0.00 | 1.49 |
July | 0.125190E+10 | 6861597.18 | 0.00 | 10380882.45 | 933010.54 | 741667.95 | 0.522266E+10 | 0.00 | 1.57 |
August | 0.142515E+10 | 0.00 | 0.00 | 10548824.05 | 0.00 | 0.00 | 0.525178E+10 | 0.00 | 1.75 |
September | 0.183721E+10 | 0.00 | 0.00 | 6625569.31 | 0.00 | 50772067.79 | 0.365352E+10 | 0.00 | 1.29 |
October | 0.260700E+10 | 0.00 | 0.00 | 1066508.46 | 0.00 | 0.761521E+09 | 0.781932E+09 | 0.00 | 0.63 |
November | 0.213535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177869E+10 | 0.00 | 0.00 | 0.50 |
December | 0.133835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288303E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.229763E+11 | 8662024.67 | 0.00 | 50579822.44 | 8474119.50 | 0.117459E+11 | 0.288559E+11 | 0.00 | 0.94 |
Minimum of Months | 0.125190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.326637E+10 | 6861597.18 | 0.00 | 10548824.05 | 7541108.96 | 0.288303E+10 | 0.531684E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316107E+10 | 0.00 | 0.00 | 1970224.66 | 0.00 | 0.252687E+10 | 0.150410E+10 | 0.00 | 0.50 |
February | 0.305201E+10 | 0.00 | 0.00 | 3399334.39 | 0.00 | 0.175796E+10 | 0.217038E+10 | 0.00 | 0.55 |
March | 0.452673E+10 | 0.00 | 0.00 | 908470.09 | 0.00 | 0.163060E+10 | 0.799961E+09 | 0.00 | 0.52 |
April | 0.232127E+10 | 0.00 | 0.00 | 13222118.30 | 594102.25 | 0.445923E+09 | 0.836330E+10 | 0.00 | 1.15 |
May | 0.357410E+10 | 0.00 | 0.00 | 7886753.40 | 0.00 | 0.326116E+09 | 0.596759E+10 | 0.00 | 1.02 |
June | 0.295591E+10 | 536121.77 | 0.00 | 9783284.70 | 11077816.54 | 20987139.74 | 0.623702E+10 | 0.00 | 1.28 |
July | 0.228467E+10 | 2680371.50 | 0.00 | 12821596.06 | 3637744.84 | 587156.52 | 0.690523E+10 | 0.00 | 1.44 |
August | 0.218475E+10 | 0.00 | 0.00 | 19205796.36 | 0.00 | 0.00 | 0.847535E+10 | 0.00 | 1.85 |
September | 0.234213E+10 | 0.00 | 0.00 | 18431413.22 | 0.00 | 46785058.60 | 0.894569E+10 | 0.00 | 1.78 |
October | 0.310759E+10 | 0.00 | 0.00 | 7209795.21 | 0.00 | 0.876707E+09 | 0.500165E+10 | 0.00 | 0.92 |
November | 0.331418E+10 | 0.00 | 0.00 | 1749564.81 | 0.00 | 0.174063E+10 | 0.122581E+10 | 0.00 | 0.52 |
December | 0.235058E+10 | 0.00 | 0.00 | 803336.72 | 0.00 | 0.350173E+10 | 0.557045E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.351750E+11 | 3216493.26 | 0.00 | 97391687.92 | 15309663.63 | 0.128749E+11 | 0.561531E+11 | 0.00 | 1.00 |
Minimum of Months | 0.218475E+10 | 0.00 | 0.00 | 803336.72 | 0.00 | 0.00 | 0.557045E+09 | 0.00 | 0.46 |
Maximum of Months | 0.452673E+10 | 2680371.50 | 0.00 | 19205796.36 | 11077816.54 | 0.350173E+10 | 0.894569E+10 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247879E+10 | 0.00 | 0.00 | 36480.13 | 0.00 | 0.244585E+10 | 43222360.64 | 0.00 | 0.54 |
February | 0.264579E+10 | 0.00 | 0.00 | 462439.61 | 0.00 | 0.147208E+10 | 0.409912E+09 | 0.00 | 0.55 |
March | 0.391709E+10 | 0.00 | 0.00 | 306099.12 | 0.00 | 0.102224E+10 | 0.284728E+09 | 0.00 | 0.60 |
April | 0.281823E+10 | 0.00 | 0.00 | 6393268.47 | 453658.38 | 0.189407E+09 | 0.372965E+10 | 0.00 | 1.08 |
May | 0.299123E+10 | 0.00 | 0.00 | 7360047.03 | 0.00 | 0.126538E+09 | 0.428871E+10 | 0.00 | 1.20 |
June | 0.199920E+10 | 21231938.48 | 0.00 | 10940392.54 | 0.00 | 697687.25 | 0.567818E+10 | 0.00 | 1.68 |
July | 0.152554E+10 | 4656573.51 | 0.00 | 13782346.64 | 955121.04 | 0.00 | 0.583781E+10 | 0.00 | 1.81 |
August | 0.171382E+10 | 0.00 | 0.00 | 12138539.12 | 0.00 | 0.00 | 0.505798E+10 | 0.00 | 1.80 |
September | 0.269426E+10 | 0.00 | 0.00 | 5259443.73 | 0.00 | 26218395.85 | 0.294858E+10 | 0.00 | 1.35 |
October | 0.328172E+10 | 0.00 | 0.00 | 1109097.96 | 0.00 | 0.647128E+09 | 0.938823E+09 | 0.00 | 0.74 |
November | 0.284931E+10 | 0.00 | 0.00 | 87956.49 | 0.00 | 0.142778E+10 | 0.104872E+09 | 0.00 | 0.56 |
December | 0.179667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292181E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.307116E+11 | 25888512.00 | 0.00 | 57876110.85 | 1408779.43 | 0.102798E+11 | 0.293225E+11 | 0.00 | 1.04 |
Minimum of Months | 0.152554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.391709E+10 | 21231938.48 | 0.00 | 13782346.64 | 955121.04 | 0.292181E+10 | 0.583781E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3092236.72 | 0.00 | 0.00 | 0.638153E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7639859.46 | 0.00 | 0.00 | 0.562287E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13182980.74 | 0.00 | 0.00 | 0.623715E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17433199.29 | 0.00 | 0.00 | 0.466282E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4036401.71 | 0.00 | 0.00 | 0.472447E+09 | 0.00 | 0.29 |
June | 0.00 | 115179.85 | 0.00 | 8495370.06 | 0.00 | 0.00 | 0.323094E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 12434909.99 | 0.00 | 0.00 | 0.229074E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 18452509.32 | 0.00 | 0.00 | 0.223996E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 3963770.95 | 0.00 | 0.00 | 0.311467E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8260656.96 | 0.00 | 0.00 | 0.462919E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12026824.93 | 0.00 | 0.00 | 0.530421E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16503659.15 | 0.00 | 0.00 | 0.612673E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 115179.85 | 0.00 | 0.125522E+09 | 0.00 | 0.00 | 0.545653E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3092236.72 | 0.00 | 0.00 | 0.223996E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 115179.85 | 0.00 | 18452509.32 | 0.00 | 0.00 | 0.638153E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124952E+09 | 0.00 | 0.00 | 16934137.58 | 0.00 | 0.00 | 0.627182E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 61558621.52 | 0.00 | 0.00 | 0.563720E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.114209E+09 | 0.00 | 0.00 | 0.625440E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.161086E+09 | 0.00 | 0.00 | 0.467620E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 33098680.98 | 0.00 | 0.00 | 0.473460E+10 | 0.00 | 0.29 |
June | 0.00 | 1056446.25 | 0.00 | 78015117.89 | 0.00 | 0.00 | 0.324262E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.116204E+09 | 0.00 | 0.00 | 0.230136E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.173682E+09 | 0.00 | 0.00 | 0.225190E+10 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 32808727.39 | 0.00 | 0.00 | 0.313722E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 69170250.52 | 0.00 | 0.00 | 0.464581E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.102017E+09 | 0.00 | 0.00 | 0.532238E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.141306E+09 | 0.00 | 0.00 | 0.614920E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.124952E+09 | 1056446.25 | 0.00 | 0.110009E+10 | 0.00 | 0.00 | 0.546247E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 16934137.58 | 0.00 | 0.00 | 0.225190E+10 | 0.00 | 0.28 |
Maximum of Months | 0.124952E+09 | 1056446.25 | 0.00 | 0.173682E+09 | 0.00 | 0.00 | 0.627182E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.221281E+09 | 0.00 | 0.00 | 711310.78 | 0.00 | 0.00 | 0.415587E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5110008.72 | 0.00 | 0.00 | 0.564834E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10395376.99 | 0.00 | 0.00 | 0.626491E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15579314.44 | 0.00 | 0.00 | 0.468146E+09 | 0.00 | 0.29 |
May | 2746090.95 | 0.00 | 0.00 | 2864072.35 | 0.00 | 0.00 | 0.471343E+09 | 0.00 | 0.29 |
June | 0.00 | 109665.47 | 0.00 | 7580793.33 | 0.00 | 0.00 | 0.324740E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 11475904.00 | 0.00 | 0.00 | 0.230453E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 17170867.56 | 0.00 | 0.00 | 0.225564E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 2834320.48 | 0.00 | 0.00 | 0.315227E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5973708.60 | 0.00 | 0.00 | 0.466144E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9143116.06 | 0.00 | 0.00 | 0.533549E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13055690.96 | 0.00 | 0.00 | 0.616039E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.224027E+09 | 109665.47 | 0.00 | 0.101894E+09 | 0.00 | 0.00 | 0.525812E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 711310.78 | 0.00 | 0.00 | 0.225564E+09 | 0.00 | 0.28 |
Maximum of Months | 0.221281E+09 | 109665.47 | 0.00 | 17170867.56 | 0.00 | 0.00 | 0.626491E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.504393E+09 | 0.00 | 0.00 | 0.406467E+12 | 0.00 | 8.98 |
February | 0.00 | 0.00 | 0.00 | 0.938587E+09 | 0.00 | 0.00 | 0.632697E+12 | 0.00 | 15.50 |
March | 0.00 | 0.00 | 0.00 | 0.141495E+10 | 0.00 | 0.00 | 0.100948E+13 | 0.00 | 23.81 |
April | 0.00 | 0.00 | 0.00 | 0.222393E+10 | 0.00 | 0.00 | 0.119113E+13 | 0.00 | 35.07 |
May | 0.00 | 0.00 | 0.00 | 0.549966E+09 | 0.00 | 0.00 | 0.375503E+12 | 0.00 | 12.53 |
June | 0.00 | 2302985.66 | 0.00 | 0.109559E+10 | 0.00 | 0.00 | 0.555435E+12 | 0.00 | 26.31 |
July | 0.00 | 18233325.35 | 0.00 | 0.194077E+10 | 0.00 | 0.00 | 0.714953E+12 | 0.00 | 36.98 |
August | 0.00 | 0.00 | 0.00 | 0.265625E+10 | 0.00 | 0.00 | 0.690280E+12 | 0.00 | 41.48 |
September | 0.00 | 0.00 | 0.00 | 0.547725E+09 | 0.00 | 0.00 | 0.342282E+12 | 0.00 | 16.52 |
October | 0.00 | 0.00 | 0.00 | 0.998165E+09 | 0.00 | 0.00 | 0.637803E+12 | 0.00 | 20.30 |
November | 0.00 | 0.00 | 0.00 | 0.147544E+10 | 0.00 | 0.00 | 0.924293E+12 | 0.00 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.211522E+10 | 0.00 | 0.00 | 0.129371E+13 | 0.00 | 28.47 |
Annual Sum or Average | 0.00 | 20536311.01 | 0.00 | 0.164610E+11 | 0.00 | 0.00 | 0.877404E+13 | 0.00 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.504393E+09 | 0.00 | 0.00 | 0.342282E+12 | 0.00 | 8.98 |
Maximum of Months | 0.00 | 18233325.35 | 0.00 | 0.265625E+10 | 0.00 | 0.00 | 0.129371E+13 | 0.00 | 41.48 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:49:12
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.145999E+12 | 0.658851E+10 | 0.00 | 0.229637E+13 | 0.121855E+12 |
February | 0.235747E+12 | 0.937325E+10 | 0.00 | 0.235621E+13 | 0.175822E+12 |
March | 0.283568E+12 | 0.584426E+10 | 0.00 | 0.301470E+13 | 0.264100E+12 |
April | 0.731439E+12 | 0.726030E+10 | 0.00 | 0.345338E+13 | 0.448364E+12 |
May | 0.902242E+12 | 0.171953E+11 | 0.00 | 0.258579E+13 | 0.168809E+12 |
June | 0.905826E+12 | 0.135458E+11 | 0.00 | 0.277790E+13 | 0.447765E+12 |
July | 0.913541E+12 | 0.129217E+11 | 0.00 | 0.293290E+13 | 0.839762E+12 |
August | 0.746516E+12 | 0.956169E+10 | 0.00 | 0.285535E+13 | 0.139633E+13 |
September | 0.552157E+12 | 0.101661E+11 | 0.00 | 0.259231E+13 | 0.361623E+12 |
October | 0.254070E+12 | 0.100430E+11 | 0.00 | 0.271993E+13 | 0.175472E+12 |
November | 0.113697E+12 | 0.122054E+11 | 0.00 | 0.279774E+13 | 0.249550E+12 |
December | 0.552968E+11 | 0.165254E+11 | 0.00 | 0.305432E+13 | 0.365895E+12 |
Annual Sum or Average | 0.584010E+13 | 0.131231E+12 | 0.00 | 0.334369E+14 | 0.501535E+13 |
Minimum of Months | 0.552968E+11 | 0.584426E+10 | 0.00 | 0.229637E+13 | 0.121855E+12 |
Maximum of Months | 0.913541E+12 | 0.171953E+11 | 0.00 | 0.345338E+13 | 0.139633E+13 |